You are on page 1of 240

Low voltage

Canalis KTC
1000 - 5000 A
Busbar trunking systems
Copper

Catalogue
2011

YFJYVIIVGIT

6FKQHLGHU(OHF ULF

)55(9$

Contents

DEBU024EN_Contents.indd

Index
Introduction

3
17

Presentation and description

35

Catalogue numbers
and dimensions

63

Design guide

133

Design and installation guide

171

Recommandations

231

version: 1.1

version: 1.1

DEBU024EN_Contents.indd

Index of catalogue numbers

Index

Cat. no.

Designations

03000
03561

CANALIS SUPPORT

Pages

Cat. no.

Designations

78

87813

DBA 115 CONNECTING BLOCK FOR KT BBT 78


2000/2500A 3P TDC

87814

DBA 115 CONNECTING BLOCK FOR KT BBT 78


2000/2500A 4P TDC

87815

DBA 115 CONNECTING BLOCK FOR KT BBT 78


3200A 3P TDC

87816

DBA 115 CONNECTING BLOCK FOR KT BBT 78


3200A 4P TDC

87817

DBA 115 CONNECTING BLOCK FOR KT BBT 78


4000A 3P TDC

87818

DBA 115 CONNECTING BLOCK FOR KT BBT 78


4000A 4P TDC

87821

DBA 115 CONNECTING BLOCK FOR KT BBT 78


800/1600A 3P RC

87822

DBA 115 CONNECTING BLOCK FOR KT BBT 78


800/1600A 4P RC

87823

DBA 115 CONNECTING BLOCK FOR KT BBT 78


2000/2500A 3P RC

87824

DBA 115 CONNECTING BLOCK FOR KT BBT 78


2000/2500A 4P RC

87825

DBA 115 CONNECTING BLOCK FOR KT BBT 78


3200A 3P RC

87826

DBA 115 CONNECTING BLOCK FOR KT BBT 78


3200A 4P RC

87827

DBA 115 CONNECTING BLOCK FOR KT BBT 78


4000A 3P RC

87828

DBA 115 CONNECTING BLOCK FOR KT BBT 78


4000A 4P RC

77

04000

Pages

04694

CONNECTION SUPPORT, 115 MM BETWEEN 77


CENTRES

04703

CANALIS INTERFACE, 1600 A, 3P

76

04704

CANALIS INTERFACE, 1600 A, 4P

76

04711

CANALIS CONNECTION FOR FRONTCONNECTED NS-NT, 3P

77

04712

CANALIS CONNECTION FOR FRONTCONNECTED NS-NT, 4P

77

04713

CANALIS CONNECTION FOR REARCONNECTED NS-NT, 3P

77

04714

CANALIS CONNECTION FOR REARCONNECTED NS-NT, 4P

77

04715

CANALIS CONNECTION, 1600 A, NW, 3P

76

04716

CANALIS CONNECTION, 1600 A, NW, 4P

76

04725

CANALIS CONNECTION, 2500 A, NW, 3P

76

04726

CANALIS CONNECTION, 2500 A, NW, 4P

76

04735

CANALIS CONNECTION, 3200 A, NW, 3P

76

04736

CANALIS CONNECTION, 3200 A, NW, 4P

76

04737

CANALIS CONNECTION, 4000 A, NW, 3P

76

04738

CANALIS CONNECTION, 4000 A, NW, 4P

76

04851

FRONT CONNECTION COVER FOR


VERTICAL FIXED NS1600

77

04852

FRONT CONNECTION COVER FOR


VERTICAL FIXED NS1600-NT

77

04853

REAR CONNECTION COVER FOR VERTICAL 77


FIXED NS1600

KH010SD85

KH BOX PLUG IN 3L PEN SECT MULLER


100 T00

124

04854

REAR CONNECTION COVER FOR VERTICAL 77


FIXED NS1600-NT

KH016CB

KH0

04861

FRONT CONNECTION COVER FOR NW

77

04863

REAR CONNECTION COVER FOR NW

77

04871

CANALIS COVER

77

12 ADHESIVE LABEL HOLDERS, H=24 MM,


W=432 MM

110

12 ADHESIVE LABEL HOLDERS, H=24 MM,


W=180 MM

110

12 ADHESIVE LABEL HOLDERS, H=24 MM,


W=650 MM

110

08000
08903
08905
08907

13000
13940

BLANKING PLATES, SET OF 10X5 MODULES 110


FORR KAEDRA

30000
33596

ARC-CHUTE COVER, FIXED NS, 3P

77

33597

ARC-CHUTE COVER, FIXED NS, 4P

77

40000
47335

ARC-CHUTE COVER, FIXED NT, 3P

77

47336

ARC-CHUTE COVER, FIXED NT, 4P

77

DBA 115 INSTALLATION KIT FOR KT BBT


800/4000A TDC

79

87801

DBA 115 INSTALLATION KIT FOR KT BBT


800/3200A RC

79

87811

DBA 115 CONNECTING BLOCK FOR KT BBT 78


800/1600A 3P TDC

87812

DBA 115 CONNECTING BLOCK FOR KT BBT 78


800/1600A 4P TDC

80000
87800

DEBU024EN_Index.indd

CONNECTING LINKS SHIELD

127

KH016CB311571 CONNECTING LINKS SHIELD

127

KH018CB

CONNECTING LINKS SHIELD

127

KH018CB311571 CONNECTING LINKS SHIELD

127

KH018CB86NS

CONNECTING LINKS TAP OFF BOX SB


NS1000

128

KH025SB131

KH FIXED BOX 3L PE FUS 250 T2 N1

127

KH025SB132

KH FIXED BOX 3L PE FUS 250 T2 N2

127

KH025SB141

KH FIXED BOX 3L N PE FUS 250 T2 N1

127

KH025SB142

KH FIXED BOX 3L N PE FUS 250 T2 N2

127

KH025SD14

KH BOX PLUG IN 3L N PE FUSES 250 T2

123

KH025SD15

KH BOX PLUG IN 3L PEN FUSES 250 T2

123

KH025SD541

KH BOX PLUG IN 3L N PE NSX250

122

KH025SD542

KH BOX PLUG IN 3L N PE NSX250

122

KH025SD551

KH BOX PLUG IN 3L PEN NSX250

122

KH025SD552

KH BOX PLUG IN 3L PEN NSX250

122

KH025SD85

KH BOX PLUG IN 3L PEN SECT MULLER


250 T1

124

KH025SE341

KH BOX PLUG IN 3L N PE INTER FUSES


250 T1

126

KH025SE351

KH BOX PLUG IN 3L PEN INTER FUSES 250


T1

126

KH025ZA05

CABLE BOX 1 HOLE FOR KH025SE

126

KH026CB

CONNECTING LINKS SHIELD

127

KH026CB311571 CONNECTING LINKS SHIELD

127

KH028CB86NS

CONNECTING LINKS TAP OFF BOX SB


NS1000

128

KH036CB

CONNECTING LINKS SHIELD

127

KH036CB311571 CONNECTING LINKS SHIELD

127

KH038CB86NS

CONNECTING LINKS TAP OFF BOX SB


NS1000

128

KH040SD85

KH BOX PLUG IN 3L PEN SECT MULLER


400 T2

124

KH040SD9502

KH BOX PLUG IN 3L PEN SECT PEHLA 400


T2

125

KH040SE341

KH BOX PLUG IN 3L N PE INTER FUSES


400 T2

126

version: 1.1

Index of catalogue numbers

Index

Cat. no.

Designations

Pages

Cat. no.

Designations

Pages

KH040SE351

KH BOX PLUG IN 3L PEN INTER FUSES 400


T2

126

KSB160SE4

TAP-OFF UNIT 160 A FUSE T00

106, 108

KSB160SE5

TAP-OFF UNIT 160 A FUSE T00

106, 108

KH040ZA05

CABLE BOX 1 HOLE FOR KH040SE

126

KSB160SF4

TAP-OFF UNIT 160 A FUSE T0

106

KH040ZA06

CABLE BOX 2 HOLES FOR KH040SE

126

KSB160SF5

TAP-OFF UNIT 160 A FUSE T0

106

KH046CB

CONNECTING LINKS SHIELD

127

KSB160SG4

TAP-OFF UNIT 160 A FUSE BS88

109

KH046CB311571 CONNECTING LINKS SHIELD

127

KSB160SM413

TAP-OFF UNIT NG 160 A

102

KH048CB86NS

CONNECTING LINKS TAP OFF BOX SB


NS1000

128

KSB160SM513

TAP-OFF UNIT NG 160 A

102

CONNECTING LINKS SHIELD

127

KSB250DC4

TAP-OFF UNIT 250 A COMPACT NS

103

KH056CB

KH056CB311571 CANAL ELEC EQUIP ECLIS COF 1000A

127

KH058CB86NS

CONNECTING LINKS TAP OFF BOX SB


NS1000

128

KH063SB131

KH FIXED BOX 3L PE FUS 630 T3 N1

KH063SB132
KH063SB141

KSB250DC4TRE TAP-OFF UNIT 250 A COMPACT NS TRE

104

KSB250DC5

103

TAP-OFF UNIT 250 A COMPACT NS

KSB250DC5TRE TAP-OFF UNIT 250 A COMPACT NS TRE

104

127

KSB250SE4

TAP-OFF UNIT 250 A FUSE T1

106, 108

KH FIXED BOX 3L PE FUS 630 T3 N2

127

KSB250SE5

TAP-OFF UNIT 250 A FUSE T1

106, 108

KH FIXED BOX 3L N PE FUS 630 T3 N1

127

KSB400DC4

TAP-OFF UNIT 400 A COMPACT NS

103
104
103

KH063SB142

KH FIXED BOX 3L N PE FUS 630 T3 N2

127

KSB400DC4TRE TAP-OFF UNIT 400 A COMPACT NS TRE

KH063SD14

KH BOX PLUG IN 3L N PE FUSES 630 T3

123

KSB400DC5

KH063SD15

KH BOX PLUG IN 3L PEN FUSES 630 T3

123

KSB400DC5TRE TAP-OFF UNIT 400 A COMPACT NS TRE

103

TAP-OFF UNIT 400 A FUSE T2

106, 108
106, 108

TAP-OFF UNIT 400 A COMPACT NS

KH063SD541

KH BOX PLUG IN 3L N PE NSX630

122

KSB400SE4

KH063SD541

KH BOX PLUG IN 3L N PE NSX630

122

KSB400SE5

TAP-OFF UNIT 400 A FUSE T2

KH063SD551

KH BOX PLUG IN 3L PEN NSX630

122

KSB400ZC1

TAP-OFF UNIT DOOR MICROSWITCH 400 A 110

KH063SD552

KH BOX PLUG IN 3L PEN NSX630

122

KH063SD85

KH BOX PLUG IN 3L PEN SECT MULLER


630 T3

124

KH063SD9502

KH BOX PLUG IN 3L PEN SECT PEHLA 630


T3

125

KH063SE341

KH BOX PLUG IN 3L N PE INTER FUSES


630 T3

126

KH063SE351

KH BOX PLUG IN 3L PEN INTER FUSES 630


T3

126

EXTENDED REMOTE HANDLE FOR TOU


FUPACT KH0XXSE3X1

126

KH063ZA05

CABLE BOX 1 HOLE FOR KH063SE

KH063ZA06

KTB
KTB0000CR4

KT VERT COVER FEED EL N1 TO 4

92

KTB0000CR5

KT HORI COVER FEED EL N1 TO 4

92

KTB0000YB1

KT BOLT SNAP-OF HEAD

96

KTB0000YB2

KT SCREWS M12X60 NUTS & PLATES

96

KTB0000YB3

KT SCREWS M12X60 & TORQUE NUTS

96

KTB0000YB4

KT SCREWS M12X80 & TORQUE NUTS

96

KTB0000YC1

KT FLEXIBLE LINK L600 4

94

KTB0000YC2

KT FLEXIBLE LINK L250A600 8

94

126

KTB0000YC3

KT WAVY FLEXIBLE LINK L400 4

94

CABLE BOX 2 HOLES FOR KH063SE

126

KTB0000YC4

KT WAVY FLEXIBLE LINK L400 8

94

KH063ZA10

CABLE GLAND 185 A 240 MM2

126

KTB0000YC5

KT INSULATED FLEX LINK L1000 4

94

KH086SB131

KH FIXED BOX 3L PE FUS T4 1000 N1

127

KTB0000YE1

KT L PLATE 160

91

KH086SB132

KH FIXED BOX 3L PE FUS T4 1000 N2

127

KTB0000YE2

KT L PLATE 200

91

KH086SB141

KH FIXED BOX 3L N PE FUS 1000 T4 N1

127

KTB0000YF1

KT INSULATING SHEATH

95

KH086SB142

KH FIXED BOX 3L N PE FUS 1000 T4 N2

127

KTB0000YS1

KT SUPPORT FOR BARS DBA115

97

KH086SB5311

KH FIXED BOX 3L PE NS1000 N1

128

KTB0000YS2

KT CLAMP 100

97

KH086SB5312

KH FIXED BOX 3L PE NS1000 N2

128

KTB0000YS3

KT CLAMP 120

97

KH086SB5411

KH FIXED BOX 3L N PE NS1000 T4 N1

128

KTB0000YT1

KT BRAID 600MM2 L400 8

95

KH086SB5412

KH FIXED BOX 3L N PE NS1000 T4 N2

128

KTB0000ZA1

KT HORI FIXING BRACKED

98

KTB0000ZA3

KT FIXING GRIP

98

KTB074CF6

KT FIRE BARRIER KIT H74 L650

100

KH063ZA03

KSB
KSB25SD4

TAP-OFF UNIT 25 A FUSE E27

107

KTB0074FA

KT END COVER H74

70

KSB25SD5

TAP-OFF UNIT 25 A FUSE E27

107

KTB0074TT01

KT KT ROOF PLATE H74

79

KSB32SG4

CONNECTOR 32 A FUSE BS88A1

109

KTB0074ZA4

KT HORI TOP BRACKED H74

98

KSB50SF4

TAP-OFF UNIT 50 A FUSE 14X51

105

KTB0104CF6

KT FIRE BARRIER KIT H104 L650

100

KSB50SF5

TAP-OFF UNIT 50 A FUSE 14X51

105

KTB0104FA

KT END COVER H104

70

KSB50SN4

TAP-OFF UNIT 50 A FUSE E18

107

KTB0104TT01

KT KT ROOF PLATE H104

79

KSB50SN5

TAP-OFF UNIT 50 A FUSE E18

107

KTB0124CF6

KT FIRE BARRIER KIT H124 L650

100

KSB63SD4

TAP-OFF UNIT 63 A FUSE E33

107

KTB0124FA

KT END COVER H124

70

KSB63SD5

TAP-OFF UNIT 63 A FUSE E33

107

KTB0124TT01

KT KT ROOF PLATE H124

79

KSB63SM48

TAP-OFF UNIT 63 A 8 MODULES

101

KTB0164CF6

KT FIRE BARRIER KIT H164 L650

100

KSB63SM58

TAP-OFF UNIT 63 A 8 MODULES

101

KTB0164FA

KT END COVER H164

70

KSB80SG4

TAP-OFF UNIT 80 A FUSE BS88A1

109

KTB0164PE1

KT END COVER H164

76, 78, 79

KSB100SE4

TAP-OFF UNIT 100 A FUSE T00

106, 108

KTB0164TT01

KT KT ROOF PLATE H164

79

KSB100SE5

TAP-OFF UNIT 100 A FUSE T00

106, 108

KTB0164ZA5

KT VERT FIXING BRACKED H74A164

99

KSB100SF4

TAP-OFF UNIT 100 A FUSE 22X58

105

KTB0204CF6

KT FIRE BARRIER KIT H204 L650

100

KSB100SF5

TAP-OFF UNIT 100 A FUSE 22X58

105

KTB0204FA

KT END COVER H204

70

KSB100SM412

TAP-OFF UNIT 100 A 12 MODULES

101

KTB0204TT01

KT KT ROOF PLATE H204

79

KSB100SM512

TAP-OFF UNIT 100 A 12 MODULES

101

KTB0204ZA5

KT VERT FIXING BRACKED H204

99

KSB160DC4

TAP-OFF UNIT 160 A COMPACT NS

103

KTB0230BC01

KT CABLES BOX Y230

87

KSB160DC5

TAP-OFF UNIT 160 A COMPACT NS

103

KTB0230CR1

KT HORI COVER FEED ER Y230

84

version: 1.1

DEBU024EN_Index.indd

Cat. no.

Designations

Pages

Cat. no.

Designations

Pages

KTB0230CR2

KT HIGH VERT COVER FEED Y230

85

KTC1000CP41

KT 4X1000CO FLAT EDGEWISE N1

75

KTB0230CR3

KT LOW VERT COVER FEED Y230

85

KTC1000CP42

KT 4X1000CO FLAT EDGEWISE N2

75

KTB0230CR6

KT HORI COVER FEED EL N5 Y230

93

KTC1000CP43

KT 4X1000CO FLAT EDGEWISE N3

75

KTB0230CR7

KT HORI COVER FOR OIL TR Y230

86

KTC1000CP44

KT 4X1000CO FLAT EDGEWISE N4

75

KTB0230CR8

KT VERT COVER FOR OIL TR Y230

86

KTC1000CP51

KT 5X1000CO FLAT EDGEWISE N1

75

KTB0230CS0

KT FLEXIBLE COVER Y230 E115

87

KTC1000CP52

KT 5X1000CO FLAT EDGEWISE N2

75

KTB0244CF6

KT FIRE BARRIER KIT H244 L650

100

KTC1000CP53

KT 5X1000CO FLAT EDGEWISE N3

75

KTB0244FA

KT END COVER H244

70

KTC1000CP54

KT 5X1000CO FLAT EDGEWISE N4

75

KTB0244PE1

KT END COVER H244

76, 78, 79

KTC1000CP71

KT 5X1000CO FLAT EDGEWISE N1

75

KTB0244TT01

KT KT ROOF PLATE H244

79

KTC1000CP72

KT 5X1000CO FLAT EDGEWISE N2

75

KTB0244ZA5

KT VERT FIXING BRACKED H244

99

KTC1000CP73

KT 5X1000CO FLAT EDGEWISE N3

75

KTB0324CF6

KT FIRE BARRIER KIT H324 L650

100

KTC1000CP74

KT 5X1000CO FLAT EDGEWISE N4

75

KTB0324FA

KT END COVER H324

70

KTC1000DB310 KT 3X1000CO EXPANSION UNIT

69

KTB0324TT01

KT KT ROOF PLATE H324

79

KTC1000DB410 KT 4X1000CO EXPANSION UNIT

69

KTB0324ZA5

KT VERT FIXING BRACKED H324

99

KTC1000DB510 KT 5X1000CO EXPANSION UNIT

69

KTB0350BC01

KT CABLES BOX Y350

87

KTC1000DB710 KT 5X1000CO EXPANSION UNIT

69

KTB0350CR1

KT HORI COVER FEED ER Y350

84

KTC1000EB320 KT 3X1000CO BOLT ON LENGTH 2M

67

KTB0350CR2

KT HIGH VERT COVER FEED Y350

85

KTC1000EB340 KT 3X1000CO BOLT ON LENGTH 4M

67

KTB0350CR3

KT LOW VERT COVER FEED Y350

85

KTC1000EB420 KT 4X1000CO BOLT ON LENGTH 2M

67

KTB0350CR6

KT HORI COVER FEED EL N5 Y350

93

KTC1000EB440 KT 4X1000CO BOLT ON LENGTH 4M

67

KTB0350CR7

KT HORI COVER FOR OIL TR Y350

86

KTC1000EB520 KT 5X1000CO BOLT ON LENGTH 2M

67

KTB0350CR8

KT VERT COVER FOR OIL TR Y350

86

KTC1000EB540 KT 5X1000CO BOLT ON LENGTH 4M

67

KTB0350CS0

KT FLEXIBLE COVER Y350 E115

87

KTC1000EB720 KT 5X1000CO BOLT ON LENGTH 2M

67

KTB0350HT01

KT CONNECTION KHF KGF Y350 N1

118

KTC1000EB740 KT 5X1000CO BOLT ON LENGTH 4M

67

KTB0350HT02

KT CONNECTION KHF KGF Y350 N2

118

KTC1000ED320 KT 3X1000CO PLUG-IN LENGTH 2M

66

KTB0404CF6

KT FIRE BARRIER KIT H404 L650

100

KTC1000ED340 KT 3X1000CO PLUG-IN LENGTH 4M

66

KTB0404FA

KT END COVER H404

70

KTC1000ED420 KT 4X1000CO PLUG-IN LENGTH 2M

66

KTB0404PE1

KT END COVER H404

76, 78, 79

KTC1000ED440 KT 4X1000CO PLUG-IN LENGTH 4M

66

KTB0404TT01

KT KT ROOF PLATE H404

79

KTC1000ED520 KT 5X1000CO PLUG-IN LENGTH 2M

66

KTB0404ZA4

KT HORI TOP BRACKED H104 A 404

98

KTC1000ED540 KT 5X1000CO PLUG-IN LENGTH 4M

66

KTB0404ZA5

KT VERT FIXING BRACKED H404

99

KTC1000ED720 KT 5X1000CO PLUG-IN LENGTH 2M

66

KTB0510BC01

KT CABLES BOX Y510

87

KTC1000ED740 KT 5X1000CO PLUG-IN LENGTH 4M

66

KTB0510CR1

KT HORI COVER FEED ER Y510

84

KTC1000EH320 KT 3X1000CO KH PLUG-IN LENGTH 2M

68

KTB0510CR2

KT HIGH VERT COVER FEED Y510

85

KTC1000EH340 KT 3X1000CO KH PLUG-IN LENGTH 4M

68

KTB0510CR3

KT LOW VERT COVER FEED Y510

85

KTC1000EH420 KT 4X1000CO KH PLUG-IN LENGTH 2M

68

KTB0510CR6

KT HORI COVER FEED EL N5 Y510

93

KTC1000EH440 KT 4X1000CO KH PLUG-IN LENGTH 4M

68

KTB0510CR7

KT HORI COVER FOR OIL TR Y510

86

KTC1000EH520 KT 5X1000CO KH PLUG-IN LENGTH 2M

68

KTB0510CR8

KT VERT COVER FOR OIL TR Y510

86

KTC1000EH540 KT 5X1000CO KH PLUG-IN LENGTH 4M

68

KTB0510CS0

KT FLEXIBLE COVER Y510 E115

87

KTC1000EL31

KT 3X1000CO FEED UNIT EL N1

88

KTB0510HT01

KT CONNECTION KHF KGF Y510 N1

118

KTC1000EL32

KT 3X1000CO FEED UNIT EL N2

88

KTB0510HT02

KT CONNECTION KHF KGF Y510 N2

118

KTC1000EL33

KT 3X1000CO FEED UNIT EL N3

89

KTB0510HT03

KT CONNECTION KHF KGF Y510 N3

118

KTC1000EL34

KT 3X1000CO FEED UNIT EL N4

89

KTB0630CB3

KT FIXED TAP-OFF 3L PE NS630

111

KTC1000EL35

KT 3X1000CO FEED UNIT EL N5

90

KTB0630CB4

KT FIXED TAP-OFF 3L N PE NS630

111

KTC1000EL41

KT 4X1000CO FEED UNIT EL N1

88

KTB0630CB5

KT FIXED TAP-OFF 3L PEN NS630

111

KTC1000EL42

KT 4X1000CO FEED UNIT EL N2

88

KTB0630HF3

KT COFF 3L PE FUS SWITCH 630

112

KTC1000EL43

KT 4X1000CO FEED UNIT EL N3

89

KTB0630HF4

KT COFF 3L N PE FUS SWITCH 630

112

KTC1000EL44

KT 4X1000CO FEED UNIT EL N4

89

KTB0630HF5

KT COFF 3L PEN FUS SWITCH 630

112

KTC1000EL45

KT 4X1000CO FEED UNIT EL N5

90

KTB1000CB3

KT FIXED TAP-OFF 3L PE NS1000

111

KTC1000EL51

KT 5X1000CO FEED UNIT EL N1

88

KTB1000CB4

KT FIXED TAP-OFF 3L N PE NS1000

111

KTC1000EL52

KT 5X1000CO FEED UNIT EL N2

88

KTB1000CB5

KT FIXED TAP-OFF 3L PEN NS1000

111

KTC1000EL53

KT 5X1000CO FEED UNIT EL N3

89

KTB1000HF3

KT COFF 3L PE FUS SWITCH 1000

112

KTC1000EL54

KT 5X1000CO FEED UNIT EL N4

89

KTB1000HF4

KT COFF 3L N PE FUS SWITCH 1000

112

KTC1000EL55

KT 5X1000CO FEED UNIT EL N5

90

KTB1000HF5

KT COFF 3L PEN FUS SWITCH 1000

112

KTC1000EL71

KT 5X1000CO FEED UNIT EL N1

88

KTB1250CB3

KT COFF BOULO 3L PEN NS1000

111

KTC1000EL72

KT 5X1000CO FEED UNIT EL N2

88

KTB1250CB4

KT COFF BOULO 3L PEN NS1000

111

KTC1000EL73

KT 5X1000CO FEED UNIT EL N3

89

KTB1250CB5

KT COFF BOULO 3L PEN NS1000

111

KTC1000EL74

KT 5X1000CO FEED UNIT EL N4

89

KTC1000EL75

KT 5X1000CO FEED UNIT EL N5

90

KTC1000

KTC1000ER31

KT 3X1000CO FEED UNIT ER N1

80

KTC1000CP31

KT 3X1000CO FLAT EDGEWISE N1

75

KTC1000ER32

KT 3X1000CO FEED UNIT ER N2

80

KTC1000CP32

KT 3X1000CO FLAT EDGEWISE N2

75

KTC1000ER33

KT 3X1000CO FEED UNIT ER N3

81

KTC1000CP33

KT 3X1000CO FLAT EDGEWISE N3

75

KTC1000ER34

KT 3X1000CO FEED UNIT ER N4

81

75

KTC1000ER35

KT 3X1000CO FEED UNIT ER N5

82

KTC1000CP34

KT 3X1000CO FLAT EDGEWISE N4

DEBU024EN_Index.indd

version: 1.1

Index of catalogue numbers

Index

Cat. no.

Designations

Pages

Cat. no.

KTC1000ER36

KT 3X1000CO FEED UNIT ER N6

82

KTC1000LP4A2 KT 4X1000CO FLAT ELBOW N2

71

KTC1000ER37

KT 3X1000CO FEED UNIT ER N7

83

KTC1000LP4B1 KT 4X1000CO FLAT ELBOW N1

71

KTC1000ER41

KT 4X1000CO FEED UNIT ER N1

80

KTC1000LP4B2 KT 4X1000CO FLAT ELBOW N2

71

KTC1000ER42

KT 4X1000CO FEED UNIT ER N2

80

KTC1000LP4C1 KT 4X1000CO FLAT ELBOW N1

71

KTC1000ER43

KT 4X1000CO FEED UNIT ER N3

81

KTC1000LP4C2 KT 4X1000CO FLAT ELBOW N2

71

KTC1000ER44

KT 4X1000CO FEED UNIT ER N4

81

KTC1000LP5A1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER45

KT 4X1000CO FEED UNIT ER N5

82

KTC1000LP5A2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER46

KT 4X1000CO FEED UNIT ER N6

82

KTC1000LP5B1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER47

KT 4X1000CO FEED UNIT ER N7

83

KTC1000LP5B2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER51

KT 5X1000CO FEED UNIT ER N1

80

KTC1000LP5C1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER52

KT 5X1000CO FEED UNIT ER N2

80

KTC1000LP5C2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER53

KT 5X1000CO FEED UNIT ER N3

81

KTC1000LP7A1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER54

KT 5X1000CO FEED UNIT ER N4

81

KTC1000LP7A2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER55

KT 5X1000CO FEED UNIT ER N5

82

KTC1000LP7B1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER56

KT 5X1000CO FEED UNIT ER N6

82

KTC1000LP7B2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER57

KT 5X1000CO FEED UNIT ER N7

83

KTC1000LP7C1 KT 5X1000CO FLAT ELBOW N1

71

KTC1000ER71

KT 5X1000CO FEED UNIT ER N1

80

KTC1000LP7C2 KT 5X1000CO FLAT ELBOW N2

71

KTC1000ER72

KT 5X1000CO FEED UNIT ER N2

80

KTC1000PL31

KT 3X1000CO LINE PROTECTOR NS

115

KTC1000ER73

KT 5X1000CO FEED UNIT ER N3

81

KTC1000PL41

KT 4X1000CO LINE PROTECTOR NS

115

KTC1000ER74

KT 5X1000CO FEED UNIT ER N4

81

KTC1000PL51

KT 5X1000CO LINE PROTECTOR NS

115

KTC1000ER75

KT 5X1000CO FEED UNIT ER N5

82

KTC1000PL71

KT 5X1000CO LINE PROTECTOR NS

115

KTC1000ER76

KT 5X1000CO FEED UNIT ER N6

82

KTC1000SL31

KT 3X1000CO ISOLATOR UNIT NA

113

KTC1000ER77

KT 5X1000CO FEED UNIT ER N7

83

KTC1000SL41

KT 4X1000CO ISOLATOR UNIT NA

113

KTC1000ET31A KT 3X1000CO FEEDER LENGTH

66

KTC1000SL51

KT 5X1000CO ISOLATOR UNIT NA

113

KTC1000ET320

66

KTC1000SL71

KT 5X1000CO ISOLATOR UNIT NA

113

KTC1000ET32B KT 3X1000CO FEEDER LENGTH

66

KTC1000TC3

KT 3X1000CO TEE ON EDGE

73

KTC1000ET32C KT 3X1000CO FEEDER LENGTH

66

KTC1000TC4

KT 4X1000CO TEE ON EDGE

73

KTC1000ET33D KT 3X1000CO FEEDER LENGTH

66

KTC1000TC5

KT 5X1000CO TEE ON EDGE

73

KTC1000ET340

66

KTC1000TC7

KT 5X1000CO TEE ON EDGE

73

KTC1000ET41A KT 4X1000CO FEEDER LENGTH

66

KTC1000TN410

KT 4X1000CO NEUTRAL PERMUTA

69

KTC1000ET420

66

KTC1000TP410

KT 4X1000CO PHASES PERMUTA

69

KTC1000ET42B KT 4X1000CO FEEDER LENGTH

66

KTC1000YA3

KT 3X1000CO JUNCTION BLOC

70

KTC1000ET42C KT 4X1000CO FEEDER LENGTH

66

KTC1000YA4

KT 4X1000CO JUNCTION BLOC

70

KTC1000ET43D KT 4X1000CO FEEDER LENGTH

66

KTC1000ZC31

KT 3X1000CO EDGEWISE ZED N1

74

KTC1000ET440

66

KTC1000ZC32

KT 3X1000CO EDGEWISE ZED N2

74

KTC1000ET51A KT 5X1000CO FEEDER LENGTH

66

KTC1000ZC41

KT 4X1000CO EDGEWISE ZED N1

74

KTC1000ET520

66

KTC1000ZC42

KT 4X1000CO EDGEWISE ZED N2

74

KTC1000ET52B KT 5X1000CO FEEDER LENGTH

66

KTC1000ZC51

KT 5X1000CO EDGEWISE ZED N1

74

KTC1000ET52C KT 5X1000CO FEEDER LENGTH

66

KTC1000ZC52

KT 5X1000CO EDGEWISE ZED N2

74

KTC1000ET53D KT 5X1000CO FEEDER LENGTH

66

KTC1000ZC71

KT 5X1000CO EDGEWISE ZED N1

74

KTC1000ET540

66

KTC1000ZC72

KT 5X1000CO EDGEWISE ZED N2

74

KTC1000ET71A KT 5X1000CO FEEDER LENGTH

66

KTC1000ZP3

KT 3X1000CO ZED ON FLAT

74

KTC1000ET720

66

KTC1000ZP4

KT 4X1000CO ZED ON FLAT

74

KTC1000ET72B KT 5X1000CO FEEDER LENGTH

66

KTC1000ZP5

KT 5X1000CO ZED ON FLAT

74

KTC1000ET72C KT 5X1000CO FEEDER LENGTH

66

KTC1000ZP7

KT 5X1000CO ZED ON FLAT

74

KTC1000ET73D KT 5X1000CO FEEDER LENGTH

66

KTC1000ET740

KT 5X1000CO FEEDER LENGTH 4M

66

KTC1350

KTC1000LC3A

KT 3X1000CO EDGEWISE ELBOW

72

KTC1350CP31

KT 3X1350CO FLAT EDGEWISE N1

75

KTC1000LC3B

KT 3X1000CO EDGEWISE ELBOW

72

KTC1350CP32

KT 3X1350CO FLAT EDGEWISE N2

75

KTC1000LC4A

KT 4X1000CO EDGEWISE ELBOW

72

KTC1350CP33

KT 3X1350CO FLAT EDGEWISE N3

75

KTC1000LC4B

KT 4X1000CO EDGEWISE ELBOW

72

KTC1350CP34

KT 3X1350CO FLAT EDGEWISE N4

75

KTC1000LC5A

KT 5X1000CO EDGEWISE ELBOW

72

KTC1350CP41

KT 4X1350CO FLAT EDGEWISE N1

75

KTC1000LC5B

KT 5X1000CO EDGEWISE ELBOW

72

KTC1350CP42

KT 4X1350CO FLAT EDGEWISE N2

75

KTC1000LC7A

KT 5X1000CO EDGEWISE ELBOW

72

KTC1350CP43

KT 4X1350CO FLAT EDGEWISE N3

75

KTC1000LC7B

KT 5X1000CO EDGEWISE ELBOW

72

KTC1350CP44

KT 4X1350CO FLAT EDGEWISE N4

75

KTC1000LP3A1 KT 3X1000CO FLAT ELBOW N1

71

KTC1350CP51

KT 5X1350CO FLAT EDGEWISE N1

75

KTC1000LP3A2 KT 3X1000CO FLAT ELBOW N2

71

KTC1350CP52

KT 5X1350CO FLAT EDGEWISE N2

75

KTC1000LP3B1 KT 3X1000CO FLAT ELBOW N1

71

KTC1350CP53

KT 5X1350CO FLAT EDGEWISE N3

75

KTC1000LP3B2 KT 3X1000CO FLAT ELBOW N2

71

KTC1350CP54

KT 5X1350CO FLAT EDGEWISE N4

75

KTC1000LP3C1 KT 3X1000CO FLAT ELBOW N1

71

KTC1350CP71

KT 5X1350CO FLAT EDGEWISE N1

75

KTC1000LP3C1 KT 3X1000CO FLAT ELBOW N1

71

KTC1350CP72

KT 5X1350CO FLAT EDGEWISE N2

75

KTC1000LP3C2 KT 3X1000CO FLAT ELBOW N2

71

KTC1350CP73

KT 5X1350CO FLAT EDGEWISE N3

75

KTC1000LP4A1 KT 4X1000CO FLAT ELBOW N1

71

KTC1350CP74

KT 5X1350CO FLAT EDGEWISE N4

75

KT 3X1000CO FEEDER LENGTH 2M

KT 3X1000CO FEEDER LENGTH 4M


KT 4X1000CO FEEDER LENGTH 2M

KT 4X1000CO FEEDER LENGTH 4M


KT 5X1000CO FEEDER LENGTH 2M

KT 5X1000CO FEEDER LENGTH 4M


KT 5X1000CO FEEDER LENGTH 2M

Designations

version: 1.1

Pages

DEBU024EN_Index.indd

Cat. no.

Pages

Cat. no.

Designations

Pages

KTC1350DB310 KT 3X1350CO EXPANSION UNIT

Designations

69

KTC1350ER54

KT 5X1350CO FEED UNIT ER N4

81

KTC1350DB410 KT 4X1350CO EXPANSION UNIT

69

KTC1350ER55

KT 5X1350CO FEED UNIT ER N5

82

KTC1350DB510 KT 5X1350CO EXPANSION UNIT

69

KTC1350ER56

KT 5X1350CO FEED UNIT ER N6

82

KTC1350DB710 KT 5X1350CO EXPANSION UNIT

69

KTC1350ER57

KT 5X1350CO FEED UNIT ER N7

83

KTC1350EB320 KT 3X1350CO BOLT ON LENGTH 2M

67

KTC1350ER71

KT 5X1350CO FEED UNIT ER N1

80

KTC1350EB340 KT 3X1350CO BOLT ON LENGTH 4M

67

KTC1350ER72

KT 5X1350CO FEED UNIT ER N2

80

KTC1350EB420 KT 4X1350CO BOLT ON LENGTH 2M

67

KTC1350ER73

KT 5X1350CO FEED UNIT ER N3

81

KTC1350EB440 KT 4X1350CO BOLT ON LENGTH 4M

67

KTC1350ER74

KT 5X1350CO FEED UNIT ER N4

81

KTC1350EB520 KT 5X1350CO BOLT ON LENGTH 2M

67

KTC1350ER75

KT 5X1350CO FEED UNIT ER N5

82

KTC1350EB540 KT 5X1350CO BOLT ON LENGTH 4M

67

KTC1350ER76

KT 5X1350CO FEED UNIT ER N6

82

KTC1350EB720 KT 5X1350CO BOLT ON LENGTH 2M

67

KTC1350ER77

KT 5X1350CO FEED UNIT ER N7

83

KTC1350EB740 KT 5X1350CO BOLT ON LENGTH 4M

67

KTC1350ET31A KT 3X1350CO FEEDER LENGTH

66

KTC1350ED320 KT 3X1350CO PLUG-IN LENGTH 2M

66

KTC1350ET320

66

KTC1350ED340 KT 3X1350CO PLUG-IN LENGTH 4M

66

KTC1350ET32B KT 3X1350CO FEEDER LENGTH

66

KTC1350ED420 KT 4X1350CO PLUG-IN LENGTH 2M

66

KTC1350ET32C KT 3X1350CO FEEDER LENGTH

66

KTC1350ED440 KT 4X1350CO PLUG-IN LENGTH 4M

66

KTC1350ET33D KT 3X1350CO FEEDER LENGTH

66

KTC1350ED520 KT 5X1350CO PLUG-IN LENGTH 2M

66

KTC1350ET340

66

KTC1350ED540 KT 5X1350CO PLUG-IN LENGTH 4M

66

KTC1350ET41A KT 4X1350CO FEEDER LENGTH

66

KTC1350ED720 KT 5X1350CO PLUG-IN LENGTH 2M

66

KTC1350ET420

66

KTC1350ED740 KT 5X1350CO PLUG-IN LENGTH 4M

66

KTC1350ET42B KT 4X1350CO FEEDER LENGTH

66

KTC1350EH320 KT 3X1350CO KH PLUG-IN LENGTH 2M

68

KTC1350ET42C KT 4X1350CO FEEDER LENGTH

66

KTC1350EH340 KT 3X1350CO KH PLUG-IN LENGTH 4M

68

KTC1350ET43D KT 4X1350CO FEEDER LENGTH

66

KTC1350EH420 KT 4X1350CO KH PLUG-IN LENGTH 2M

68

KTC1350ET440

66

KTC1350EH440 KT 4X1350CO KH PLUG-IN LENGTH 4M

68

KTC1350ET51A KT 5X1350CO FEEDER LENGTH

66

KTC1350EH520 KT 5X1350CO KH PLUG-IN LENGTH 2M

68

KTC1350ET520

66

KTC1350EH540 KT 5X1350CO KH PLUG-IN LENGTH 4M

68

KTC1350ET52B KT 5X1350CO FEEDER LENGTH

66

KTC1350EL31

KT 3X1350CO FEED UNIT EL N1

88

KTC1350ET52C KT 5X1350CO FEEDER LENGTH

66

KTC1350EL32

KT 3X1350CO FEED UNIT EL N2

88

KTC1350ET53D KT 5X1350CO FEEDER LENGTH

66
66

KT 3X1350CO FEEDER LENGTH 2M

KT 3X1350CO FEEDER LENGTH 4M


KT 4X1350CO FEEDER LENGTH 2M

KT 4X1350CO FEEDER LENGTH 4M


KT 5X1350CO FEEDER LENGTH 2M

KTC1350EL33

KT 3X1350CO FEED UNIT EL N3

89

KTC1350ET540

KT 5X1350CO FEEDER LENGTH 4M

KTC1350EL34

KT 3X1350CO FEED UNIT EL N4

89

KTC1350ET71A KT 5X1350CO FEEDER LENGTH

66

KTC1350EL35

KT 3X1350CO FEED UNIT EL N5

90

KTC1350ET720

66
66

KT 5X1350CO FEEDER LENGTH 2M

KTC1350EL41

KT 4X1350CO FEED UNIT EL N1

88

KTC1350ET72B KT 5X1350CO FEEDER LENGTH

KTC1350EL42

KT 4X1350CO FEED UNIT EL N2

88

KTC1350ET72C KT 5X1350CO FEEDER LENGTH

66

KTC1350EL43

KT 4X1350CO FEED UNIT EL N3

89

KTC1350ET73D KT 5X1350CO FEEDER LENGTH

66

KT 5X1350CO FEEDER LENGTH 4M

66

KTC1350EL44

KT 4X1350CO FEED UNIT EL N4

89

KTC1350ET740

KTC1350EL45

KT 4X1350CO FEED UNIT EL N5

90

KTC1350LC3A

KT 3X1350CO EDGEWISE ELBOW

72

KTC1350EL51

KT 5X1350CO FEED UNIT EL N1

88

KTC1350LC3B

KT 3X1350CO EDGEWISE ELBOW

72

KT 5X1350CO EDGEWISE ELBOW

72

KTC1350EL52

KT 5X1350CO FEED UNIT EL N2

88

KTC1350LC4A

KTC1350EL53

KT 5X1350CO FEED UNIT EL N3

89

KTC1350LC4B

KT 4X1350CO EDGEWISE ELBOW

72

KTC1350EL54

KT 5X1350CO FEED UNIT EL N4

89

KTC1350LC5A

KT 5X1350CO EDGEWISE ELBOW

72

KT 5X1350CO EDGEWISE ELBOW

72

KTC1350EL55

KT 5X1350CO FEED UNIT EL N5

90

KTC1350LC5B

KTC1350EL71

KT 5X1350CO FEED UNIT EL N1

88

KTC1350LC7A

KT 5X1350CO EDGEWISE ELBOW

72

KTC1350EL72

KT 5X1350CO FEED UNIT EL N2

88

KTC1350LC7B

KT 5X1350CO EDGEWISE ELBOW

72

89

KTC1350LP3A1 KT 3X1350CO FLAT ELBOW N1

71

KTC1350LP3A2 KT 3X1350CO FLAT ELBOW N2

71

KTC1350LP3B1 KT 3X1350CO FLAT ELBOW N1

71

KTC1350LP3B2 KT 3X1350CO FLAT ELBOW N2

71

KTC1350LP3C1 KT 3X1350CO FLAT ELBOW N1

71

KTC1350LP3C1 KT 3X1350CO FLAT ELBOW N1

71

KTC1350LP3C2 KT 3X1350CO FLAT ELBOW N2

71

KTC1350LP4A1 KT 4X1350CO FLAT ELBOW N1

71

KTC1350LP4A2 KT 4X1350CO FLAT ELBOW N2

71

KTC1350LP4B1 KT 4X1350CO FLAT ELBOW N1

71

KTC1350LP4B2 KT 4X1350CO FLAT ELBOW N2

71

KTC1350LP4C1 KT 4X1350CO FLAT ELBOW N1

71

KTC1350LP4C2 KT 4X1350CO FLAT ELBOW N2

71

KTC1350LP5A1 KT 5X1350CO FLAT ELBOW N1

71

KTC1350LP5A2 KT 5X1350CO FLAT ELBOW N2

71

KTC1350LP5B1 KT 5X1350CO FLAT ELBOW N1

71

KTC1350LP5B2 KT 5X1350CO FLAT ELBOW N2

71

KTC1350LP5C1 KT 5X1350CO FLAT ELBOW N1

71

KTC1350LP5C2 KT 5X1350CO FLAT ELBOW N2

71

KTC1350LP7A1 KT 5X1350CO FLAT ELBOW N1

71

KTC1350LP7A2 KT 5X1350CO FLAT ELBOW N2

71

KTC1350EL73

KT 5X1350CO FEED UNIT EL N3

KTC1350EL74

KT 5X1350CO FEED UNIT EL N4

89

KTC1350EL75

KT 5X1350CO FEED UNIT EL N5

90

KTC1350ER31

KT 3X1350CO FEED UNIT ER N1

80

KTC1350ER32

KT 3X1350CO FEED UNIT ER N2

80

KTC1350ER33

KT 3X1350CO FEED UNIT ER N3

81

KTC1350ER34

KT 3X1350CO FEED UNIT ER N4

81

KTC1350ER35

KT 3X1350CO FEED UNIT ER N5

82

KTC1350ER36

KT 3X1350CO FEED UNIT ER N6

82

KTC1350ER37

KT 3X1350CO FEED UNIT ER N7

83

KTC1350ER41

KT 4X1350CO FEED UNIT ER N1

80

KTC1350ER42

KT 4X1350CO FEED UNIT ER N2

80

KTC1350ER43

KT 4X1350CO FEED UNIT ER N3

81

KTC1350ER44

KT 4X1350CO FEED UNIT ER N4

81

KTC1350ER45

KT 4X1350CO FEED UNIT ER N5

82

KTC1350ER46

KT 4X1350CO FEED UNIT ER N6

82

KTC1350ER47

KT 4X1350CO FEED UNIT ER N7

83

KTC1350ER51

KT 5X1350CO FEED UNIT ER N1

80

KTC1350ER52

KT 5X1350CO FEED UNIT ER N2

80

KTC1350ER53

KT 5X1350CO FEED UNIT ER N3

81

DEBU024EN_Index.indd

version: 1.1

Index of catalogue numbers

Index

Cat. no.

Pages

Cat. no.

KTC1350LP7B1 KT 5X1350CO FLAT ELBOW N1

Designations

71

KTC1600ED340 KT 3X1600CO PLUG-IN LENGTH 4M

66

KTC1350LP7B2 KT 5X1350CO FLAT ELBOW N2

71

KTC1600ED420 KT 4X1600CO PLUG-IN LENGTH 2M

66

KTC1350LP7C1 KT 5X1350CO FLAT ELBOW N1

71

KTC1600ED440 KT 4X1600CO PLUG-IN LENGTH 4M

66

KTC1350LP7C2 KT 5X1350CO FLAT ELBOW N2

71

KTC1600ED520 KT 5X1600CO PLUG-IN LENGTH 2M

66

KTC1350PL31

KT 3X1350CO LINE PROTECTOR NS

115

KTC1600ED540 KT 5X1600CO PLUG-IN LENGTH 4M

66

KTC1350PL41

KT 4X1350CO LINE PROTECTOR NS

115

KTC1600ED720 KT 5X1600CO PLUG-IN LENGTH 2M

66

KTC1350PL51

KT 5X1350CO LINE PROTECTOR NS

115

KTC1600ED740 KT 5X1600CO PLUG-IN LENGTH 4M

66

KTC1350PL71

KT 5X1350CO LINE PROTECTOR NS

115

KTC1600EH320 KT 3X1600CO KH PLUG-IN LENGTH 2M

68

KTC1350SL31

KT 3X1350CO ISOLATOR UNIT NA

113

KTC1600EH340 KT 3X1600CO KH PLUG-IN LENGTH 4M

68

KTC1350SL41

KT 4X1350CO ISOLATOR UNIT NA

113

KTC1600EH420 KT 4X1600CO KH PLUG-IN LENGTH 2M

68

KTC1350SL51

KT 5X1350CO ISOLATOR UNIT NA

113

KTC1600EH440 KT 4X1600CO KH PLUG-IN LENGTH 4M

68

KTC1350SL71

KT 5X1350CO ISOLATOR UNIT NA

113

KTC1600EH520 KT 5X1600CO KH PLUG-IN LENGTH 2M

68

KTC1350TC3

KT 3X1350CO TEE ON EDGE

73

KTC1600EH540 KT 5X1600CO KH PLUG-IN LENGTH 4M

68

KTC1350TC4

KT 4X1350CO TEE ON EDGE

73

KTC1600EL31

KT 3X1600CO FEED UNIT EL N1

88

KTC1350TC5

KT 5X1350CO TEE ON EDGE

73

KTC1600EL32

KT 3X1600CO FEED UNIT EL N2

88

KTC1350TC7

KT 5X1350CO TEE ON EDGE

73

KTC1600EL33

KT 3X1600CO FEED UNIT EL N3

89

KTC1350TN410

KT 4X1350CO NEUTRAL PERMUTA

69

KTC1600EL34

KT 3X1600CO FEED UNIT EL N4

89

KTC1350TP410

KT 4X1350CO PHASES PERMUTA

69

KTC1600EL35

KT 3X1600CO FEED UNIT EL N5

90

KTC1350YA3

KT 3X1350CO JUNCTION BLOC

70

KTC1600EL41

KT 4X1600CO FEED UNIT EL N1

88

KTC1350YA4

KT 4X1350CO JUNCTION BLOC

70

KTC1600EL42

KT 4X1600CO FEED UNIT EL N2

88

KTC1350ZC31

KT 3X1350CO EDGEWISE ZED N1

74

KTC1600EL43

KT 4X1600CO FEED UNIT EL N3

89

KTC1350ZC32

KT 3X1350CO EDGEWISE ZED N2

74

KTC1600EL44

KT 4X1600CO FEED UNIT EL N4

89

KTC1350ZC41

KT 4X1350CO EDGEWISE ZED N1

74

KTC1600EL45

KT 4X1600CO FEED UNIT EL N5

90

KTC1350ZC42

KT 4X1350CO EDGEWISE ZED N2

74

KTC1600EL51

KT 5X1600CO FEED UNIT EL N1

88

KTC1350ZC51

KT 5X1350CO EDGEWISE ZED N1

74

KTC1600EL52

KT 5X1600CO FEED UNIT EL N2

88

KTC1350ZC52

KT 5X1350CO EDGEWISE ZED N2

74

KTC1600EL53

KT 5X1600CO FEED UNIT EL N3

89

KTC1350ZC71

KT 5X1350CO EDGEWISE ZED N1

74

KTC1600EL54

KT 5X1600CO FEED UNIT EL N4

89

KTC1350ZC72

KT 5X1350CO EDGEWISE ZED N2

74

KTC1600EL55

KT 5X1600CO FEED UNIT EL N5

90

KTC1350ZP3

KT 3X1350CO ZED ON FLAT

74

KTC1600EL71

KT 5X1600CO FEED UNIT EL N1

88

KTC1350ZP4

KT 4X1350CO ZED ON FLAT

74

KTC1600EL72

KT 5X1600CO FEED UNIT EL N2

88

KTC1350ZP5

KT 5X1350CO ZED ON FLAT

74

KTC1600EL73

KT 5X1600CO FEED UNIT EL N3

89

KTC1350ZP7

KT 5X1350CO ZED ON FLAT

74

KTC1600EL74

KT 5X1600CO FEED UNIT EL N4

89

KTC1600EL75

KT 5X1600CO FEED UNIT EL N5

90

KTC1600ER31

KT 3X1600CO FEED UNIT ER N1

80

KTC1600

Designations

Pages

KTC1600CP31

KT 3X1600CO FLAT EDGEWISE N1

75

KTC1600ER32

KT 3X1600CO FEED UNIT ER N2

80

KTC1600CP32

KT 3X1600CO FLAT EDGEWISE N2

75

KTC1600ER33

KT 3X1600CO FEED UNIT ER N3

81

KTC1600CP33

KT 3X1600CO FLAT EDGEWISE N3

75

KTC1600ER34

KT 3X1600CO FEED UNIT ER N4

81

KTC1600CP34

KT 3X1600CO FLAT EDGEWISE N4

75

KTC1600ER35

KT 3X1600CO FEED UNIT ER N5

82

KTC1600CP41

KT 4X1600CO FLAT EDGEWISE N1

75

KTC1600ER36

KT 3X1600CO FEED UNIT ER N6

82

KTC1600CP42

KT 4X1600CO FLAT EDGEWISE N2

75

KTC1600ER37

KT 3X1600CO FEED UNIT ER N7

83

KTC1600CP43

KT 4X1600CO FLAT EDGEWISE N3

75

KTC1600ER41

KT 4X1600CO FEED UNIT ER N1

80

KTC1600CP44

KT 4X1600CO FLAT EDGEWISE N4

75

KTC1600ER42

KT 4X1600CO FEED UNIT ER N2

80

KTC1600CP51

KT 5X1600CO FLAT EDGEWISE N1

75

KTC1600ER43

KT 4X1600CO FEED UNIT ER N3

81

KTC1600CP52

KT 5X1600CO FLAT EDGEWISE N2

75

KTC1600ER44

KT 4X1600CO FEED UNIT ER N4

81

KTC1600CP53

KT 5X1600CO FLAT EDGEWISE N3

75

KTC1600ER45

KT 4X1600CO FEED UNIT ER N5

82

KTC1600CP54

KT 5X1600CO FLAT EDGEWISE N4

75

KTC1600ER46

KT 4X1600CO FEED UNIT ER N6

82

KTC1600CP71

KT 5X1600CO FLAT EDGEWISE N1

75

KTC1600ER47

KT 4X1600CO FEED UNIT ER N7

83

KTC1600CP72

KT 5X1600CO FLAT EDGEWISE N2

75

KTC1600ER51

KT 5X1600CO FEED UNIT ER N1

80

KTC1600CP73

KT 5X1600CO FLAT EDGEWISE N3

75

KTC1600ER52

KT 5X1600CO FEED UNIT ER N2

80

KTC1600CP74

KT 5X1600CO FLAT EDGEWISE N4

75

KTC1600ER53

KT 5X1600CO FEED UNIT ER N3

81

KTC1600DB310 KT 3X1600CO EXPANSION UNIT

69

KTC1600ER54

KT 5X1600CO FEED UNIT ER N4

81

KTC1600DB410 KT 4X1600CO EXPANSION UNIT

69

KTC1600ER55

KT 5X1600CO FEED UNIT ER N5

82

KTC1600DB510 KT 5X1600CO EXPANSION UNIT

69

KTC1600ER56

KT 5X1600CO FEED UNIT ER N6

82

KTC1600DB710 KT 5X1600CO EXPANSION UNIT

69

KTC1600ER57

KT 5X1600CO FEED UNIT ER N7

83

KTC1600EB320 KT 3X1600CO BOLT ON LENGTH 2M

67

KTC1600ER71

KT 5X1600CO FEED UNIT ER N1

80

KTC1600EB340 KT 3X1600CO BOLT ON LENGTH 4M

67

KTC1600ER72

KT 5X1600CO FEED UNIT ER N2

80

KTC1600EB420 KT 4X1600CO BOLT ON LENGTH 2M

67

KTC1600ER73

KT 5X1600CO FEED UNIT ER N3

81

KTC1600EB440 KT 4X1600CO BOLT ON LENGTH 4M

67

KTC1600ER74

KT 5X1600CO FEED UNIT ER N4

81

KTC1600EB520 KT 5X1600CO BOLT ON LENGTH 2M

67

KTC1600ER75

KT 5X1600CO FEED UNIT ER N5

82

KTC1600EB540 KT 5X1600CO BOLT ON LENGTH 4M

67

KTC1600ER76

KT 5X1600CO FEED UNIT ER N6

82

KTC1600EB720 KT 5X1600CO BOLT ON LENGTH 2M

67

KTC1600ER77

KT 5X1600CO FEED UNIT ER N7

83

KTC1600EB740 KT 5X1600CO BOLT ON LENGTH 4M

67

KTC1600ET31A KT 3X1600CO FEEDER LENGTH

66

KTC1600ED320 KT 3X1600CO PLUG-IN LENGTH 2M

66

KTC1600ET320

66

KT 3X1600CO FEEDER LENGTH 2M

version: 1.1

DEBU024EN_Index.indd

Cat. no.

Pages

Cat. no.

Designations

Pages

KTC1600ET32B KT 3X1600CO FEEDER LENGTH

Designations

66

KTC1600TC4

KT 4X1600CO TEE ON EDGE

73

KTC1600ET32C KT 3X1600CO FEEDER LENGTH

66

KTC1600TC5

KT 5X1600CO TEE ON EDGE

73

KTC1600ET33D KT 3X1600CO FEEDER LENGTH

66

KTC1600TC7

KT 5X1600CO TEE ON EDGE

73

KTC1600ET340

66

KTC1600TN410

KT 4X1600CO NEUTRAL PERMUTA

69

KTC1600ET41A KT 4X1600CO FEEDER LENGTH

66

KTC1600TP410

KT 4X1600CO PHASES PERMUTA

69

KTC1600ET420

66

KTC1600YA3

KT 3X1600CO JUNCTION BLOC

70

KTC1600ET42B KT 4X1600CO FEEDER LENGTH

66

KTC1600YA4

KT 4X1600CO JUNCTION BLOC

70

KTC1600ET42C KT 4X1600CO FEEDER LENGTH

66

KTC1600ZC31

KT 3X1600CO EDGEWISE ZED N1

74

KTC1600ET43D KT 4X1600CO FEEDER LENGTH

66

KTC1600ZC32

KT 3X1600CO EDGEWISE ZED N2

74

KTC1600ET440

66

KTC1600ZC41

KT 4X1600CO EDGEWISE ZED N1

74

KTC1600ET51A KT 5X1600CO FEEDER LENGTH

66

KTC1600ZC42

KT 4X1600CO EDGEWISE ZED N2

74

KTC1600ET520

66

KTC1600ZC51

KT 5X1600CO EDGEWISE ZED N1

74

KTC1600ET52B KT 5X1600CO FEEDER LENGTH

66

KTC1600ZC52

KT 5X1600CO EDGEWISE ZED N2

74

KTC1600ET52C KT 5X1600CO FEEDER LENGTH

66

KTC1600ZC71

KT 5X1600CO EDGEWISE ZED N1

74

KTC1600ET53D KT 5X1600CO FEEDER LENGTH

66

KTC1600ZC72

KT 5X1600CO EDGEWISE ZED N2

74

KTC1600ET540

66

KTC1600ZP3

KT 3X1600CO ZED ON FLAT

74

KTC1600ET71A KT 5X1600CO FEEDER LENGTH

66

KTC1600ZP4

KT 4X1600CO ZED ON FLAT

74

KTC1600ET720

66

KTC1600ZP5

KT 5X1600CO ZED ON FLAT

74

KTC1600ET72B KT 5X1600CO FEEDER LENGTH

66

KTC1600ZP7

KT 5X1600CO ZED ON FLAT

74

KTC1600ET72C KT 5X1600CO FEEDER LENGTH

66

KTC1600ET73D KT 5X1600CO FEEDER LENGTH

66

KTC2000

KTC1600ET740

KT 5X1600CO FEEDER LENGTH 4M

66

KTC2000CP31

KT 3X2000CO FLAT EDGEWISE N1

75

KTC1600LC3A

KT 3X1600CO EDGEWISE ELBOW

72

KTC2000CP32

KT 3X2000CO FLAT EDGEWISE N2

75

KTC1600LC3B

KT 3X1600CO EDGEWISE ELBOW

72

KTC2000CP33

KT 3X2000CO FLAT EDGEWISE N3

75

KTC1600LC4A

KT 4X1600CO EDGEWISE ELBOW

72

KTC2000CP34

KT 3X2000CO FLAT EDGEWISE N4

75

KTC1600LC4B

KT 4X1600CO EDGEWISE ELBOW

72

KTC2000CP41

KT 4X2000CO FLAT EDGEWISE N1

75

KTC1600LC5A

KT 5X1600CO EDGEWISE ELBOW

72

KTC2000CP42

KT 4X2000CO FLAT EDGEWISE N2

75

KTC1600LC5B

KT 5X1600CO EDGEWISE ELBOW

72

KTC2000CP43

KT 4X2000CO FLAT EDGEWISE N3

75

KTC1600LC7A

KT 5X1600CO EDGEWISE ELBOW

72

KTC2000CP44

KT 4X2000CO FLAT EDGEWISE N4

75

KTC1600LC7B

KT 5X1600CO EDGEWISE ELBOW

72

KTC2000CP51

KT 5X2000CO FLAT EDGEWISE N1

75

KTC1600LP3A1 KT 3X1600CO FLAT ELBOW N1

71

KTC2000CP52

KT 5X2000CO FLAT EDGEWISE N2

75

KTC1600LP3A2 KT 3X1600CO FLAT ELBOW N2

71

KTC2000CP53

KT 5X2000CO FLAT EDGEWISE N3

75

KTC1600LP3B1 KT 3X1600CO FLAT ELBOW N1

71

KTC2000CP54

KT 5X2000CO FLAT EDGEWISE N4

75

KTC1600LP3B2 KT 3X1600CO FLAT ELBOW N2

71

KTC2000CP71

KT 5X2000CO FLAT EDGEWISE N1

75

KTC1600LP3C1 KT 3X1600CO FLAT ELBOW N1

71

KTC2000CP72

KT 5X2000CO FLAT EDGEWISE N2

75

KTC1600LP3C2 KT 3X1600CO FLAT ELBOW N2

71

KTC2000CP73

KT 5X2000CO FLAT EDGEWISE N3

75

KTC1600LP4A1 KT 4X1600CO FLAT ELBOW N1

71

KTC2000CP74

KT 5X2000CO FLAT EDGEWISE N4

75

KTC1600LP4A2 KT 4X1600CO FLAT ELBOW N2

71

KTC2000DB310 KT 3X2000CO EXPANSION UNIT

69

KTC1600LP4B1 KT 4X1600CO FLAT ELBOW N1

71

KTC2000DB410 KT 4X2000CO EXPANSION UNIT

69

KTC1600LP4B2 KT 4X1600CO FLAT ELBOW N2

71

KTC2000DB510 KT 5X2000CO EXPANSION UNIT

69

KTC1600LP4C1 KT 4X1600CO FLAT ELBOW N1

71

KTC2000DB710 KT 5X2000CO EXPANSION UNIT

69

KTC1600LP4C2 KT 4X1600CO FLAT ELBOW N2

71

KTC2000EB320 KT 3X2000CO BOLT ON LENGTH 2M

67

KTC1600LP5A1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000EB340 KT 3X2000CO BOLT ON LENGTH 4M

67

KTC1600LP5A2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000EB420 KT 4X2000CO BOLT ON LENGTH 2M

67

KTC1600LP5B1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000EB440 KT 4X2000CO BOLT ON LENGTH 4M

67

KTC1600LP5B2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000EB520 KT 5X2000CO BOLT ON LENGTH 2M

67

KTC1600LP5C1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000EB540 KT 5X2000CO BOLT ON LENGTH 4M

67

KTC1600LP5C2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000EB720 KT 5X2000CO BOLT ON LENGTH 2M

67

KTC1600LP7A1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000EB740 KT 5X2000CO BOLT ON LENGTH 4M

67

KTC1600LP7A2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000ED320 KT 3X2000CO PLUG-IN LENGTH 2M

66

KTC1600LP7B1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000ED340 KT 3X2000CO PLUG-IN LENGTH 4M

66

KTC1600LP7B2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000ED420 KT 4X2000CO PLUG-IN LENGTH 2M

66

KTC1600LP7C1 KT 5X1600CO FLAT ELBOW N1

71

KTC2000ED440 KT 4X2000CO PLUG-IN LENGTH 4M

66

KTC1600LP7C2 KT 5X1600CO FLAT ELBOW N2

71

KTC2000ED520 KT 5X2000CO PLUG-IN LENGTH 2M

66

KTC1600PL31

KT 3X1600CO LINE PROTECTOR NS

115

KTC2000ED540 KT 5X2000CO PLUG-IN LENGTH 4M

66

KTC1600PL41

KT 4X1600CO LINE PROTECTOR NS

115

KTC2000EH320 KT 3X2000CO KH PLUG-IN LENGTH 2M

68

KTC1600PL51

KT 5X1600CO LINE PROTECTOR NS

115

KTC2000EH340 KT 3X2000CO KH PLUG-IN LENGTH 4M

68

KTC1600PL71

KT 5X1600CO LINE PROTECTOR NS

115

KTC2000EH420 KT 4X2000CO KH PLUG-IN LENGTH 2M

68

KTC1600SL31

KT 3X1600CO ISOLATOR UNIT NA

113

KTC2000EH440 KT 4X2000CO KH PLUG-IN LENGTH 4M

68

KTC1600SL41

KT 4X1600CO ISOLATOR UNIT NA

113

KTC2000EH520 KT 5X2000CO KH PLUG-IN LENGTH 2M

68

KTC1600SL51

KT 5X1600CO ISOLATOR UNIT NA

113

KTC2000EH540 KT 5X2000CO KH PLUG-IN LENGTH 4M

68

KTC1600SL71

KT 5X1600CO ISOLATOR UNIT NA

113

KTC2000EL31

KT 3X2000CO FEED UNIT EL N1

88

KTC1600TC3

KT 3X1600CO TEE ON EDGE

73

KTC2000EL32

KT 3X2000CO FEED UNIT EL N2

88

KT 3X1600CO FEEDER LENGTH 4M


KT 4X1600CO FEEDER LENGTH 2M

KT 4X1600CO FEEDER LENGTH 4M


KT 5X1600CO FEEDER LENGTH 2M

KT 5X1600CO FEEDER LENGTH 4M


KT 5X1600CO FEEDER LENGTH 2M

DEBU024EN_Index.indd

version: 1.1

Index of catalogue numbers

Index

Cat. no.

Designations

Pages

Cat. no.

Designations

Pages

KTC2000EL33

KT 3X2000CO FEED UNIT EL N3

89

KTC2000ET540

KT 5X2000CO FEEDER LENGTH 4M

66

KTC2000EL34

KT 3X2000CO FEED UNIT EL N4

89

KTC2000ET71A KT 5X2000CO FEEDER LENGTH

66

KTC2000EL35

KT 3X2000CO FEED UNIT EL N5

90

KTC2000ET720

66

KTC2000EL41

KT 4X2000CO FEED UNIT EL N1

88

KTC2000ET72B KT 5X2000CO FEEDER LENGTH

66

KTC2000EL42

KT 4X2000CO FEED UNIT EL N2

88

KTC2000ET72C KT 5X2000CO FEEDER LENGTH

66

KTC2000EL43

KT 4X2000CO FEED UNIT EL N3

89

KTC2000ET73D KT 5X2000CO FEEDER LENGTH

66

KTC2000EL44

KT 4X2000CO FEED UNIT EL N4

89

KTC2000ET740

KT 5X2000CO FEEDER LENGTH 4M

66

KTC2000EL45

KT 4X2000CO FEED UNIT EL N5

90

KTC2000LC3A

KT 3X2000CO EDGEWISE ELBOW

72

KTC2000EL51

KT 5X2000CO FEED UNIT EL N1

88

KTC2000LC3B

KT 3X2000CO EDGEWISE ELBOW

72

KTC2000EL52

KT 5X2000CO FEED UNIT EL N2

88

KTC2000LC4A

KT 4X2000CO EDGEWISE ELBOW

72

KTC2000EL53

KT 5X2000CO FEED UNIT EL N3

89

KTC2000LC4B

KT 4X2000CO EDGEWISE ELBOW

72

KTC2000EL54

KT 5X2000CO FEED UNIT EL N4

89

KTC2000LC5A

KT 5X2000CO EDGEWISE ELBOW

72

KTC2000EL55

KT 5X2000CO FEED UNIT EL N5

90

KTC2000LC5B

KT 5X2000CO EDGEWISE ELBOW

72

KTC2000EL71

KT 5X2000CO FEED UNIT EL N1

88

KTC2000LC7A

KT 5X2000CO EDGEWISE ELBOW

72

KTC2000EL72

KT 5X2000CO FEED UNIT EL N2

88

KTC2000LC7B

KT 5X2000CO EDGEWISE ELBOW

72

KTC2000EL73

KT 5X2000CO FEED UNIT EL N3

89

KTC2000LP3A1 KT 3X2000CO FLAT ELBOW N1

71

KTC2000EL74

KT 5X2000CO FEED UNIT EL N4

89

KTC2000LP3A2 KT 3X2000CO FLAT ELBOW N2

71

KTC2000EL75

KT 5X2000CO FEED UNIT EL N5

90

KTC2000LP3B1 KT 3X2000CO FLAT ELBOW N1

71

KTC2000ER31

KT 3X2000CO FEED UNIT ER N1

80

KTC2000LP3B2 KT 3X2000CO FLAT ELBOW N2

71

KTC2000ER32

KT 3X2000CO FEED UNIT ER N2

80

KTC2000LP3C1 KT 3X2000CO FLAT ELBOW N1

71

KTC2000ER33

KT 3X2000CO FEED UNIT ER N3

81

KTC2000LP3C1 KT 3X2000CO FLAT ELBOW N1

71

KTC2000ER34

KT 3X2000CO FEED UNIT ER N4

81

KTC2000LP3C2 KT 3X2000CO FLAT ELBOW N2

71

KTC2000ER35

KT 3X2000CO FEED UNIT ER N5

82

KTC2000LP4A1 KT 4X2000CO FLAT ELBOW N1

71

KTC2000ER36

KT 3X2000CO FEED UNIT ER N6

82

KTC2000LP4A2 KT 4X2000CO FLAT ELBOW N2

71

KTC2000ER37

KT 3X2000CO FEED UNIT ER N7

83

KTC2000LP4B1 KT 4X2000CO FLAT ELBOW N1

71

KTC2000ER41

KT 4X2000CO FEED UNIT ER N1

80

KTC2000LP4B2 KT 4X2000CO FLAT ELBOW N2

71

KTC2000ER42

KT 4X2000CO FEED UNIT ER N2

80

KTC2000LP4C1 KT 4X2000CO FLAT ELBOW N1

71

KTC2000ER43

KT 4X2000CO FEED UNIT ER N3

81

KTC2000LP4C2 KT 4X2000CO FLAT ELBOW N2

71

KTC2000ER44

KT 4X2000CO FEED UNIT ER N4

81

KTC2000LP5A1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER45

KT 4X2000CO FEED UNIT ER N5

82

KTC2000LP5A2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER46

KT 4X2000CO FEED UNIT ER N6

82

KTC2000LP5B1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER47

KT 4X2000CO FEED UNIT ER N7

83

KTC2000LP5B2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER51

KT 5X2000CO FEED UNIT ER N1

80

KTC2000LP5C1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER52

KT 5X2000CO FEED UNIT ER N2

80

KTC2000LP5C2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER53

KT 5X2000CO FEED UNIT ER N3

81

KTC2000LP7A1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER54

KT 5X2000CO FEED UNIT ER N4

81

KTC2000LP7A2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER55

KT 5X2000CO FEED UNIT ER N5

82

KTC2000LP7B1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER56

KT 5X2000CO FEED UNIT ER N6

82

KTC2000LP7B2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER57

KT 5X2000CO FEED UNIT ER N7

83

KTC2000LP7C1 KT 5X2000CO FLAT ELBOW N1

71

KTC2000ER71

KT 5X2000CO FEED UNIT ER N1

80

KTC2000LP7C2 KT 5X2000CO FLAT ELBOW N2

71

KTC2000ER72

KT 5X2000CO FEED UNIT ER N2

80

KTC2000SL31

KT 3X2000CO ISOLATOR UNIT INV

113

KTC2000ER73

KT 5X2000CO FEED UNIT ER N3

81

KTC2000SL41

KT 4X2000CO ISOLATOR UNIT INV

113

KTC2000ER74

KT 5X2000CO FEED UNIT ER N4

81

KTC2000SL51

KT 5X2000CO ISOLATOR UNIT INV

113

KTC2000ER75

KT 5X2000CO FEED UNIT ER N5

82

KTC2000SL71

KT 5X2000CO ISOLATOR UNIT INV

113

KTC2000ER76

KT 5X2000CO FEED UNIT ER N6

82

KTC2000TC3

KT 3X2000CO TEE ON EDGE

73

KTC2000ER77

KT 5X2000CO FEED UNIT ER N7

83

KTC2000TC4

KT 4X2000CO TEE ON EDGE

73

KTC2000ET31A KT 3X2000CO FEEDER LENGTH

66

KTC2000TC5

KT 5X2000CO TEE ON EDGE

73

KTC2000ET320

66

KTC2000TC7

KT 5X2000CO TEE ON EDGE

73

KTC2000ET32B KT 3X2000CO FEEDER LENGTH

66

KTC2000TN410

KT 4X2000CO NEUTRAL PERMUTA

69

KTC2000ET32C KT 3X2000CO FEEDER LENGTH

66

KTC2000TP410

KT 4X2000CO PHASES PERMUTA

69

KTC2000ET33D KT 3X2000CO FEEDER LENGTH

66

KTC2000YA3

KT 3X2000CO JUNCTION BLOC

70

KTC2000ET340

66

KTC2000YA4

KT 4X2000CO JUNCTION BLOC

70

KTC2000ET41A KT 4X2000CO FEEDER LENGTH

66

KTC2000ZC31

KT 3X2000CO EDGEWISE ZED N1

74

KTC2000ET420

66

KTC2000ZC32

KT 3X2000CO EDGEWISE ZED N2

74

KTC2000ET42B KT 4X2000CO FEEDER LENGTH

66

KTC2000ZC41

KT 4X2000CO EDGEWISE ZED N1

74

KTC2000ET42C KT 4X2000CO FEEDER LENGTH

66

KTC2000ZC42

KT 4X2000CO EDGEWISE ZED N2

74

KTC2000ET43D KT 4X2000CO FEEDER LENGTH

66

KTC2000ZC51

KT 5X2000CO EDGEWISE ZED N1

74

KTC2000ET440

66

KTC2000ZC52

KT 5X2000CO EDGEWISE ZED N2

74

KTC2000ET51A KT 5X2000CO FEEDER LENGTH

66

KTC2000ZC71

KT 5X2000CO EDGEWISE ZED N1

74

KTC2000ET520

66

KTC2000ZC72

KT 5X2000CO EDGEWISE ZED N2

74

KTC2000ET52B KT 5X2000CO FEEDER LENGTH

66

KTC2000ZP3

KT 3X2000CO ZED ON FLAT

74

KTC2000ET52C KT 5X2000CO FEEDER LENGTH

66

KTC2000ZP4

KT 4X2000CO ZED ON FLAT

74

KTC2000ET53D KT 5X2000CO FEEDER LENGTH

66

KTC2000ZP5

KT 5X2000CO ZED ON FLAT

74

10

KT 3X2000CO FEEDER LENGTH 2M

KT 3X2000CO FEEDER LENGTH 4M


KT 4X2000CO FEEDER LENGTH 2M

KT 4X2000CO FEEDER LENGTH 4M


KT 5X2000CO FEEDER LENGTH 2M

KT 5X2000CO FEEDER LENGTH 2M

version: 1.1

DEBU024EN_Index.indd

Cat. no.

Designations

Pages

Cat. no.

Designations

Pages

KTC2000ZP7

KT 5X2000CO ZED ON FLAT

74

KTC2500EL74

KT 5X2500CO FEED UNIT EL N4

89

KTC2500EL75

KT 5X2500CO FEED UNIT EL N5

90

KTC2500ER31

KT 3X2500CO FEED UNIT ER N1

80

75

KTC2500ER32

KT 3X2500CO FEED UNIT ER N2

80

KT 3X2500CO FEED UNIT ER N3

81

KTC2500
KTC2500CP31

KT 3X2500CO FLAT EDGEWISE N1

KTC2500CP32

KT 3X2500CO FLAT EDGEWISE N2

75

KTC2500ER33

KTC2500CP33

KT 3X2500CO FLAT EDGEWISE N3

75

KTC2500ER34

KT 3X2500CO FEED UNIT ER N4

81

KTC2500CP34

KT 3X2500CO FLAT EDGEWISE N4

75

KTC2500ER35

KT 3X2500CO FEED UNIT ER N5

82

KT 3X2500CO FEED UNIT ER N6

82

KTC2500CP41

KT 4X2500CO FLAT EDGEWISE N1

75

KTC2500ER36

KTC2500CP42

KT 4X2500CO FLAT EDGEWISE N2

75

KTC2500ER37

KT 3X2500CO FEED UNIT ER N7

83

KTC2500CP43

KT 4X2500CO FLAT EDGEWISE N3

75

KTC2500ER41

KT 4X2500CO FEED UNIT ER N1

80

KT 4X2500CO FEED UNIT ER N2

80

KTC2500CP44

KT 4X2500CO FLAT EDGEWISE N4

75

KTC2500ER42

KTC2500CP51

KT 5X2500CO FLAT EDGEWISE N1

75

KTC2500ER43

KT 4X2500CO FEED UNIT ER N3

81

KTC2500CP52

KT 5X2500CO FLAT EDGEWISE N2

75

KTC2500ER44

KT 4X2500CO FEED UNIT ER N4

81

KTC2500CP53

KT 5X2500CO FLAT EDGEWISE N3

75

KTC2500ER45

KT 4X2500CO FEED UNIT ER N5

82

KTC2500CP54

KT 5X2500CO FLAT EDGEWISE N4

75

KTC2500ER46

KT 4X2500CO FEED UNIT ER N6

82

KTC2500CP71

KT 5X2500CO FLAT EDGEWISE N1

75

KTC2500ER47

KT 4X2500CO FEED UNIT ER N7

83

KTC2500CP72

KT 5X2500CO FLAT EDGEWISE N2

75

KTC2500ER51

KT 5X2500CO FEED UNIT ER N1

80

KT 5X2500CO FEED UNIT ER N2

80

KTC2500CP73

KT 5X2500CO FLAT EDGEWISE N3

75

KTC2500ER52

KTC2500CP74

KT 5X2500CO FLAT EDGEWISE N4

75

KTC2500ER53

KT 5X2500CO FEED UNIT ER N3

81

69

KTC2500ER54

KT 5X2500CO FEED UNIT ER N4

81

KTC2500DB410 KT 4X2500CO EXPANSION UNIT

69

KTC2500ER55

KT 5X2500CO FEED UNIT ER N5

82

KTC2500DB510 KT 5X2500CO EXPANSION UNIT

69

KTC2500ER56

KT 5X2500CO FEED UNIT ER N6

82

KTC2500DB710 KT 5X2500CO EXPANSION UNIT

69

KTC2500ER57

KT 5X2500CO FEED UNIT ER N7

83

KTC2500EB320 KT 3X2500CO BOLT ON LENGTH 2M

67

KTC2500ER71

KT 5X2500CO FEED UNIT ER N1

80

KTC2500EB340 KT 3X2500CO BOLT ON LENGTH 4M

67

KTC2500ER72

KT 5X2500CO FEED UNIT ER N2

80

KTC2500EB420 KT 4X2500CO BOLT ON LENGTH 2M

67

KTC2500ER73

KT 5X2500CO FEED UNIT ER N3

81

KTC2500EB440 KT 4X2500CO BOLT ON LENGTH 4M

67

KTC2500ER74

KT 5X2500CO FEED UNIT ER N4

81

KTC2500EB520 KT 5X2500CO BOLT ON LENGTH 2M

67

KTC2500ER75

KT 5X2500CO FEED UNIT ER N5

82

KTC2500EB540 KT 5X2500CO BOLT ON LENGTH 4M

67

KTC2500ER76

KT 5X2500CO FEED UNIT ER N6

82

KTC2500EB720 KT 5X2500CO BOLT ON LENGTH 2M

67

KTC2500ER77

KT 5X2500CO FEED UNIT ER N7

83

KTC2500EB740 KT 5X2500CO BOLT ON LENGTH 4M

67

KTC2500ET31A KT 3X2500CO FEEDER LENGTH

66

KTC2500ED320 KT 3X2500CO PLUG-IN LENGTH 2M

66

KTC2500ET320

66

KTC2500ED340 KT 3X2500CO PLUG-IN LENGTH 4M

66

KTC2500ET32B KT 3X2500CO FEEDER LENGTH

66

KTC2500ED420 KT 5X2500CO PLUG-IN LENGTH 2M

66

KTC2500ET32C KT 3X2500CO FEEDER LENGTH

66

KTC2500ED440 KT 4X2500CO PLUG-IN LENGTH 4M

66

KTC2500ET33D KT 3X2500CO FEEDER LENGTH

66

KTC2500ED520 KT 5X2500CO PLUG-IN LENGTH 2M

66

KTC2500ET340

66

KTC2500ED540 KT 5X2500CO PLUG-IN LENGTH 4M

66

KTC2500ET41A KT 4X2500CO FEEDER LENGTH

66

KTC2500ED720 KT 5X2500CO PLUG-IN LENGTH 2M

66

KTC2500ET420

66

KTC2500ED740 KT 5X2500CO PLUG-IN LENGTH 4M

66

KTC2500ET42B KT 4X2500CO FEEDER LENGTH

66

KTC2500EH320 KT 3X2500CO KH PLUG-IN LENGTH 2M

68

KTC2500ET42C KT 4X2500CO FEEDER LENGTH

66

KTC2500EH340 KT 3X2500CO KH PLUG-IN LENGTH 4M

68

KTC2500ET43D KT 4X2500CO FEEDER LENGTH

66

KTC2500EH420 KT 4X2500CO KH PLUG-IN LENGTH 2M

68

KTC2500ET440

66

KTC2500EH440 KT 4X2500CO KH PLUG-IN LENGTH 4M

68

KTC2500ET51A KT 5X2500CO FEEDER LENGTH

66

KTC2500EH520 KT 5X2500CO KH PLUG-IN LENGTH 2M

68

KTC2500ET520

66

KTC2500EH540 KT 5X2500CO KH PLUG-IN LENGTH 4M

68

KTC2500ET52B KT 5X2500CO FEEDER LENGTH

66

KTC2500EL31

88

KTC2500ET52C KT 5X2500CO FEEDER LENGTH

66
66
66

KTC2500DB310 KT 3X2500CO EXPANSION UNIT

KT 3X2500CO FEED UNIT EL N1

KT 3X2500CO FEEDER LENGTH 2M

KT 3X2500CO FEEDER LENGTH 4M


KT 4X2500CO FEEDER LENGTH 2M

KT 4X2500CO FEEDER LENGTH 4M


KT 5X2500CO FEEDER LENGTH 2M

KTC2500EL32

KT 3X2500CO FEED UNIT EL N2

88

KTC2500ET53D KT 5X2500CO FEEDER LENGTH

KTC2500EL33

KT 3X2500CO FEED UNIT EL N3

89

KTC2500ET540

KTC2500EL34

KT 3X2500CO FEED UNIT EL N4

89

KTC2500ET71A KT 5X2500CO FEEDER LENGTH

66
66

KT 5X2500CO FEEDER LENGTH 4M

KTC2500EL35

KT 3X2500CO FEED UNIT EL N5

90

KTC2500ET720

KT 5X2500CO FEEDER LENGTH 2M

KTC2500EL41

KT 4X2500CO FEED UNIT EL N1

88

KTC2500ET72B KT 5X2500CO FEEDER LENGTH

66

KTC2500EL42

KT 4X2500CO FEED UNIT EL N2

88

KTC2500ET72C KT 5X2500CO FEEDER LENGTH

66
66

KTC2500EL43

KT 4X2500CO FEED UNIT EL N3

89

KTC2500ET73D KT 5X2500CO FEEDER LENGTH

KTC2500EL44

KT 4X2500CO FEED UNIT EL N4

89

KTC2500ET740

KT 5X2500CO FEEDER LENGTH 4M

66

KTC2500EL45

KT 4X2500CO FEED UNIT EL N5

90

KTC2500LC3A

KT 3X2500CO EDGEWISE ELBOW

72

KTC2500EL51

KT 5X2500CO FEED UNIT EL N1

88

KTC2500LC3B

KT 3X2500CO EDGEWISE ELBOW

72

KT 4X2500CO EDGEWISE ELBOW

72

KTC2500EL52

KT 5X2500CO FEED UNIT EL N2

88

KTC2500LC4A

KTC2500EL53

KT 5X2500CO FEED UNIT EL N3

89

KTC2500LC4B

KT 4X2500CO EDGEWISE ELBOW

72

KTC2500EL54

KT 5X2500CO FEED UNIT EL N4

89

KTC2500LC5A

KT 5X2500CO EDGEWISE ELBOW

72

KT 5X2500CO EDGEWISE ELBOW

72

KTC2500EL55

KT 5X2500CO FEED UNIT EL N5

90

KTC2500LC5B

KTC2500EL71

KT 5X2500CO FEED UNIT EL N1

88

KTC2500LC7A

KT 5X2500CO EDGEWISE ELBOW

72

KTC2500EL72

KT 5X2500CO FEED UNIT EL N2

88

KTC2500LC7B

KT 5X2500CO EDGEWISE ELBOW

72

89

KTC2500LP3A1 KT 3X2500CO FLAT ELBOW N1

KTC2500EL73

KT 5X2500CO FEED UNIT EL N3

DEBU024EN_Index.indd

version: 1.1

71

11

Index of catalogue number

Index

Cat. no.

Pages

Cat. no.

Designations

Pages

KTC2500LP3A2 KT 3X2500CO FLAT ELBOW N2

Designations

71

KTC3200CP72

KT 5X3200CO FLAT EDGEWISE N2

75

KTC2500LP3B1 KT 3X2500CO FLAT ELBOW N1

71

KTC3200CP73

KT 5X3200CO FLAT EDGEWISE N3

75

KTC2500LP3B2 KT 3X2500CO FLAT ELBOW N2

71

KTC3200CP74

KT 5X3200CO FLAT EDGEWISE N4

75

KTC2500LP3C1 KT 3X2500CO FLAT ELBOW N1

71

KTC3200DB310 KT 3X3200CO EXPANSION UNIT

69

KTC2500LP3C1 KT 3X2500CO FLAT ELBOW N1

71

KTC3200DB410 KT 4X3200CO EXPANSION UNIT

71

KTC2500LP3C2 KT 3X2500CO FLAT ELBOW N2

71

KTC3200DB510 KT 5X3200CO EXPANSION UNIT

71

KTC2500LP4A1 KT 4X2500CO FLAT ELBOW N1

71

KTC3200DB710 KT 5X3200CO EXPANSION UNIT

71

KTC2500LP4A2 KT 4X2500CO FLAT ELBOW N2

71

KTC3200EB320 KT 3X3200CO BOLT ON LENGTH 2M

67

KTC2500LP4B1 KT 4X2500CO FLAT ELBOW N1

71

KTC3200EB340 KT 3X3200CO BOLT ON LENGTH 4M

67

KTC2500LP4B2 KT 4X2500CO FLAT ELBOW N2

71

KTC3200EB420 KT 4X3200CO BOLT ON LENGTH 2M

67

KTC2500LP4C1 KT 4X2500CO FLAT ELBOW N1

71

KTC3200EB440 KT 4X3200CO BOLT ON LENGTH 4M

67

KTC2500LP4C2 KT 4X2500CO FLAT ELBOW N2

71

KTC3200EB520 KT 5X3200CO BOLT ON LENGTH 2M

67

KTC2500LP5A1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200EB540 KT 5X3200CO BOLT ON LENGTH 4M

67

KTC2500LP5A2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200EB720 KT 5X3200CO BOLT ON LENGTH 2M

67

KTC2500LP5B1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200EB740 KT 5X3200CO BOLT ON LENGTH 4M

67

KTC2500LP5B2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200ED320 KT 3X3200CO PLUG-IN LENGTH 2M

66

KTC2500LP5C1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200ED340 KT 3X3200CO PLUG-IN LENGTH 4M

66

KTC2500LP5C2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200ED420 KT 4X3200CO PLUG-IN LENGTH 2M

66

KTC2500LP7A1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200ED440 KT 4X3200CO PLUG-IN LENGTH 4M

66

KTC2500LP7A2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200ED520 KT 5X3200CO PLUG-IN LENGTH 2M

66

KTC2500LP7B1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200ED540 KT 5X3200CO PLUG-IN LENGTH 4M

66

KTC2500LP7B2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200ED720 KT 5X3200CO PLUG-IN LENGTH 2M

66

KTC2500LP7C1 KT 5X2500CO FLAT ELBOW N1

71

KTC3200ED740 KT 5X3200CO PLUG-IN LENGTH 4M

66

KTC2500LP7C2 KT 5X2500CO FLAT ELBOW N2

71

KTC3200EH320 KT 3X3200CO KH PLUG-IN LENGTH 2M

68

KTC2500SL31

KT 3X2500CO ISOLATOR UNIT INV

113

KTC3200EH340 KT 3X3200CO KH PLUG-IN LENGTH 4M

68

KTC2500SL41

KT 4X2500CO ISOLATOR UNIT INV

113

KTC3200EH420 KT 4X3200CO KH PLUG-IN LENGTH 2M

68

KTC2500SL51

KT 5X2500CO ISOLATOR UNIT INV

113

KTC3200EH440 KT 4X3200CO KH PLUG-IN LENGTH 4M

68

KTC2500SL71

KT 5X2500CO ISOLATOR UNIT INV

113

KTC3200EH520 KT 5X3200CO KH PLUG-IN LENGTH 2M

68

KTC2500TC3

KT 3X2500CO TEE ON EDGE

73

KTC3200EH540 KT 5X3200CO KH PLUG-IN LENGTH 4M

68

KTC2500TC4

KT 4X2500CO TEE ON EDGE

73

KTC3200EL31

KT 3X3200CO FEED UNIT EL N1

88

KTC2500TC5

KT 5X2500CO TEE ON EDGE

73

KTC3200EL32

KT 3X3200CO FEED UNIT EL N2

88

KTC2500TC7

KT 5X2500CO TEE ON EDGE

73

KTC3200EL33

KT 3X3200CO FEED UNIT EL N3

89

KTC2500TN410

KT 4X2500CO NEUTRAL PERMUTA

69

KTC3200EL34

KT 3X3200CO FEED UNIT EL N4

89

KTC2500TP410

KT 4X2500CO PHASES PERMUTA

69

KTC3200EL35

KT 3X3200CO FEED UNIT EL N5

90

KTC2500YA3

KT 3X2500CO JUNCTION BLOC

70

KTC3200EL41

KT 4X3200CO FEED UNIT EL N1

88

KTC2500YA4

KT 4X2500CO JUNCTION BLOC

70

KTC3200EL42

KT 4X3200CO FEED UNIT EL N2

88

KTC2500ZC31

KT 3X2500CO EDGEWISE ZED N1

74

KTC3200EL43

KT 4X3200CO FEED UNIT EL N3

89

KTC2500ZC32

KT 3X2500CO EDGEWISE ZED N2

74

KTC3200EL44

KT 4X3200CO FEED UNIT EL N4

89

KTC2500ZC41

KT 4X2500CO EDGEWISE ZED N1

74

KTC3200EL45

KT 4X3200CO FEED UNIT EL N5

90

KTC2500ZC42

KT 4X2500CO EDGEWISE ZED N2

74

KTC3200EL51

KT 5X3200CO FEED UNIT EL N1

88

KTC2500ZC51

KT 5X2500CO EDGEWISE ZED N1

74

KTC3200EL52

KT 5X3200CO FEED UNIT EL N2

88

KTC2500ZC52

KT 5X2500CO EDGEWISE ZED N2

74

KTC3200EL53

KT 5X3200CO FEED UNIT EL N3

89

KTC2500ZC71

KT 5X2500CO EDGEWISE ZED N1

74

KTC3200EL54

KT 5X3200CO FEED UNIT EL N4

89

KTC2500ZC72

KT 5X2500CO EDGEWISE ZED N2

74

KTC3200EL55

KT 5X3200CO FEED UNIT EL N5

90

KTC2500ZP3

KT 3X2500CO ZED ON FLAT

74

KTC3200EL71

KT 5X3200CO FEED UNIT EL N1

88

KTC2500ZP4

KT 4X2500CO ZED ON FLAT

74

KTC3200EL72

KT 5X3200CO FEED UNIT EL N2

88

KTC2500ZP5

KT 5X2500CO ZED ON FLAT

74

KTC3200EL73

KT 5X3200CO FEED UNIT EL N3

89

KTC2500ZP7

KT 5X2500CO ZED ON FLAT

74

KTC3200EL74

KT 5X3200CO FEED UNIT EL N4

89

KTC3200EL75

KT 5X3200CO FEED UNIT EL N5

90

KTC3200ER31

KT 3X3200CO FEED UNIT ER N1

80

KTC3200
KTC3200CP31

KT 3X3200CO FLAT EDGEWISE N1

75

KTC3200ER32

KT 3X3200CO FEED UNIT ER N2

80

KTC3200CP32

KT 3X3200CO FLAT EDGEWISE N2

75

KTC3200ER33

KT 3X3200CO FEED UNIT ER N3

81

KT 3X3200CO FEED UNIT ER N4

81

KTC3200CP33

KT 3X3200CO FLAT EDGEWISE N3

75

KTC3200ER34

KTC3200CP34

KT 3X3200CO FLAT EDGEWISE N4

75

KTC3200ER35

KT 3X3200CO FEED UNIT ER N5

82

KTC3200CP41

KT 4X3200CO FLAT EDGEWISE N1

75

KTC3200ER36

KT 3X3200CO FEED UNIT ER N6

82

KTC3200CP42

KT 4X3200CO FLAT EDGEWISE N2

75

KTC3200ER37

KT 3X3200CO FEED UNIT ER N7

83

KTC3200CP43

KT 4X3200CO FLAT EDGEWISE N3

75

KTC3200ER41

KT 4X3200CO FEED UNIT ER N1

80

KTC3200CP44

KT 4X3200CO FLAT EDGEWISE N4

75

KTC3200ER42

KT 4X3200CO FEED UNIT ER N2

80

KTC3200CP51

KT 5X3200CO FLAT EDGEWISE N1

75

KTC3200ER43

KT 4X3200CO FEED UNIT ER N3

81

KT 4X3200CO FEED UNIT ER N4

81

KTC3200CP52

KT 5X3200CO FLAT EDGEWISE N2

75

KTC3200ER44

KTC3200CP53

KT 5X3200CO FLAT EDGEWISE N3

75

KTC3200ER45

KT 4X3200CO FEED UNIT ER N5

82

KTC3200CP54

KT 5X3200CO FLAT EDGEWISE N4

75

KTC3200ER46

KT 4X3200CO FEED UNIT ER N6

82

75

KTC3200ER47

KT 4X3200CO FEED UNIT ER N7

83

KTC3200CP71

12

KT 5X3200CO FLAT EDGEWISE N1

version: 1.1

DEBU024EN_Index.indd

Cat. no.

Designations

Pages

Cat. no.

KTC3200ER51

KT 5X3200CO FEED UNIT ER N1

80

KTC3200LP5C1 KT 5X3200CO FLAT ELBOW N1

71

KTC3200ER52

KT 5X3200CO FEED UNIT ER N2

80

KTC3200LP5C2 KT 5X3200CO FLAT ELBOW N2

71

KTC3200ER53

KT 5X3200CO FEED UNIT ER N3

81

KTC3200LP7A1 KT 5X3200CO FLAT ELBOW N1

71

KTC3200ER54

KT 5X3200CO FEED UNIT ER N4

81

KTC3200LP7A2 KT 5X3200CO FLAT ELBOW N2

71

KTC3200ER55

KT 5X3200CO FEED UNIT ER N5

82

KTC3200LP7B1 KT 5X3200CO FLAT ELBOW N1

71

KTC3200ER56

KT 5X3200CO FEED UNIT ER N6

82

KTC3200LP7B2 KT 5X3200CO FLAT ELBOW N2

71

KTC3200ER57

KT 5X3200CO FEED UNIT ER N7

83

KTC3200LP7C1 KT 5X3200CO FLAT ELBOW N1

71

KTC3200ER71

KT 5X3200CO FEED UNIT ER N1

80

KTC3200LP7C2 KT 5X3200CO FLAT ELBOW N2

71

KTC3200ER72

KT 5X3200CO FEED UNIT ER N2

80

KTC3200SL31

KT 3X3200CO ISOLATOR UNIT NW

114

KTC3200ER73

KT 5X3200CO FEED UNIT ER N3

81

KTC3200SL41

KT 4X3200CO ISOLATOR UNIT NW

114

KTC3200ER74

KT 5X3200CO FEED UNIT ER N4

81

KTC3200SL51

KT 5X3200CO ISOLATOR UNIT NW

114

KTC3200ER75

KT 5X3200CO FEED UNIT ER N5

82

KTC3200SL71

KT 5X3200CO ISOLATOR UNIT NW

11

KTC3200ER76

KT 5X3200CO FEED UNIT ER N6

82

KTC3200TC3

KT 3X3200CO TEE ON EDGE

73

KTC3200ER77

KT 5X3200CO FEED UNIT ER N7

83

KTC3200TC4

KT 4X3200CO TEE ON EDGE

73

KTC3200ET31A KT 3X3200CO FEEDER LENGTH

66

KTC3200TC5

KT 5X3200CO TEE ON EDGE

73

KTC3200ET320

66

KTC3200TC7

KT 5X3200CO TEE ON EDGE

73

KTC3200ET32B KT 3X3200CO FEEDER LENGTH

66

KTC3200TN410

KT 4X3200CO NEUTRAL PERMUTA

69

KTC3200ET32C KT 3X3200CO FEEDER LENGTH

66

KTC3200TP410

KT 4X3200CO PHASES PERMUTA

69

KTC3200ET33D KT 3X3200CO FEEDER LENGTH

66

KTC3200YA3

KT 3X3200CO JUNCTION BLOC

70

KTC3200ET340

66

KTC3200YA4

KT 4X3200CO JUNCTION BLOC

70

KTC3200ET41A KT 4X3200CO FEEDER LENGTH

66

KTC3200ZC31

KT 3X3200CO EDGEWISE ZED N1

74

KTC3200ET420

66

KTC3200ZC32

KT 3X3200CO EDGEWISE ZED N2

74

KTC3200ET42B KT 4X3200CO FEEDER LENGTH

66

KTC3200ZC41

KT 4X3200CO EDGEWISE ZED N1

74

KTC3200ET42C KT 4X3200CO FEEDER LENGTH

66

KTC3200ZC42

KT 4X3200CO EDGEWISE ZED N2

74

KTC3200ET43D KT 4X3200CO FEEDER LENGTH

66

KTC3200ZC51

KT 5X3200CO EDGEWISE ZED N1

74

KTC3200ET440

66

KTC3200ZC52

KT 5X3200CO EDGEWISE ZED N2

74

KTC3200ET51A KT 5X3200CO FEEDER LENGTH

66

KTC3200ZC71

KT 5X3200CO EDGEWISE ZED N1

74

KTC3200ET520

66

KTC3200ZC72

KT 5X3200CO EDGEWISE ZED N2

74

KTC3200ET52B KT 5X3200CO FEEDER LENGTH

66

KTC3200ZP3

KT 3X3200CO ZED ON FLAT

74

KTC3200ET52C KT 5X3200CO FEEDER LENGTH

66

KTC3200ZP4

KT 4X3200CO ZED ON FLAT

74

KTC3200ET53D KT 5X3200CO FEEDER LENGTH

66

KTC3200ZP5

KT 5X3200CO ZED ON FLAT

74

KTC3200ET540

66

KTC3200ZP7

KT 5X3200CO ZED ON FLAT

74

KT 3X3200CO FEEDER LENGTH 2M

KT 3X3200CO FEEDER LENGTH 4M


KT 4X3200CO FEEDER LENGTH 2M

KT 4X3200CO FEEDER LENGTH 4M


KT 5X3200CO FEEDER LENGTH 2M

KT 5X3200CO FEEDER LENGTH 4M

KTC3200ET71A KT 5X3200CO FEEDER LENGTH

66

KTC3200ET720

KT 5X3200CO FEEDER LENGTH 2M

Designations

Pages

66

KTC4000

KTC3200ET72B KT 5X3200CO FEEDER LENGTH

66

KTC4000CP31

KT 3X4000CO FLAT EDGEWISE N1

75

KTC3200ET72C KT 5X3200CO FEEDER LENGTH

66

KTC4000CP32

KT 3X4000CO FLAT EDGEWISE N2

75

KTC3200ET73D KT 5X3200CO FEEDER LENGTH

66

KTC4000CP33

KT 3X4000CO FLAT EDGEWISE N3

75

KTC3200ET740

KT 5X3200CO FEEDER LENGTH 4M

66

KTC4000CP34

KT 3X4000CO FLAT EDGEWISE N4

75

KTC3200LC3A

KT 3X3200CO EDGEWISE ELBOW

72

KTC4000CP41

KT 4X4000CO FLAT EDGEWISE N1

75

KTC3200LC3B

KT 3X3200CO EDGEWISE ELBOW

72

KTC4000CP42

KT 4X4000CO FLAT EDGEWISE N2

75

KTC3200LC4A

KT 4X3200CO EDGEWISE ELBOW

72

KTC4000CP43

KT 4X4000CO FLAT EDGEWISE N3

75

KTC3200LC4B

KT 4X3200CO EDGEWISE ELBOW

72

KTC4000CP44

KT 4X4000CO FLAT EDGEWISE N4

75

KTC3200LC5A

KT 5X3200CO EDGEWISE ELBOW

72

KTC4000CP51

KT 5X4000CO FLAT EDGEWISE N1

75

KTC3200LC5B

KT 5X3200CO EDGEWISE ELBOW

72

KTC4000CP52

KT 5X4000CO FLAT EDGEWISE N2

75

KTC3200LC7A

KT 5X3200CO EDGEWISE ELBOW

72

KTC4000CP53

KT 5X4000CO FLAT EDGEWISE N3

75

KTC3200LC7B

KT 5X3200CO EDGEWISE ELBOW

72

KTC4000CP54

KT 5X4000CO FLAT EDGEWISE N4

75

KTC3200LP3A1 KT 3X3200CO FLAT ELBOW N1

71

KTC4000CP71

KT 5X4000CO FLAT EDGEWISE N1

75

KTC3200LP3A2 KT 3X3200CO FLAT ELBOW N2

71

KTC4000CP72

KT 5X4000CO FLAT EDGEWISE N2

75

KTC3200LP3B1 KT 3X3200CO FLAT ELBOW N1

71

KTC4000CP73

KT 5X4000CO FLAT EDGEWISE N3

75

KTC3200LP3B2 KT 3X3200CO FLAT ELBOW N2

71

KTC4000CP74

KT 5X4000CO FLAT EDGEWISE N4

75

KTC3200LP3C1 KT 3X3200CO FLAT ELBOW N1

71

KTC4000DB310 KT 3X4000CO EXPANSION UNIT

69

KTC3200LP3C1 KT 3X3200CO FLAT ELBOW N1

71

KTC4000DB410 KT 4X4000CO EXPANSION UNIT

69

KTC3200LP3C2 KT 3X3200CO FLAT ELBOW N2

71

KTC4000DB510 KT 5X4000CO EXPANSION UNIT

69

KTC3200LP4A1 KT 4X3200CO FLAT ELBOW N1

71

KTC4000DB710 KT 5X4000CO EXPANSION UNIT

69

KTC3200LP4A2 KT 4X3200CO FLAT ELBOW N2

71

KTC4000EB320 KT 3X4000CO BOLT ON LENGTH 2M

67

KTC3200LP4B1 KT 4X3200CO FLAT ELBOW N1

71

KTC4000EB340 KT 3X4000CO BOLT ON LENGTH 4M

67

KTC3200LP4B2 KT 4X3200CO FLAT ELBOW N2

71

KTC4000EB420 KT 4X4000CO BOLT ON LENGTH 2M

67

KTC3200LP4C1 KT 4X3200CO FLAT ELBOW N1

71

KTC4000EB440 KT 4X4000CO BOLT ON LENGTH 4M

67

KTC3200LP4C2 KT 4X3200CO FLAT ELBOW N2

71

KTC4000EB520 KT 5X4000CO BOLT ON LENGTH 2M

67

KTC3200LP5A1 KT 5X3200CO FLAT ELBOW N1

71

KTC4000EB540 KT 5X4000CO BOLT ON LENGTH 4M

67

KTC3200LP5A2 KT 5X3200CO FLAT ELBOW N2

71

KTC4000EB720 KT 5X4000CO BOLT ON LENGTH 2M

67

KTC3200LP5B1 KT 5X3200CO FLAT ELBOW N1

71

KTC4000EB740 KT 5X4000CO BOLT ON LENGTH 4M

67

KTC3200LP5B2 KT 5X3200CO FLAT ELBOW N2

71

KTC4000ED320 KT 3X4000CO PLUG-IN LENGTH 2M

66

DEBU024EN_Index.indd

version: 1.1

13

Cat. no.

Pages

Cat. no.

KTC4000ED340 KT 3X4000CO PLUG-IN LENGTH 4M

66

KTC4000ET32B KT 3X4000CO FEEDER LENGTH

66

KTC4000ED420 KT 4X4000CO PLUG-IN LENGTH 2M

66

KTC4000ET32C KT 3X4000CO FEEDER LENGTH

66

KTC4000ED440 KT 4X4000CO PLUG-IN LENGTH 4M

66

KTC4000ET33D KT 3X4000CO FEEDER LENGTH

66

KTC4000ED520 KT 5X4000CO PLUG-IN LENGTH 2M

66

KTC4000ET340

66

KTC4000ED540 KT 5X4000CO PLUG-IN LENGTH 4M

66

KTC4000ET41A KT 4X4000CO FEEDER LENGTH

66

KTC4000ED720 KT 5X4000CO PLUG-IN LENGTH 2M

66

KTC4000ET420

66

KTC4000ED740 KT 5X4000CO PLUG-IN LENGTH 4M

66

KTC4000ET42B KT 4X4000CO FEEDER LENGTH

66

KTC4000EH320 KT 3X4000CO KH PLUG-IN LENGTH 2M

68

KTC4000ET42C KT 4X4000CO FEEDER LENGTH

66

KTC4000EH340 KT 3X4000CO KH PLUG-IN LENGTH 4M

68

KTC4000ET43D KT 4X4000CO FEEDER LENGTH

66

KTC4000EH420 KT 4X4000CO KH PLUG-IN LENGTH 2M

68

KTC4000ET440

66

KTC4000EH440 KT 4X4000CO KH PLUG-IN LENGTH 4M

68

KTC4000ET51A KT 5X4000CO FEEDER LENGTH

66

KTC4000EH520 KT 5X4000CO KH PLUG-IN LENGTH 2M

68

KTC4000ET520

66

KTC4000EH540 KT 5X4000CO KH PLUG-IN LENGTH 4M

68

KTC4000ET52B KT 5X4000CO FEEDER LENGTH

66

KTC4000EL31

KT 3X4000CO FEED UNIT EL N1

88

KTC4000ET52C KT 5X4000CO FEEDER LENGTH

66

KTC4000EL32

KT 3X4000CO FEED UNIT EL N2

88

KTC4000ET53D KT 5X4000CO FEEDER LENGTH

66

KTC4000EL33

KT 3X4000CO FEED UNIT EL N3

89

KTC4000ET540

66

KTC4000EL34

KT 3X4000CO FEED UNIT EL N4

89

KTC4000ET71A KT 5X4000CO FEEDER LENGTH

66

KTC4000EL35

KT 3X4000CO FEED UNIT EL N5

90

KTC4000ET720

66

KTC4000EL41

KT 4X4000CO FEED UNIT EL N1

88

KTC4000ET72B KT 5X4000CO FEEDER LENGTH

66

KTC4000EL42

KT 4X4000CO FEED UNIT EL N2

88

KTC4000ET72C KT 5X4000CO FEEDER LENGTH

66

KTC4000EL43

KT 4X4000CO FEED UNIT EL N3

89

KTC4000ET73D KT 5X4000CO FEEDER LENGTH

66

KTC4000EL44

KT 4X4000CO FEED UNIT EL N4

89

KTC4000ET740

KT 5X4000CO FEEDER LENGTH 4M

66

KTC4000EL45

KT 4X4000CO FEED UNIT EL N5

90

KTC4000LC3A

KT 3X4000CO EDGEWISE ELBOW

72

KTC4000EL51

KT 5X4000CO FEED UNIT EL N1

88

KTC4000LC3B

KT 3X4000CO EDGEWISE ELBOW

72

KTC4000EL52

KT 5X4000CO FEED UNIT EL N2

88

KTC4000LC4A

KT 4X4000CO EDGEWISE ELBOW

72

KTC4000EL53

KT 5X4000CO FEED UNIT EL N3

89

KTC4000LC4B

KT 4X4000CO EDGEWISE ELBOW

72

KTC4000EL54

KT 5X4000CO FEED UNIT EL N4

89

KTC4000LC5A

KT 5X4000CO EDGEWISE ELBOW

72

KTC4000EL55

KT 5X4000CO FEED UNIT EL N5

90

KTC4000LC5B

KT 5X4000CO EDGEWISE ELBOW

72

KTC4000EL71

KT 5X4000CO FEED UNIT EL N1

88

KTC4000LC7A

KT 5X4000CO EDGEWISE ELBOW

72

KTC4000EL72

KT 5X4000CO FEED UNIT EL N2

88

KTC4000LC7B

KT 5X4000CO EDGEWISE ELBOW

72

KTC4000EL73

KT 5X4000CO FEED UNIT EL N3

89

KTC4000LP3A1 KT 3X4000CO FLAT ELBOW N1

71

KTC4000EL74

KT 5X4000CO FEED UNIT EL N4

89

KTC4000LP3A2 KT 3X4000CO FLAT ELBOW N2

71

KTC4000EL75

KT 5X4000CO FEED UNIT EL N5

90

KTC4000LP3B1 KT 3X4000CO FLAT ELBOW N1

71

KTC4000ER31

KT 3X4000CO FEED UNIT ER N1

80

KTC4000LP3B2 KT 3X4000CO FLAT ELBOW N2

71

KTC4000ER32

KT 3X4000CO FEED UNIT ER N2

80

KTC4000LP3C1 KT 3X4000CO FLAT ELBOW N1

71

KTC4000ER33

KT 3X4000CO FEED UNIT ER N3

81

KTC4000LP3C1 KT 3X4000CO FLAT ELBOW N1

71

KTC4000ER34

KT 3X4000CO FEED UNIT ER N4

81

KTC4000LP3C2 KT 3X4000CO FLAT ELBOW N2

71

KTC4000ER35

KT 3X4000CO FEED UNIT ER N5

82

KTC4000LP4A1 KT 4X4000CO FLAT ELBOW N1

71

KTC4000ER36

KT 3X4000CO FEED UNIT ER N6

82

KTC4000LP4A2 KT 4X4000CO FLAT ELBOW N2

71

KTC4000ER37

KT 3X4000CO FEED UNIT ER N7

83

KTC4000LP4B1 KT 4X4000CO FLAT ELBOW N1

71

KTC4000ER41

KT 4X4000CO FEED UNIT ER N1

80

KTC4000LP4B2 KT 4X4000CO FLAT ELBOW N2

71

KTC4000ER42

KT 4X4000CO FEED UNIT ER N2

80

KTC4000LP4C1 KT 4X4000CO FLAT ELBOW N1

71

KTC4000ER43

KT 4X4000CO FEED UNIT ER N3

81

KTC4000LP4C2 KT 4X4000CO FLAT ELBOW N2

71

KTC4000ER44

KT 4X4000CO FEED UNIT ER N4

81

KTC4000LP5A1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER45

KT 4X4000CO FEED UNIT ER N5

82

KTC4000LP5A2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER46

KT 4X4000CO FEED UNIT ER N6

82

KTC4000LP5B1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER47

KT 4X4000CO FEED UNIT ER N7

83

KTC4000LP5B2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER51

KT 5X4000CO FEED UNIT ER N1

80

KTC4000LP5C1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER52

KT 5X4000CO FEED UNIT ER N2

80

KTC4000LP5C2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER53

KT 5X4000CO FEED UNIT ER N3

81

KTC4000LP7A1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER54

KT 5X4000CO FEED UNIT ER N4

81

KTC4000LP7A2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER55

KT 5X4000CO FEED UNIT ER N5

82

KTC4000LP7B1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER56

KT 5X4000CO FEED UNIT ER N6

82

KTC4000LP7B2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER57

KT 5X4000CO FEED UNIT ER N7

83

KTC4000LP7C1 KT 5X4000CO FLAT ELBOW N1

71

KTC4000ER71

KT 5X4000CO FEED UNIT ER N1

80

KTC4000LP7C2 KT 5X4000CO FLAT ELBOW N2

71

KTC4000ER72

KT 5X4000CO FEED UNIT ER N2

80

KTC4000TC3

KT 3X4000CO TEE ON EDGE

73

KTC4000ER73

KT 5X4000CO FEED UNIT ER N3

81

KTC4000TC4

KT 4X4000CO TEE ON EDGE

73

KTC4000ER74

KT 5X4000CO FEED UNIT ER N4

81

KTC4000TC5

KT 5X4000CO TEE ON EDGE

73

KTC4000ER75

KT 5X4000CO FEED UNIT ER N5

82

KTC4000TC7

KT 5X4000CO TEE ON EDGE

73

KTC4000ER76

KT 5X4000CO FEED UNIT ER N6

82

KTC4000TN410

KT 4X4000CO NEUTRAL PERMUTA

69

KTC4000ER77

KT 5X4000CO FEED UNIT ER N7

83

KTC4000TP410

KT 4X4000CO PHASES PERMUTA

69

KTC4000ET31A KT 3X4000CO FEEDER LENGTH

66

KTC4000YA3

KT 3X4000CO JUNCTION BLOC

70

KTC4000ET320

66

KTC4000YA4

KT 4X4000CO JUNCTION BLOC

70

14

Designations

KT 3X4000CO FEEDER LENGTH 2M

Designations

Pages

KT 3X4000CO FEEDER LENGTH 4M


KT 4X4000CO FEEDER LENGTH 2M

KT 4X4000CO FEEDER LENGTH 4M


KT 5X4000CO FEEDER LENGTH 2M

KT 5X4000CO FEEDER LENGTH 4M


KT 5X4000CO FEEDER LENGTH 2M

version: 1.1

DEBU024EN_Index.indd

Cat. no.

Designations

Pages

Cat. no.

Designations

Pages

KTC4000ZC31

KT 3X4000CO EDGEWISE ZED N1

74

KTC5000EL43

KT 4X5000CO FEED UNIT EL N3

89

KTC4000ZC32

KT 3X4000CO EDGEWISE ZED N2

74

KTC5000EL44

KT 4X5000CO FEED UNIT EL N4

89

KTC4000ZC41

KT 4X4000CO EDGEWISE ZED N1

74

KTC5000EL45

KT 4X5000CO FEED UNIT EL N5

90

KTC4000ZC42

KT 4X4000CO EDGEWISE ZED N2

74

KTC5000EL51

KT 5X5000CO FEED UNIT EL N1

88

KTC4000ZC51

KT 5X4000CO EDGEWISE ZED N1

74

KTC5000EL52

KT 5X5000CO FEED UNIT EL N2

88

KTC4000ZC52

KT 5X4000CO EDGEWISE ZED N2

74

KTC5000EL53

KT 5X5000CO FEED UNIT EL N3

89

KTC4000ZC71

KT 5X4000CO EDGEWISE ZED N1

74

KTC5000EL54

KT 5X5000CO FEED UNIT EL N4

89

KTC4000ZC72

KT 5X4000CO EDGEWISE ZED N2

74

KTC5000EL55

KT 5X5000CO FEED UNIT EL N5

90

KTC4000ZP3

KT 3X4000CO ZED ON FLAT

74

KTC5000EL71

KT 5X5000CO FEED UNIT EL N1

88

KTC4000ZP4

KT 4X4000CO ZED ON FLAT

74

KTC5000EL72

KT 5X5000CO FEED UNIT EL N2

88

KTC4000ZP5

KT 5X4000CO ZED ON FLAT

74

KTC5000EL73

KT 5X5000CO FEED UNIT EL N3

89

KTC4000ZP7

KT 5X4000CO ZED ON FLAT

74

KTC5000EL74

KT 5X5000CO FEED UNIT EL N4

89

KTC5000EL75

KT 5X5000CO FEED UNIT EL N5

90

KTC5000ER31

KT 3X5000CO FEED UNIT ER N1

80

KTC5000
KTC5000CP31

KT 3X5000CO FLAT EDGEWISE N1

75

KTC5000ER32

KT 3X5000CO FEED UNIT ER N2

80

KTC5000CP32

KT 3X5000CO FLAT EDGEWISE N2

75

KTC5000ER33

KT 3X5000CO FEED UNIT ER N3

81

KTC5000CP33

KT 3X5000CO FLAT EDGEWISE N3

75

KTC5000ER34

KT 3X5000CO FEED UNIT ER N4

81

KT 3X5000CO FEED UNIT ER N5

82

KTC5000CP34

KT 3X5000CO FLAT EDGEWISE N4

75

KTC5000ER35

KTC5000CP41

KT 4X5000CO FLAT EDGEWISE N1

75

KTC5000ER36

KT 3X5000CO FEED UNIT ER N6

82

KTC5000CP42

KT 4X5000CO FLAT EDGEWISE N2

75

KTC5000ER37

KT 3X5000CO FEED UNIT ER N7

83

KT 4X5000CO FEED UNIT ER N1

80

KTC5000CP43

KT 4X5000CO FLAT EDGEWISE N3

75

KTC5000ER41

KTC5000CP44

KT 4X5000CO FLAT EDGEWISE N4

75

KTC5000ER42

KT 4X5000CO FEED UNIT ER N2

80

KTC5000CP51

KT 5X5000CO FLAT EDGEWISE N1

75

KTC5000ER43

KT 4X5000CO FEED UNIT ER N3

81

KT 4X5000CO FEED UNIT ER N4

81

KTC5000CP52

KT 5X5000CO FLAT EDGEWISE N2

75

KTC5000ER44

KTC5000CP53

KT 5X5000CO FLAT EDGEWISE N3

75

KTC5000ER45

KT 4X5000CO FEED UNIT ER N5

82

KTC5000CP54

KT 5X5000CO FLAT EDGEWISE N4

75

KTC5000ER46

KT 4X5000CO FEED UNIT ER N6

82

KTC5000CP71

KT 5X5000CO FLAT EDGEWISE N1

75

KTC5000ER47

KT 4X5000CO FEED UNIT ER N7

83

KTC5000CP72

KT 5X5000CO FLAT EDGEWISE N2

75

KTC5000ER51

KT 5X5000CO FEED UNIT ER N1

80

KTC5000CP73

KT 5X5000CO FLAT EDGEWISE N3

75

KTC5000ER52

KT 5X5000CO FEED UNIT ER N2

80

KTC5000CP74

KT 5X5000CO FLAT EDGEWISE N4

75

KTC5000ER53

KT 5X5000CO FEED UNIT ER N3

81

KTC5000DB310 KT 3X5000CO EXPANSION UNIT

69

KTC5000ER54

KT 5X5000CO FEED UNIT ER N4

81

KTC5000DB410 KT 4X5000CO EXPANSION UNIT

69

KTC5000ER55

KT 5X5000CO FEED UNIT ER N5

82

KTC5000DB510 KT5X5000CO EXPANSION UNIT

69

KTC5000ER56

KT 5X5000CO FEED UNIT ER N6

82

KTC5000DB710 KT5X5000CO EXPANSION UNIT

69

KTC5000ER57

KT 5X5000CO FEED UNIT ER N7

83

KTC5000EB320 KT 3X5000CO BOLT ON LENGTH 2M

67

KTC5000ER71

KT 5X5000CO FEED UNIT ER N1

80

KTC5000EB340 KT 3X5000CO BOLT ON LENGTH 4M

67

KTC5000ER72

KT 5X5000CO FEED UNIT ER N2

80

KTC5000EB420 KT 4X5000CO BOLT ON LENGTH 2M

67

KTC5000ER73

KT 5X5000CO FEED UNIT ER N3

81

KTC5000EB440 KT 4X5000CO BOLT ON LENGTH 4M

67

KTC5000ER74

KT 5X5000CO FEED UNIT ER N4

81

KTC5000EB520 KT 5X5000CO BOLT ON LENGTH 2M

67

KTC5000ER75

KT 5X5000CO FEED UNIT ER N5

82

KTC5000EB540 KT 5X5000CO BOLT ON LENGTH 4M

67

KTC5000ER76

KT 5X5000CO FEED UNIT ER N6

82

KTC5000EB720 KT 5X5000CO BOLT ON LENGTH 2M

67

KTC5000ER77

KT 5X5000CO FEED UNIT ER N7

83

KTC5000EB740 KT 5X5000CO BOLT ON LENGTH 4M

67

KTC5000ET31A KT 3X5000CO FEEDER LENGTH

66

KTC5000ED320 KT 3X5000CO PLUG-IN LENGTH 2M

66

KTC5000ET320

66

KTC5000ED340 KT 3X5000CO PLUG-IN LENGTH 4M

66

KTC5000ET32B KT 3X5000CO FEEDER LENGTH

66

KTC5000ED420 KT 4X5000CO PLUG-IN LENGTH 2M

66

KTC5000ET32C KT 3X5000CO FEEDER LENGTH

66

KTC5000ED440 KT 4X5000CO PLUG-IN LENGTH 4M

66

KTC5000ET33D KT 3X5000CO FEEDER LENGTH

66

KTC5000ED520 KT 5X5000CO PLUG-IN LENGTH 2M

66

KTC5000ET340

66

KTC5000ED540 KT 5X5000CO PLUG-IN LENGTH 4M

66

KTC5000ET41A KT 4X5000CO FEEDER LENGTH

66

KTC5000ED720 KT 5X5000CO PLUG-IN LENGTH 2M

66

KTC5000ET420

66

KTC5000ED740 KT 5X5000CO PLUG-IN LENGTH 4M

66

KTC5000ET42B KT 4X5000CO FEEDER LENGTH

66

KTC5000EH320 KT 3X5000CO KH PLUG-IN LENGTH 2M

68

KTC5000ET42C KT 4X5000CO FEEDER LENGTH

66

KTC5000EH340 KT 3X5000CO KH PLUG-IN LENGTH 4M

68

KTC5000ET43D KT 4X5000CO FEEDER LENGTH

66

KTC5000EH420 KT 4X5000CO KH PLUG-IN LENGTH 2M

68

KTC5000ET440

66

KTC5000EH440 KT 4X5000CO KH PLUG-IN LENGTH 4M

68

KTC5000ET51A KT 5X5000CO FEEDER LENGTH

66

KTC5000EH520 KT 5X5000CO KH PLUG-IN LENGTH 2M

68

KTC5000ET520

66

KTC5000EH540 KT 5X5000CO KH PLUG-IN LENGTH 4M

68

KTC5000ET52B KT 5X5000CO FEEDER LENGTH

66

KTC5000EL31

KT 3X5000CO FEED UNIT EL N1

88

KTC5000ET52C KT 5X5000CO FEEDER LENGTH

66

KTC5000EL32

KT 3X5000CO FEED UNIT EL N2

88

KTC5000ET53D KT 5X5000CO FEEDER LENGTH

66

KTC5000EL33

KT 3X5000CO FEED UNIT EL N3

89

KTC5000ET540

66
66
66

KT 3X5000CO FEEDER LENGTH 2M

KT 3X5000CO FEEDER LENGTH 4M


KT 4X5000CO FEEDER LENGTH 2M

KT 4X5000CO FEEDER LENGTH 4M


KT 5X5000CO FEEDER LENGTH 2M

KT 5X5000CO FEEDER LENGTH 4M

KTC5000EL34

KT 3X5000CO FEED UNIT EL N4

89

KTC5000ET71A KT 5X5000CO FEEDER LENGTH

KTC5000EL35

KT 3X5000CO FEED UNIT EL N5

90

KTC5000ET720

KTC5000EL41

KT 4X5000CO FEED UNIT EL N1

88

KTC5000ET72B KT 5X5000CO FEEDER LENGTH

66

88

KTC5000ET72C KT 5X5000CO FEEDER LENGTH

66

KTC5000EL42

KT 4X5000CO FEED UNIT EL N2

DEBU024EN_Index.indd

KT 5X5000CO FEEDER LENGTH 2M

version: 1.1

15

Cat. no.

Designations

Pages

KTC5000ET73D KT 5X5000CO FEEDER LENGTH

66

KTC5000ET740

KT 5X5000CO FEEDER LENGTH 4M

66

KTC5000LC3A

KT 3X5000CO EDGEWISE ELBOW

72

KTC5000LC3B

KT 3X5000CO EDGEWISE ELBOW

72

KTC5000LC4A

KT 4X5000CO EDGEWISE ELBOW

72

KTC5000LC4B

KT 4X5000CO EDGEWISE ELBOW

72

KTC5000LC5A

KT 5X5000CO EDGEWISE ELBOW

72

KTC5000LC5B

KT 5X5000CO EDGEWISE ELBOW

72

KTC5000LC7A

KT 5X5000CO EDGEWISE ELBOW

72

KTC5000LC7B

KT 5X5000CO EDGEWISE ELBOW

72

KTC5000LP3A1 KT 3X5000CO FLAT ELBOW N1

71

KTC5000LP3A2 KT 3X5000CO FLAT ELBOW N2

71

KTC5000LP3B1 KT 3X5000CO FLAT ELBOW N1

71

KTC5000LP3B2 KT 3X5000CO FLAT ELBOW N2

71

KTC5000LP3C1 KT 3X5000CO FLAT ELBOW N1

71

KTC5000LP3C1 KT 3X5000CO FLAT ELBOW N1

71

KTC5000LP3C2 KT 3X5000CO FLAT ELBOW N2

71

KTC5000LP4A1 KT 4X5000CO FLAT ELBOW N1

71

KTC5000LP4A2 KT 4X5000CO FLAT ELBOW N2

71

KTC5000LP4B1 KT 4X5000CO FLAT ELBOW N1

71

KTC5000LP4B2 KT 4X5000CO FLAT ELBOW N2

71

KTC5000LP4C1 KT 4X5000CO FLAT ELBOW N1

71

KTC5000LP4C2 KT 4X5000CO FLAT ELBOW N2

71

KTC5000LP5A1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP5A2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000LP5B1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP5B2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000LP5C1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP5C2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000LP7A1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP7A2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000LP7B1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP7B2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000LP7C1 KT 5X5000CO FLAT ELBOW N1

71

KTC5000LP7C2 KT 5X5000CO FLAT ELBOW N2

71

KTC5000TC3

KT 3X5000CO TEE ON EDGE

73

KTC5000TC4

KT 4X5000CO TEE ON EDGE

73

KTC5000TC5

KT 5X5000CO TEE ON EDGE

73

KTC5000TC7

KT 5X5000CO TEE ON EDGE

73

KTC5000TN410

KT 4X5000CO NEUTRAL PERMUTA

69

KTC5000TP410

KT 4X5000CO PHASES PERMUTA

69

KTC5000YA3

KT 3X5000CO JUNCTION BLOC

70

KTC5000YA4

KT 4X5000CO JUNCTION BLOC

70

KTC5000ZC31

KT 3X5000CO EDGEWISE ZED N 1

74

KTC5000ZC32

KT 3X5000CO EDGEWISE ZED N2

74

KTC5000ZC41

KT 4X5000CO EDGEWISE ZED N1

74

KTC5000ZC42

KT 4X5000CO EDGEWISE ZED N2

74

KTC5000ZC51

KT 5X5000CO EDGEWISE ZED N1

74

KTC5000ZC52

KT 5X5000CO EDGEWISE ZED N2

74

KTC5000ZC71

KT 5X5000CO EDGEWISE ZED N1

74

KTC5000ZC72

KT 5X5000CO EDGEWISE ZED N2

74

KTC5000ZP3

KT 3X5000CO ZED ON FLAT

74

KTC5000ZP4

KT 4X5000CO ZED ON FLAT

74

KTC5000ZP5

KT 5X5000CO ZED ON FLAT

74

KTC5000ZP7

KT 5X5000CO ZED ON FLAT

74

16

Cat. no.

Designations

version: 1.1

Pages

DEBU024EN_Index.indd

Canalis is evolving
to meet your needs

Introduction

PD202382-m_r

Canalis on its second world tour


b
b
b
b
b

To better meet your needs, Canalis extends its system solutions.


New low and medium power busbar trunking products.
Pre-equipped luminaires.
Strip lighting.
Specially designed cable trays.

A total coordination with the


Schneider Electric system
Canalis is now part of a comprehensive offering of Schneider Electric products
designed to operate together. This concept covers all low and medium
voltage electrical distribution components. The result is an optimised electrical
installation with even higher performance through full electrical, mechanical and
communication compatibility.
With the new Canalis range, you get a complete, tested distribution solution
that complies with standards. It is perfectly suited to traditional applications
(factories, warehouses, etc.) and to the distribution of electrical power from the
incoming transformer on through to all types of loads in offices, commercial
premises, laboratories, etc.

More than 50,000 km of Canalis busbar trunking has been


sold around the world.

Canalis KT is changing to provide you


with

PD202088-104_r

b more flexibility
b ease of connection with the plug and play transformer and switchboard
connections
b more assistance. Our teams will assist you throughout your project.

Canalis moves forward without changing


the way you work
The new Canalis range is fully compatible with the existing range.
An existing installation can be upgraded without any problem.

K9CE01010.indd

version: 1.1

17

For each distribution system


its own Canalis

DD205848

Distribution systems

Schneider Electric offers different distribution systems to fit your operating needs.

Centralised distribution
b
v
v
v
v
v
b
v
v
v

For all continuous processes:


cement plants
oil and gas
petrochemicals
steel
paper, etc.
Centralised distribution offers:
continuity of service
combined distribution of power, control and monitoring circuits
supervision, etc.

DD205849

Our solutions:
b Prisma Plus and Okken switchboards.

Decentralised distribution
b
v
v
v
v
v
v
v
b
v
v
v
v

For manufacturing industries:


mechanical
textiles
lumber
injection moulding
electronics
pharmaceuticals
livestock, etc.
Decentralised distribution lets you:
design installations without layout details
upgrade without shutting down production
get systems up and running sooner thanks to faster installation
generate savings depending on the number of loads.

DD205850

Our solutions:
b Prisma Plus switchboards
b Canalis busbar trunking.

Combined distribution
Where the advantages of both centralised and decentralised distribution are
required.
b Commercial and service buildings:
v offices
v stores
v hospitals
v exhibition halls, etc.
b Infrastructures:
v airports
v telecommunications
v internet data centres
v tunnels, etc.
b Industrial facilities:
v pharmaceuticals
v food processing, etc.
Our solutions:
b Prisma Plus and Okken switchboards
b Canalis busbar trunking.

18

version: 1.1

K9CE01020.indd

Electrical power available at all points,throughout the


installation.

The Canalis decentralised


distribution concept
PD202427_r

Exclusive features of the Schneider Electric system

Total coordination of the Schneider Electric system provides maximum safety of life
and property, continuity of service, upgradeability and ease of installation.
Total coordination is made easy by the tables in the Selection Guide. They help
you chose the right combination of circuit breakers and busbar trunking.
Product characteristics are checked by calculations and tests carried out in our
laboratories.

A competitive installation.

Simplicity, upgradeability, safety and continuity of service and operation.

PD202383_r

DD205658

Savings start with installation


With tap-off points every 3 metres, Canalis busbar trunking reduces installation
costs.
Given the low cost of adding new circuits, savings increase as the number of loads
increases, a natural consequence of the growth of your business.

Upgradeable during operation


In decentralised distribution, evolving operating requirements and costs are
integrated right from the start.
b The addition, relocation or replacement of load equipment can be carried out
quickly, without de-energising the supply trunking or shutting down operation.
b The cost of making such changes is greatly reduced:
v loads are located close to supply points
v tap-off points are always available
v tap-units can be reused or new ones added quickly for load relocation or
replacement needs.

Reusable in the event of major changes


When making major modifications to your installation, the existing trunking can be
easily dismantled and reused.

K9CE01020.indd

version: 1.1

19

Canalis, in total harmony with


the environment

DD205675

Safety of life and property

With Canalis, no toxic emission in case of fire

The busbar trunking has a low combustible load. Its construction uses very little
consumable material and is halogen free.
In the event of a fire, the busbar trunking does not emit any gas or toxic smoke.
The busbar trunking helps prevent the propagation of a fire through partition walls
and floors.
Halogen-sensitive applications
b Public buildings (infrastructures, hospitals, schools, etc.).
b Buildings with evacuation difficulties (high-rises, ships, etc.) and service-activity
buildings.
b Sensitive processes (production of electronic components, etc.).

Canalis contains no PVCs

Example:
Consequences of a fire in a 100 m office with
electrical distribution by cables.
200 kg of cables (i.e. 20 kg of PVC) produces:
b 4400 m3 of smoke
b 7.5 m3 of hydrochloric acid
b 3.7 kg of corroded steel.

DD205674

Health

When PVCs burn, they produce large amounts of smoke that can be a serious
safety hazard.
b Reduced visibility:
v risk of panic
v complicates rescue work
b Smoke toxicity:
v hydrogen chloride gas (highly toxic)
v carbon monoxide (danger of asphyxiation).

Canalis reduces the risk of exposure to electromagnetic fields


According to the WHO (World Health Organisation), exposure to electromagnetic
fields can be a health hazard starting at levels as low as 0.2 micro-Teslas and
could represent a long-term risk of cancer. Some countries have created standards
that stipulate limits (e.g. 0.2 T at 1 metre in Sweden).
All electrical conductors generate magnetic fields proportional to the distance
between them. The design of Canalis busbar trunking with tightly spaced
conductors in a metal enclosure helps to considerably reduce radiated
electromagnetic fields.
The electromagnetic field characteristics of Canalis busbar trunking are welldefined and measurements show that they are far below potentially dangerous
levels.
You will find the magnetic induction values of our products on the Characteristics
pages.

20

version: 1.1

K9CE01030.indd

DD205673

Environment

Canalis is fully recyclable

b Canalis busbar trunking can be reused.


Canalis busbar trunking is designed for a long service life and can easily be
dismantled, cleaned and reused.
b All packaging materials can be recycled (cardboard or recyclable polyethylene
film).
b All Canalis products are designed for safe end-of-life recycling. PVC, on the
other hand, requires neutralisation of the hydrochloric acid produced using lime
and generates dioxins that are extremely toxic.

Canalis helps conserve natural resources

Example:
1 kg of PVC generates 1 kg of waste.

Conservation of natural
resources

The depletion of raw materials (copper, plastics, etc.) is one of our ongoing
concerns.
For this reason, we have optimised the used of all materials used to make our
busbar trunking.
b Reduction of dangerous or polluting materials. We design our products to meet
future European directives.
b Reduction in the weight of insulating materials.
b Reduction in the use of plastics for improved fire performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction
(lower calorific value).

Canalis reduces your line losses by 20 %


Canalis divides your consumption of plastic by a factor of
four

The cost of an electrical installation includes the initial investment for the
equipment and its installation, the cost of maintenance and the cost of energy
losses during operation.
The concept of decentralised distribution is a way to merge all the circuits in one
and thus to reduce to the maximum the low cross-section lengths and the weight of
insulating materials.

DD206048

Example:
34 m of Canalis KS 250 A trunking equipped with fourteen 4-pole 25 A feeders.

K9CE01030.indd

version: 1.1

21

PD202384_r

From the transport to the


distribution, Canalis is the core
of your installation

22

version: 1.1

K9CE01040.indd

K9CE01040.indd

version: 1.1

23

Canalis KT, a display of


advantages

b The compact size of Canalis KT means it takes up very little space in the
building:
v used as a rising main, it takes up only a minimum of space
v used for horizontal distribution, it fits easily into the buildings structure (false
floors, false ceilings, service shafts, etc).

A compact solution

b Changes in direction have been designed to optimise the space taken up,
contrary to an equivalent installation using cables which requires large bending
radii.

DD210860

b Tap-off units, complete with protective devices, are fitted along the entire length
of the busbar trunking thus reducing the floor area taken up by the electrical
distribution switchboards.

b The design study is easy to perform as it does not require a detailed layout of
each load. Equipment choice is pre-determined and optimised.

A simple and economical


system

b Installing the busbar trunking requires 2 or 3 people only, for a time equivalent
to that for installing cableways. The time normally needed for laying cables is
therefore saved.
b Connection to the MV/LV substation is made using a quick fitting joint block. The
tap-off units can be prepared in the workshop thus reducing on-site time. Their
connection to the busbar trunking is done in a single plugging-on operation.
b Installing busbar trunking lengths can be done as and when building work
progresses, thus optimising on-site work and allowing possible unexpected events
to be anticipated in advance.

PD202385_r

b It is also important to note that busbar trunking is a factory tested solution,


meaning the time needed for inspecting connections is reduced (visual inspection
of tightening torque).

24

version: 1.1

K9CE02010.indd

Complete safety

b Busbar trunking temperature rise and short-circuit withstand are known and
independent of the installation. Coordination of the Schneider Electric system
results in complete control of the electrical network.
b Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter
5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbar
trunking. Paralleling many cables leads to uneven distribution of currents and the
risk of abnormal temperature rise.

PD202386_r

b The busbar trunking and tap-off units are designed to guarantee the safety of
personnel and equipment:
v plug-on connections to silver-plated copper bars
v bolted connections with tightening torque guaranteed by torque nuts
v foolproof system to avoid the risk of assembly errors
v IP55 certified splash and dust protection
v sprinkler resistance test in compliance with Volkswagen specifications (valid
only for top-mounted units).
v access to live parts have IPxxD protection (1 mm wire diameter).
Its metal enclosure and high protection degree protect the busbar trunking from all
external aggressions (corrosion, rodents, etc).
b Seismic certification to IEC 60980, Richter scale >7 and MSK 64 severity 9.

Operating continuity

When working on the electrical installation, the busbar trunking provides immediate
readability of the electrical circuit thus allowing the appropriate zone to be quickly
identified.
Tap-off units can be plugged-on and off without the need for a shutdown; service
continuity is thus irreproachable.
The quality of the electrical contacts guarantees maintenance free operating
continuity.

PD202229-68_r

A large range of tap-off units

Canalis KS tap-off units are fully compatible with Canalis KT:


b they cover all your requirements:
v Canalis KS tap-off units: 63 to 400 A
v Canalis KT tap-off units: 400 to 1250 A
b they offer circuit breaker or fuse protection.
This offer includes tap-off units that can be fitted with the Transparent Ready
system:
v they monitor your installation to avoid overloads, thus ensuring service continuity
v they provide metering to allow accurate management of your electrical
distribution network (allocation of costs to each consumer).

K9CE02010.indd

version: 1.1

25

Canalis KT is adapted for all


types of building

Key points

Office and hospital buildings


PD202391_r

b Fire barrier.
b Halogen free.
b Small size.

PD202389_r

PD202388_r

b Operating continuity.

Key points

Shopping centres, airports


and exhibition centres

b Halogen free.

PD202387_r

b Distribution and metering.


b Able to be evolved.

PD202390_r

b Sprinklers.

26

version: 1.1

K9CE02020.indd

Key points

Car industry and


industrial buildings

b Operating continuity.

PD395077-68_r

b Able to be evolved.
b Low voltage drops.

PD202393_r

PD202392_r

b Network readability.

Key points

Internet Data Centers


109405_r

b Operating continuity.
b High tap-off density.
b Able to be evolved.

PD202395_r

PD202394_r

b Network compactness and readability.

K9CE02020.indd

version: 1.1

27

Canalis, the reference all around


the world

Tertiary
Name

Lighting and low current

Medium current

High
current

KDP

KN

KT

KBA

KBB

KS

Country

Offices
PD202244_r

Air France (headquarters)

Axa
Chamber of Commerce

b
b

Telefnica

Trade Center
Tour du RDC

Turning Torso

Vodafone

Sweden

Luxembourg
Germany

b
b

Germany
France

Commerz Bank
b

Lexel

France

Allianz

Spain

Spain

Tunisia
Sweden
New Zealand

Internet Data Center


PD202245_r

Banco Commercial Portugus

Colt

Digiplex

Portugal

France
Sweden

IBM

Spain, Italy

MCI-Worldcom

Italy, United Kingdom

Tunisia

Hotels and restaurants


PD202246_r

Hyatt
Mc Donalds

France

Soldeo Andorra Hotel

Spain

Sweden

Hospitals
PD202247_r

Children Clinic
Brussels University Hospital

Belgium

Derby Hospital

United Kingdom

Oran Hospital

Algeria

St Joseph Hospital

France

Stockholm Hospital

Sweden

Val de Grce Hospital

Michalon Hospital

Manussia Hospital

France
b

France
Egypt

Supermarkets and hypermarkets


PD202248_r

Alcampo
Auchan

b
b

B&Q
Carrefour

Coop

Fnac

Ikea
Mark & Spencer

b
b

Spain

World
United Kingdom

World
Italy

Spain, France

China, Spain, France,


Sweden
Belgium, Spain,
United Kingdom

ToysR Us

28

version: 1.1

Spain

K9CE02030.indd

Industry
Name

Lighting and low current

Medium current

KDP

KBA

KBB

KN

KS

High
current
KT

Country

Car industry
PD202249_r

BMW
Citron

Daewo

Italy
b

Dacia

Iveco

Peugeot

China, Spain, France


South Korea

b
b

Romania

Spain, Italy

China, Spain, France

Nissan

Spain

Renault

Spain, France, Czech


Republic

Seat

Spain

Valo

Volkswagen

China, France, Italy,


Poland
Spain, Germany

Other industries
Aerospace industry
Airbus

Italy

Spain, Italy, Belgium

World

Food-processing industry
Coca-Cola

Danone

Pasquier

France

Livestock production farms and greenhouses


Favier henhouse

France

Greenhouse

Netherlands

Ceramic industry
Esmalglas ceramic

Legrand

Rolex

Intel

ST Micro-electronique

Spain

Electricity
France, Turkey

Watch-making
b

Switzerland

Microelectronics
b

Irelande
b

France

Lead industry and water treatment


Grundfos

China

China

Netherlands

Sweden

Spain

Industrial technology
Bosch

Telephony
Phillips
Nokia

Louis Vuitton

Delta

Textile industry

K9CE02030.indd

version: 1.1

Israel

29

Canalis, the reference all around


the world

Infrastructure
Name

Lighting and low current

Medium current

High
current

KDP

KBA

KBB

KN

KS

KT

Country

Airports
PD202250_r

Paris Airport
Cairo Airport
Heathrow Airport

Hong-Kong Airport
Landvetter Airport
Arlanda

United Kingdom

China
Sweden

b
b

Satelite Barajas

France
Egypt

Sweden

Spain

PD202251_r

Marine
Chantier de lAtlantique

France

Meyerwerft

Germany

Undergrounds
PD202252_r

Guanghzou Underground
Madrid Underground

China

London Underground

United Kingdom

b
b

Singapore Underground

Spain

Singapore

Egypt

Other infrastructures
Alexandria Library
Centre international dexposition
de Suzhou

30

b
b

China

CERN

Switzerland

Stade de France

France

version: 1.1

K9CE02030.indd

Canalis tools and services

Technical files

The technical files have been compiled from completed contracts and provide
answers to questions concerning the installation of Canalis busbar trunking in
specific business sectors.

In data centers
Reference:
ART 37222
DESBS001EN

In exhibition centres
Reference:
ART 65946
KD0C00CTAFEEN

In shopping centres
Reference:
Available in your sales office.

In electronics factories
Reference:
ART 65944
KD0C00CTAFEEN

In tiles factories
Reference:
DEBU005EN

In car plants
Reference:
Available in your sales office.

In livestock buildings
Reference:
DESWED105010EN

In greenhouses
Reference:
ART 808260
DESWED105013EN

In logistic centres
Reference:
ART 807993
DESWED105011EN

In cruise ships
Reference:
DESWED105014EN

In garages
Reference:
DESWED103004EN

Find a large range of Cahier Technique publications on the Schneider Electric


web site: www.schneider-electric.com.

K9CE02040.indd

version: 1.1

31

Canalis tools and services

Our teams are available to provide customers with technical assistance throughout
the installation of their projects.

PD202396_r

Work-out your
solution together

b
v
v
v
v

Design of electrical distribution architectures:


design of decentralised transport and distribution systems
technical and financial optimisation of busbar trunking design projects
transformer/switchboard link
installation coordination and discrimination.

b
v
v
v

Full installation drawings:


3D Autocad drawings with corresponding parts lists
2D drawing with dimensions
detailed connection drawings.

b Site supervision and commissioning assistance.

DD210862

b Training for designers and contractors.

Project
launch

Technical
support
CanBrass
drawing

After-sales
service
Autocad
drawing
On-site
instruction
and
installation
Production
Project
management

32

version: 1.1

K9CE02040.indd

Schneider Electric offers a comprehensive design and costing software.


The CanBrass software, edited by Schneider Electric, was developed to help you
design and cost Canalis busbar trunking runs.

PD202374_r

CanBrass gives you all the


help you need

CanBrass, a comprehensive tool


The CanBrass software allows you to quickly design the best layout for your
project.
It allows:
b the material needed to be easily chosen
b a list of catalogue numbers and their exact quantities to be defined
b a comprehensive quote that includes material and labour.
b There are 2 options:
b linear metre costing
b graphical costing.

Design guide

Linear metre costing

PD202375_r

The user enters the following parameters:


b for the power run: rating, polarity, protection degree
b for each feeder: number of machines, rating and protection
b overall run length, number of change-of-direction sections and the connection
type.

PD202376_r

Enter Canalis run characteristics.

Switchboard access estimation of material and labour costs.

K9CE02040.indd

version: 1.1

33

Canalis tools and services

Graphical costing

PD202377_r

Simply create a 3D drawing of the busbar trunking using appropriate dialogue


boxes.
Enter the following:
b rating
b polarity
b connection types.

Definition of catalogue numbers

PD202378_r

The software gives an optimum breakdown of the project and provides a bill of
materials: catalogue number, quantity, price.
The software can also generate 2D or 3D drawings with dimensions.

Breakdown of the run by product function.

Quote

PD202379_r

The CanBrass software can generate a comprehensive customised quote (quantity,


catalogue number, unit price, total net price and installation time).

34

version: 1.1

K9CE02040.indd

Contents

Presentation and description

Index
Introduction

3
17

Presentation

36

Panorama of Canalis range

36

Lighting distribution 36
Power distribution 38

Canalis KTC from 800 to 4000 A

42

For horizontal transport and distribution


For distribution to different levels

42
44

Tap-off units from 25 to 1250 A

45

Description

46

General

46

Run sections

48

Other run sections Disconnectors and run protective devices

49

Change of direction sections

50

Connection sections

51

Connection accessories

56

Supports and fixings

58

Tap-off units

59

Plug-on tap-off units for circuit breakers

60

Plug-on tap-off units for fuses

61

Fixed tap-off units for circuit breakers

62

Catalogue numbers and dimensions


Design guide
Design and installation guide
Recommandations

DEBU024EN_Presentation.indd

version: 1.1

63
133
171
231

35

Presentation

Panorama of Canalis range


Lighting distribution

Canalis KTC

Canalis KDP
PD202216_r

Range

Run components
IP55
1
20 A
1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm
24 and 192 meters
0,70 meter

Degree of protection
Number of circuits
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points

PD202225_r

KDP-KBA-KBB tap-off units

Rating

10 and 16 A

Option
-

36

version: 1.1

K9CE11000.indd

Canalis KBB
PD202219_r

PD202217_r

Canalis KBA

IP55
1 or 2
25 and 40 A
500 and 1000 mm
2 and 3 meters
Galvanised steel
5 meters

PD202225_r

PD202225_r

IP55
1
25 and 40 A
500 - 1000 and 1500 mm
2 and 3 meters
Galvanised steel
3 meters

10 and 16 A

10 and 16 A

White RAL 9010


Bus conductor
-

White RAL 9010


Bus conductor
Clean earth

K9CE11000.indd

version: 1.1

37

Panorama of Canalis range

Presentation

Power distribution
Canalis KTC

Canalis KN
PD202221_r

Range

Run components
IP55
3L + N + PE
40, 63, 100 and 160 A
500 - 1000 or 3000 mm
3 meters
White RAL 9001
3 meters

Degree of protection
Polarity
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points

PD202227_r

Tap-off units

Rating

Plug-in
Bolt-on

16 to 63 A

Option
Remote control conductor

38

version: 1.1

K9CE11000.indd

Canalis KS, rising mains


PD202223_r

PD202222_r

Canalis KS

IP55
3L + N + PE
100, 160, 250, 400, 500, 630, 800 and 1000 A
500 mm
Defined by the floor pitch
White RAL 9001
Defined by the floor pitch

PD202228_r

PD202228_r

IP55
3L + N + PE
100, 160, 250, 400, 500, 630, 800 and 1000 A
1000 mm on each face
3 and 5 meters
White RAL 9001
3 meters

25 to 400 A

25 to 400 A

K9CE11000.indd

version: 1.1

39

Panorama of Canalis range

Presentation

Power distribution
Canalis KTC

Canalis KT
PD202088-74_r

Range

Run components
IP55
3L + PE ; 3L + N +PE ; 3L + N + oversized PE
800, 1000, 1250, 13A
500 - 1000 mm
2 and 4 meters
White RAL 9001
3 meters

Degree of protection
Polarity
Rating
Tap-off intervals
Standard lengths
Finish
Maximum distance between fixing points

PD202229_r

Tap-off units

Rating

Plug-in
Bolt-on

25 to 400 A
400 to 1250 A

Option
-

40

version: 1.1

K9CE11000.indd

K9CE11000.indd

version: 1.1

41

Canalis KTC from 1000 to 5000 A

Presentation

For horizontal transport and distribution


Canalis KTC
Run sections

b Canalis KS plug-on tap-off units are


compatible with the Canalis KT busbar
trunking:
v protection by 25 to 400 A fuses
v protection by 100 to 400 A Compact NSX
circuit breakers.
b Canalis KT fixed tap-off units:
v protection by 400 to 1250 A
Compact NS and NSX circuit breakers
v protection by 400 to 1000 A fuses.

b Change-of-direction sections adapt to all


busbar trunking requirements.
b There are both fixed and made-tomeasure lengths.

PD202328_r

PD202312_r

PD202313_r

Change-of-direction sections

PD202315_r

Rating: 1000 to 5000 A.


Transport sections:
fixed lengths: 2 and 4 meters
non-standard lengths: 0.5 and 3 meters
Distribution sections:
fixed lengths: 2 and 4 meters.

PD202314_r

b
b
v
v
b
v

Tap-off units

42

version: 1.1

K9CE11500.indd

Interface connections

Universal supply connections

PD202300_r

PD202431_r

b There are two types of support for


installing the busbar trunking horizontally.
b One type of fixing: to fix the busbar
trunking to its support.

PD202318_r

b Supply connections allow the


busbar trunking to be connected to the
switchboards busbar or to the transformer.

PD202317_r

b Pre-fabricated interfaces connections can


be incorporated into:
v Prisma Plus and Okken switchboards
v France Transfo dry-type transformers.

Horizontal fixing supports

K9CE11500.indd

version: 1.1

43

Canalis KTC from 1000 to 5000 A

Presentation

For distribution to different levels


Rising mains
Canalis KTC
Run sections

PD202319_r

PD202320_r

b Rating: 1000 to 5000 A.


b Distribution sections, fixed 2 meter lengths.
b Transport sections for going through floor slabs,
fixed 0.5 to 3 meter lengths.

Vertical fixing support

PD202321_r

b For installing the busbar trunking vertically, they


ensure:
v height and depth adjustment
v load sharing
v absorption of expansions, vibrations, etc.
b They can be fixed either to the floor, the wall or to
a bracket.

Tap-off units

PD202322_r

b Canalis KS tap-off units are compatible with the


Canalis KT busbar trunking:
v protection by 25 to 400 A fuses
v protection by 100 to 400 A Compact NSX circuit
breakers.
b Canalis KT fixed tap-off units:
v protection by 400 to 1250 A Compact NS and NSX
circuit breakers
v protection by 400 to 1000 A fuses.

44

version: 1.1

K9CE11500.indd

Tap-off units from 25 to 1250 A

Rating (A)

Type of protection
Modular switchgear

Compact NS and NSX

Fuses

Compact NSX with


measurement and metering

PD202138_r

PD202150_r

25/50 A for NF/DIN fuses


32 A for BS fuses
For Compact NSX100 circuit
breaker

63 A for DIN fuses


100 A for NF/DIN fuses
80 A for BS fuses
PD202323_r

PD202150_r

160

PD202150_r

100 A, 12 x 18 mm modules

PD202324_r

250 to 400

160 A for NF/DIN/BS fuses


Fitted with DIN rail for Powerlogic
PM810

PD202184_r

For NG125/160 circuit breaker For Compact NSX160 circuit


breaker

PD202324_r

PD202148_r

63 A, 8 x 18 mm modules

PD202147_r

25 to 100

PD202149_r

Plug-on tap-off units

For Compact NSX250 circuit


breaker

250/400 A for NF/DIN fuses

For Compact NSX400 circuit


breaker

For Compact NSX400 circuit


breaker
DB402028

DB402027

630

PD202325_r

PD202325_r

For Compact NSX250 circuit


breaker

For Compact NSX630 circuit


breaker

630 A for NF fuses

800, 1000 and 1250

PD202327_r

For Compact NSX400 and


NSX630 circuit breakers

PD240004_r

400 to 630 A for DIN fuses(1)


PD240005_r

400 and 630

PD202326_r

Fixed tap-off units

For Compact NS800, NS1000 and 800 to 1000 A for DIN fuses(1)
NS1250(1) circuit breakers
(1) Tap-off units for NS1250 and fuses (from 400 to 1000 A) in IP31 only.

K9CE11500.indd

version: 1.1

45

General

Description

Canalis KTC
The Canalis KT busbar trunking is intended for high power distribution and
transport in industrial, commercial and tertiary buildings.
Assembly of prefabricated sections that adapt to all run configurations.

Run sections
DD205853

DD202434-m

b
b
b
b
b
b

DD202435-m

3L + PE

3L + N + PE

DD202436-m

-1/2

L1 L2 L3 N PE

DD205854

The conductors are sandwiched together inside the metal


casing.

8 ratings are available, from 1000 to 5000 A.


4 copper live conductors with identical cross-sections (3L + N + PE version).
Conductors insulated using polyester film, class B 130 C, halogen free.
Standard busbar trunking is IP55.
Insulation voltage: 1000 Volts.
Available polarities: 3L + PE, 3L + N +PE, 3L + N + PER (reinforced PE)

The KT busbar trunking is of compact design and can be installed edgewise, flat or
vertically.
This design, allows the busbar trunking to be installed through a floor slab or fire
barrier wall.
As standard, the Canalis KT busbar trunking acts as a fire barrier in accordance
with IEC 60439-2.
The RAL 9001 pre-lacquered galvanized steel casing provides protection and
mechanical fixing of the conductors.
Further, it is used as the PE protective conductor (in accordance with NFC 15100
and IEC 60364).
In its reinforced version 3L + N + PER, the busbar trunking is fitted with an
additional internal copper conductor with a cross-section equal to half that of the
phase conductor.
A reinforced version can be supplied on demand. This version has lateral
reinforcement (see page Characteristics).
The Canalis KT busbar trunking is suitable for applications containing harmonics by
taking into account the appropriate derating factor. See Harmonic currents in the
Design guide.

3L + N + PER

Tap-off contact
The KS plug-on tap-off units are connected to the busbar trunking whilst live (offload) via spring jaw connections.
Contact zone coating:
b silver-plated copper at jaw contact points.

46

version: 1.1

K9CE12000.indd

Joint block
DD202445

The junction between sections is made using a joint block.


The joint block provides the following:
b electrical junction between live conductors and between PE protective
conductors, mechanical link between the two sections.
Contact zone coating:
b silver-plated copper

DD205857

It provides simultaneous continuity between all conductors.


It is tightened using torque bolt(s) (1 to 4 depending on the rating) with snap-off
heads.
The nut head snaps-off, freeing a red washer, when the correct tightening torque is
reached.
This operation is checked visually:
b if the red washer is absent: it has been tightened
b if the red washer is visible: it has not been tightened.
This device guarantees the necessary contact pressure between live conductors
and is operator independent.
For dismantling or maintenance operations, the nut has a second head.
The tightening torque is 6 daN.m.
All sections (apart from ER and EL feed units) are supplied with their joint
block, delivered in a separate parcel.
If the run has a feed unit (ER or EL) at each end, an additional joint block
must be ordered.

Phase order

DD205858

The standard phase order for the busbar trunking is denoted N321.

-1/2

L1 L2 L3 N PE

-1/2

L1 L2 L3 N PE

DD205859

However, this order can be changed to N123. A label showing the phase order
N123 is supplied with each element to indicate the change.

-1/2

L1 L2 L3 N PE

-1/2

L1 L2 L3 N PE

K9CE12000.indd

version: 1.1

47

Run sections

Description

Canalis KTC
Straight sections
Transport sections - Type ET

DD202390

Transport the current without tap-off points.


Available in 2 and 4 metre fixed lengths or made to measure from 0.50 to 3 metres.

Sections with tap-off points for plug-on tap-off units Type ED

DD205860

ED run sections are for current distribution.


They use 25 to 400 A KS tap-off units.
These tap-off units can be plugged-on whilst live, but off-load.
Available in fixed 2 or 4 metre lengths with 3 tap-off points on one side.

Sections with tap-off points for fixed tap-off units - Type EB

DD205861

EB run sections are for current distribution.


They use specific KT 400 to 1250 A tap-off units.
These tap-off units can only be fitted / removed when the run is not energised.
Available in a 2 metre fixed length with one tap-off point or a 4 metre fixed length
with 2 tap-off points.

48

version: 1.1

K9CE12000.indd

Other run sections


Disconnectors and run
protective devices
Other run sections
DD202446

Expansion section - Type DB

It controls and absorbs the expansion of Canalis runs and must be used on runs
over 30 metres and each time the busbar trunking passes through a building
expansion joint.
Refer to the installation guide.
Available in a 1 metre length, it can be fitted vertically or horizontally.
At its centre it has flexible conductor joints and a sliding case able to absorb the
relative movements of each part of the section.

Transposition sections - Types TN, TP

DD205863

DD202439

Used when the phase order of the switchboard is different to that of the
transformer.
Available in a 1 metre length and is the same physical size as a transport section.
b The TN version transposes the neutral.

DD205862

DD205856

DD205864

b The TP type transposes the phases.

Additional joint block - Type YA

If the run has a feed unit (supplied without a joint block) at each end, an additional
joint block must be ordered.
Each joint block is supplied with the necessary covers, nuts and bolts.

Run end cover - Type FA

The end cover protects and insulates the conductor ends and is fitted to the last
section.

Disconnectors and run protective devices

DD202441

DD202440

Fitted between 2 flat or edgewise sections, they isolate or protect a busbar


trunking part run.
Each assembly is supplied fitted with a 3 or 4-pole device complete with rotary
handle.
Supplied with:
b an auxiliary connection terminal
b lifting rings
b upstream and downstream terminal shields.
Colour: white RAL 9001, 100 % polyester paint on galvanized sheet steel.
Refer to manufacturers data for switchgear characteristics.
Fitted with a rotary handle, the tap-off unit can only be opened once the device
has been switched off.

Run disconnector tap-off units - Type SL

Type SL for:
b Compact NS1000 to 1600 A type NA fixed isolators:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied)
b Interpact INV isolator, 2000 to 2500 A:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied)
b Masterpact NW3200 A type HA fixed isolator supplied with:
v transparent protection cover
v adaptation kit for Ronis lock + 1 Ronis lock
v complete Harting plug, not cabled.

Run protection tap-off units - Type PL

Type PL for:
b Compact NS1000 to 1600 A type N fixed circuit-breakers:
v unhingeable door
v 3-point closing (possibility of locking with key lock, not supplied).
For circuit-breakers greater than 1600 A, consult the sales office.

K9CE12000.indd

version: 1.1

49

Change of direction sections

Description

Canalis KTC
Simple changes of direction
Elbows - Types LP and LC

DD205865

To go up or down, to turn right or left:


b type LP, flat elbow available in fixed or made-to-measure lengths

DD202432

b type LPpC, flat made-to-measure angled elbow

DD205866

b type LC, edgewise elbow available in fixed or made-to-measure lengths

DD205867

b type LCpC, edgewise made-to-measure angled elbow.

Edgewise T junctions - Type TC


DD205868

To feed runs perpendicular to the main run.

Changes of direction
Zeds - Types ZP, ZC and CP

DD205869

3-branch made-to-measure:
b flat or edgewise, to move the run axis upwards, downwards, to the right or to the
left without having to bend the busbar trunking:
v type ZP, flat Zed

DD205870

v type ZC, edgewise Zed

DD205871

b edgewise / flat, to provide the busbar trunking with a bend:


v Type CP, edgewise and/or flat Zed.

50

version: 1.1

K9CE12000.indd

Connection sections

To connect the KTC busbar trunking to different terminals or to transformer,


switchboard, generator set, etc. busbars. Canalis offers high performance
connection sections which meet all requirements.
These sections provide installation flexibility combined with quick and simple
assembly.
Further, the connections are made using torque bolts which provide both ease
of installation (use of a standard spanner for tightening to 6 daN.m) and a visual
check before energising.

Connections via interface to Prisma Plus, Okken and Trihal

DD202314

DD202306

Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.
Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.
Quick and simple connection of the busbar trunking to the interface.
Reduced size.
Joint block integrated into the interface.
A sealing kit (rating dependent) must be ordered.

DD202310

Prisma Plus switchboard


Sealing kit

Prisma Plus and Okken switchboards

For fixed or draw-out incoming device, front or rear connection:


b Masterpact NW08 to NW40 or NT06 to NT16 circuit-breaker
b Compact NS630b to NS1600 circuit-breaker.
Possibility of switching the phases around.

Okken switchboard
DD202503

France Transfo Trihal dry type transformers


For naturally ventilated or force ventilated transformers.
Protection degree:
b IP00
b IP31.
Secondary voltage: 410 V
15 mm adjustment in the 3 axes.

K9CE12000.indd

version: 1.1

51

Connection sections

Description

Canalis KTC
Universal connections to switchboards and oil immersed transformers
DD210777

Feed units - Type ER

They allow the busbar trunking to be connected to a switchboards busbar, or to the


terminals of an oil immersed transformer, generator set, etc.
They come complete with a mounting plate fitted:
b either directly to the roof of the switchboard
b or via the intermediary of a protective cover.

DD205872

Vertical or horizontal incoming busbar trunking.

DD202502

Types ER N1/N2

Types ER N3/N4

Types ER N5/N6

Type ER N7

Connection:
b either directly to the busbar
b or by flexible bars and connection plates
b or by braids
b or by cables.
b ER feed units are supplied without a joint block.
b If the run has a feed unit at each end, an additional joint block must be ordered.

52

version: 1.1

K9CE12000.indd

DD210866

Protective covers - Types CS, CR, BC

DD210864

Protects the external part of the connection.

b Type CS
Height adaptable flexible protective cover adaptable for ER N1 to N6 feed units
with a between centres distance of 115 mm.

For a vertical incomer - Types CR1 to CR3

DD205873

Made-to-measure rigid protective cover for ER N1 to N7 feed units.


They are height adjustable by 50 mm.
b Type CR 1 for a horizontal incomer.

DD205624

DD210865

b Types CR2 and CR3 for a vertical incomer.

b Types CR7 and CR8


Protective covers for oil immersed transformers.
Only for ER N1 to N6 feed units with a between centres distance of 150 or 170 mm
depending on the rating.
Fit directly onto the BT series transformer tanks.
Never use with HV porcelaine bushings.

DD202321

v Type CR7 for a vertical incomer.

DD202325

v Type CR8 for a horizontal incomer.

v Type BC
Protective cover for direct cable connection to ER N1 to N6 feed units with a
between centres distance of 115 mm.

K9CE12000.indd

version: 1.1

53

Connection sections

Description

Canalis KTC

DD202447

Universal connections to dry type transformers


Feed units - Type EL

For dry type transformers with the neutral between the phases.
They allow optimum connection to the busbar trunking.

DD205874

The junction with the busbar trunking is achieved:


b either from the side

Type EL N1/N2.

DD205877

Type EL N3/N4.

DD205876

DD205875

b or from the centre.

Type EL N5.

They are of similar design to straight transport sections and can be installed
edgewise or flat.
If installed flat, a set of angle brackets can be ordered.
The following must be specified at the time of order:
b phase order
b distance between phases (a 20 mm lateral adjustment can be made use of on
site).
The link between the transformer terminals and the connection section is either by
flexible bar connection plates or by braids.

54

version: 1.1

K9CE12000.indd

Protective covers - Type CR4 to CR6

These protect the connections with an IP31 casing when connecting to a


transformer.
They are height adjustable by 50 mm.

DD202342

b Type CR4
Protective cover for EL N1 to N4 feed units.
Edgewise assembly.

DD202343

b Type CR5
Protective cover for EL N1 to N4 feed units.
Flat assembly.

DD202346

b Type CR6
Protective cover for EL N5 feed unit.
Edgewise assembly.

K9CE12000.indd

version: 1.1

55

Connection accessories

Description

Canalis KTC
Accessories for direct connection to the switchboard
DD202363

The conductors of ER N1 to N6 feed units are connected directly to the


switchboard busbars.
YB2 copper spacers are available to compensate differences in thickness between
the switchboard bars (10 mm) and the connection part (6 mm).
DD202400

Make-up of kit:
b 8 x 2 mm thick copper spacers
b 16 off M12 x 60 mm bolts, class 8.8
b 16 contact washers
b 16 torque nuts
b 8 steel spacer plates.
Order a set per feed unit whatever the rating.

Switchboard connection accessories using connection plates


DD210784

The conductors of ER N1 to N6 feed units are connected via connection plates to


the switchboard busbars.
The YC types are flexible bars made up of 5 copper sheets of 1 x 100 mm (500
mm cross-section).
The number of connection plates needed is proportional to the busbar trunking
rating.
There are 3 types:
b YC1, uninsulated 600 mm long bar with 4 oblong holes at one end.
The length of the holes at the switchboard side are to be adapted on-site
104202DD
DD202402

b YC2, uninsulated bar, made-to-measure length of 250 to 600 mm with 4 oblong


holes at each end, ready to use

DD202403

b YC5, insulated 1000 mm long flexible bar, stripped at one end and with 4 oblong
holes.
The length of the holes at the switchboard side are to be adapted on-site.

DD205878

Nuts and bolts


The connection plates are fixed to the feed unit using the YB3 nut and bolt kit,
made up of:
b 16 off M12 x 60 mm bolts, class 8.8
b 16 contact washers
b 16 torque nuts
b 8 steel spacer plates.

DD202411

Clamps
YS1 clamps enable high short-circuit current levels to be withstood; only for bars
with a 115 mm spacing.

Insulation
See page 57.

56

version: 1.1

K9CE12000.indd

Transformer connections - Types YC, YT


DD205879

The feed unit conductors are connected to the transformer bars via connection
plates or braids:
b connection plates, YC types, are flexible bars made up of 5 copper sheets of
1 x 100 mm (500 mm cross-section)
b braids, YT type, are copper braids with a 600 mm cross-section.
The number of connection plates needed is proportional to the busbar trunking
rating.

Connection plates

DD202412

The YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4
holes at one end.
They can be fitted to the transformer side:
b either using bar clamps (no drilling)
b or drilled and bolted (to be carried out on site).

DD205880

YS2 and YS3 bar clamps enable connection without the need to drill the connection
plates.
They allow height adjustment.
b Type YS2, bar clamps for 100 mm transformer connection terminals.
b Type YS3, bar clamps for 120 mm transformer connection terminals.
Make-up of kit: 1 set of 8 parts.

DD202414

b The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has
4 oblong holes at each end (ready to use).

Braids
DD202415

Type YT, 400 mm long insulated braid with 4 holes at each end.

DD230229

The connection plates and braids are fixed to the feed unit using the YB4 nut and
bolt kit, made up of:
b 16 off M12 x 80 mm bolts, class 8.8
b 16 contact washers
b 16 torque nuts
b 8 steel spacer plates.

Insulation

DD230230

The YF conduit allows the various conductors of a connection performed with


braids or with bare copper foils to be insulated.
Installation is performed after complete assembly of the connection, with scratch
fastening for easier setup.
The insulating conduit is formed of a 2-metre plastic duct that can be cut to length
as needed.

K9CE12000.indd

version: 1.1

57

Supports and fixings

Description

Canalis KTC
Horizontal supports
273202DD

The ZA types allow the busbar trunking to be fixed and adjusted along its length, as
well as absorbing its movements.

Supports for horizontal sections

DD202485

b Type ZA1, to support edgewise busbar trunking only, consists of a steel angle
bracket and 2 x 2 metre threaded M10 rods.
The maximum distance between supports is:
v 3 metres for edgewise busbar trunking
v 2 metres for flat busbar trunking.
See installation precautions.

DD202368

DD202486

b Type ZA4, to support the busbar trunking from the top.


b These supports are needed to fix edgewise EL N1 to N4 feed units for dry type
transformers (rods not supplied).

DD202369

Fixing bracket
DD202484

The ZA3 keeps the busbar trunking in place on its support, without blocking it, in
order to allow expansion movements.

Vertical supports

DD202496

DD202374

The ZA5 is for supporting vertical sections.


They fix sections of a vertical run to the buildings structure.
This type of fixing support has the following advantages:
b assembly:
v to a wall
v to a wall bracket
v to the floor
b height and depth adjustment
b spring adjustment to ensure distribution of the load at each floor
b avoids the transmission of building forces to the busbar trunking (expansion and
vibration).

For KTC1000 to KTC2000.

For KTC2500 to KTC5000.

To a wall.

58

To a wall bracket.

version: 1.1

To the floor.

K9CE12000.indd

Tap-off units

Description

Canalis KTC

DD210275

The tap-off units are used to instantly connect loads or secondary runs, and comply
with installation standards and regulations (IEC 60364), whatever the earthing
system (TT, TNS, TNC or IT).
When off-load, they can be plugged-on and off and be operated whilst live.
Plugging-on and plugging-off automatically opens and closes the tap-off point.

DD210276

No live part is accessible with the door open. The protection degree is IPXXB
(finger protection).
They are IP55 by construction (no accessory is required).

Safety and operation

Fuse and modular switchgear tap-off units (AC20) are isolated as soon as the tapoff unit door is opened.
Tap-off unit disconnection by opening or closing the cover should be carried
out only if the downstreamload is de-energised.
For circuit breaker tap-off units, there are safety mechanisms to prevent:
b the tap-off unit being plugged-on and plugged-off with the tap-off unit door closed
b the door being closed if the tap-off unit has not been locked onto the busbar
trunking
b access to the electrical equipment and connection terminals when live
b the door being opened in the "ON" position for tap-off units fitted with a Compact
NS or NSX or NG circuit breaker.

DD210466

These tap-off units can be fitted with accessories such as:


b door early break contacts
b adapter for lead sealing
b etc.
The sheet steel tap-off units are fitted with a carrying handle.
Characteristics of tap-off units up to 100 A
b Colour:
v white (RAL 9001) body and carrying handles
v transparent green door (similar design to the Kaedra enclosures).
b Material: self-extinguishing, halogen-free insulating plastic (fire resistant and very
high temperature withstand).
Other characteristics: cable gland drilling zone, stainless steel screws and the door
can be lead sealed.

DD202012

Characteristics of tap-off units from 160 to 400 A


b Colour:
v white (RAL 9001) body
v black carrying handles (RAL 9005)
v 100 % polyester paint.
b Material: galvanized sheet steel.
Other characteristics:
b unhingeable door (120 opening hinges)
b vertically bevelled polyurethane seals with a double fold for increased rigidity
(similar design to the Sarel Spatial 3D enclosures)
b 25 mm grill type gland plates for a maximum access area.

K9CE13000.indd

version: 1.1

59

Description

Plug-on tap-off units for circuit


breakers

DD210454

Canalis KTC
Isolator tap-off units for modular switchgear

Most 18 mm Multi 9 modular devices can be fitted into these tap-off units.
They have a window on the front face for switchgear control and visualisation.
A transparent shutter ensures the window can be sealed.
Two tap-off ratings are available:
b 63 A nominal current for 8 modules
b 100 A nominal current for 12 modules (accepts C120 circuit breakers).

Tap-off units for NG type modular switchgear


DD202154

These tap-off units are fitted with a DIN rail and upstream connections for 18 mm
wide modular devices.
The switchgear is operated via a rotary handle which prevents door opening when
the circuit breaker is in the ON position.
Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fitted
with a Vigi unit).

Isolator tap-off units for Compact NSX circuit breakers


DD210461

These tap-off units are fitted with mounting plates and upstream connections
for fixed, front-connected 100 to 400 A Compact NSX circuit breakers (N, H or L
version) with a rotary handle.
The 400 A tap-off units can only be fitted onto straight lengths with a rating greater
than 400 A.
For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electric
contact.

Measurement and metering isolator tap-off units


DD210465

These tap-off units allow sub-metering to re-allocate power consumption costs by


consumer and to monitor installations by, for example, following run load levels.
The values measured using the Compact NSX TI unit are sent to the measurement
unit which then sends the information to a central unit via a bus (See Measurement
and metering).
They are fitted with:
b a mounting plate for a Compact NSX 250 or 400 A circuit breaker with an
extended rotary handle and a Compact NSX current transformer module (TI unit)
b a DIN rail for installing a Powerlogic PM810 measurement unit, a set of
terminals, etc.
In severe operating conditions (> 40 C ambient temperature), we recommend the
use of a PM810 without display.

60

version: 1.1

K9CE13000.indd

Plug-on tap-off units for fuses

These tap-off units provide the tap-offs with fuse protection (fuses not supplied).

Plastic tap-off units


DD210466

Fitted with carriers for:


b 50 to 100 A cylindrical NF fuses
b 25 to 63 A DIN screwed fuses
b 100 A DIN blade fuses
b 32 to 80 A BS screwed fuses.

Steel tap-off units

DD210472

DD202012

Fitted with carriers for:


b 160 to 400 A NF/DIN blade fuses
b 160 A BS screwed fuses.

K9CE13000.indd

version: 1.1

61

Description

Fixed tap-off units for circuit


breakers

Canalis KTC
Safety and operation

The electrical connection is made by plugging-on the tap-off unit into dedicated tapoff point whilst the busbar trunking is de-energised (plugging-off the unit must also
be done with the busbar trunking de-energised).
The connection is mechanically tightened using a one-use torque bolt (10 daN.m).
A mechanical foolproof system avoids the risk of incorrect assembly.
The door can only be opened once the load has been isolated (rotary handle).
The bolt can only be tightened or untightened with the door open.
No live part is accessible with the door open, protection degree IP2X.

Characteristics of tap-off units from 400 to 1250 A

b Colour:
v white (RAL 9001) body.
b Material: galvanized sheet steel.
b Other characteristics:
v the cables exit laterally through 2 aluminium plates (to be drilled by the
installation contractor)
v cabling space can be increased by using the cable box supplied with the tap-off
unit
v the door is fixed using 6 captive M6 screws and can be completely removed to
facilitate cabling.

DD202451

Steel tap-off units

These tap-off units are used to supply loads or secondary runs (e.g. medium power
distribution using Canalis KS).
They are fitted to specific EB type straight lengths.
They comply with installation standards and regulations, whatever the earthing
system (TT, IT, TNS or TNC):
b tap-off units fitted with a mounting plate for Compact NS and NSX 400/1250 A,
3 or 4 P:
v fixed device
v front connections
v extended rotary handle.

DD202497

3 models:
b Compact NSX400/630 A, connection capacity:
v IP54
v 3 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm),
v 150 mm for the PE
b Compact NS800/1000 A, connection capacity:
v IP54
v 4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm)
v 200 mm2 for the PE (cable clamp)
b Compact NS1250 A, connection capacity:
v IP31
v 4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm)
v 200 mm2 for the PE (cable clamp).

62

version: 1.1

K9CE13000.indd

Catalogue numbers and


dimensions

Contents

Index
Introduction
Presentation and description

3
17
35

Catalogue-number coding

65

Run components

66

Additional run components

69

Elbow components for changing direction

71

Zed components for changing direction

74

IP55

74

Canalis interfaces for Prisma Plus LV switchboard

76

Canalis interfaces for Okken LV switchboard

78

Sealing kits

79

Feed units for switchboards and oil immersed transformers

80

Rigid protective covers

84

Flexible protective covers Cable boxes

87

IP55

87

Feed units for dry-type transformers

88

Protective covers for dry-type transformers

92

IP55

92

Connection accessories

94

Supports and fixings

98

Accessories

100

Fire-barrier kit S120 100

Tap-off units from Canalis KS range

101

63 to 100 A tap-off units for modular devices


101
125 to 160 A tap-off units for modular devices
102
100 to 400 A tap-off units for Compact NS circuit breakers 103
250 to 400 A tap-off units for Compact NS circuit breakers 104
50 to 100 A tap-off units for NF fuses 105
100 to 400 A tap-off units for NF fuses 106
25 to 63 A tap-off units for DIN fuses 107
100 to 400 A tap-off units for DIN fuses
108
32 to 160 A tap-off units for BS fuses
109

Accessories for tap-off units from Canalis KS range

110

Bolted tap-off units from Canalis KT for Compact NSX/NS


400 to 1250 A circuit breakers

111

630 and 1000 A bolted tap-off units with switch-disconnetors


for DIN fuses

112

IP31 112

Design guide
Design and installation guide
Recommandations
DEBU024EN_Catalogue numbers.
indd

133
171
231

Coupling isolators from1000 to 2500 A

113

Coupling isolators 3200 A

114

Protection of the run using Compact NS circuit breakers


from1000 1600 A

115

Special products

116

Canalis KH substitution by Canalis KT

118

KHF/KTC connection elements 118


Preserved KH tap-off units and substitution table 119
250 and 630 A tap-off units from Canalis KH range
for Compact NSX circuit breakers 122
250 and 630 A tap-off units from Canalis KH range for NF fuses 123
100 to 630 A tap-off units from Canalis KH with disconnector Jean Muller 124
400 and 630 A tap-off units from Canalis KH with disconnector Jean Muller 125
250 to 630 A tap-off units from Canalis KH range
with Fupact INF fuse switch - IP43 126
250 to 1000 A fixed tap-off units for Canalis KHF range,
with isolator and fuse carriers 127
Fixed tap-off units for Canalis KHF or KGF range,
for circuit breaker NS630b, NS800, NS1000 128
Expansion of a Canalis KH line by means of Canalis KT 129
Expansion of a Canalis KH line by means of Canalis KT with a T-piece tap-off unit 130
Mid KT line power supply with KH tap-off units installed 131
version: 1.1

63

64

version: 1.1

K9CE20000.indd

Catalogue-number coding

Catalogue numbers and


dimensions
Canalis KTC
Catalogue-number composition
b One letter designating the material.
Type
Copper
Non conducting

KT

Code
C
B

b Two letters identifying the type of component.


Type
Code
Adjustable straight length
AJ
Cable box
BC
Bolted tap-off unit
CB
Edgewise and flat zed
CP
Rigid protective cover
CR
Flexible protective cover
CS
Expansion unit
DB
Distribution length for bolt-on tap-off units
EB
Distribution length for plug-in tap-off units
ED
Distribution length for KH plug-in tap-off units EH
Feed unit for dry-type transformers
EL
Feed unit
ER
Feeder length
ET
End cover
FA
Bolted tap-off unit for fuses
HF
Connection KH/KT
HT
Edgewise elbow
LC
Flat elbow
LP
Tap-off unit with protective device
PL
Tap-off unit with isolator
SL/RL
Edgewise tee
TC
Neutral crossover
TN
Phase crossover
TP
Sealing kit
TT
Connection device
YA
Connection torque nut kit
YB
Flexible bar
YC
Bracket
YE
Insulating sheath
YF
Bar supports
YS
Braids
YT
Supports and fixing devices
ZA
Edgewise zed
ZC
Flat zed
ZP

p p p p p p p p pp

b Four digits indicationg


the rating of the trunking.

b One digit indicating the trunking


polarity
Polarity

PE protective
conductor (1)
3L + PE
Standard
3L + N + PE
Standard
3L + N + PER Reinforced
3L + N + PER Reinforced

Short circuit
level (1)
Standard
Standard
Standard
Reinforced

Code
3
4
5
7

(1) For further information, see page 134 "Characteristics".

b Variable number of alphanumeric


characters indicating characteristics
specific to the component.
See the section dealing with the given
component.

Trunking cross section


1350
1
100 x 6

1600
1
120 x 6

2000
2
160 x 6

2500
2
200 x 6

3200
4000
5000
2
4
4
2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)

230

230

230

350

350

350

DD202180

1000
1
70 x 6

DD202182

Rating (A)
Number of bar jointing bolts
Bar cross-section (mm)
Trunking height H (mm)

DD202181

Holes for connections (mm)

K9CE20000.indd

version: 1.1

510

510

65

Run components

Catalogue numbers and


dimensions

IP55

Canalis KTC
Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b add the dimensions of the selected component as a technical comment
Example: the catalogue number of an 1000 A feeder length, 3L + N + PE,
2450 mm long, is:
KTC1000ET42C, L = 2450
Rating

DD210794

Straight feeder lengths


Type

Fixed
Made to
measure

Length "L"
(mm)

Cat. no.

2000

KTCppppET320 KTCppppET420 KTCppppET520

4000

KTCppppET340 KTCppppET440 KTCppppET540

500 to 1500

KTCppppET31A KTCppppET41A KTCppppET51A

1501 to 1999

KTCppppET32B KTCppppET42B KTCppppET52B

3L + PE

3L + N + PE

3L + N + PER (1)

2001 to 2500

KTCppppET32C KTCppppET42C KTCppppET52C


2501 to 3000
KTCppppET33D KTCppppET43D KTCppppET53D
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppET5pp by
KTCppppET7pp.

KTCppppETppp

DD210795

KTCppppETppp

(1) See the "Trunking cross-section" table opposite.

DD210798

Straight lengths for KS plug-in tap-off units


Type Length
"L" (mm)
Fixed

2000

Number of
tap-offs

Cat. no.

KTCppppED320 KTCppppED420 KTCppppED520

3L + PE

3L + N + PE

3L + N + PER (1)

4000
3
KTCppppED340 KTCppppED440 KTCppppED540
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppED5pp by
KTCppppED7pp.

DD210800

KTCppppEDp20

KTCppppEDp20

DD402701

KTCppppEDp40
16

KTCppppEDp40
(1) See the "Trunking cross-section" table opposite.

66

version: 1.1

K9CE21010.indd

DD210766

Straight lengths for bolted tap-off units


Type
Fixed

Length
"L" (mm)

Number of
tap-offs

Cat. no.

2000

KTCppppEB320 KTCppppEB420 KTCppppEB520

4000

3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppEB340 KTCppppEB440 KTCppppEB540


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppEB5pp by
KTCppppEB7pp.

DD210803

KTCppppEBp20

DD210801

KTCppppEBp20

DD210802

KTCppppEBp40
KTCppppEBp40

(1) See the "Trunking cross-section" table below.

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

K9CE21010.indd

version: 1.1

67

Run components

Catalogue numbers and


dimensions

IP55

Canalis KTC
Ordering
Complete the catalogue number by replacing the "pppp" with the rating.
Example: a transport section 1000 A, length 4 m.
Catalogue number for 3L + N + PE: KTC1000EH640.

Straight sections with KH withdrawable tap-off units


Type

Length
"L" (mm)

Fixed

Number of Cat. no.


tap-off
3L + PE
units

3L + N + PE

3L + N + PER

2000

KTCppppEH320

KTCppppEH420 KTCppppEH520

4000

KTCppppEH340

KTCppppEH440 KTCppppEH540

(1) See the "Trunking cross-section" table opposite.

DB402025

DB402102

KTCppppEHp20

KTCppppEHppp

DB402127

KTCppppEHp40

68

version: 1.1

K9CE21010.indd

Additional run components


IP55

Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b add the dimensions of the selected component as a technical comment.
Example: the catalogue number of a 1350 A straght expansion unit, 3L + PE, 1000
mm long, is:
KTC1350DB310
Rating

DD210805

Straight expansion unit


Type

Length "L"
(mm)

Cat. no.
3L + PE

3L + N + PE

3L + N + PER(1)

Fixed
1000
KTCppppDB310 KTCppppDB410 KTCppppDB510
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppDB510 by
KTCppppDB710.

DD210806

KTCppppDBp10

KTCppppDBp10

(1) See the "Trunking cross-section" table opposite.

DD210807

Neutral crossover length


Type
Fixed

Length "L"
(mm)

Cat. no.

1000

KTCppppTN410

3L + N + PE

DD210808

KTCppppTNp10

KTCppppTNp10
(1) See the "Trunking cross-section" table opposite.

DD210809

Phase crossover length


Type
Fixed

Length "L"
(mm)

Cat. no.

1000

KTCppppTP410

3L + N + PE

DD210810

KTCppppTPp10

KTCppppTPp10
(1) See the "Trunking cross-section" table opposite.

K9CE21020.indd

version: 1.1

69

Additional run components

Catalogue numbers and


dimensions

IP55

Canalis KTC

DD210811

Additional jointing units


Type

Cat. no.

Jointing unit

3L + PE

3L + N + PE

3L + N + PER

KTCppppYA3

KTCppppYA4

KTCppppYA4

DD210812

KTCppppYAp

DD210868

KTCppppYAp

(1) See the "Trunking cross-section" table below.

DD210813

End covers
Type
End cover

Rating of the
trunking (A)

Height H of the
trunking (mm)

Cat. no.

1000
1350
1600
2000
2500
3200
4000
5000

74
104
124
164
204
244
324
404

KTB0074FA
KTB0104FA
KTB0124FA
KTB0164FA
KTB0204FA
KTB0244FA
KTB0324FA
KTB0404FA

KTB0ppppFA
DD210814n

KTB0ppppFA

(1) See the "Trunking cross-section" table below.

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

70

version: 1.1

K9CE21020.indd

Elbow components for changing


direction
IP55

Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b add the dimensions of the selected component as a technical comment.
Example: the catalogue number of a 2000 A flat elbow, N1, 3L + N + PE with
dimensions A = 300 mm and B = 650 mm is:
KTC2000LP4B1, A = 300, B = 650.
Rating

Flat elbows
DD210815

Type
Fixed
Made to
measure

Position of
neutral

Cat. no.
3L + PE

N1

KTCppppLP3A1 KTCppppLP4A1 KTCppppLP5A1

N2

KTCppppLP3A2 KTCppppLP4A2 KTCppppLP5A2

N1

KTCppppLP3B1 KTCppppLP4B1 KTCppppLP5B1

3L + N + PE

3L + N + PER (1)

N2

KTCppppLP3B2 KTCppppLP4B2 KTCppppLP5B2


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppLP5pp by
KTCppppLP7pp.

DD210822

KTCppppLPppp

DD210816

KTCppppLPpp1

(1) See the "Trunking cross-section" table opposite.


Dimensions
Type

Rating (A)

Dimensions (mm)

A
Fixed
All
300
All
300
Made to
measure (2)
301 to 799
(2) Only one llmb may be made to measure.

KTCppppLPpp2

B
300
301 to 799
300

DD210821

Flat elbows with made to measure angles


Type
Made to
measure angle

Position of
neutral

Cat. no.
3L + PE

N1

KTCppppLP3C1 KTCppppLP4C1 KTCppppLP5C1

3L + N + PE

3L + N + PER (1)

N2
KTCppppLP3C2 KTCppppLP4C2 KTCppppLP5C2
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppLP5Cp by
KTCppppLP7Cp.

DD210824

KTCppppLPpCp

DD210823

KTCppppLPpC1

(1) See the "Trunking cross-section" table opposite.


Dimensions
Type

Rating (A)

Made to measure All

Dimensions (mm)
A
300

B
300

W
91 to 179

KTCppppLPpC2

K9CE22010.indd

version: 1.1

71

Elbow components for changing


direction

Catalogue numbers and


dimensions

IP55
Canalis KTC

DD210825

Edgewise elbows
Type

Cat. no.

Fixed

3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppLC3A

KTCppppLC4A

KTCppppLC5A

Made to measure
KTCppppLC3B KTCppppLC4B KTCppppLC5B
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppLC5p by
KTCppppLC7p.

DD210826

KTCppppLCpp

KTCppppLCpp

(1) See the "Trunking cross-section" table below.


Dimensions
Type

Rating (A)

Dimensions (mm)

A
275
290
300
320
340
360
400
440
Made to
276 to 774
275
measure (2)
1350
291 to 789
290
1600
301 to 799
300
2000
321 to 819
320
2500
341 to 839
340
3200
361 to 859
360
4000
401 to 899
400
5000
441 to 939
440
(2) Only one llmb may be made to measure.
Fixed

B
275
290
300
320
340
360
400
440
275
276 to 774
290
291 to 789
300
301 to 799
320
321 to 819
340
341 to 839
360
361 to 859
400
401 to 899
440
441 to 939

1000
1350
1600
2000
2500
3200
4000
5000
1000

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

72

version: 1.1

K9CE22010.indd

DD210819

Edgewise tee
Type

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

Fixed
KTCppppTC3
KTCppppTC4
KTCppppTC5
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppTC5 by
KTCppppTC7.

DD210820

KTCppppTCp

KTCppppTCp

(1) See the "Trunking cross-section" table below.


Dimensions
Type
Fixed

Rating (A)

Dimensions (mm)

1000
1350
1600
2000
2500
3200
4000
5000

A
275
290
300
320
340
360
400
440

B
275
290
300
320
340
360
400
440

C
275
290
300
320
340
360
400
440

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

K9CE22010.indd

version: 1.1

73

Zed components for changing


direction

Catalogue numbers and


dimensions

IP55
Canalis KTC

Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b add the dimensions of the selected component as a technical comment.
Example: the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PE
with dimensions A = 300 mm, B = 450 mm, C = 300 mm is:
KTC1600ZC42, A = 300, B = 450, C = 300.
Rating

DD202183

Flat zed units


Type

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

Made to measure

KTCppppZP3
KTCppppZP4
KTCppppZP5
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppZP5 by
KTCppppZP7.

DD202184

KTCppppZPp

KTCppppZPp

(1) See the "Trunking cross-section" table opposite.


Dimensions
Rating (A)

Dimensions (mm)

All

A
300

B
130 to 599

C
300

DD202185

Edgewise zed units


Type
Made to
measure

Position of
neutral

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

N1

KTCppppZC31

KTCppppZC41

KTCppppZC51

N2
KTCppppZC32
KTCppppZC42
KTCppppZC52
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppZC5p by
KTCppppZC7p.
DD202186

KTCppppZCpp

DD210827

KTCppppZCp1

(1) See the "Trunking cross-section" table opposite.


Dimensions
Rating (A)

Dimensions (mm)

1000
1350
1600
2000
2500
3200
4000

A
275
290
300
320
340
360
400

KTCppppZCp2

74

B
90 to 549
90 to 579
90 to 599
90 to 639
90 to 679
90 to 719
90 to 799

version: 1.1

C
275
290
300
320
340
360
400

K9CE22020.indd

Edgewise and flat zed units


DD202187

Type
Made to
measure

Position of
neutral
N1

Cat. no.
3L + PE
KTCppppCP31

3L + N + PE
KTCppppCP41

3L + N + PER (1)
KTCppppCP51

N2

KTCppppCP32

KTCppppCP42

KTCppppCP52

N3

KTCppppCP33

KTCppppCP43

KTCppppCP53

N4

KTCppppCP34 KTCppppCP44 KTCppppCP54


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppCP5p by
KTCppppCP7p.
KTCppppCPp1 and KTCppppCPp2

DD210828

DD202188

KTCppppCPp1

DD210829

KTCppppCPp2

DD202367

KTCppppCPp3 and KTCppppCPp4

DD210830

KTCppppCPp3

Dimensions
Rating (A)

KTCppppCPp4

A
300
300
300
300
300
300
300
300

1000
1350
1600
2000
2500
3200
4000
5000

(1) See the "Trunking crosssection" table below.

Dimensions (mm)
B
195 to 574
210 to 589
220 to 599
240 to 619
260 to 639
280 to 659
320 to 699
360 to 739

C
275
290
300
320
340
360
400
440

Trunking cross-section
3L + PE
3L + N + PE
3L + N + PER

1000
19
23
25

1350
25
31
33

1600
29
35
39

2000
36
45
49

2500
44
55
60

DD210867

Height H (mm)
Width W (mm)

K9CE22020.indd

3200
51
64
71

4000
66
84
92

5000
82
104
114
DD202180

Rating (A)
Weight (kg/m)

version: 1.1

75

Catalogue numbers

Canalis interfaces for Prisma


Plus LV switchboard

Canalis KTC

DD202304

Interfaces for Masterpact NW circuit breakers


Circuit
breaker

Type of
circuit
breaker

Canalis
polarity

NW08/16

Fixed or
drawout

NW20/25

NW32

Fixed or
drawout
Fixed or
drawout

Top direct connection


DD202305

NW40

Fixed or
drawout

Cat. no.

3L+PE

No. of poles Connection


of circuit
Top
Rear
breaker
direct
b
b
3P

3L+N+PE

4P

04716

3L+N+PER

4P

04716+KTB0164PE1

3L+PE

3P

04725

3L+N+PE

4P

04726

3L+N+PER

4P

04726+KTB0244PE1

3L+PE

3P

04735

3L+N+PE

4P

04736

3L+N+PER

4P

04736+KTB0404PE1

3L+PE

3P

04737

3L+N+PE

4P

04738

b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".

04715

04738+KTB0404PE1

Number of modules required in the switchboard


Circuit breaker
NW08/16

NW20/32

Rear connection

Connection

Type of circuit
breaker

Number of vertical
modules (1)

Top direct

Fixed or drawout

27

Rear

Fixed

16

Drawout

17

Top direct

Fixed or drawout

28

Rear

Fixed

16

Drawout

17

Fixed or drawout

36

NW40
Rear
(1) 1 module = 50 mm.

DD202306

Interfaces for Masterpact NT and Compact NS circuit breakers


Masterpact NT
Circuit Type of
breaker circuit
breaker
NT06/12 Fixed or
drawout
NT16

Fixed or
drawout

Canalis
polarity
3L+PE

No. of poles Connection


of circuit
Top
Rear
breaker
direct
b
b
3P

04703

3L+N+PE

4P

04704

3L+N+PER 4P

04704+KTB0164PE1

3L+PE

3P

04703

3L+N+PE

4P

04704

b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".
Top direct connection

04704+KTB0164PE1

Compact NS
Circuit Type of
breaker circuit
breaker

DD202307

Cat. no.

NS630b/ Fixed or
1250
drawout
NS1600

Fixed or
drawout

Canalis
polarity
3L+PE

No. of poles Connection


of circuit
Top
Rear
breaker
direct
b
b
3P

Cat. no.

3L+N+PE

4P

04704

3L+N+PER 4P

04704+KTB0164PE1

04703

3L+PE

3P

04703

3L+N+PE

4P

04704

b
3L+N+PER 4P
For the position in the switchboard, see the "Installation guide".

04704+KTB0164PE1

Number of modules required in the switchboard


Rear connection

Circuit breaker

Connection

Type of circuit
breaker

Number of vertical
modules (1)

Top direct

Fixed

17

Drawout

18

Rear

Fixed or drawout

16

NT16
Rear
NS1600
(1) 1 module = 50 mm.

Fixed or drawout

16

NT06/12
NS630b/1250

76

version: 1.1

K9CE23000.indd

DD202308

Interface supports and protection covers


Masterpact NW
Circuit
breaker
NW08/32
03561
DD202309

NW40

Type of circuit Connection


breaker

Supports Terminal
Cover
extension
bar supports

Fixed or
drawout

Top direct

03561

3 x 04694

04871 + 04861

Rear

03561

2 x 04694

04871 + 04863

Fixed or
drawout

Top direct

03561

04871 + 04861

Rear

03561

04871 + 04863

Masterpact NT
Circuit
breaker
04711
04712
04713
04714

NT06/12

Type of
circuit
breaker

Canalis
polarity

Connection Supports Canalis/


Cover
circuit
breaker
connection

Fixed or
drawout

3P

Top direct

03561

04712

04871 + 04852

Rear

03561

04713

04871 + 04853

Top direct

03561

04712

04871 + 04852

Rear

03561

04714

04871 + 04853

3P

Rear

03561

04713

04871 + 04854

4P

Rear

03561

04714

04871 + 04854

Type of
circuit
breaker

Canalis
polarity

Connection Supports Canalis/


Cover
circuit
breaker
connection

Fixed

3P

Top direct

03561

04712

04871 + 04851

Rear

03561

04713

04871 + 04853

Top direct

03561

04712

04871 + 04851

Rear

03561

04714

04871 + 04853

Top direct

03561

04711

04871 + 04852

Rear

03561

04713

04871 + 04854

Top direct

03561

04712

04871 + 04852

Rear

03561

04714

04871 + 04854

3P

Rear

03561

04713

04871 + 04853

4P

Rear

03561

04714

04871 + 04853

3P

Rear

03561

04713

04871 + 04854

4P

Rear

03561

04714

04871 + 04854

4P
NT16

Fixed or
drawout

Compact NS
Circuit
breaker

NS630b/
1250

4P
Drawout

3P
4P

NS1600

Fixed
Drawout

Arc-chute covers
Circuit breaker
Masterpact NT
Compact NS

K9CE23000.indd

Type of circuit breaker

Canalis polarity

Cat. no.

Fixed

3P

47335

4P

47336

3P

33596

4P

33597

Fixed

version: 1.1

77

Catalogue numbers

Canalis interfaces for Okken


LV switchboard

Canalis KTC
Interfaces for Masterpact NW circuit breakers
DD202310

Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuit
breaker

Type of
circuit
breaker

Canalis
polarity

NW08/16

Drawout

3L+PE

No. of poles Connection


of circuit
Top
Rear
breaker
direct
b
3P
b

3L+N+PE

4P

b
b

DD202311

Top direct connection (RDH)

Drawout

3L+PE

3P

3L+N+PE

4P

3L+N+PER 4P
NW32

Drawout

3L+PE

3P

87823

87824

87824+KTB0244PE1

87814

87814+KTB0244PE1

4P

3L+N+PER 4P

87815

Drawout

3L+PE

3P

3L+N+PE

Rear connection (RAR)

4P

3L+N+PER 4P

87825
87816

NW40

87822+KTB0164PE1
87813

b
3L+N+PE

87822
87812+KTB0164PE1

b
NW20/25

87811
87821
87812

b
3L+N+PER 4P

Cat. no.

87826
87816+KTB0404PE1

87826+KTB0404PE1

87827

87828

87817

87818

87818+KTB0404PE1
b

87828+KTB0404PE1

For the position in the switchboard, see the "Installation guide".

Interfaces forMasterpact NT circuit breakers


DD202312

Fitting the interface does not change switchboard modularity as fixed by the devices.
Circuit
breaker
NT08/16

Type of
circuit
breaker

Canalis
polarity

Drawout

3L+PE

No. of poles Connection


of circuit
Top
Rear
breaker
direct
b
3P
b

3L+N+PE

4P

3L+N+PER 4P

Cat. no.

87811
87821
87812

87822
87812+KTB0164PE1

87822+KTB0164PE1

For the position in the switchboard, see the "Installation guide".

DD202313

Top direct connection (RDH)

Rear connection (RAR)

78

version: 1.1

K9CE23000.indd

Sealing kits
IP55

Interface supports
Circuit breaker
NW08/40
NT08/16

Type of circuit breaker

Connection

Cat. no.

Drawout

Top direct

87800

NW08/32 (1)
Drawout
Rear
87801
NT08/16
(1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are
supplied with the interface.

DD202314

Sealing kits for switchboard and Trihal transformer roofs with interface
Type
Sealing kit

Rating of the
trunking (A)

Height H of the
trunking (mm)

Cat. no.

1000

74

KTB0074TT01

1350

104

KTB0104TT01

1600

124

KTB0124TT01

2000

164

KTB0164TT01

2500

204

KTB0204TT01

3200

244

KTB0244TT01

4000

324

KTB0324TT01

5000

404

KTB0404TT01

KTB0ppppTT01

DD230215

Reinforced protective earth (PER) for Prisma Plus and Okken interfaces
Number of holes

Cat.no.

160

Height "H" (mm)

KTB0164PE1

240

KTB0244PE1

400

KTB0404PE1

DD230216

KTB0pppPE1

Thickness: 3mm.

KTB0pppPE1

K9CE23000.indd

version: 1.1

79

Feed units for switchboards and


oil immersed transformers

Catalogue numbers and


dimensions

IP55
Canalis KTC

Ordering
Complete the catalogue number by replacing pppp" by the rating.
Important:
b add the dimensions of the selected unit as a technical comment.
Example: the catalogue number of a 1250 A made to measure end feed unit, N2,
3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is:
KTC1350ER42, A = 235, J = 170, K = 170 and M = 170.
Rating

DD210831

Straight feed units


Type
Fixed

Position of
neutral

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

N1

KTCppppER31

KTCppppER41

KTCppppER51

Made to measure N2

KTCppppER32 KTCppppER42 KTCppppER52


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppER5p by
KTCppppER7p.

DD210832

KTCppppERp1, KTCppppERp2
3L + N + PE ou PER

KTCppppERp1
KTCppppERp2

DD230218

3L + PE
(1) See the "Trunking cross-section" table in the
following page.
(2) PE drilled diameter = 14 mm pour cables
with crimped lugs.

Table of dimensions
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Neutral

Dimensions (mm)

N1
N2
N1
N2
N1
N2

A
235
235 to 734
235
235 to 734
235
235 to 734

J, K, M
115
80 to 250
115
80 to 250
115
80 to 250

Y
230
230
350
350
510
510

Dimensions of connection pads


1000

1350

1600

2000

2500

3200

4000

5000
DD202182

Rating (A)
Drilling for connection (mm)
Thickness of conductor = 6 mm.

80

version: 1.1

K9CE24010.indd

DD210833

Flat elbow feed units


Type

Position of
neutral

Cat. no.

Made to measure N3

3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppER33

KTCppppER43

KTCppppER53

N4

KTCppppER34 KTCppppER44 KTCppppER54


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppER5p by
KTCppppER7p.

DD210835

KTCppppERp3(3), 3L + N + PE or PER KTCppppERp4(3), 3L + N + PE or PER

DD210834

KTCppppERp3

(1) See the "Trunking cross-section" table below.


(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
(3) 3L + PE version, see page 80.

KTCppppERp4

Tableau of dimensions
Rating (A)

Neutral

1000 to 1600 N3, N4


2000 to 3200 N3, N4
4000 and 5000 N3, N4

Dimensions (mm)
A
200 to 534
200 to 534
200 to 534

B
300
300
300

J, K, M
80 to 250
80 to 250
80 to 250

Y
230
350
510

DD210836

Cut-out drawing for feed units placed directly on the device roof

Table of dimensions
Rating (A)

Dimensions (mm)

Y
1000 to 1600 230
2000 to 3200 350
4000 and 5000 510

U
K/2 + J + 80
K/2 + J + 80
K/2 + J + 80

V
K/2 + M + 80
K/2 + M + 80
K/2 + M + 80

For the 3L + PE version, consider M = J to calculate the Y quotation.

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

K9CE24010.indd

version: 1.1

81

Feed units for switchboards and


oil immersed transformers

Catalogue numbers and


dimensions

IP55
Canalis KTC

DD210837

Edgewise elbow feed units


Type

Position of
neutral

Made to measure N5

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppER35

KTCppppER45

KTCppppER55

N6

KTCppppER36 KTCppppER46 KTCppppER56


(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppER5p by
KTCppppER7p.
DD210839

KTCppppERp5 (3), 3L + N + PE ou PER KTCppppERp6 (3), 3L + N + PE ou PER

DD210838

KTCppppERp5

(1) See the "Trunking cross-section" table opposite.


(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
(3) 3L + PE version, see page 80.
KTCppppERp6

Table of dimensions
Rating (A) Neutral

Dimensions (mm)

1000
1350
1600
2000
2500
3200
4000
5000

A
175 to 509
190 to 524
200 to 534
220 to 554
240 to 574
260 to 594
300 to 634
340 to 674

N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6
N5, N6

B
275
290
300
320
340
360
400
440

J, K, M
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250
80 to 250

Y
230
230
230
350
350
350
510
510

DD210836

Cut-out drawing for feed units placed directly on the device

For the 3L + PE version, consider M = J


to calculate the Y quotation.
Table of dimensions
Rating (A)

Dimensions (mm)

Y
1000 to 1600 230
2000 to 3200 350
4000 and 5000 510

U
K/2 + J + 80
K/2 + J + 80
K/2 + J + 80

V
K/2 + M + 80
K/2 + M + 80
K/2 + M + 80

Dimensions of connection pads


1000

1350

1600

2000

2500

3200

4000

5000
DD202182

Rating (A)
Drilling for connection (mm)
Thickness of conductor = 6 mm.

82

version: 1.1

K9CE24010.indd

Bar feed units, flat outlets


Cat. no.
3L + PE

DD202315

Type

3L + N + PE
3L + N + PER (1)
Made to measure
KTCppppER37 KTCppppER47 KTCppppER57
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppER57 by
KTCppppER77.
Connection pad dimensions are identical to those of the feed units.

DD202316

KTCppppERp7
3L + N + PE ou PER

DB402690

KTCppppERp7

3L + PE

(1) See the "Trunking cross-section" table below.


Table of dimensions
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Dimensions (mm)
A
235 to 734
235 to 734
235 to 734

P-Q
160 to 600
160 to 600
160 to 600

S - R ou R - S
160 to 600
160 to 600
160 to 600

Q, R, S minimum
80
80
80

Y
230
350
510

DD202317

Cut-out drawing for straight feed units connected directly to the device

For the 3L + PE version,


consider S = 0 to calculate
the V quotation.
Table of dimensions
Rating (A)

Dimensions (mm)

Y
1000 to 1600 230
2000 to 3200 350
4000 and 5000 510

U = P + 80

if S > R, V = S + 80
if R > S, V = R + 80

Trunking cross-section
3L + PE
3L + N + PE
3L + N + PER

1000
19
23
25

1350
25
31
33

1600
29
35
39

2000
36
45
49

2500
44
55
60

DD210867

Height H (mm)
Width W (mm)

K9CE24010.indd

3200
51
64
71

4000
66
84
92

5000
82
104
114
DD202180

Rating (A)
Weight (kg/m)

version: 1.1

83

Rigid protective covers

Catalogue numbers and


dimensions

IP55

Canalis KTC
Ordering
To order a protective cover onto which a feed connector is fitted, the parameters D,
G and Z, which depend on the feed connector, must be given.
Example: the catalogue number of a rigid vertical protective cover with dimension
Y = 350 mm intended for a feed unit with different between centre dimensions D, G
and Z (in mm) is:
KTB0350CR2, D = 330, G = 450 and Z = 500.

Rigid horizontal protective covers for feed units ER N1 to N7

DD202325

Important : when ordering a horizontal cover, make sure you indicate dimensions "D, G and Z"
with the catalogue number.
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Dimensions "Y" (mm)


230
350
510

Cat. no.
KTB0230CR1
KTB0350CR1
KTB0510CR1

Weight (kg)
12.00
12.00
12.00

KTBppppCR1

DD202326

KTBppppCR1

Protective cover for ER N1 to N6 straight end feed connectors


Dimensions D and G are determined by the between centres dimensions (J, K and M) of the
end feed connector bars to be protected.
The position of the neutral on the feed connector also determines the rule to be used for
calculating parameters D and G.
If the feed connector comes into the cover with the neutral on the right:
D = K/2 + M + 100
G = K/2 + J + 100
If the feed connector comes into the cover with the neutral on the left:
D = K/2 + J + 100
G = K/2 + M + 100
For the 3L + PE version, consider M = J to calculate the D and G quotations.
Table of dimensions
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Dimensions (mm)
Y
230
350
510

D
220 to 475
220 to 475
220 to 475

G
220 to 475
220 to 475
220 to 475

Z
310 to 800
430 to 800
590 to 800

Protective cover for ER N7 straight end feed connectors


Dimensions D and G are determined by the between centres dimensions (P, Q, R and S) of the
end feed connector bars to be protected.
Position of the neutral on the feed connector also determines the rule to be used for calculating
parameters D and G.
If the feed connector comes into the cover with the neutral on the right:
D = max(R ; S) + 100
G = max(P ; Q) + 100
If the feed connector comes into the cover with the neutral on the left:
D = max(P ; Q) + 100
G = max(R ; S)+ 100
For the 3L + PE version, consider S = 0 to calculate the D and G quotations.
Table of dimensions
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

84

Dimensions (mm)
Y
230
350
510

D
340 to 1000
340 to 1000
340 to 1000

version: 1.1

G
340 to 1000
340 to 1000
340 to 1000

Z
310 to 800
430 to 800
590 to 800

K9CE24010.indd

Rigid vertical protective covers for feed units ER N1 to N7


Important: when ordering a vertical cover, make sure you indicate dimensions D, G and Z
with the catalogue number.
DD202321

400 to 800 mm high covers


Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Dimensions "Y" (mm)


230
350
510

Cat. no.
KTB0230CR2
KTB0350CR2
KTB0510CR2

Weight (kg)
40.00
40.00
40.00

DD202322

KTBppppCR2

KTBppppCR2

Dimensions D and G are determined by the between centres dimensions (J, K and M) of
the end feed connector bars to be protected.
D = K/2 + J + 100
G = K/2 + M + 100
For the 3L + PE version, consider M = J to calculate the D and G quotations.
Table of dimensions for ER N1 to N6 straight feed units
Rating (A)

DD202323

1000 to 1600
2000 to 3200
4000 and 5000

Dimensions (mm)
Y
230
350
510

D
220 to 475
220 to 475
220 to 475

G
220 to 475
220 to 475
220 to 475

Z
400 to 800
400 to 800
400 to 800

100 to 400 mm high covers


Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000

Dimensions "Y" (mm)


230
350
510

Cat. no.
KTB0230CR3
KTB0350CR3
KTB0510CR3

Weight (kg)
17.00
17.00
17.00

KTBppppCR3

DD202324

KTBppppCR3

Dimensions D and G are determined by the between centres dimensions of the end feed
connector bars to be protected.
Table of dimensions for ER N1 to N6 straight feed units
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000
D = K/2 + J + 100
G = K/2 + M + 100

Dimensions (mm)
Y
230
350
510

D
220 to 475
220 to 475
220 to 475

G
220 to 475
220 to 475
220 to 475

Z
100 to 400
100 to 400
100 to 400

For the 3L + PE version, consider M = J to calculate the D and G quotations.


Table of dimensions for ER N7 straight feed units
Rating (A)
1000 to 1600
2000 to 3200
4000 and 5000
D = max (P ; Q) + 100
G = max (R ; S) + 100

Dimensions (mm)
Y
230
350
510

D
220 to 475
220 to 475
220 to 475

G
220 to 475
220 to 475
220 to 475

Z
100 to 400
100 to 400
100 to 400

For the 3L + PE version, consider S = 0 to calculate the D and G quotations.

K9CE24010.indd

version: 1.1

85

Catalogue numbers and


dimensions

Adjustable protective covers for


oil immersed transformers
IP55

Canalis KTC
Ordering
There is no need to add technical comments to the catalogue number ordered.

Adjustable protective covers for horizontal incomers

DD210872n

DD202871

Height adjustable cover for the fitting of a feed unit with between centre dimensions of
150 or 170 mm depending on the rating.
Never use with HV porcelaine bushings.
Rating (A)
Between centres Dimensions "Y"
Cat. no.
Weight (kg)
"J, K and M" (mm) (mm)
1000 and 1350
150
230
KTB0230CR7
30.00
1600
150
230
KTB0230CR72 30.00
2000 and 2500
170
350
KTB0350CR7
36.00
3200
170
350
KTB0350CR72 36.00
4000 and 5000
170
510
KTB0510CR7
42.00
KTBppppCR5

KTBppppCR5

Table of dimensions
Rating (A)
1000 and 1350
1600
2000 and 2500
3200
4000 and 5000

Dimensions (mm)
Y
230
230
350
350
510

Z
565
565
825
825
905

X
450
450
650
650
650

A
830
830
890
890
960

B
750
750
810
810
880

E
330
330
350
350
460

F
125
125
265
265
185

G
365
365
485
485
645

Adjustable protective covers for vertical incomers


DD202869

Height adjustable cover for the fitting of a feed unit with between centre dimensions of
150 or 170 mm depending on the rating.
Never use with HV porcelaine bushings.
Rating (A)

Dimensions "Y"
(mm)
230
230
350
350
510

Cat. no.

Weight (kg)

KTB0230CR8
KTB0230CR82
KTB0350CR8
KTB0350CR82
KTB0510CR8

30.00
30.00
36.00
36.00
42.00

DD210870n

1000 and 1350


1600
2000 and 2500
3200
4000 and 5000
KTBppppCR8

Between centres
"J, K and M" (mm)
150
150
170
170
170

KTBppppCR8

Table of dimensions
Rating (A)
1000 and 1350
1600
2000 and 2500
3200
4000 and 5000

86

Dimensions (mm)
Y
230
230
350
350
510

Z
600
600
600
600
600

A
830
830
890
890
960

B
750
750
810
810
880

version: 1.1

C
345
345
460
460
625

E
330
330
350
350
460

K9CE24010.indd

Flexible protective covers


Cable boxes
IP55

DD202318

Flexible vertical protective covers for straight feed units


Covers for ER N1 to N7 straight feed units with between centre dimensions = 115 mm.
Rating (A)
Dimensions "Y" (mm)
Cat. no.
1000 to 1600
230
KTB0230CS0
2000 to 3200
350
KTB0350CS0
4000 and 5000
510
KTB0510CS0
It is recommended to use insulating sheaths KTB0000YF1 with connection braids
KTB0000YT1.

Weight (kg)
15.00
17.00
19.00

DD202319

KTBppppCS0
Table of dimensions

KTBppppCS0

Rating (A)

Dimensions (mm)

1000 to 1600
2000 to 3200
4000 and 5000

Y
230
350
510

C
200 to 650
200 to 650
200 to 650

DD202320

Cut-out drawing for fixing the flexible vertical protective cover

DD202327

Cable boxes
Rating (A)
Dimensions "Y" (mm)
Cat. no.
Weight (kg)
1000 to 1600
230
KTB0230BC01 15.00
2000 to 3200
350
KTB0350BC01 17.00
4000 and 5000
510
KTB0510BC01 19.00
Cable boxes are only to be used on ER N1 to N6 straight feed units with standard between
centre distances = 115 mm.

KTBppppBC01

DD202328

KTBppppBC01

Cable entry.
Aluminium plate to be drilled.
Table of dimensions
Rating (A)

Dimensions (mm)

Y
1000 to 1600
230
2000 to 3200
350
4000 and 5000
510
See table page 83 for connection pad dimensions.

K9CE24010.indd

version: 1.1

87

Feed units for dry-type


transformers

Catalogue numbers and


dimensions

IP55
Canalis KTC

Ordering
Complete the catalogue number by replacing "pppp" by the rating.
Important:
b add the dimensions of the selected unit as a technical comment.
Example: the catalogue number of a 3200 A end feed unit, N2, 3L + N + PER, with
a between centre distance E = 550 mm, length N = 310 mm and phase order
T = 3N21 is:
KTC3200EL52, E = 550 mm, N = 310 mm and T = 3.
Rating

DD202329

N1 and N2 feed units for dry-type transformers


Type

Position of
neutral

Cat. no.

Made to measure N1

3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppEL31

KTCppppEL41

KTCppppEL51

N2
KTCppppEL32 KTCppppEL42 KTCppppEL52
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppEL5p by
KTCppppEL7p.
For an installation with flat mounted busbar trunking, add angle brackets between the
transformer and the feed unit, see page 91.
For fixing supports, see KTBppppZA4 page 98.

DD210330n

KTCppppELp1, KTCppppELp2

DD202331

KTCppppELp1

(1) See the "Trunking cross-section" table in the following page.


Table of dimensions
KTCppppELp2

Rating (A)

Neutral

1000 to 1600 N1, N2


2000 to 5000 N1, N2

Dimensions (mm)
E
N
390 to 700 195 to E - 195
470 to 700 235 to E - 235

X
160
200

Selecting phase order T

-1/2

-1/2

L1 L2 L3 N PE

-1/2

L1 L2 L3 N PE

DD230219

Views according to F

-1/2

-1/2

KTCppppELp2
L1 L2 L3 N PE

L1 L2 L3 N PE

KTCppppELp1

-1/2

L1 L2 L3 N PE

DD230220

KTCppppELp2

L1 L2 L3 N PE

Top views
KTCppppELp1

88

version: 1.1

K9CE24020.indd

N3 and N4 feed units for dry-type transformers


DD202333

Type

Position of
neutral

Made to measure N3

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (1)

KTCppppEL33

KTCppppEL43

KTCppppEL53

N4
KTCppppEL34 KTCppppEL44 KTCppppEL54
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppEL5p by
KTCppppEL7p.
For an installation with flat mounted busbar trunking, add angle brackets between the
transformer and the feed unit, see page 91.
For fixing supports, see KTBppppZA4 page 98.

DD210335n

KTCppppELp3, KTCppppELp4

DD202334

KTCppppELp3

(1) See the "Trunking cross-section" table below.


Table of dimensions
Rating
(A)

Neutral

Dimensions (mm)
E
N
390 to 700 195 to E - 195

1000 to 1600 N3, N4

F
0 to 200

X
160

KTCppppELp4

Selecting phase order T

-1/2

L1 L2 L3 N PE

-1/2

L1 L2 L3 N PE
DD230221

-1/2

-1/2

KTCppppELp4
L1 L2 L3 N PE

L1 L2 L3 N PE

KTCppppELp3

-1/2

-1/2

KTCppppELp4
L1 L2 L3 N PE

DD230222

Top views
KTCppppELp3

L1 L2 L3 N PE

Views according to F

Trunking cross-section
See page 91.

K9CE24020.indd

version: 1.1

89

DD202340

Angle brackets for installing N1 to N5 feed units flat


Description

Rating (A)

4 angle brackets 1000 to 1600


+ screws
2000 to 5000

Phase width "X" (mm)

Cat. no.

160

KTB0000YE1

200

KTB0000YE2

DD210341n

KTB0000YE1, KTB0000YE2

KTB0000YE1, KTB0000YE2

Trunking cross-section
Weight (kg/m)

1000

1350

1600

2000

2500

3200

4000

5000

3L + PE

19

25

29

36

44

51

66

82

3L + N + PE

23

31

35

45

55

64

84

104

3L + N + PER

25

33

39

49

60

71

92

114
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

(1) Important: for the 800 A rating, indicate "KTC0800".

K9CE24020.indd

version: 1.1

91

Protective covers for dry-type


transformers

Catalogue numbers and


dimensions

IP55
Canalis KTC

Ordering
There is no need to add technical comments to the catalogue number ordered.

Adjustable vertical protective covers for EL, N1 to N4 feed units, edgewise mounting
DD202342

Type
Vertical cover

Position of neutral

Cat. no.

Weight (kg)

N1, N2, N3 and N4

KTB0000CR4

24.00

Position of neutral

Cat. no.

Weight (kg)

N1, N2, N3 and N4

KTB0000CR5

32.00

DD202344

KTB0000CR4

KTB0000CR4

Table of dimensions
Rating (A)

Dimensions (mm)

Z
Minimum
1000 to 1600
200
2000 to 3200
200
4000 and 5000 200

Maximum
350
350
350

Adjustable horizontal protective covers for EL, N1 to N4 feed units, flat mounting
DD202343

Type
Horizontal cover

DD202345

KTB0000CR5

KTB0000CR5

Table of dimensions
Rating (A)

Dimensions (mm)

Z
Minimum
1000 to 1600
330
2000 to 3200
330
4000 and 5000 330

92

Maximum
480
480
480

version: 1.1

K9CE24020.indd

DD202346

Horizontal protective covers for dry-type transformer N5 feed units


Type
Horizontal covers

Position of neutral Dimension "Y"


(mm)

Cat. no.

Weight (kg)

N5

230

KTB0230CR6

38.00

350

KTB0350CR6

40.00

510

KTB0510CR6

47.00

DD202347

KTBppppCR6

KTBppppCR6

Table of dimensions
Rating (A)

Dimensions (mm)
Y

1000 to 1600
230
2000 to 3200
350
4000 and 5000 510

Z
Minimum
380
500
660

Maximum
530
650
810

DD230224

Cut-out drawing for dry-type transformer N5 feed units

K9CE24020.indd

version: 1.1

93

Connection accessories

Catalogue numbers and


dimensions
Canalis KTC

DD202348

Connection plates
Type

Options

Number of ends drilled

Cat. no.

Weight (kg)

KTB0000YC1

2.70

KTB0000YC2

2.70

with onde 1

KTB0000YC3

2.30

KTB0000YC4

2.30

KTB0000YC5

4.50

Uninsulated -

Connector plates for low voltage


switchboards

Connector plates for transformers

KTB0000YC1

KTB0000YC3

KTB0000YC4
DD202353

DD202352

KTB0000YC2
DD202351

DD202350

Insulated
1
Each connector plate is made up 5 x 1 mm thick sheets.

DD202354

KTB0000YC5

Determining the number of connection plates required

1500

2500

1500

3200

2000

4000

2500

5000

3000

Busbar trunking 1350 to


rating (A)
1600

DD210789

1000

2000

DD210788

1000

DD210787

1600

DD210786

1350

Connection
plates

94

Connection plates per phase


Number
Section (mm2)

DD206057

Busbar trunking rating


(A)

2000 to
2500

version: 1.1

3200

4000

5000

K9CE24030.indd

DD202355

Connection braids
Description
Connection braid

Cat. no.

Weight (kg)

KTB0000YT1

2.80

DD202356

KTB0000YT1

KTB0000YT1
Determining the number of braids required
Busbar trunking rating (A)

Braids per phase


1200

1600

1200

2000

1200

2500

1800

3200

1800

4000

2400

5000

3000

Busbar
trunking rating
(A)

1350 to 2000

2500 to 3200

DD206056

DD210770

Braids

DD202376

Cross-section (mm)

DD210773

Number
1350

4000

5000

Insulating sheaths
DD230229

The YF conduit allows the various conductors of a connection performed with


braids or with bare copper foils to be insulated.
Installation is performed after complete assembly of the connection, with scratch
fastening for easier setup.
The insulating conduit is formed of a 2-metre plastic duct that can be cut to length
as needed.
Description
Insulating sheath

Cat. no.

Weight (kg)

KTB0000YF1

1.00

DD202479

KTB0000YF1

KTB0000YF1

K9CE24030.indd

version: 1.1

95

Connection accessories

Catalogue numbers and


dimensions
Canalis KTC

DD202363

Spacers
Description

Weight
(kg)

Connection torque nut kit

1 torque nut + 2 flat washers


( 60) + 1 elastic washer
( 55)

KTB0000YB1

Spacers for direct


connection

8 x 3 mm galvanized steel
spacers + 8 x 2 mm copper
spacers + 16 x M12 x 60 bolts
+ washers and nuts

KTB0000YB2

5.50

Spacer plates for connector


plate connections

8 x 3 mm galvanized steel
plates + 16 x M12 x 60 bolts +
washers and nuts

KTB0000YB3

4.00

8 x 3 mm galvanized steel
plates + 16 x M12 X 80 bolts +
washers and nuts

KTB0000YB4

4.00

Galvanized steel spacer plates


DD202366

Copper spacer
DD202365

Cat. no.

DD230233

KTB0000YB2

DD202364

KTB0000YB3

KTB0000YB4

96

version: 1.1

K9CE24030.indd

DD202359

Bar supports
Description
Bar support, 115 mm between centres
for bar of 5 or 10 mm

Cat. no.

Weight (kg)

KTB0000YS1

2.40

DD202360

KTB0000YS1

KTB0000YS1

DD202361

Bar clamps
Description
1 bar clamps

Dimensions of transformer Cat. no.


connection terminals (mm)

Weight (kg)

100

KTB0000YS2

6.40

120

KTB0000YS3

6.40

Order indivisible quantity: 8.


Each bar clamp includes 2 cross members and associated fixings.
KTB0000YS3
DD202500

DD202362

KTB0000YS2

KTB0000YSp

K9CE24030.indd

version: 1.1

97

Supports and fixings

Catalogue numbers and


dimensions
Canalis KTC

DD202372

Horizontal supports
Description

Rating
(A)

1 support from the bottom (2) Set of 2 supports from the


top for universal feeding of
dry-type transformer

Busbar trunking
height (mm)

Cat. no.

Weight
(kg)

KTB0000ZA1

2.80

1000 A

74

KTB0074ZA4

3.20

1350
5000

104 to 404

KTB0404ZA4

3.80

DD202370

KTB0000ZA1

KTB0000ZA1

DD202371

DD202368

KTBppppZA4
Table of dimensions
Height "H"
(mm)
74
104 to 404

Dimensions (mm)
A
74
86

B
160
186

C
110
136

(1) See "Busbar trunking cross-section" table opposite.


(2) Threaded rods, length = 2 metres, are supplied with the support.
KTBppppZA4

DD202369

Hooks
2 fixing grips are needed for each fixing point.
Description
1 fixing grip
Order indivisible quantity: 8.

Cat. no.

Weight
(kg)

KTB0000ZA3

0.60

98

DD202373

KTB000ZA3
KTB0000ZA3

version: 1.1

K9CE25000.indd

DD202374

Vertical supports
Description
Fixings

Rating
(A)

Busbar trunking height


(mm)

Cat. no.

Weight
(kg)

1000 to 2000

74 to 164

KTB0164ZA5

5.75

2500

204

KTB0204ZA5

10.02

3200

244

KTB0244ZA5

10.62

4000

324

KTB0324ZA5

11.82

404

KTB0404ZA5

12.58

DD202375

5000
For further detail see page 191.
KTB0164ZA5

KTBppppZA5

(1) Dimensions with free springs.


Table of dimensions

DD202499

Rating (A) Dimensions "Y" (mm)


All
50 < Y < 100
KTB0204ZA5 to KTB0404ZA5

Table of dimensions
Rating Dimensions (mm)
(A)
L
M
N
2500
202 205 152 to 202
3200
240 245 172 to 222
4000
322 325 212 to 262
5000
402 325 252 to 302

(1) Dimensions with free springs.

Trunking cross-section
1000

1350

1600

2000

2500

DD210867

Height H (mm)
Width W (mm)

K9CE25000.indd

3200

4000

5000
DD202180

Rating (A)

version: 1.1

99

Accessories

Catalogue numbers and


dimensions

Fire-barrier kit

Canalis KTC

DB401570

Fire-barrier
Type
Fire-barrier kit

Busbar trunking
rating (A)
1000
1350
1600
2000
2500
3200
4000
5000

Busbar trunking
height "H" (mm)
74
104
124
164
204
244
324
404

Fire barrier
length
650
650
650
650
650
650
650
650

Cat. no.
KTB074CF6
KTB104CF6
KTB124CF6
KTB164CF6
KTB204CF6
KTB244CF6
KTB324CF6
KTB404CF6

DB401571

The filler material around the busbar trunking must meet the requirements currently
in force to guarantee that the wall and ceiling fire-resistance class (for example
DIN 1045 and DIN 1053-1) is maintained.
Filler material not supplied.

The fire barrier kit can also be made up on site by the installer according to
Schneider Electric's drawings and specifications.
For further information, consult your sales office.

100

version: 1.1

K9CE25000.indd

63 to 100 A tap-off units from


Canalis KS range for modular
devices
Tap-off units with isolator, not equipped
Disconnection by opening the tap-off unit cover

System earthing
arrangement

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC

Tap-off polarity

3L + N + PE (2)

KSB63SMp8,
KSB100SMp12

Connection

DD205033

Tap-off diagram
(e.g. circuit breaker
protection)

Rating
(A)

Number of 18 mm
modules(3)

Max. size
(mm2)
Flexible

Rigid

63

On devices

16

100

12

On devices

35

L1 L2 L3 N PE

3L + PEN
DD205034

DD210454

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.

L1 L2 L3 N PE

Cable gland (4) Cat. no.


(not supplied)

Cat. no.

Weight
(kg)

16

ISO 50 max.

KSB63SM48

KSB63SM58

2.40

35

ISO 63 max.

KSB100SM412

KSB100SM512 5.00

(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Supplied with blanking plates:1x5 divisible (8 modules) or 2x5 divisible (12 modules).
(4) Maximum diameter for a multipolar cable.

DD210455n

DD202008

KSB63SMp8, KSB100SMp12

X = 432.5 (KSB63SMp8)
X = 545.5 (KSB100SMp12)

Cable exit
Centre line of tap-off outlets
(5) Protruding
Dimensions Rating (A)
A
B
C
D
E
F

K9CE26010_bis.indd

63
357
158
167
309
108
202

100
444
183
202
397
133
220

version: 1.1

101

125 to 160 A tap-off units from


Canalis KS range for modular
devices

Catalogue numbers
Dimensions
Canalis KTC

Tap-off units for NG modular devices, not equipped

System earthing
arrangement

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. circuit breaker
protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

DD210452

Tap-off polarity
DD210452

DD202154

The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.

KSB160SMp13
Rating
(A)

Type of
circuit-breaker

160

NG125 ou NG160
Rotary handle
28060

Connection

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

ISO 25 max.

KSB160SM513 8.50

Weight
(kg)

Flexible Rigid
Terminals

50

70

KSB160SM413

DD202008

(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD202155

KSB160SMp13

X = 625.5

Cable exit
Centre line of tap-off outlets
(4) Protruding

102

version: 1.1

K9CE26010_bis.indd

100 to 400 A tap-off units from


Canalis KS range for Compact
NSX circuit breakers
Tap-off units for Compact NSX, fixed, front-connected circuit breakers, not equipped

System earthing
arrangement

KSBpppDCp

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. circuit breaker
protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Rating
(A)

Type of
circuit breaker

Connection

Max. size
(mm2)
Flexible

Rigid

160

NSX100 or NSX160 Terminals


Curve N, H or L
Rotary handle
29338

50

250

NSX250
Curve N, H or L
Rotary handle
29338

Terminals

400

NSX400
Curve N, H or L
Rotary handle
32598

Terminals

DD210452

Tap-off polarity
DD210452

DD210461

The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

Weight
(kg)

70

ISO 25 max.

KSB160DC4

KSB160DC5

9.00

70

150

ISO 32 max.

KSB250DC4

KSB250DC5

12.50

150

240

ISO 40 max.

KSB400DC4

KSB400DC5

18.00

(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD210462

DD202008

KSB160DCp

DD202008

X = 625.5

DD210463

KSB250DCp

X = 726.5

DD202008

DD210464

KSB400DCp

X = 976.5
4

Cable exit
Centre line of tap-off outlets
(4) Protruding

K9CE26010_bis.indd

version: 1.1

103

250 to 400 A tap-off units from


Canalis KS range for Compact
NSX circuit breakers

Catalogue numbers
Dimensions
Canalis KTC

Tap-off units for measurements and metering, not equipped

System earthing
arrangement

KSBpppDCpTRE

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. circuit breaker
protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Connection

Max. size
(mm2)

Cable gland (3) Cat. no.


(not supplied)

DD210452

Tap-off outlets
DD210452

DD210465

The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.

Rating
(A)

Type of circuit
breaker

Flexible

Rigid

250

NSX250
Curve N, H or L
Rotary handle
29338

Terminals

70

150

ISO 32 max.

KSB250DC4TRE KSB250DC5TRE 13.50

400

NSX400
Curve N, H or L
Rotary handle
32598

Terminals

150

240

ISO 40 max.

KSB400DC4TRE KSB400DC5TRE 19.50

Cat. no.

Weight
(kg)

(1) The neutral must be protected or not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible).
(3) Maximum diameter by unipolar cable.

DD202085

DD202008

KSB250DCpTRE

X = 726.5

DD202008

DD202086

KSB400DCpTRE

X = 976.5

Cable exit
Centre line of tap-off outlets
(4) Protruding

104

version: 1.1

K9CE26010_bis.indd

50 to 100 A tap-off units from


Canalis KS range for NF fuses

Tap-off units with isolator for cylindrical fuses


Disconnection by opening the tap-off unit cover

System earthing
arrangement

KSBpppSFp

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Rating
(A)

For fuses
(not supplied)

Connection

Max. size
(mm2)

50

NF 14 x 51
Type gG : 50 A max.
Type aM : 50 A max.

Terminals

25

100

NF 22 x 58
Terminals
Type gG : 100 A max.
Type aM : 100 A max.

50

DD210471

Tap-off polarity
DD210470

DD210466

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

Weight
(kg)

25

ISO 50 max.

KSB50SF4

KSB50SF5

2.40

50

ISO 63 max.

KSB100SF4

KSB100SF5

5.00

Flexible Rigid

(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.

DD210467n

DD202008

KSB50SFp, KSB100SFp

X = 432.5 (KSB50SFp)
X = 545.5 (KSB100SFp)

Cable exit
Centre line of tap-off outlets
(4) Protruding
Dimensions Rating (A)
A
B
C
D
E
F

K9CE26010_bis.indd

50
356
153
167
309
103
202

100
444
178
202
397
128
220

version: 1.1

105

100 to 400 A tap-off units from


Canalis KS range for NF fuses

Catalogue numbers
Dimensions
Canalis KTC

Tap-off units with isolator for blade-type fuses


Disconnection by opening the tap-off unit cover

System earthing
arrangement

Rating
(A)

For blade-type fuses


(not supplied)

DD210472

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Connection

DD210470

Tap-off polarity

KSB400SEp

KSB160SEp
KSB250SEp

Busbar trunking

Max. size
(mm2)

Cable gland
(not supplied)

Flexible

Rigid

DD210471

DD202012

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised. It is possible to install an OF contact triggered by cover
opening (see the "Accessories" section, page 110.

Cat. no.

Cat. no.

Weight
(kg)

100

Size 00
Terminals
Type gG : 100 A max.
Type aM : 100 A max.

50

50

ISO 63 (3) max. KSB100SE4 (5)

KSB100SE5 (5) 5.00

160

Size 00
Terminals
Type gG : 160 A max.
Type aM : 160 A max.

35

50

ISO 20 (4) max. KSB160SE4

KSB160SE5

11.00

Size 0
Terminals
Type gG : 160 A max.
Type aM : 160 A max.

35

50

ISO 20 (4) max. KSB160SF4

KSB160SF5

11.00

250

Size 1
Terminals
Type gG : 250 A max.
Type aM : 250 A max.

150

150

ISO 32 (4) max. KSB250SE4

KSB250SE5

20.00

400

Size 2
Terminals
Type gG : 400 A max.
Type aM : 400 A max.

240

240

ISO 40 (4) max. KSB400SE4

KSB400SE5

29.20

(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100A dimensions, see "Tap-off units with insulators for cylindrical fuses", page 105,
catalogue number KSB100SFp.

(1)

DD210473n

DD202008

KSB160SEp, KSB250SEp
Dimensions Rating (A)
A
B
C
D
E
F
G
H

(2)

(1)
6

X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)

160
450
257
300
395
207
32
32
182

250
600
308
400
548
258
32
32
192

DD202008

DD210474n

KSB400SEp

X = 855

Cable exit : (1) exit of KSB160Spp, (2) exit of KSB250SEp


Centre line of tap-off outlets
(6) Protruding

106

version: 1.1

K9CE26010_bis.indd

25 to 63 A tap-off units from


Canalis KS range for DIN fuses

Tap-off units with isolator for screw-type fuses


Disconnection by opening the tap-off unit covert

System earthing
arrangement

KSBppSpp

Busbar trunking

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC (2)


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Rating
(A)

For fuses
(not supplied)

Connection

Max. size
(mm2)

25

Diazed E27

Terminals

25

50

Noezd E18

Terminals

25

63

Diazed E33

Terminals

25

DD210471

Tap-off polarity
DD210470

DD210466

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.

Cable gland (3) Cat. no.


(not supplied)

Cat. no.

Weight
(kg)

25

ISO 50 max.

KSB25SD4

KSB25SD5

2.40

25

ISO 50 max.

KSB50SN4

KSB50SN5

2.40

25

ISO 63 max.

KSB63SD4

KSB63SD5

2.40

Flexible Rigid

(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a multipolar cable.

DD202008

DD205037

KSBppSpp

X = 432.5 (KSB25SDp, KSB50SNp)


X = 545.5 (KSB63SDp)

Cable exit
Centre line of tap-off outlets
(4) Protruding
Dimensions Rating (A)
A
B
C
D
E
F

K9CE26010_bis.indd

25 and 50
356
153
167
309
103
202

63
444
178
202
397
198
220

version: 1.1

107

100 to 400 A tap-off units from


Canalis KS range for DIN fuses

Catalogue numbers
Dimensions
Canalis KTC

Tap-off units with isolator for blade-type fuses


Disconnection by opening the tap-off unit cover

System earthing
arrangement

Rating
(A)

For blade-type fuses


(not supplied)

DD210472

TT-TNS-TNC-IT (1) TNC

Tap-off unit

TT-TNS-TNS-IT (1) TNC


3L + N + PE (2)

3L + PEN

Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

L1 L2 L3 N PE

Connection

DD210470

Tap-off polarity

KSB400SEp

KSB160SEp
KSB250SEp

Busbar trunking

Max. size
(mm2)

Cable gland
(not supplied)

Flexible

Rigid

DD210471

DD202012

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised. It is possible to install an OF contact triggered by cover
opening (see the "Accessories" section, page 110.

Cat. no.

Cat. no.

Weight
(kg)

100

Size 00
Terminals
Type gG : 100 A max.
Type aM : 100 A max.

50

50

ISO 63 (3) max. KSB100SE4 (5)

KSB100SE5 (5) 5.00

160

Size 00
Terminals
Type gG : 160 A max.
Type aM : 160 A max.

35

50

ISO 20 (4) max. KSB160SE4

KSB160SE5

11.00

250

Size 1
Terminals
Type gG : 250 A max.
Type aM : 250 A max.

150

150

ISO 32 (4) max. KSB250SE4

KSB250SE5

20.00

400

Size 2
Terminals
Type gG : 400 A max.
Type aM : 400 A max.

240

240

ISO 40 (4) max. KSB400SE4

KSB400SE5

29.20

(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed, IT system also possible only if N not
distributed).
(3) Maximum diameter for a unipolar cable.
(4) Cable gland for multipolar cable only.
(5) For 100A dimensions, see "Tap-off units with insulators for cylindrical fuses", page 105,
catalogue number KSB100SFp.

(1)

DD210473n

DD202008

KSB160SEp, KSB250SEp
Dimensions Rating (A)
A
B
C
D
E
F
G
H

(2)

(1)
6

X = 577.5 (KSB160SEp)
X = 777 (KSB250SEp)

160
450
257
300
395
207
32
32
182

250
600
308
400
548
258
32
32
192

DD210474n

DD202008

KSB400SEp

X = 855

Cable exit : (1) exit of KSB160Spp, (2) exit of KSB250SEp


Centre line of tap-off outlets
(6) Protruding

108

version: 1.1

K9CE26010_bis.indd

32 to 160 A tap-off units from


Canalis KS range for BS fuses

Tap-off units for screw-mounted fuses


Disconnection by unplugging the tap-off unit

System earthing
arrangement

DD202014

KSB160SG4

Busbar trunking

TT-TNS-TNC-IT (1)

Tap-off unit

TT-TNS-TNS-IT (1)

Tap-off polarity

3L + N + PE (2)

Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

Connection

DD210470

DD202013

Tap-off unit disconnection by opening or closing the cover should be carried out only if the
downstreamload is de-energised.

Rating
(A)

For fuses
(not supplied)

Max. size
(mm2)

Cable gland
(not supplied)

Cat. no.

Weight
(kg)

Flexible

Rigid

32

BS88 A1

Terminals

25

25

ISO 50 (3) maxi.

80

BS88 A1 or A3

Terminals

KSB32SG4

2.40

35

50

ISO 63 or
ISO 20 (3) maxi.

KSB80SG4

5.00

160

BS88 B1 or B2

Terminals

35

50

ISO 20 (4) maxi.

KSB160SG4

11.00

(1) The neutral must be not distributed (3L+PE) for the IT system.
(2) Also suitable for tap-off unit 3L + PE (N not distributed).
(3) Maximum diameter for a multipolar cable.
(4) Maximum diameter for a unipolar cable.

KSBppSG4

DD202267n

DD202008

KSB32SG4, KSB80SG4
Dimensions Rating (A)
A
B
C
D
E
F

32
356
153
167
309
103
202

80
444
178
202
397
128
220

DD202008

X = 432.5 (KSB32SG4)
X = 545.5 (KSB80SG4)

DD202015n

KSB160SG4

X = 577.5

Cable exit
Centre line of tap-off outlets
(5) Protruding

K9CE26010_bis.indd

version: 1.1

109

Catalogue numbers
Dimensions

Accessories for tap-off units


from Canalis KS range

Canalis KTC
Accessories for all tap-off units for modular devices
Designation

Description

Modular blanking plate Divisible set of 10 x 5

Cat. no.

Weight
(kg)

13940

0.08

Set of 12 label-holders (H = 24 mm,


W = 180 mm)

08905

Set of 12 labels (H = 24 mm, W = 432 mm)

08903

Set of 12 divisible labels (H = 24 mm,


08907
W = 650 mm)
(1) Self-adhesive support complete with transparent cover and paper label.

Adhesive label (1)

Accessories for all sheet-metal tap-off units


Designation

For tap-off unit

Cover contact
KSB100Sp to KSB400Sp
(break before opening)

110

version: 1.1

Order in
multiples of

Cat. no.

Weight
(kg)

KSB400ZC1 0.03

K9CE26010_bis.indd

Bolted tap-off units from


Canalis KT for Compact NSX/NS
400 to 1250 A circuit breakers
Bolted tap-off units for Compact NSX/NS with front connections (1)
3L + PEN

Tap-off diagram
(e.g. circuit breaker
protection)

L1 L2 L3 PE

L1 L2 L3 N PE

L1 L2 L3 N PE

Rating
(A)

Type of circuit breaker

400 to
630

NSX400 or NSX630
Rotary handle 32598

3 x 300

150

KTB0630CB3

KTB0630CB4

KTB0630CB5 35.00

800 to
1000

NSX800 or NSX1000 (3) 4 x 300


Rotary handle
33878

200

KTB1000CB3

KTB1000CB4

KTB1000CB5 45.00

240

KTB1250CB3

KTB1250CB4

KTB1250CB5 50.00

(2)

Max. connection capacity


(mm2)

DD210452

3L + N + PE
3L + N + PER
DD210451

3L + PE
DD230225

Tap-off polarity

Phases and neutral

1250 (4) NSX1250


Rotary handle
33878

4 x 300

Cat. no.

Weight
(kg)

PE

DD202451

(1) Installation KTAppppEBppp bolted section only.


(2) Circuit breaker and rotary handle not supplied.
(3) It is recommended a derating factor of 0.93 be applied when using a Compact NS1000
type L circuit breaker.
(4) IP31 only.

DD210462

KTBppppCBp from 400 to 1000 A

DD202497

KTB0630CBp

Table of dimensions
Dim.

A
B
C
D
E

400 to
630
860
350
300
547
315

800 to
1000
1130
550
330
710
510

DD230206

KTB1000CBp

Rating (A)

DD230207

From 1250 A

DD210880

KTB1250CBp

Cable exit
Center line of tap-off outlets
Axis of Canalis KT
Connection box to be fitted above or below

K9CE26020_bis.indd

version: 1.1

111

Catalogue numbers and


dimensions

630 and 1000 A bolted tap-off


units with switch-disconnetors
for DIN fuses
IP31

Canalis KTC

Bolted tap-off units with switch-disconnectors (1)


3L + PEN

Tap-off diagram
(e.g. circuit breaker
protection)

L1 L2 L3 PE

L1 L2 L3 N PE

L1 L2 L3 N PE

Max. connection capacity


(mm2)

DD230228

3L + N + PE
3L + N + PER
DD230226

3L + PE
DD230227

Tap-off polarity

Rating
(A)

DIN fuse size


(not supplied) (2)

630 (3)

T3

3 x 300

150

KTB0630HF3

KTB0630HF4

KTB0630HF5

54.00

1000 (3)

T4

4 x 300

200

KTB1000HF3

KTB1000HF4

KTB1000HF5

96.00

Phases and neutral

Cat. no.

Weight
(kg)

PE

DD230200

(1) Installation KTAppppEBppp bolted section only.


(2) Switch-disconnectors and rotary handle supplied.
(3) Derating coefficient to apply:0.8.

DD230223

KTBppppHFp

DD230203

KTB0630HFp

Table of dimensions
Dim.

DD210880

KTB1000HFp

112

A
B
C
D
E

Rating (A)
630
1108
480
300
786.5
315

1000
1438
690
330
1010
510

Cable exit
Center line of tap-off outlets
Axis of Canalis KT
Connection box to be fitted above or below

version: 1.1

K9CE26020_bis.indd

Coupling isolators from


1000 to 2500 A

Compact NS type NA coupling isolators


DD202377

Fits equally on ducting in a flat position, on the edge or vertically.


Tap-off unit door locking is achieved using a door key lock.
Rating Type of isolator Cat. no.
(A)
(supplied)
3L + PE

3L + N + PE

3L + N + PER (1)

Weight
(kg)

1000

NS1000 NA

KTC1000SL31

KTC1000SL41

KTC1000SL51

150.00

1350 (1)

NS1250 NA

KTC1350SL31

KTC1350SL41

KTC1350SL51

165.00

1600
NS1600 NA
KTC1600SL31
KTC1600SL41
KTC1600SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppSL51 by
KTCppppSL71.

180.00

KTCppppSLp1

DD202381

DD230214

KTCppppSLp1

(1) Rated current : 1250 A.


(2) See the "Trunking cross-section" table below.

Interpact INV coupling isolators


DD202377

Fits equally on ducting in a flat position, on the edge or vertically.


Tap-off unit door locking is achieved using a door key lock.
Rating Type of isolator Cat. no.
(A)
(supplied)
3L + PE

3L + N + PE

3L + N + PER (1)

Weight
(kg)

KTC2000SL41

KTC2000SL51

200.00

2500
INV2500
KTC2500SL31
KTC2500SL41
KTC2500SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppSL51 by
KTCppppSL71.

210.00

2000

INV2000

KTC2000SL31

DD202378

KTCppppSLp1

DD202381

KTCppppSLp1

(1) See the "Trunking cross-section" table below.

Trunking cross-section
1000

1350

1600

2000

2500

DD210867

Height H (mm)
Width W (mm)

K9CE26030_bis.indd

3200

4000

5000
DD202180

Rating (A)

version: 1.1

113

Coupling isolators 3200 A

Catalogue numbers and


dimensions
Canalis KTC
Masterpact NW coupling isolators
DD230212

Notice: If the coupling isolator is installed on a horizontal busbar trunking the


device must be only used as a disconnector and without any accessories (MX, XF,
Motor MCH...).
Rating Type of isolator Cat. no.
(A)
(supplied)
3L + PE

3L + N + PE

3L + N + PER (1)

3000 (2) NW3200 HA


KTC3200SL31 KTC3200SL41 KTC3200SL51
(1) To order the 3L+N+PER version with reinforced Icc, replace KTCppppSL51 by
KTCppppSL71.
(2) The use of this coupling isolator requires derating the busway run to 3000 A.

Weight
(kg)
360.00

DD205942

KTC3200SLp1

KTC3200SLp1

244

114

version: 1.1

K9CE26030_bis.indd

Protection of the run using


Compact NS circuit breakers
from1000 1600 A
Protection of the run using Compact NS circuit breakers
DD202377

Fits equally on ducting in a flat position, on the edge or vertically.


Tap-off unit door locking is achieved using a door key lock.
Rating Type of
(A)
isolator (3)
(supplied)

Cat. no.
3L + PE

3L + N + PE

3L + N + PER (4)

Weight
(kg)

1000

NS1000 N

KTC1000PL31

KTC1000PL41

KTC1000PL51

150.00

1350 (1)

NS1250 N

KTC1350PL31

KTC1350PL41

KTC1350PL51

165.00

1600

NS1600 N

KTC1600PL31

KTC1600PL41

KTC1600PL51

180.00

DD230214

KTCppppPLp1

DD202381

KTCppppPLp1

(1) Rated current : 1250 A.


(2) See the "Trunking cross-section" table below.
(3) Manual fixed compact NS circuit breakers type N equipped with a Micrologic 2.0 control
unit.
(4) To order the 3L+N+PER version with reinforced Icc, replace KTCppppPL51 by
KTCppppPL71.

Protection of a run > 1600 A


To install protection of a run > 1600 A, consult your sales office.

Trunking cross-section
1000

1350

1600

2000

2500

DD210867

Height H (mm)
Width W (mm)

K9CE26030_bis.indd

3200

4000

5000
DD202180

Rating (A)

version: 1.1

115

Special products

Catalogue numbers and


dimensions
Canalis KTC

For further information about the use and the dimensions, consult your sales office.

Double skin aluminium enclosure

DD210882

DD210884

For outdoor applications.

Reduction sections
DD210883

For reducing busbar trunking ratings.


Note: must be used in conjunction with appropriate protection.
Table of sizes
A

B
74

104

124

164

204

244

324

404

74
104
124
164
204
244
324
404

DD230234

Available.

DD210817

Edgewise elbow with made to measure angles

116

version: 1.1

K9CE27000_bis.indd

DD210885

4-limb zed unit

DD210881

Edgewise/flat elbow feed unit

On demand
b
b
b
b

K9CE27000_bis.indd

Surface treatment on conductors for corrosive atmospheres.


Special colours.
Seaworthy packaging.
etc.

version: 1.1

117

Canalis KH substitution by
Canalis KT

Catalogue numbers and


dimensions

new

KTC/KGF connection elements

Canalis KTC or KGF


Connection elements
Cat. no.

DB401490

Ratings

3L + PE

3L + N + PE

3L + N + PER

Weight (kg)

KTB0350HT01

KTB0350HT01

KTB0350HT01

63.00

KTB0350HT02

KTB0350HT02

KTB0350HT02

80.00

KTB0510HT01

KTB0510HT01

88.00

KTB0510HT02

KTB0510HT02

127.00

KTB0510HT03

KTB0510HT03

137.00

See the table


KTB0510HT01
below
KTB0510HT02
KTB0510HT03

KTB0pppHT0

DB402128

End feed units (E=115) are not included in the reference and must be ordered separately.

Table of dimensions
B

KTB0350HT01 850

331.5

518.5

300

300

600

258

208

466

KTB0350HT02 850

331.5

518.5

300

300

600

258

208

466

KTB0510HT01 890

310

580

300

300

600

329

306

635

KTB0510HT02 890

310

580

300

300

600

329

306

635

KTB0510HT03 890

310

580

300

300

600

329

306

635

DB402831

DB402830

KGF type Rating L busway KT type

Rating H busway H flange Connection ref.

KGF16

1600

166

KTC1600

1600

124

230

KTB0350HT01

KGF26

2750

238

KTC3200

3200

244

350

KTB0350HT02

KGF36

3750

310

KTC4000

4000

324

510

KTB0510HT01

KGF46

5000

382

KTC5000

5000

404

510

KTB0510HT02

KGF56

5000

454

KGF16

KGF26

KTC1600

KTC3200

Line extension with KT is not possible


KGF36

KGF46

KTC4000

KGF Polarity

KGF56

KTC5000

KTC Polarity

3L+PE

3L+PE

3L+1/2N+PE

3L+N+PE

3L+N+PE

3L+N+PE

3L+N+PER (1)

3L+N+PER

(1) Version with 120 mm2 cu conductor or entire conductor.

118

version: 1.1

K9CE27000_bis.indd

new

Preserved KH tap-off units


and substitution table

Plug-in tap-off units


Protection type
Isolator and fuse carriers

Polarity

Rating

Catalogue number

Status

Substitued by

3L+PE

160
250
400
630
160
250
400
630
160
250
400
630

KH016SD13
KH025SD13
KH040SD13
KH063SD13
KH016SD14
KH025SD14
KH040SD14
KH063SD14
KH016SD15
KH025SD15
KH040SD15
KH063SD15
KH063SD1530758
KH016SD24
KH025SD24
KH040SD24
KH063SD24
KH020SD33
KH031SD33
KH050SD33
KH005SD34
KH010SD34
KH020SD34
KH025SE341
KH031SD34
KH040SE341
KH050SD34
KH063SE341
KH005SD35
KH010SD35
KH020SD35
KH025SE351
KH031SD35
KH040SE351
KH050SD35
KH063SE351
KH020SD44
KH031SD44
KH050SD44
KH016SD541
KH025SD541
KH040SD541
KH063SD541
KH016SD551
KH025SD551
KH040SD551
KH063SD551
KH016SD542
KH025SD542
KH040SD542
KH063SD542
KH016SD552
KH025SD552
KH040SD552
KH063SD552
KH063SD841
KH010SD85
KH025SD85
KH040SD85
KH063SD85
KH063SD8502
KH040SD9502
KH063SD9502
KH0SD108919802
KH0SD108919803
KH0SD108920002
KH0SD108922201
KH0SD108922202
KH0SD107080401
KH0SD107076901
KH0SD107080402
KH0SD107076902
KH0SD1530710

Removed
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Removed
Removed
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed

KH025SD15
KH025SD15
KH063SD15
KH063SD15
KH025SD14
KH063SD14
KH025SD15
KH063SD15
KH063SD15
No
No
No
No
KH025SE351
KH040SE351
KH063SE351
KH025SE341
KH025SE341
KH025SE341
KH040SE341
KH063SE341
KH025SE351
KH025SE351
KH025SE351
KH040SE351
KH063SE351
No
No
No
KH025SD541
KH063SD541
KH025SD541
KH063SD551
KH025SD542
KH063SD541
KH025SD542
KH063SD551
No
KH063SD85
No
No
No
No
No
No
No
No
No
No

3L+N+PE

3L+PEN

3L+NP+PE

Switch and fuse carriers

3L+PE

3L+N+PE

3L+PEN

3L+NP+PE

Circuit breaker manuel

3L+N+PE

3L+PEN

Circuit breaker electrical control

3L+N+PE

3L+PEN

Muller Isolator

3L+N+PE
3L+PEN

Muller Isolator + Pelha

3L+PEN

Dumeco switch

Other

3L+N+PE
3L+PEN
-

K9CE27000_bis.indd

160
250
400
630
200
315
500
50
100
200
250
315
400
500
630
50
100
200
250
315
400
500
630
200
315
500
160
250
400
630
160
250
400
630
160
250
400
630
160
250
400
630
630
100
250
400
630
400
630
-

100
60
100
60
400

version: 1.1

119

Design guide

new
Canalis KTC

Canalis KH substitution by
Canalis KT
Preserved KH tap-off units
and substitution table

Bolted tap-off units


Protection
Isolator and fuse carriers

Polarity

Rating

Catologue number

Status

Substitued by

3L+PE

160

KH016SB131
KH016SB132
KH025SB131
KH025SB132
KH040SB131
KH040SB132
KH063SB131
KH063SB132
KH086SB131
KH086SB132
KH0SB331132
KH016SB141
KH016SB142
KH025SB141
KH025SB142
KH040SB141
KH040SB142
KH063SB141
KH063SB142
KH086SB141
KH086SB142
KH016SB151
KH016SB152
KH025SB151
KH025SB152
KH040SB151
KH040SB152
KH063SB151
KH063SB152
KH086SB151
KH086SB152
KH016SB241
KH016SB242
KH025SB241
KH025SB242
KH040SB241
KH040SB242
KH063SB241
KH063SB242
KH086SB241
KH086SB242
KH086SB331
KH086SB332
KH025SB331
KH025SB332
KH040SB331
KH040SB332
KH063SB331
KH063SB332
KH086SB351
KH086SB352
KH025SB341
KH025SB342
KH025SB441
KH025SB442
KH040SB341
KH040SB342
KH040SB441
KH040SB442
KH063SB341
KH063SB342
KH063SB441
KH063SB442
KH086SB341
KH086SB342

Removed
Removed
Preserved
Preserved
Removed
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Preserved
Preserved
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed

KH025SB131
KH025SB132
KH063SB131
KH063SB132
KH086SB132
KH025SB141
KH025SB142
KH063SB141
KH063SB142
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

250
400
630
1000

3L+N+PE

160
250
400
630
1000

3L+PEN

160
250
400
630
1000

3L+NP+PE

160
250
400
630
1000

Switch and fuse carriers

3L+PE

1000

3P+PE

250
400
630

3P+PEN

1000

3L+N+PE

250

400

630

1000

120

version: 1.1

K9CE27000_bis.indd

new
Bolted tap-off units
Protection
Switch and fuse carriers (cont)

Polarity

Rating

Catologue number

Status

Substitued by

3L+PEN

250

KH025SB351
KH025SB352
KH040SB351
KH040SB352
KH063SB351
KH063SB352
KH086SB5311
KH086SB5312
KH025SB5411
KH025SB5412
KH040SB5411
KH040SB5412
KH063SB5411
KH063SB5412
KH086SB5411
KH086SB5412
KH025SB5511
KH025SB5512
KH040SB5511
KH040SB5512
KH063SB5511
KH063SB5512
KH086SB5511
KH086SB5512
KH025SB5521
KH040SB5521
KH063SB5521
KH025SB5421
KH025SB5422
KH040SB5421
KH040SB5422
KH063SB5421
KH063SB5422
KH025SB5522
KH040SB5522
KH063SB5522
KH040DD411
KH0SB1393108
KH0SB1393132
KH0SA345794
KH0SB1041086
KH0SA1088568
KH0SA1088123

Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Preserved
Preserved
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed
Removed

No
No
No
No
No
No
KH086SB5411
KH086SB5412
KH086SB5411
KH086SB5412
KH086SB5411
KH086SB5412
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

400
630
Circuit breaker manuel

3L+PE

1000

3L+N+PE

250
400
630
1000

3L+PEN

250
400
630
1000

Circuit breaker electrical controle 3P+PEN

3L+N+PE

250
400
630
250
400
630

3L+PEN

Circuit breaker plug-out

3L+PEN

250
400
630
1000

Others

1000
1500
2000

K9CE27000_bis.indd

version: 1.1

121

Canalis KH substitution by
Canalis KT

Catalogue numbers and


dimensions

250 and 630 A tap-off units from Canalis


KH range for Compact NSX circuit
breakers

new
Canalis KTC

Tap-off units for Compact NSX, fixed, front-connected circuit breakers, not equipped
DB402027

The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.

Plug-in tap-off units for extended rotary


Busbar
trunking

TT-TNS-TNC-IT TNC

Tap-off unit

TT-TNS-TNS-IT

TNC

3L + N + PE

3L + PEN

DD210452

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)
KH0ppSD5pp

Rating Type of
(A)
circuit
breaker

Cable
Cable
capacity clamp on
2
(mm )
(mm)

L1 L2 L3 N PE

DB401484

System earthing
arrangement (1)

L1 L2 L3 N PE

Cat. no.

Weight
(kg)

250

NSX250 N/H/L 1 x 150

30...70

KH025SD541

KH025SD551

32.00

630

NSX630 N/H/L 2 x 300

2 x 30...70

KH063SD541

KH063SD551

45.00

(1) These units can be fitted either on Canalis KTC or KGF.

Plug-in tap-off units for motor mechanisme control 220 V 50 Hz (not supplied)
Busbar
trunking

TT-TNS-TNC-IT TNC

Tap-off unit

TT-TNS-TNS-IT

TNC

3L + N + PE

3L + PEN

Rating Type of circuit Cable


Cable
(A)
breaker
capacity clamp on
(mm2)
(mm)

Cat. no.

Weight
(kg)

NSX250 N/H/L
control 31541

KH025SD542

KH025SD552

32.00

630

NSX630 N/H/L
control 32841

KH063SD542

KH063SD552

45.00

KH063SDppp

DD402104

DD402103

L1 L2 L3 N PE

250

KH025SDppp
DB401483

L1 L2 L3 N PE

Tap-off diagram
(e.g. fuse protection)

DD210452

Tap-off polarity

DB401484

System earthing
arrangement (1)

DB401483

x = 520

x = 646

122

version: 1.1

K9CE27000_bis.indd

new

250 and 630 A tap-off units from Canalis


KH range for NF fuses

Tap-off units with isolator for blade-type fuses

System earthing
arrangement (1)

Busbar
trunking

TT-TNS-TNC-IT TNC

Tap-off unit

TT-TNS-TNS-IT

TNC

3L + N + PE

3L + PEN

DD210470

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 N PE

DD210471

DB402028

Tap-off disconnection by opening or closing the cover should be carried out only
if the downstreamload is de-energised.

L1 L2 L3 N PE

KH0ppSD1p
Rating
(A)

Fuse Cable
Cable
size capacity clamp on
2
(mm )
(mm)

Cat. no.

Weight
(kg)

250

1 x 95

1 x 30-70

KH025SD14

KH025SD15

37.00

630

2 x 185

2 x 30-70

KH063SD14

KH063SD15

56.00

(1) These units can be fitted either on Canalis KTC or KGF.

DD402108

KH063SDpp

DD402107

KH025SDpp

DD202008

DD202008

x = 790

K9CE27000_bis.indd

x = 920

version: 1.1

123

Canalis KH substitution by
Canalis KT

Catalogue numbers and


dimensions

new

100 to 630 A tap-off units from Canalis


KH with disconnector Jean Muller

Canalis KTC

Tap-off units with disconnector Jean Muller

DB402115

System earthing arrangement (1)

Busbar
trunking
Tap-off unit

3L + PEN

Tap-off diagram
(e.g. fuse protection)

Ith (A)

100
250

Fuse
size
With MULLER disconnector
With MULLER disconnector

00
1

Cable
capacity
(mm2)
1 x 50
1 x 95

2
1 x 185
400
With MULLER disconnector
3
2 x 185
630
With MULLER disconnector
(1) These units can be fitted either on Canalis KTC or KGF.

KH010SD85

TNC
DD210471

Tap-off polarity

TNC

L1 L2 L3 N PE

Cat. no.

Weight
(kg)

KH010SD85
KH025SD85

12.50
37.00

KH040SD85
KH063SD85

39.00
46.00

DB402116

KH010SD85

DB402118

DB402117

KH025SD85 - KH040SD85 - KH063SD85

KH040SD85

124

version: 1.1

K9CE27000_bis.indd

new

400 and 630 A tap-off units from Canalis


KH with disconnector Jean Muller

Tap-off units with disconnector internal arc tested IEC 61-641

DD401398

System earthing arrangement (1)

Busbar
trunking
Tap-off unit

3L + PEN

Tap-off diagram
(e.g. fuse protection)

Fuse
size

Ith (A)
400
630

TNC
DD210471

Tap-off polarity

TNC

With MULLER disconnector


With MULLER disconnector

2
3

Cable
capacity
(mm2)
1 x 185
2 x 185

L1 L2 L3 N PE

Cat. no.

Weight
(kg)

KH040SD9502
KH063SD9502

39.00
46.00

(1) These units can be fitted either on Canalis KTC or KGF.

KH040SD9502

DB401399

KH040SD9502

Connecting box is equipped with a 30 to 70mm aluminium cable clamp.

DB401401

DD401400

KH063SD9502

KH063SD9502

Connecting plate is equipped with 4 plastic cable clamps.


K9CE27000_bis.indd

version: 1.1

125

Catalogue numbers and


dimensions

new
Canalis KTC

Canalis KH substitution by
Canalis KT

250 to 630 A tap-off units from Canalis KH


range with Fupact INF fuse switch - IP43

Tap-off units from Canalis KH range with Fupact INF fuse switch
DB401471

Tap-off unit installed under voltage, unloaded, for KTC2500, KTC3200, KTC4000.

Functionalities

b Insulation and protection of the outlet by Fupact fuse-switch Schneider Electric


(supplied).
b IP43 for both mounting positions, above or below the busbar trunking.
TNC

Tap-off polarity

TT-TNS-TNS-IT
3L + N + PE

TNC
3L+ PEN

Tap-off diagram

L1 L2 L3 N PE

Rating (A)

DB401476

KH0ppSE3p1

DD210470

Busbar
trunking
Tap-off unit

Ith (A)

Fuse size
(DIN 43653)

Cat. no.

DB401472

TT-TNS-TNC-IT

System earthing arrangement (1)

L1 L2 L3 N PE

250

250

KH025SE341

KH025SE351

400

350

KH040SE341

KH040SE351

630

500

KH063SE341

KH063SE351

(1) These units can be fitted either on Canalis KTC or KGF.


Dimensions KHOppSE3p1
Dimensions (mm)

DB401480

KH025SEp1

KH040SEp1

KH063SEp1

569

569

665

700

760

765

590

590

620

165

165

165

255

255

285

550

550

650

Optional accessories

DB401475

Accessories

Cat. no.

Extension handle (for KH0ppSE3p1)

KH063ZA03

Cable box with 1 hole (for for KH025SE3p1)


(cable gland not supplied, to be ordered separately)

KH025ZA05

Cable box with 1 hole (for for KH040SE3p1)


(cable gland not supplied, to be ordered separately)

KH040ZA05

Cable box with 1 hole (for for KH063SE3p1)


(cable gland not supplied, to be ordered separately)

KH063ZA05

Cable box with 2 hole (for for KH040SE3p1)


(cable gland not supplied, to be ordered separately)

KH040ZA06

Cable box with 2 hole (for for KH063SE3p1)


(cable gland not supplied, to be ordered separately)

KH063ZA06

Cable gland (185 - 240 mm2) for cable boxes KH0ppZA05 and KH0ppZA06

KH063ZA10

DB401474

DB401473

Extension handle.

Cable box with 1 hole + cable


gland.

126

Cable box with 2 hole + cable


glands.w

version: 1.1

K9CE27000_bis.indd

250 to 1000 A fixed tap-off units for


Canalis KGF range, with isolator and fuse
carriers

new
Canalis KGF only

Tap-off units with isolator for blade-type fuses

System earthing
arrangement (1)

Busbar
trunking

IT-TT-TNS

TT-TNS-TNC-IT (3)

Tap-off
unit

IT-TT-TNS

TT-TNS-TNS-IT (3)

3L + PE

3L + N + PE

DB401487

Cat. no. (4)

Weight Cat. no. (4)


(kg)

Weight
(kg)

250

1 x 150

1 x 30-70

KH025SB13p

46.00

KH025SB14p

48.00

630

2 x 300

2 x 30-70

KH063SB13p

71.00

KH063SB14p

75.00

1000

4 x 185

KH086SB13p

86.00

KH086SB14p

90.00

(1) To be installed only on Canalis KGF junction, do not use on Canalis KT.
(3) Also suitable for tap-off unit 3L + PE (N not distributed).
(4) The reference number ends with 1 if the tap-off unit is mounted on the identification label
side. The reference number ends with 2 if the tap-off unit is mounted on the opposite side to the
label.

Opposite of yellow label.

KH0ppSBppp

y
l
n
o
1
e
l
2
b
0
a
l
i
2
a til
v
A un

Fuse Cable
Cable
size capacity clamp on
2
(mm )
(mm)

In front of yellow label.

L1 L2 L3 N PE

Rating
(A)

DB402113

DB401486

KH0ppSB1pp

L1 L2 L3 PE

Tap-off diagram
(e.g. fuse protection)

DD230227

Tap-off polarity

DD230226

DB401455

The cover of the tap-off unit may be opened or closed only when the circuit breaker
is in the Off position.

160/250

Rating (A)

540

500

630

265

400/630

640

600

750

290

1000

650

485

300

120

Connexion equipment for type SB (2) tap-off units

Note: this equipment sould be ordered at the same time as the SB tap-off unit.
Type of busbar trunking SB tap-off unit (except 1000 A) SB tap-off unit 1000 A only
KGF 16

KH016CB

KH016CB311571

KGF 26

KH026CB

KH026CB311571

KGF 36

KH036CB

KH036CB311571

KGF 46

KH046CB

KH046CB311571

KGF 56

KH056CB

KH056CB311571

(2) The neutral must be not distributed (3L + PE) for the IT system.

K9CE27000_bis.indd

version: 1.1

127

Canalis KH substitution by
Canalis KT

Catalogue numbers
and dimensions

new
Canalis KGF only

Fixed tap-off units for Canalis KGF


range, for circuit breaker NS630b,
NS800, NS1000

Fixed tap-off units for Canalis KGF range

System earthing arrangement (1)

Busbar
trunking

IT-TT-TNS

TT-TNS-TNC-IT

Tap-off unit

IT-TT-TNS

TT-TNS-TNS-IT

3L + PE

3L + N + PE

y
l
n
o
1
e
l
2
b
0
a 2
l
i
a til
v
A un

DD230225

Tap-off polarity
Tap-off diagram
(e.g. fuse protection)

L1 L2 L3 PE

DD210452

DB401485

b Tap-off units are installed in the joint of 2 elements (1).


b The link between tap-off unit and busbar trunking is realised by a set connecting
links (see below the complementary kit catalogue numbers).
b Connection of 3 cables maxi per phase (holes 14).
b Protection indice: IP31.
b Type of circuit breaker:
v extended rotary handle ref. 33878
v fixed device with Front connection.

L1 L2 L3 N PE

DB401487
DB401487

DB401486

KH086SB5p1p

In front of yellow label.

Rated
Control Type of
current In
circuit
(2)
35 C
breakers
1000 A

Manual

Opposite of yellow label.

N, H, L
MG
NS630b,
NS800,

Side

Cat. no. (3)

In front of
yellow label

KH086SB5311

Opposite of
yellow label

KH086SB5312 KH086SB5412 88.00

Weight
(kg)
KH086SB5411 88.00

(1) To be installed only on Canalis KGF junction, do not use on Canalis KT.
(2) The circuit breaker more than 1000 A, with the same dimension, cannot be used on these tapoff units.
(3) The reference number ends with 1 if the tap-off unit is mounted on the identification label side.
The reference number ends with 2 if the tap-off unit is mounted on the opposite side to the label.

Connexion equipment for type SB5 tap-off units


Complementary kit

y
l
n
o
1
e
l
2
b
0
a
l
i
2
a til
v
A un

128

Note: this equipment should be ordered at the same time as the SB tap-off unit.
Type of busbar
trunking

Cat. no.

Mounting position

KGF 16

KH018CB86NS

KGF 26

KH028CB86NS

KGF 36

KH038CB86NS

KGF 46

KH048CB86NS

KGF 56

KH058CB86NS

or

version: 1.1

K9CE27000_bis.indd

Expansion of a Canalis KH line by means


of Canalis KT

DB401535

new

K9CE27000_bis.indd

version: 1.1

129

Catalogue numbers
and dimensions

new

Expansion of a Canalis KH line by means


of Canalis KT with a T-piece tap-off unit

DB401534

Canalis KTC

Canalis KH substitution
byCanalis KT

130

version: 1.1

K9CE27000_bis.indd

Mid KT line power supply with KH tap-off


units installed

DB401497

new

K9CE27000_bis.indd

version: 1.1

131

132

version: 1.1

K9CE27000_bis.indd

Contents

Design guide

Index
Introduction
Presentation and description
Catalogue numbers and dimensions

Characteristics

3
17
35
63

134

Canalis KTC 3L + PE 134


Canalis KTC 3L + N + PE 135
Canalis KTC 3L + N + PER 136

Other characteristics

137

Determining the rating

138

Providing power distribution using Canalis 138

Sizing the busbar trunking

140

Protection of circuits supplied by several paralleled transformers

142

Coordination

144

Protection of busbar trunking against overloads 144


Protection against short-circuits 146

Circuit breaker/busbar trunking coordination

147

Non-limiting or time-delayed circuit breaker 147


Limiter circuit breaker 148

Protecting busbar trunking with a Compact NS circuit breaker

149

Selection guide

150

Degree of protection

152

Harmonic currents

154

Direct current

156

Frequencies

158

400 Hz 158

Measurements and metering

159

Transparent Ready units 159

DEBU024EN_Design guide.indd

Fire resistance

162

Seismic resistance

164

Testing and commissioning procedure

166

Design and installation guide


Recommandations

171
231

version: 1.1

133

Characteristics

Design guide

Canalis KTC 3L + PE
Canalis KTC
Characteristics of run sections
Symbol

Unit

General characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Compliance with standards

IEC/EN 60439-2

Protection degree

IP

55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.

Shock resistance

IK

Nominal rated current at an ambient temperature of


35 C

Inc

08

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

c 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

110

113

Allowable rated peak current

Ipk

kA

110

110

143

242

248

Maximum thermal stress I2t (t = 1s)

I2t

A2s 106

2500

2500

4225

4900

mW/m

0.041

0.029

0.024

mW/m

0.049

0.035

0.029

1000

1350

1600

2000

2500

3200

4000

5000

86

90

95

189

198

209

6400

7396

8100

9025

0.018

0.014

0.012

0.009

0.007

0.022

0.018

0.015

0.012

0.009

1000
1000

Short-circuit current withstand


Standard version 3L + PE

Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 C R20
R1

Average resistance at Inc and at 35 C

Average reactance at Inc and at 35 C and at 50 Hz

X1

mW/m

0.022

0.016

0.015

0.013

0.011

0.008

0.007

0.007

Average impedance at Inc and at 35 C and at 50 Hz

Z1

mW/m

0.054

0.039

0.033

0.026

0.021

0.017

0.014

0.012

PE = casing
Average resistance at an ambient temperature of 20 C

mW/m

0.203

0.178

0.164

0.143

0.126

0.113

0.093

0.080

Casing
(Equivalent copper cross-section)

mm

120

130

140

155

165

180

190

200

Fault loop characteristics


Fault loop
Ph/PE
characteristics at 20 C

Average resistance

R0 ph/PE

mW/m

0.688

0.566

0.509

0.435

0.378

0.335

0.279

0.238

Average reactance

X0 ph/PE

mW/m

0.666

0.489

0.410

0.315

0.247

0.196

0.147

0.113

Average impedance
Impedance
method

mW/m

0.958

0.748

0.654

0.537

0.452

0.388

0.315

0.263

Average resistance

Ph/Ph Rb0 ph/ph

mW/m

0.078

0.056

0.047

0.036

0.029

0.025

0.019

0.015

Ph/PE Rb0 ph/PE

mW/m

0.439

0.351

0.298

0.239

0.199

0.170

0.135

0.110

At Inc and Average resistance


at 35 C

Ph/Ph Rb1 ph/ph

mW/m

0.094

0.068

0.057

0.044

0.036

0.032

0.024

0.019

Ph/PE Rb1 ph/PE

mW/m

0.527

0.428

0.364

0.292

0.247

0.214

0.173

0.141

At Inc and Average reactance


at 35 C
and at
50 Hz

Ph/Ph Xb ph/ph

mW/m

0.040

0.029

0.024

0.019

0.015

0.013

0.010

0.008

Ph/PE Xb ph/PE

mW/m

0.426

0.329

0.275

0.212

0.170

0.141

0.106

0.084

At 20 C

Z0 ph/PE

Other characteristics
Voltage drop
Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
For a cosine j of

V/100 m/A

0.0043

0.0031

0.0026

0.0019

0.0015

0.0013

0.0010

0.0008

0.9

V/100 m/A

0.0047

0.0034

0.0029

0.0022

0.0018

0.0015

0.0012

0.0010

0.8

V/100 m/A

0.0046

0.0033

0.0028

0.0022

0.0018

0.0015

0.0012

0.0010

0.7

V/100 m/A

0.0044

0.0031

0.0027

0.0021

0.0018

0.0014

0.0012

0.0010

kg/m

19

25

29

36

44

51

66

82

kWh/m

2.1

2.9

3.2

3.9

5.7

6.2

8.9

11.2

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Average weight
3L + PE

Fire load value

Radiated magnetic field


Radiated magnetic field strength 1 metre from the
trunking

134

version: 1.1

K9CE39000.indd

Canalis KTC 3L + N + PE

Characteristics of run sections


Symbol

Unit

General characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Compliance with standards

IEC/EN 60439-2

Protection degree

IP

55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.

Shock resistance

IK

Nominal rated current at an ambient temperature of


35 C

Inc

08

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

c 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

70

80

Allowable rated peak current


Maximum thermal stress I2t (t = 1s)

Ipk
I2t

kA
A2s 106

110
2500

110
2500

143
4225

154
4900

176
6400

R20
R1
X1
Z1

mW/m
mW/m
mW/m
mW/m

0.041
0.049
0.022
0.054

0.029
0.035
0.016
0.039

0.024
0.029
0.015
0.033

0.018
0.022
0.013
0.026

mW/m
mm

0.203
120

0.178
130

0.164
140

R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE

mW/m
mW/m
mW/m
mW/m
mW/m
mW/m

0.192
0.124
0.229
0.688
0.666
0.958

0.138
0.089
0.164
0.566
0.489
0.748

Ph/Ph
Ph/N
Ph/PE
Ph/Ph

Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph

mW/m
mW/m
mW/m
mW/m

0.078
0.080
0.439
0.094

Ph/N

Rb1 ph/N

mW/m

Ph/PE
Ph/Ph
Ph/N
Ph/PE

Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE

mW/m
mW/m
mW/m
mW/m

1000

1350

1600

2000

2500

3200

4000

5000

86

90

95

189
7396

198
8100

209
9025

0.014
0.018
0.011
0.021

0.012
0.015
0.008
0.017

0.009
0.012
0.007
0.014

0.007
0.009
0.007
0.012

0.143
155

0.126
165

0.113
180

0.093
190

0.080
200

0.116
0.075
0.138
0.509
0.410
0.654

0.089
0.058
0.106
0.435
0.315
0.537

0.071
0.044
0.084
0.378
0.247
0.452

0.062
0.040
0.074
0.335
0.196
0.388

0.046
0.030
0.055
0.279
0.147
0.315

0.037
0.024
0.044
0.238
0.113
0.263

0.056
0.057
0.351
0.068

0.047
0.048
0.298
0.057

0.036
0.037
0.239
0.044

0.029
0.029
0.199
0.036

0.025
0.026
0.170
0.032

0.019
0.019
0.135
0.024

0.015
0.015
0.110
0.019

0.096

0.070

0.059

0.045

0.036

0.032

0.024

0.020

0.527
0.040
0.065
0.426

0.428
0.029
0.047
0.329

0.364
0.024
0.040
0.275

0.292
0.019
0.030
0.212

0.247
0.015
0.024
0.170

0.214
0.013
0.021
0.141

0.173
0.010
0.016
0.106

0.141
0.008
0.013
0.084

1000
1000

Short-circuit current withstand


Standard version 3L + N + PE

Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 C
Average resistance at Inc and at 35 C
Average reactance at Inc and at 35 C and at 50 Hz
Average impedance at Inc and at 35 C and at 50 Hz

PE = casing
Average resistance at an ambient temperature of 20 C
Casing
Equivalent copper cross-section

Fault loop characteristics


Fault loop
Ph/N
Average resistance
characteristics at 20 C Average reactance
Average impedance
Ph/PE
Average resistance
at 20 C Average reactance
Average impedance
Impedance
method

At 20C

Average resistance

At Inc and Average resistance


at 35 C
At Inc and Average reactance
at 35 C
and at
50 Hz

Other characteristics
Voltage drop

For a cosine j of

Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A 0.0043 0.0031 0.0026 0.0019 0.0015 0.0013 0.0010 0.0008
0.9
V/100 m/A 0.0047 0.0034 0.0029 0.0022 0.0018 0.0015 0.0012 0.0010
0.8
V/100 m/A 0.0046 0.0033 0.0028 0.0022 0.0018 0.0015 0.0012 0.0010
0.7
V/100 m/A 0.0044 0.0031 0.0027 0.0021 0.0018 0.0014 0.0012 0.0010

Average weight
3L + N + PE

kg/m

25

33

39

49

60

71

92

114

kWh/m

2.5

3.6

4.1

5.9

7.3

8.0

11.5

14.4

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Fire load value

Radiated magnetic field


Radiated magnetic field strength 1 metre from the
trunking

K9CE39000.indd

version: 1.1

135

Design guide

Characteristics

Canalis KTC 3L + N + PER


Canalis KTC
Characteristics of run sections
Symbol

Unit

General characteristics
Compliance with standards
Protection degree

Shock resistance
Nominal rated current at an ambient temperature of
35 C
Rated insulation voltage
Rated operating voltage
Operating frequency

IP

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50
IEC/EN 60439-2
55
Any installation (indoors only) is possible for the busbar truncking: edgewise,
flat or vertical. See test condition, page 153.
08
1000
1350
1600
2000
2500
3200
4000
5000

IK
Inc

Ui
Ue
f

V
V
Hz

c 50/60 (for 60 to 400 Hz AC or for DC, consult us)

Allowable rated short-time withstand current (t = 1 s)

Icw

kA

50

50

65

70

80

86

90

95

Allowable rated peak current


Maximum thermal stress I2t (t = 1s)

Ipk
I2t

kA
A2s 106

110
2500

110
2500

143
4225

154
4900

176
6400

189
7396

198
8100

209
9025

Icw
Ipk
I2t

kA
kA
A2s 106

65
143
4225

65
143
4225

85
187
7225

110
242
12100

113
248
12769

113
248
12769

120
264
14400

120
264
14400

R20
R1
X1
Z1

mW/m
mW/m
mW/m
mW/m

0.041
0.049
0.022
0.054

0.029
0.035
0.016
0.039

0.024
0.029
0.015
0.033

0.018
0.022
0.013
0.026

0.014
0.018
0.011
0.021

0.012
0.015
0.008
0.017

0.009
0.012
0.007
0.014

0.007
0.009
0.007
0.012

mW/m
mm

0.050
210

0.039
300

0.034
360

0.026
480

0.022
600

0.019
720

0.014
960

0.012
1200

R0 ph/N
X0 ph/N
Z0 ph/N
R0 ph/PE
X0 ph/PE
Z0 ph/PE

mW/m
mW/m
mW/m
mW/m
mW/m
mW/m

0.189
0.087
0.208
0.206
0.067
0.217

0.134
0.061
0.148
0.157
0.051
0.164

0.113
0.054
0.125
0.135
0.043
0.142

0.085
0.042
0.095
0.106
0.034
0.111

0.069
0.041
0.080
0.087
0.028
0.091

0.057
0.029
0.064
0.074
0.024
0.078

0.043
0.022
0.049
0.057
0.019
0.060

0.035
0.018
0.039
0.047
0.015
0.049

Rb0 ph/ph
Rb0 ph/N
Rb0 ph/PE
Rb1 ph/ph
Rb1 ph/N
Rb1 ph/PE
Xb ph/ph
Xb ph/N
Xb ph/PE

mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m
mW/m

0.083
0.087
0.105
0.099
0.104
0.126
0.028
0.043
0.050

0.058
0.059
0.077
0.071
0.072
0.094
0.020
0.032
0.040

0.048
0.019
0.065
0.059
0.060
0.080
0.017
0.028
0.035

0.036
0.239
0.050
0.044
0.045
0.061
0.013
0.021
0.039

0.029
0.199
0.041
0.036
0.036
0.051
0.011
0.017
0.023

0.024
0.170
0.034
0.030
0.031
0.043
0.009
0.015
0.020

0.018
0.135
0.026
0.023
0.023
0.033
0.004
0.011
0.016

0.014
0.110
0.021
0.019
0.019
0.027
0.006
0.009
0.013

1000
1000

Short-circuit current withstand


Standard version 3L + N + PER

Reinforced version 3L + N + PER (optional)


Allowable rated short-time withstand current (t = 1 s)
Allowable rated peak current
Maximum thermal stress

Conductor characteristics
Phase conductors
Average resistance at an ambient temperature of 20 C
Average resistance at Inc and at 35 C
Average reactance at Inc and at 35 C and at 50 Hz
Average impedance at Inc and at 35 C and at 50 Hz

PE = internal copper protective conductor


Average resistance at an ambient temperature of 20 C
Copper cross-section

Fault loop characteristics


Fault loop
Ph/N
characteristics at 35 C
Ph/PE
at 35 C
Impedance
method

Average resistance
Average reactance
Average impedance
Average resistance
Average reactance
Average impedance

At 20 C

Average resistance Ph/Ph


Ph/N
Ph/PER
At Inc and Average resistance Ph/Ph
at 35 C
Ph/N
Ph/PE
At Inc and Average reactance Ph/Ph
at 35 C
Ph/N
and at
Ph/PE
50 Hz

Other characteristics
Voltage drop

For a cosine j of

Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load spread over the
run. For the case of loads concentrated at the end of a run, the voltage drops are double those shown in
this table.
1
V/100 m/A 0.0043 0.0031 0.0026 0.0019 0.0015 0.0013 0.0010 0.0008
0.9
V/100 m/A 0.0047 0.0034 0.0029 0.0022 0.0018 0.0015 0.0012 0.0010
0.8
V/100 m/A 0.0046 0.0033 0.0028 0.0022 0.0018 0.0015 0.0012 0.0010
0.7
V/100 m/A 0.0044 0.0031 0.0027 0.0021 0.0018 0.0014 0.0012 0.0010

Average weight
3L + N + PER

kg/m

25

33

39

49

60

71

92

114

kWh/m

2.5

3.6

4.1

5.9

7.3

8.0

11.5

14.4

0.4

0.5

0.75

0.9

1.3

1.6

2.1

3.0

Fire load value


Radiated magnetic field
Radiated magnetic field strength 1 metre from the
trunking

136

version: 1.1

K9CE39000.indd

Other characteristics

Characteristics of run sections


Symbol

Unit

Other characteristics

Busbar trunking rating (A)


KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Choice of products when harmonics are present (see harmonic currents for more details).
Rated current according to THD3 (3rd order
distortion)

THD < 15 %

1000

1350

1600

2000

2500

3200

4000

5000

15 % < THD < 33 %

1000

1350

1600

2000

2500

3200

4000

THD > 33 %

1000

1350

1600

2000

2500

3200

Allowable current as a function of ambient temperature


Canalis busbar trunking is sized to operate at an ambient air does not exceed +40 C and its average over a period of 24 h does not exceed
+35 C, above this value, the busbar trunking must be derated.
Where k1 = ambient temperature derating coefficient.
Ambiant temperature 24 hours average
C

35

40

45

50

Busbar trunking installed indoors

k1

k1=1

k1=0.95

k1=0.90

k1=0.84

Busbar trunking installed outside under an


aluminium roof

k1

Busbar trunking installed in a fire duct

k1

See "Busbar trunking installed outside under an aluminium roof"


on page 139.
Please, see your sales office.

Through-wall fire barrier

Tests performed in accordance with the requirements of NF EN 1363-1 and those specific to EN 1366-3.
Performance criteria
Fire integrity

Thermal
insulation

Without external fire barrier

120 mn

30 mn

With external fire barrier

120 mn

120 mn

Tap-off unit characteristics


General characteristics

Symbol

Protection degree

IP

Shock resistance

IK

Rated insulation voltage

Ui

Rated operating voltage

Ue

Operating frequency

Hz

K9CE39000.indd

Unit
55
08
400 or 500 depending on protection device
50/60

version: 1.1

137

Design guide

Determining the rating

Providing power distribution using Canalis


Canalis KTC
Apart from extreme atmospheres, Canalis can be installed anywhere!
The order described below is only aimed at presenting the different stages for a
simple installation.
For a detailed design, it is necessary to use appropriate tools, approved by control
bodies, in compliance with local installation standards.
The Ecodial software, edited by Schneider Electric, meets this requirement
perfectly.

Design order:

1 Define run layouts.


2 Identify external influences.
3 Determine the current rating (Ib).
4 Calculate the nominal current (In) taking into account derating coefficients.
5 Choose the busbar trunking rating.
6 Check the rating with respect to allowable voltage drop.
7 Check busbar trunking overloads.
8 Check the rating with respect to short-circuit withstand current.
9 Choose the source and feeder circuit breakers.

1 - Canalis busbar trunking layout


The layout of the distribution runs depends on the position of the loads and where
the source is located.
Load protection is placed in the tap-off boxes, at the point of use.
A single and same Canalis busbar trunking supplies a group of loads of different
ratings.
Schneider Electric has tools you can use to help you choose the architecture best
suited to your application:
b the Idpro software to simulate the organisation of your electrical networks
b application orientated technical guides (car industry, data centers, shopping
centres, etc).

DD202142

2 - Identification of external influences


Protection degree
Canalis KT busbar trunking is IP55 and IPxxD by construction.
This protection degree protects the busbar trunking against:
b dust
b penetration by a 1mm diameter wire
b water projections from all directions.
It can be installed in almost all premises; for more details see the "Determining the
protection degree" pages.
Wherever the busbar trunking must pass outside the building, an aluminium
roof can be supplied; consult your Schneider Electric distributor for information
concerning this option.
Corrosive atmosphere
The busbar trunking has been qualified for industrial atmospheres.
For sulphurous atmospheres such as sulphur dioxide (SO2) and hydrogen sulphide
(H2S), there is a suitable Canalis KT solution; consult your Schneider Electric
distributor for more information on this option.
Example: paper mills, water treatment works, etc.

138

version: 1.1

K9CE31000.indd

DD210982n

Radiated electromagnetic fields

According to the WHO (World Health Organisation), exposure to radiated


electromagnetic fields above 0.2 micro Tesla can be dangerous causing a risk of
cancer over the long term. Some countries have standardised the limit: Sweden =
0.2 T, at a distance of 1 metre.
All electrical conductors generate a magnetic field, the strength of which is
proportional to the distance between them. The Canalis busbar trunking concept
(metal casing and conductors near together) helps to considerably reduce radiated
electromagnetic fields.
In specific cases where particularly low values are required (computer rooms,
hospitals, some offices), it is important to keep in mind the following:
b the induction generated around 3-phase distribution. This is proportional to the
current and the distance between the conductors, and inversely proportional to the
square of the distance with respect to the busbar trunking and the screening effect
of the case
b the induction generated around busbar trunking. This is less than the induction
generated around an equivalent cable distribution
b Canalis steel casing. This attenuates the induction more than an equivalent
aluminium casing of the same thickness (screening effect)
b the induction generated around busbar trunking with sandwiched bars. This is
particularly low because of the short distance between the bars and the additional
attenuation provided by the steel casing.

DD210066

3 - Determining the current rating (Ib)

Ib

Ib

Ib

Ib
Ib

Ib
Ib

Ib

Ib
Ib

Ib

In

Calculation of the total current (Ib) absorbed by a run is equal to the sum of the
currents absorbed by all of the loads.
The loads do not all operate at the same time and, as they are not continuously at
full load, a stacking or simultaneity factor Ks has to be taken into account:
Ib = Ib load x Ks

Ib

Stacking factor Ks depending on the number of loads according to


IEC 60439- 1
Application
Lighting, heating

Number of loads

Ks coefficient

Distribution (mechanic workshop) 2...3

0.9

4...5

0.8

6...9

0.7

10...40

0.6

40 and over
0.5
Caution: for industrial installations, remember to take into account future increases in the
number of machines. A 20 % reserve is recommended.

4 - Calculating nominal current (ln) by applying a derating coefficient


Ambient temperature
Canalis busbar trunking is sized to operate at an
average ambient temperature of 35 C, above this
value, the busbar trunking must be derated.
Example: Canalis KT 1350 A installed inside with an
ambient temperature of 45 C:
In = 1250 x 0.90 = 1215 A.
In u Ib x k1 = Iz

Type of
installation

Canalis
KT

Ambiant temperature 24 hours


average (C)
35
40
45
50

55

Busbar trunking
installed inside

All

0.95

0.90

0.84

0.79

Busbar trunking
installed outside under
an aluminium roof

KTC1000

0.97

0.95

0.90

0.84

0.79

KTC1350

0.96

0.93

0.89

0.84

0.79

KTC1600

0.94

0.91

0.87

0.84

0.79

KTC2000

0.96

0.93

0.89

0.84

0.79

KTC2500

0.93

0.90

0.86

0.82

0.78

KTC3200

0.85

0.83

0.80

0.77

0.74

KTC4000

0.87

0.85

0.81

0.78

0.75

KTC5000

0.86

0.84

0.81

0.78

0.75

Where k1 = ambient temperature derating coefficient.

Busbar trunking
installed in a fire duct

K9CE31000.indd

Please, see your sales office.

version: 1.1

139

Design guide

Sizing the busbar trunking

Canalis KTC
5 - Choosing the busbar trunking rating according to the nominal current ln
Nominal current
In (A)

Busbar trunking

0 to 1000

KTC1000

1001 to 1350

KTC1350

1351 to 1600

KTC1600

1601 to 2000

KTC2000

2001 to 2500

KTC2500

2501 to 3200

KTC3200

3201 to 4000

KTC4000

4001 to 5000

KTC5000

6 - Checking the rating with respect to allowable voltage drop.


The voltage drop between the start and all points of use must not be greater than
the values in the table below:
Lighting

Other use

Low voltage public distribution network

3%

5%

High voltage distribution network

6%

8%

Installation supplied by:

The allowable voltage drop is that which is compatible with correct load operation
(refer to manufacturers guides).
b Read voltage drop in V/100 m/A
for the busbar trunking chosen in accordance
with temperature rise.
b Determine the voltage drop for the worst case loads, i.e. those furthest from the
source and for the highest current.
If the voltage drop exceeds allowable limits, choose the next rating up.
Re-check the voltage drop for the new rating.
Voltage drop, in volts per 100 metres and per amp for 3-phase 50 Hz current with
load spread over the run. For loads concentrated at the end of a run (transport),
the voltage drops are double those shown in the table below:
Delta U
for evenly distributed loads (V/100m/A)
KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50
Cosine j = 1

0.0043

0.0031

0.0026

0.0019

0.0015

0.0013

0.0010

0.0008

Cosine j = 0.9

0.0047

0.0034

0.0029

0.0022

0.0018

0.0015

0.0012

0.0010

Cosine j = 0.8

0.0046

0.0033

0.0028

0.0022

0.0018

0.0015

0.0012

0.0010

Cosine j = 0.7

0.0044

0.0031

0.0027

0.0021

0.0018

0.0014

0.0012

0.0010

Example: for the KTC1600 A busbar trunking:


Ib = 1530 A
In = 1600 A
Length L = 87 m
Cosine = 0.8.
According to the above table, the voltage drop coefficient for 100 metres and per
amp is equal to 0.0028V/100m/A
.

0.0028 x 0.87 x 1530 = 3.72 V


For a voltage = 400 V, in percentages:
3.72/400 = 0.0093 that is to say 0.09 %.

140

version: 1.1

K9CE31000.indd

7 - Protecting against busbar trunking overloads.


To allow for extensions, the busbar trunking is generally protected at its nominal
current Inc (or its allowable current Iz if the ambient temperature coefficient k1 is
applied).
b Circuit breaker protection:
v adjust Ir of the circuit breaker such that:
Iz = Ib x k1 y Ir y Inc
Circuit breaker protection allows the Canalis busbar trunking to be used at full
capacity because the standardised nominal current In of the circuit breaker is
In y Inc/K2 where K2 = 1.
b Protection using gG (gI) fuse:
v determine the standardised nominal current In of the fuse such that: In y Inc/K2
v where K2 = 1.1
v choose the standardised rating In that is equal to or just lower.
Check the following condition: In u Ib x k1 = Iz.
If this condition is not met, choose the busbar trunking with the next rating up.
Note: using gI fuses for protection means reducing the busbar trunkings allowable
current.

8 - Checking the rating and choice of circuit breaker with respect to short-circuit withstand current
Short-circuit current withstand is shown in the table below.
This value must be greater than the prospective short-circuit current, at all points of
the installation.
b Calculate the short-circuit current value at the worst case points.
b Check the chosen rating allows the busbar trunking to cope with this short-circuit
current.
b If this is not the case, there are 2 possible solutions:
b choose a higher rating busbar trunking and re-check
b provide a peak current limiting protection system upstream of the busbar
trunking.
Standard version 3L + N + PE or 3L + PE
Unit

KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Allowable
Icw kArms/1s 50
rated shorttime withstand
current (t =1s)

50

65

70

80

86

90

95

Allowable
rated peak
current

110

110

143

154

176

189

198

209

2500

2500

4225

4900

6400

7396

8100

9025

Ipk k

Maximum
I2t
thermal stress

A2s.106

Reinforced version 3L + N+ PER


Allowable
Icw kArms/1s 65
rated shorttime withstand
current (t=1s)

65

85

110

113

113

120

120

Allowable
rated peak
current

143

143

187

242

248

248

264

264

4225

4225

7225

12100 12769 12769 14400 14400

Ipk k

Maximum
I2t
thermal stress

A2s.106

Canalis KT is more than sized to cope with short-circuit currents.


Some specific cases require checks to be carried out: transformers in parallel, low
rating Canalis installed close to a transformer, etc.

K9CE31000.indd

version: 1.1

141

Protection of circuits supplied


by several paralleled
transformers

Design guide

Canalis KTC
9 - Choosing source and feeder circuit breakers according to the number and rating of the supply
transformers

DD210981

The choice of a circuit breaker to protect a circuit depends mainly on the following
2 criteria:
b the nominal current of the source or the loads, which determines the appropriate
rating of the device,
b the maximum short-circuit current at the point in question, which determines the
minimum breaking capacity of the device.

For the case of several parallel transformers (1):


b the source circuit breaker D1 must have a breaking capacity greater than the
largest of the 2 following values:
v either Isc1 (short-circuit at B1)
v or Isc2 + Isc3 (short-circuit at A1)
b the feeder circuit breaker D4 must have a breaking capacity greater than Isc1 +
Isc2 + Isc3.
The table allows the following to be determined:
b the source circuit breaker, according to the number and rating of the supply
transformers (in the case of a single transformer, the table recommends a fixed
circuit breaker; in the case of several transformers, the table shows a drawout
circuit breaker and a fixed circuit breaker)
b the feeder circuit breaker, according to the sources and the nominal current
rating of the feeder (the circuit breakers shown in the table can be replaced by
limiter circuit breakers if the cascading technique is to be used with other circuit
breakers downstream of the feeder).
(1) To couple several transformers in parallel, the transformers must have the same Usc,
the same transformation ratio, the same coupling and the ratio of the power rating of the
2transformers must be less than or equal to 2.

DD210983n

Example:
3 incoming 1250 kVA transformers 20 kV/410 V (In = 1760 A).
Feeders: including one 2000 A feeder, one 1600 A feeder and one 1000 A feeder.
What circuit breakers should be fitted at the incomer and for the feeders?
b Incomer circuit breakers:
either the Drawout Masterpact NW20N1 or the Drawout NS2000N circuit breakers
can be chosen. The choice will depend on the options required.
b Feeder circuit breakers:
the NW20H2 for the 2000 A feeder, the NW16H2 for the 1600 A feeder and the
NW10H2 for the 1000 A feeder are to be chosen.
These circuit breakers have the advantage of providing discrimination (full
discrimination) with the NW12H1 or NS1250N circuit breakers.

142

version: 1.1

K9CE31000.indd

Calculation assumption:
b the upstream network short-circuit power is not defined
b the transformers are 20 kV/410 V
b between each transformer and corresponding circuit breaker there is 5 metres of
KT busbar trunking
b between a source circuit breaker and a feeder circuit breaker there is 1 metre of
bars
b the equipment is installed into a switchboard with an ambient temperature of 40
C.
Transformer
P (kVA) In (A)

Usc
(%)

Isc
(kA)

Source Source circuit breaker


min.
break.
cap.
(kA)

Feeder Feeder circuit breaker


min.
250 A
y 100 A 160 A
break.
cap.
(kA)

400 A

630 A

1 transformer
50

70

NSX100N TM-D/STR22SE

NSX100N

100

141

NSX160N TM-D/STR22SE

NSX100N NSX160N

160

225

NSX250N TM-D/STR22SE

NSX100N NSX160N NSX250N

250

352

NSX400N STR23SE/53UE

NSX100N NSX160N NSX250N NSX400N

400

563

14

14

NSX630N STR23SE/53UE

14

NSX100N NSX160N NSX250N NSX400N NSX630N

630

887

22

22

NS1000N NT10H1 NW10N1 Micrologic

22

NSX100N NSX160N NSX250N NSX400N NSX630N

800

1127

19

19

NS1250N NT12H1 NW12N1 Micrologic

19

NSX100N NSX160N NSX250N NSX400N NSX630N

1000

1408

23

23

NS1600N NT16H1 NW16N1 Micrologic

23

NSX100N NSX160N NSX250N NSX400N NSX630N

1250

1760

29

29

NW20N1 Micrologic

29

NSX100H NSX160N NSX250N NSX400N NSX630N

1600

2253

38

38

NW25H1 Micrologic

38

NSX100H NSX160H NSX250H NSX400N NSX630N

2000

2816

47

47

NW32H1 Micrologic

47

NSX100H NSX160H NSX250H NSX400H NSX630H

2500

3521

59

59

NW40H1 Micrologic

59

NSX100H NSX160H NSX250H NSX400H NSX630H

2 transformers
50

70

NSX100N TM-D/STR22SE

NSX100N NSX160N

100

141

NSX160N TM-D/STR22SE

NSX100N NSX160N NSX250N

160

225

NSX250N TM-D/STR22SE

11

NSX100N NSX160N NSX250N NSX400N

250

352

NSX400N STR23SE/53UE

18

NSX100N NSX160N NSX250N NSX400N NSX630N

400

563

14

14

NSX630N STR23SE/53UE

28

NSX100H NSX160N NSX250N NSX400N NSX630N

630

887

22

22

NS1000N NT10H1 NW10N1 Micrologic

44

NSX100H NSX160H NSX250H NSX400N NSX630N

800

1127

19

19

NS1250N NT12H1 NW12N1 Micrologic

38

NSX100H NSX160H NSX250H NSX400N NSX630N

1000

1408

23

23

NS1600N NT16H1 NW16N1 Micrologic

47

NSX100H NSX160H NSX250H NSX400H NSX630H

1250

1760

29

29

NW20N1 Micrologic

59

NSX100H NSX160H NSX250H NSX400H NSX630H

1600

2253

38

38

NW25H1 Micrologic

75

NSX100L NSX160L NSX250L NSX400L NSX630L

2000

2816

47

47

NW32H1 Micrologic

94

NSX100L NSX160L NSX250L NSX400L NSX630L

2500

3521

59

59

NW40H1 Micrologic

117

NSX100L NSX160L NSX250L NSX400L NSX630L

3 transformers
50

70

NSX100N TM-D/STR22SE

NSX100N NSX160N NSX250N

100

141

NSX160N TM-D/STR22SE

11

NSX100N NSX160N NSX250N NSX400N

160

225

11

NSX250N TM-D/STR22SE

17

NSX100N NSX160N NSX250N NSX400N NSX630N

250

352

18

NSX400N STR23SE/53UE

26

NSX100H NSX160N NSX250N NSX400N NSX630N

400

563

14

28

NSX630N STR23SE/53UE

42

NSX100H NSX160H NSX250H NSX400N NSX630N

630

887

22

44

NS1000N NT10L1 NW10H1 Micrologic

67

NSX100H NSX160H NSX250H NSX400H NSX630H

800

1127

19

38

NS1250N NT12H1 NW12N1 Micrologic

56

NSX100H NSX160H NSX250H NSX400H NSX630H

1000

1408

23

47

NS1600N NW16H1 Micrologic

70

NSX100H NSX160H NSX250H NSX400H NSX630H

1250

1760

29

59

NS2000N NW20N1 Micrologic

88

NSX100L NSX160L NSX250L NSX400L NSX630L

1600

2253

38

75

NS2500N NW25H2 Micrologic

113

NSX100L NSX160L NSX250L NSX400L NSX630L

2000

2816

47

94

NS3200N NW32H2 Micrologic

141

NSX100L NSX160L NSX250L NSX400L NSX630L

Usc values as defined in HD 428.

K9CE31000.indd

version: 1.1

143

Design guide

Coordination

Protection of busbar trunking against


overloads
Canalis KTC
Introduction

System performance is guaranteed by coordination between the Schneider Electric


circuit breaker protection and the distribution spread over the Canalis busbar
trunking.
Fully coordinated distributed electrical distribution perfectly meets the requirements
of safety, service continuity, system changes and simplicity.
In the following pages, we will explain the advantages of the Schneider Electric
system and Schneider Electric circuit breaker protection, as well as the selection
guide tables for coordination between the Schneider Electric circuit breakers and
the Canalis busbar trunking.
The use of Schneider Electric circuit breakers provides:
b protection against overloads and short-circuits
b coordination between the protective devices and the Canalis busbar trunking:
v full discrimination from 1 to 6300 A between all the circuit breakers of the
Schneider Electric ranges
v cascading:
- reinforcement of the small and medium power busbar trunking short-circuit
protective devices. This enables all short-circuit levels to be covered
- protection of tap-offs using standard circuit breakers: this is achieved whatever
the position of the tap-off unit on the Canalis busbar trunking
b the use of standard circuit breakers makes for simpler design whilst respecting a
high level of dependability
b fault location is quick and easy
b resetting is easy once the fault has been cleared by the site operator.

Adequacy between circuit breaker


ratings and busbar trunking

In order to take into consideration thermal overload protection of busbar trunking,


the different technologies of the protection switchgear and the maximum overload
operating currents must be considered.
By design, the thermal adjustment of a circuit breaker is more accurate.

DD210888

Fuse

b
v
v
v
v


b
b

Inc = Ib x k1 x k2
Ib : current rating
Inc : allowable busbar trunking current
k1 : temperature derating coefficient
k2 : derating coefficient linked to the type of switchgear:
- fuse k2 = 1.1
- circuit breaker k2 = 1.
Iz = Ib x k1.
In = I standardised fuse or circuit breaker.

Example:
For a current rating Ib = 1900 A in an ambient temperature of 35 C:
b fuse protection:

Inc = Ib x k1 x k2 = 1900 x 1 x 1.1 = 2090 A

The correct choice of busbar trunking is the KTC2500 (Inc = 2500 A),
b circuit breaker protection:

Inc = Ib x k1 x k2 = 1900 x 1 x 1 = 1900 A

The correct choice of busbar trunking is the KTC2000 (Inc = 2000 A),
A difference of 20 % in the measurement of operating currents results in an overrating of the busbar trunking of 10 % if it is protected by fuses.

DD210887

Circuit breaker

Explanations
b Calibration of thermal asymptotes:
v the distribution fuse is calibrated to operate for overloads of between 1.25 and
1.6 times its nominal current (In fuse)
v the circuit breaker is calibrated to operate for overloads of between 1.05 and
1.3times (1.2 for circuit breakers with electronic protection) its setting current (Ir
which is a function of circuit breaker In).
b Maximum operating current:
v the maximum limit for this current is set by installation standards (IEC 364,
NFC15-100, etc) at 1.45 times the allowable current of the busbar trunking.

In

144

version: 1.1

K9CE31000.indd

Thermal setting accuracy

b A fuse is for a fixed rating, a change in the current to be protected requires a


change of fuse.
The spacing between 2 fuse ratings is around 25 %.
The typical ratings are conform to the numbers of the "Renard" series.
Example: 40 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - etc.
b The circuit breaker provides the possibility of fine adjustment:
v 5 % for circuit breakers fitted with standard thermal-magnetic trip units
v 3 % for circuit breakers fitted with electronic trip units.
A circuit breaker with a nominal rating of 100 A can be easily set to the following
values:
Ir = 100 A, 95 A, 90 A, 85 A, 80 A.
Example:
A circuit breaker with a nominal rating of 1600 A set at 1344 A would be used to
protect a KTC1600 (Inc = 1344 A) busbar trunking used in an ambient temperature
of 50 C (k1 = 0.84).

Setting range of circuit breakers fitted


with electronic trip units

Circuit breakers fitted with electronic trip units have the following setting ranges:
b thermal protection Ir adjustable from 0.4 In to In
b short-circuit protection adjustable from 2 Ir to 10 Ir.

DD210603

Example:
A 250 A circuit breaker (NS250N fitted with an STR22SE) can easily have the
following settings:
b thermal protection from 100 to 250 A
b short-circuit protection from 200 to 2500 A.

Example of setting possibilities.

K9CE31000.indd

Avdantages
This provides great flexibility for:
b modifications (flexibility), extensions (installation changes): the protective
devices easily adapt to the load to be protected and to the earthing system
(protection of personnel and equipment)
b maintenance, the use of this type of device considerably reduces the stocks of
maintenance components.

version: 1.1

145

Design guide

Coordination

Protection against short-circuits


Canalis KTC
Busbar trunking characteristics

The busbar trunking must meet all of the rules detailed in IEC 60439.1 and
IEC 60439.2.
The sizing of busbar trunking for short-circuits is determined by the following
characteristics:
b the allowable rated peak current Ipk (k).
This characteristic represents the busbar trunkings instantaneous electrodynamic
withstand limits. The peak current value is often the most restrictive instantaneous
characteristic for the protective device
b The maximum short-time withstand rms current Icw (kArms/s).
This characteristic represents the allowable temperature rise limit of the conductors
during a given time period (0.1 to 1s)
b The thermal stress in A2s.
This characteristic represents the instantaneous thermal stress withstand of the
busbar trunking. In general, if the short-circuit generates fault conditions compatible
with the first two characteristics, this constraint is "automatically satisfied".

Circuit breaker characteristics

The circuit breaker must satisfy the requirements of product construction standards
(IEC 60947-2, etc) and installation standards (IEC 60364 or those in force in
the country concerned), i.e. have a breaking capacity Icu (1) greater than the
prospective short-circuit current Isc at the point where it is installed.
(1) Installation standard IEC 60364 and construction standards specify the breaking capacity of
a circuit breaker as being:
- the ultimate breaking capacity, Icu, if it is not coordinated with an upstream protective device,
- the reinforced breaking capacity (cascading) if there is coordination with the upstream
protective device.

DD210986

Circuit breaker/busbar trunking system


characteristics

When the busbar trunking is directly protected, the circuit breaker must be chosen
as follows:
b Icu of the circuit breaker u prospective Isc at point A
b I peak of the busbar trunking u prospective asymmetrical or limited Isc at point A
b busbar trunking thermal withstand Icw u thermal stress through the busbar
trunking.

DD210987

When the busbar trunking is protected downstream of a cable, the circuit breaker
must be chosen as follows:
b Icu of the circuit breaker u prospective Isc at point A
b I peak of the busbar trunking u prospective asymmetrical or limited Isc at point B
b busbar trunking thermal withstand Icw u thermal stress through the busbar
trunking.

146

version: 1.1

K9CE31000.indd

Circuit breaker/busbar trunking


coordination
Non-limiting or time-delayed circuit
breaker
DD210988

This is applicable for non-limiting circuit breakers (instantaneous or time-delayed)


and time-delayed limiting circuit breakers.
These are mainly air circuit breakers (u 800 A).
This type of circuit breaker is used for time discrimination and is therefore often
associated with KT type busbar trunking.

DD210989

Current value of the 1st peak as a function of Isc rms.

It must be checked that the busbar trunking can handle the peak fault current to
which it may be subjected and the thermal withstand during any time delay.
The allowable peak current (I peak) of the busbar trunking must be greater than the
peak current value of the prospective asymmetrical short-circuit current (Isc asym)
at A.
The asymmetrical short-circuit current value is obtained by multiplying the
symmetrical short-circuit current value (Isc) by a standardised asymmetrical
coefficient (k).
It is the first value of the 1st transient asymmetrical peak of the short-circuit which is
taken into account.
Standardised table for calculating asymmetrical short-circuit values

Transient and established conditions of a short duration shortcircuit.

Isc: prospective symmetrical shortcircuit value


kA (rms value)

Asymmetrical coefficient

4,5 y I y 6

1.5

6 < I y 10

1.7

10 < I y 20

2.0

20 < I y 50

2.1

50 < I

2.2

Example:
For a circuit with a prospective short-circuit current of 50 kA rms, the 1st peak
reaches 105 k (50 kA x 2.1), see figure opposite.

DD210990n

The short-time withstand value (Icw) of the busbar trunking must be greater than
the current flowing through the installation during the duration of the short-circuit
(Isc) (duration T - total breaking time - including any time delay).

At point A, the prospective short-circuit current is 117 KArms.


To meet this constraint, a reinforced KTC4000 is needed because:
Icw KTC4000 > Isc prospective at point A.
The Icw or IPK values of standard or reinforced KTC trunking allow the easy
construction of circuits with time discrimination, even with high short-circuit values.

K9CE31000.indd

version: 1.1

147

Circuit breaker/busbar trunking


coordination

Design guide

Limiter circuit breaker


Canalis KTC

This is mainly applicable to the protection of busbar trunking using moulded case
circuit breakers (y 1600 A).
This type of circuit breaker is used for energy discrimination and is therefore often
associated with Canalis KTC.

DD210991

Here, it has to be checked that the busbar trunking can cope with the peak current
(Ipk) limited by the protective device and the corresponding thermal stress (As):
b the peak current (I peak), once limited by the circuit breaker, must be less than
the allowable peak current value of the busbar trunking
b the thermal stress, once limited by the circuit breaker, must be less than the
allowable thermal stress of the busbar trunking.

DD210992

Checking peak I withstand of the busbar trunking.

Checking As withstand of the busbar trunking.

148

version: 1.1

K9CE31000.indd

Protecting busbar trunking with


a Compact NS circuit breaker

Limiting capacity

Compact NS circuit breakers are high current limiting circuit breakers.


The limiting capacity of a circuit breaker is its capacity to only allow a limited
current (IL) to flow in the event of a short-circuit. This limited current being less
than the prospective asymmetrical peak short-circuit current (Isc).
This greatly reduces the electrodynamic and thermal constraints on the installation
to be protected.

Applying limiting capacity to busbar


trunking protection

Even if this combination is less frequent than for KS busbar trunking, some KT
ratings can benefit from the association with a limiter circuit breaker.

DD210993nC

High power installation


If the circuit breakers limiting capacity is not taken into account:
b the prospective short-circuit current value (Isc) at point A would be 121 k
b KTC1600 would be the appropriate choice of busbar trunking.
If the limiting capacity of the Compact NS1000L is taken into account, the limited
Ipk is 50 k < 110 k of the KTC1000 busbar trunking.
Because of the high limiting capacity of the Compact NS1000L, a KTC1000 busbar
trunking can be installed into a prospective short-circuit current at point A of 150 kA
rms or 300 k.

K9CE31000.indd

version: 1.1

149

Design guide

Selection guide

Canalis KTC
The selection guide below will, according to the prospective short-circuit current of
the installation, allow you to determine the type of circuit breaker needed to fully
protect the busbar trunking.

For a voltage of 380/415 V


Max. Isc current in kA rms KTC1000
Circuit breakers

Example: for an installation with a prospective Isc of 55 kA, the circuit breaker
needed to protect a KTC1350 A busbar trunking is a NW10L1 or NW12L1 (the
rating depends on the circuits nominal current).
42 kA

50 kA

60 kA

150 kA

NT1.H1

NS800N/H

NW10L1

NS1000L

NW1.N1

NS1000N/H

NW12L1

NT10L1

NS1200N/H
NT.H2
NW1.H1/H2

Max. Isc current in kA rms KTC1350


Circuit breakers

42 kA

50 kA

55 kA

150 kA

NT1.H1

NS1000N/H

NW10L1

NS1000L

NW1.N1

NS1200N/H

NW12L1

NT10L1

NS1600N/H
NT.H2
NT.H2

Max. Isc current in kA rms KTC1600


Circuit breakers

42 kA

50 kA

60 kA

80 kA

NT12H1

NS1200N

NS1200H

NW12L1

NT16H1

NS1600N

NS1600H

NW16L1

NW12N1

NT12H2

NW12H1/H2

NW20L1

NW16N1

NT16H2

NW16H1/H2

NW20N1

Max. Isc current in kA rms KTC2000


Circuit breakers

NW2.H1/H2

42 kA

50 kA

65 kA

72 kA

110 kA

NT16H1

NS1600N

NW16H1

NW16H2

NW16L1

NW16N1

NT16H2

NW2.H1

NW2.H2

NW20L1

NW20N1

Max. Isc current in kA rms KTC2500


Circuit breakers

NW25H3

42 kA

65 kA

80 kA

150 kA

NW20N1

NW2.H1

NW40bH1

NW16L1

NW32H1

NW2.H2

NW20L1

NW40H1

NW32H2
NW40H2
NW..H3

Max. Isc current in kA rms KTC3200


Circuit breakers

65 kA

86 kA

150 kA

NW25H1

NW40bH1

NW20L1

NW32H1

NW2.H2

NW40H1

NW32H2
NW40H2
NW..H3

Max. Isc current in kA rms KTC4000


Circuit breakers

65 kA

90 kA

NW32H1

NW40bH1

NW40H1

NW50H1
NW32H2
NW40H2
NW50H2
NW32H3
NW40H3

Max. Isc current in kA rms KTC5000


Circuit breakers

95 kA
NW40bH1/H2
NW40H2/H3
NW50H1/H2
NW63H1/H2

150

version: 1.1

K9CE31000.indd

For a voltage of 660/690 V


Max. Isc current in kA rms
KTC1000
Circuit breakers

25 kA

28 kA

30 kA

40 kA

NS1000L

NS1600bN

NS1000N

NS1000H

NS1200N

NS1200H

NS1600N

NS1600H

NT10L1

NT1.H1/H2
NW..N1
NW1.H1/H2
NW10L1
NW12L1

Max. Isc current in kA rms


KTC1350
Circuit breakers

25 kA

30 kA

38 kA

42 kA

50 kA

NS1000L

NS1000N

NS1600bN

NS1000H

NW1.H1

NT10L1

NS1200N

NS1200H

NW1.H2

NS1600N

NS1600H

NW10L1

NT1.H1/H2

NW12L1

NW..N1

Max. Isc current in kA rms


KTC1600
Circuit breakers

42 kA

60 kA

65 kA

NT12H.

NS1600bN

NW..L1

NT16H.

NS2000N

NW12N1

NW12H1/H2

NW16N1

NW16H1/H2

NW20N1

NW20H1/H2
NW25H3

Max. Isc current in kA rms


KTC2000
Circuit breakers

42 kA

65 kA

72 kA

100 kA

NT16H1/H2

NS1600bN

NW16H2

NW16L1

NW16N1

NS2000N

NW20H2

NW20L1

NW20N1

NS2500N

NW25H2/H3

NW16H1
NW20H1
NW25H1

Max. Isc current in kA rms


KTC2500
Circuit breakers

42 kA

65 kA

80 kA

100 kA

NW20N1

NS2000N

NW40bH1

NW16L1

NS2500N

NW25H2/H3

NW20L1

NS3200N

NW32H2/H3

NW20H1

NW40H2/H3

NW25H1

NW40bH2

NW32H1
NW40H1

Max. Isc current in kA rms


KTC3200
Circuit breakers

Max. Isc current in kA rms


KTC4000
Circuit breakers

65 kA

85 kA

NS2500N

NW40bH1

NS3200N

NW2.H2/H3

NW25H1

NW32H2/H3

NW32H1

NW40H2

NW40H1

NW40bH2

65 kA

85 kA

90 kA

NS3200N

NW32H2

NW40bH1

NW32H1

NW40H2

NW50H1

NW40H1

NW40bH2
NW50H2
NW32H3
NW40H3

Max. Isc current in kA rms


KTC5000
Circuit breakers

95 kA
NW40bH1/H2
NW40H2/H3
NW50H1/H2
NW63H1/H2

K9CE31000.indd

version: 1.1

151

Design guide

Degree of protection

Canalis KTC
Standard IEC 60364-5-51 categorises a large number of external influences to
which electrical installations can be subjected, for instance the presence of water,
solid objects, shocks, vibrations and corrosive substances.
The importance of these influences depends on the installation conditions. For
example, the presence of water can vary from a few drops to total immersion.

Degree of protection IP

Standard IEC 60529 (February 2001) indicates the degree of protection provided
by electrical equipment enclosures against accidental direct contact with live parts
and against the ingress of solid foreign objects or water.
This standard does not apply to protection against the risk of explosion or
conditions such as humidity, corrosive gases, fungi or vermin.
The IP code comprises 2 characteristic numerals and may include an additional
letter when the actual protection of persons against direct contact with live parts is
better than that indicated by the first numeral.
The first numeral characterises the protection of the equipment against penetration
of solid objects and the protection of people.
The second numeral characterises the protection of the equipment against
penetration of water with harmful effects.

Remarks concerning the degree of protection IP

The degree of protection IP must always be read and understood numeral by


numeral and not as a whole.
For example, an IP31 enclosure is suitable for an environment that requires a
minimum degree of protection IP21. However an IP30 wall-mount enclosure is not
suitable.
The degrees of protection indicated in this catalogue are valid for the enclosures
as presented. However, the indicated degree of protection is guaranteed only when
the installation and device mounting are carried out in accordance with professional
standard practice.

Additional letter

Protection of persons against direct contact with live parts.


The additional letter is used only if the actual protection of persons is higher than
that indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by the letter "X", e.g. IPxxB.

Degree of protection IK

Standard IEC 62-262 defines a coding system (IK code) indicating the degree of
protection provided by electrical equipment enclosures against external mechanical
impact.
Installation standard IEC 60-364 provides a cross-reference between the various
degrees of protection and the environmental conditions classification, relating to
the selection of equipment according to external factors.

IK codepp

The IK code comprises 2 characteristic numerals (e.g. IK05).


Practical guide UTE C 15-103 shows, in the form of tables, the characteristics
required for electrical equipment (including minimum degrees of protection),
according to the locations in which they are installed.

152

version: 1.1

K9CE32000.indd

The new Canalis KTC busbar trunking products are designed to provide IP55D and
IK08 protection.
DD202437

Meaning of the numerals and letters


representing the degree of protection IP.

Non-protected.

Non-protected.

Protected against the


penetration of solid objects
having a diameter greater than
or equal to 50 mm.

Protected against direct


contact with the back of the
hand (accidental contact).

DD210014

Protected against vertical


dripping water (condensation).

Protected against the


penetration of solid objects
having a diameter greater than
or equal to 12.5 mm.

Protected against direct


finger contact.

DD210015

Protected against dripping


water at an angle of up to 15.

Protected against the


penetration of solid objects
having a diameter greater than
or equal to 2.5 mm.

Protected against direct


contact with a 2.5 mm
diameter tool.

DD210016

Protected against rain at an


angle of up to 60.

Protected against the


penetration of solid objects
having a diameter greater than
1 mm.

Protected against direct


contact with a 1 mm diameter
wire.

DD210017

Protected against splashing


water in all directions.

DD210009

Protected against direct


contact with a 1 mm diameter
wire.

Protected against water jets


in all directions.
Test duration: 1 mn/m casing

DD210010

Protected against direct


contact with a 1 mm diameter
wire.

Protected against powerful jets


of water and waves.

DD210011

Protected against the effects of


temporary immersion.

DD210012

Protected against the effects


of prolonged immersion under
specified conditions.

DD210013

Dust protected
(no harmful deposits).

Dust tight.

DD210008

DD210007

DD210006

Non-protected.

DD210018

2nd characteristic numeral: corresponds to


protection of equipment against penetration of
water with harmful effects.
Protection of equipment

DD210019

1st characteristic numeral: corresponds to protection of equipment against


penetration of solid objects and protection of persons against direct contact with
live parts.
Protection of equipment Protection of persons

Additional letter
Corresponds to protection of persons against direct contact with
live parts.

With the back of the hand.

B
C
D

With the finger.


With a 2.5 mm diameter tool
With a 1 mm diameter tool

Degrees of protection IK against mechanical impact

DD210533

The IK code comprises 2 characteristic numerals corresponding


to a value of impact energy, in joules.

Weight
(kg)
00

Non-protected

01

0.20

Energy
(J)

7.50

0.15

02

10

0.20

03

17.50

0.35

04

25

0.50

05

35

0.70

0.50

20

40

08

1.70

30

09

20

10

40

20

06
07

10

K9CE32000.indd

Height
(cm)

version: 1.1

153

Harmonic currents

Design guide

Canalis KTC
Harmonic currents are caused by non-linear loads connected to distribution
systems, i.e. by loads that draw current with a waveform different that that of the
voltage that supplies them.

Origin of harmonic currents

The most common non-linear loads are equipment including rectifiers, fluorescent
lighting and computer hardware.
In installations with a distributed neutral, non-linear loads may cause significant
overloads in the neutral conductor due to the presence of third-order harmonics.

DD210679

Harmonic order
The order is the ratio
between the harmonic
frequency fn and the
fundamental frequency
(generally the power
frequency, 50 or 60 Hz):
n = fn/f1
By definition, the
fundamental f1 is order 1
(H1).
Third-order harmonics (H3)
have a frequency of 150 Hz
(when f1 = 50 Hz).

The presence of third-order harmonics depends on the applications involved.


It is necessary to carry out an in-depth study on each non-linear load to determine
the level of H3:
ih3 (%) = 100 x i3 / i1
b i3 = rms current of H3
b i1 = rms current of the fundamental

Estimating THD (total harmonic


distortion)

Assuming that H3 is preponderant among harmonics, the THD is close to the value
of H3 (ih3 (%)).

PD202029_r

PD202028_r

There are two decisive factors:


b the types of connected devices:
v disturbing loads: fluorescent lighting, computer hardware, rectifiers, arc furnaces,
etc.
v non-disturbing loads: heating, motors, pumps, etc.
b the ratio between the two types of disturbing loads.

Workshops

Offices

Low probability of harmonics


THD y 15 %.

High probability of harmonics


15 % < THD y 33 %.

Mix of disturbing loads (computers,


UPSs, fluorescent lighting) and nondisturbing loads (motors, pumps,
heating).

154

version: 1.1

Numerous disturbing loads (computers,


UPSs, fluorescent lighting).

K9CE33000.indd

Ph1 Ph2 Ph3

Fundamental frequency: ih1 (50 Hz)

i h1

i h1

Ph1 Ph2 Ph3

i h1

i h1

i h1

i h3

i h3

i h3

i h3

i h3

i h3

DD210680

No current in the neutral.


The conductors are correctly sized.

i h1

DD210681

Effects of harmonics on Canalis busbar


trunking

Fundamental frequency: ih1 (50 Hz) and 33 % of


H3
Abnormal temperature rise in the conductors caused
by current at a higher frequency in the phases (skin
effect) and current in the neutral caused by summing
of the H3 harmonics.

i h3

i h3

Reduce the current


density in ALL conductors
by using appropriately
sized trunking.

i h3

i h3

i h1

i h3
i h3

i h1

i h1
i h3

i h3

i h1
i h3

i h1

i h1
i h3

Ph1 Ph2 Ph3

Fundamental frequency:
ih1 (50 Hz) and
33 % H3

Busbar-trunking selection
THD y 15 % 15 % < THD y 33 % THD > 33 %

Busbar trunking Rating (A)

1000

800

630

KTC

1000

1350

1000

800

KTC

1350

1600

1350

1000

KTC

1600

2000

1600

1350

KTC

2000

2500

2000

1600

KTC

2500

3200

2500

2000

KTC

3200

4000

3200

2500

KTC

4000

5000
4000
3200
KTC
5000
Example. For a total rms current of 2356 A (estimation based on power drawn by loads,
including harmonics), the operational current is 2500 A.
THD is estimated at 30 %. The appropriate trunking is KTC 3200 A.

For more information on harmonics

See the Cahier Technique publications on the Schneider Electric web site:
www.schneider-electric.com

K9CE33000.indd

version: 1.1

155

DD210683

i h3

Ph1 Ph2 Ph3

i h3

DD210680

The only effective solution

Direct current

Design guide

Canalis KTC
Determining the DC current value

Thermal effect
Rule
The total power dissipated as heat must remain constant in the duct:
Pac = Pdc
Where:
b the power dissipated as heat: Pac = 3 x R x Iac where:
v R= resistance of a conductor
v Iac = conductor rms current
b the dissipated power for 4 conductors: Pdc = 4 x R x Idc where:
v Idc = direct current.

Selection table

DD210893

b 1 source
Case of 2 conductors in parallel for the + and 2 conductor in parallel for the (only
1 circuit in the busbar trunking):

DD210894

b 2 sources
Case of 1 conductor for the + and 1 conductor for the (2 circuits possible in the
same busbar trunking):

156

Busbar trunking rating (A)

1 source

2 sources

1000

1732

866

1350

2165

1083

1600

2771

1385

2000

3464

1732

2500

4330

2165

3200

5542

2771

4000

6928

3464

5000

8660

4330

version: 1.1

K9CE34010.indd

Protection

With DC, there is no zero crossing point of the voltage and current to facilitate arc
extinction in the protective device.
The arcing time is longer and the energy that has to be absorbed is higher than for
AC.
The voltage of the DC arc must rise to the source voltage very quickly in order to
"put out" the short-circuit current.
"Shortened" electrical equation: U network = R x Isc + Uarc where:
b Isc = U network - Uarc / R
b Isc = 0 when Uarc = U network.

Use with specific switchgear

A quick rise in arcing voltage can be achieved by using series fuses, one fuse on
the + and one fuse on the of each circuit.
For some current rating and fuse characteristics, the placing of two fuses in series
on each polarity may be specified (highly inductive circuit).
In some cases, two fuses must be placed in parallel for each polarity.

K9CE34010.indd

version: 1.1

157

Design guide

Frequencies
400 Hz

Canalis KTC
KT busbar trunking derating at 400 Hz

Values at 35 C.
Application of a derating coefficient at 400 Hz combined with that for temperature
derating.
Busbar trunking derating
KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Voltage drop

In (A)

688

851

1014

1327

1635

2024

2394

3162

Coefficient K at
400 Hz

0.86

0.85

0.84

0.83

0.82

0.81

0.80

0.79

3-phase voltage drop, in millivolts per metre and per amp 400 Hz with load spread
over the run.
For a concentration of load at the end of a run (transport), the voltage drops are
double those shown in the table below.
Delta U evenly spread (mV. A. m)
KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50

Conductor characteristics

Cos = 1.0

0.079

0.068

0.057

0.044

0.038

0.033

0.025

0.020

Cos = 0.9

0.12

0.109

0.096

0.079

0.067

0.054

0.045

0.039

Cos = 0.8

0.13

0.121

0.108

0.089

0.076

0.060

0.051

0.045

Conductor impedance
KTC10 KTC13 KTC16 KTC20 KTC25 KTC32 KTC40 KTC50
Average ohmic
resistance of
phase and neutral
conductors at In (1)
Rb1ph (m/m)

158

0.092

0.079

0.066

0.051

0.044

0.039

0.029

0.023

Average resistance
0.14
0.128
0.120
0.104
at In and rated
(1)
F(Hz)
Xph (m/m)
(1) In line with the CENELEC RO.64.013 document.

0.088

0.064

0.059

0.056

version: 1.1

K9CE34020.indd

Measurements and metering


Transparent Ready units

Transparent Ready is a simple solution to access information (status,


measurements, etc.) available from your electrical distribution equipment
(transformers, switchboards, busbar trunking).

DD205669_r

The Transparent Ready concept

This information can be accessed from any PC connected to your Ethernet network
via a simple Web browser (e.g. Internet Explorer). No other software is required.

DD205671

DD205668_r

DD205666

Transparent Ready can make your company more competitive by:


b reducing operating costs
b optimising equipment performance
b improving the reliability of the electrical power supply.

Customer needs for measurements and


metering

In all non-residential buildings, the need for sub-metering exists and is growing
underthe combined effects of:
b national and supra-national energy regulations
b the need to reduce overheads and production costs
b the allocation of energy expenditures to cost centres
b the outsourcing of operations tasks to specialists.
Operators must therefore have access to reliable pre-processed information in
order to:
b identify areas for potential savings
b model building energy flows and anticipate evolving needs
b optimise energy supply and consumption.

K9CE34030.indd

version: 1.1

159

Measurements and metering

Design guide

Transparent Ready units


Canalis KTC

Canalis offers measurement and metering units that can be mounted on both
Canalis KS and KT trunking ranges, available in two ratings (250 A and 400 A).
They are equipped with mounting plates designed to receive a PowerLogic
PM810 Power Meter, a Compact NS circuit breaker and the associated current
transformers.

DD205664

Canalis and Transparent Ready

These units are connected to Transparent Ready solutions using a Modbus


communication network.

DD205663

An automatic PowerLogic gateway (EGX400) provides the link between Modbus


and Ethernet TCP/IP networks.

When busbar trunking is located upstream of a secondary trunking line, the


measurement devices should be installed in the tap-off units.

DD205665

Data acquisition in distributed


architectures

160

version: 1.1

K9CE34030.indd

When the power-monitoring unit is installed in a tap-off unit, it is often too high for
easy reading of the measurements.

DD205667n

Canalis and Transparent Ready

We therefore recommend using a Power Meter PM810 with a Modbus


communication option.

DD202287n

Then the Canalis solution is to install a KBA line 25ED4303T parallel to the main
line and dedicated to carry the information (as a Modbus network) from the
powermonitoring tap-off unit to the Ethernet TCP/IP network (see "The Transparent
Ready Concept") and the connections are:

K9CE34030.indd

version: 1.1

161

Design guide

Fire resistance

Canalis KTC
As required by standards, Canalis KT busbar trunking complies with:
1 - material resistance to abnormal temperatures.
2 - flame propagation resistance.
3 - fire barrier function when going through a partition wall.
4 - conservation of all circuits for 1.30 hours in an insulating sheath.

Definition of tests

1 - Insulating material resistance test to abnormal


temperatures
Objective
To check a material will not be suspected as being the origin of a secondary fire
outbreak.
As defined in standards 8.2.13 IEC 60439-2 and IEC 60695-2-10 to -2-13.
Method
Application of an incandescent wire for 30 seconds on the insulating materials in
contact with live parts.
Result criteria
The specimen is considered to have passed the incandescent wire test if:
b if there is no visible flame and no sustained incandescence
b the specimens flames and incandescence go out within 30 seconds of the
incandescent wire being removed.

2 - Flame propagation resistance test


Objective
To check a busbar trunking will not create secondary fire outbreaks.
As defined in standards 8.2.14 IEC 60439-2 and IEC 60332 part 3.
Method
b Application of a flame for 40 minutes on a straight length of busbar trunking
whose centre is located 2.5 metres from the edge of the burner.
Result criteria
The specimen is considered to have passed the test if:
b combustion does not occur
b the maximum extent of the burned part (external and internal) of the busbar
trunking does not go beyond 2.5 metres above the lower edge of the burner.

162

version: 1.1

K9CE35000.indd

Fire resistance

3 - Fire barrier test through a partition wall


Objective
To check a busbar trunking will not propagate a fire from one room to another by
crossing a fire barrier wall for 60, 120, 180, or 240 minutes.
As defined in standard EN 1366-3; EN 1363-1; ISO 834; DIN 4102 part 9.
Method
The fire barrier busbar trunking section to be tested is placed in an oven which
executes a standardised temperature-time curve.
Result criteria
The specimen is considered to have passed the test if:
b there are no flames behind the fire barrier
b there is no smoke or gas behind the fire barrier (not requested by the standard;
can appear as a remark in the test report)
b the temperature rise of the casing behind the fire barrier does not exceed 180 C.

4 - Conservation of all circuits in fire conditions test


Objective
To check all the busbar trunkings electrical circuits are preserved in fire conditions.
As defined in standard DIN 4102 part 12.
Method
Its entire length inserted, the busbar trunking is taken as a specimen in an
insulating sheath.
Result criteria
The specimen is considered to have passed the test if:
b conductor continuity is preserved
b there is no short-circuit between conductors.

K9CE35000.indd

version: 1.1

163

Seismic resistance

Design guide

Canalis KTC

DD405612

Seismic zones worldwide


zone 4
zone 3
zone 2
zone 1
zone 0

Canalis KT is seismic certified in accordance with the protocol described in IEC


60980 and a seismic level equivalent to >7 on the Richter scale and severity 9 on the
international MSK- 64 scale.
The spectrum used for testing is the one specified for civil engineering and nuclear
applications in GOST 17516.1-90.

DB402698

Spectrum according to GOST


GOST nuclear market spectra
4

Acceleration (g)

10

15

20

25

30

Frequency (Hz)
GOST horizontal
GOST vertical

164

version: 1.1

K9CE35000.indd

Installation and support

Supports for conventional applications can be used for seismic applications by


following the recommendations below:

DB402682

b For flexible support


Use of supports and rods, reference KTB0000ZA1, with a minimum length of 1000
mm and additional clamping as per the following diagram.

Safety limit: 250 mm round the busbar trunking (amplitude noted during testing).

DB402683

b For rigid support


Use of conventional mechanically welded consoles with rigid busbar trunking
fastening.

For both cases:


b its conventional fixing centre distances are maintained (3 m edgewise, 2 m flat)
b the levels achieved are applicable for horizontal, edgewise or flat or vertical
installations.

K9CE35000.indd

version: 1.1

165

Design guide

Testing and commissioning


procedure

Canalis KTC
All the operations described below are given for indication only. Under no
circumstances can they be used to substitute the installation companys own
procedures and engage Schneider Electrics responsibility.

Scope

High power busbar trunking, transformer-switchboard links.


Required tools
b Multimeter.
b 500 V megger.
b Roto-phase.

Prerequisites

b If need be, the old equipment has been removed from the premises.
b The new equipment has been manoeuvred into the premises where it is to be
installed by the installation contractor.
b The equipment has been installed by the installation contractor in accordance
with manufacturers recommendations.
b The equipments installation diagram, connection diagram and assembly results
sheet are available for the commissioning engineer.

De-energising the installation and making it safe

The works manager is responsible for worksite safety and must ensure the
installation is de-energised and made safe in accordance with safety rules before
any inspection or measurement is performed.

Equipment checking, positioning and


identification

After the installation contractor has positioned, assembled and connected the
busbar trunking in accordance with the supplied installation, assembly and
connection diagrams, and using the recommended tools and handling equipment,
the following characteristics must:
b be noted
b be checked for compliance with respect to the details shown on the drawing.
Brand

Busbar trunking rating:

Equipment type:

Serial number:

Reference:

Date of manufacture:

Transformer power:

Source circuit breaker


(busbar trunking
protection):

General visual inspection

The equipment has been chosen according to its electrical environment (rating and
protection adapted to operating conditions).
The following points do not require checking.
Points concerning reception, storage and handling
No signs of:
b shock (which may deteriorate internal insulation: conductor insulation on straight
lengths or at the tap-off points or joint blocks)
b humidity or oxidation (equipment stored outside should have been covered with
a plastic sheet, sheltered from humidity, dirt and dust)
b firms label defining the products characteristics.

166

version: 1.1

K9CE36000.indd

DD206098

Points concerning installation and fittings


Assembly compliance with the specifications of the installation drawing, service
instructions and the catalogue:
b no busbar trunking twisting
b positioning and distance of the busbar trunking with respect to the building
b fixings, compliance of the between centres distance of the equipment for flat or
edgewise, horizontal or vertical distribution
b clamps, not fully blocked to allow movement due to longitudinal forces
b presence of expansion sections if necessary.

General visual inspection

Checking power connections


DD210781

Check the number of connection parts and their cross-sections for each conductor
(see "Installation guide").
Check insulation distances between 2 conductors and between conductors and
metal panels.

DD210764

DD202389

Check the tightening torque of bolts not fitted with torque nuts. For bolts fitted with
torque nuts, check the head has broken-off.

Check the bolt length exceeding the nut ; some bolts may have been removed and
then put back, but left untightened.
Mark each tightened nut using indelible varnish. As well as a means of selfinspection to ensure correct tightening torque, it also allows any untightening to be
identified.
Class 8-8 nuts and bolts (M8 on LV switchboard side, see "Commissioning Guide
for Schneider Electric LV Switchboards").
Bolt
HM16
HM14
HM12
HM10

Tightening torque
16 mdaN
12 mdaN
7 mdaN
5 mdaN

PB104861

The results of all these checks must be noted on the results sheet by the
installation contractor.

Checking insulation between live conductors

These measurements and checks can only be performed if:


b each link is disconnected by an isolating device
b each link is disconnected from the upstream transformer, with the main circuit
breaker upstream of the LV switchboard unplugged and in the open position.
Test means: 500V DC megger (DC to avoid capacitive currents)
Measurements: 6 measurements between live conductors (between phases and
then between each phase and neutral).
LV circuit insulation value (U < 500 Volts): 1000 ohms/volt of nominal voltage
(IEC 60 439-1) allowed.
In all cases, the insulation resistance must not be less than 0.5 M for each link
(operating device).
Note: KT busbar trunking is given for U = 1000V and Ri = 1 M (value to be taken
into account for all elements: transport and accessories, distribution).
K9CE36000.indd

version: 1.1

167

Design guide

Testing and commissioning


procedure

Canalis KTC
Checking the earth network and locks

Earth network
General visual inspection
Check:
b the galvanised steel casing sides are earthed (note: this depends on the earthing
system)
b connection quality
b cable cross-section
b there are no loose metal parts (washers, screws) in the tap-off units.
Note: the results of these checks must have already been noted on the results
sheet by the installation contractor.
Checking insulation between live conductors and earth
Following this check, each link must be reconnected to the upstream transformer
(use the 2nd available 6 daN.m torque bolt heads).

PB104862

Test means: 500V DC megger (DC to avoid capacitive currents)


Measurements: between each phase or neutral (1) and earth (the casing if it is
connected to earth).
LV circuit insulation value (U < 500 V): 1000 of nominal voltage (IEC 60 439-1)
allowed.
In all cases, the insulation resistance must not be less than 0.5 M for each link
(operating device).
Note: KT busbar trunking is given for U = 1000 V and Ri = 1 M (value to be taken
into account for all elements: transport and accessories, distribution).
(1) No neutral insulation if the earthing system is such that the neutral is connected to or used
as the earth.
Caution: In this case, once the transformer has been reconnected (star secondary), the phaseearth measurement is the winding resistance.

PE protective circuit equipotential

Reference: IEC 60 439-1:


Check PE protective circuit continuity by visual inspection and random continuity
testing.
The previously performed "phases-PE" insulation test must have been compliant.
Test means: ohmmeter.

Locks

To protect personnel by not allowing access to live parts through the use of locks.
Only concerns key operated safety locks.

Checking connections and auxiliary


testing

168

Check not relevant to busbar trunking.

version: 1.1

K9CE36000.indd

De-energised equipment operating tests

Checking source circuit breaker protection settings

Compliance check in accordance with the installation drawing specifications:


b Imax thermal
b In magnetic.
Note: this check is only to be performed if the busbar trunking is commissioned
at the same time as the transformer: the source circuit breaker protection setting
checks are related to transformer commissioning.
Check not relevant if the transformer has already been commissioned.
If this check is successful, the busbar trunking can be commissioned and
the energised operating tests performed with the appropriate protective
equipment

Commissioning and energised


equipment operating tests

Note: commissioning can only be carried out by personnel with appropriate


authorisations.
Preliminary operation: energising the off-load transformer.
Closing the source circuit breaker.

Checking phase order

Objective: to detect, in order to correct, an inversion of the phases or neutral


amongst the busbar trunkings 4 incoming and outgoing connections with respect
to the transformer output.
Test means: roto-phase or 3-phase harmonic analyser.
If busbar trunking energising is successful, a progressive start-up of the factory
must be requested to definitively validate commissioning.
If unsuccessful, the previous checks must be carried out again to try and
locate the fault. Before undertaking this, the equipment must once again be
made safe.

Final putting into service test

This test is performed once the busbar trunking has been energised. The
progressive start-up of loads will highlight any undesirable phenomena due to the
increased average load.
Real life operating test
Once the high power busbar trunking has been energised, the other busbar
trunking must be gradually put into service starting with those furthest from the
load, then each load itself, those with high pull-in currents, then the lighting,
contactors, heating, motors, etc.
There must not be excessive vibration, and no sparkovers should be observed.
The test simply consists of checking correct busbar trunking operation according
to:
b the average number of machines in operation
b the load variation of each individual load
b the simultaneous operation of machines (superimposing of peaks).
If everything is in order, the busbar trunking is declared "in-service".
Testing is completed.

K9CE36000.indd

version: 1.1

169

170

version: 1.1

K9CE36000.indd

Contents

Design and installation guide

Index
Introduction
Presentation and description
Catalogue numbers and dimensions
Design guide

3
17
35
63
133

Layout advice

172

Run optimisation 172


Positioning and supports 175
Anticipate unexpected worksite problems 178
Tips for determining dimensions at the worksite 179

Horizontal distribution

182

Positioning the tap-off units 182


Tap-off units 183
Checking and compensating for expansion 184

Rising mains

188

General 188
Positioning the busbar trunking without external fire barrier 189
Positioning the tap-off units 190
Positioning of supports 191
Positioning the external fire barriers 192
Installation with feed via a cable box or direct onto the switchboard 193

Panorama ofconnection solutions

196

Connection to LV switchboards

198

Selection guide 198

DEBU024EN_Installation guide.indd

Connection to Okken andPrisma Plus LV switchboards

200

By Canalis interface

200

Connection to Okken switchboards

201

By Canalis interface

201

Connection to Prisma Plus LV switchboards

203

By Canalis interface

203

Connection to Okken andPrisma Plus LV switchboards

205

By Canalis interface

205

Connection to LV switchboards

206

By universal feed unit


Via flange feed unit and flexible bars
By feed and connection plates

206
208
209

Connection to cast resin transformers

212

Selection guide

212

Connection to Trihal cast resin transformers

214

By Canalis interface
By universal feed and connection plates

214
217

Connection to oil immersed transformers

222

Selection guide
By feed and connection plates or braids
Other connection solutions

222
224
229

Recommandations

231

version: 1.1

171

Layout advice

Installation guide

Run optimisation
Canalis KTC

CanBrass software can be used to design the busbar trunking line.


The easy-to-use program creates a graphic model of the line, determines the
length and draws up the list of Canalis KT parts to order.

PD202428_r

CanBrass software

The Canalis KT line is easy to specify simply by indicating the required dimensions.
However, it is strongly advised to use the shortest and simplest path possible
between the transformer and the switchboard.
It is important to carefully plan the layout of the transformer and switchboard in
order to use:
b the maximum number of standard components rather than made-to-measure
components
b the minimum number of components for changing direction
b straight made-to-measure components rather than made-to-measure
components for changing direction.

Before defining your busbar trunking run, it is recommended you pay particular
attention to the various parameters which could be detrimental to the installation.

Advice

DD210900

DD210895

Obstacles that obstruct the busbar trunking such as beams,


pipes, etc.

DD210903

DD210902

Badly positioned places for going through walls and floors.

172

DD210896

DD210897

Joint positions in the middle of a partition wall.

version: 1.1

K9CE41000.indd

Insufficient ceiling height.

DD210898

DD210899

If the busbar trunking must be installed edgewise between a transformer and


switchboard, ensure the ceiling height is sufficient for fitting the joint blocks from
the top.
Reserve a space between the busbar trunking and the ceiling equal to 100 mm
(variable depending on the rating, see "Catalogue numbers and dimensions").

DD210903

DD210904

Going through a floor to bottom feed a switchboard on the


next floor.

DD210905

Difference in floor levels of 2 rooms.

Also make sure that as the work progresses other tradesmen do not carry out
installations that could hinder your initial layout.

K9CE41000.indd

version: 1.1

173

Layout advice

Installation guide

Run optimisation
Canalis KTC

Example 1
Reducing the number of changes of direction by modifying the switchboard or
transformer layout.
DD210910

Examples of link optimisation

DD210911

Example 2
Use of 2 standard elbows in place of a made to measure zed by increasing
dimension "L".

DD210912

Modification of the busbar trunking height


By slightly increasing dimension "Z", replace a made to measure elbow feed
connector with a standard feed connector and standard elbow section.

When choosing the layout of the electrical installation, it is important care is taken
when positioning the neutral between the transformer and the switchboard.
If the neutral position is different to that planned, it is recommended the transformer
is moved, if possible, to align the neutral with respect to the switchboards neutral.
When it is not possible to move the transformer, it is recommended the phase order
in the switchboard is inversed.
If this cannot be done, use the phase and neutral transposition section.
DD210780

Neutral position

KTCppppTNp10

KTCppppTPp10

174

version: 1.1

K9CE41000.indd

Layout advice

DD210935

Positioning and supports

Edgewise passage through


partition wall
DD210932

DD210933

Flat passage through partition wall

K9CE41000.indd

Rating (A)

1000

1350

1600

2000

2500

3200

4000

5000

Height H (mm)

74

104

124

164

204

244

324

404

version: 1.1

175

Layout advice

Installation guide

Positioning and supports


Canalis KTC
A support point as close as possible to the connections is needed because
transformers, generator sets and switchboards must not support the weight of the
busbar trunking.
In some industries, for service continuity reasons, transformers may be replaced
quickly. The busbar trunking must be able to support itself.
The maximum recommended distance between supports is 3 metres.
In all cases, provide for 2 supports for 4 metre sections.

Edgewise horizontal installation

DD210930

For clamping busbar trunking to support brackets, see page 186.

3000

The recommended distance between supports is 2 metres. In addition, a support


must be placed at 300 or 400 mm from the joint block axis.

Flat horizontal installation

DD210931

For clamping busbar trunking to support brackets, see page 186.

Plan for a maximum distance between supports of 3 metres.


DD210929

Example of spreading out supports

176

version: 1.1

K9CE41000.indd

The position of the joint block with respect to the transformer axes and switchboard
edges (defined in the "Installation guide").
DD210924

Defining the layout, dimensions to be


provided

Distance between busbar trunking


(without tap-off units)

Edgewise installation
DD210928

DD210927

Flat installation

Rating (A)

1000

1350

1600

2000

2500

3200

4000

5000

Height H (mm)

74

104

124

164

204

244

324

404

Edgewise installation
DD210925

Distance of the busbar trunking from


the wall

(1) Provide 2 times the height if the joint block must be fitted from the top.
Direction of fitting joint blocks.

DD210926

Flat installation

Direction of fitting joint blocks.

K9CE41000.indd

version: 1.1

177

Layout advice

Installation guide

Anticipate unexpected worksite problems


Canalis KTC
This section will be ordered after the gap to be filled has been measured at the end
of the job. To optimise its delivery to site, prefer a straight section with a length of
less than 2 metres rather than made to measure elbows.
DD210906

1: Standard straight
section.
2: Made to measure
elbow.

DD210907

DD202390

Undecided section

3: Made to measure
straight section.
4: Standard elbow.

DD210908

On the drawing, provide a minimum dimension of 700 mm to guarantee an


adjustment of 200 mm on-site. The minimum length of straight sections being
equal to 500 mm.

In order to provide for the place needed for an adjustable or undecided section,
install the elbows and the sections attached to the elbows in each angle (support
each assembly using 2 supports on each straight section).
DD210994

Layout recommendations for adjustable


or undecided sections

And then complete the layout with standard and made to measure straight
sections.

178

version: 1.1

K9CE41000.indd

Layout advice

Tips for determining dimensions at the


worksite
The nominal length "L" of a straight section is measured from the axis of the
joint block to the other axis of the joint block, in millimetres (the joint block axis is
located 20 mm from the end of the bars).
Dimension L of the standard or made to measure section = x - 40 mm.
DD210913

Straight section

(1): For the different busbar trunking heights, see page 177.
(2): See "Run sections" in "Catalogue numbers and Dimensions".
x : measured dimension.

Example: x = 1860 mm hence L = 1860 - 40 = 1820 mm.

Flat elbows

Change-of-directions

DD210918

DD210916

The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.

A and B: See "Changes of direction" in "Catalogue numbers


and Dimensions".

"Flat" elbow, external positioning


A = A1 + A2 + (140/2) - 20
"Flat" elbow, internal positioning
A = A1 - A2 - (140/2) - 20
(1) See "Changes of direction" in "Catalogue numbers and Dimensions".

K9CE41000.indd

version: 1.1

179

Layout advice

Installation guide

Tips for determining dimensions at the


worksite
DD210917

Canalis KTC
Edgewise elbows

DD210919

The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.

A and B: See "Changes of direction" in "Catalogue numbers


and Dimensions".

"Edgewise" elbow, external


positioning
A = A1 + A2 + (H/2) - 20

"Edgewise" elbow, internal


positioning
A = A1 - A2 - (H/2) - 20

(1) See "Changes of direction" in "Catalogue numbers and Dimensions".

DD210921

Flat Zed

DD210922

The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.

A, B and C: See "Changes of direction" in "Catalogue


numbers and Dimensions".

B = B1 - B2
(1) See "Changes of direction" in "Catalogue numbers and Dimensions".

180

version: 1.1

K9CE41000.indd

DD210920

Edgewise Zed

DD210923

The nominal length of each branch is measured from the axis of the joint block to
the axis of the other branch, in millimetres. The joint block axis is located 20 mm
from the end of the bars.
The nominal length of the intermediary branch(es) is measured from the axis of
one branch to the axis of another.

A, B and C: See "Changes of direction" in "Catalogue


numbers and Dimensions".

B = B1 - B2
(1) See "Changes of direction" in "Catalogue numbers and Dimensions".

Reminder: the final section should preferably be a straight section.


Take into account the neutral position when choosing the section.

Definition of final section parameters

DD210914

Tools
Tape
measure

Spirit level

Lead line

Stick

Ruler

Laser or infra-red reader

DD210915

Their use

K9CE41000.indd

version: 1.1

181

Horizontal distribution

Installation guide

Positioning the tap-off units


Canalis KTC

PD202398_r

It is possible to combine the following in the same installation:


b straight transport sections with straight sections containing fixed or plug-on tapoff points
b straight sections of different lengths
b straight sections with different numbers of fixed or plug-on tap-off points
b

Several configurations are possible.


Some examples:
b on a 2000 mm straight section with plug-on tap-off points (KTCppppEDp20):
v 3 x 160 A circuit breaker tap-off units:
DD210938

Positioning the tap-off units on the


busbar trunking

DD210936

v 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit

DD210939

v 3 x 160 A fuse tap-off units:

DD210995

b on a 4000 mm straight section with plug-on tap-off points (KTCppppEDp40):


v 1 x 400 A circuit breaker tap-off unit, 1 x 250 A circuit breaker tap-off unit and 1 x
160 A circuit breaker tap-off unit:

DD210996

v 1 x 400 A fuse tap-off unit, 1 x 250 A fuse tap-off unit and 1 x160 A fuse tap-off
unit:

DD210937

b on a 4000 mm straight section with fixed tap-off points (KTBppppEBp40):


v 1 x 400 to 630 A fixed tap-off unit and 1 x 800 to 1000 A fixed tap-off unit:

Cable exit.

182

version: 1.1

K9CE41000.indd

Horizontal distribution
Tap-off units

DD210997

When the tap-off units have to be distributed along the length of the busbar
trunking, use 2 metre sections and alternate the tap-off point positions.

For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.
DD210940

Recommendations for installing


2parallel busbar trunking runs

Type

Circuit
breaker
tap-off units

Fuse tap-off
units

KSB160DCp

160

150

KSB250DCp

240

160

KSB400DCp

240

160

KTB0630CBp

175

175

KTB1000CBp

275

275

KSB160SEp

150

150

KSB250SEp

250

160

KSB400SEp

440

160

DD210941

Cat. no.

Dimensions
(mm)
X
E (1)

Circuit
breaker
tap-off units

KSB160DCp

625.5

246

KSB250DCp

726.5

300

KSB400DCp

976,5

350

Fuse tap-off
units

KSB160SEp

577,5

207

KSB250SEp

777

258

KSB400SEp
(1) With the handle.

855

316

DD210942

Type

Rating (A)

K9CE41000.indd

Dimensions
(mm)
A
B

Provide for a minimum distance of 1000 mm between the busbar trunking and the
ceiling to allow for the opening of tap-off unit doors.

Tap-off unit door opening

Installing an isolator or run protective


device

Cat. no.

Dimensions (mm)
A
B

1000

174

514

1350

159

529

1600

149

539

2000

129

559

2500

109

579

3200

89

599

version: 1.1

183

Horizontal distribution

Installation guide

Checking and compensating for


expansion
Canalis KTC
DD202446

Expansion poses a problem when:


b the runs are made up of long straight sections
b when the busbar trunking passes through an expansion joint between two
buildings.

Electrical busbar trunking can be subjected to a multitude of load variations during


its service life (e.g. day / night, summer / winter) which cause temperature rise
differences and thus variable expansions.
To absorb expansion in a Canalis KT busbar trunking, a specific section must be
used: the expansion section.

Long part runs

Horizontal runs without tap-off units

If the busbar trunking length is greater than 30 metres, provide for expansion
sections and appropriate blocking means. The ends and, in some cases, the
centre of part runs must be blocked in order to direct the extensions towards the
expansion sections.

DD210998

Layout of expansion sections and blocking means for the following busbar
trunking lengths:
b 0 to 30 metres:

DD210999

b 31 to 60 metres:

DD211000

b 61 to 90 metres:

DD211001

91 to 120 metres:

Blocked fixing supports,


Expansion section,
Direction of expansion.

184

version: 1.1

K9CE41000.indd

Horizontal runs with tap-off units

DD211002

Layout of expansion sections and blocking means for the following busbar trunking
lengths:
b 0 to 30 metres:

DD211003

b 31 to 60 metres:

DD211004

b 61 to 120 metres:

Blocked fixing supports,


Expansion section,
Direction of expansion,
Tap-off unit.

DD2111005

Transformer / switchboard links

Blocked fixing supports,


Expansion section,
Direction of expansion.

K9CE41000.indd

version: 1.1

185

Horizontal distribution

Installation guide

Checking and compensating for


expansion
Canalis KTC
Rules for fixing busbar trunking to the supports

DD211006

For correct system operation, the expansion of the part run in question must be
directed towards the expansion section.
This implies:
b the busbar trunking must be free from all longitudinal movement on its supports
b the expansion section must be blocked on the opposite side to that by which it is
pushed.

1
2

Free fixings.
Blocked fixings.
Direction of expansion.

Installation of free fixings


Edgewise assembly
DD211008

DD211007

Flat assembly

Installation of blocked fixings


Edgewise assembly
DD211009

DD211010

Flat assembly

186

version: 1.1

K9CE41000.indd

Here, the expansion section allows the busbar trunking to absorb the forces due to
the relative movement between the 2 buildings.
DD211012

Passing through a joint between


2buildings

Building A

Building B

DD211011

Blocked fixing supports.

1 Blocked fixings.

Installation of blocked fixings


Flat assembly

DD211009

DD211010

Edgewise assembly

K9CE41000.indd

version: 1.1

187

Installation guide

Rising mains
General

Canalis KTC
PD202319_r

Canalis KT enables power distribution to each floor of multi-storey buildings (office


buildings, hotels, hospitals, etc).
In this application, Canalis KT retains all its construction principles:
Vertically mounted, the protection degree of the KT busbar trunking is IP55 as
standard.

Installing a rising main


1 Installation principle
Installation at each floor of:
b a 2 metre distribution section,
b a made to measure transport section to go through the floor slab,
b a busbar trunking support,
b up to 3 x 160 A tap-off units or a 250 or 400 A tap-off unit and a 160 A tap-off unit.

2 Installation feed
The installation feed is achieved using either a cable box or by direct connection to
an electrical distribution switchboard.

3 Busbar trunking supports


The supports fix the vertical run section to the building structure. a floor slab
support. It can be fixed to either the wall, to a wall bracket or directly to the floor,
This type of fixing support has the following advantages:
b fitting to either the wall, to a wall bracket or directly to the floor
b height adjustment to make up for positioning errors
b depth adjustment from 50 to100 mm
b spring adjustment to ensure distribution of the load at each floor
b absorption of building stresses with respect to the busbar trunking (expansion,
vibration, etc) thanks to the springs.

4 Tap-off units
All Canalis KS tap-off units can be mounted vertically on the Canalis KT without the
risk of interference with the supports.

188

version: 1.1

K9CE45000.indd

DD210960

Positioning the busbar trunking without


external fire barrier
Positioning the neutral

The busbar trunking must be positioned with the neutral on the right.

Positioning the joint block

It is important the joint block is not positioned in the floor slab.

DD210961

We recommend you provide for a distance of:


b 400 mm between the floor slab and the joint block axis to be able to install a
support to the wall or wall bracket to facilitate the re-filling of the hole and to cope
with possible building faults (e.g. screed not indicated on the drawings). Provide
500 mm for a floor fixing.
b 200 mm between the upper joint block and the ceiling to allow the busbar
trunking to be boxed-in when filling-in the hole with plaster or concrete.

Positioning the tap-offs

The run sections are fitted with 3 tap-off points. Spaced at 500 mm intervals, they
provide a high density of tap-offs per floor.

Flat passage through


partition wall

K9CE45000.indd

DD210933

DD210932

Edgewise passage through


partition wall

Rating (A)

800

1000

1250

1600

2000

2500

3200

4000

height H (mm)

74

104

124

164

204

244

324

404

version: 1.1

189

Rising mains

Installation guide

Positioning the tap-off units


Canalis KTC
DD210962

Positioning the tap-off units on the busbar trunking

Several configurations are possible.


Some examples:
1 - 3 x 160 A circuit breaker tap-off units
2 - 1 x 400 A circuit breaker tap-off unit and 1 x 160 A circuit breaker tap-off unit
3 - 3 x 160 A fuse tap-off units
4 - 1 x 800 to 1000 A bolted tap-off unit.

Cable exit
DD210964

R = 12 x of cable

Recommendations for installing 2 rising mains in parallel

Cable exit.

DD210954

For an installation with tap-off units, provide for a between centres distance that
takes into account the minimum dimension of 100 mm and the dimensions A and B
of the tap-off units.

Type

Circuit
breaker
tap-off units

Fuse tap-off
units

Cat. no

Dimensions
(mm)
A
B

KSB160DCp

160

150

KSB250DCp

240

160

KSB400DCp

240

160

KTB0630CBp

175

175

KTB1000CBp

275

275

KSB160SEp

150

150

KSB250SEp

250

160

KSB400SEp

440

160

Tap-off unit door opening

DD210963

If installed in a technical room, provide for a minimum distance of 1000 mm


between the busbar trunking and the wall in order to be able to open the doors of
the tap-off units.

190

version: 1.1

K9CE45000.indd

Positioning of supports

DD210968

2 fixing systems are available:


b a rear wall fixing system for 800 A to 1600 A busbar trunking
b a side wall fixing system for 2000 A to 4000 A busbar trunking.

DD210967

Wall support

Wall drilling drawing to fix


the support.

1000 to 2000 A

2500 to 5000 A

(1) Dimensions with free springs.


Y : 50 mm minimum to 100 mm maximum

DD210966

Wall bracket support (if Y > 100 mm)

X u 400.

1000 to 2000 A

2500 to 5000 A

DD210965

Floor support

1000 to 2000 A

K9CE45000.indd

2500 to 5000 A

version: 1.1

191

Rising mains

Installation guide

Positioning the external fire barriers


Canalis KTC
Horizontal mounting

200

DB401852

DB401853

Vertical mounting

The filler material around the


busbar trunking must meet the
requirements currently in force to
guarantee that the wall and
ceiling fire-resistance class
(for example DIN 1045 and
DIN 1053-1) is maintained.
Filler material not supplied.

400

200

200

400

200

L
650
650
650
750
750
750
950
950

200

DB402665

600

DB402664

500

500

Rating
KTC1000
KTC1250
KTC1600
KTC2000
KTC2500
KTC3200
KTC4000
KTC5000

20

Distances to comply
DB402678

DB402680

Edgewise passage through partition wall

DB402681

Flat passage through partition wall

DB402679

192

version: 1.1

K9CE45000.indd

Installation with feed via a cable box or


direct onto the switchboard

Installation with feed via a cable box.

K9CE45000.indd

DD210979

2 possibilities:
b installation with feed direct to the switchboard
b installation with feed via a cable box.

version: 1.1

193

Rising mains

Installation guide

Installation with feed via a cable box or


direct onto the switchboard
Installation with feed direct to the
switchboard

194

DD211013

Canalis KTC

version: 1.1

K9CE45000.indd

K9CE45000.indd

version: 1.1

195

Design and installation guide

Panorama of
connection solutions

Canalis KTC
The Schneider Electric system
The comprehensive Schneider Electric system makes it simple to design a
complete transformer/Canalis KT/switchboard installation.
Using dedicated interfaces, the trunking connects directly to the dry-type
transformer and the switchboard for:
b tested and standardised connections
b fast and flexible installation
b shorter lead times.
Advantages
b No design work for the connections.
b Simplified layout design:
v pre-defined position of the jointing unit
v simplified routing (only three dimensions required)
v smaller size (no additional covers required).
b Transformer and switchboard supplied with connections already mounted.
b Short lead times and fewer catalogue numbers for connections.
b Adaptable on the worksite:
v transformer end: 15 mm adjustments along all three axes
v switchboard end: phases can be inverted.
b Continuity of service:
v transformer can be replaced in less than one hour
v transformer, trunking and switchboard designed to be used together.
b Safety:
v trunking fully tested in compliance with IEC 60439-1 and 2
v compliance with standards and installation rules
v excellent fire-withstand capability.
b Comfort:
v low level of electromagnetic radiation
v no noise.
Compatibility between Trihal transformers/Canalis KT/Prisma Plus or Okken switchboards
Trihal transformers
Rating
Naturally
ventilated
(AN) dry-type
transformers
Ie max.
630 kVA

887 A

Forced ventilated
(AF) dry-type
transformers,
25 % overload
Interfaces
accepted Ie max.
Junctions
1109 A
n1
H124

800 kVA

1126 A

1408 A

n2

H164

1000 kVA 1408 A

1760 A

n3

H204

1250 kVA 1760 A

2200 A

n4

H244

Prisma Plus or Okken switchboards


NS/NT/NW circuit breakers
800 A
08/16
H164
KTC1000,
KTC1350,
KTC1600
KTC1350,
KTC1600,
KTC2000
KTC1600,
KTC2000
-

1000 A

1250 A

KTC1000,
KTC1350,
KTC1600
KTC1350,
KTC1600,
KTC2000
KTC1600,
KTC2000
-

KTC1000,
KTC1350,
KTC1600
KTC1350,
KTC1600,
KTC2000
KTC1600,
KTC2000
-

1600 A

NS/NW circuit breakers

2000 A
20/25
H244
KTC1000, KTC1350,
KTC1600
KTC1350, KTC2000
KTC1600,
KTC2000
KTC1600, KTC2000,
KTC2000 KTC2500
KTC2000,
KTC2500,
KTC3200
KTC2500,
KTC3200
-

2500 A

3200 A
32
H404
-

NW circuit
breakers
4000 A
40
H404
-

KTC2000 -

KTC2000,
KTC2500
KTC2000,
KTC2500,
KTC3200
KTC2500,
KTC3200
-

KTC3200, KTC3200,
KTC4000 KTC4000
2000 kVA 2813 A
3516 A
n6
H404
KTC3200, KTC3200,
KTC4000, KTC4000,
KTC5000 KTC5000
2500 kVA 3520 A
4400 A
n7
H404
KTC4000, KTC4000,
KTC5000 KTC5000
(1) The compatibilities indicated correspond to the electrical connection possibilities; in all cases, coordination between circuit breaker and electrical busbar
trunking must be checked.
1600 kVA 2253 A

2816 A

n5

H324

Connection to an LV
switchboard using a
dedicated interface,
see page 200.

PD202432_r

Connection to a drytype transformer using a


dedicated interface, see
page 214.

196

version: 1.1

K9CE42000.indd

Connection to an LV
switchboard using a
dedicated interface,
see page 200.

PD202301_r

Connection to a drytype transformer using


a dedicated interface,
see page 217.

Universal
connection to an
oil-filled transformer,
see page 224.
PD202302_r

Universal
connection to an
LV switchboard,
see page 206.

K9CE42000.indd

version: 1.1

197

Design and installation guide

Connection to LV switchboards
Selection guide

Canalis KTC
This guide may be used to:
v select the connection best suited to your installation (incoming direction, trunking
installed flat or edgewise, different phase order),
v check the total height of the connection with respect to the ceiling, i.e.
dimension Z0 + Z2 (100 mm minimum clearance required between top of
connection and ceiling),
v optimise the connection by ensuring that (Z0 + Z1)switchboard = (Z0 + Z1)transformer to
avoid having to use elbows and zed units,
v position the fixing devices used to support the trunking.

Connection with an interface

DD210755

SB2
DD210754

SB1

Direct connection
Without protective covers
SB3

DD21v0753

PD202304_r

Type of connection

see page 200

see page 200

As per manufacturing drawing

minimum

74

82

138

maximum

472

Z2

Z1 + 140

Z1 + H

Z1 + H

Phase order can be changed

Mounting in workshop

Exit through front or rear

Z0
Z1

Exit through left or right side

Edgewise installation

Flat installation

198

version: 1.1

K9CE42000.indd

1000

1350

1600

2000

2500

3200

4000

5000
DD202180

Rating (A)

DD210867

Height H (mm)
Width W (mm)

With protective covers


SB7
DD210759

SB6
DD210758

SB5
DD210757

SB4
DD210756

gs

Trunking cross-section

As per manufacturing drawings

As per manufacturing drawings

As per manufacturing drawings

As per manufacturing drawings

473

130

465

H = 74 to 124 mm

195 - H/2

H = 164 to 244 mm

255 - H/2

H = 324 to 404 mm

355 - H/2

464

Z1 + H

Z1 + 140

Z1 + 140

H = 74 or 104 or 124 mm
H = 164 or 204 or 244 mm
H = 324 or 404 mm

Z1 + H/2 + 115
Z1 + H/2 + 175
Z1 + H/2 + 255

b
b

b
b

K9CE42000.indd

version: 1.1

199

Connection to Okken and


Prisma Plus LV switchboards

Design and installation guide

By Canalis interface
Canalis KTC
PD202350

Switchboards can be equipped with connections for Canalis KT. Jointing with the
switchboard is via a standard run component (straight length, elbow, etc.) and a
jointing unit (identical to those used between line components). The trunking enters
the switchboard via the top (roof).
Switchboard connections are available from 800 to 4000 A.
Type of
switchboard
Prisma Plus

Okken

Rating of trunking Type of circuit


(A)
breaker

Type of connection

800 to 1600

Compact NS

Top direct and rear

Masterpact NT

Top direct and rear

800 to 3200

Masterpact NW

Top direct and rear

4000

Masterpact NW

Rear

800 to 4000

Masterpact NW

Top direct and rear

Connections are tested and qualified under normal operating conditions in


terms of temperature rise () and short-circuit currents (Isc).
The panel builder receives and connects the Canalis KT interface in the workshop.
The phase order at the interface output can be adapted if necessary (this
information must be forwarded to the panel builder).
The switchboard is then delivered to the site and the trunking can be rapidly
connected using a simple jointing unit with torque nuts to ensure the correct
tightening torque.
Compatibility between Canalis KT and the interface in the switchboard (1)(2)
Canalis KT
Cat. no.

KTC1000
KTC1350
KTC1600
KTC2000
KTC2500
KTC3200
KTC4000
KTC5000

Rating
(A)

Height
(mm)

Sealing kit

1000
1350
1600
2000
2500
3200
4000
5000

74
104
124
164
204
244
324
404

KTB0074TT01
KTB0104TT01
KTB0124TT01
KTB0164TT01
KTB0204TT01
KTB0244TT01
KTB0324TT01
KTB0404TT01

Circuit breakers in Okken et Prisma Plus switchboards


NS/NT/NW
NS/NW
800 and 1000 A 1250 A
1600 A
2000 A
2500 A
Interface 08/16
Interface 20/25
H164 (3)
H244 (3)

NW
3200 A
4000 A
Interface 32 Interface 40
H404 (3)
H404 (3)

(1) The compatibilities indicated correspond to the electrical connection possibilities; in all
cases, coordination between circuit breaker and electrical busbar trunking must be checked.
(2) Coordination with a dry-type transformer, see the "Transformer" section, see page 214.
(3) Height of the jointing unit in millimetres.

The prefabricated connections installed in the switchboard are designed to operate


without derating and can therefore operate at the rated circuit-breaker current.
Using the dedicated interface, it is possible to change the phase order if it is
different between the trunking and the switchboard.
DD210772

Phase order

200

version: 1.1

K9CE42000.indd

Connection to Okken
switchboards
By Canalis interface

To 800 to 4000 A Masterpact NW circuit breakers


b Enclosure 600 or 1000 mm deep, access through the front.

DD202310

Top direct connection (TDC)

Position of the jointing unit


Circuit breaker
Drawout, 3P/4P (1)

Dimensions (mm)
A
B

NW08/16

175

325

156

NW20/25

175

325

156

NW32

175

325

156

175

325

156

DD206059

NW40
(1) To order, see "Catalogue numbers", page 78.

Reference

point

K9CE42000.indd

version: 1.1

201

Connection to Okken
switchboards

Design and installation guide

By Canalis interface
Canalis KTC

To 800 to 4000 A Masterpact NW circuit breakers


b Enclosure 1000, 1200 or 1400 mm deep, access through the rear.

DD202311

Rear connection (RC)

Position of the jointing unit


Circuit breaker

Drawout, 3P/4P (1),


top position

Drawout, 3P/4P (1),


medium position

Drawout, 3P/4P (1),


bottom position

Dimensions (mm)
A
Depth (mm)
1000 1200 1400

317

NW08/16

825

363

NW20/25

825

363

317

NW32

825

363

317

953

NW40

NW08/16

825

363

156

363

942
942

NW20/25

825

363

NW32

825

363

942

NW40

953

363

881

NW08/16

1225

363

1417

NW20/25

1225

363

1417

1225

363

1417

DD206058

NW32
(1) To order, see "Catalogue numbers", page 78.

Depth: 1200 mm

Depth: 1400 mm

DD202384

Top views
Depth: 1000 mm

Reference

point

Bottom connection

202

For installations with connections through the bottom, please consult us.

version: 1.1

K9CE42000.indd

Connection to Prisma Plus


LV switchboards
By Canalis interface

To a Compact NS1250 or Masterpact NT1200 circuit breaker


b Enclosure 400 mm deep, access through the front.

DD202306

Top direct connection (TDC)

Position of the jointing unit


Dimensions (1) (mm)
A
B
C

Circuit breaker
Fixed, 3P/4P (2)

NS800/1250

236

325

160

NT08/12

260

325

160

260

325

170

NS800/1250
or 08/NT12
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 76.
DD210765

Drawout, 3P/4P (2)

Reference

point
DD202304

To 800 to 3200 A Masterpact NW circuit breakers


b Enclosure 600 mm deep, access through the front.
Position of the jointing unit
Dimensions (1) (mm)
A
B
C

Circuit breaker
Fixed, 3P/4P (2)

NW08/16

185

325

264

NW20/25

185

325

289

NW32

185

325

264

NW08/16

185

344

164

NW20/25

185

344

214

NW32
185
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 76.

344

214

DD210767

Drawout, 3P/4P (2)

Reference

point

K9CE42000.indd

version: 1.1

203

Connection to Prisma Plus


LV switchboards

Design and installation guide

By Canalis interface
Canalis KTC

To a Compact NS1600 or Masterpact NT1600 circuit breaker


b Two enclosures combined:
v 1 enclosure, 400 mm deep, for the circuit breaker
v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface.

DD202307

Rear connection (RC)

Position of the jointing unit


Dimensions (1) (mm)
A
B
C

Circuit breaker
Fixed, 3P/4P (2)

NS800/1600
or NT08/16

NS800/1600
or NT08/16
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 76.

325

160

638

325

170

DD210769

Drawout, 3P/4P (2)

638

Reference

point

DD202305

To 800 to 4000 A Masterpact NW circuit breakers


b Two enclosures combined:
v 1 enclosure, 600 mm deep, for the circuit breaker
v 1 enclosure, 400 mm deep, for the Canalis KT/switchboard interface.
Position of the jointing unit
Dimensions (1) (en mm)
A
B
C

Disjoncteur
Fixed, 3P/4P (2)

NW08/16

815

325

264

NW20/25

757

325

414

NW32

774

325

414

NW40

790

325

439

NW08/16

815

317

414

NW20/25

815

342

414

NW32

815

317

439

NW40
790
(1) Dimensions measured from switchboard framework.
(2) To order, see "Catalogue numbers", page 76.

325

439

DD210771

Drawout, 3P/4P (2)

Reference

point

204

version: 1.1

K9CE42000.indd

Connection to Okken and


Prisma Plus LV switchboards
By Canalis interface

The sealing kit must be ordered with the KT trunking. The size of the trunking
determines that of the sealing kit. For the different types of kit, see the "Catalogue
numbers and dimensions" pages.
The kit includes a drilling and cut-out drawing for the switchboard roof.
DD210775

DD202314

Sealing kit

DD210774

KTB0ppppTT01

It is advised to cut out the switchboard roof in the workshop.


Important. The dimensions are measured from switchboard framework.

DD210776

Cut-out drawing (for all the ratings)

Centre lines.

K9CE42000.indd

version: 1.1

205

Connection to LV switchboards

Design and installation guide

By universal feed unit


Canalis KTC
PD202351

Canalis KT can be connected to switchboards via a universal connector. To simplify


the work, it is advised to fit the switchboard busbars with a distance between
centres of 115 mm.
Jointing with the switchboard is via a straight or elbow universal feed unit with a
straight or flat outlet.
Connections are made using torque nuts offering both ease of use and the
possibility of a visual check before energising.
Enclosure depth depending on the rating of the trunking
Minimum depth X of
switchboard (mm)

1000 to 1600

230

400

2000 to 3200

350

400

4000 and 5000

510

600

DD210779

Busbars in switchboard
(recommended distance between
centres = 115 mm)

Depth Y of flange feed


unit plate (mm)

DD210778

Rating of trunking (A)

DD210781

If the order of the


phases in the trunking
and the switchboard is
different, it is advised to
invert the phases in the
switchboard. If that is not
possible, use the phase
and neutral crossover
components.
For more information, see
the "Description" section
page 49 and "Catalogue
numbers/Dimensions"
section, page 69.

DD210780

Phase order

KTCppppTNp10

KTCppppTPp10
206

version: 1.1

K9CE42000.indd

Cut-out drawing

It is advised to cut out the switchboard roof in the workshop.


Cut-out for universal feeder unit, with distance between centres = 115 mm
Rating of trunking (A)

Depth Y of flange feed unit plate (mm)


230

2000 to 3200

350

4000 and 5000

510

DD210782

1000 to 1600

Centre lines.

K9CE42000.indd

version: 1.1

207

Connection to LV switchboards

Design and installation guide

Via flange feed unit and flexible bars


Canalis KTC
PD202353

Connection plates are flexible copper bars, insulated or not, and drilled at one or
both ends. They are supplied with bolts, washers and torque nuts for connection to
straight or elbow universal feed units.
To simplify the work, it is advised to universal feed units with a distance between
centres of 115 mm.
Enclosure depth depending on the rating of the trunking
Rating of trunking (A)

Minimum depth X of
switchboard (mm)

1000 to 1600

230

400

2000 to 3200

350

400

4000 and 5000

510

600

Vertical incomer

Horizontal incomer

DD210779

DD210783

DD202385

Universal feed unit


(recommended distance between
centres = 115 mm)

Depth Y of flange feed


unit plate (mm)

KTCppppERpp

208

version: 1.1

K9CE42000.indd

By feed and connection plates

The required number of connection plates is indicated in the table below.

1000

2000

1500

2500

1500

3200

2000

4000

2500

5000

3000

DD210789m

1000

DD210789

1600

DD210787

1350

Connection
plates

DD210785

Connection plates per phase


Number
Section (mm2)

DD210786

DD210764

Busbar trunking rating


(A)

DD210788

Selection of connection plates

Busbar trunking 1350 to


1600
rating (A)

2000 to
2500

3200

4000

5000

Short-circuit withstand table

Short-circuit withstand
DD202359

Short-time withstand current (Icw)

Maximum distance between support


centres X (mm)

y 43 kA

400

43 kA y Icw y 50 kA

225

50 kA y Icw y 100 kA

150

Vertical incomer

DD210790

DD202349

Horizontal incomer

If the order of the phases in the trunking and the switchboard is different, it is
advised to invert the phases in the switchboard. If that is not possible, use the
phase and neutral crossover components.
For more information, see the "Description" section page 49 and "Catalogue
numbers/Dimensions" section, page 69.
DD210780

DD210781

DD210791

Phase order

KTCppppTNp10

KTCppppTPp10
K9CE42000.indd

version: 1.1

209

Connection to LV switchboards

Design and installation guide

By feed and connection plates


Canalis KTC
Dimensions of protective covers

Horizontal incomer

DD202326

Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors


type N1 to N6
Rating (A)

Dimensions (mm)
Y
D

1000 to 1600

230

220 to 475

220 to 475

310 to 800

2000 to 3200

350

220 to 475

220 to 475

430 to 800

4000 and 5000

510

220 to 475

220 to 475

590 to 800

KTBppppCR1

It is advised to cut out the switchboard roof in the workshop.


DD210953n

Cut-out drawing

Centre lines.

210

version: 1.1

K9CE42000.indd

Vertical incomer
DD202322

Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight


outlet feed connectors type N1 to N6
Rating (A)
Dimensions (mm)
Y
D
G
Z
1000 to 1600

230

220 to 475

220 to 475

400 to 800

2000 to 3200

350

220 to 475

220 to 475

400 to 800

4000 and 5000

510

220 to 475

220 to 475

400 to 800

KTBppppCR2

It is advised to cut out the switchboard roof in the workshop.

DD210953n1

Cut-out drawing

Centre lines.

DD202324

Rigid vertical cover KTBppppCR3 (100 to 400 mm height) for ER straight


outlet feed connectors type N1 to N6
Rating (A)
Dimensions (mm)
Y
D
G
Z
1000 to 1600

230

220 to 475

220 to 475

400 to 800

2000 to 3200

350

220 to 475

220 to 475

400 to 800

4000 and 5000

510

220 to 475

220 to 475

400 to 800

KTBppppCR3

It is advised to cut out the switchboard roof in the workshop.

DD210953n2

Cut-out drawing

Centre lines.

K9CE42000.indd

version: 1.1

211

Connection to cast resin


transformers

Installation guide

Selection guide
Canalis KTC

This guide will allow you to:


v choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order),
v check the total height of the link with respect to the premises ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling),
v optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels,
v position the sections for the busbar trunking supports.

Z2

Z1 + 140

Selecting phase order

Fixed

Front or rear exit

maximum

Right or left exit


Edgewise layout
Flat layout

DD202490

230

Z1 minimum

TS4

DD202489

See page 214

Z0

Universal connection
TS3

DD202488

Connection with interface to Trihal transformers


TS1
TS2
DD202487

PD202399_r

Type of connection

See page 214


238

According to manufacturers
drawing
350

According to manu
drawing
280

350

280 (1)

Z1 + H

Z1 + H

420 (1)

Fixed

At time of order

At time of order

b
(1) To use standard connection plates L = 406 mm in accordance with our recommendations.

212

version: 1.1

K9CE43000.indd

1000

1350

1600

2000

2500

3200

4000

5000
DD202180

Rating (A)

TS6

TS7

TS8
DD202494

DD202492

TS5

DD202493

DD210867

Height H (mm)
Width W (mm)

DD202491

ufacturers

Trunking cross-section

According to manufacturers
drawing
350

According to manufacturers drawing According to manufacturers


drawing
280
350

According to manufacturers
drawing
-

350 (1)

280 (1)

350 (1)

Z1 + H

420 (1)

At time of order

At time of order

H = 74 or 104 or Z1 + H/2 + 115 500 (1)


124 mm
H = 164 or 204 Z1 + H/2 + 175
or 244 mm
H = 324 or
Z1 + H/2 + 255
404 mm
At time of order
At time of order

b
b

K9CE43000.indd

version: 1.1

213

Installation guide

Connection to Trihal cast resin


transformers
By Canalis interface

Canalis KTC
PD202434_r

The Trihal dry-type transformers are supplied with a specific interface tested to
receive the Canalis KT busbar trunking. Jointing with the switchboard is achieved
using a standard run section (straight, elbow section, etc) and a joint block identical
to that for connecting run elements.
The Canalis KT/dry type transformer interface, which is fitted to the transformer,
is designed to accept the transformers 25 % overload in the case of forced
ventilation.
The connections are tested and qualified in normal operating conditions with
respect to temperature rise (Dq) and short-circuits (Isc).
The busbar trunking is quickly connected to the dry-type transformer using a simple
joint block with torque nuts, guaranteeing tightening torque.
Table of compatibility between Canalis KT and the connection interface for
naturally ventilated (AN) dry-type transformers.
Dry-type transformer

Canalis KTC

Rating l nominal (1) Interface


(kVA) (A)
Type Junction Rating (A)

Cross-section

Type

630

887

H124

1600

140 x 74

KTC1000

800

1126

H164

2000

140 x 104

KTC1350

1000

1408

H204

2500

140 x 124

KTC1600

1250

1760

H244

3200

140 x 164

KTC2000

1600

2253

H324

4000

140 x 204

KTC2500

2000

2816

H404

5000

140 x 244

KTC3200

2500
3520
7
H404
5000
140 x 324
(1) I is given as an indication only and is calculated with U - 410 V.

KTC4000

Table of compatibility between Canalis KT and the connection interface for


forced ventilated (AF) dry-type transformers.
Dry-type transformer

Canalis KTC

Rating l nominal (1) Interface


(kVA) (A)
Type Junction Rating (A)

Cross-section

Type

630

1108

H124

1600

140 x 104

KTC1350

800

1407

H164

2000

140 x 124

KTC1600

1000

1760

H204

2500

140 x 164

KTC2000

1250

2253

H244

3200

140 x 204

KTC2500

1600

2816

H324

4000

140 x 244

KTC3200

2000
3520
6
H404
5000
140 x 324
(1) I is given as an indication only and is calculated with U - 410 V.

KTC4000

If, for reasons of busbar trunking operating conditions or performance


requirements, you have to use a rating other than those defined in the above
tables, consult us.

If the phase order of


the busbar trunking is
different to that of the
switchboards busbars, it
is recommended a phase
inversion is carried out
in the switchboard. If
this cannot be done, use
the phase and neutral
transposition section.
For more information on
transposition sections,
see "Description" page 49
and "Catalogue numbers
and Dimensions"
page 69.

DD210780

DD210945

Phase order

KTCppppTNp10

KTCppppTPp10

214

version: 1.1

K9CE43000.indd

DD210946

Reference point

Dimensions

Dimensions X, Y and Z
Dimensions
(mm)

Transformer power (kVA)


630
800
1000 1250

1600

2000

2500

147

150

170

147

150

170

153

100

100

108

93

124

144

149

X0

233

215

265

245

300

300

322.5

Interface type

Dimensions Y0 and Z0
Y0 = X + L
Z0 = C - M
Dimensions C and L are different according to country standards.
French standard
FT no.235627 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 410 V
Dimensions
(mm)

Transformer power (kVA)


630
800
1000 1250

1600

2000

2500

1614

1744

1749

1929

2089

2209

2297

220

225

240

240

240

257

275

German standard
FT no.235763 rev. 0 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 400 V
Dimensions
(mm)

Transformer power (kVA)


630
800
1000 1250

1600

2000

2500

1734

1744

1749

2019

1979

2199

2279

210

220

225

245

255

255

265

Spanish standard
FT no.235515 rev. 3 - Primary voltage: 20 kV - Insulation voltage: 24 kV Secondary voltage: 420 V
Dimensions
(mm)

Transformer power (kVA)


630
800
1000 1250

1600

2000

1614

1744

1879

1929

1979

2194

220

225

215

245

250

245

Belgian standard
FT no.235820 rev. 0 - Primary voltage: 15 kV - Insulation voltage: 17.5 kV Secondary voltage: 400 V
Dimensions
(mm)

K9CE43000.indd

Transformer power (kVA)


630
800
1000 1250

1600

2000

2500

1484

1564

1694

1844

2054

2149

2164

215

210

215

225

230

255

235

version: 1.1

215

Installation guide

Connection to Trihal cast resin


transformers
By Canalis interface

Canalis KTC

DD210947

Sealing kit

The sealing kit must be ordered with the KT busbar trunking. The busbar trunking
size defines the sealing kit size. For the different types of kit, see "Catalogue
numbers/Dimensions".
The kit includes a drilling and cut-out template for the dry-type transformer panels.

KTB0ppppTT01
It is recommended that the cutting-out of the transformer panels is done in the
workshop.

DD210776

Cut-out drawing

Junction axis.

216

version: 1.1

K9CE43000.indd

Connection to cast resin


transformers

By universal feed and connection plates


PD202352

Canalis KT can be connected to cast resin transformers using a universal feed.


The connection is made using a flexible busbar (connection plates or braids) to
avoid transmitting vibrations and expansions. The connection plates are made up
of either insulated or non-insulated flexible copper bars, drilled at one or both ends.
A nut and bolt kit allows connection to the feed.
The connections use torque-head bolts which provide both ease of installation and
visual inspection of correct tightening before energising.
If the transformer is supplied with panels, provide for an additional cover to
maintain the protection degree.
Choice of Canalis KT busbar trunking rating according to transformer power.
Transformer
Power (kVA)

I nominal (1) (A)

KTC rating at

nominal
power (2) (A)

630

887

1000

800

1126

1350

1000

1408

1600

1250

1760

2000

1600

2253

2500

2000

2816

3200

2500

3520

4000

3150
4435
5000
(1) I is given as an indication only and is calculated with U = 410 V and at transformer nominal
setting, without forced ventilation.
(2) The busbar trunking rating is defined for normal operating conditions.

TS3 and TS5 universal connection, edgewise mounting


DD210949

Recommended configurations for shortcircuit withstand


(connection plate L = 400 mm)

KTCppppELp1 or KTCppppELp2 or KTCppppELp3 or KTCppppELp4

DD210948

TS4 and TS6 universal connection, flat mounting (using angle brackets)

KTCppppELp1 or KTCppppELp2 or KTCppppELp3 or KTCppppELp4 with angle


bracket KTB0000YE1
K9CE43000.indd

version: 1.1

217

Connection to cast resin


transformers

Installation guide

By universal feed and connection plates


Canalis KTC

DD202481

TS7 universal connection, edgewise mounting

KTCppppELp5

DD202480

TS7 universal connection, flat mounting (using angle brackets)

KTCppppELp5 with angle bracket KTB0000YE


The number of connection plates is defined in the table below:

1500

2500

1500

3200

2000

4000

2500

5000

3000

Busbar trunking 1350 to


rating (A)
1600

2000 to
2500

version: 1.1

3200

4000

DD210789m

1000

2000

DD210789

1000

DD210788

1600

Connection
plates

218

Connection plates per phase


Number
Section (mm2)

1350

DD210786

DD210950

Busbar trunking rating


(A)

DD210787

Definition of connection plates

5000

K9CE43000.indd

Phase selection is made when the feed is ordered.


Phase L2 is fixed and can therefore be used as a reference for installing the feed
on the transformer.

Phase order

The different phase selection possibilities (T)

DD210951

b Dedicated feeds N1 to N4,

Important: the drawings and references above correspond to a phase order of


N321, joint block side. If the phase order on the joint block side is N123, inverse
T=1 with T=3 and T=2 with T=4.

DD210952

b Feed with flat bars N5.

Important: the drawings and references above correspond to a phase order of


N321, joint block side. If the phase order on the joint block side is N123, inverse L1
and L3 on the transformer side marking.

K9CE43000.indd

version: 1.1

219

Connection to cast resin


transformers

Installation guide

By universal feed and connection plates


Canalis KTC
Vertical protection covers for dry-type transformer feeds N1, N2, N3
and N4
Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum

Dimensions of protective covers

1000 to 1600

230

200

350

2000 to 3200

350

200

350

4000 to 5000

510

200

350

DD202344n

KTB0000CR4

Horizontal protection covers for dry-type transformer feeds N1, N2, N3


and N4
Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum
1000 to 1600

230

330

480

2000 to 3200

350

330

480

4000 to 5000

510

330

480

DD202345n

KTB0000CR5

220

version: 1.1

K9CE43000.indd

Horizontal protection cover for dry-type transformer feed N5


Rating (A)
Dimensions (mm)
Y
Z
Minimum
Maximum
1000 to 1600

230

380

530

2000 to 3200

350

500

650

4000 to 5000

510

660

810

DD202347

KTBppppCR6

It is recommended that the cutting-out of the transformer panels is done in the


workshop.
DD230224

Cut-out drawing for dry-type


transformer panels

K9CE43000.indd

version: 1.1

221

Installation guide

Connection to oil immersed


transformers
Selection guide

Canalis KTC
This guide will allow you to:
v choose the connection best suited to your layout (incoming direction, flat or
edgewise busbar trunking, possibility of adjusting phase order)
v check the total height of the link with respect to the premises ceiling height,
dimension Z0 + Z2 (plan for 100 mm minimum between the upper point of the link
and the ceiling)
v optimise your link whilst respecting the following rule:
(Z0 + Z1)switchboard = (Z0 + Z1)transformer to avoid multiple elbows to change levels
v position the sections for the busbar trunking supports.

TH3

According to manufacturers drawing

According to manufacturers drawing

According

minimum

738

1073

730

maximum

1072

1064

Z2

Z1 + H

Z1 + H

Z1 + 140

Front or rear exit


Right or left exit
Edgewise layout

Z0
Z1

DD202418

TH2
DD202417

Vertical incomer
TH1
DD202416

PD202429_r

Incomer type

b
b

Flat layout
222

version: 1.1

K9CE44000.indd

Trunking cross-section
1000

1350

1600

2000

2500

3200

4000

5000
DD202180

Rating (A)

g to manufacturers drawing

TH4

Direct connection
TH5

DD202419

DD202420

DD210867

Height H (mm)
Width W (mm)

According to manufacturers drawing

According to manufacturers drawing

1065

Z1 = (Y/H)/2

Z1 = (Y/H)/2

Z1 + 140

H = 74 or 104 or 124 mm
H = 164 or 204 or244 mm
H = 324 or 404 mm
b

510
770
850

b
b
b

K9CE44000.indd

version: 1.1

223

Connection to oil immersed


transformers

Installation guide

By feed and connection plates or braids


Canalis KTC
PD202344

Connection to an oil immersed transformer is made using flexible bars (connection


plates) to avoid transmitting transformer vibrations to the busbar trunking and to
limit the stress on connection terminals.
Choice of busbar trunking
Dry-type transformer
Rating (kVA)
l nominal (1)
(A)

Canalis KTC busbar trunking


Rating (A)
Cross-section

630

887

1000

140 x 74

800

1126

1350

140 x 104

1000

1408

1600

140 x 124

1250

1760

2000

140 x 164

1600

2253

2500

140 x 204

2000

2816

3200

140 x 244

2500

3520

4000

140 x 324

3150
4435
5000
(1) I is given as an indication only and is calculated with U - 410 V.

140 x 404

Note: If, for reasons of busbar trunking operating conditions or performance requirements, you
have to use a rating other than those defined in the above tables, consult us.

Protective cover width


Busbar trunking rating (A)

230

2000 to 3200

350

4000 to 5000

510

Vertical incomer

Horizontal incomer

DD202422n

DD202421n

Recommended configurations for shortcircuit withstand


(connection plate L = 400 mm)

Dimensions "Y" of the feed

1350 to 1600

224

version: 1.1

K9CE44000.indd

With drilled connection


plates (KTB0000YC4) or
braids
DD202425n

DD202423n

With connection plates


with kink to be drilled
DD202424n

With connection plates


with kink and bar clamp

Several connection possibilities

If the phase order of the busbar trunking is different to that of the switchboards
busbars, it is recommended a phase inversion is carried out in the switchboard. If
this cannot be done, use the phase and neutral transposition section.
For more information on transposition sections, see "Description" page 49 and

"Catalogue numbers/Dimensions" page 69.

DD210780

DD210781

DD210791

Phase order

KTCppppTNp10

KTCppppTPp10

K9CE44000.indd

version: 1.1

225

Installation guide

Connection to oil immersed


transformers

By feed with connection plates or braids


Canalis KTC
The number of connection plates is defined in the table below:

1000

1000

2000

1500

2500

1500

3200

2000

4000

2500

5000

3000

DD210789m

DD210789

1600

DD210787

1350

Connection
plates

DD202426

Connection plates per phase


Number
Section (mm2)

DD210786

DD210764

Busbar trunking rating


(A)

DD210788

Definition of connection plates

2000 to
2500

3200

4000

5000

DD210785

Busbar trunking 1350 to


1600
rating (A)

The number of braids is defined in the table below:


Busbar trunking rating (A)

1200

2000

1200

2500

1800

3200

1800

4000

2400

5000

3000

Busbar
trunking rating
(A)

1350 to 2000

2500 to 3200

version: 1.1

4000

DD202376m

1200

1600

DD210773

Cross-section (mm)

DD210770

Number
1350

Braids

226

Braids per phase

DD202376

DD202355

Definition of braids

5000

K9CE44000.indd

Dimensions of protective covers

Horizontal incomer
Rigid horizontal cover KTBppppCR1 for ER straight outlet feed connectors
type N1 to N6
Rating (A)

Dimensions (mm)
Y
D

1000 to 1600

230

220 to 475

220 to 475

310 to 800

2000 to 3200

350

220 to 475

220 to 475

430 to 800

4000 to 5000

510

220 to 475

220 to 475

590 to 800

DD202326

KTBppppCR1

Adjustable cover KTBppppCR7 for horizontal incomer feed connectors with a


between centres distance of 150 or 170 mm
Rating (A)

Dimensions (mm)
Y
Z
X

1000 to 1350

230

565

450

830

750

330

125

365

1600

230

565

450

830

750

350

125

365

2000 to 2500

350

825

650

890

810

350

265

485

3200

350

825

650

960

880

460

265

485

4000 to 5000

510

905

650

960

880

460

185

645

DD210872n

KTBppppCR7

Vertical incomer
Rigid vertical cover KTBppppCR2 (400 to 800 mm height) for ER straight
outlet feed connectors type N1 to N6
Rating (A)
Dimensions (mm)
Y
D
G
Z
1000 to 1600

230

220 to 475

220 to 475

400 to 800

2000 to 3200

350

220 to 475

220 to 475

400 to 800

4000 to 5000

510

220 to 475

220 to 475

400 to 800

DD202322

KTBppppCR2

K9CE44000.indd

version: 1.1

227

Connection to oil immersed


transformers

Installation guide

By feed with connection plates or braids


Canalis KTC
Adjustable cover KTBppppCR8 for vertical incomer feed connectors with a
between centres distance of 150 or 170 mm
Rating (A)

Dimensions (mm)
Y
Z
A

1000 to 1350

230

600

830

750

345

330

1600

230

600

830

750

420

350

2000 to 2500

350

600

890

810

460

350

3200

350

600

960

880

575

460

4000 to 5000

510

600

960

880

625

460

DD210870n

KTBppppCR8

Flexible cover KTBppppCR8 for vertical incomer straight outlet feed


connectors with a between centres distance of 115 mm
Rating (A)
Dimensions (mm)
Y
C
1000 to 1600

230

200 to 650

2000 to 3200

350

200 to 650

4000 to 5000

510

200 to 650

DD202319

KTBppppCS0

228

version: 1.1

K9CE44000.indd

Connection to oil immersed


transformers
Other connection solutions

Canalis KT is easily connected to Minera oil immersed transformers (France


Transfo offer).
For more details of drilling dimensions for the bushings and the connection
terminals, refer to the manufacturers catalogue.
DD210955

Connection to bar bushings

Connections to Minera ground mounted oil immersed transformers


from 630 to 3150 kVA - y 24 kV/400 V
Bar bushings (A)
1250

1250

2500

DD202429

1600

DD202428

800

1000

2500

5000

DD202431

3150

DD202430

1600

2000

3150

K9CE44000.indd

Dimensions (mm)
DD202427

Power (kVA)
630

version: 1.1

229

Connection to oil immersed


transformers

Installation guide

Other connection solutions


Canalis KTC

Connection terminals of the type defined below must be used. These are available
in the transformer manufacturers catalogues.
DD210959

Connection to porcelain bushings

The transformers can be supplied with or without a low voltage cover. This cover is
not used in our solutions.
DD210957

Cover

230

version: 1.1

K9CE44000.indd

Contents

DEBU024EN_Recommandations.
indd

Recommandations

Index
Introduction
Presentation and description
Catalogue numbers and dimensions
Design guide
Design and installation guide

3
17
35
63
133
171

Reception, handling and storage

232

Maintenance

234

Run sections

234

Recycling

235

version: 1.1

231

Recommendations

Reception, handling and


storage

Canalis KTC
This document contains practical information, lays out the general
recommendations (as a complement to the installation regulations) and specifies
the basic instructions that must be respected when handling and storing Schneider
Electric Canalis busbar trunking system.
The purchasers engineering, installation and operating staff must become
acquainted with this document and become familiar with the appearance and
characteristics of each of the Canalis busbar trunking systems components.
Appropriate planning and coordination between the different job functions is
indispensable for ensuring an efficient installation of the equipment.
Each Canalis busbar trunking system is carefully inspected and packaged at the
assembly plant.
The entire system is checked both structurally and electrically.
At the end of inspection, the busbar trunking system is prepared for shipping.
Each section is packed to guarantee easy handling before its installation.
The catalogue number is written on each shipping unit.
Warning
RISK OF ELECTRIC SHOCK, BURNS OR EXPLOSION
b Protect the equipment against all contact with water, salt, concrete and other
corrosive surroundings both before and during installation.
b Outdoor equipment is not resistant to bad weather until after it has been fully and
correctly installed.
b Do not sit or walk on the equipment.
If these instructions are not respected, the equipment may deteriorate leading to a
risk of serious or mortal injury.

Reception

Upon reception, check the information on the shipping note corresponds to the
equipment received to ensure all of the order has been received and shipped.
Complaints concerning missing components or other errors must be sent in
writing to Schneider Electric SAS within 30 days from the date the shipping item
was received. If no complaint has been received within 30 days from the date the
shipping item was received, Schneider Electric SAS will no longer be responsible
for repairs or replacements that may be required.
Upon reception, check the various units of the busbar trunking system immediately
to identify any damage that has occurred during transport.
If there is observed or suspected damage, file a claim immediately with the carrier
and inform the nearest Schneider Electric office.

Handling

Handle Canalis products with the greatest of care to avoid damaging the internal
components of the system and to avoid changing the external appearance of the
various parts, as well as the bar ends (connection terminals).
The busbar trunking must be constantly supported by independent means, in
such a way its weight is not resting on the top of the transformers or distribution
switchboards.
The distance between these support means must not exceed 3 metres.
Avoid exposing the busbar trunking to twisting, embossing or impacts, and all other
actions likely to causing damage.
Ensure the handling equipment available at the site of installation is suitable for
handling busbar trunking. In particular, check the lifting capacity of the crane or the
other lifting equipment to be used.

232

version: 1.1

K9CE51000.indd

Take great care when unpacking the equipment:


b use a nail-head puller when unpacking wooden crates
b if hauling the busbar trunking with a crane, use Nylon slings to spread the weight
of the unit being lifted
b if using cables, insert a spacing means to avoid damaging the busbar trunking
b if using a forklift truck, position the busbar trunking on the forks in such a way the
weight is evenly distributed.
1 - Cut the strapping holding the packaging case using suitable cutting tools.
2 - Use suitable tools to remove the strengthened steel packaging at each end of
the busbar trunking.
Take care not to damage the steel box so as not to damage the busbar trunking.
Avoid the use of objects with sharp edges when lifting the busbar trunking.
3 - Dispose of all used packaging in an appropriate way.
Never drag the busbar trunking along the floor. Do not use the end bars to lift
sections of the busbar trunking.

Protection against humidity during


storage

If the busbar trunking is not installed and commissioned immediately, leave it in


the original Canalis packaging and store it in a clean and dry place at a uniform
temperature.
The busbar trunking must not be stored outside. However, if outside storage
is necessary, cover the busbar trunking in such a way as to protect it from bad
weather and to avoid contact with the elements.
Temporary electrical heating must be provided for underneath the covering means
to prevent condensation.
The supplied heat must be of suitable temperature and uniformly distributed
underneath the covering means.
Outdoor busbar trunking is not resistant to bad weather until after it has been fully
and correctly installed.
During installation, take particular care to protect rising mains from humidity arising
from unfinished roofs, walls and other similar elements.

K9CE51000.indd

version: 1.1

233

Recommendations

Maintenance
Run sections

Canalis KTC
Danger

RISK OF ELECTRIC SHOCK, BURNS OR EXPLOSION


The installation, operation and maintenance of the equipment must only be
carried out by qualified electrical maintenance staff. This document must not be
considered as being a sufficient means for allowing non-qualified staff to undertake
the operation and maintenance of the equipment.
b Cut the electrical supply to the busbar trunking before installing, removing or
working on the equipment.
b Always use a suitable nominal voltage detection means to confirm the supply
has been cut.
b Effective use of the equipment requires the implementation of appropriate
handling, installation, functioning and maintenance operations.
If these instructions are not respected, there is a risk of serious injury or
death.

Warning

RISK OF DAMAGING THE EQUIPMENT


Hydrocarbon aerosols and aerosols using a hydrocarbon base may cause the
deterioration of certain plastics.
Before using certain products to clean, dry or lubricate the different components
during installation or maintenance, consult your nearest Schneider Electric SAS
office.
If these instructions are not respected, the equipment may deteriorate
leading to a risk of serious injury or death.

Run sections

Canalis prefabricated busbar trunking is designed to operate maintenance-free.


Nevertheless, as for all screw-type connections, it is advised to check tightness
one year after installation and then run checks at longer intervals.
The tightening of the terminal blocks is made with a torque wrench:
value of 6 daN.m +- 10%.
Bolt
HM 16
HM 14
HM 12
HM 10

Tightening torque
16 mdaN
12 mdaN
7 mdaN
5 mdaN

If one of the joints or terminals is highly discoloured, corroded or pitted, or shows


signs it has been exposed to high temperatures, the material concerned must be
replaced with new factory mounted material. Consult your local Schneider Electric
office for all replacements,
b ensure all mechanisms are in good working order.
Lubricate the moving parts of the various mechanisms if necessary. Similarly,
remove all excess lubrication to avoid undesirable foreign bodies from gathering
b check the insulation resistance before re-energising the busbar trunking.
It is recommended that resistance measurements are recorded. If these values
decrease significantly over time, it means deterioration is underway.
Carry out an insulation resistance test in compliance with the instructions given in
the testing and comissioning procedure section.
Re-energise the equipment in accordance with the instructions given in the testing
and comissioning procedure section.

234

version: 1.1

K9CE52000.indd

Recycling

After having performed all the necessary inspections and repairs mentioned above,
it may be desirable to carry out infrared temperature measurements on all the
electrical connections. This operation must be done once the busbar trunking has
been re-energised and reached a stabilized temperature.
Responsibility
Schneider Electric declines all responsibility for maintenance carried out in a
non-compliant way with respect to specifications or installation regulations, for
inappropriate storage conditions, for inappropriate product environments (chemical
and ambient conditions, atmospheric conditions, etc.), for the incorrect use of the
products, and for the non-respect of installation and/or connection procedures.

Distribution tap-off units

Contact between busbar trunking and tap-off boxes.

Busbar trunking contacts consist of sprung silver plated contact jaws to ensure
optimum contact quality. The contacts do not use plastic for their support or
transmission of force.
They are connected to the live conductors of the run at the tap-off point. Silverplated copper conductors are used at the place of contact.
These devices are maintenance-free.

Cable connection

Cable connection of the feeders are via terminals or lugs.


As with all screw connections, it is recommended that tightening torque be checked
one year after installation and then to space-out the checks.

Protection switchgear

For all devices fitted in Canalis tap-off units, the manufacturers recommendations
must be complied with.

Checking appearance

It is recommended the external cleanliness of the tap-off units be checked yearly


to remove dust, water and oil deposits, and all other conductive bodies from the
sensitive zones.
Check for signs of shock which may affect the protection degree.

Recycling busbar trunking

Canalis busbar trunking can be reused. Canalis busbar trunking is designed for a
long service life and can easily be dismantled, cleaned and reused.

DD205673_r

All packaging materials can be recycled (cardboard or recyclable polyethylene


film).
All Canalis products are designed for safe end-of-life recycling. PVC, on the other
hand, requires neutralisation of the hydrochloric acid produced using lime and
generates dioxins that are extremely toxic.

Canalis helps conserve natural resources

Example:
1 kg of PVC generates 1 kg of waste.

K9CE52000.indd

The depletion of raw materials (copper, plastics, etc.) is one of our ongoing
concerns.
For this reason, we have optimised the used of all materials used to make our
busbar trunking.
b Reduction of dangerous or polluting materials. We design our products to meet
future European directives.
b Reduction in the weight of insulating materials.
b Reduction in the use of plastics for improved fire performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction
(lower calorific value).

version: 1.1

235

236

version: 1.1

K9CE52000.indd

YFJYVIIVGIT

6FKQHLGHU(OHF ULF

)55(9$

35, rue Joseph Monier


CS30323
F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com

DEBU024EN

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this document.
This document has been printed on ecological paper.
Design: Schneider Electric
Photos: Schneider Electric
Printing:
03-2011

ART960138 2011 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS

You might also like