You are on page 1of 208

Content

Instruction Manual

SF6 circuit--breaker
GL314
With spring operating mechanisms
FK3--1

Administrator
AHT

06--2004
E ALSTOM

First issue
15--04--2004

Compiled by
J.C. Labadie

Approved by
X. Allaire

D1211EN/02
1/6

Content

Instruction Manual
This page is intentionally blank.

06--2004
E ALSTOM

D1211EN/02
2/6

Content

Instruction Manual
Safety
Product safety sheets

Annexes

Technical data
Technical characteristics

L10--006EN/02

Description and operation


General description of the circuit--breaker

L12--016EN/01

Description of the interrupting chamber

L12--103EN/02

Pole operation (interrupting principle)

L13--003EN/02

Operating device

L14--007EN/01

SF6 gas monitoring

L20--001EN/04

Packaging - Shipping and storage


Packaging -- Identification -- Storage

06--2004
E ALSTOM

L22--008EN/01

D1211EN/02
3/6

Content

Instruction Manual
Installation

06--2004
E ALSTOM

Erection general instructions

T30--002EN/01

Tightening torques

T31--001EN/02

Erection general procedures

T31--003EN/01

Checking for presence of SF6 gas in poles

L31--059EN/01

Checking for presence of stop ring of the fusible


pin

L31--090EN/01

Support--frame assembly

L31--113EN/01

Lifting and positionning the pole

L31--201EN/02

Installing terminals with preparation of contact surfaces

L31--500EN/03

Installing the operating device

L31--789EN/01

Calculation of the SF6 gas filling pressure for using


the pressure gauge (tool)

L31--901EN/02

Filling with SF6 gas

L32--007EN/01

D1211EN/02
4/6

Content

Instruction Manual
Commissioning
Pre--commissioning inspections

L34--004EN/04

Maintenance plan

L51--003EN/03

Electrical wear limits

L51--051EN/01

Electrical contact densimeter threshold inspection

L51--107EN/01

Intervention on the operating device

L51--302EN/01

Replacing the operating device FK3--1

L51--800EN/04

Tooling and accessories

L60--010EN/02

Maintenance

Annexes

Product safety sheets


Acceptance criteria
Manual operations (FK3--1)
Instructions on the handling of used SF6 gas and
decomposition products

06--2004
E ALSTOM

PS0000/A
CA 103 141/3/004
48.020.181E
T51--251EN/01

D1211EN/02
5/6

Content

Instruction Manual
This page is intentionally blank.

06--2004
E ALSTOM

D1211EN/02
6/6

Technical data

Technical characteristics
GL314 technical characteristics
Performances

Ur
Ir
fr
Ip
Ik

Ud

Up

Isc

The table below gives the circuit--breaker performances :

Designation
Rated voltage (r.m.s. value)
Standard
Rated normal current
Rated frequency
Rated withstand current (peak value)
Short--time withstand current (r.m.s. value)
Rated insulation level
(At sea level)
Rated short--duration power--frequency withstand
voltage (r.m.s. value)
D Phase--to--earth and phase--to--phase
D Across open contacts
Rated lightning impulse withstand voltage (peak
value)
D Phase--to--earth and phase--to--phase
D Across open contacts
Rated breaking current in symmetrical short-circuit
Rated making current (peak value)
Total break time

GL314
kV
A
Hz
kA
kA

50
100

242
ANSI
3150
60
108

60
108
40

kV
kV

460
460

425
425

kV
kV

1050
1050

900
900

kA
kA
ms

Rated operating sequence


Resistance of main contacts
(new contact)

245
IEC
3150

40
100

108
108
40 2
CO -- 15s -- CO
or
O -- 0.3s -- CO -- 3min -- CO
chamber without H.V. connectors
55

The above characteristics are of a general nature, only those values given on
the circuit--breakers rating plates are contractually binding.
Continued on next page.

08--2000
E ALSTOM

L10--006EN/02
1/2

Technical data

Technical characteristics
GL314 technical characteristics, continued
SF6 gas

The table below gives the SF6 gas characteristics :


NOTE : Two pressure scales are possibles, depending the specifications of the apparatus.

GL314
Absolute pressure at 20C(68F)
Filling absolute pressure for the insula0.75 MPa
0.85 MPa
pre
tion
(108.8 p.s.i.)
(123.2 p.s.i.)
i.e. effective pressure
at 20C(68F) and 101.3 kPa
Filling rated effective pressure
0.65 MPa
0.75 MPa
+ 0.01
pre
-- 0
for the insulation
(94.3 p.s.i.)
(108.8 p.s.i.)
Alarm effective pressure for the + 0.02 0.54 MPa (pme+0.03 MPa) 0.64 MPa (pme+0.02 MPa)
pae
-- 0
insulation
(78.3 p.s.i.)
(92.8 p.s.i.)
Minimal effective pressure for
0.51 MPa
0.61 MPa
+ 0.02
pme
-- 0
the insulation
(74 p.s.i.)
(88.5 p.s.i.)
SF6 mass
16.5 kg
19 kg
for one three--pole circuit--breaker
SF6 gas density
pre
49.59 kg/m3
57.04 kg/m3
pae
41.66 kg/m3
48.86 kg/m3
3
pme
39.55 kg/m
46.68 kg/m3
The above characteristics are of a general nature, only those values given on
the circuit--breakers rating plates are contractually binding.

Operating device

The table below gives low voltage components characteristics of the FK3--1
operating device :

Auxiliary voltages (usual) :


Ua
Opening and closing circuits
Heating (and lighting) circuits
Motor
Consumption :
Closing and opening coils
Permanent heating
Motor

48--110--125--220--250 V (dc)
220 V (ac)
110--220 (dc) or 220 V (ac)
340W / coil
50 W
800 W (dc) or 950 VA (ac)

The above characteristics are of a general nature, only those values given on
the circuit--breakers rating plates are contractually binding.

08--2000
E ALSTOM

L10--006EN/02
2/2

Description and operation

General description of the circuit-- breaker

Circuit--breaker GL314 with spring operating mechanism FK3-- 1

Description

The circuit--breaker is made up of three poles, each activated by a spring operating mechanism.

Diagram

A
C

Parts table

The table below gives the main parts of the circuit--breaker :


Mark
A
B
C
D

06--2003
E ALSTOM

Component
Pole of the circuit--breaker
Support--frame
Operating device
Marshalling cubicle

Page
2
3
4
5

L12--016EN/01
1/6

Description and operation

General description of the circuit-- breaker

Pole of the circuit-- breaker

Description

The pole of the circuit--breaker is made up with three main components :


D The interrupting chamber (1).
D The support column (2).
D The housing of the mechanism (3).

Diagram

5
2
3

Interrupting
chamber

The pole is comprised of an interrupting chamber (1) in a ceramic or composite envelope -- laid out vertically -- equipped at each end with an HV terminal
(5).

Support column

Consisting of one or two ceramic or composite insulators, the support column


(2) allows the circuit--breaker to be ground--insulated and it also encloses the
operating tie--rod which is attached to the interrupting chambers moving contact.

Housing of the
mechanism

A housing (3) -- situated at the base of the column -- contains the lever and
crank assembly and which operates the moving contact.
The SF6 filling and monitoring device (7) is also situated on the housing.
An external cylinder (4) mechanically links the pole to the operating device.

06--2003
E ALSTOM

L12--016EN/01
2/6

Description and operation

General description of the circuit-- breaker

Support-- frame

Description

The support--frame (9) is fastened to the ground and supports all the circuit-breaker components.
The support--frame may be supplied by either ALSTOM or the customers.

Diagram

06--2003
E ALSTOM

L12--016EN/01
3/6

Description and operation

General description of the circuit-- breaker

Operating device

Description

The operating device (10) is a spring operating mechanism of the FK3--1 type.
The door of the operating device (10) is equipped with two windows. These
windows permit to display the optical signalization of the circuit--breaker state
and closing spring state.

Diagram
10
3

Fastening

06--2003
E ALSTOM

The operating device is fastened on the housing (3).

L12--016EN/01
4/6

Description and operation

General description of the circuit-- breaker

Marshalling cubicle

Description

The marshalling cubicle (D) is fastened on the ground near the central
pole. Included with :
D The relays required to operate the circuit--breaker.
D The interconnection terminals boards.
D The terminals boards.

Diagram

06--2003
E ALSTOM

L12--016EN/01
5/6

Description and operation

General description of the circuit-- breaker


This page is intentionally blank.

06--2003
E ALSTOM

L12--016EN/01
6/6

Description and operation

Description of the interrupting chamber


Presentation
Quenching medium

The quenching medium is pressurized SF6 gas or -- in particular instances -pressurized SF6+CF4 gas mixture.

Interrupting principle

The interrupting chamber is of thermal blasting type, using the energy from
the arc, with an auxiliary autopneumatic effect.

Description

The interrupting chamber has been designed in such a way as to increase the
mechanical resistance of the working part and take advantage of the low wear
rate of the contacts subjected to the arc in SF6. The working part is enclosed
in a leak tight ceramic envelope, providing insulation between the circuit-breaker input and output.
The chamber is made up of the following elements :
1

Mark
2

11

Component

Terminal

Fixed contact support

Main contacts

Moving contact

Moving contact support

Envelope

10

Arcing contacts

11

Fixed contact rod

12

Insulating nozzle

13

Valve

12

10

13
5

08--2000
E ALSTOM

L12--103EN/02
1/2

Description and operation

Description of the interrupting chamber


This page is intentionally blank.

08--2000
E ALSTOM

L12--103EN/02
2/2

Description and operation

Pole operation
(Interrupting principle)
Presentation
Introduction

In CLOSED position the current passes through :


-- the terminal (1),
-- the fixed contact support (2),
-- the main contacts (3),
-- the moving contact (4),
-- the moving contact support (5),
-- the opposite terminal (1).

2
3

In this module

This module contains the stages of the pole operation :


Stage
Opening
Closing

08--2000
E ALSTOM

Page
2
5

L13--003EN/02
1/6

Description and operation

Pole operation
(Interrupting principle)
Opening
Description

When an electrical or manual opening order is given, the energy accumulated


in the opening spring (7) -- inside the operating device -- is released.
The insulating tie--rod (8), directly activated by the opening spring (7), transmits the movement to the moving contact (4) which causes the contacts to
separate.

Continued on next page.

08--2000
E ALSTOM

L13--003EN/02
2/6

Description and operation

Pole operation
(Interrupting principle)
Opening, continued
Operation

The table below gives the stages of opening :


Stage
Start of opening

Description
When the moving contact (4) separates from the main
contacts (3), the current is switched onto the arc contacts (10). The compression of the (Vp) volume causes the first rise of pressure.

3
Thermal effect

10

Vp

When the contacts (10) separate, the arc appears and


its energy causes the pressure to rise in the thermal
expansion volume (Vt), closed by the fixed contact rod
(11) and the insulating nozzle (12).

11
Interrupting and
assistance
at opening

12

10

Vt

When the rod (11) comes out of the nozzle (12), the
thermal overpressure in the volume (Vt) is released
causing an energy blast to occur, just before the current zero passage, ensuring final quenching of the arc.
The (Vp) volume pressure decreases to the ambiant
pressure by means of the valve (13) to allow the end
of the opening.

11

12

Vt

Vp

13

Continued on next page.

08--2000
E ALSTOM

L13--003EN/02
3/6

Description and operation

Pole operation
(Interrupting principle)
Opening, continued
Operation, continued

The table below gives the continuation of opening stages :


Stage
OPEN position

Special case
of small currents

Description
The arc has been extinguished.
The SF6 molecules, separated by the arc, are re-formed instantaneously.
Residual gases left over from the interruption operation are absorbed by the molecular sieve, situated at
the base of the pole. A few powdery compounds are
deposited in the form of dust which is quite harmless
for the circuit breaker.

For small currents (example : operating no--load lines, transformers or capacitor banks), the thermal energy of the arc is too low to provide enough excess pressure.
Consequently, the conventional autopneumatic effect developing in the volume (Vp) is used mainly, to blast the arc.

Vp

08--2000
E ALSTOM

L13--003EN/02
4/6

Description and operation

Pole operation
(Interrupting principle)
Closing
Description

When an electrical or manual closing order is given, the energy accumulated


in the closing spring (15) -- situated inside the operating device -- is released.
This energy is transmitted directly to the pole operating shaft (16), to ensure
closing.
The release of the energy stored up in the closing spring (15) causes displacement of the moving parts -- and so the closing of the interrupting chamber -and also reloads the opening spring (7).

16

15

08--2000
E ALSTOM

L13--003EN/02
5/6

Description and operation

Pole operation
(Interrupting principle)
This page is intentionally blank.

08--2000
E ALSTOM

L13--003EN/02
6/6

Description and operation

Operating device

Presentation

Introduction

The operating device is a spring operating mechanism of type FK3--1.


The operating mechanism is usually electrically remote--controlled.
During commissioning or when auxiliary voltage is lacking, operations can
also be performed directly on the mechanism.

Warning

OPERATION AUTHORIZED ONLY IF THE OPERATING DEVICE IS CONNECTED TO THE CIRCUIT BREAKER.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.

In this module

This module contains the following topics :


Topic
Description of the mechanism
Auxiliary fittings
Operating principle

07--2003
E ALSTOM

Page
2
3
5

L14--007EN/01
1/6

Description and operation

Operating device

Description of the mechanism

Drive shaft

D The main shaft (1) is linked up to the the circuit--breaker pole by means
of a cylinder (2).
D A damper (4) is linked up to the lever (32).
D In the CLOSED position, the main shaft (1) rests on the opening latch
(6) by means of the lever (5).
D The lever with roller (11) rests on the closing cam (10).
D The opening spring (3) activates the lever (33) by means of the chain
(34). This spring is a pressure helical type.
NOTE : The levers (5)--(11)--(32)--(33) form one piece only.

Closing shaft

D On the closing shaft (7) are placed :


-- The inertia flywheel (8).
-- The closing cam (10).
-- The cam (26) that engages the limit switch (17) of the motor (12).
D The closing spring (9) activates the inertia flywheel (8) by means of the
chain (15). This spring is a pressure helical type.
The rotation torque -- created on the inertia flywheel (8) by means of the
loaded closing spring (9) -- is balanced : closing latch (14) / roller (16).
2

Diagram

6
1

14

32

4
9

5
33
16

26

10

32

15

5
34

11

07--2003
E ALSTOM

33

12
17

L14--007EN/01
2/6

Description and operation

Operating device

Auxiliary fittings

Reloading the closing The closing spring (9) is loaded by means of the reducing gears (13) and the
spring
motor (12).
13
9
12
13
12

Auxiliary electric
fittings

The table below describes the main parts of the auxiliary electric fittings :
Auxiliary electric fittings
The alarm contacts (30) are activated by a rod and a lever (31), the latter is activated by the main shaft (1).

Diagram
30
31

The limit switch of the motor (17) is


activated by the cam (26) and the
lever (35).
The cam (26) is installed on the closing shaft (7).

7
26
35
17

The closing latch (14) and the opening latch (6) are electrically activated
by coils (22) Closing and (27)
Opening.

27
22
6
14

Continued on next page.


07--2003
E ALSTOM

L14--007EN/01
3/6

Description and operation

Operating device

Auxiliary fittings, continued

Auxiliary mechanical
fittings

The table below describes the main parts of the auxiliary mechanical fittings :
Auxiliary mechanical fittings
The operating mechanism can be activated by the manual levers (24)
Closing and (28) Opening.

Diagram
24

28

The indicator (29) gives the OPEN


or CLOSED positions of the circuit-breaker. An operation counter (36)
gives the number of realized operations.

36
29

Circuit--breaker
Open
The indicator (23) gives the
LOADED or RELEASED states of
the closing spring.

23

Closing spring
Loaded

If the auxiliary current supply fails, the


hand--held crank (21) permits the
closing spring to be fully loaded.

21

07--2003
E ALSTOM

L14--007EN/01
4/6

Description and operation

Operating device

Operating principle

Closing

The table below gives the stages of closing operation :


OPERATION AUTHORIZED ONLY IF THE OPERATING DEVICE IS CONNECTED TO THE CIRCUIT BREAKER.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.
Stage
1

Description
When the closing coil is
stimulated or the manual
closing lever is operated,
the closing latch (14) releases the inertia flywheel
(8).

Diagram
14

8
2

D The closing shaft (7) effects a 180 rotation generated by the loaded closing
spring (9).
D The cam (10) rotates the
main shaft (1) by means of
the lever with roller (11). After a 60 rotation, the lever
(5) rests on the opening
latch (6).

33

11
1

60

7
3

2 bis

D Simultaneously,
the
opening spring (3) is loaded
by means of the chain (34)
activated by the rotation of
the lever (33).
D A freewheel, installed on
the gear wheel (19), avoids
the reducing gears (13) and
the motor (12) being driven
by the gear wheel of the inertia flywheel (8).
NOTE : A device prevents all closing operations if the circuit--breaker
is
already
in
the
CLOSED position.

180

9
10
34

8
19
12
13

Continued on next page.


07--2003
E ALSTOM

L14--007EN/01
5/6

Description and operation

Operating device

Operating principle, continued

Reloading the closing When the motor (12) is supplied with current, it immediately starts to load
spring
the closing spring (9) by means of the reducing gears (13) of the inertia
flywheel (8) and the chain (15).
At the full stroke, the gear (19) is at the no tooth sector of the inertia flywheel (8) and the reducing gears (13) can stop without causing strain on
the closing latch (14).
NOTE : During the loading of the closing spring, the supplying circuit
of the closing coil is cut to avoid an untimely closing operation.
14
8

8
9
19

15
12
13

Opening

D When the opening coil (27) is stimulated or the manual opening lever
(28) is operated, the opening latch (6) releases the lever (5).
D The main shaft (1) effects a 60 clockwise rotation -- generated by the
loaded opening spring (3) -- before reaching the circuit--breaker OPEN
position.
D A damper (4) dampens the excess energy to smoothly finish travel.
OPERATION AUTHORIZED ONLY IF THE OPERATING DEVICE IS CONNECTED TO THE CIRCUIT BREAKER.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.
6
5
4

60

3
1

07--2003
E ALSTOM

L14--007EN/01
6/6

Description and operation

SF6 gas monitoring

Presentation

Introduction

The circuit--breaker uses pressurized SF6 gas as electric arc quenching gas.
The SF6 gas pressure monitoring is essential to assure the circuit--breaker
performances.

Principle

There is two SF6 gas pressure monitoring types :


D Permanent monitoring with the help of a threshold densimeter.
D Periodic monitoring with the help of a dial densimeter (visual control)

Symbols

IEC symbols for the apparatus technical characteristics.


Symbol
pre
pae
pme

In this module

Designation
Filling rated pressure for the insulation
Alarm pressure for the insulation
Minimal pressure for the insulation

This module contains the following topics :


Topic
Gas pressure and density
Pressure measurement
Measuring density
Densimeter

01--2003
E ALSTOM

Page
2
3
4
5

L20--001EN/04
1/6

Description and operation

SF6 gas monitoring

Gas pressure and density

Introduction

The electrical characteristics of switchgear depend on the density of SF6 gas


i.e. the mass of gas pumped into a compartment of a given volume.

Constant
temperature

At constant temperature, an increase of gas density results in a higher gas


pressure against the walls of compartment.

Constant density

At constant density, with an fixed compartment volume, the pressure


changes in the same way as the temperature. Since the gas density remains invariable owing to the fact that no modification occurs in the quantity of gas or the volume of the relevant compartment, the electrical characteristics of the switchgear will remain unchanged.

Conclusion

Since it is difficult to measure the gas density directly, it is essential to


know accurately its absolute pressure and temperature.

01--2003
E ALSTOM

L20--001EN/04
2/6

Description and operation

SF6 gas monitoring

Pressure measurement

Effective pressure ?
Absolute pressure ?

Absolute pressure = effective pressure + atmospheric pressure

Pressure

Description
The pressure of SF6 gas is measured by of a standard pressure
gauge with a deformable diaphragm
actuating an indicating pointer.
One surface of the diaphragm is in
contact with the SF6 gas, while the
other is in contact with the atmosphere. The difference between the
Effective gas and the atmosphere is thus
measured, taking atmospheric
pressure as a reference. This is the
measurement of the effective pressure of the SF6 gas.

Diagram
Standard pressure gauge

SF6
Atmospheric pressure
If the deformable diaphragm, one
surface of which is in contact with
the SF6 gas, blocks a volume where
a vacuum has been developed, the
pressure gauge measures the pressure difference between that of the
SF6 gas and the vacuum. Since the
latter is zero, the pressure gauge
measures the absolute pressure of
the gas.
The absolute pressure of the SF6
gas, independent of atmospheric
pressure, reflects the quantity of
Absolute gas introduced into the compartment and hence its density at the
present temperature.
This is measured by means of an
absolute pressure gauge which is
less generally used and more delicate than a effective pressure
gauge. This is the reason why a effective pressure gauge is used, provision being made for corrections
required by atmospheric pressure
variations resulting from atmospheric disturbances and differences of elevation.

01--2003
E ALSTOM

Absolute
pressure gauge

SF6
Vacuum volume

L20--001EN/04
3/6

Description and operation

SF6 gas monitoring

Measuring density

Pressure units

D The international unit pressure is the Pascal (Pa).


D The practical unit is the bar (14.503 p.s.i.)
1 bar = 1,000 hPa
1 bar = 100 kPa
10 bar = 1 MPa
D Standard atmospheric pressure is equal to 101.3 kPa at sea level and an
air temperature of 20C (68F).

Measuring density

When it is not possible to directly measure density, this may be checked


using an industrial pressure gauge capable of measuring the effective
pressure.
An effective pressure value corresponds to the rated density, determined
for normal atmospheric pressure (101.3 kPa) and an ambient temperature
of 20C (68F).
For each pressure reading (filling, inspection of densimeter thresholds...), the
rated effective pressure should be corrected according to the ambient temperature and atmospheric pressure of the site at the time the reading is taken.
See the module Calculation of the SF6 gas filling pressure to using the
pressure gauge (tool).
The real pressure is therefore :

Preal = Prated effective in accordance with temperature + Pp*


* Pp : correction in accordance with atmospheric pressure.

01--2003
E ALSTOM

L20--001EN/04
4/6

Description and operation

SF6 gas monitoring

Densimeter

Function

D Permanent SF6 gas density monitoring.


D Visual SF6 gas real pressure information (MPa -- psi).

Localization

The densimeter is situated onto the bottom of the pole of the circuit--breaker,
and joined to the gas volume of the circuit--breaker.

Working

The densimeter is fitted with internal contacts. These contacts close successively if the gass density diminishes and determine 2 distinct thresholds.
These contacts are wired to the terminal block inside the cubicle and are usually left at the users disposal for the following use :
D Alarm pressure pae acts as a warning (topping up necessary).
D Minimum functional pressure for insulation pme must be used either to
lock the circuit--breaker in position or to cause automatic opening. The option
is chosen by the client in keeping with operating requirements.
All the circuit--breakers rated performances are guaranteed up to the minimum specified ambient temperature and the minimum functional
pressure for insulation pme.
Continued on next page.

01--2003
E ALSTOM

L20--001EN/04
5/6

Description and operation

SF6 gas monitoring

Densimeter, continued

Reading the dial

The dial is divided into three colored areas : Green, Yellow and Red. The position of the needle indicates the SF6 gas effective pressure value.

-1
0

Needle position

Colored area

Direction

GREEN

None

YELLOW

Perform a topping--up
operation.

RED

01--2003
E ALSTOM

Abnormally low density,


find the origin of the
leak and contact
ALSTOM T&D S.A.
After--sales Service.

L20--001EN/04
6/6

Packaging -- Shipping and storage

Packaging - Identification - Storage

Presentation

Information

The poles are filled with gas SF6 for transport purposes to an effective pressure of 0.3 bar 20C (1,013 hPa).

In this module

This module contains the following topics :


Topic
Packaging
Identifying sub--assemblies and their packaging
Storage

09--2003
E ALSTOM

Page
2
3
4

L22--008EN/01
1/4

Packaging -- Shipping and storage

Packaging - Identification - Storage

Packaging

Introduction

For transport, the different parts of the apparatus are divided--up between
several cases. The number of cases and their contents depend of dimensions
of the pole of the circuit breaker.

Example 1

D A main case containing :


-- The poles.
-- The operating devices vacuum--wrapped in a protective bag containing desiccants.
-- The different frame parts if the latter is supplied by ALSTOM.
-- The marshalling cubicle.
-- Connection cables, if supplied by ALSTOM.
D The SF6 bottle(s) or depending of the apparatus SF6 bottle(s) and CF4
bottle(s).
D A case containing assembly products (grease, oil, etc.) required for installation.
D A case containing the accessories : spare parts ...

Example 2

D A main case containing :


-- The poles.
-- The different frame parts if the latter is supplied by ALSTOM.
D A case containing the operating devices. The operating devices are vacuum--wrapped in a protective bag containing desiccants.
D A case containing the marshalling cubicle.
D The SF6 bottle(s) or depending of the apparatus SF6 bottle(s) and CF4
bottle(s).
D A case containing assembly products (grease, oil, etc.) required for installation.
D A case containing the accessories : spare parts ...
GL314

Packaging case type

Example

Length
cm

Width
cm

Height
cm

537 -- 600

219

113

580 -- 625

183

113

251

78

113

178
111

72
80

113
190

188

58

65

60

60

70

80

60

70

Poles
Operating devices
Marshalling cubicle *
SF6 gas
Necessities (products)
for assembly
Accessories *

1
1
1

Gross weight
kg

* Depending of the apparatus


NOTE : the values in the above table are given as an indication so
that an appropriate means of lifting can be envisaged.

09--2003
E ALSTOM

L22--008EN/01
2/4

Packaging -- Shipping and storage

Packaging - Identification - Storage

Identifying sub--assemblies and their packaging

Introduction

Each circuit--breaker sub--assembly (poles, operating mechanism, etc.) is


identified by a plate giving its reference numbers.
These numbers are marked on the packaging cases of each sub--assembly.

Example of marking
and identifying

-- Manufacturer reference No. = 101 525


-- Circuit--breaker identification No. 1
-- Pole No. 2
IDENTIFICATION OF SUB-ASSEMBLIES AND TOOLING

MARKING OF
PACKAGING CASES

MANUFACTURER
REFERENCE No.

101 525 0010


0101

101 525 0010


no SRIE
Rep. 01/2

POLE No.

CASE No.

CIRCUIT--BREAKER
IDENTIFICATION No.

Place of the plates

Choose and install the components identified by the plate (1) and self-adhesive (3).
101 525 0010
no SRIE
Rep. 01/2
1

OUTSIDE PLATE

INSIDE PLATE

09--2003
E ALSTOM

L22--008EN/01
3/4

Packaging -- Shipping and storage

Packaging - Identification - Storage

Storage

Introduction

The storage procedures defined below are for storage times of less than 2
years. For longer periods, special packaging must be designed and appropriate procedures devised.

Short--term storage
(6 months)

The apparatus must be stored in its transport packaging and placed on beams
in a flood--proof place.

Medium--term storage The table below indicate how to stock the main components of the circuit-(less than 2 years)
breaker for a medium--term storage :
Component
Circuit--breaker pole

Operating device

Storage
The apparatus must be stored with its
transport packaging open whilst
placed on beams in a closed, but ventilated, flood--proof place.
The operating device should be
stored in the same place as the circuit--breaker, these two sub--assemblies being inseparable. Check that
the vacuum packaging is leak--tight.
If this has been damaged, proceed as
follows :
D Completely remove the packaging
protection so that air can enter
through the vents of the rear plate and
side panels.
D In order to prevent corrosion damage due to formation of condensation,
it is mandatory that the heating circuit
be switched on.

ANY CHANGE OF LOCATION OF THE APPARATUS (EVEN AFTER COMMISSIONING) SHOULD BE DONE AT A REDUCED PRESSURE OF
0.3 BAR.

09--2003
E ALSTOM

L22--008EN/01
4/4

Installation

Erection general instructions


Erection general instructions
Instructions
of environment

The table below gives the instructions of environment to respect for the erection :
Instruction

Erection
instructions

Verify the Civil engineering work : dimensions,


levels of concrete pads (structure fixation), in
accordance with the tolerances given by Civil
work standards (refer to circuit--breaker outline).

Avoid any dust production and masonry work


during erection of the circuit--breaker.

The table below gives the instructions to respect for proper erection of the circuit--breaker :
Instruction

Warning

07--1998
E ALSTOM

Comment

Comment

Read all the Installation modules completely


before beginning erection works.
The erection instructions describe all the procedures to be carried out as well as their chronological order.

Handle sub--assemblies in a correct manner,


particularly insulators.

The shipping case should be open as required


during erection procedures.
CAUTION : Respect sub--assemblies identification.

When shipping covers are removed, proceed to


the next assembly sequence in as short as possible time.
Store the shipping covers under shelter, for a
possible future use.

Respect references to
i.e. :Tightening torquesI.

other

modules,

No responsibility is taken over by ALSTOM T&D S.A. for damages and


disturbances resulting out of non--adherence to the Installation modules.
T30--002EN/01
1/2

Installation

Erection general instructions


This page is intentionally blank.

07--1998
E ALSTOM

T30--002EN/01
2/2

Installation

Tightening torques
Presentation
Introduction

In the assembling with screws, all the fastening screws must be greased before torque tightening.

Products used

The table below gives the list of the used products for the screws before tightening :
Designation
Grease
Contact grease
Silicon grease
Glue

In this module

ALSTOM item
reference
--01835208
(1kg box)
--01835118
(200g tube)
--01835265
(100g tube)
--01818327
(250ml)

06--2002

MOBIL OIL
EPMF

Supplier item
reference
MOBILPLEX 47
MOBILUX EP3
CONTACTAL
HPG

SAMARO

MOLYKOTE 111

LOCTITE

LOCTITE 225

This module contains the following topics :


Topic
Screw greasing before tightening
Tightening torques values

E ALSTOM

Supplier

Page
2
3

T31--001EN/02
1/4

Installation

Tightening torques
Screw greasing before tightening
Choice of the
product to use

The table below gives the product to use for the screws before tightening depending on the assembling type :
If assembling...
usual
electrical connections

with seals

Where to apply
the product ?

Product to use ...


MOBILPLEX 47
MOBILUX EP3
CONTACTAL HPG
Can be
dismantled ?
YES
NO

Product ...
MOLYKOTE 111
LOCTITE 225

The table below indicates the part of the screws to treat with the appropriate
product before tightening depending on the assembling type :
If assembling...

With screws

With bolts

usual

electrical connections

Tapping or threading
with seals

06--2002
E ALSTOM

Tapping or threading

T31--001EN/02
2/4

Installation

Tightening torques
Tightening torques values
Values table

The tool and the tightening method must be such that the torque actually applied to the screw head corresponds with the reference torque shown in the
table below, to within a tolerance of  20%.

TIGHTENING TORQUES
in daN.m
daN m
STEEL SCREWS

06--2002
E ALSTOM

CLASS 6.8
or
STAINLESS A2--70, A4--70
STAINLESS A2--80, A4--80

CLASS 8.8
88

M2,5

0,05

0,06

M3

0,09

0,11

M4

0,19

0,26

M5

0,38

0,51

M6

0,66

0,88

M8

1,58

2,11

M10

3,20

4,27

M12

4,97

6,63

M14

8,67

11,56

M16

13,42

17,90

M20

26,22

34,98

M24

45,68

60,93

M30

90,44

120,65

T31--001EN/02
3/4

Installation

Tightening torques
This page is intentionally blank.

06--2002
E ALSTOM

T31--001EN/02
4/4

Installation

Erection general procedures


Presentation
Introduction

During the erection of the circuit--breaker, some particular mounting or checking operations will be realized.

In this module

This module contains the following topics :


Topic
Preparing and installing static seals
Screw sealing
Using a water pressure gauge

09--1998
E ALSTOM

Page
2
3
5

T31--003EN/01
1/6

Installation

Erection general procedures


Preparing and installing static seals
Necessary products

List of the ALSTOM products necessary for the installing :


ALSTOM
reference

Process

Can of ISOPROPANOL (1l)

--01835265

MOLYKOTE 111 (100g tube)

The table below gives the steps of installing static seals :

4
5

Action
Clean bearing grooves and surfaces using ISOPROPANOL.
Rid the seal of all foreign bodies
such as paintbrush bristles or filings...
Remove (where applicable) the
color identification point with fingernail, never with a sharp instrument.
Lightly lubricate the seal by hand
using MOLYKOTE 111 grease.

Comment

Check the condition of the seal


which should present no
scratches or deformation (it
should be neither flattened,
stretched, nor broken).
Do not use a brush to do this.
Eliminate excess grease by
squeezing the seal between
fingers, leaving only a thin layer
on the entire surface.

Put the seal(s) in place.


Lubricate both bearing surfaces Do not put grease on the inside
with MOLYKOTE 111.
surface.
Fill the residual volume of the
seals outside groove with grease.

Greasing
zone

09--1998

Designation

--01861262

Step
1

E ALSTOM

Diagram

Only seals are


greased in this zone

Greasing
zone

T31--003EN/01
2/6

Installation

Erection general procedures


Screw sealing
Introduction

To prevent humidity from penetrating SF6 gaskets, the outer mounting screws
should be sealed by applying an appropriate product.
NOTE : This procedure should be applied to all assemblages of parts
submitted to SF6 pressure and electrical connection assembling.

Necessary products

List of the ALSTOM products and accessories necessary for the screw sealing :
ALSTOM
reference

Choice of the
product to use

Diagram

Designation

--01818327

LOCTITE 225 (250ml)

--01835265

MOLYKOTE 111 (100g tube)

--01835118

CONTACTAL HPG (200g tube)

The table below gives the product to use for the screw sealing depending on
the assembling type :
If assembling...

with seals

electrical connections

Product to use ...


Can be
dismantled ?
YES
NO

Product ...
MOLYKOTE 111
LOCTITE 225

CONTACTAL HPG
Continued on next page.

09--1998
E ALSTOM

T31--003EN/01
3/6

Installation

Erection general procedures


Screw sealing, continued
Where to apply
the product ?

The table below indicates the part of the screws to treat with the appropriate
product before tightening depending on the assembling type :
Assembling with screws

Assembling with bolts

Tapping or threading
Tapping or threading

09--1998
E ALSTOM

T31--003EN/01
4/6

Installation

Erection general procedures


Using a water pressure gauge
Introduction

In each assemblage performed using a double seal (1) and (2), the volume
(3) communicates with the outside by a channel (4), blocked--off by a plug (5)
or (6), so that leak--tightness can be checked.
1
3
2
4

Process

The table below gives the steps of the leak--tightness checking using a
water pressure gauge :
Step
1

Action
Remove the leak test plug (5) or (6)
and its seal (7) if necessary, leave
open for half an hour.

Diagram
7

2...3 turns
2

Connect up the water pressure gauge


(8), using the adapter (9) or (10).

10
8
9

Fill the water pressure gauges U tube


to half way up.
NOTE : If temperature is less
than 0C, use an anti--freeze mixture instead of water.
D After a few minutes note the water
column level R1.
D Note the water column level R2
again after half an hour.
The displacement H should be less
than 10 mm.
At the end of the inspection, pull the
adapter of the water pressure gauge
and replace the leak test plug (5) or (6)
and its seal (7), where required.
5

H
R2
R1

7
6

09--1998
E ALSTOM

T31--003EN/01
5/6

Installation

Erection general procedures


This page is intentionally blank.

09--1998
E ALSTOM

T31--003EN/01
6/6

Installation

Checking for presence of SF6 gas in poles

Presentation

Introduction

The pole are filled with SF6 gas for transport purposes to an effective pressure
of 0,03 MPa at 20C (101.3 kPa).

Necessary tools

List of the necessary ALSTOM tools for the checking for presence of SF6 gas
in poles :
Mark

In this module

Diagram

Designation

Filling tool

06--2003

This module contains the following topics :


Topic
Pole checking when the cases are opened on the site
Checking for presence of SF6 gas in poles

E ALSTOM

Number

Page
2
3

L31--059EN/01
1/4

Installation

Checking for presence of SF6 gas in poles

Pole checking when the cases are opened at site

Preparing the pole

Remove only the cover of the case. Remove partially packaging protection
to free the housing (7) of the poles.

Visual inspection
of the ples

06--2003
E ALSTOM

D Begin visual inspection to check the condition of ceramic envelopes. Make


sure that their enamel has not been chipped or in any way damaged during
transportation.
D It is of prime importance that the presence of SF6 gas in pole be verified
before going any further with installation

L31--059EN/01
2/4

Installation

Checking for presence of SF6 gas in poles

Checking for presence of SF6 gas in poles


Process

The table below gives the steps of checking for presence of SF6 gas in poles :
Step
1

Action
Remove the plug (1) and install
the filling tool (3), tighten the filling tool BY HAND.

Diagram

1
2

Unscrew the valve--cap (4) and


press on the valve briefly :
some gas should escape.
If no gas is expelled, contact
our Customer Service.

4
3

D Replace the valve--cap (4)


and remove the filling tool (3).
D Re--install the plug (1), applying a tightening torque of
4 daN.m; leak--tightness is
only guaranteed if this condition is respected.

06--2003
E ALSTOM

L31--059EN/01
3/4

Installation

Checking for presence of SF6 gas in poles


This page is intentionally blank.

06--2003
E ALSTOM

L31--059EN/01
4/4

Installation

Checking for presence of


stop ring of the fusible pin
Presentation
Fusible pin

The coupling cylinder of the pole (2) is maintained to circuit--breaker in


OPENED position by a fusible pin (1) assembled in factory. The holding
of the coupling cylinder -- in this position -- is essential to ensure the coupling
with the operating mechanism in good conditions.
NOTE : This fusible pin will be broken at the first operation.
The holding of the fusible pin -- in its housing -- is ensured by a stop ring
(3) held by a screw (4).
Before continuing the installation of the pole, checking the presence
of this stop ring.
2
3
4
2

In this module

This module contains the following topics :


Topic
Checking the presence of the stop ring of the fusible pin
Installing the stop ring site of the fusible pin
(in case of absence of the stop ring)

03--2004
E ALSTOM

Page
2
3

L31--090EN/01
1/4

Installation

Checking for presence of


stop ring of the fusible pin
Checking the presence of the stop ring of the fusible pin
Visual inspection

Check the presence of the stop ring (3) of the fusible pin.
NOTE : If the stop ring (3) is absent, install the stop ring site.

03--2004
E ALSTOM

L31--090EN/01
2/4

Installation

Checking for presence of


stop ring of the fusible pin
Installing the stop ring site of the fusible pin
(in case of absence of the stop ring)
Necessary
components

List of the ALSTOM components necessary for the assembling :


Mark

Necessary products

Diagram

Designation

Number

(5)

Stop ring site

(4)

Screw

List of the ALSTOM products necessary for the installing :


ALSTOM
reference

Diagram

Designation

--01818327

Installing

LOCTITE 225 (250ml)

Install the stop ring site (5) and hold in place using the screw (4).
NOTE : Stick the screw (4) using LOCTITE 225 and apply a tightening
torque of 17 N.m.
5

03--2004
E ALSTOM

L31--090EN/01
3/4

Installation

Checking for presence of


stop ring of the fusible pin
This page is intentionally blank.

03--2004
E ALSTOM

L31--090EN/01
4/4

Installation

Support-- frame assembly

Presentation

Reminder

Frames may be supplied by either ALSTOM or the customer.

In this module

This module contains the following topics :


Topic
Components necessary for the operation
Support--frame components (per pole)
Preparing the column
Frame--support assembly

06--2003
E ALSTOM

Page
2
3
4
5

L31--113EN/01
1/6

Installation

Support-- frame assembly

Components necessary for the operation

Necessary product

Grease MOBILPLEX 47 -- MOBILUX EP3 (screws greasing).

Necessary tools

List of the tools necessary for the installing :


Mark

(1)

Lifting equipment

Diagram

Designation

Number

Lifting strap
(3 m)

Provide for appropriate lifting equipment :


(3,000 daN) (minimum)
H+2m
H

Handling

06--2003
E ALSTOM

The support--frame assembly operations and lifting


the pole should be performed by at least two persons.

L31--113EN/01
2/6

Installation

Support-- frame assembly

Support--frame components (per pole)

Introduction

If the support--frame is supplied by ALSTOM, check the necessary components to the assembling.

Necessary
components

List of the ALSTOM components necessary for the assembling :


Mark

06--2003
E ALSTOM

Diagram

Designation

Number

(2)

Support

(3)

Support

(7)

Screws
H M16-35

L31--113EN/01
3/6

Installation

Support-- frame assembly

Preparing the column

Dismantling the case


of the poles

Remove the strenghtening beams of the case and free the support legs of the
frame.
Remove the side panels of the case.

Preparing the pole

D Sling the pole with the aid of two flexible lifting straps (1).
D Extract the pole from the case and put it down on the case wood cover laying :
-- first, the interrupting--chamber extremity (4) on a wood wedge,
-- second, the upper part of the housing (10) on a wood wedge to ensure the
correct installing of the frame supports.
X minimum = 260 mm
1

1
4

10
X/2

06--2003
E ALSTOM

L31--113EN/01
4/6

Installation

Support-- frame assembly

Frame--support assembly

Process

The table below gives the steps of installing the supports of the frame :
Step
1

Action
With the aid of two flexible lifting straps, position the frame--support
(2) onto the housing (10) and fasten it with the use of the screws (7).

x2

H M16--35
18 daN.m

2
10
2

With the aid of two flexible lifting straps, position the frame--support
(3) onto the housing (10) and fasten it with the use of the screws (7).

x2

H M16--35
18 daN.m

3
10
Continued on next page.

06--2003
E ALSTOM

L31--113EN/01
5/6

Installation

Support-- frame assembly

Frame--support assembly, continued

Process, continued

The table below gives the steps of installing the supports of the frame :
Step
3

Action
Position the last frame--supports (2) onto the housing (10) and fasten
with the use of the screws (7).

x2

x2
7

H M16--35
18 daN.m

7
H M16--35
18 daN.m

10

06--2003
E ALSTOM

L31--113EN/01
6/6

Installation

Lifting and positionning the pole

Presentation

Necessary
components

List of the ALSTOM components necessary for the assembling :


Mark

Diagram

(12)

Necessary tools

Diagram

(1)

Number

LIFTING STRAP
(3 m -- 1000 kg)

This module contains the following topics :

Lifting the pole


Positioning the pole

07--2003

Thick washer

Designation

Topic

E ALSTOM

Number

List of the necessary ALSTOM tools for the lifting and positionning of the
pole :
Mark

In this module

Designation

Page
2
3

L31--201EN/02
1/4

Installation

Lifting and positionning the pole

Lifting the pole

Process

Install the two flexible lifting straps (1), placing these at the end of the interrupting chamber.
By means of a lifting device hoist the pole up whilst allowing it to rest on the
base of the frame.
Place the trip ropes (10) on the support legs of the frame (9) to ensure guidance of the pole at the time of lifting.
Lift the pole with precaution.

9
10

07--2003
E ALSTOM

L31--201EN/02
2/4

Installation

Lifting and positionning the pole

Positioning the pole

Process

The table below gives the steps of positioning the pole :


Step
1
2

Action
Install the lower washers (12) on the fixation mounting.
Use a lifting device to position the chassis frame onto its ground
attachment points but do not secure it, whilst respecting the orientation of the pole indicated on the sketch of the device.

If necessary, place shims under the supports of the frame so that the
upper plate is level.
Install the upper washers (12) and clamp the whole to the ground
using nut.
Remove the lifting straps.
Check the tightening torques of all frame screws.

4
5
6

12
12

12
18 daN.m

07--2003
E ALSTOM

L31--201EN/02
3/4

Installation

Lifting and positionning the pole


This page is intentionally blank.

07--2003
E ALSTOM

L31--201EN/02
4/4

Installation

Installing terminals
with preparation of contact surfaces
Presentation
Necessary products
and accessories

List of the ALSTOM products and accessories necessary for the installing :
ALSTOM
reference

Diagram

Designation

--01861262

Can of ISOPROPANOL (1l)

--01835106

Vaseline 204--9

--01835118

Contactal grease

--01831320

Abrasive paper A400

--02212334

Rag

--02211842

Round brush No.4

--02211831

Brush No.16

Necessary document

Take the circuit--breaker layout to know the position of the treminals.

In this module

This module contains the following topics :


Topic
Preparing the contact surfaces
Installing terminals

08--2000
E ALSTOM

Page
2
3

L31--500EN/03
1/4

Installation

Installing terminals
with preparation of contact surfaces
Preparing the contact surfaces
Preparing the
contact grease

The contact grease is a mixture composed of Vaseline and Contactal grease.


CONTACT GREASE = 50% Vaseline + 50% Contactal grease

Preparing the
contact surfaces

The table below gives the steps of preparing the contact surfaces :

08--2000
E ALSTOM

Step

Action

Check the positionning of the terminals using the circuit--breaker


layout.

Remove the temporary screws


from the terminal pads X1 and X2
(an arrow indicates the terminal
positions).

Dry rub with fine emery cloth.

Eliminate the dust produced.

Coat with CONTACT GREASE.

Wipe with a clean rag, leaving just


a thin layer of grease.

Rub over the grease with waterproof abrasive paper A400.

Diagram

X1

X2

L31--500EN/03
2/4

Installation

Installing terminals
with preparation of contact surfaces
Installing terminals
Lower terminal

Assemble immediately the terminals (1) on the interrupting chamber (3) after
preparation of contact surfaces. Fasten the terminals using screws (5); use
CONTACT GREASE to seal the screws.

x 4
5

Upper terminal

H M12--70
5 daN.m

Assemble immediately the terminals (1) on the interrupting chamber (3) after
preparation of contact surfaces. Fasten the terminals using screws (4); use
CONTACT GREASE to seal the screws.

1
4

x 4

H M12--45
5 daN.m

Comment

08--2000
E ALSTOM

D The electrical resistance value of the assembly should be :


R 2
D Before installing H.V. connectors, prepare the contact surfaces in the
same way.

L31--500EN/03
3/4

Installation

Installing terminals
with preparation of contact surfaces
This page is intentionally blank.

08--2000
E ALSTOM

L31--500EN/03
4/4

Installation

Installing the operating device


Presentation
Necessary product

Grease MOBILPLEX 47 (screws greasing)

Necessary ALSTOM
tools

List of the ALSTOM tools necessary for the installing :


Mark

(1)

Diagram

Designation

Number

Lifting strap

Lifting equipment

Provide an appropriate lifting equipment (130 daN).

Process

The table below gives the steps of installing the operating device on the
pole--support :
Step
A
B
C
D
E
F

01--2004
E ALSTOM

Topic
Preparing the operating device
Positioning the pole operating shaft
Coupling the operating device
Low voltage electrical wiring
Installing side panels of the operating device
Permanent heating system

Page
2
3
4
6
7
8

L31--789EN/01
1/8

Installation

Installing the operating device


Preparing the operating device
Unpacking

Remove packaging protection and check that operating device and pole
reference numbers are the right ones.

Optical signalizations Check the position of operating device optical signalization :

Circuit--breaker
Open

Removing
side panels

Closing spring
Released

The table below gives the steps of side panels removing :


Step
1

Action
Remove the nuts (2) from
the left side panel (3).

Diagram

x2
2
NYLSTOP
M8

Operating shaft

Take hold of the left side


panel (3) from underneath,
pull slightly towards the outside, then downwards to remove it.
Proceed in the same way
for the right side panel.

Check the presence of the seal (11) on the operating shaft (13).
Check the presence of grease (ASEOL 0--365.2) on the operating shaft
(13).
11
13

01--2004
E ALSTOM

L31--789EN/01
2/8

Installation

Installing the operating device


Positioning the pole operating shaft
Fusible pin

The pole is equipped -- for transport purposes and installing the operating
device -- with a positioning fusible pin (4) of the pole operating shaft.
Check the presence of this pin.
This pin must remain in place during all the operation of assembly of the operating mechanism, IT IS STRICTLY FORBIDDEN TO REMOVE IT.

01--2004
E ALSTOM

L31--789EN/01
3/8

Installation

Installing the operating device


Coupling the operating device
Necessary
components

List of the ALSTOM components necessary for the operation :


Mark

Installing the
fastening screws

Diagram

Designation

Number

Screw H M16--80

10

Washer (979997001)

14

Nut H M16

Install the screws (9) -- equipped with the washers (10) -- inside the operating
device.
10

x 4
10

9
9
Continued on next page.

01--2004
E ALSTOM

L31--789EN/01
4/8

Installation

Installing the operating device


Coupling the operating device, continued
Coupling

The table below gives the steps of the operating device coupling :
Step
1

Action
Sling the operating device
using the lifting strap (1) like
diagram.
NOTE : Do not remove the
roof (17) of the operating
device before slinging.

Lift the operating device and


make this level.

Approach the operating device


in assembly position.

Comment
1

17

The final approach must be


done with extreme caution.

Introduce the operating device


shaft (13) into the cylinder (12).

13
12

D Put the washers (10) and


nuts (14) in place and tighten to
recommended torque.
D Remove the flexible strap.
10

x 4

14
H M16
18 daN.m

01--2004
E ALSTOM

L31--789EN/01
5/8

Installation

Installing the operating device


Low voltage electrical wiring
Process

Connect up the operating devices wires refer to the wiring diagram of the circuit--breaker.
If the circuit breaker is equipped with a marshalling cubicle, connect up the
operating devices wires to the marshalling cubicle.

Connecting up the
contact densimeter
cable

Connect the wires from the electrical contact SF6 densimeter (18) cable (19)
to the operating mechanism terminal block, in accordance with the relative
diagram.

18
19

01--2004
E ALSTOM

L31--789EN/01
6/8

Installation

Installing the operating device


Installing side panels of the operating device
Process

Reinstall the side panels (3) of the operating device using new nuts (2).

x2
2
NYLSTOP
M8
1,6 daN.m
3

01--2004
E ALSTOM

L31--789EN/01
7/8

Installation

Installing the operating device


Permanent heating system
Process

Switch on the permanent heating system of the operating device (in both summer and winter) to avoid condensation, and the corrosion which might result
from this.

DO NOT SUPPLY THE OPERATING MECHANISM MOTOR WITH CURRENT TO AVOID THE CLOSING SPRING BEING RELOADED.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.

01--2004
E ALSTOM

L31--789EN/01
8/8

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
Presentation

Introduction

SF6 pressure values, for the filling, must obligatorily be read on the pressure
gauge 0--1 MPa (tooling). Pay no attention to indications given by the dial
densimeter (MPa -- psi), it is not accurate enough for the filling.

Pressure gauge 0--1 MPa

Pressure units
(reminder)

D The international unit pressure is the Pascal (Pa).


1 bar (14.503 psi) = 1,000 hPa
1 bar = 100 kPa
10 bar = 1 MPa

Symbols

IEC symbols for the apparatus technical characteristics.


Symbol
pre
pae
pme

In this module

Designation
Filling rated pressure for the insulation
Alarm pressure for the insulation
Minimal pressure for the insulation

This module contains the following topics :


Topic
Example of the filling pressure calculation
Calculation of the filling pressure at site
Values of the SF6 gas pressures in accordance
with the temperature

08--2000
E ALSTOM

Page
2
3
4

L31--901EN/02
1/6

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
Example of the filling pressure calculation

Example

Determination of the circuit--breakers filling pressure with SF6 gas.


Parameters
pre
SF6 gas rated filling effective
pressure for the insulation
Ambient temperature
Local atmospheric pressure

SF6 gas filling

08--2000

0.65 MPa (94.3 psi)


5C
93.2 kPa

The table below gives the calculation steps of the pure SF6 filling pressure :
Step
1

E ALSTOM

Values

Action
In the chart (page 5) Values of the
SF6 gas effective pressures in accordance with the temperature,
read the pre value on the tC = 5
row.
Calculate the difference of the atmospheric pressure :
0.1013 -- 0.0932
Calculate the rated effective pressure pre :
0.603 + 0.0081
Filling is carried out to the calculated pressure, plus 0,01 MPa,
that is to say : 0.6111 + 0.01

Result

0.603 MPa

0.0081 MPa

0.6111 MPa
Pure SF6 gas filling pressure
0.6211 MPa

L31--901EN/02
2/6

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
Calculation of the filling pressure at site

Measurement

Write down the result measurement into the corresponding box :


Measure the atmospheric pressure in MPa.
A

Measure the ambient temperature in C.


B

Calculation of the
pure SF6 gas filling
pressure

Transfer the values into the corresponding box and write down the result :

With the help of the table (page 5) Values of the SF6 gas
effective pressures in accordance with the temperature,
determine the value pre in accordance with
the ambient temperature (B) " C

pre

,
Value of the reference atmospheric pressure in MPa D 0 , 1 0 1
Transfer the value of the local atmospheric pressure
(A) " A - ,
Calculate the difference of the atmospheric pressure
(D -- A) " E
,
Transfer the value (C) "
C+ ,
Calculate the rated effective pressure
(E + C) " F
,
The filling with SF6 gas is carried out
to the calculated pressure, plus 0.01 MPa, + 0 , 0 1
(F + 0.01) " G

08--2000
E ALSTOM

L31--901EN/02
3/6

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
Values of the SF6 gas effective pressures in accordance with the temperature
Rated effective pressure 0.75 MPa

Values of the SF6 gas effective pressures (MPa) corrected in accordance with
temperature for an atmospheric pressure of 101.3 kPa :
t_C

pre

pae

pme

t_C

pre

pae

pme

--25
--24
--23
--22
--21
--20
--19
--18
--17
--16
--15
--14
--13
--12
--11
--10
--9
--8
--7
--6
--5
--4
--3
--2
--1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

0,584
0,588
0,591
0,595
0,599
0,602
0,606
0,610
0,613
0,617
0,621
0,625
0,628
0,632
0,636
0,639
0,643
0,647
0,650
0,654
0,658
0,661
0,665
0,669
0,673
0,676
0,680
0,684
0,687
0,691
0,695
0,698
0,702
0,706
0,709
0,713
0,717
0,720
0,724
0,728
0,732
0,735
0,739

0,500
0,503
0,506
0,509
0,512
0,516
0,519
0,522
0,525
0,528
0,531
0,534
0,537
0,540
0,544
0,547
0,550
0,553
0,556
0,559
0,562
0,565
0,568
0,572
0,575
0,578
0,581
0,584
0,587
0,590
0,593
0,596
0,600
0,603
0,606
0,609
0,612
0,615
0,618
0,621
0,624
0,628
0,631

0,477
0,480
0,483
0,486
0,489
0,492
0,495
0,498
0,501
0,504
0,507
0,509
0,512
0,515
0,518
0,521
0,524
0,527
0,530
0,533
0,536
0,539
0,542
0,545
0,548
0,551
0,554
0,557
0,560
0,563
0,566
0,569
0,572
0,575
0,577
0,580
0,583
0,586
0,589
0,592
0,595
0,598
0,601

18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

0,743
0,746
0,75
0,754
0,757
0,761
0,765
0,768
0,772
0,776
0,780
0,783
0,787
0,791
0,794
0,798
0,802
0,805
0,809
0,813
0,816
0,820
0,824
0,827
0,831
0,835
0,839
0,842
0,846
0,850
0,853
0,857
0,861
0,864
0,868
0,872
0,875
0,879
0,883
0,887
0,890
0,894
0,898

0,634
0,637
0,64
0,643
0,646
0,649
0,652
0,656
0,659
0,662
0,665
0,668
0,671
0,674
0,677
0,680
0,684
0,687
0,690
0,693
0,696
0,699
0,702
0,705
0,708
0,712
0,715
0,718
0,721
0,724
0,727
0,730
0,733
0,736
0,740
0,743
0,746
0,749
0,752
0,755
0,758
0,761
0,764

0,604
0,607
0,61
0,613
0,616
0,619
0,622
0,625
0,628
0,631
0,634
0,637
0,640
0,643
0,645
0,648
0,651
0,654
0,657
0,660
0,663
0,666
0,669
0,672
0,675
0,678
0,681
0,684
0,687
0,690
0,693
0,696
0,699
0,702
0,705
0,708
0,711
0,713
0,716
0,719
0,722
0,725
0,728

Continued on next page.

08--2000
E ALSTOM

L31--901EN/02
4/6

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
Values of the SF6 gas effective pressures in accordance with the temperature,
continued
Rated effective pressure 0.65 MPa

08--2000
E ALSTOM

Values of the SF6 gas effective pressures (MPa) corrected in accordance with
temperature for an atmospheric pressure of 101.3 kPa :
t_C

pre

pae

pme

t_C

pre

pae

pme

--30
--29
--28
--27
--26
--25
--24
--23
--22
--21
--20
--19
--18
--17
--16
--15
--14
--13
--12
--11
--10
--9
--8
--7
--6
--5
--4
--3
--2
--1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

0,492
0,495
0,498
0,501
0,505
0,508
0,511
0,514
0,517
0,520
0,524
0,527
0,530
0,533
0,536
0,539
0,543
0,546
0,549
0,552
0,555
0,558
0,562
0,565
0,568
0,571
0,574
0,577
0,580
0,584
0,587
0,590
0,593
0,596
0,599
0,603
0,606
0,609
0,612
0,615
0,618
0,622
0,625
0,628
0,631
0,634

0,409
0,412
0,415
0,417
0,420
0,422
0,425
0,428
0,430
0,433
0,435
0,438
0,441
0,443
0,446
0,449
0,451
0,454
0,456
0,459
0,462
0,464
0,467
0,469
0,472
0,475
0,477
0,480
0,483
0,485
0,488
0,490
0,493
0,496
0,498
0,501
0,503
0,506
0,509
0,511
0,514
0,516
0,519
0,522
0,524
0,527

0,387
0,389
0,391
0,394
0,396
0,399
0,401
0,404
0,406
0,409
0,411
0,414
0,416
0,419
0,421
0,424
0,426
0,429
0,431
0,433
0,436
0,438
0,441
0,443
0,446
0,448
0,451
0,453
0,456
0,458
0,461
0,463
0,466
0,468
0,470
0,473
0,475
0,478
0,480
0,483
0,485
0,488
0,490
0,493
0,495
0,498

16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

0,637
0,641
0,644
0,647
0,65
0,653
0,656
0,659
0,663
0,666
0,669
0,672
0,675
0,678
0,682
0,685
0,688
0,691
0,694
0,697
0,701
0,704
0,707
0,710
0,713
0,716
0,720
0,723
0,726
0,729
0,732
0,735
0,738
0,742
0,745
0,748
0,751
0,754
0,757
0,761
0,764
0,767
0,770
0,773
0,776

0,530
0,532
0,535
0,537
0,54
0,543
0,545
0,548
0,550
0,553
0,556
0,558
0,561
0,564
0,566
0,569
0,571
0,574
0,577
0,579
0,582
0,584
0,587
0,590
0,592
0,595
0,597
0,600
0,603
0,605
0,608
0,611
0,613
0,616
0,618
0,621
0,624
0,626
0,629
0,631
0,634
0,637
0,639
0,642
0,645

0,500
0,503
0,505
0,508
0,51
0,512
0,515
0,517
0,520
0,522
0,525
0,527
0,530
0,532
0,535
0,537
0,540
0,542
0,545
0,547
0,550
0,552
0,554
0,557
0,559
0,562
0,564
0,567
0,569
0,572
0,574
0,577
0,579
0,582
0,584
0,587
0,589
0,591
0,594
0,596
0,599
0,601
0,604
0,606
0,609

L31--901EN/02
5/6

Installation

Calculation of the SF6 gas filling pressure


for using the pressure gauge (tool)
This page is intentionally blank.

08--2000
E ALSTOM

L31--901EN/02
6/6

Installation

Filling with SF6 gas

Presentation

Warning

DUE TO RISK OF DAMAGE TO CERAMIC ENVELOPES DURING


TRANSPORTATION, PEOPLE PRESENT AT THE GAS FILLING OPERATION SHOULD SHELTER THEMSELVES OR STAY AT A MINIMUM
PROTECTION DISTANCE (ABOUT 50 m).

Necessary equipment List of the necessary ALSTOM equipment and tools for the filling with SF6
and tools
gas :
Mark

Diagram

Designation

Number

Filling tool

Pressure reducer

SF6 gas bottle(s)

14

Gauge 0--1 MPa

* depending on the apparatus.

In this module

This module contains the following topics :


Topic
Filling with SF6 gas
Confirm the pressure
Checking pressure
Checking gas--tightness
Moisture content of SF6 gas in circuit--breaker

07--2002
E ALSTOM

Page
2
3
4
6
7

L32--007EN/01
1/8

Installation

Filling with SF6 gas

Filling with SF6 gas


Filling pressure
calculation

Calculate the SF6 gas filling pressure in accordance with the temperature and
the local atmospheric pressure.
Filling is carried out to calculated pressure plus 0.01 MPa.

See the module SF6 gas monitoring (Calculation of the filling pressure at
site).

Process

The table below gives the steps of the filling with SF6 gas operation :
7
11
Open

SF6

Step
1

2
3

07--2002
E ALSTOM

Closed

Action
Comment
Open the SF6 gas bottle tap (7) Close the tap (7) from time to
and adjust gas output by acting on time to check pressure on the
the cock (9) of the pressure reduc- gauge (11).
er (reduced flow rate).
Start filling again until the required pressure is reached.
Close in this order : the tap (7),
then the cock (9).

L32--007EN/01
2/8

Installation

Filling with SF6 gas

Confirm the pressure

Process

The table below gives the confirmation operation steps of the filling pressure
with SF6 gas :
Step
1

Action
Disconnect the tube (10) -- of the
pressure reducer -- from the filling
tool (2).
NOTE : Keep the unconnected
end of the tube (10) higher
than the other end, to stop the
SF6 gas which it contains from
escaping and to prevent moisture entering.

Comment/Diagram

2
10

S Connect the tube (15) -- of the


gauge 0--1 MPa (14) -- to the filling
tool (2).
S When the required pressure is
confirmed, remove the gauge (14)
and and store it away from humidity.

15
14

Remove the filling tool (2) and refit


the plug (17) (4 daN.m)
17

07--2002
E ALSTOM

L32--007EN/01
3/8

Installation

Filling with SF6 gas

Checking pressure

Principle

Having allowed the temperature to remain steady for at least 12 hours after
filling, it is necessary to check and definitively adjust the pressure to its corrected value -- defined according to both ambient temperature and atmospheric pressure.

Preparation

The table below gives the preparation steps before checking pressure :
Step
1

Action
S Remove the plug (17) and
install the filling tool (2).
S Unscrew the valve--cap (3).

Diagram

17

S Connect the tube (15) -- of the


gauge 0--1 MPa (14) -- to the filling
tool (2).
2

15
14

Continued on next page.

07--2002
E ALSTOM

L32--007EN/01
4/8

Installation

Filling with SF6 gas

Checking pressure, continued

Decision table

The table below gives the process depending the pressure measured :

14
16

If the pressure measured is ...


correct
too high

too low

End of control

Action
End of control
Adjust the pressure by means of valve
(16) on the gauge (14) to reach the required corrected pressure.
Top--up with SF6 gas
If the pressure
Action
adjustment
is ...
0.05 MPa
End of control
> 0.05 MPa
Proceed to a
new inspection
after a stabilization period of
2--3 hours.

The table below gives the end steps of the checking pressure :
Step
1

Disconnect
0--1 MPa.

Action
the gauge

Diagram
(14)
14

S Remove the filling tool (2) and


re--install the plug (17), applying
a tightening torque of 4 daN.m;
leak--tightness is only guaranteed
if this condition is respected.
S Screw the valve--cap (3) on
the filling tool (2).

17
2
3

07--2002
E ALSTOM

L32--007EN/01
5/8

Installation

Filling with SF6 gas

Checking gas-- tightness

Necessary ALSTOM
tools

List of the ALSTOM tools necessary for the tightness inspection :


Mark

12

Process

Diagram

Designation

Number

Leak detector (optional)

Make sure that the plug (17) is perfectly leak--tight using the leak detector
(12).

12
17

07--2002
E ALSTOM

L32--007EN/01
6/8

Installation

Filling with SF6 gas

Moisture content of SF6 gas in circuit-- breaker


Principle

07--2002
E ALSTOM

This measurement is not required, the equipment being provided with molecular sieves in sufficient quantity to give a dew point of 0C (32F) for an ambient temperature of 20C (68F), this applies for a unit filled to its nominal
pressure for 2 or 3 months.

L32--007EN/01
7/8

Installation

Filling with SF6 gas


This page is intentionally blank.

07--2002
E ALSTOM

L32--007EN/01
8/8

Commissioning

Pre--commissioning inspections
Presentation
Introduction

After installation of the bay, completion of all earth circuit and electrical connections, it is necessary to perform certain pre--commissioning inspections.
These inspections should be performed with the apparatus ready to be commissioned (energized), in other words
D LV electrical circuits conforming, in voltage and type, with the low--voltage
diagrams and rating plate of the apparatus.
D SF6 envelopes at rated SF6 pressure.
NOTE : Rated pressure, pressure of equipment after SF6 gas filling.
D Flexible connections linking circuit--breaker to busbar installed.

Caution

DURING OPERATIONS REQUIRED AS PART OF INSPECTION PROGRAMME PRIOR TO COMMISSIONING, ALL POSSIBLE SAFETY PRECAUTIONS SHOULD BE TAKEN TO PROTECT PERSONNEL WORKING ON THE EQUIPMENT.

In this module

This module contains the following checking inspections :


Inspections
SF6 gas
Operating device
Test operations
Information concerning the stop ring of the fusible pin
Removing the stop ring site

04--2004
E ALSTOM

Page
2
3
4
5
6

L34--004EN/04
1/6

Commissioning

Pre--commissioning inspections
SF6 gas
Reminder

SF6 envelopes are at rated pressure following the SF6 gas filling operation.

Parameters

Take note of parameters below :


D site altitude, in meters,
D atmospheric pressure of site in kPa,
D site temperature in C.

Checking SF6 gas

SF6 pressure values must obligatorily be read on the pressure inspection


gauge (tooling). Pay no attention to indications given by the dial
densimeter on the filling control block (where applicable) ; it is not accurate
enough for this inspection.
See the module Calculation of the SF6 gas filling pressure to using the
pressure gauge (tool).
The table below gives the steps of checking :
Step
1
2

Action
Comment
Measure SF6 gas pressure by Follow the instructions given in
means of the pressure inspection module Filling with SF6 gas.
gauge (tooling)
Correct pressure found.
Follow the instructions given in
module Calculation of the SF6
gas filling pressure to using the
pressure gauge (tool).

SF6 gas
humidity level

The SF6 humidity level need not be known as the equipment is fitted with molecular sieves in sufficient numbers to give a dew point lower than, or equal
to, 0C at an ambient temperature of 20C, for an apparatus filled to its rated
pressure for 2 or 3 months.

Checking tightness
of assemblages
under SF6 pressure

Each on site assemblage of parts subjected to SF6 gas requires seals. The
quality of these assemblages must be checked.
This inspection should be undertaken once all the filling and pressure control
operations are finished.
Execute this checking according to instructions given in module SF6 gas
monitoring.

04--2004
E ALSTOM

L34--004EN/04
2/6

Commissioning

Pre--commissioning inspections
Operating device
Measurements

Note the supply voltage of motors on the operating mechanism terminals.

Inspection

Check that the following items are working correctly :


-- heating,
-- connections on terminals (no excessive tightening).

04--2004
E ALSTOM

L34--004EN/04
3/6

Commissioning

Pre--commissioning inspections
Test operations
Test operations

D The connection of auxiliary circuits is sufficiently advanced to allow remote


controls to be used.
D Perform 5 CLOSING -- OPENING cycles electrically, by remote control.
OPERATION AUTHORIZED ONLY IF THE SF6 PRESSURE GAS IS
GREATER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.

Caution

DUE TO RISK OF DAMAGE TO CERAMIC ENVELOPES DURING TRANSPORTATION, PEOPLE PRESENT AT THE TEST OPERATIONS SHOULD
SHELTER THEMSELVES OR STAY AT A MINIMUM PROTECTION DISTANCE (ABOUT 50 m).

VERY IMPORTANT

AFTER THE FIRST TEST OPERATION, IT IS FORBIDDEN TO REMOVE


THE OPERATING MECHANISM WITHOUT USING THE BLOCKING
TOOL (4).
NOTE : To remove the operating mechanism, see in Maintenance,
the module Replacing the operating device FK3--1.

04--2004
E ALSTOM

L34--004EN/04
4/6

Commissioning

Pre--commissioning inspections
Information concerning the stop ring of the fusible pin
Process

The table below indicates the procedure -- after the first operation of the circuit
breaker -- according to the type of stop ring :
Case

Stop ring type

Direction

None

None

None

See : Removing the


stop ring site

04--2004
E ALSTOM

L34--004EN/04
5/6

Commissioning

Pre--commissioning inspections
Removing the stop ring site
Process

The table below gives the steps of removing the stop ring site
Step
1

Action
Switch--off the supply circuit of
the reloading motor.

Activate the closing handle and


the opening handle like below :
1 -- Close
2 -- Open

Comment / Diagram

Open

Check that the operating


mechanisms optical signalization shows the symbols opposite :
Closing spring
Released

04--2004
E ALSTOM

Remove the stop ring site and


the broken part of the fusible
pin.

Switch--on the motor supply The motor starts--up and reloads


circuit.
the closing spring.

L34--004EN/04
6/6

Maintenance

Maintenance plan
Presentation
Introduction

GL circuit--breakers use pure SF6 gas as an arc quenching medium (or a


SF6+CF4 gas mixture) and require only a reduced amount of maintenance.

In this module

This module contains the following topics :


Topic
Maintenance plan
Maintenance operations
Detail of maintenance operations

06--2004
E ALSTOM

Page
2
3
4

L51--003EN/03
1/6

Maintenance

Maintenance plan
Maintenance plan
Maintenance
frequency

Under normal operating conditions, the maintenance plan may be defined as


follows :
Type of
examination

06--2004
E ALSTOM

Frequency

Maintenance
visits

Once or twice a year

Inspections

Every five years

Overhaul

Perform when one of the


following criteria is reached :
D operating
life
time
20 years
D number of mechanical
cycles 3,000
D electric wear limit

Comment
It is advisable to perform at
least 2 CO duty cycles per
year, when apparatus are
scarcely used, in order to
check
that
the
circuit--breaker
and
associated control circuits
are working properly.
This
necessitates
circuit--breaker shutdown. It
is not necessary, however to
dismantle
interrupting
chambers
and
other
sub--assemblies.
However, it is recommended
to proceed with inspection of
the pole or circuit--breaker
used the most, then to adapt
the maintenance programme
for the other breakers
depending on the results
observed.

L51--003EN/03
2/6

Maintenance

Maintenance plan
Maintenance operations
Guide

The table below is a guide of the operations to be carried out at each


maintenance stage :
MAINTENANCE VISITS (1 or 2 times a year)
INSPECTION (every 5 years)
OVERHAUL (OPERATING TIME : 20 years)
OVERHAUL (MECHANICAL OPERATIONS : 3 000 cycles)
OVERHAUL (ELECTRICAL WEAR : see Electrical wear
limits)

J J J J J Operation counter reading.


Overall inspection : appearance (corrosion, paintwork,
signs of overheating).
Check operation of permanent heating. Check condition
J J J J
of air vents.
If the circuit--breaker is fitted with an SF6 dial densimeter
or a pressure gauge, check SF6 pressure (or SF6+CF4
J J
gas mixture).
It is advisable to perform at least 2 CO duty cycles per
year, when apparatus are scarcely used, in order to
check that circuit--breaker and associated control circuits
are working properly.
Check SF6 densimeter thresholds. Then adjust pressure
J J
to its rated value.
Check tightening of parts not subjected to pressure
J J J
(frame -- deck -- cubicle).
Check tightening of low voltage terminals (* 6 months
J J J
after commissioning).
Check relay operation.
J J J
Change door seal, side panels seal and roof seal.
J

J J J
J
J

J J J J Measure operating times for poles and auxiliary contacts.


Carry out operations at recommended duties and rated
voltage.
J J Change (or recondition) interrupting chambers.

J J J J

06--2004
E ALSTOM

L51--003EN/03
3/6

Maintenance

Maintenance plan
Detail of maintenance operations
Caution

DURING MAINTENANCE OPERATIONS ALL POSSIBLE SAFETY


PRECAUTIONS SHOULD BE TAKEN TO PROTECT PERSONNEL
WORKING ON THE EQUIPMENT.

General condition
of the apparatus

The apparatus should be subjected to visual inspection. If patches of


corrosion are found begin reconditioning of the affected parts.
The table below gives the process respecting surface finish and protection :
Support

Inspection

Galvanized
steel

Oxidized parts

Light scratches
Painted
galvanized
steel
or
painted
aluminium
alloy

Deep scratches
or flaking

Action
D Thorough brushing of oxidized
parts.
D Degreasing with solvent.
D Application of a coat of zinc
paint.
D Thorough degreasing with
solvent.
D Application of a coat of lacquer
using a brush.
D Scouring of paint surface with
emery paper 400.
D Thorough degreasing with
solvent.
D Application of a coat of primer,
then drying for 24 h.
D Application of a coat of
polyurethane lacquer using a
brush.

Products used :
D RUMCOAT EEVA primer by DERIVERY ref. 333103.
D Polyurethane lacquer 780 by DERIVERY, ref. depending on color of
equipment.
Continued on next page.

06--2004
E ALSTOM

L51--003EN/03
4/6

Maintenance

Maintenance plan
Detail of maintenance operations, continued
SF6 pressure gas

For a circuit--breaker equipped with a dial--type SF6 gas densimeter, check


the position of the needle.
Needle position

Colored area

Direction

GREEN

None

YELLOW

Perform a topping--up
operation.

RED

Abnormally low density,


find the origin of the
leak and contact
ALSTOM T&D S.A.
After--sales Service.

NOTE : If the intersection is in either the yellow or red zone, without


any particular indication from the electrical contact densimeter, verify
the concordance of different information sources to find the defective
element and then replace it.

Operating device

Air--vents should be clean, free of dust and unobstructed. If necessary clean


using a solvent.
Make sure that the permanent resistors are working properly by checking that
these give off heat and that there are no overheating marks (a zone notorious
for this).
For thermally controlled resistors, check that energizing and de--energizing
takes place correctly at voltage supply terminals by means of a thermostat
(recommended thermostat temperature : +5C).
If necessary, change resistors found to be defective.

Operation counter

Read indications given by the counter(s) and note these on the inspection
sheet Maintenance visits.
The number of circuit--breaker operations recorded influences future
maintenance operations.
Continued on next page.

06--2004
E ALSTOM

L51--003EN/03
5/6

Maintenance

Maintenance plan
Detail of maintenance operations, continued
Electrical densimeter
thresholds

Check the electrical contact SF6 densimeter thresholds.


If the values found are outside required tolerances replace the densimeter.

Tightening of
mountings

Check and adjust, with a torque wrench, the tightening torques of screws on
sub--assemblies not subjected to gas pressure. The tightening torques are
given in paragraph Tightening torques.

Relay operation

Check relay operation by executing the following circuit--breaker sequences :


-- closing lock--out,
-- automatic opening,
-- anti--pumping.

Tightening
LV terminals

With the electric cubicle out of service, check that the connectors and tips of
conductors are tightened correctly and check the torque of connection
mountings.
Tool used : 4 mm diameter screw driver , for terminals of the Entrelec type
(for example).
CAUTION :
SCREWS
OVER--TIGHTENED.

ON

TERMINALS

MUST

NOT

BE

Insulating envelopes

Check the condition of insulating envelopes, these should be free from impact
marks, splintering, cracks, dust deposits, pollution etc...
If necessary, clean these using a dry rag.
If anomalies are found contact :
ALSTOM T&D SA, After--sales Service in order to change the defective parts.

Interrupting
chambers

Check the condition of interrupting chambers. This operation necessitates


complete dismantling of the interrupting chamber to gain access to the
elements to be inspected and should obligatorily be performed by ALSTOM
T&D SA, After--sales Service -- to be contacted before all operations of this
kind, preferably at the maintenance planning stage.

06--2004
E ALSTOM

L51--003EN/03
6/6

Maintenance

Electrical wear limits


Electrical wear limits
Estimation

Electrical wear can be determined by means of the curve below. This


curve corresponds with the formula :
NI2 = 16,000 kA2 (*)
N = number of interruptions on value I.
Example : it is possible to perform 40 interruptions on a current of 20 kA.
(*) Normal guarantee. In certain special operation conditions, other values
may be guaranteed.

Diagram

I (kA)

40
20
10

10

20 30

50

100

500

1000

3000

Number of interruptions

11--1999
E ALSTOM

L51--051EN/01
1/2

Maintenance

Electrical wear limits


This page is intentionally blank.

11--1999
E ALSTOM

L51--051EN/01
2/2

Maintenance

Electrical contact densimeter threshold inspection

Presentation

Necessary tools

List of the ALSTOM tools necessary for the operation :


Mark

Diagram

Designation

Reference

Number

(11)

Gauge 0--1 MPa

--02842117
+
N55161602

(17)

Pressure reducer

--02557208
+
N55161601

Test lamp

--02861501

Electrical contact densimeter threshold inspection


V0003731001
case

In this module

This module contains the following topics :


Topic
Contents of the densimeter threshold inspection case
Preparing the densimeter
Linking the densimeter on the control tool
Densimeter threshold inspection
Replacing the densimeter
Putting away the control tool

06--2003
E ALSTOM

Page
2
3
4
5
7
8

L51--107EN/01
1/8

Maintenance

Electrical contact densimeter threshold inspection

Contents of the densimeter threshold inspection case

Parts table

The table below describes the parts of the densimeter threshold inspection
case :
Mark
(3)

Component
Case

(4)

Threshold inspection tank

(5)

Connection valve block

(6)

Linking pipe

(7)

Set of seals

Information
Put the tool
Connection : densimeter -- standard gauge -- SF6 gas bottle.
Supports the densimeter during
the threshold inspection.
Connection : connection valve
block -- threshold inspection tank.
Seals used for the connection
valve block and replacing the
densimeters of the three poles.

4
6

06--2003
E ALSTOM

L51--107EN/01
2/8

Maintenance

Electrical contact densimeter threshold inspection

Preparing the densimeter

Introduction

The densimeter is located at the base of the pole of the circuit--breaker, and
is joined to the SF6 (or SF6+CF4) gas volume of the circuit--breaker.
To realize the electrical contact densimeter threshold inspection, it is imperative to isolate the densimeter volume from the pole SF6 (or SF6+CF4) gas volume.

Process

The table below gives the process to preparing the densimeter :


Step
1

Action
Remove the densimeter
(1), held in place by screws
(8), on the housing cover (2)
of the circuit--breaker.

Remove the protective


plates (9) and (10), of the
connection valve block (5),
held in place by screws (14)
and (15).

Diagram

x3
8
H M6--20
0,7 daN.m

x3

5
14

x3
H M6--20
0,7 daN.m

15
H M6--20
0,7 daN.m

10
3

Install the seal (16) on the


connection valve block (5).

16
5

06--2003
E ALSTOM

Install the connection valve


block (5) on the housing
cover (2), of the circuit-breaker, using screws (8).
Install the densimeter (1) on
the connection valve block
(5) using screws (15).
NOTE : Before installing,
check the presence of
seals on the densimeter.

x3
x3

8
H M6--20

15
1

H M6--20

L51--107EN/01
3/8

Maintenance

Electrical contact densimeter threshold inspection

Linking the densimeter on the control tool

Process

The table below gives the process to link the densimeter on the control
tool :
Step
1
2
3
4

Action
Check that the REGULATION knurl knob (20) of the threshold
inspection tank (4) is in valve closed position (unscrewed).
Connect the pipe (12) of the gauge (11) on the PRESSURE
GAUGE valve of the threshold inspection tank (4).
Connect the supplied pipe (6) on the DENSIMETER valve of the
threshold inspection tank (4).
Briefly open the SF6 gas bottle tap (21) and the cock (22) of the pressure reducer to eliminate any air inside the pipe (23) (approx. 20 s
at low flow--rate).
Connect the pipe (23) on the SUPPLY valve of the threshold inspection tank (4).
Briefly open the SF6 gas bottle tap (21) and the cock (22) of the pressure reducer to eliminate any air inside the pipe (6) (approx. 20 s at
low flow--rate).
NOTE : Keep the end of the tube (6) in high position to keep
the SF6 gas which it contains and to prevent damp air from
entering.
Connect the pipe (6) on the valve (24) of the connection valve block
(5).
12
20

11

20

OPEN

CLOSE

(leak)

21
23

24
6

SF6
22
6

06--2003
E ALSTOM

L51--107EN/01
4/8

Maintenance

Electrical contact densimeter threshold inspection

Densimeter threshold inspection

SF6 gas pressure


adjustment

The table below gives the steps of SF6 gas pressure adjustment of the connection valve block (5) :
Step
1

2
3

Action
Open the SF6 gas bottle tap (21)
and adjust gas output by acting on
the cock (22) of the pressure reducer (reduced flow rate).
Close the tap (21) from time to
time to check pressure on the gauge (11).

Comment

See the module Calculation


of the SF6 gas filling pressure to using the pressure
gauge (tool).

Start filling again until the required


pressure is reached.
Close in this order : the tap (21),
then the cock (22).
5

11

21

Open

SF6

22

Closed

Continued on next page.

06--2003
E ALSTOM

L51--107EN/01
5/8

Maintenance

Electrical contact densimeter threshold inspection

Densimeter threshold inspection, continued

Testing

The table below gives the steps of densimeter testing :


Step
1

Action
Connect a test lamp to the
Alarm pressure for the insulation pae densimeter threshold.
Calculate the effective pressure at which the Alarm pressure for the insulation pae contact switches over -- corrected
in keeping with temperature
and local atmospheric pressure.
D Create a leak by screwing
the REGULATION knurl knob
(20) of the threshold inspection
assembly (4), making sure that
the contact switches over at
the previously calculated value.
D Proceed in the same way to
check the contact of Minimal
pressure for the insulation
pme.

Comment/Diagram
Connection to the terminal block of
the operating mechanism in accordance with the electrical diagram.
Value pae : see technical characteristics).
See the module Calculation of
the SF6 gas filling pressure to
using the pressure gauge (tool).

20
4
20

OPEN

CLOSE

(leak)

If one of the thresholds does not


comply with the specified value, replace the densimeter.

06--2003
E ALSTOM

L51--107EN/01
6/8

Maintenance

Electrical contact densimeter threshold inspection

Replacing the densimeter

Process

The table below gives the process to replace the densimeter :


Step
1

Action
Disconnect the pipe (6)
from the valve (24) of the
connection valve block (5).
Screw the valve--cap (25)
on the valve (24).
NOTE : Keep the end of
the tube (6) in high position to keep the SF6 gas
which it contains and to
prevent damp air from
entering.
Remove the densimeter
(1), held in place by screws
(15), on the connection
valve block (5).

Diagram
24

6
25
5

5
1

x3
15
H M6--20

Remove the connection


valve block (5), held in place
by screws (8), on the housing cover (2) of the circuit-breaker.
NOTE : If the connection
valve block (5) is any
more used, see the next
paragraph Putting away
the control tool.
Install new seals (26) and
(27) on the densimeter (1),
referring to Preparing and
installing static seals in
Erection general procedures.
Install the densimeter (1) on
the housing cover (2), of the
circuit--breaker,
using
screws (8).

x3

8
H M6--20

2
27
26
1

06--2003
E ALSTOM

x3
8
H M6--20
0,7 daN.m

L51--107EN/01
7/8

Maintenance

Electrical contact densimeter threshold inspection

Putting away the control tool

Process

The table below gives the steps of putting away the control tool :
Step
1

Action
Take precautions to remove
the seal (16) from the connection valve block (5) and
put it away into the SET OF
SEALS box of the densimeter threshold inspection
case.
Install the protective plates
(9) and (10) on the connection valve block (5), using
screws (14) and (15).
Put away the connection
valve block (5) into the
densimeter
threshold
inspection case.

Diagram
16
5

x3

9
5

14

x3
H M6--20
0,7 daN.m

15
H M6--20
0,7 daN.m

10
3

Disconnect the pipe (6)


from the DENSIMETER
valve of the threshold
inspection tank (4) and put
it away into the densimeter
threshold inspection case.

4
4

Disconnect the pipe (12)


from the the PRESSURE
GAUGE valve of the
threshold inspection tank
(4).

11

12

4
5

Disconnect the pipe (23)


from the SUPPLY valve of
the threshold inspection
tank (4).
Put away the threshold
inspection tank (4) into the
densimeter
threshold
inspection case.

SF6

06--2003
E ALSTOM

23

L51--107EN/01
8/8

Maintenance

Intervention on the operating device


Presentation
Warning

BEFORE ALL INTERVENTION ON THE OPERATING DEVICE, MAKE


SURE THAT THE CIRCUIT--BREAKER IS OPEN AND ITS POSITION INDICATOR IS IN THE POSITION BELOW.

Circuit--breaker
Open

Closing spring
Released

NEVER WORK THE OPERATING DEVICE WHEN THIS IS NOT COUPLED


TO THE CIRCUIT--BREAKER.

In this module

This module contains the following topics :


Topic
Positions of optical signalization
Safety measures
Preparing the operating device
Replacing an opening or closing electro--magnet
Resumption of service
Lubrication
Cleaning the windows

10--1999
E ALSTOM

Page
2
3
4
5
6
8
9

L51--302EN/01
1/10

Maintenance

Intervention on the operating device


Positions of optical signalization
A position
Circuit-breaker
Open

Closing spring
Loaded

Circuit-breaker
Closed

Closing spring
Released

Circuit-breaker
Closed

Closing spring
Loaded

Circuit-breaker
Open

Closing spring
Released

B position

C position

D position

10--1999
E ALSTOM

L51--302EN/01
2/10

Maintenance

Intervention on the operating device


Safety measures
Circuit--breaker
general preparing

The table below gives the steps to prepare the circuit--breaker to work safely :
Step
1

Action
Comment
Isolate the circuit--breaker from Shut down the circuit--breaker,
the network.
de--energize and earth it.
Switch--off the supply circuit of
the reloading motor.
Check the SF6 pressure gas. Make sure that the SF6 pressure
gas is pme.
Below this level, no mechanical
operating is allowed.

2
3

Release the springs

The table below gives the procedure to release the closing spring and the
opening spring depending the circuit--breaker state :
If the circuit--breaker
position is ...

Closed

Open

Check the optical


signalization

10--1999

In the operating device, activate the


opening handle and the closing handle like below :
1 -- Open
2 -- Close
3 -- Open
Activate the closing handle and the
opening handle like below :
1 -- Close
2 -- Open

Check that the operating mechanisms optical signalization shows the symbols below :

Circuit-breaker
Open

E ALSTOM

Action

Closing spring
Released

L51--302EN/01
3/10

Maintenance

Intervention on the operating device


Preparing the operating device
Introduction

In order to perform certain maintenance operations inside the operating device it is necessary to remove some cabinet parts.

Removing
side panels

The table below gives the steps of side panels removing :


Step
1

Action
Remove the nuts (2) from
the left side panel (3).

Diagram

x2
2
NYLSTOP
M8

Removing the
roof plate

Take hold of the left side


panel (3) from underneath,
pull slightly towards the outside, then downwards to remove it.

Proceed in the same way


for the right side panel.

Take the roof plate (4) from the operating device by removing the nuts (8).
NOTE : The spacers (7), washers (6) and screws (5) stay on the roof
plate.

x4
5
4

6
7
8
H M6--60
0,7 daN.m

10--1999
E ALSTOM

L51--302EN/01
4/10

Maintenance

Intervention on the operating device


Replacing an opening or closing electro-- magnet
Process

10--1999
E ALSTOM

The table below gives the steps of replacing an opening or closing electro-magnet :
Step
1

Action
Disconnect the supply wires from
the coil (9).

Diagram

Extract the blade spring (10) by


pressing outwards on the rivet with
a finger.

Remove the core (11).

10

Remove the faulty coil and replace


it by a new one carrying the same
reference.

11

Reinstall the core (11).

Reinstall the blade spring (10).

Connect supply wires to the new


coil (9).

10

L51--302EN/01
5/10

Maintenance

Intervention on the operating device


Resumption of service
Installing the roof

Install the roof plate (4) of the operating device (1) using the screws (5), washers (6), spacers (7) and nuts (8).

x4
5
4

6
7
8

H M6--60
0,7 daN.m

Installing the side


panels

Insert the side panel (3) under the edge of the roof plate (4). Press it down to
insert the mounting screws and fasten using new nuts (2).
4
3
2

x2

NYLSTOP
M8
Continued on next page.

10--1999
E ALSTOM

L51--302EN/01
6/10

Maintenance

Intervention on the operating device


Resumption of service, continued
Energizing

The table below gives the resumption of service steps of the circuit--breaker
pole :
Step
1
2

Check the optical


signalization

Action
Comment
Re--energize the closing and
opening circuits.
Switch--on the motor supply cir- The motor starts--up and recuit.
loads the closing spring.

Check that the operating mechanisms optical signalization shows the symbols below :

Circuit-breaker
Open

Conclusion

10--1999
E ALSTOM

Closing spring
Loaded

The circuit--breaker is ready for normal use.

L51--302EN/01
7/10

Maintenance

Intervention on the operating device


Lubrication
Principle

No future lubrication will be necessary. The bearings and rollers have been
lubricated in our workshops with special grease :
ASEOL SYLITEA 4--018
This grease can easily endure very low temperatures and has an excellent
resistance to ageing. So that its qualities are not modified during use, it is prohibited to :
D Mix this grease with any other lubricant.
D Lubricate later with any other oil.
D Spray parts of the apparatus with a protective liquid against corrosion or
with any kind of lubricating oil.
Mixture with other lubricants can cause the layer of grease to become too
hard.

10--1999
E ALSTOM

L51--302EN/01
8/10

Maintenance

Intervention on the operating device


Cleaning the windows
Recommended
product

To clean the windows, use exclusively soapy water.

DO NOT USE SCOURING PAD.

10--1999
E ALSTOM

L51--302EN/01
9/10

Maintenance

Intervention on the operating device


This page is intentionally blank.

10--1999
E ALSTOM

L51--302EN/01
10/10

Maintenance

Replacing the operating device FK3--1


Presentation
Warning

BEFORE ALL INTERVENTION ON THE OPERATING DEVICE, MAKE


SURE THAT THE CIRCUIT--BREAKER IS OPEN AND ITS POSITION INDICATOR IS IN THE POSITION BELOW.

Circuit--breaker
Open

Closing spring
Released

Lifting equipment

Provide an appropriate lifting equipment (130 daN).

Necessary tools

List of the ALSTOM tools necessary for removing the operating device :
Mark

Replacing steps

Designation

Number

(1)

Lifting strap

(4)

BLOCKING TOOL

Replacing the operating device must be done in several steps :


Step
A
B
C
D
E
F
G
H

04--2004
E ALSTOM

Diagram

Topic
Safety measures
Deflating the pole
Holding of the coupling cylinder
Preparing the operating device
Disconnecting the low voltage cables
Removing the operating device
Installing the new operating device
Reinflating the pole

Page
2
4
5
7
8
9
11
12

L51--800EN/04
1/12

Maintenance

Replacing the operating device FK3--1


Safety measures
Circuit--breaker
general preparing

The table below gives the steps to prepare the circuit--breaker to work safely :
Step
1

Action
Comment
Isolate the circuit--breaker from Shut down the circuit--breaker,
the network.
de--energize and earth it.
Switch--off the supply circuit of
the reloading motor.
Check the SF6 pressure gas. Make sure that the SF6 pressure
gas is pme (P2).
Below this level, no mechanical
operating is allowed.

2
3

Release the springs

The table below gives the procedure to release the closing spring and the
opening spring depending the circuit--breaker state :
NOTE : For the manual discharge of closing spring, see in annexes,
the module Manual operations 48.020.181E.

If the circuit--breaker
position is ...

Closed

Open

Action
In the operating device, activate the
opening handle and the closing handle like below :
1 -- Open
2 -- Close
3 -- Open
Activate the closing handle and the
opening handle like below :
1 -- Close
2 -- Open

Continued on next page.

04--2004
E ALSTOM

L51--800EN/04
2/12

Maintenance

Replacing the operating device FK3--1


Safety measures, continued
Check the optical
signalization

Check that the operating devices optical signalization shows the symbols below :

Circuit--breaker
Open

04--2004
E ALSTOM

Closing spring
Released

L51--800EN/04
3/12

Maintenance

Replacing the operating device FK3--1


Deflating the pole
Process

Deflate the pole, using gas recovery chart.


DEFLATE THE CIRCUIT--BREAKER SF6 PRESSURE GAS TO 0.3 bar AT
20C (1,013 hPa) REFERRING TO THE MODULE IN ANNEXES Instructions on the handling of used SF6 gas and decomposition products.

04--2004
E ALSTOM

L51--800EN/04
4/12

Maintenance

Replacing the operating device FK3--1


Holding of the coupling cylinder
Optical signalizations Check the position of operating device optical signalization :

Circuit--breaker
Open

Stop ring

Closing spring
Released

If the pole is equipped with a stop ring (5) of the fusible pin (9), release the
screw (6) and move the stop ring (5) in order to reach the positioning hole of
the blocking tool (4).
NOTE : Two possible cases (A or B).
9

4
9

6
Continued on next page.

04--2004
E ALSTOM

L51--800EN/04
5/12

Maintenance

Replacing the operating device FK3--1


Holding of the coupling cylinder
Blocking tool

Screw the blocking tool (4) into the free hole allowed on the cylinder (12).
This blocking tool is removed once removing and coupling of the operating device is finished.

12

04--2004
E ALSTOM

L51--800EN/04
6/12

Maintenance

Replacing the operating device FK3--1


Preparing the operating device
Side panel

The table below gives the steps of side panel removing :


Step
1

Action
Remove the nuts (2) from
the left side panel (3).

Diagram

x2
2
NYLSTOP
M8

04--2004
E ALSTOM

Take hold of the left side


panel (3) from underneath,
pull slightly towards the outside, then downwards to remove it.
Proceed in the same way
for the right side panel.

L51--800EN/04
7/12

Maintenance

Replacing the operating device FK3--1


Disconnecting the low voltage cables
Disconnecting the
contact densimeter
cable

Disconnect the wires of the electrical contact SF6 densimeter (18) cable (19)
from the operating device terminal block.

18
19

L.V. cables

04--2004
E ALSTOM

Disconnect all the L.V. cables from the operating device terminal block.

L51--800EN/04
8/12

Maintenance

Replacing the operating device FK3--1


Removing the operating device
Process

The table below gives the steps of removing the operating device :
Step
1

Action
Sling the operating device using a lifting strap (1) like diagram.
NOTE : Do not remove the
roof (17) of the operating
device before slinging.

Diagram
1

17

Remove the nuts (14) and


washers (10).

10

x 4

14
H M16

Remove the operating shaft (7)


from the cylinder (12) and remove the operating device
(20).
7
12

20

Continued on next page.


04--2004
E ALSTOM

L51--800EN/04
9/12

Maintenance

Replacing the operating device FK3--1


Removing the operating device, continued
Process, continued

The table below gives the steps of removing the operating device :
Step
4

Action
Remove the screws (9) and the
washers (10).

Diagram

x 4
10

Insert the side panel (3) under the


edge of the roof plate (4). Press it
down to insert the mounting
screws and fasten using nuts (2).

x2
2
4

NYLSTOP
M8

04--2004
E ALSTOM

L51--800EN/04
10/12

Maintenance

Replacing the operating device FK3--1


Installing the new operating device
Warning

NEVER WORK THE OPERATING DEVICE WHEN THIS IS NOT COUPLED


TO THE CIRCUIT--BREAKER.

Process

To make this operation, refer to the module Installing the operating device .
NOTE : Not to hold account of the fusible pawn (new apparatus)
indicated in the module Installing the operating device. At the time
of the maintenance actions, the function of the fusible pin is fulfilled
by the blocking tool indicated below.

Removing the blocking tool

AFTER THE ASSEMBLY OF THE NEW OPERATING MECHANISM, IT IS


IMPERATIVE TO REMOVE THE BLOCKING TOOL (4) BEFORE THE
FIRST OPERATION OF THE CIRCUIT--BREAKER.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.

4
Stop ring

If the pole is equipped with a stop ring (5) of the fusible pin (9), reposition
the stop ring (5) and hold in place using the screw (6).
NOTE : Stick the screw (6) using LOCTITE 225 and apply a tightening
torque of 17 N.m.
9

04--2004
E ALSTOM

L51--800EN/04
11/12

Maintenance

Replacing the operating device FK3--1


Reinflating the pole
DO NOT SUPPLY THE OPERATING MECHANISM MOTOR WITH CURRENT TO AVOID THE CLOSING SPRING BEING RELOADED.
THE CIRCUIT BREAKER MUST NOT BE OPERATED AT A SF6 PRESSURE GAS LOWER THAN THE MINIMAL PRESSURE FOR THE INSULATION pme.

Process

To make this operation, refer to the modules :


S Calculation of the SF6 gas filling pressure for using the pressure
gauge (tool)
S Filling with SF6 gas

04--2004
E ALSTOM

L51--800EN/04
12/12

Annexes

Tooling and accessories

Presentation

Introduction

Special tooling is necessary for :


H commissioning,
I maintenance of the circuit--breaker.
Only the tools and accessories specified on ordering are delivered. Commercially available tools (e.g. : spanners, torque wrenches, spirit levels...) are not
supplied.

In this module

This module contains the following topics :


Topic
Special tools
Accessories

07--2003
E ALSTOM

Page
2
4

L60--010EN/02
1/6

Annexes

Tooling and accessories

Special tools

Table of special
tools

The table below gives the ALSTOM special tools :


NUMBER

DESIGNATION

USE

D001875..
EMPTY
TRANSPORT
CASE
(OPTIONAL)

Transport of SF6 gas


filling tools and control
tools.

FILLING TOOL

SF6 filling, topping


topping-up.

PRESSURE
GAUGE

SF6 filling, topping-up.


Inspection of
densimeter
thresholds.

N55000401

--02842117
N55161602

HI

465059004
WATER PRESSURE GAUGE
(OPTIONAL) I

Checking for leaks

--02557208
N55161601
PRESSURE
REDUCER

SF6 filling, topping-up.

V0004240001
Blocking tool of the
pole operating shaft
BLOCKING TOOL
for replacing the operating device.

Continued on next page.

07--2003
E ALSTOM

L60--010EN/02
2/6

Annexes

Tooling and accessories

Special tools, continued

Table of special
tools, continued

The table below gives the continuation of ALSTOM special tools :


NUMBER

V0003731001
I

D00220301
H

07--2003
E ALSTOM

DESIGNATION

USE

Electrical contact
Inspection of densidensimeter threshmeter thresholds.
old inspection case

LIFTING STRAP

Handling of the pole


and operating mechanism

D00001901
HI

Checking gas--tightLEAK DETECTOR ness of SF6 filling plug.


SF6 leak detection.

--02861501
I

TEST LAMP

Inspection of densimeter thresholds.


Inspection of interruption contact wear.

D00477401
I

CRANK HANDLE

Spring reloading.

L60--010EN/02
3/6

Annexes

Tooling and accessories

Accessories

Table of accessories

The table below gives the ALSTOM accessories :


NUMBER
--01861432
HI

DESIGNATION

USE

42 kg
SF6 BOTTLE

SF6 filling topping--up.


topping up

SF6 BOTTLE

SF6 filling topping--up.


topping up

SF6 BOTTLE

SF6 filling topping--up.


topping up

SF6 BOTTLE

SF6 filling topping--up.


topping up

--01818336
01818336

LOCTITE 262
(50 ml)

Screw locking.
locking

--01818327
01818327

LOCTITE 225
(250 ml)

Screw sealing.
sealing

--01835265
01835265

MOLYKOTE 111
GREASE

Preparation
seals.

--01835208
01835208

MOBILPLEX47
GREASE

Lubricating screws before tightening to


torques.

--01835106
01835106

VASELINE 204--9
204 9

Preparation of electri
electrical contact surfaces.

--01861435
HI

--01861434
HI

--01861433
HI

20 kg

10 kg

5 kg

of

SF6

Continued on next page.

07--2003
E ALSTOM

L60--010EN/02
4/6

Annexes

Tooling and accessories

Accessories, continued

Table of accessories,
continued

The table below gives the continuation of ALSTOM accessories :


NUMBER

07--2003
E ALSTOM

DESIGNATION

USE

--01835118
01835118

CONTACTAL
GREASE

Preparation of electri
electrical contact surfaces.

--01835251
01835251

ASEOL 0
0--365.2
365.2
GREASE

General lubrication.
lubrication

--01831320

ABRASIVE PAPER
A 400

Preparation of electrical contact surfaces.

--02212334
02212334

RAG

Preparation of electri
electrical contact surfaces.

--02211842
02211842

ROUND BRUSH
No.4

Preparation of electri
electrical contact surfaces.

--02211831
02211831

BRUSH No.16
No 16

Preparation of electri
electrical contact surfaces.

--01861262
01861262

CAN OF
ISOPROPANOL
(1 l)

Preparation
seals.

of

SF6

L60--010EN/02
5/6

Annexes

Tooling and accessories


This page is intentionally blank.

07--2003
E ALSTOM

L60--010EN/02
6/6

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SUMMARY

of PRODUCT SAFETY SHEETS


for equipment * manufactured by
ALSTOM T&D - AHT

SUBJECT

Reference N

Revision

Summary

PS 0000/A

03

Working environment

PS 0001/A

02

Handling Operations

PS 0002/A

02

Pressurized Equipment

PS 0003/A

02

SF6 : Use and Handling.

PS 0004/A

02

Chemicals

PS 0005/A

02

Electrical Equipment

PS 0006/A

02

Machinery

PS 0007/A

03

Operation

PS 0008/A

03

Maintenance

PS 0009/A

03

Remarks

Not applicable to pneumatically


operated circuit breakers

* : excluding lightning arresters.

PS 0000/A

03

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

Ch. MANIN
Signature Approved by

29/08/98

Date

1/1
Signature Page

This page is intentionally blank.

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

WORKING
ENVIRONMENT

CAUSE OR ORIGIN OF HAZARD.


Any negligence as regards site organisation may cause an accident.

WORK REQUIREMENTS.

All remedial action, for all life-cycles of the equipment, must be carried out in a safe working environment.

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

PS 0001/A

02

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

P. VANDAME
Signature Approved by

98-08-28

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

TRANSPORT

INSTALLATION

START-UP

OPERATION

MAINTENANCE

SCRAPPING &
RECYCLING

SAFETY INSTRUCTIONS

PACKING

High voltage switchgear

1 Personnel :
-

Appropriate clothing, gloves, helmet, safety boots,


harness, etc..

The personnel concerned must be familiar with the


basic working regulations governing a given work
station: mechanical, dielectric, pressure hazards, etc..

2 Handling Equipment :
-

This must be in good working order, regularly


maintained, properly adjusted and compliant with the
standards in force in the country of use.

3 Tools in General :
-

Only use tools appropriate to the type of work to be


carried out.

4 Working Area :
-

Make sure the floor is safe (free from oil, blunt


objects, etc.).

The site must be properly demarcated and kept clear.

PS 0001/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-12
Revision date

2/2
Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

HANDLING OPERATIONS

CAUSE OR ORIGIN OF HAZARD.


Any handling operation may involve danger :

- for the personnel,


- for the equipment being handled,
- for the installations or equipment in the vicinity.

WORK REQUIREMENTS.

As a general rule, handling operations must be carried out by personnel familiar with the basic handling
regulations, using equipment in good working order, and wearing the appropriate protective clothing or
equipment.
Ensure that the condition of the cases is such that they can be safely handled (state of the wood, shockresistance, etc.).

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

PS 0002/A

02

G. BERNARD

1998-08-11

Sheet N

Revision

Written by

Date

F. PIRAUD
Signature Approved by

98-09-08

Date

1/3
Signature Page

TRANSMISSION & DISTRIBUTION

SAFETY INSTRUCTIONS

PACKING

TRANSPORT

INSTALLATION

START-UP

OPERATION

MAINTENANCE

SCRAPPING &
RECYCLING

High voltage switchgear

Handling operations must be carried out by personnel


familiar with the basic handling regulations.

Personnel must be qualified to operate lifting equipment,


cranes, overhead conveyors, etc..

Equipment in proper working order :


-

Equipment must be checked and maintained regularly in


accordance with local regulations.

All equipment must be properly housed.

Familiarity with the load to be handled (see details on the


case).
Use of the appropriate handling equipment :
-

Type of sling(s),

Correct slinging methods,

Use of special ALSTOM handling equipment.

Follow the handling instructions on :


- the cases (pictorial symbols: centre of gravity, slinging
points, etc.),
-

the assembly instructions.

Compliance with the relevant work station safety instructions


(proximity of electrical equipment).
Operator Safety :
-

use of gloves, helmets, safety boots, etc.,

loads not to be carried with personnel underneath.

PS 0002/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-11
Revision date

2/3
Page

TRANSMISSION & DISTRIBUTION

SCRAPPING &
RECYCLING

Bring insulating jacket working pressure back to transport


pressure (300 hPa maximum).

Ensure that cases have not been damaged during handling


or prolonged storage.
Follow the stacking instructions.

PS 0002/A
Sheet N

02
Revision

It is essential to open cases from the top and to take care


when unpacking.

1996-03-18
1st issue

OPERATION

Before handling any mechanically operated component,


disable the springs.

Handling of insulating jackets at transport pressure (300 hPa


maximum).

START-UP

INSTALLATION

TRANSPORT

Before handling any hydraulically operated component,


bring oil pressure back to atmospheric pressure.

SAFETY INSTRUCTIONS

PACKING

MAINTENANCE

High voltage switchgear

1998-08-11
Revision date

3/3
Page

This page is intentionally blank.

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

PRESSURIZED EQUIPMENT

CAUSE OR ORIGIN OF HAZARD.


Our equipment includes gas pressure assemblies (SF6, nitrogen, air, etc.) or fluids (oil).

WORK REQUIREMENTS.
Comply with the storage, transport and operating instructions supplied with our equipment.
Before initial filling and pressurizing, check the overall condition of the shielding concerned :
-

no signs of impact, splitting or chipping on the porcelain components, etc.,

no visible damage to hoses and/or rigid pipes (cuts, folds, corrosion, etc.) or to fittings and metal
protection (accumulators, tank, etc.).

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

As a general rule, all work on pressurized equipment must be carried out by qualified personnel.

PS 0003/A

02

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

F. PIRAUD
Signature Approved by

98-09-08

Date

1/3
Signature Page

TRANSMISSION & DISTRIBUTION

INSTALLATION

START-UP

OPERATION

MAINTENANCE

SCRAPPING &
RECYCLING

TRANSPORT

SAFETY INSTRUCTIONS

PACKING

High voltage switchgear

Pressurized Equipment : General.


1.1

Comply with the assembly instructions shown on


both our equipment and the gas bottles.

1.2
1.3

Before starting work on any pressurized piece of


equipment, make sure there is no pressure.

Before any handling, check to see how the


equipment is fixed to its frame and how the frame is
itself anchored.

1.4

High-pressure pipes must be fixed or otherwise


made safe.

1.5

Before initial pressurization, check that all circuits


are properly sealed.

1.6

Never tighten a pressure fitting.

1.7

Ensure that for every bolted connection for a volume


under pressure there is an appropriate and properly
fastened bolt at each relevant point.

It is strictly forbidden to lift or otherwise move a


piece of equipment inflated to a pressure in excess
of 300 hPa of gas.

Before giving any orders to move equipment, check


visually or by ear that all the relevant pipe fittings
are tight.

1.8

1.9

1.10 Comply with the standard instructions governing the


use of compressed gas bottles (e.g. keep the bottle
away from any source of heat).

PS 0003/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-12
Revision date

2/3
Page

TRANSMISSION & DISTRIBUTION

START-UP

2.2

An effective pressure of 300 hPa, used for the


transport and storage of our products, is not
regarded as a potential hazard.

SCRAPPING &
RECYCLING

INSTALLATION

See SF6 Safety Sheet.

MAINTENANCE

TRANSPORT

2.1

SAFETY INSTRUCTIONS

OPERATION

PACKING

High voltage switchgear

SF6 Pressure Equipment.

2.3

Always fill the unit using the appropriate equipment,


which should include a safety valve.

2.4

Do not inflate over and above the prescribed


pressure.

2.5

It is strictly forbidden to release SF6 to atmosphere.


All discharged gas must without exception be
recovered.

3
3.1

3.2

Hydraulic Equipment.
Circuit Purging.
This must be done under pressure. Use the
appropriate equipment.
Hydraulic Control Unit.
The doors must be kept shut except when control
tests are being carried out.

PS 0003/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-12
Revision date

3/3
Page

This page is intentionally blank.

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

SF6
Use and Handling

CAUSE OR ORIGIN OF HAZARD.


Sulphur hexafluoride (SF6) is a gas which in its basic state is colourless, odourless and tasteless. It is not toxic,
but it cannot sustain life. It is a heavy gas that is dispersed slowly into the atmosphere.
In its natural state, SF6 is delivered and stored in pressurized tanks (bottles or spheres) at a pressure of
approximately 20 bar at 20C (in its liquid form) and complies with IEC standard 376.
However, under the effect of the electric arc, the SF6 molecules break up and the elements mostly recombine
during cooling either due to extinction of the arc or by regeneration caused by the presence of active
absorbent charges within the circuit breaker.
Various chemical reactions, associated with the volatilization of the materials in contact with the electric arc,
create either fluoridized or sulphurous secondary gas products or solid products in the form of metallic fluoride
powder ; or again, in the presence of traces of water or moisture, hydrofluoric acid or sulphur dioxide.
In the life-cycle of the equipment, SF6 can be observed not only in its pure state, but also in its contaminated
state :
-

the use of new SF6 for filling or adding,

leaks under normal operating conditions,

maintenance involving the opening of circuit breakers containing old SF6 (decomposition products),

abnormal conditions (internal arc fault causing the shielding to break),

circuit breaker recycling on end of life-cycle.

WORK REQUIREMENTS.
Follow the instructions for the transport of pressurized containers.
The storage of these containers is governed by the same storage regulations as compressed gas bottles :
-

keep away from any source of heat and in a cool, dry and well-ventilated area,
always fit a pressure reducing valve.

PS 0004/A

02

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

Ch. MANIN
Signature Approved by

29/8/98

Date

1/3
Signature Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

Whilst SF6 in its pure state is not toxic, the decomposition products have varying degrees of toxicity. They may
irritate the skin, the eyes and the mucous membranes; and in massive amounts may cause serious lesions
(oedema, heart failure, circulatory disorders and unconsciousness).
However, very rapidly and before there is any real danger, signs such as a pungent smell, irritation of the
mucous of the nose, the eyes and the mouth will give a warning and the personnel concerned will have
sufficient time to take the necessary safety actions.
Where the gas is used or handled within enclosed premises, ensure adequate ventilation, especially low down.
If the gas is inhaled, the area concerned must be evacuated immediately.
Under normal operating conditions, leaks are exceptionally minor and not critical, even when the gas contains
impurities (due to the regenerating filters in the circuit breaker).
Filling and where necessary topping up operations must be carried out using the appropriate tools.
During maintenance operations, or at the end of the life-cycle, dust inside the equipment must be removed by
a vacuum extractor and the operator should wear a mask. Gas recovery must be carried out using the
appropriate gas recovery equipment.
Gases and decomposition products must be treated and/or disposed of by specialist organizations.
Under extremely abnormal conditions (e.g. break in the shielding) in an enclosed space, individual protective
equipment is recommended.
Lastly, it is forbidden to smoke, drink, eat or keep food in the vicinity of open SF6 equipment, whether indoors
or outside (harmful dust).

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

It is essential that both the fitter and the user read IEC Technical Report 1634 regarding the use and
handling of sulphur hexafluoride gas.

PS 0004/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-12
Revision date

2/3
Page

TRANSMISSION & DISTRIBUTION

Contaminated SF6

PS 0004/A
Sheet N

02
Revision

X
X

1996-03-18
1st issue

1998-08-12
Revision date

SCRAPPING &
RECYCLING

Pure SF6

MAINTENANCE

OPERATION

START-UP

TRANSPORT

Transport of SF6

SAFETY INSTRUCTIONS

INSTALLATION

PACKING

High voltage switchgear

3/3
Page

This page is intentionally blank.

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

CHEMICALS

CAUSE OR ORIGIN OF HAZARD.


Generally speaking, the products used for installation and commissioning are bought chemical products,
namely :
-

Hydraulic oil

Grease

Loctite

Touching-up paint

Isopropanol

Drying agents

These must be kept in their original packing and the tops replaced after use.
Some packing products require careful handling as they may contain preservatives.
WORK REQUIREMENTS.
As a general rule, chemical products must be used and stored away from any source of heat. Smoking is to be
avoided.
Avoid contact with the skin and any splashes to the eyes.
Take the basic health and safety precautions.
Products and packing must be destroyed in accordance with local environmental regulations.
SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

Other products: SF6 (see relevant sheet)

PS 0005/A

02

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

Ch. MANIN
Signature Approved by

29/8/98

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

Hydraulic Oil

Consumables (Grease & Paint) (Isopropanol)

Loctite

PS 0005/A
Sheet N

02
Revision

1996-03-18
1st issue

1998-08-12
Revision date

SCRAPPING &
RECYCLING

MAINTENANCE

INSTALLATION

OPERATION

TRANSPORT

Drying Agents

START-UP

SAFETY INSTRUCTIONS

PACKING

High voltage switchgear

X
X

2/2
Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

ELECTRICAL EQUIPMENT

CAUSE OR ORIGIN OF HAZARD.


Our equipment is subjected to high and low tension loads that could expose the personnel to the risk of
electrocution.

WORK REQUIREMENTS.
The operating company is responsible for ensuring compliance with the safety instructions governing high
tension.
The basic regulations in respect of low tension installations must also be complied with.

SAFETY INSTRUCTIONS.
OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND
OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

All work on high-tension networks and low-tension installations must be performed by qualified operators
wearing personal protective clothing and using the appropriate tools and equipment.

PS 0006/A

02

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

G. RENAUDIN
Signature Approved by

1998-09-02

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

INSTALLATION

START-UP

OPERATION

MAINTENANCE

SCRAPPING &
RECYCLING

TRANSPORT

SAFETY INSTRUCTIONS

PACKING

High voltage switchgear

High Tension.
1.1 Comply with the regulations governing the work station.
1.2 In the case of items equipped with capacitors, make
sure they are discharged prior to removal and shortcircuited while work is being carried out.

Low Tension.
2.1 Prior to any work on the low-tension circuit or
equipment, cut off the power supply.

2.2 When replacing an electrical component on the control


equipment, follow the safety instructions shown in the
"Machinery" safety sheet.

PS 0006/A
Sheet N

02
Revision

1996-04-04
1st issue

1998-08-12
Revision date

2/2
Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

MACHINERY

CAUSE OR ORIGIN OF HAZARD.


Our equipment contains moving parts (linkage, levers, etc.), reserve power (springs, accumulators, etc.)
and pressurized sheathing ; the associated hazards are dealt with in safety sheet "Pressurized Equipment"
PS 0003/A.

WORK REQUIREMENTS.
Follow the relevant ALSTOM operating and maintenance instructions.
Prior to any work on the control equipment and the motion transfer mechanism, disable the springs on
mechanically operated units and bring pressure back to zero for hydraulically operated units.

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

As a general rule, work on the control equipment and transmissions must be performed by qualified operators
wearing personal protective clothing and using the appropriate tools and equipment.

PS 0007/A

03

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

G. RENAUDIN
Signature Approved by

1998-09-02

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

START-UP

OPERATION

MAINTENANCE

SCRAPPING &
RECYCLING

2.1 Before any work is carried out, cut off all power to the
reset motor.

2.2 Deactivate the opening and closing


accordance with ALSTOM instructions.

3.1 Before any work is carried out, cut off power to the
motor pump.

3.2 Reduce the pressure of the hydraulic circuit to zero.

SAFETY INSTRUCTIONS

Moving Parts.

1.1 Before any work is carried out on transmission


components, ensure that the control equipment has
been deactivated.
2

Spring-operated Mechanism.

springs

in

2.3 Make sure that all safety rules are complied with while
the work is being carried out.
3

TRANSPORT

PACKING

INSTALLATION

High voltage switchgear

Hydraulic Mechanism.

PS 0007/A
Sheet N

03
Revision

1996-04-04
1st issue

1998-08-12
Revision date

2/2
Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

OPERATION

CAUSE OR ORIGIN OF HAZARD.


If the unit shows any sign of an unwanted condition, it must be examined by the user.

WORK REQUIREMENTS.

The operators concerned must be suitably qualified and must comply with the normal operating and
maintenance instructions issued by ALSTOM.
Depending on the severity of the fault observed, the necessary corrective measures must be taken, e.g :

- replenish the SF6 gas in the event of a leak,


-

isolate the system in the event of a major malfunction.

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

PS 0008/A

03

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

P. VANDAME
Signature Approved by

98.08.28

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

SCRAPPING &
RECYCLING

MAINTENANCE

OPERATION

INSTALLATION

TRANSPORT

START-UP

COMPLY WITH THE SPECIFIC INSTRUCTION PROVIDED IN THE FOLLOWING CASES :

SAFETY INSTRUCTIONS

PACKING

High voltage switchgear

Opening malfunction :
-

to do with the sequencing chain,


following a mechanical fault.

Cut-off failure.

External dielectric flash-over.

SF6 pressure drop due to either :


-

major leak (switch to 2nd threshold),


no 1st threshold alarm complement.

Loss of motor power :


-

oil, compressed air, component failure.

Activation of safety device, if fitted.


Use only the appropriate products recommended
by ALSTOM.
Abnormal noise.

PS 0008/A
Sheet N

03
Revision

1996-03-18
1st issue

1998-08-12
Revision date

2/2
Page

TRANSMISSION & DISTRIBUTION

High voltage switchgear

SAFETY SHEET

MAINTENANCE

CAUSE OR ORIGIN OF HAZARD.


To ensure safe and unimpaired operation of the equipment, regular maintenance is essential.
Neglected maintenance can create hazards.
Maintenance operations involve hazards that must be guarded against.
WORK REQUIREMENTS.
Comply with the maintenance programme and service intervals shown in the ALSTOM manuals.
In addition, every maintenance operation must comply with the following requirements :
-

it must be carried out by suitably qualified personnel,

both the work involved and the associated hazards must be clearly identified beforehand,

the tools and equipment used (standard or specific to ALSTOM) must be appropriate and in proper
working order,

any replacement parts must be ALSTOM parts.

SAFETY INSTRUCTIONS.

OBSERVE ALL GENERAL INSTRUCTIONS GOVERNING INSTALLATION, COMMISSIONING AND


OPERATION IN ACCORDANCE WITH CURRENTLY ACCEPTED PRACTICES AS WELL AS THOSE LAID
DOWN IN THE DOCUMENTATION SUPPLIED WITH THE EQUIPMENT.

Refer to the relevant SAFETY sheets.

The safety instructions below are general and not exhaustive. They should therefore be modified and/or
supplemented for all specific maintenance operations to be carried out.

PS 0009/A

03

G. BERNARD

1998-08-12

Sheet N

Revision

Written by

Date

P. VANDAME
Signature Approved by

98.08.28

Date

1/2
Signature Page

TRANSMISSION & DISTRIBUTION

MAINTENANCE

SCRAPPING &
RECYCLING
X

Obtain as much information as possible from the user


regarding the condition of the unit.

Check that the unit is earthed both upstream and


downstream.

Demarcate the work area.

Ensure that the operator is equipped with the personal


protective clothes and equipment required (safety glasses,
gloves, safety boots, harness, etc.).

Ensure that the equipment used is compliant and in good


condition (scaffolding, slings, suspended platforms, electrical
equipment, tools, etc.).

Ensure that the safety instructions in respect of each


particular hazard are complied with.

PS 0009/A
Sheet N

03
Revision

1996-03-18
1st issue

START-UP

INSTALLATION

TRANSPORT

Identify the equipment to be worked on and ensure it is


switched off.

SAFETY INSTRUCTIONS

PACKING

OPERATION

High voltage switchgear

1998-08-12
Revision date

2/2
Page

TRANSMISSION & DISTRIBUTION

Appareillage haute tension

QUALIT - QUALITY
Critre d'Acceptation

ENVIRONNEMENT - ENVIRONMENT

ACCEPTANCE CRITERIA

SCURIT - SECURITY

METTEUR - TRANSMITTER :

N CRITRE DACCEPTATION
ACCEPTANCE CRITERIA NUMBER

Qual. Q4. Montage

QUALITY DEPARTEMENT

CA 103 141 3

INDICE : 004

21/01/2003

OBJET - TITLE :
DISJONCTEUR GL314 COMMANDE MCANIQUE FK3.1 - MONTAGE SITE

GL314 CIRCUIT BREAKER WITH FK3.1 SPRING MECHANISM - SITE ERECTION


-

DESTINATAIRES - EXEMPLARIES :
Responsable Coordination Technique (ATTENCIA Bernard)
Responsable Groupe devis techniques (THION Ren)
Responsable Groupe Notices (LABADIE Jean-Claude)
Responsable Qualit montage (JEULIN Michle)
Responsable Ventes aux licencis (VENARD Pierre)
Pas de poste OPM en diffusion

Rdacteur(s)

:
Drafter visa

Approbateur(s)

:
Approver visa

:
Supervisor visa

HYNAUX Patrick
Sign le 20/01/2003

MARTIN Joseph
Sign le 21/01/2003

ALLAIRE Xavier
Sign le 21/01/2003

CA 103 141 3
N dInstruction-Instruction

06/02/2002
Date dmission-Ist issue

Vrificateur(s)

004
Indice-Revision

21/01/2003
Date de rvision

1/4
Page-Sheet

Le prsent document est la proprit de ALSTOM. Remis titre This document is the sole property of ALSTOM. It is submitted on a
confidentiel, il ne peut tre communiqu des tiers ni utilis ou reproduit confidential basis and may not be passed on to third parties, used or
quen stricte conformit dautorisations expresses pralables.
reproduced except in exact accordance with prior express permission.

TRANSMISSION & DISTRIBUTION

Appareillage haute tension

VALIDIT
VALIDITY
DISJONCTEUR
CIRCUIT BREAKER

: GL314

PRESSION SF6
SF6 PRESSURE

: Pre = 0,75 - 0,85 MPa (absolue)

COMMANDE
MECHANISM

: MCANIQUE FK 3.1
: FK3.1 SPRING MECHANISM

DFINITION DES DURES

TIME DEFINITION

DURE DE FERMETURE : Intervalle de temps entre


l'instant de mise sous tension du circuit de fermeture
et l'instant o les contacts se touchent dans tous les
ples.

CLOSING TIME : Interval of time between


energizing the closing circuit and the instant when
the contacts touch in all poles.

DURE D'OUVERTURE : Intervalle de temps entre


l'instant de mise sous tension du dclencheur et
l'instant de la sparation des contacts d'arc sur tous
les ples (ou des contacts du simulateur
commands par la charge fictive).

OPENING TIME : Interval of time between the


instant of energizing the opening release and the
instant when the arcing contacts have separated in
all poles (or simulator contacts controled by the
dummy load).

DURE D'OUVERTURE-FERMETURE : Intervalle


de temps entre l'instant de sparation des contacts
dans tous les ples, et l'instant o les contacts se
touchent dans le premier ple pendant une
manoeuvre de refermeture (refermeture : l'appareil
est referm automatiquement aprs un intervalle de
temps prdtermin -220 ms-).

OPEN-CLOSE TIME : Interval of time between the


instant when the arcing contacts have separated in
all poles and the instant when the contacts touch in
the first ple during a reclosing operation (reclosing
: the equipment is automatically reclosed after a
predetermined interval of time 220 ms-).

DURE DE FERMETURE-OUVERTURE : Intervalle


de temps entre l'instant o les contacts se touchent
dans le premier ple pendant une manoeuvre de
fermeture, et l'instant o les contacts d'arc sont
spars dans tous les ples pendant la manoeuvre
d'ouverture qui lui fait suite.

CLOSE OPEN TIME : Interval of time between the


instant when the contacts touch in the first pole
during a closing operation, and the instant when the
arcing contacts have separated in all poles during
the subsequent opening operation.

CART DE SIMULTANIT ENTRE PLES : Pour la


mme manoeuvre, diffrence de temps maximale entre
les instants o les contacts de ples se touchent la
fermeture et diffrence de temps maximale entre les
instants de sparation des contacts des ples
l'ouverture.

DEVIATION BETWEEN POLES : For the same


operation maximum deviation between the instants
when the poles contacts touch during the closing
operation and maximum deviation between the
instants when the poles contacts are separated
during the opening operation.

CA 103 141 3
N dInstruction-Instruction

06/02/2002
Date dmission-Ist issue

004
Indice-Revision

21/01/2003
Date de rvision

2/4
Page-Sheet

TRANSMISSION & DISTRIBUTION

Appareillage haute tension

DURES DE FONCTIONNEMENT (en ms tension assigne)


MECHANICAL OPERATING TIMES ( in ms at rated voltage)
DURES DES CHAMBRES
TIMINGS OF CHAMBERS
MANOEUVRE
OPERATION

Minimum Maximum

Fermeture - Closing
Ouverture O1/O2 - Opening O1/O2
Ouverture par bobine MU avec relais Opening with minimum
voltage coil with relay
Fermeture par relais TEC - Closing with relay TEC
Fermeture par relais Allen Bradley - Closing with relay Allen Bradley
Fermeture par relais RE3000 - Closing with relay RE3000
Ouverture par relais TEC O1/O2 - Opening with relay TEC O1/O2
Ouverture par relais Allen Bradley O1/O2 - Opening with relay
Allen Bradley O1/O2
Ouverture par relais RE3000 O1/O2 - Opening with relay RE3000
O1/O2
Fermeture de CO - Closing of CO
Ouverture de CO - Opening of CO
CO
1re Ouverture de O-CO - 1st Opening of O-CO
Fermeture de O-CO - Closing of O-CO
2me Ouverture de O-CO - 2nd Opening of O-CO

82
16
35

102
26
70

87
94
106
20
31

112
122
132
40
54

37

63

82
30
35
16
82
30

102
50
65
26
102
50

DURES DES CONTACTS AUXILIAIRES


TIMINGS OF AUXILIARY CONTACTS
TYPE DE CONTACT - MANOEUVRE
TYPE CONTACT - OPERATION
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type

a / Fermeture de CO - Closing of CO
b / Fermeture de CO - Closing of CO
a / Ouverture de CO - Opening of CO
b / Ouverture de CO - Opening of CO
a / 1re Ouverture de O-CO - 1st Opening of O-CO
b / 1re Ouverture de O-CO - 1st Opening of O-CO
a / Fermeture de O-CO - Closing of O-CO
b / Fermeture de O-CO - Closing of O-CO
a / 2me Ouverture de O-CO - 2nd Opening of O-CO
b / 2me Ouverture de O-CO - 2nd Opening of O-CO

CA 103 141 3
N dInstruction-Instruction

06/02/2002
Date dmission-Ist issue

004
Indice-Revision

Minimum Maximum

82
67
24
34
10
20
82
67
24
34

21/01/2003
Date de rvision

110
92
54
64
30
40
110
92
54
64

3/4
Page-Sheet

TRANSMISSION & DISTRIBUTION

Appareillage haute tension

CART ENTRE POLES


DEVIATIONS BETWEEN POLES

(en ms tension assigne)


(in ms at rated voltage)

MANOEUVRE
OPERATION
Fermeture Closing rseau network 50 Hz
rseau network 60Hz
Ouverture - Opening

DURES DE REARME
CHARGING TIME
Tension Moteur en
V
Motor Voltage in V
toutes
all

Maximum
5
4
3

(en s tension assigne)


(in s at rated voltage)
Maximum
12

RESISTANCE DE CONTACT DU CIRCUIT PRINCIPAL (avec prise de courant)


(en mW sous courant continu de 100A)
MAIN CIRCUIT RESISTANCE (with HV terminal)
(in mW with a 100A direct courrent)
Type de chambre
Type of chamber
105 /4
105/ 5
105/ 7
105/ 11
105/ 12

CA 103 141 3
N dInstruction-Instruction

Maximum
48
50
52
50
52

06/02/2002
Date dmission-Ist issue

004
Indice-Revision

21/01/2003
Date de rvision

4/4
Page-Sheet

Cette page est intentionnellement blanche.

ALSTOM Transmission & Distribution / Appareillage Haute Tension


130, rue Lon Blum -- BP 1321 -- 69611 Villeurbanne cedex -- France
Tlphone : 33 (0) 4 72 68 34 34 -- Tlfax : 33 (0) 4 72 68 34 96

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Manual operations
FK 3-1 / 3-06 motor-wound spring
operating mechanisms
for outdoor circuit breakers

Administered by

First issued

Written by

Released by

SEH

15.01.1998

E. Suter/TMA-SEH /hz

E. Suter, TMA-SEH / 21.5.2003

21.5.2003
ALSTOM

48.020.181E/2
1/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

FK 3-X motor-wound spring operating mechanism for outdoor circuit breaker

Contents

21.5.2003
ALSTOM

Page

Introduction

Safety

Manual operations possible

Preparation of operating mechanism for manual operations

Slow closing

14

Slow opening

16

Manual discharge of closing spring

19

Final steps after manual operations are complete

23

48.020.181E/2
2/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Introduction
This manual describes the following manual operations:
Slow closing
Slow opening
Manual discharge of closing spring
Manual operations as described in these instructions are not necessary in
the course of installation or in normal circuit breaker operation.
The circuit breaker can be slowly closed or slowly opened as required for
adjustment and inspection purposes.
In order to remedy a problem after improper manipulations or in case of
circuit breaker malfunctions, the equipment can be slowly closed or slowly
opened or the closing spring can be manually discharged.

Safety
The 70.00 motor-wound spring operating mechanisms feature state-of-theart design and high operational reliability. They can nevertheless pose a
hazard if used improperly.
The circuit breaker operator must therefore ensure that assigned personnel
Is familiar with locally and nationally applicable safety and accidentprevention regulations, particularly as applicable to high-voltage
switchgear and other high-voltage equipment
Is aware of and comply with the contents of these instructions
Has received technical training on circuit breakers, including operating
mechanisms
Observes safety instructions affixed to the apparatus
Has the duty immediately to report any changes that interfere with safety
Necessary conditions
for performance of
manual operations

21.5.2003
ALSTOM

The circuit breaker is in open position.


The circuit breaker is earthed on both sides.
The control voltage is disconnected.

48.020.181E/2
3/26

=>?@
Safety: general

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Manipulations not in compliance with these instructions pose hazards for


the personnel involved as well as for the motor-wound spring operating
mechanism.
Manipulations on the motor-wound spring operating mechanism that do
not comply with the FK 3-X instructions create a danger of death or injury
to the person performing them. Damage to the motor-wound spring operating mechanism may also result.

DANGER

Personal safety when


performing manipulations on the operating mechanism

Perform only manipulations that comply with the instructions for


FK 3-X motor-wound spring operating mechanisms.

The closing spring is charged after the control voltage is disconnected.


Inadvertent switching operations are possible while performing manipulations on the operating mechanism even though the control voltage is
disconnected.
Injury may result from touching parts that are moving.

WARNING

To discharge the springs, use manual releases to open, close and


reopen with the control voltage disconnected.

Spring operating mechanisms with undervoltage releases open immediately when the control voltage is disconnected.
This can lead to injury when performing manipulations in the spring
operating mechanism.
WARNING

Disable the undervoltage release to prevent unforeseen opening


operations.

When the motor voltage is turned on, the motor immediately begins to
wind the closing spring.
Injury may result from touching parts that are moving and/or springdriven.
WARNING

21.5.2003
ALSTOM

When turning on the control voltage, keep body parts away from
parts of the equipment that are moving and/or spring-driven.

48.020.181E/2
4/26

=>?@
Product safety

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

If the spring operating mechanism is operated with no circuit breaker, the


total energy is released inside the spring operating mechanism.
Damage to the operating mechanism may result.

CAUTION

Operate the spring operating mechanism only with the circuit


breaker coupled to it.

If the gas pressure of the circuit breaker is lower than the minimum value
for mechanical switching operation (listed on the warning plate in the
spring operating mechanism), an excessively high energy is released inside the spring operating mechanism.
Damage to the circuit breaker and the spring operating mechanism may
result.
CAUTION

Operate the spring operating mechanism only with a circuit breaker


having a gas pressure higher than the minimum value for mechanical switching operation.
Dust inside the spring operating mechanism can interfere with the functioning of moving parts such as latches, rollers and shafts and can impair
the performance of electrical equipment.
Malfunctions and damage to the spring operating mechanism may result.

CAUTION

Always keep the inside of the spring operating mechanism free of


dust. Always close the cabinet door in correct fashion to bar the entry of dust.
The use of cleansers, rust-preventing oil or sprays can lead to heavy buildups of gum.
This can interfere with the functioning of the spring operating mechanism.

CAUTION

Use only mechanical cleaning aids when performing cleaning


and/or corrective maintenance. If relubrication is necessary, it must
be carried out in compliance with the FK 3-X lubrication instructions.
Moisture inside the spring operating mechanism leads to condensation
and subsequent corrosion of steel parts.
Malfunctions and damage to the spring operating mechanism may result.

CAUTION

21.5.2003
ALSTOM

The heating (anticondensation feature) must always be in operation, regardless of where the circuit-breaker is installed.

48.020.181E/2
5/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Manual operations possible


The motor-wound spring operating mechanism as delivered is mounted
on the circuit breaker as described in the installation manual.
If the as-delivered condition of the uncoupled operating mechanism has
been modified in error, the following manual operations can be performed in order to restore the as-delivered condition.

Note

21.5.2003
ALSTOM

Fig.

Fig.

Fig.

Fig.

opening

opening

Slow

If

Manual discharge
of closing spring

Slow

Operating mechanism not coupled

Action
No action (asdelivered condition)
Closing spring charged; circuit breaker Manually discharge
position indicator OPEN
closing spring
Closing spring discharged; circuit
Slowly open
breaker position indicator CLOSED 1)
Closing spring charged; circuit breaker 1. Slowly open
position indicator CLOSED 1)
2. Manually discharge
closing spring
Closing spring discharged; circuit
breaker position indicator OPEN

1) If the spring operating mechanism has been operated with no circuit


breaker, consult the manufacturer to identify any possible damage.

48.020.181E/2
6/26

=>?@

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

The following manual operations can be performed for inspection purposes and to remedy problems:

Slow
closing

Slow
closing

Slow
opening

Manual discharge
of closing spring

Slow
opening

Operating mechanism mounted on


circuit breaker and
coupled

Manual operations

If

Fig.

Fig.

Fig.

Fig.

21.5.2003
ALSTOM

Action

Closing spring discharged,


circuit breaker position indicator OPEN
For inspection and adjustment
Closing spring charged, circuit
breaker position indicator
OPEN
For inspection and adjustment
Circuit breaker must not
be closed
Closing spring discharged,
circuit breaker position indicator CLOSED
For inspection and adjustment
Closing spring charged, circuit
breaker position indicator
CLOSED
For inspection and adjustment

Slowly close

Slowly close

Manually discharge closing


spring

Slowly open

Slowly open

48.020.181E/2
7/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Spring position indi If the spring position indicator or the circuit breaker position indicator is
cator and circuit
in an intermediate position, there is a defect in the spring operating
breaker position indimechanism or the circuit breaker.
cator in an intermedi- Before performing manual operations, consult the manufacturer in order
ate position
to diagnose the fault and determine how to remedy it.
Possible positions of the position indicators

Spring position indicator in intermediate position

21.5.2003
ALSTOM

Circuit breaker position indicator in


intermediate position

48.020.181E/2
8/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Preparation of operating mechanism for manual operations


Prepare cabinet

If

Action

Horizontal rear panel mounting

Remove side panels 78.01


Remove side panel lock nuts 78.20
Swing side panel 78.01 outward and
pull down
Unscrew roof mounting screws 78.18
and lift off roof 78.02

Vertical rear panel mounting

Horizontal mounting shown


78.02
78.18
78.07
78.01
78.19
78.20

78.01 Side panel


78.02 Roof
78.07 Lifting lugs
Disable manual releases

78.18
78.19
78.20

Roof mounting screws


Cover panel
Side panel lock nuts

The manual releases can be inadvertently actuated when performing


manipulations on the spring operating mechanism.
Injury may result from performing manipulations on the spring operating
mechanism without disabling the manual releases.

WARNING

21.5.2003
ALSTOM

Disable the manual releases to prevent inadvertent manual actuation of the spring operating mechanism.

48.020.181E/2
9/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

If

Action

Spring operating mechanism


without undervoltage release

The manual releases are normally disabled.


If not:
Unscrew M6 screws.
Slide manual release disabling feature
70.58 as shown by arrow until manual
releases are disabled.
Retighten M6 screws.

Spring operating mechanism


with undervoltage release, with
integral disabling device

Spring operating mechanism


with undervoltage release, without disabling feature

Manual release disabling feature 70.58 is


normally not installed in this version.
Install manual release disabling device
70.58 and slide as shown by arrow
until manual releases are disabled.
Tighten M6 screws.

Manual release disabling device

70.13
70.58
70.07
M6

70.58
70.07

21.5.2003
ALSTOM

Manual release disabling


device
Manual CLOSE release

70.13

Manual TRIP release

48.020.181E/2
10/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Disable undervolt- If the spring operating mechanism is equipped with undervoltage releases
age release
and slow closing or slow opening is necessary, disable the undervoltage
release.
If

Action

Undervoltage release without disabling device


Insert hooked end of disabling device 71.20 and pull magnet out to
the stop.
Then gently tighten the nut by hand.

71.20

Nut

71.20 Undervoltage release disabling device


Undervoltage release with integral
disabling device

Turn disabling lever from service


position to disabled position.

Disabling lever in service position

Disabling lever in disabled position

21.5.2003
ALSTOM

48.020.181E/2
11/26

=>?@
Disable closing latch
if closing spring is
charged

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

The closing latch can be inadvertently actuated when performing manipulations on the spring operating mechanism.
Injury may result from performing manipulations on the spring operating
mechanism with the closing spring charged and the closing latch not
disabled.

WARNING

Disable the closing latch in order to prevent inadvertent manual


actuation of the spring operating mechanism.

Insert disabling device 70.71 of closing latch 70.05 and fix to the axle of
manual TRIP release 70.13.

70.05
70.13
70.05
70.13
70.71

Remove safety plate

Closing latch
Manual TRIP release
Closing latch disabling
device

70.71

Remove safety plate 70.48.

70.48
70.96
70.48 Safety plate

21.5.2003
ALSTOM

70.96 Securing screw

48.020.181E/2
12/26

=>?@
Install closing spring
discharging device

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Place closing spring discharging device 71.15 on securing screw 70.96


and the lip of front chassis panel 70.85.
Then turn tie rod 71.08 clockwise by hand until distance sleeve 71.07 of
the device comes to bear on guide socket 70.95.

70.26
71.07
70.95
70.85
70.96
71.08
71.09

70.26
70.85
70.95
70.96
Relieve load on chain

21.5.2003
ALSTOM

Closing chain
Front chassis panel
Guide socket
Securing screw

71.07 Distance sleeve


71.08 Tie rod
71.09 Hex nut

Turn the tie rod clockwise about four more turns to charge closing spring
further. The chain now bears no load.

48.020.181E/2
13/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Slow closing
The spring operating mechanism has been made ready for manual
operations.
Operating condition
of circuit breaker and
operating mechanism

Positions of position indicators

Spring position indicator shows closing


spring discharged or charged

Tools required

21.5.2003
ALSTOM

Circuit breaker position indicator shows OPEN

70.71
Closing latch disabling device
70.72
Slow-movement device
71.15
Closing spring discharging device
70.58
Manual release disabling plate 1)
71.20
Undervoltage release disabling device 1)
1) Required only for a spring operating mechanism equipped with an undervoltage release but no integral disabling feature

48.020.181E/2
14/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Install slowmovement device

Lay support plate 70.73 of slow-movement device 70.72 on upper right


distance sleeve 70.76 and bring to bear against operating mechanism
chassis.
Engage hook 70.74 of slow-movement device with pin 70.77 of support
latch 70.78.

Manual closing

Turn hex nut 70.75 clockwise until support latch 70.78 of roller lever
70.11 comes to rest against trip latch 70.16 with an audible snap.
As slow closing proceeds, trip spring 70.20 is simultaneously charged.
Stop sleeve 70.80 prevents overwinding.
The circuit breaker position indicator now shows CLOSED.

70.75
70.73
70.76
70.80

70.11
70.78
70.74
70.77
70.16

70.11
70.16
70.73
70.74
70.75

Operating condition
after slow closing

Roller lever
Trip latch
Support plate
Hook
Hex nut

70.76
70.77
70.78
70.80

Positions of position indicators

Spring position indicator shows closing


spring discharged or charged

Remove slowmovement device

21.5.2003
ALSTOM

Distance sleeve
Pin
Support latch
Stop sleeve

Circuit breaker position indicator shows CLOSED, trip


spring charged

Turn hex nut 70.75 counterclockwise until hook 70.74 is relieved of


enough load to allow removal of slow-movement device 70.72.

48.020.181E/2
15/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Slow opening
The spring operating mechanism has been made ready for manual
operations.
Verify operating state
of circuit breaker and
spring operating
mechanism

Positions of position indicators

Spring position indicator shows closing


spring discharged or charged

Circuit breaker position indicator shows CLOSED, trip spring


charged

Tools required

70.71
Closing latch disabling device
71.15
Closing spring discharging device
70.72
Slow-movement device
70.58
Manual release disabling plate 1)
71.20
Undervoltage release disabling device 1)
1) Required only for a spring operating mechanism equipped with an undervoltage release but no integral disabling feature

Install slowmovement device

Lay support plate 70.73 of slow-movement device 70.72 on upper right


distance sleeve 70.76 and bring to bear against operating mechanism
chassis.
Engage hook 70.74 of slow-movement device with pin 70.77 of support
latch 70.78.

Relieve load on trip


latch

Use tool to turn hex nut 70.75 clockwise until the torque increases, signalling that the load on trip latch 70.16 has been relieved.

70.75
70.73
70.76
70.80

70.11
70.74
70.77
70.78
70.16

70.11
70.16
70.73
70.74
70.75
21.5.2003
ALSTOM

Roller lever
Trip latch
Support plate
Hook
Hex nut

70.76
70.77
70.78
70.80

Distance sleeve
Pin
Support latch
Stop sleeve
48.020.181E/2
16/26

=>?@
Re-enable manual
releases

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Unscrew M6 screws.
Slide manual release disabling device 70.58 as shown by arrow.
Tighten M6 screws.

70.13
70.58
70.07
M6

70.58
70.07
Manual opening

Manual release disabling


device
Manual CLOSE release

70.13

Manual TRIP release

Use manual TRIP release 70.13 to release trip latch 70.16.


Simultaneously turn nut 70.75 counterclockwise until support latch 70.78
of roller lever 70.11 has moved past trip latch 70.16.
Continue turning nut 70.75 counterclockwise until the load on hook
70.74 is relieved.
At the end of this procedure, trip spring 70.20 is discharged and circuit
breaker position indicator 70.52 shows circuit breaker OPEN.

70.75
70.73
70.76
70.80

70.11
70.74
70.77
70.78
70.16

70.11
70.16
70.73
70.74
70.75
21.5.2003
ALSTOM

Roller lever
Trip latch
Support plate
Hook
Hex nut

70.76
70.77
70.78
70.80

Distance sleeve
Pin
Support latch
Stop sleeve

48.020.181E/2
17/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Remove slowmovement device

Turn hex nut 70.75 counterclockwise until the load on hook 70.74 is
relieved enough that slow-movement device 70.72 can be removed.

Disable manual releases

Unscrew M6 screws.
Slide manual release disabling device 70.58 as shown by arrow until
manual releases 70.07 and 70.13 are disabled.
Retighten M6 screws.

70.13
70.58
70.07
M6

70.58
70.07

Operating state of
spring operating
mechanism after slow
opening

Manual release disabling


device
Manual CLOSE release

70.13 Manual TRIP release

Positions of position indicators

Spring position indicator shows closing


spring discharged or charged

21.5.2003
ALSTOM

Circuit breaker position indicator shows OPEN, trip spring


discharged

48.020.181E/2
18/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Manual discharge of closing spring


The operating mechanism has been made ready for manual operations.
Verify operating state
of circuit breaker and
spring operating
mechanism

Positions of position indicators

Spring position indicator shows


spring charged

Circuit breaker position indicator


shows OPEN, trip spring discharged

Tools required

70.71
Closing latch disabling device
71.15
Closing spring discharging device
71.16
Motor limit switch disabling plate
70.58
Manual release disabling plate 1)
1) Required only for a spring operating mechanism equipped with an undervoltage release but no integral disabling feature

Place motor limit


switch in closing
spring discharged
position

Using open-end wrench 71.12 (S = 12 mm), turn the square shaft of the
spring position indicator counterclockwise.

FK 3-1 shown

71.12
71.16

71.16 Motor limit switch disabling plate

Block motor limit


switch in closing
spring discharged
position

21.5.2003
ALSTOM

FK 3-1 shown

71.12 Open-end wrench


(S=12)

Using the open-end wrench, turn the shaft until motor limit switch disabling plate 71.16 can be engaged with the motor limit switch bracket
and the axis of the motor limit switch lever as shown in the drawing.
Blocking the switch in this way prevents the auxiliary switch from rotating
back into the starting position.

48.020.181E/2
19/26

=>?@
Release return stop

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism
Unscrew return stop clamp shackle screw 71.13 one turn.

70.98
70.02
FK 3-1 shown

71.13

70.02 Return stop


70.98 Return stop clamp shackle
Turn back closing
shaft

71.13 Clamp shackle screw

With the right hand, press crank flywheel 70.30 counterclockwise against
the teeth of pinion shaft 70.97.
At the same time, using the left thumb, turn motor shaft pinion 70.56
counterclockwise until the clearance between roller 70.28 and closing
latch 70.05 is approx. 20-30 mm.

70.28
70.05
FK 3-1 shown

70.56
70.97
70.30
70.05 Closing latch
70.28 Roller
70.30 Crank wheel
21.5.2003
ALSTOM

70.56
70.97

Pinion
Pinion shaft

48.020.181E/2
20/26

=>?@
Discharge spring

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Turn tie rod 71.08 of closing spring discharging device 71.15 counterclockwise to discharge the closing spring. Crank flywheel 70.30 will turn
counterclockwise.
Continue turning tie rod 71.08 until closing spring discharging device
71.15 is free and can be withdrawn.

71.15
71.08

71.08 Tie rod

Operating state of
spring operating
mechanism after
manual discharge of
closing spring

71.15 Closing spring discharging device

Positions of position indicators


The spring operating mechanism now has no stored energy. The indicators
stand as shown below.

Spring position indicator shows closing


spring discharged

Set return stop

WARNING

21.5.2003
ALSTOM

Circuit breaker position indicator


shows OPEN, trip spring discharged

Tighten clamp shackle screw 71.13 to 5Nm 10%.

The return stop will not function properly if the clamp shackle screw is
not tightened to the specified torque.

If the closing spring is being charged with the hand crank under these
conditions and the hand crank is let go before the end position is
reached, it will turn backwards at high speed. Injury may result.

After performing manipulations on the return stop, tighten the


clamp shackle mounting screw to a torque of 5 Nm 10%.

48.020.181E/2
21/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

The return stop will not function properly if the clamp shackle screw is
not tightened to the specified torque.
If the closing spring is being charged by the motor under these conditions and the motor voltage drops out, the closing spring will discharge
by turning the gearing backwards. Damage to the operating mechanism
may result.
CAUTION

After performing manipulations on the return stop, tighten the


clamp shackle mounting screw to a torque of 5 Nm 10%.

Re-enable motor limit Remove motor limit switch disabling plate 71.16 so that the motor limit
switch
switch can function again.

21.5.2003
ALSTOM

48.020.181E/2
22/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Final steps after manual operations are complete


Verify
that
circuit Before performing the final actions, verify that the circuit breaker is in
breaker is OPEN
OPEN position.
Remove closing latch
disabling device

If installed (slow closing or opening with closing spring charged), remove


closing latch disabling device 70.71.

Remove closing
spring discharging
device

If closing spring discharging device 71.15 is installed (slow closing or


opening with closing spring charged), turn tie rod 71.08 counterclockwise until closing chain 70.26 is under load again and closing spring
discharging device 71.15 is free and can be withdrawn.

70.26
71.15
71.08

70.26 Closing chain


71.15 Closing spring discharging
device

21.5.2003
ALSTOM

71.08 Tie rod

48.020.181E/2
23/26

=>?@
Spring operating
mechanisms with
undervoltage release

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Re-enable the undervoltage release.


If

Action

Undervoltage release without


disabling feature
Remove undervoltage release disabling device 71.20.

71.20

Undervoltage release with integral disabling feature


Disabling lever in service position

Turn disabling lever from disabled


position to service position.

Disabling lever in disabled position


71.20 Undervoltage release
disabling feature

21.5.2003
ALSTOM

48.020.181E/2
24/26

=>?@

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Remove manual release disabling device.

70.13
70.58
70.07

Manual release disabling feature


70.58 is normally not installed in this
version.
Unscrew M6 screws and remove
manual release disabling device
70.58.

M6

70.58 Manual release disabling


device
70.07 Manual CLOSE release
70.13 Manual TRIP release

21.5.2003
ALSTOM

48.020.181E/2
25/26

=>?@
Final actions on cabinet

Manual operations

FK 3-1 / FK 3-06 motor-wound spring


operating mechanism

Reinstall side panels 78.01 and roof 78.02.


Lay roof on cabinet and align so that dimensions A, B, C, D are within a
tolerance of 1 mm. The cabinet may have to be straightened in order
to attain the specified tolerance.
Tighten roof mounting screws. After tightening, check dimensions A, B,
C, D; correct if necessary.

78.03

78.18

78.02

78.02 Roof
78.18 Roof mounting screws

78.03

Frame

Install side panels 78.01.


For proper sealing of side panels against cabinet rims, dimension E (side
panel to cabinet clearance) must be no greater than 5 mm.

78.01

78.01 Side panel


Restore to service

21.5.2003
ALSTOM

Connect control voltage.

48.020.181E/2
26/26

Maintenance

Instructions on the handling of used SF6 gas


and decomposition products
Presentation
Introduction

These maintenance directives incorporate measures for avoiding the hazards


involved in the application of SF6 gas to switchgear.
Such directives are protective measures and recommendations for the user
of SF6 switchgear.

Fundamental
rules

Instructions for performance of work on SF6 gas switchgear are given in the
appropriate instruction manuals.
Switchgear may only be opened after the preparations for scavenging have
been completed.

In this module

This module contains the following topics :


Topic
Evacuation of SF6 gas apparatus
Opening--up SF6 gas switchgear
Recapitulation of important instructions

03--1999
E ALSTOM

Page
2
3
4

T51--251EN/01
1/4

Maintenance

Instructions on the handling of used SF6 gas


and decomposition products
Evacuation of SF6 gas apparatus
Principle and
precautions

The table below gives the principle of evacuation of SF6 gas apparatus and
precautions to take :
Step
1
2
3

03--1999
E ALSTOM

Action
De--energize apparatus, switch-off where applicable and earth.
Connect the servicing unit to the
gas filling nipple by means of a
hose and using an adsorber filter.
Suck SF6 gas :
-- Into servicing unit or ,
-- After having taken the appropriate safety precautions, exhaust the gas outdoors (observe
the local regulations on emission).
Fill gas compartment if possible
with nitrogen or dry compressed
air at rated pressure and subsequently, discharge outdoors (if
possible through an adsorber filter).

Comment

Where switchgear with considerable decomposition products is


involved, exhaust outdoors only
through an adsober filter.

T51--251EN/01
2/4

Maintenance

Instructions on the handling of used SF6 gas


and decomposition products
Opening--up SF6 gas switchgear
Precautions to take

At the time of the opening--up SF6 gas switchgear, take the precautions below :
S Open--up SF6 switchgear only after the gas has been evacuated and the
pressure inside the apparatus has been reduced to that of atmospheric pressure.
S Put the ventilation system in operation or ensure that fresh air circulates
in some other manner when switchgear which contains decomposition products is opened (e.g. circuit--breaker).
S Wear suitable fresh air breathing apparatus if there is even the slightest
possibility that personnel working on the equipment could be put in danger
through inhalation of hazardous amounts of gas vapor from powdery decomposition products.
S Wear special overalls when working on opened--up SF6 switchgear which
contains powdery decomposition products. After completing work remove
overalls.
S Avoid stirring--up dust and powder from SF6 switchgear. Difficult to remove
dust can be removed with dry non--fibrous rags. A vacuum cleaner should be
used to remove loose dust. The vacuum cleaner filter should be able to retains
particles of a least 1 min size.
S Items (such as rags, vacuum cleaner, throw--away--overalls, gloves, etc.)
which come in contact with the decomposition products must be collected and
neutralized so that the dust cannot be transferred. Before getting rid of these
items neutralize in a 3 percent soda solution for 24 hours. verify the degree
of neutralization after 24 hours. When soda is added, no bubbles should be
result. If there are bubbles repeat the neutralization.
S Under all circumstances ensure that the decomposition products neither
come in contact with skin, eyes, clothes, nor that they are swallowed or inhaled. Pay special attention to cleanliness of body, clothes and work--bench.
Dust or powder that comes in contact with skin must be washed away with
plenty of water.
It is advisable to wash face, neck, arms and hands with soap and plenty of
water before work--breaks and after stoppage of work.
S Avoid eating, drinking, smoking or storing eatables in rooms or outdoors
near to opened SF6 switchgear which may contain arc--decomposed powder.

03--1999
E ALSTOM

T51--251EN/01
3/4

Maintenance

Instructions on the handling of used SF6 gas


and decomposition products
Recapitulation of important instructions
Reminder

Pure, non--contaminated SF6 gas is non--poisonous. Electrical discharges


and fault--switching arcs will give rise to different grades of poisonous decomposition products. In small amounts gaseous decomposition products produce -- within seconds and before any poisonous effects can take place -warning symptoms, such as an unpleasant piercing odor, nasal, mouth and
eye irritations, which enable working personnel to withdraw to safety. Solid
decomposition products (powdery residues from switching) can cause skin
irritations. SF6 is about five times heavier than air, and in the absence of turbulence, results in the gas collecting just above ground level and causing suffocation through a deficiency of oxygen.

Important
instructions

The table below recapitulates the important instructions to follow at the time
of handling of used SF6 gas and decomposition products :
No.
1

6
7

03--1999
E ALSTOM

Instruction
As soon as an unpleasant, piercing odor from decomposition
products becomes perceptible leave the substation room without delay. enter the room only after thorough ventilation or when
wearing suitable oxygen breathing masks (with filtering or fresh
air device).
After disturbances, enter the substation room only after having
thoroughly aired the room or when wearing independent of ambient--air operating oxygen breathing masks, or alternatively, after
verifying by measurement that the ambient air contains at least
17% volume of oxygen, especially if, one has to reckon with the
concentration of SF6 in hazardous amounts.
Enter rooms located below, and connected with the substation-rooms after thorough ventilation only, or when wearing oxygen
breathing masks which operate independent of the ambient--air,
or alternatively, after having verified by measurement that the
ambient air contains at least 17% volume of oxygen.
Ensure that the room ventilation operates satisfactorily, whilst
maintenance work is being performed on SF6 switchgear (discharging and filling of gas, opening and cleaning of equipment).
When working on opened SF6 switchgear protect skin against
contact with gas and avoid swallowing or inhaling of gas. Ensure
body, clothing and work--bench cleanliness. Wear special work-overalls and after completion of work discard latter.
Wash skin which comes in contact with powder deposits with
plenty of water. Before work--breaks and after work wash face,
neck, arms and hands thoroughly with soap and plenty of water.
Do not stir--up powder deposits resulting from arc--switching.
Remove sticky powder with dry rags. Use suitable vacuum
cleaner with paper--filter to remove loose powder. Discard used
items and filter--bags in such a manner that powder deposit does
not spread. Before discarding neutralize used items.
Avoid eating, drinking and storing eatables in rooms with opened
SF6 switchgear which contains powder deposits.

T51--251EN/01
4/4

This page is intentionally blank.

ALSTOM Transmission & Distribution / Appareillage Haute Tension


130, rue Lon Blum -- BP 1321 -- 69611 Villeurbanne cedex -- France
Tlphone : 33 (0) 4 72 68 34 34 -- Tlfax : 33 (0) 4 72 68 34 96

You might also like