DEVICENET

DEVICENET (Description / Technical Data)


CAN-based multi master system for transmission of cyclic and
acyclic messages
Supports different kinds of communication (Polling, Strobe,
Change of State, Cyclic Data Transfer)
Technical Data:
Total extent:
Length of the trunk line:

Topology:
Transmission rate:
Cycle time:
number of devices:

max. length of the main line 3 km


with the use of repeaters
500m-125kBit/s ; 125m-500kBit/s
(trunk cable use only)
Line
125-, 250-, 500 kBit/s
dependent on the number of slaves
up to 64 (e.g. 1 master, 63 slaves)

Connectors

7/8 inch
(mini-style)

flat-cable
(piercing contacts)

M12
(micro-style)

(open-style)

Pin allocation / face view

Pin

Signal

Colour

Drain

bare

V+

red

V-

black

Can_H white

Can_L

blue

Cable

Trunk- (Thick-) cable


Power: AWG 15
Data: AWG 18
Diameter: 12 mm

Drop- (Thin-) cable


Power: AWG 22
Data: AWG 24
Diameter: 6,8 mm

Topology

Trunk line, drop line configuration


Node removal without breaking trunk line
Signal and 24Vdc Power in same cable
121 ohm terminator at each trunk line end

Data rate versus bus length


Cable length subject to
data rate and kind of cable
Data rate
Length of
trunk line
(Thick-Cable)
Length of
trunk line
(Thin-Cable)
Length of
trunk line
(Flat-Cable)
Maximum
length of drop
line
Cumulative
length of all
drop lines

125 kBit/s

250 kBit/s

500 kBit/s

500 m

250 m

100 m

100 m

100 m

100 m

380 m

200 m

75 m

6m

6m

6m

156 m

78 m

39 m

Telegram
Telegram structure
S
11 Bit
O
Identifier
F

Control
Length
Field

SOF / EOF:

0 ... 8 Bytes Data

A
CRC C
K

E
O
F

Start / End of Frame

Identifier/Control Field: is needed for the data


transmission
Length:

number of reference bytes

0 ... 8 Bytes:

reference data bytes

CRC:

Cyclic Redundancy Check,


data security

ACK:

Acknowledge,
data transmission sucessful

Communication modes
Communication: Polling
Scanner

Slave #1

Slave #2

Slave #3

The master communicates with the slaves one after the other.

Communication modes
Communication: Strobe
Scanner

Slave #1

Slave #2

Slave #3

The master sends a broadcast message simultaneously to all slaves.


All slaves with inputs send their input data back to the master.

Communication modes
Communication: Change of State
Scanner

Slave #1

Slave #2

Slave #3

All devices transmit their I/O data if the status of the I/O data
changes.

Communication modes
Communication: Cyclic Data Transfer
Scanner
every 25 ms

every 1000 ms

every 200 ms

Slave #1

Slave #2

Slave #3

All devices transmit their data in fixed time intervals.

DEVICENET (Advantages/Disadvantages)
Advantages:
The most flexible system concerning the variety of communication
(Polling, Strobe, Change of State, Cyclic Data Transfer)
Efficient diagnosis functions
High data security (HD=6)
Response monitoring (slave)
Plug & Play configuration by EDS-files
Automatic detection of faults and redundant addresses

Disadvantages:

Line structure
small spatial extension
Necessity of setting address and baud rate
Software burden (hardly learnable)

DEVICENET- System

Lumberg M12-family

Variants:
16 Input (p-switching)
16 Input (n-switching)
8 Outputs (2 A)
16 Outputs (0,5 A)
8 Input / 8 Output (0,5 A)

Lumberg M12-family

Variants:
16 Input (p-switching)
8 Outputs (2 A)
8 Input / 8 Output (2 A)

Lumberg 7/8inch-family

Variants:
16 Input (p-switching)
8 Outputs (2 A)
8 Input / 8 Output (2 A)

Lumberg 7/8inch-family

Variants:
16 Input (p-switching)
16 Input (n-switching)
8 Outputs (2 A)
16 Outputs (0,5 A)
8 Input / 8 Output (0,5 A)

Lumberg 7/8inch-family

Variants:
16 Input (p-switching)
8 Outputs (2 A)
8 Input / 8 Output (2 A)

Lumberg module features


Device Net Box 8xInput/8xOutput

LED green

Actuator power supply

LED green
(Actuator power supply)

(Module supply)

LED green/red
LED green/red

(Module status)

(Network status)

LED red
(Sensor short circuit)

LED yellow

LED yellow

(Input Status
channel A / B)

(Output Status
channel A / B)

Device Net
In

Device Net
Out
Earth sheet

Lumberg module features


Mechanical:
0 to 60oC
Nema 4, 4x, 6P; IP67
Resistant against vibration and shock because of the
full potted housing
M12 sensor-/actuator connection
Electrical:
Reverse polarity protection
Short circuit protection (sensors /actuators)
Watchdog configurable by EDS-file
2A per output
Separation between the potentials of sensors and
actuators