Professional Documents
Culture Documents
Most Efficient
Welcome
- Webinar Duration: 1 hour 30 minutes
- Panelists: Please silence /shut cell phones.
- Questions to Presenters: Please type in Questions in the Q&A box at the lower
right hand corner of screen. Questions will be answered after the end of the
presentation.
Agenda
Review the 5 VSD Myths
Myth # 6 Water Flow Tracks Load
Myth # 7 Pump Speed Tracks Flow
Myth # 8 Pumps/Towers Use More Energy
Than Chillers Can Save
Summary
Q&A
Review
Review
In a central plant:
Run the fewest number
of constant speed
chillers, as heavily
loaded as possible
Review
In a central plant:
Run the fewest number
of constant speed
chillers, as heavily
loaded as possible
Review
Review
Review
10
Review
Review
Variable Speed
Drives Only Save
Energy on a Single
Chiller
12
Review
Variable Speed
Drives Only Save
Energy on a Single
Chiller
Review
14
Review
Completed..
Review the
5 Variable
Speed Drive
Myths
16
Up Next....
Present the
basics of a
Primary /
Secondary
System
Primary Pumps
17
Decoupler
/ Bypass
56F
(4C)
(13C)
56F
40F
40F
(4C)
(4C)
(13C)
Primary Pumps
9000 GPM (34000 LPM)
9000 GPM (34000 LPM) @ 56F (13C)
18
Typical
Coil
No flow
56F
(13C)
(4C)
(11C)
52F
Secondary Pumps
40F 6750 GPM (25500 LPM)
(4C)
@ 40F (4C)
(11C)
52F
40F
40F
(4C)
(4C)
(11C)
Primary Pumps
9000 GPM (34000 LPM)
9000 GPM (34000 LPM) @ 52F (11C)
19
Typical
Coil
56F
(13C)
52F
Secondary Pumps
40F 4500 GPM (17000 LPM)
(4C)
@ 40F (4C)
(11C)
52F
40F
40F
(4C)
(4C)
(11C)
Primary Pumps
6000 GPM (22700 LPM)
6000 GPM (22700 LPM) @ 52F (11C)
20
Typical
Coil
1500 GPM (5700 LPM)
@ 40F (4C)
4500 GPM (17000 LPM)
@ 56F (13C)
56F
(13C)
OFF
52F
40F
40F
(4C)
(4C)
(11C)
Primary Pumps
3000 GPM (11000 LPM)
3000 GPM (11000 LPM) @ 52F (11C)
21
Typical
Coil
750 GPM (2800 LPM)
@ 40F (4C)
2250 GPM (8500 LPM)
@ 56F (13C)
56F
(13C)
Completed..
Present the
basics of a
Primary /
Secondary
System
22
Up Next....
Review
Myth #6
23
40F
(4C)
Typical
Coil
56F (13C)
24
56F
(13C)
25
AIR FLOW
26
Secondary Pumps
16
Primary Pumps
100% Flow = 9000 GPM (34,000 LPM)
27
Decoupler /
Bypass
0 GPM (0 LPM)
Secondary Pumps
(25500 LPM)
16
Primary Pumps
100% Flow = 9000 GPM (34,000 LPM)
28
Decoupler / Bypass
2250 GPM (8500 LPM)
Secondary Pumps
14
Primary Pumps
100% Flow = 9000 GPM (34,000 LPM)
29
Decoupler / Bypass
1286 GPM (4800 LPM)
Secondary Pumps
% LOAD = % FLOW
14
Primary Pumps
100% Flow = 9000 GPM (34,000 LPM)
30
Decoupler / Bypass
1286 GPM (4800 LPM)
Secondary Pumps
(26000 LPM)
OFF?
14
Primary Pumps
100% Flow = 6000 GPM (22700 LPM)
31
Decoupler / Bypass
857 GPM (3200 LPM)
32
Secondary Pumps
% LOAD = % FLOW
14
Primary Pumps
100% Flow = 9000 GPM (34,000 LPM)
33
Decoupler / Bypass
2143 GPM (8100 LPM)
Solve at Load,
Mitigate at Plant
35
36
Completed..
Understand
Low Delta T
and
Bust Myth #6
37
Up Next....
Present the
Basics of
Variable
Primary Flow
Secondary Pumps
Primary Pumps
Bypass
Valve
38
Flow Meter
BHP =
39
GPM X Head
3960 X PumpEff
40
40F
56F
(4C)
(13C)
40F
56F
16
(4C)
(13C)
(4C)
(13C)
Primary Pumps
9000 GPM
(34,000 LPM)
41
Bypass
Closed
Typical
Load with
2-Way
Valve
40F
56F
(4C)
(13C)
40F
56F
16
(4C)
(13C)
(4C)
(13C)
Primary Pumps
6750 GPM
(25500 LPM)
Bypass
Closed
6750 GPM (25500 LPM) @ 56F (13C)
42
Typical
Load with
2-Way
Valve
Automatic
Isolation Valve
Pump off ?
40F
56F
16
(4C)
(13C)
(4C)
(13C)
Primary Pumps
6000 GPM
(22700 LPM)
43
Bypass
Closed
Typical
Load with
2-Way
Valve
Automatic
Isolation Valve
40F
56F
14
(4C)
(13C)
(4C)
(13C)
Primary Pumps
6857 GPM
(26000 LPM)
44
Bypass
Closed
Typical
Load with
2-Way
Valve
46
50% Speed
50 % Flow
47
62.3 % Speed
50 % Flow
48
49
Completed..
Busting
Myth #7
51
Up Next....
Chiller Plant
VPF Design
Considerations
52
53
Primary Pumps
1650 GPM (6200 LPM)
Each
3300 GPM (12000 LPM)
@ 57F (14C)
54
41F
3300 GPM
(12000 LPM)
(5C)
Bypass
Closed
Typical
Load with
2-Way
Valve
Load = F X DT
DT = 16 = 57- 41
DT = 32
LCHWT = 25!
1650 GPM
(6200 LPM)
57F
(14C)
Primary Pumps
3300 GPM
(12000 LPM)
55
1650 GPM
(6200 LPM)
41F
(5C)
Bypass
Closed
Typical
Load with
2-Way
Valve
57
58
Automatic
Isolation Valve
Pumps
off
52F
(11C)
Primary Pump
776 GPM (2900 LPM)
(one operating)
40F
(4C)
Bypass Open
326 GPM
Typical
Load with
2-Way
Valve
(1234 LPM)
@ 40F (4C)
Flowmeter
60
Completed..
Chiller Plant
VPF Design
Considerations
61
Up Next....
Review
Myth #8
62
18000 GPM
Condenser
Water
Pumps
63
Bypass
100 % Cooling
Tower Fan Speed
Plant Energy
Higher or Lower?
64
65
P/ S - LOAD
BASED SEQ
VPF - ENERGY
BASED SEQ
Chilled Water
Pumps
1,374,000
629,000
628,000
Condenser Water
Pumps
1,424,000
1,464,000
843,000
Cooling Tower
Fans
1,100,000
1,100,000
569,000
Chillers
12,855,000
8,577,000
9,307,000
Total
16,754,000
11,770,000
11,349,000
66
P/ S - LOAD
BASED SEQ
VPF - ENERGY
BASED SEQ
Chilled Water
Pumps
1,374,000
629,000
628,000
Condenser Water
Pumps
1,424,000
1,464,000
843,000
Cooling Tower
Fans
1,100,000
1,100,000
569,000
Chillers
12,855,000
8,577,000
9,307,000
Total
16,754,000
11,770,000
11,349,000
67
P/ S - LOAD
BASED SEQ
VPF - ENERGY
BASED SEQ
Chilled Water
Pumps
1,374,000
629,000
628,000
Condenser Water
Pumps
1,424,000
1,464,000
843,000
Cooling Tower
Fans
1,100,000
1,100,000
569,000
Chillers
12,855,000
8,577,000
9,307,000
Total
16,754,000
11,770,000
11,349,000
Design Considerations
Chillers
Ensure chillers can provide full or greater capacity at 50-55 F
Entering Condenser Water Temps
At reduced entering condenser water temperature centrifugal
chillers can produce more than design load.
70
71
Design Considerations
Chillers
Ensure chillers can provide full or greater capacity at 50-55 F
Entering Condenser Water Temps
Condenser Flow
Recommend staying at roughly .8 or 80 % minimum flow
Must stay above 3.3 fps or tube fouling becomes asymptotic
Dont vary flow too fast recommend 10% per minute
Dont exceed 12 fps or 45 ft pressure drop for 2 pass (67 for 3 pass)
72
Design Considerations
Cooling Tower
Manufacturers do not like flow varying more than +/- 15 % from Design.
Varying water flow too low
Creates dry spots in fill resulting in large approach increases . (Chiller
energy increases with increased approach)
73
Summary
74
Summary
75
Summary
Summary
77
Summary
Summary
79
Summary
Summary
- Speed does not track flow, and flow does not track load
- Reducing condenser flow and tower air flow saves net
plant energy even though chiller energy increases as long
as those reductions arent too low (80% min typical)
82
Conclusion
- Please type in Q&A box lower right hand corner.
- Moderator will handle questions to presenter.
- Please complete the survey following the webinar
- Webinar will be recorded and available via download or streaming.
Presentation slides will be available in pdf format at www.districtenergy.org
- If you are listening to the webinar recording and have questions, send them
to jill.h.woltkamp@jci.com
- Registration information for the next webinar will be distributed towards the
end of November
84