Professional Documents
Culture Documents
Storm
2013
Earthquake
Wind Storm
Storm
Earthquake
Wind Storm
1976
1991
2012
1990
1970
Storm
2011
Wind Storm
1984
Storm
Volacano
2006
1911
Wind Storm
1984
7,354
6,000
5,956
1,901
1,621
1,551
1,439
1,399
1,399
1,335
1,079
DAMAGE
U$$1,000
1,000,000
Storm
Earthquake
Storm
Wind Storm
Storm
2013
920,000
898,352
709,000
2009
585,379
Wind Storm
435,000
Wind Storm
1990
388,500
Storm
2011
344,173
Wind Storm
319,176
Wind Storm
311,000
Meanwhile, the Asian Disaster Reduction Center (ADRC), which is based in Japan,
analyzed
a
very
similar
database
of
disasters
from
1901
to
2013
(www.adrc.or.jp/databook_20th/). Nationwide, 35 natural disasters were listed; the sum of
people killed reached 57,280; and the sum of the material damage exceeded US$8-Billion.
Both the CRED and ADRC databases list many types of natural disaster, which are listed
below in alphabetical order.
Earthquake
Wild Fire
Flood
Wind Storm
Insect Infestation
The ADRC analysis of the natural disasters indicates the following historical trends.
1. Wind storms lead, in terms of frequency, in total number of people killed, injured, or
otherwise affected, and in value of damage.
2. Earthquakes rank second, in terms of total number of people killed or injured, and in
monetary value of damage. Floods place second, too, in terms of frequency, in total number of
people affected and in monetary value of damage.
3. Volcano eruptions rank third, in terms of number of people killed and in monetary value of
damage.
In summary, the hazards that caused the most disasters were, and still are, as
listed below in the order of overall significance:
Wind storms
Earthquakes
Floods, and
Volcano eruptions
CEMENT
SAND
GRAVEL
REINFORCING STEEL BARS
STANDARD WIRE REINFORCEMENT (WELDED WIRE MESH)
STRUCTURAL STEEL
b.1
To produce concrete, mix cement, sand and gravel with measured quantity of clean
water. Depending upon the mixture and used of the concrete, the strength produced may
varies. (The figure below shows the stress strain diagram for concrete.
b.2 The reinforcing steel bar commonly used in the Philippines is subdivided into three (3)
according to properties:
1. Philippine Standard Structural Grade, Grade 230 fy = 230 MPa (33,000 psi)
2. Philippine Standard International Grade, Grade 275 -fy = 275 MPa (40,000 psi)
3. Philippine Standard Hard Grade, Grade 414 -fy = 414 Mpa (60,000 psi)
Reinforced Concrete is a term when concrete is reinforced with reinforcing steel bar.
TABLE b.3- STEEL REINFORCEMENT INFORMATION ON SIZES, AREAS AND WEIGHTS
Mass, kg/m
0.618
0.890
1.580
2.465
3.851
4.831
6.310
7.986
42
58
1385
2642
10.870
20.729
PLAIN
DEFORMED
Diameter,
mm
Mass,
CENTER-TO-CENTER SPACING, mm
kg/m
50
75
100
150
200
250
300
MW290
MD290
19.22
2.270
5800
3900
2900
1900
1450
1160
970
MW200
MD200
15.95
1.570
4000
2700
2000
1300
1000
800
670
MW130
MD130
12.90
1.020
2600
1700
1300
870
650
520
430
MW120
MD120
12.40
0.942
2400
1600
1200
800
600
480
400
MW100
MD100
11.30
0.785
2000
1300
1000
670
500
400
330
MW90
MD90
10.70
0.706
1800
1200
900
600
450
360
300
MW80
MD80
10.10
0.628
1600
1100
800
530
400
320
270
MW70
MD70
9.40
0.549
1400
930
7100
470
350
280
230
MW65
MD65
9.10
0.510
1300
870
650
430
325
260
220
MW60
MD60
8.70
0.471
1200
800
600
400
300
240
200
MW55
MD55
8.44
0.432
1100
730
550
370
275
220
180
MW50
MD50
8.00
0.393
1000
670
500
330
250
200
170
MW45
MD45
7.60
0.353
900
600
450
300
225
180
150
MW40
MD40
7.10
0.314
800
530
400
270
200
160
130
MW35
MD35
6.70
0.275
700
470
350
230
175
140
120
MW30
MD30
6.20
0.236
600
400
300
200
150
120
100
MW25
MD25
5.60
0.196
500
330
250
170
125
100
83
MW20
5.00
0.157
400
270
200
130
100
80
67
MW15
4.40
0.118
300
200
150
100
75
60
50
MW10
3.60
0.079
200
130
100
70
50
40
33
MW5
2.50
0.039
100
67
50
33
25
20
17
These sections are available in the market with the corresponding strength:
ASTM A7 fy = 33 ksi
ASTM A36 fy = 36 ksi
COMBINED FOOTING
MAT FOOTING
PILE FOOTING
- DRIVEN PILE
BORED PILE
c.3 SUPERSTRUCTURE
c.3.1 Column is a compression member carrying loads from beams and transmitting it to the
footing. It is also a part of special moment frame subjected to bending and axial load.
Under Zone 4, the column, as a member of moment resisting frame must satisfy the following
requirements:
1. Size or Section - The shortest cross-sectional dimension measured on a straight line
passing through the geometric centroid, shall not be less than 300 mm except for
buildings or structures regulated by NSCP Volume 3 and BP 220. The ratio of the
shortest cross-sectional dimension to the perpendicular dimension shall not be less than
0.40
2. Longitudinal Reinforcement or main bar shall have an area A st not less than 0.01Ag or
more than 0.06Ag. .
3. Transverse reinforcement or column ties (seeFig.4.3) is reinforcing steel bars that is used to
enclose the main unprestressed reinforcement throughout the column length.
Recommended sizes to be used are:
for main bar 32mm and smaller ..............................................................................use 10
for main bar 36mm, 42mm, 58mm and bundled longitudinal bars ...............use 12
The location and recommended spacing of column ties are:
At Confined region with a length of Lo
of the minimum of dimension of the member.
6x diameter of the smallest longitudinal bar
So = 100 + (350 hx)
3
The value of the So shall not exceed 150mm and need not be taken less than 100mm.
hx = the dimension perpendicular to the axis of bending
c.3.2 Beam
The length Lo shall be the longest among:
- depth of the member at the joint face or at the section where flexural yielding is
likely to occur,
- 1/6 of the clear span of the member
- 450mm
At unconfined region beyond Lo
Column ties spacing shall be the smallest among:
- 6x dia. of the smallest longitudinal column bar
- 150mm
At joint reinforcement column ties shall be same spacing at confined region.
Beam - is a structural element that is capable of withstanding load primarily by
resisting bending. The bending force induced into the material of the beam as a result of the
external loads, own weight, span and external reactions to these loads is called a bending
moment.
Under Zone 4, beams to be used as flexural members of special moment frames
shall satisfy the following requirements: (see Fig. 4.4)
1. Clear span shall not be less than 4 times its effective depth.
clear span L1 > 4d
2. Width of member shall not be less than the smaller of 0.3h and 250mm where: h =
overall depth of beam
bw
0.30h
250
3. Width of member shall not exceed the width of the supporting member
bw
Width of column
4. The minimum overall depth of the beam unless deflections are computed is given in
Table 4.1
5. Reinforcing Steel Bars
Longitudinal reinforcement:
minimum, Asmin
fc bwd
4fy
1.40 bwd
fy
max As
0.25 bwd
Solid one-way
slabs
Beams or ribbed
one-way slabs
Simply
Supported
One end
continuous
Both ends
continuous
Cantilever
l/16
l/18.5
l/21
l/8
c.3.3 SLAB
a. ONE WAY SLAB
-
The ratio of longer span to the shorter span is greater than 2.0 and due to the huge
difference in lengths, load is not transferred to the shorter beams.
Reinforcement for shrinkage and temperature stressed normal to flexural reinforcement
shall be provided in structural slabs where the flexural reinforcement extends in one
direction
only.
-The ratio of the longer span to shorter span is less than 2.0 and the load is
transferred/carried in both directions.
Design Computations
The minimum requirements of a moment existing frame under Zone 4 Seismic
conditions are:
a.
b.
c.
d. Beam
2nd Floor 250 x 350 with 3-20 top
and bottom bars and hoops 1@50,
10@70, rest@145 O.C
e. Slab
two way slab : 120mm thick with main
reinforcement
short span
continuous:
midspan:
discontinuous:
10 @ 200 O.C
10 @ 250 O.C
10 @ 200 O.C
long span
continuous:
midspan:
discontinuous:
10 @ 200 O.C
10 @ 250 O.C
10 @ 200 O.C
Retrofitting Works
PRACTICAL SOLUTIONS TO SEISMIC
RETROFITTING / REHABILITATION
Jacketing
Posttensioning
Carbon fiber wrap
RETROFITTING: POSTTENSIONING
2 - STOREY BUILDING
Perspective
ROOF PLAN
Roof Beam
2/f Beam
Slab
Column
0.35 F.F.L
0.0 N.G.L
Footing
LONGITUDINAL SECTION
FOUNDATION PLAN
C-PURLINS
TRUSS
ROOF BEAM
CROSS BRACING
SAGROD