i) Draw the system diagram indicating all the impedances and the fault
bus..........................................................................................................3
ii) Use MATLAB to get the bus admittance and impedance matrix......4
iii) Use MATLAB to get the fault in per unit, and kA...........................5
iv) Calculate the rated short-circuit current and the rated momentary
current....................................................................................................6
V) Using inverse IDMT characteristics to compute the value of time
delay and plot the curve.........................................................................7
Vi) Justify the multiplying factor (k) is 1 when X/R ratio is less than 15
................................................................................................................9
3.Conclusion......................................................................................11
4.References...................................................................................12
1. Introduction
A power system consists generation, transmission and distribution. None of the power system in
the world is perfect. A fault issue may occur in any power system. If the fault is not solved, it
may cause problem to the company and the public who are making use of electricity from the
power system. Hence, it is important to analyze the fault issue and solve it as soon as possible. A
case study will be analyzed and a plan will be devised to prevent the fault from damaging the
power system and cause disturbances.
ii) Use MATLAB to get the bus admittance and impedance matrix
The next step is to form to a 33 admittance matrix.(Y bus). The impendence matrix of the 3bus system is just the inverse of its admittance matrix. ([Z]=[Y]-1 )
iv) Calculate the rated short-circuit current and the rated momentary current
Given the R/L ratio is 7, for a 3 cycle(50 Hz) breaker, rated short-circuit current and rated
momentary current able to obtained from MATLAB program.
V) Using inverse IDMT characteristics to compute the value of time delay and
plot the curve
In the Inverse IDMT characteristics, K=1 is the slowest time multiplier. Hence, time
delay is able to compute in the MATLAB given Alpha and Beta. Given I base
=524.8639A, Set I(pickup)=1.2 of I base.
Vi) Justify the multiplying factor (k) is 1 when X/R ratio is less than 15.
Figure 10: K Factor when f=50Hz, Cycle=3 and variable X/R ratio
Figure 11: K Factor when f=50Hz, Cycle=8 and variable X/R ratio
Figure 12: K Factor when f=50Hz, Cycle=14 and variable X/R ratio
(Eq.1)
3.Conclusion
From the case study shown above, applying the fault knowledge enable electrical engineers to
design an adequate protection to the power system in advance. Without setting up protection to
the power system, the power system would not last for several years when fault occurred. In
additional, and it is not wise to keep splurging money to build new power system when it is
damaged since the cost is high. Hence, setting protection devices in power system helps to
prolong the power system lifespan and continues its productivity to the consumers.