Professional Documents
Culture Documents
SESWG/A2300E
Edition 3, 1995-02
2.0
~~t~h.!.n~
!:i~h~n~n~
er~t~c~o-n
er~t~c!!o-n
~e::::e~
~e::::e~
1.5
~~e-d ~~t~g~
1.0
C.?~ti~u-o~s-.ee!.a~i~g-v9:I~~e0.5
cf5:>
~~
~
0.0
o
11
o
o
o
o
o
o
o
.o
o
T-
o
o
o
o
o
o
Current (A)
CONTENTS
Page No
Chapter 1 General intraductian and definitians
1.
2.
Chapter 2
lntroduction
Definition
General
Step 1: Obtain system parameters
Step 2: Check for abnormal service conditions
Step 3: Check for other reasons for TOV occurences
Step 4: Select the continuous operating voltage
Step 5: Select suitable TOV capability
Selection tables
Chapter 4
Chapter 5
General
Step 1: Detertnine the switching parameters
Step 2: Calculate the arrester energy
Step 3: Select an arrester with adequateenergy capability
Step 4: Check capability with respect to lightning energy
1
1
2
5
5
5
6
6
7
7
9
11
11
12
13
13
16
17
1. General
2. Temperature
3. Terminal connectors
4. Ice
5. Wind
6. Determine porcelain strength
7. Earthquake
8. Determine pressurerelief capability
9. Creepagedistances
10. External insulation of surge arresters
20
22
I.
2.
3.
4.
5.
6.
lntroduction
Consideration of the protective characteristics
Co-ordinating currents
Protective rnargins
Protective distances
Extremmelyclose lightning strokes
17
17
17
17
17
18
18
19
19
22
22
24
25
25
28
Chapter
I: GENERAL
D EFINITI
INTRODUCTION
O NS
AND
Introduction
Surge arrestersare the primary protection against different types of overvoltages
(atmospheric or switching). They are generally connected in parallel with the
equipment to be protected to divert the surge currents.
The active elements (blocks) ofABB surge arrestersare manufactured using a
highly non-linear ceramic resistor material composed for the most part of Z nO
mixed with other metal oxides and sintered together. Hence the arrestersare also
commonly called Z nO arrestersor metaIoxide (MO) arresters.A typical
characteristic is shown in Figure 1.1. Further information is available in the
general product literature.
Typical voltage-curreot
characteristics
2.5
"'
Q)
=
~
> 2.0
~
.~i~
-~~i~c-~~~~~
~~ -~-~~~:~~~~~
P!?!~~~?~--~e-v-e}
!~~~~
~
~
g
>
~
~
~
"""'
o
d
ci.
=
~~-- ---~
1.5
I Rated
valtage
1.0
I"-:~
1"
I'J..\)
~tfnuus-pertlng-vorige-lf~
~---~---~~
0.5
0.0
~
-g
~
~
o
q
o
~
ci
o
o
o
Current (A)
Figure
A major difference from the earlier gapped SiC arrestersis the fact that the blocks
are now stressedcontilluously under service voltage as well as under any
abnormal service conditions. It is, therefore, very importallt to dimension the
arrestersso that they can withstand these stressesfor their lifetime. Satisfactory
(stable), thermal behaviour of the arrestersis of vital importance too.
It also makes it necessaryto define the terrninology used and the following
chapter attempts to deal with this in a rational and simpie-to-understand manner.
(For strict definitions refer to Standards.)
Definitions
UnIess otherwise stated hereunder,reference is made to normal A.C. systerns
(15 to 62 Hz).
2.
Max. system voltage (Vm) is the highest r.m.s. phase-to-phasevoltage which occurs
under normaloperation conditions at any time and at any point in the system.
2.2
2.3
2.4
Temporaryovervoltages
(TOV), as differentiated from surge overvoltages, are
oscillatory overvoltages of relatively long duration and which are undamped or
only weakly damped.
Rated voltage (Ur) as per IEC means that an arrester fulfilling the IEC standard must
withstand its rated voltage for at least 10 secondsafter being both preheated to
60OCand subjected to a high energy injection as defined in the standard. Hence,
the TOY capability for 10 seconds,according to IEC, has to be minimum Ur. The
TOY capacity for EXLIM HY surge arrestersexceedsthe IEC requirements.
Additionally, the rated voltage is used as a reference parameter.
2.6
2.7
Impulse
Waveshape (T1/T2)
Tt
= 1 J.ls
Tt
= 8 J.ls
Tt ~ 30 J.ls
Tt = 4 J.ls
T2 ~ 20 J.ls
T2 = 20 J.lS
T2 ~ 60 J.ls
T2 = 10 J.ls
Voltage waveshape
(CWWL:
(LIWL)
(SIWL)
1.2/50
250/2500
50 H z or 60 H z
sinusoidal
Residual voltage (Ures) is the voltage that appears between the tenninals of an
arrester during passage of discharge current through it. It depends on the
magnitude as well as the waveshape of the discharge current and is expressed as a
peak value. For current amplitudes and waveshapes which differ from the
nominal discharge current, Ures is usually expressed in per cent of the residual
voltage for the nominal current.
.
')
10
Switching impulse protection level (SIPL) of the arrester is the residual voltage
for a specified switching impulse current.
Protective ratio is the ratio of the equipment insulation withstand level to the
corresponding protection level of its arrester .
2.14 Protective margin is the protective ratio minus 1 and expressedas a percelltage. As
an absolute minimum, the margin should cover the voltage increase due to the
connections between the arrester and the protected equipment as well as the
increase in the residual voltage due to the discharge amplitude and front-time
being different from the nominal discharge current of the arrester.
2.15
Continuous current (Ic) is the clirrent that flows throligh the arrester at Uc. This
clirrent is predominantly capacitive and is generally expressed as a peak vallie.
Reference current (Irer) is the peak value of the power frequency resistive current
at which the reference voltage is measured.For ABB arresters,the reference
current is in the range 0.4 to 10 mA peak for standard arrester types.
Reference voltage (Uref) is the peak value divided by -.J2af the valtage measured
acrass the arrester at reference current (Iref).
Nominal discharge current
used to classify an arrester .
\
2.19 Single impulse energy capability is the maximum permissible amount of energy,
expressedin kJ, which the arrester is able to absorb in one single impulse with a
specific duration. When expressed~nkJ/kV(Ur), it is called specific single
impulse energy capability.
Earth-fault factor (ke) is the ratio of the voltages in the healthy phases during and
prior to earth-fault conditions. If the system neutral is directly earthed then
ke ~ 1.4 while a resonant earthed or isolated system gives ke as 1.73
approximately.
Pressure relief capability is the ability of the arrester, in the event of its
overloading due to any reason, to conduct the resulting system short-circuit
current through it without a violent explosion which may dammagenearby
equipment or injure personnel. Af ter the operation of the pressure relief, the
arrester must be replaced.
The short-circuit current may be high or low depending on the system impedance
and/or earthing conditions. Hence the-fJfessurerelief capability is verified by both
high and low current tests.
Chapter
2: MA TCHING
ARRESTERS
SYSTEM
p ARAMETERS
(Selection
of Uc and Ur}
TO
General
2.
Earth-fault canditians.
The most commonly known TOV is that at single line-earth fault. The amplitude
is given by multiplying Um/--j3by the earth-fault factor ke which in tum is
determined from the earthing conditions. Figure 2.1 gives the vallie ofke
depending on the system sequencereactancesand resistancesfor the most
unfavourable fault resistance.Should these system parametersbe unknown, ke is
estirnatedas 1.4 for directely earthed systernsand 1.73 for resonant earthed or
isolated neutral systerns.
Xo/X
Figure 2.1 Curves showing re1ationshipbetween Ro!Xl and Xorxl for constant va1uesof earth fault
factor ke. (Source: IEC)
Ro = zero sequence
resistance
Xo = zero sequence
reactance
Xl
= positive
sequence
reactance
The duration dependson the fault-clearance time and if this is not known, it is
estirnated as 1 to 3 secondsfor directly earthed HY systernsand 3 to 10 seconds
for directly earthed distribution systerns.For isolated neutral or resonant earthed
systerns,the duration is important as it may vary from a few secondsto some
hours depending on whether fault-clearing is used or not. For anticipated fault
durations over 2 hours, the TOY should generally be considered as continuous (in
most cases)and the arrester chosen accordingly.
occurrence are rare, it may be justified to accept a risk of arrester failure instead
of selecting an arrester with a higher TOV capabilityand thus a higher protective
level.
If dliring a load rejection, an earth falilt is encolintered, the TOV on the healthy
phasestends to rise flirther than it wolild if the events occlirred singly.
5
In a 3-phase system with the arresters connected phase-ground, Uca=Um!-.J3. If the
system does not have abnormal service conditions outlined in step 2 above, Uc
therefore should be equal to or higher than Um!-.J3.To make the selection easier,
the tables in the relevant catalogues contain all the system voltages as per IEC
(and some other commonly found system voltage) and corresponding
IIcommon-choice arresters ".
It should be noted that if the actual system voltage is not above the voltage given
in the tables, all arresters listed for that specific system voltage are equally
suitable concerning the continuous operating voltage. Only if the actual voltage is
higher, then the column which shows Uc for each arrester must be used to make a
proper selection. The required Uc is then calculated as the actual system voltage
divided by -.J3,and an arrester with higher or equal Uc should be selected from the
table.
6.1
In general, surge arresters are not used to protect equipment against TOV as this
would require an enormous number of parallel columns of blocks. Such
applications may be considered on ly in cases of limitation or elimination of
resonance TOV. Careful detailed studies are required in such cases to select
arresters with suitable energy capability.
TOV
capability
The short-circuit impedance seenfrom the arrester during TOV conditions plays
an important role in determining the energy requirement for the arrester. Figure
2.2 exemplifies this for an arrester type EXLIM P-A.
Figure 2.2
As seenfrom the curves in Figure 2.2, the arrester could withstand 10 times
longer prospective TOV at 1.3 p.u. if the short-circuit current is reduced from
40 kA to 0.5 kA r.m.s. On the other hand, the arrester current is too low at 1.1 p.u.
to affect the prospective over-voltage even at only 0.5 kA r.m.s. short-circuit
current.
Other factors affecting TOV capabilityare energy absorbed (i.e. the initial
temperature of the blocks) prior to the application of TOV and the applied voltage
following the TOV.
For a given arrester type the rated voltage (Ur) is a measureof its over-voltage
capability. Hence, the additional TOV capability of the arrester can be specifled
as a multiple of Ur as shown in Figure 2.3. This approach is used for all EXLIM
arresters.(A different philosophy adopted by some manufacturers is to give the
TOV capability in multiples of Uc.)
p expressed
--::. 1.3
E-o
'-"
...
1.2
-5
1.1
u
~
00
~
~
-1.0
"'
>
~
0.9
0.8-
0.7
~~
.II
,.
()'
~.
,().
11111
'...'
.().~
...~
...()~
P-A & P-B
P-C
.().-
.0.-
,0
.00
Time (s)
(Ur)
2.3
The curves in Figure 2.3 are established by tests with power frequency voltage.
For TOV with lower frequencies, the same curves may be used.
For frequencies higher than a power frequency of 50 or 60 Hz, it can be assumed
that, for the samevoltage amplitude, the arrester withstands the same time in
secondsas for power frequency if the duration is less than lo s. In other cases
ABB has to be consulted.
6.2
The following procedures should be adopted for selecting an arrester with sufficient
TOV capability:
.
'.
For other
..
It
cases,
see Figure
ti
2.1.
UrI = TOVI!TrI.
Ur2 = TOV2!Tr2
etc.
Select a final rated voltage, Ur, which is the highest of the vallles uro, Ure,
UrI, Ur2
Ur n. If this is a non-standard rating, choose the next higher rating
from the cataloglles.
Selection tables
For the most common 3-phase systerns,ABB recommends arrester ratings as per
table 2.2, basedon the following assumptions in table 2.1.
Assumptions
TOV in p.u. of
Um!--j3
Fault duration
Prior energy
1.55
1.5
1.73
I s
rated
1s
rated
lOs and 2 h
rated
Table
2.1
Directlvearthed
l System
Fault-clearance
time
Arrester type
Single impulse
energy
capability
kJ/kV Ur
Vm
kV
4
7
12
18
24
36
45
52
60
72
84
100
123
145
170
245
300
362
420
550
~ Is
EXLIM
P&T
EXLIM
Q
4.5
71)
EXLIM
R
2.5
EXLIM
P&T
71)
10
EXLIM
:s;
EXLIM
4.5
2.5
EXLIM
P&T
102)
102)
133)
133)
133)
Ur
kV
Ur
kV
EXLIM
71)
102)
Ur
kV
12
12
12
15
15
18
21
21
24
30
30
33
36
36
42
42
42
48
48
48
60
60
60
66
66
66
84
4.5
Ur
kV
6*)
9
15*)
21
27
42*)
54
60
66
84
96
120 *)
84
84
96
96
96
120
120
120
132
144*)
162 *)
132
132
162
192*)
192
192
228
276
330
420
Table 2.2 Recommended rated voltages for ABB arresters type EXLIM T, P, Q and R. Selection
based on assumptions as per table 2.1.
l) Energy capability for EXLIM P-A and EXLIM P-B
2) Energy capability for EXLIM T
3) Energy capability for EXLIM P-C
*) Note! For these rated voltages refer to catalogue data for the next higher system voltage.
10
2h
EXLIM
R
2.5
Chapter
3: MA TCHING
SYSTEM
ARRESTERS
p ARAMETERS
(~:nergy withstand
1
TO
capability)
General
If the surge travel time of the lille is short compared with olle cycle of
power-frequency and Zl representsa low impedance, the current through the
arrester will have a rectangular shapewith a duration equal to twice the travel
time T of the w ave on the lille. The current through the arrester and its residual
voltage at this current are given by the intersection of the relevant switching surge
characteristic and the load lille and can be determined by plotting a load diagram
as in Figure 3.2.
UL
Z
la
Ures
=
=
=
=
Prospective overvoltage
Line surge impedance
Surge arrester current
Surge arrester residual voltage
I1
In a real case, the arrester current does not have a pure rectangular wavefoml. The
-source irnpedance,Zl, will affect the voltage w ave irnposed on the line at
breaker-closing, the voltage w ave will be distorted during its travelon the line,
return waves will causereflections at the sending end and, for rnulti-phase
systerns,the phaseswill interact.
However, this simple single-phasemodel is useful in many cases.To avoid
expensive computer and/or transient network analyser (TNA) studies, the
simplified method can be applied as a first attempt to estimate the arrester stresses
causedby switching. If these calculations reveal high energies and the need for
more qualified studies than had been considered initially, a more accurate study
would be justified.
Different types and makes of arresterscould also be easily compared when high
absolute accuracy in calculated stressesis not required.
Step I: Determine
the switching
parameters
In order to use the simplified method, the parameters in Figure 3.2 must be
determined in some way. Typical vallles for different system voltages are given in
table 3.1.
Under 145
145 to 345
362 to 525
765
450
400
350
300
3.0
3.0
2.6
2.2
Table 3.1
12
Location of measurements
End of the line O
Kind of operation
Closing .
3-phase reclosingo
~mgle-step closrng
Resistors
Yes. NoO
Feeding network
Complex.
InductiveO
Parallel cornpensation
~o%.
<50%0
I Nr.
of evaJualed
varianIs
17 I 8
Max
M~j
i
~
1.
Figure 3.3 Evaluation of overvoltage factors (2% values) dependent on kind of operation, closing
resistors, feeding network and parallel compensation. (Source: CIGRPlELECTRA)
UL
Ures
with adequate
energy capability
13
ARRESTER TYPES
EXLIM
EXLIM
EXLIM
EXLIM
EXLIM
2
3
4
5
5
Table
R
Q
P-A and EXLIM
T
P-C
P-B
3.2
Note! The parameters of the lille discharge classesin IEC 99-4 standard result in higher energy
stressesfor the same residual voltages whell compared with the classesin the standard for
non-linear gapped surge arrestersIEC 99-1/1991.
~
~
>.. 5
u
.0
"u
&
~
4-
\'
,\,
'. '\
.'\~~
5'-,
-~
3-
-\ \ ,',, , ,
..,
1
\
o
1
I\\~
l
3
4
Ures / Ur
Figure 3.4 Specific energy in kJ per kV rated voltage, Ur, dependent on the ratio of switching
imptilse residual voltage, Ures,to the rms valtie of rated voltage, Ur, of the arrester.
Parameter: Line discharge class. (Source: IEC)
Nate! Due ta required test ta1erances, the actua1 test energies are usua11y 10-20% higher.
14
For a specific ABB arrester, an estimate of the energy absorbedin the relevant
lille discharge class test could be obtained by using the arrester switching surge
protective level from the catalogues and checking for absorbedenergy in Figure
3.4. This value is then compared with the required discharge energy from the
equation 3.1.
The IEC line discharge test coffiprises repeated discharges and the thermal
stability of the arrester has to be verified for t wo consecutive discharges with 50
to 60 seconds between theffi. For single operations, the ABB arresters could be
stressed with a higher energy equal to the single iffipulse energy capability.
tl
u sually , the design case has a very low probability of occurrence and it is
sufficient, therefore, to design for olle single operation and not for t wo
consecutive discharges.The single impulse energy capability is given in table 3.3.
EXLIM p-C is a double column arrester for which both good current and hence
energy sharing are ensured in routine tests.
Arrester Type
Specific single
impulse energy
capability
kJ/kV(Ur)
Approx crest.
current for
4 ms rectangular
w ave
A
EXLIM
EXLIM
EXLIM
EXLIM
Q
P-A and EXLIM
T
EXLIM
P-C
P-B
2.5
4.5
7.0
10.0
13.0
300
600
1000
1400
1800
Table 3.3 For all arrester types the full energy can be taken for any impulse with equivalent
rectangular shape and duration 4 ms or longer.
If the chosen energy capability is not sufficient, the most economical solution is
to increasethe arrester rated voltage. If this leads to ullacceptable protection level,
then select another type with a higher energy capability. Arresters with energy
capability in excessof the values in table 3.3 are quoted on request.
In some casesparallel arrestersmust be used to meet high energy requirements.
The arrestersmust then be properly matched together to ensure a sufficiently
good current sharing. This matching of the arrestersmust be specially requested.
With standard arrestersfull current sharing is not necessarily ensured.
15
energy
At lower system voltages (below 200 kV), the energy due to switching will
generally be low. At the same time, less attention is paid to effective grounding
and shielding of such systerns.Hence, the design capability will be determined by
lightning stresses.
A conservative estimate for the arrester energy capability for lightning surgesis
obtained in the high current test using 4/10 impulse. This w ave subjects the
arrester to a high energy during a very short time and hence to a thermal shock as
weIl. Note that dischargesof the amplitudes stipulated in the tests occur with a
very low probability in real situations. Furthermore, the real impulse duration
may be longer than the stipulated test impulse duration.
The standard peak current amplitudes are 65 kA and 100 kA as per ANSI/IEC,
ABB arresters withstand even higher currents as seen from table 3.4.
High current withstand
(2 shots, 4/10 impulse)
kA crest
Arrester
Type
EXLIM
EXLIM
EXLIM
EXLIM
EXLIM
R
Q
P-A and EXLIM
T
P-C
P-B
100
100
100
150
200
Table 3.4
An arrester with blocks of larger diameter will withstand the lightning stresses
better for t wo reasons:
l. The current density will be lawer .
2. The residual valtage will be lawer and cansequently alsa the energy discharged.
For this reason, it is advantageousto choose an arrester with larger diameter
blocks (and consequently a higher discharge capability) for:
.
Important installations.
16
Chapter
4: MA TCHING
THE
MECHANICAL
CHARACTERISTICS
General
It is equally important that the arrestersare mechanically so designed that they
can withstand normal as weIl as specifled abnormal service conditions.
Some of these conditions are detailed here.
Temperature
ABB arrestersare designed for mean alnbient temperaturesin the range -40C to
+45C.
While temporary increasesup to +60OCmay be permissible, in general
temperatureshigher than +45C need de-rated special designs and ABB should be
consulted.
Similafly, for alnbient temperatureslower than above, the arrester sealing system
has to be specially designed and ABB should be consulted.
Terminal
connectors
The lille conductors, when connected to the arrester lille terminals, impose a load
on the terminals as weIl as a bending moment at the arresterbase. Both these
values can usually be reduced to acceptablevalues by use of lighter tee-offs and
clarnps. Note that arrestersdo not carry current continuously and hence should
not be connected with conductors of heavy cross-section.
Ice
Ice on the leads to the arresters will contribute to an increase in the terminal
loading and must be accounted for .
Wind
Heavy wind increasesthe horizontalloading on the arrester.Wind velocities up to
100 km/h are generally not a problem. The wind velocity (in mls) can be
expressedas a pressure, Pw = 1/2 x p x v2 (in N/m2). The force on the arrester
surface, according to Htitte, is then expressedas:
Fw
p
v
d
kw
Pw x 1 x d x kw, where
air density at 20 C = 1.293 kg/m3
velocity (mls )
arrester height (m)
mean arrester diameter (m)
correction factor for cylindrical
4.1
Fig. 4.1
For system
voltages
(kVffilS)
EXLIM R-A
EXLIM R-A
EXLIM Q-B
EXLIM Q-A
EXLIM Q-A
EXLIM P-A
EXLIM P-B
EXLIMT-A
EXLIM P-C
~24
~36
~24
;?:36
Minimum breaking
moment (Nm) acc. to
DIN 48113
1600
2500
2500
1600
6000
6000
12500
12500
16600
Table4.1
Earthquake
For areaswith high seismic risks, the arresterswithstand capability against
seismic forces should be verified. Different specifications exist and in general
ABB should be consulted. Reference is also made to Technical Information
SESWG/A 2382 E: Earthquake Design ofABB Arresters.
18
I
Pk
Vm =
EXLIM
EXLIM
EXLIM
EXLIM
EXLIM
EXLIM
50/65
65
R
Q
P-A
P-B
T
P-C
*)
65
80
80
65
*) ActuaI current class depends on arrester rated voltage. For a specific rated voltage consult
catalogues.
Table
4.2
Pollution performance
For a given pollution level, the perfonnance of gaplessarresterscan be improved
in general by employing any or all of the following measures:
.Increasing
current.
.Using
capability.
.Improving
the TOV capability, that is by increasing the rated voltage (Ur) for
the same arrester type.
.Improving
.Using
blocks with lower losses at Uc
ABB arrestersalready employ blocks with very low losses and the heat transfer
mechanism is optimised for these blocks. Thus, pollution performance is
improved by using one or more of the first three methods. In this connection it is
important to note that an increasedUc (without corresponding improvement in
TOV capability) is not effective.
19
ABB arrestersare designed to meet different pollution levels as per table 4.3
Creepage distance (I)
Pollution level
il
m
IV
-Light
-Medium
-Heavy
-Very heavy
16
20
25
31
(I) For the actual creepage distance, the specifled manufacturing tolerances are applicable
(see IEC).
(2) Voltage corresponding to the highest voltage for equipment (phase-to-phase).
Table
4.3
External
insolation
of sorge arresters
20
The EXLIM surge arresterscornply fully with both the IEC and ANSI and thus
the probability of external fiashovers due to overvoltages in service is extremmely
low.
A camparisall
af the bath
standards
tabulated:
IEC *)
>,
u
=
~
5~
4-;
ANSI
Ur < 200 kV
Ur ~ 200 kV
1.06/"2 x SIPL
for arresters with
In = 10 kA and 20 kA
Not applicable
0.82 x SIPL
1.25
Not defined
&
or
0.88/"2 x LIPL
for arresters with
In = 1.5 kA, 2.5 kA and 5 kA
SIWL
Not applicable
LIWL
~
~
*) All
**)
All
**)
installations
installations
x SIPL
1.42 x LIPL at 20 kA
for all arresters
~ 1000 m
~ 1800 m
21
-Chapter
5. PROTECTION
SELECTION
PHILOSOPHY
OF PROTECTIVE
CHARACTERISTICS
Introduction
The overvoltage protection of a substation is not only a question of which
arrestersto choose. For protection against close lightning surges it is even more
important to install the arrestersin the most efficient way. By means of
oscillograms from different calculations the importance of short leads and short
distances between the arrestersand the object being protected can be seen.
Further, they show the great benefit of additional arresterson the incoming lines
outside the line breaker.
The possible reduction in insulation levels using improved surge arrestershas
become even more obvious with the introduction of Z nO arresters.However, this
will require a closer look at the actual installations and the arrester locations in the
substations. Arresters on the incoming lilles as weIl as at the transformer may be
necessary.Complex and especially important installations are best analysed using
computer analysis. The following chapter, however, presentsgeneral guidance
basedupon simplified considerations.
Consideration
Usually residual voltages for 8/20 as weIl as 30/60 currents impulses are given.
For co-ordination against even steepersurges,a voltage level for a current
impulse with virtual front time 1 J.ls,the steepcurrent, is presentedexplicitly or in
per cent of the 8/20 impulses.
According to IEC, actual test current w ave may have a virtual time to half value
of less than 20 Jls. The current w ave, therefore, is designated 1/(2 -20) here.
22
Diagraffis could also be used to show the protective characteristic as in Figure 5.1
for arrester type EXLIM P-A.
P-A
8/20
160
I=40kA
<
... 150
o
I = 20 kA
-..I
o;:;
140
= 15 kA
-I=10kA
~e
I=
130
--I=
5kA
3kA
120110
100
90
80
0.1
0.5
1.0
10.0
Front time of voltage
(~s)
Figure 5.1
In this figure, the residual voltage is given in per cent of the residual voltage at the
nominal current for different times to voltage crest with the current amplitude as
parameter. This approach based on time to crest of voltage w ave is mainly
adopted by countries following ANSI standard.
The residual voltages are detennined with three current waves having virtual front
times of 8, 2 and 1 ~s. The actual time to voltage crest, which will be somewhat
shorter than for the current, is measuredand then the curves are extrapolated
towards shorter times.
The residual voltage which is obtained at a time to voltage crest of 0.5 ~s is
referred to as the "equivalent front-of-wave discharge voltage". Withstand curves
for equipment which shall be protected by the arrester could then be plotted in the
samediagram to check if a sufficient safety margin exists.
It must however be pointed out that for this type of very steep voltage w ave the
effect of connection leads as well as the distance between the arrester and the
protected equipment must be considered in order to determine an exact voltage
stresson the equipment.
23
Figure
8/20
5.2
It should be noted that the characteristic for switching surges with longer front
times is below the 30/60 curve.
In figure 5.2 the residual voltages are plotted in per cent of the guaranteed
residua! voltage at 10 kA 8/20 cuITentimpulse. This is in line with the
IEC standard where the protective characteristics shall be determined in multiples
of a residual voltage determined in routine tests. For ABB arrestersthis
coITespondsto the residual voltage at lOkA 8/20 current impulse except for
double column arresterstype EXLIM P-C for which the 20 kA residua! voltage is
used. The approach based on per cent will be the preferred ABB way of
presenting the protective characteristics.
Co-ordinating
3.1
LIWL co-ordination.
currents
24
The waveshapeof the current is usually taken as 8/20. For shorter front time of
the current w ave, the residua! voltage shows an increase of less than 10% with a
reduction in front time from 8 to 1 ~s. However, much more important than this
small increase is to consider circuit inductances and distance effects when arrester
protection is wanted for shielding failures or for back fiashovers close to the
station.
3.2
SIWL
co-ordination.
0.5
145 -362
420
Table
-800
5.
The w ave shapeof the cuuent is assumedto be 30/60. For even longer front times
the deviation in the residual voltage from the 30/60 w ave (for the same cuuent
amplitude) is very small, within a few percent.
Protective
margios
The protective level and the electrical withstand of the insulation changes
depending on the steepness,duration and amplitude of the applied impulse. The
protective margin has to be fairly large, therefore, especially if long separation
distancesexist, or if protection against close lightning strokes is necessaryand
only olle set of arrestersis used inside the substation. A better solution then may
be to install arrestersalso on the incoming lille or lilles.
Protective distances
One can as well ask w hy a high protective margin is required. The answer is that
the calculated protective margins are only valid if the arrester is directly mounted
on the protected object. When there are connection leads and a distance between
arrester and object, then the protected object will be subjected to a higher
overvoltage.
The situation is illustrated in Figure 5.3
25
The old generally-used fonnula to estimate the voltage increase due to distance
effects gives:
u =
U
Ures
S
L
v
The simplified method for rough calculations should be used with sofie caution.
It does not take into account any capacitanceof the protected object, nor inductive
effects nor the initial voltage at the instant of surge.
A comparison between the simple formula and a computer calculation is shown in
Figure 5.4 for a case with a 145 kV transformer with LIWL 650 kV protected by
an arrester type EXLIM P-A with rated voltage 120 kV using the following
assumptions:
Length of the arrester
and connection leads:
Incoming surge:
Arrester LIPL:
26
6m
800 kV with steepness 1200 kV/~s
276 kV
Arrester
protective
Comparison
distance
-simplified
method
and
computer
calculations
System voltage: 145 kV. Arrester type and rated voltage: EXLIM p 120 A
Ampl. ofincoming surge: 800kV. Steepness: 1200kV/fls.
1nitial voltage at instant of surge: -145/..J3 x ..J2kV peak.
800
>
~
'"-"
...
~ 700
~
c2
"'
600
.:::
~
~500
;:::.
;:>c400
Simplified
300
200
method
...Computer
calculations
--Computer
calculations
for transf.
15
20
Ii.
25
30
I
3511~~-~-~--r~I
40
45
cap. = 2 nF
50
55
60
10
Distance
point
Figure 5.4
As shown, the simplified method gives a result on the safe side if no capacitance
is assumedfor the transformer. This is mainly due to the fact that the Z nO arrester
starts to conduct before the protective leve1276 kV is reached. On the other hand
if the transformer capacitance is say 2 nF, the simplified method shows a
protective margin which does not really exist for distances less than 40 m.
Rough estirnation, therefore, could be troublesorne if srnall rnargins between
arresterprotective level and transformer LIWL are used. Furthermore, the
irnportance of short distances and connection leads cannot be over-ernphasizedin
suchcases.
In table 5.2 protective distances based on computer calculation are given for some
"common choice arresters" as per table 2.2 in chapter 2.
Power
..
frequency
voltage
crest
value
with
opposite
polarity
at instant
of
mcommg surge.
.
Increase in arrester residual voltage for current impulses with shorter front
times than the standard 8 ~s for the nominal current.
27
System Incaming
valtage w ave
LIWL af Surge
pratected arrester
abject
kV
245
kV peak
kV peak
2000
1300
type
EXLIM
1200kV/~s
2000kV/~s
ffi
ffi
P330-B
P360-B
24
16
10
1500
1175
P276
Q276-A
30
27
14
12
1300
1050
P192-A
Q192-A
55
50
27
25
800
650
P120-A
Q120-A
R120-A
37
35
24
16
15
10
Table 5.2 Protective distances for some "common choice" arresters based on computer
calculations.
Note! For longer length of connection leads plus arrester height the protective distance decreases;
for shorter the protective distance will be longer.
For further infonnation
protection" .
Extremely
Guidelines
for station
28
9
~
~
..
~
~
i
j
.1!
~
g
'5
o:
~
<
~
~
.
~
u
.
c
"-
ABB 8witchgear AB
8urge Ar~ester Division
Dept. 8E~WG/AF
8-771 80 LUDVIKA,8weden
Tel. +4624082000
Telex 74507 abblu s
Telefax +46240 17983
~
i.
~