A. 1.95%
B. 3.39%
C.
D.
3.02%
2.23%
B.
The following data were obtained when a short
circuit test was performed upon a 100 kVA,
2400/240 volts distribution transformer: Esc = 72
volts; Isc = 41.6 A; Psc = 1,180 W. All instruments
are on the high side during the short circuit test.
Calculate the percent regulation at a power factor
of 0.75 lagging.
A. 2.54%
C. 2.62%
B. 2.86%
D. 2.71%
Transformer connection that can transform threephase system to two-phase system and vice
versa
A. Scott or T-connection
B. open delta
C. autotransformer connection
D. wye-delta connection
frequency
voltage
current
voltage and current
C.
D.
power
frequency
indicates that
A. there are 20 turns on primary one turn on
secondary
th
B. secondary voltage is 1/20 of primary
voltage
C. primary current is 20 times greater than the
secondary current
D. for every 20 turns on primary, there is one
turn on secondary
transformer
A. high voltage side is usually short circuited
B. low voltage side is usually short circuited
C. any side is short circuited with preference
D. none of the above
C.
D.
leading
lagging
because
A. load power factor is often not know
B. kVA is fixed whereas kW depends on load
p.f.
C. total transformer loss depends on voltampere
D. it has become customary
D.
Cu loss is small
Unsolved problems
71. EE Board Exam October 1991, April 1994
A 1000 kVA, 6,600/400 volts 60 cycle single
phase core type transformer has the following
average daily load:
Full-load at 0.8 pf for 8 hours
Half-load at 0.707 pf for 10 hours
No-load for 6 hours
Calculate the ratio of full-load copper loss to the
iron loss for the transformer to be most
economical for the above loading.
A. 2.05
C. 2.17
B. 3.09
D. 2.28
THREE PHASE TRANSFORMER CONNECTIONS
72. EE Board Exam June 1990
What should be the KVA rating of each two
transformers in an open-delta bank when the
three-phase balanced load is 290.4 kVA?
A. 155.60 kVA
B. 173.40 kVA
C. 150.25 kVA
D. 167.66 kVA
A balanced 3-phase transformer bank has deltaconnected primary and secondary windings. The
primary to secondary winding voltage ratio is
88.
B. 76, 99
D.
75, 100
1998
The loads of a wye-connected transformer are:
Ia = 10 cis (-30) A
Ib = 12 cis 215 A
Ic = 15 cis 82 A
What is the neutral current?
A. 1.04 cis 72.8 A
B. 0.92 cis 62.5 A
C. 2.21 cis -30 A
D. 3.11 cis 72.8 A
100.
101.
102.
103.
104.
EE Board Exam
April 1988
Two single-phase transformers each rated 75kVA are connected in V-V or open-delta, to serve
a three-phase load of 120 kW at 0.80 power
factor lagging. To prevent the overloading of
transformers, determine the size of the capacitor
in kVAR.
A. 50
C. 30
B. 40
D. 20
105.
106.
107.
108.
109.
110.
111.
112.
113.
114.
115.
116.
C. Stray capacitance
D. Iron losses
117.
118.
A transformer will
work on ____.
A. a.c. only
B. d.c. only
C. a.c. as well as d.c.
D. none of the above
119.
electrically
magnetically
electrically & magnetically
none of the above
120.
A transformer is
an efficient device because it ____.
A. is a static device
B. uses capacitive coupling
C. uses inductive coupling
D. uses electric coupling
121.
A transformer
transfers electrical energy from primary to
secondary usually with a change in ____.
A. frequency
C. voltage
B. power
D. time period
122.
123.
124.
A transformer
does not possess ____ changing property.
A. impedance
B. voltage
C.
D.
current
power
133.
125.
The iron-core is
used to ____ of the transformer.
A. increase the weight
B. provide tight magnetic coupling
C. reduce core losses
D. none of the above
126.
If a transformer
core has air gaps, then ____.
A. reluctance of magnetic path is decreased
B. hysteresis loss is decreased
C. magnetizing current is greatly increased
D. eddy current is increased
127.
128.
129.
A transformer is
so designed that primary and secondary have
____.
A. high leakage flux
B. large resistance
C. tight magnetic coupling
D. good electric coupling
130.
131.
An ideal
transformer is one which ____.
A. has no losses and leakage reactance
B. does not work
C. has the same number of primary and
secondary turns
D. none of the above
132.
The no-load
primary current Io is about ____ of full-load
primary current.
A. 3 5%
C. 30 40%
B. 15 30%
D. above 40%
A.
B.
C.
D.
134.
135.
136.
A transformer
operates poorly at very low frequencies because
____.
A. permeability of core is increased
B. magnetizing current is abnormally high
C. primary reactance is too much increased
D. none of the above
137.
If a power
transformer is operated at very high frequencies,
then ____.
A. primary reactance is too much increased
B. primary will draw large power
C. core losses will be excessive
D. none of the above
138.
The primary
leakage flux links ____.
A. primary winding only
B. secondary winding only
C. both primary and secondary winding
D. none of the above
139.
The effect of
leakage flux in a transformer is to ____.
A.
B.
C.
D.
140.
Leakage flux in a
transformer occurs because ____.
A. iron core has high permeability
B. air is not good magnetic insulator
C. applied voltage is sinusoidal
D. transformer is not an efficient device
141.
142.
Cores of large
transformer are built up to nearly circular crosssection in order to reduce ____.
A. leakage reactance
B. iron losses
C. eddy current loss
D. copper loss
Unsolved problems
143.
144.
145.
146.
147.
April 2004
148.
149.
150.
Which of the
following connection is best suited for 3-phase, 4wire service?
A.
C.
Y
B. Y Y
D. Y
151.
In a three-phase Y
Y transformer connection, neutral is
fundamental to the
A. suppression of harmonies
B. passage of unbalanced currents due to loads
C. provision of dual electric service
D. balancing of phase voltages with respect to
line voltages
152.
As compared to
bank, the capacity of the V V bank of
transformers is ____ percent.
A. 57.7
C. 50
B. 66.7
D. 86.6
153.
If three
transformers in a are delivering their rated load
and one transformer is removed, then overload
and each of the remaining transformer is ____
percent.
A. 66.7
C. 73.2
B. 173.2
D. 58
154.
When a V V
system is converted into a system, increase in
a capacity of the system is ____ percent.
A. 86.6
B. 66.7
C.
D.
73.2
50
155.
For supplying is a
balanced 3- load of 40-kVA, rating of each
transformer in V V bank, should be nearly ____
kVA.
A. 20
C. 34.6
B. 23
D. 25
156.
157.
A. 0.886
B. 0.75
C.
D.
0.51
0.65
158.
A T T connection
has a higher ratio of utilization that a V V
connection only when
A. identical transformers are used
B. load power factor is leading
C. load power factor is unity
D. non-identical transformer are used
159.
The biggest
advantage of T T connection over the V V
connection for 3-phase power transformation is
that it provides
A. a set of balanced voltages under load
B. a true 3-phase, 4 wire system
C. a higher ratio of utilization
D. more voltages
160.
One of the
following statements concerning parallel
operation of transformer, the one which is not
correct is
A. transformers have equal voltage ratings
B. transformers must have same ratio of
transformation
C. transformers must be operated at the same
frequency
D. transformers must have equal
161.
Statement. An
auto-transformer is more efficient in transferring
energy from primary to secondary circuit.
Reason. Because it does so both inductively and
conductively.
Key
A. statement is false, reason is correct and
relevant
B. statement is correct, reason is correct but
irrelevant
C. both statement and reason are correct and
are connected to each other as cause and
effect
D. both statement and reason are false
162.
Out of the
following given choices for polyphase transformer
connections which one will you select for threeto-two phase conversion?
A. Scott
B. star/star
C. double Scott
D. star/double-delta
163.
ATT
transformer cannot be paralleled with ____
transformer.
A. V V
C. Y Y
B. Y
D.
164.
Instrument
transformers are used in a.c. circuits for
extending the range of
A. ammeters
B. voltmeters
C. wattmeters
D. all of the above
165.
Before removing
the ammeter from the current transformer, its
secondary must be short-circuited in order to
avoid
A. excessive heating of the core
B. high secondary emf
C. increase in iron losses
D. all of the above
166.
transformer is made of
A. silicon steel
B. annealed copper
C. seasoned copper
D. aluminum
The core of a
167.
The core of a
transformer is assembled with laminated sheets
to reduce
A. hysteresis loss
B. eddy-current loss
C. magnetic noise
D. magnetizing current
168.
169.
Cooling of
transformers is necessary to
A. increase the efficiency
B. dissipate the heat generated in the windings
C. reduce the losses
D. reduce humming
170.
171.
A 100-kVA,
1100/440-V, 50-Hz single-phase transformer has
100 turns on the secondary winding. The number
of turns in the primary will be
A. 550
C. 2750
B. 275
D. 5500
172.
173.
The copper-loss
and core-loss of a transformer of a transformer at
various loads are as shown below. At what load
will the efficiency of the transformer be a
maximum?
A. Load = 50 kVA, Core loss = 320 W, Copper
Loss = 500 W
B. Load = 40 kVA, Core loss = 320 W, Copper
Loss = 320 W
C. Load = 30 kVA, Core loss = 320 W, Copper
Loss = 180 W
D. Load = 20 kVA, Core loss = 320 W, Copper
Loss = 80 W
174.
A transformer
when supplying a load maintained 11 kV across
terminals. When the load was switched off, the
terminal voltage became 11550 V. What is the
voltage regulation of the load?
A. 11.55%
C. 5%
B. 5.5%
D. 55%
175.
176.
Maximum
efficiency of a transformer occurs when
A. hysteresis loss and eddy current loss are
minimum
177.
The all-day
efficiency of a transformer is the ratio of
A.
B.
C.
D.
178.
179.
For satisfactory
parallel operation of two single-phase
transformers a number of conditions are to be
fulfilled. A number of conditions are written below.
Indicate which of these is not required to be
fulfilled.
A. kVA ratings of the two transformers should
be equal
B. Transformers should be properly connected
with regard to their polarity
C. Voltage ratings of the primary windings
should be suitable for supply system voltage
and frequency. The turns ratio of the
transformer should be equal.
D. The percentage impedance of the two
transformers should be equal.
180.
An additional
condition for parallel operation of three-phase
transformers over single-phase transformers is
that
A. the transformers should belong to the same
vector group
B. ratios of winding resistances to resistances
for the transformers should be equal
C. the transformers should have the same kva
ratings
D. the transformers should not belong to the
same vector group
181.
182.
3780 V
3945 V
3590 V
3850 V
183.
_____current are
wasteful currents which flow in cores of
transformers and produced heat.
A. Residual
C. Sneak
B. Eddy
D. Magnetizing
184.
185.
10 A
12 A
20 A
15 A
static induction
dynamic induction
mutual induction
self-induction
A transformer
operates
A. always at unity power factor
B. has its own power factor
C. at power factor below a particular value
D. at power factor depending on the power
factor of the load
191.
The laminations
are made from
A. low carbon steel
B. silicon steel sheet
C. nickel alloy steel stampings
D. chrome steel sheets
192.
193.
A.
B.
C.
D.
electric circuit
magnetic circuit
winding wire gauge
none of the above
195.
Transformer is
C.
D.
power
power factor
188.
189.
190.
What is common
in the two windings of a transformer?
The principle of
working of working of the transformer is
187.
electrically
electromagnetically
194.
186.
A.
B.
C.
D.
C.
D.
Electric power is
transformed from one coil to the other in a
transformer
A. physically
B. magnetically
196.
Preferably, the
resistance between the primary and the
secondary of a transformer should be
A. as low as possible
B. as high as possible
C. low or high depending upon whether it is
step up or step down respectively
D. high or low depending upon whether it is
step up or step down respectively
197.
Ideal transformer
A.
B.
C.
D.
198.
The reactance of
a transformer is determined by its
A. leakage flux
B. common core flux
C. size of core
D. permeability of the material of the core
199.
The efficiency of
the transformer is normally in the range of
A.
B.
C.
D.
50% to 70%
60% to 75%
80% to 90%
90% to 98%
The resistance of
the low voltage winding of a transformer
B.
C.
D.
201.
The basic
property of the transformer is that is changes the
voltage level of an a.c. signal
A. without changing the power
B. without changing its shape
C. without changing its frequency
D. without changing power, frequency or shape
202.
203.
At every instant
the direction of secondary current in a
transformer must be such as to oppose any
change in flux. This is in accordance with
A. Faradays law
B. Joules law
C. Lenzs law
D. Coulombs law
204.
transformation ratio is
A. E1/E2
B. N1/N2
The voltage
E2/E1
N2/N1
205.
The magnitude of
the mutual flux in a transformer is
A. low at low loads and high at high loads
B. high at low loads and low at high loads
C. same at all levels
D. varies at low loads and constant at high
loads
206.
The concentric
windings are used in core type transformer with
A.
B.
C.
D.
200.
A.
C.
D.
207.
Cross-over
windings are used for
A. high voltage winding of small rating
transformers
B. low voltage winding of small rating
transformers
C. high voltage winding of large rating
transformers
D. none of the above
208.
In an ideal
transformer on no-load, the primary applied
voltage is balanced by
A. the secondary voltage
B. the drop across resistance and reactances
C. the secondary induced emf
D. the primary induced emf
209.
Transformers are
rated in
A. kW
B. kV
C. kWh
D. kVA
210.
211.
air core
closed iron core
aluminum core
open iron core
If in a transformer
the secondary winding are doubled and at the
same time the primary voltage is reduced to half,
then secondary voltage will
A. be halved
B. not change
C. be four times as much
D. be reduced to a quarter
B. 375
212.
The no-load
current of a transformer in terms of full-load
current is usually
A. 1 to 3%
B. 3 to 9%
C. 9 to 12%
D. 12 to 20%
213.
Which is the
common method of cooling a power transformer?
A.
B.
C.
D.
362
220.
A. 3780 V
B. 3945 V
C.
D.
3590 V
3850 V
221.
air cooling
air blast cooling
oil cooling
natural cooling
214.
215.
What is the
efficiency of transformer compared with that of
electrical motors of the same power?
A. much smaller
B. somewhat smaller
C. much higher
D. about the same
216.
The transformer
oil used in transformer provide
A. cooling and lubrication
B. insulation and lubrication
C. insulation and cooling
D. insulation, cooling and lubrication
217.
In any transformer
the voltage per turn in primary and secondary
remains
A. always different
B. always same
C. always in the ratio of a
D. sometime same
218.
In transformer the
purpose of breather is to
A. extract moisture of the air
B. to take insulating oil from conservator
C. to provide cooling to the winding
D. to provide insulation to the winding
219.
A. 292
D.
C.
288
A. 10 A
B. 12 A
C.
D.
20 A
15 A
222.
223.
A 20-kVA, 500-V
load is to be supplied by an ideal step-up
autotransformer from a 400-V source. Find the
current in the common winding.
A. 30 A
B. 40 A
C. 50 A
D. none of these
224.
225.
The current
densities in the primary and secondary windings
of a step don transformer are 1250 and 1500 A
per square inch, respectively. The ratio of
transformation is 10:1 and the mean length per
turn of the primary is 15% greater than that of the
secondary. If the primary winding resistance is 20
ohms, calculate the resistance of the secondary
windings.
A. 0.202 ohm
C. 0.209 ohm
B. 0.219 ohm
D. 0.220 ohm
226.
A 10-kVA,
2000/400 V, single-phase transformer has
primary and secondary winding impedances of
5.0 + j10 and 0.2 + j0.45 ohms, respectively.
Calculate the voltage across the secondary
227.
An open delta
bank, consisting of two-single phase transformers
is operating with balanced three-phase load of
50 kVA, 440 V at 0.8 p lagging and a single
phase load of 10 kW resistive connected across
c-a leg. Determine the minimum ratings of the
transformers. Assume a phase sequence of a-bc.
A. 38.80 kVA, 34.06 kVA
B. 34.32 kVA, 33.40 kVA
C. 35.48 kVA, 36.34 kVA
D. 30.83 kVA, 39.52 kVA
228.
An open delta,
three-phase transformer consisting of two singlephase transformers is operating with a balanced
three-phase load of 50 kVA, 440-V at a lagging pf
of 0.8. Determine the operating pf of each
transformer.
A. 0.393 lagging, 0.993 lagging
B. 0.383 lagging, 0.887 lagging
C. 0.383 lagging, 0.993 lagging
D. 0.393 lagging, 0.887 lagging
229.
Which of the
following given below is the eddy current loss not
proportional to
A. square of the thickness
B. square of the frequency
C. square of the load current of the laminated
core
D. square of the flux density
230.
A transformer will
have negative voltage regulation when its load is
A. capacitive
B. resistive
C.
D.
inductive
both B and C
231.
EE Board Exam
April 1990
Copper loss of a transformer are determined by
means of a
A. polarity test
B. short circuit test
C. open circuit test
D. inductive circuit test
232.
The secondary of
a transformer is connected wye-grounded. The
voltage from line to neutral is 132 volts. If the load
current is 40 amperes, calculate the load in kVA.
A. 5.28 kVA
B. 9.15 kVA
C.
D.
20.11 kVA
15.84 kVA
233.
234.
The secondary
current of a 20 kV/7.97-kV autotransformer is 100
amperes. Determine the current that flows
through the common winding.
A. 60 amperes
C. 70 amperes
B. 100 amperes
D. 50 amperes
235.
Two transformer
are connected in parallel supplying a load of
2,500 kVA. The first transformer has an
impedance of 3% and a rating of 1,250 kVA while
the second has an impedance of 3% and a rating
of 1,500 kVA. Calculate the load shared by the
second transformer.
A. 1453.19 kVA
C. 1363.64 kVA
B. 1792.51 kVA
D. 1227.53 kVA
236.
A transformer has
a core loss of 64 W and a copper loss of 144 W
when it is carrying 20% overload current. The
load at which this transformer will operate at the
maximum efficiency is ____ percent.
A. 80
B. 66
C.
D.
237.
120
75
238.
A.
B.
C.
D.
239.
A.
B.
C.
D.