DM Water System
DMCW system
CW System
ACW System
DS System
Compressors.
Circulating Water: Condensation of steam in condenser
Aux. Cooling Water: DMCW cooling & TG Lub oil cooling.
Service Water: Washing , cleaning & different cooling purpose.
stock pile
Seal Water System: for gland sealing of HP/LP Pp. & HCSS
Charge Pp
BA Zero Discharge System: for bottom ashing
Effects of Impurities
Sodium/Iron/Copper : Boiler/Turbine Deposits.
Bicarbonate Hardness : Boiler/Turbine Deposits
Organics/Oil : Foaming in Boiler Drum
Silica : Boiler/Turbine Deposits
Dissolved O2 & CO2 : Corrosion by localised cell formation
CWR
FM
Flocculation
Tank
ISS
FWR
DMP
Daily Consumption:46000Ton
80 150 ppm
170 ppm as CaCO3
8 12 ppm as SiO2
15 25 PPM as CaCO3
5 10 ppm as CaCO3
5 NTU
7.0 to 7.5
De-mineralisation System
FWR
GSF
ACF
SAC
DG
Blower
DMST
WBA
SBA
MB
De-mineralisation
Clarified water to DM water:1. GSF: removes suspended particles
De-mineralisation
5. WBA(Weak Base Anion): Strong anions are removed
H2SO4 + R-OH = R2SO4 + H2O
HCl + R-OH = RCl + H2O
6. SBA(Strong Base Anion): Weak anions like Si
H2SiO3 + R-OH : R2SiO3 + H2O
7. MB(Mixed Bed): Residual / spillage cations & anions are
removed
DM storage capacity
DMST ( 2 nos) : 1000 Ton
CST (2 nos) : 800 Ton
DMCW circuits
The two DMCW circuits are interconnected through Main
unit-2
Point of usage : All Coolers & Heat exchangers except where
ACW is used
8.5 to 8.8
Conductivity:
3 s/cm
CW system
Number of pumps : Two for each unit (discharge side
interconnection provided)
Water source: Forebay
Discharge valve is hydraulically operated
Supplies water only to Condenser
The water gets cooled in Cooling Tower
Specification of CW Pumps
Make:
WPIL
Capacity:
15500 m3/hr
Speed:
497 rpm
No of stages:
single
Total dynamic head:
26 mwc
Pump efficiency: 89%
Pump input at dynamic pr.:
1233.14 kw
ACW system
Number of pumps : Two for each unit (discharge side
interconnection provided)
Water source : Forebay
Discharge valve is electrically actuated
Return line is connected with CW return line
Supplies water only to TG Lub oil Cooler, Nash pump
cooler, Central AC plant Condenser (new provision) &
DMCW HEX.
Provision of CT blowdown from CW-ACW return line.
The CT blowdown water is consumed through Service water
& Zero discharge make-up.
CWR
Usage : Washing/cleaning, Air Heater & ESP hopper
Jockey
Pumps
There are two Jockey pumps which maintain the water pressure in both
Hydrant & Mulsifyre System
Hydro
pneumatic
Tank
This tank can store sufficient volume of water at 9 Kg/cm2 pressure and
is connected to both hydrant & mulsifyre systems . Two motor driven
compressors maintain the pressure inside the tank
Source of
Water for
Fire
Fighting
Cooling Towers
No. of Cooling Towers: 4
Number of ADPs : 3
IA-1
IA-2
IA-3
IA-4
IA-5
H
O
T
A
I
R
B
U
S
ADP-1
ADP-2
ADP-3
ADP-4
AIR
RECEIVER
Ingersoll Rand
Screw
1
20 m3/min
7 kg/cm2
128 Kw
Thank You