Professional Documents
Culture Documents
LIQUID COOLERS
In the refrigeration process, heat is transferred from
the medium being cooled to the refrigerant as it changes
phase in the evaporator. A refrigerant-to-air, or direct
expansion (DX), evaporator is typically used with smaller vapor compression systems with a higher-pressure
refrigerant, such as HCFC-22, CFC-12, and HFC-134a.
The DX evaporator shown in Figure 35-1 is a finned-tube
coil over which air is passed and thereby cooled.
Large central
air conditioning or
process cooling systems with multiple
terminal units use a
brine or chilled
water cooling system because it is
impractical to circulate large volumes of refrigerant
throughout a facility. In this case, the
Fig. 35-1 Illustration of Fin-Tube Evaporator. chilled water serves
as an indirect or
Source: The Trane Company
AND
FLOW
= 2.4 g pm/ton
(2.6 lpm/kWr )
662
Copyright 2003 by The Fairmont Press.
AND
Chilled
Water
Supply
Constant Flow
Pump
Chilled
Water
Return
663
Copyright 2003 by The Fairmont Press.
Constant
Flow
Chilled
Water
Return
Chilled
Water
Supply
Bypass
Priority
Chiller
Constant
Flow
Constant
Flow
Variable Flow
Drive
Auto Switch
Over
Chilled
Water
Return
refrigeration systems.
In many localities, depending on the particular cooling process, there are periods during the course of the year
when ambient wet-bulb temperature will be sufficiently
depressed to permit the cooling tower (or other heat rejection system) to produce a low enough water temperature
to satisfy the facility cooling requirement. Supply water
temperature can also usually be raised during free cooling
operation in air conditioning applications, because overall
load, and particularly dehumidification load, is reduced as
a result of cool and/or dry ambient air conditions.
Direct water-side free cooling, illustrated in Figure
35-8, bypasses the chiller completely and allows condenser water to flow directly to the load. Typically, the chilled
water pump is bypassed and only the condenser pump is
used. It is critical to ensure that the raw condenser water
from the tower or body of water does not contaminate the
relatively clean chilled water circuit. This system is often
referred to as a strainer cycle, indicating the need for a
strainer or filter. Cooling tower freeze protection is also a
concern, and variable-speed fans as well as basin heating
are often required. While it has proven effective in a number of field applications, the stringent operating requirements and risks associated with this approach have limited
its use.
Chilled
Water
Supply
Bypass
Electric
Chiller
Variable
Flow Drive
Auto
Switch Over
Absorption
Chiller
Cooling
Load
Condenser
Constant
Flow
Valves
Full-Flow
Filter
Chilled Water
Pump
Chilled
Water
Return
664
Copyright 2003 by The Fairmont Press.
Evaporator
Condenser
Pump
Constant
Flow
standard operation. Figure 35-10 is a schematic representation of a vapor compression system designed to operate
as an isolated indirect free cooling loop.
An additional water-side free cooling method, known
as thermal-siphon or refrigerant migration, is accomplished by allowing the chiller itself to function as a heat
exchanger. When the condenser water is at a lower temperature than the chilled water, it is sometimes possible for
the refrigerant to reject heat absorbed from the chilled
water to the condenser water without mechanical compression. A small refrigerant pump may be used. Care
must be taken when switching to normal compressor
operation, since condenser water must be brought up to
safe operating temperatures.
Cooling Tower
Heat
Exchanger
Cooling
Load
Condenser
Evaporator
Condenser
Pump
Chilled
Water
Pump
Heater
Compressor
Cond
Load
Evap
Condenser
Water Pump
Chilled
Water Pump
665
Copyright 2003 by The Fairmont Press.
Liquid Systems
Liquid (water) storage is usually the simplest for heating and cooling applications. In cooling applications,
liquid storage may be applied with a wider range of refrigeration systems than can ice systems, including LiBr-type
absorption chillers. The high specific heat of water, which
is approximately 1 Btu/lbm F (1.16 Wh/kg K), makes
it well suited for TES. Above ground tanks are commonly
made of steel and buried tanks are commonly made of
concrete.
The principle advantages of chilled water storage systems are simplicity and the ability to operate chillers at or
close to normal supply (suction) temperatures. The ability
to operate at relatively high supply temperatures results in
greater chiller performance.
A principle disadvantage of water storage is the
immense storage equipment size and space requirement.
Given the temperature differential range between stored
and supplied chilled water, which is limited to 10 or 20F
(6 or 11C), chilled water storage requires a very large
amount of storage volume. With hot water storage systems, however, a far greater temperature differential can be
used, resulting in a lesser volume requirement for equivalent amounts of stored energy.
Another disadvantage of water storage systems is the
tendency for mixing or temperature blending of the water
returning to storage and the colder stored water. There are
Chiller
Building
Air Flow
Pump
Cooling Coil
Temperature
Control Valve
Storage
System
Ice Systems
The high heat of fusion of ice 144 Btu/lbm (0.093
kWh/kg) makes it an excellent storage medium. Three
common types of ice storage systems are ice builder
systems, ice harvesting systems, and ice slurry systems.
Ice builder systems may operate with DX systems or
brine (typically 25% ethylene glycol/75% water)
chiller systems. The refrigerant or brine coils, which
are submerged in a water storage tank, freeze the
water in their immediate vicinity. The water then
melts when warm return water is introduced to the
tank. Primary concerns with any type of refrigerant
coil system are 1) minimizing bridging of ice between
coils to promote water circulation and increase
exposed ice surface area and 2) creation of the minimal necessary ice thickness to reduce compressor
loading during the build cycle. Typical storage
systems use plastic containers filled with deionized
water and an ice nucleating agent placed in a steel,
concrete, fiberglass, or polyurethane tank. The inventory of available ice can be determined by measuring
the water volume and adjusting for the expansion to
ice (about 9%).
Ice harvesting systems consist of an ice producing
section and an ice/water storage section. Ice is accumulated on the outside of the evaporator in the ice producing section and then drops to storage as hot gas is
passed through the evaporator to break the bond
between the ice and the evaporator wall. Typical cycle
intervals are about 30 minutes. Since the ice floats on
water and does not completely displace its own volume,
inventory of available ice must be determined by water
conductivity or heat balance methods.
Ice slurry systems use a brine solution, which is
cooled to its freezing point where ice crystals form in
its fluid film. The slurry portion is pumped to storage,
where it forms a floating porous ice pack, and the
remaining concentrated solution is re-cooled. The
process is continuous, with the brine solution continually circulating through the evaporator until the
desired stored capacity is reached as indicated by
temperature measurement of the solution in storage at
666
Copyright 2003 by The Fairmont Press.
Eutectic Salts
Eutectic salts change phase at various temperatures.
The most commonly used eutectic salt consists primarily
of sodium sulfate, which has a heat of fusion of 41
Btu/lbm (0.026 kWh/kg) and freezes and melts at about
47F (8C). Other types of eutectic salts may have a higher heat of fusion. Systems typically consist of containers
stacked in a tank with small clearances for chilled water to
circulate. A principal advantage is that cool storage can be
generated with typical chilled water temperatures in excess
of 40F (4C). Their advantage versus ice is that they can
operate more efficiently because they do not have to
produce such low temperatures. Their advantage over
water is that they require half of the space (significantly
more space than ice). Their primary disadvantage is
significantly higher capital cost than conventional water
or ice storage systems.
TES APPLICATIONS
TES applications can be classified into four basic categories: load shifting, downsizing equipment, intermittent
use to improve system performance, and excess capacity
storage.
Load Shifting
Load shifting involves generating thermal energy
during periods when energy costs are lower and storing it
for use when energy costs are higher. This type of application is used almost exclusively with electric motor-driven
vapor compression systems. The basic concept is to generate thermal energy in the form of ice, chilled water, or
other media during off-peak periods when electricity costs
are low, and use it during peak periods when electricity
costs are high. This can be particularly effective in eliminating peak electric demand charges.
Over the past two decades, these applications were a
major focus of electric utility demand-side management
(DSM) and marketing programs. The impetus for the customer is operating cost savings resulting from replacing
the use of high-cost peak cooling season electric usage
with low-cost off-peak usage. The impetus for the electric
utility has been to limit utility system peak demand
and/or to retain loads that might otherwise be lost to nonelectric technologies. Given the reduced emphasis on
DSM, due to the evolving process of deregulation and/or
the condition of excess generation capacity in many
regions, utility support for this technology application has
recently declined. However, with the trend toward
increasingly stratified electricity rates, load shifting
remains an effective technology application for many
facilities, even absent additional utility incentives.
Systems may be designed for full storage where all
of the peak cooling requirements are served by storage; or
partial storage where only a portion of the peak cooling load is met by storage, with the rest served directly by
the refrigeration-cycle machine. Frequently, partial storage
667
Copyright 2003 by The Fairmont Press.
Downsizing Equipment
Given the short duration of design cooling load conditions, the limited use of storage can typically reduce
refrigeration machine capacity requirement by providing
cooling during those limited peak hours. Thus, the refrigeration machine and system auxiliaries, such as the cooling tower and condenser pump, can be sized at a capacity
lower than that of a facilitys full peak requirement. The
stored cold thermal energy, generated during off-peak load
periods, can then be used during peak load conditions to
make up the capacity deficit. With the trend toward market-based RTP electric rates, the availability of a limited
amount of storage capacity may prove economical by providing the ability to eliminate the few most costly kWh
purchased on a given day. As with other load shifting
strategies, it is, however, difficult to predict the optimal
amount of storage capacity.
This strategy can be employed with virtually any type
of refrigeration system. It can also be used when load
growth has exceeded the current chiller or boiler capacity,
or both. Storage can be employed permanently, or as a
stop-gap measure until load growth is significant enough
668
Copyright 2003 by The Fairmont Press.
669
Copyright 2003 by The Fairmont Press.
670
Copyright 2003 by The Fairmont Press.