A100K10864
System CTB-100V
Table of Contents
1. GENERAL...................................................................................................................................................................... 1
1.1
Purpose of this manual ........................................................................................................................................................1
1.2.
Related documents ...............................................................................................................................................................1
1.3.
Publication log ......................................................................................................................................................................1
1.4.
Requirements ........................................................................................................................................................................1
1. SYSTEM OVERVIEW.................................................................................................................................................... 2
2.1.
Introduction ........................................................................................................................................................ 2
2.2.
Features .................................................................................................................................................................................2
2.2.
Optional Equipment.............................................................................................................................................................3
2.4.
Functions & User Facilities. ................................................................................................................................................4
2.4.1
General ..................................................................................................................................................................................4
2.4.2
Line selection / Single call ....................................................................................................................................................4
2.4.3
Signal and extra signal device for substations...................................................................................................................4
2.4.4
Group call..............................................................................................................................................................................4
2.4.5
All call ....................................................................................................................................................................................5
2.4.6
Calls from and between Operation panels.........................................................................................................................5
2.4.7
Call from substations ...........................................................................................................................................................5
2.4.8
Parallel communication .......................................................................................................................................................6
2.4.9
AUX function ........................................................................................................................................................................6
2.4.10
Audio from external audio to All........................................................................................................................................6
2.4.11
Operation of external Public address system. ...................................................................................................................7
2.4.12
Emergency Public address operation. ................................................................................................................................7
2.4.13
Hands free operation............................................................................................................................................................8
2.4.14
Privacy functions ubstation STB-1 .....................................................................................................................................8
2.4.15
Two-way voice communication, Nautical Safety...............................................................................................................8
2.4.16
Monitor loudspeaker............................................................................................................................................................9
2.4.17
External loudspeaker. ..........................................................................................................................................................9
2.4.18
Dimmer of call light..............................................................................................................................................................9
2.4.19
Volume adjustment ..............................................................................................................................................................9
2.4.20
Powersupply SPS-4 (Option)...............................................................................................................................................9
3. INSTALLATION AND CONFIGURATION PROCEDURES ......................................................................................... 10
3.1
General ................................................................................................................................................................................10
3.2
Mounting & Terminal configuration. ..............................................................................................................................10
3.2.1
Central unit CU-100 & CU-200 ........................................................................................................................................10
3.2.2
Operation panel CTB-10 & 20 ..........................................................................................................................................12
3.2.3
CTB-10W / V01, CTB-20W / V01.....................................................................................................................................12
3.2.4
Identification sign plate CTB-panels................................................................................................................................12
3.2.5
Substations and other equipment. ....................................................................................................................................12
3.2.6
Identification sign plate substation...................................................................................................................................12
3.3
Cable requirements ............................................................................................................................................................12
3.4
Power supply requirements...............................................................................................................................................13
3.5
Set priority in CU-100 & CU-200 .....................................................................................................................................13
3.6
Set receive-call from substation. .......................................................................................................................................13
3.7
Set public address zones SPA............................................................................................................................................13
3.8
Volume and signal adjustment..........................................................................................................................................14
3.8.1
Substations ..........................................................................................................................................................................14
3.8.2
Auxiliary and Public address. ...........................................................................................................................................14
3.8.3
Call signal ............................................................................................................................................................................14
3.9
Dimmer on / off in Operation panel .................................................................................................................................15
3.10
Substation STB-1 ................................................................................................................................................................15
3.11
Substation STB-3 ................................................................................................................................................................15
3.12
Substation STB-5 ................................................................................................................................................................15
3.13
Installation for C500 Nautical Safety ...............................................................................................................................15
4. USER INSTRUCTIONS ............................................................................................................................................... 16
4.1
Operation from the operation panel.................................................................................................................................16
4.1.1
Make a call to an substation. .............................................................................................................................................18
4.1.2
Make a call to group of substations. .................................................................................................................................19
4.1.3
All Call .................................................................................................................................................................................20
4.1.4
Handsfree operation...........................................................................................................................................................21
4.1.5
Give signal to substations with extra signal device. ........................................................................................................21
4.1.6
Receive a call from an substation. ....................................................................................................................................22
4.1.7
Receive a call from two or more substations. ..................................................................................................................23
4.1.8
AUX function ......................................................................................................................................................................24
4.1.9
Audio from external audio to All......................................................................................................................................25
4.1.10
Public Address Operation of external system .................................................................................................................26
4.1.11
Emergency Public Address Operation. ............................................................................................................................27
4.1.12
Volume.................................................................................................................................................................................29
4.1.13
Dimming of call light..........................................................................................................................................................29
4.2
Parallel communication .....................................................................................................................................................30
4.2.1
Operation.............................................................................................................................................................................31
4.3
Operation from substations...............................................................................................................................................32
1. GENERAL
1.1
This manual supplies an engineer with the information required to install and commissioning
a CTB-100V system and the end-user with all necessary instructions for operating the CTB_100V system.
Refer to Service Manual for maintenance and repair.
The manual can also be used as a guideline for design and planning of the system.
1.2.
Related documents
1.3.
Publication log
Product / Ver.no.:
CTB Ver.07
Title:
Doc.no. / Rev.
Author:
Verified By:
Revision
00
Issued
2001.09.06
Changes / Comments
First issue, User & Technical Manual
Draft I
2005.10.06
01
2006.06.08
01.1
2007.01.22
A100K10864
2008.08.26
Zenitel Norway AS and its subsidiaries assume no responsibilities for any errors that may appear in this
publication, or for damages arising from the information in it. No information in this publication should be
regarded as a warranty made by Zenitel Norway AS.
The information in this publication may be updated or changed without notice. Product names mentioned in
this publication may be trademarks, they are used only for identification.
Zenitel Norway AS, August 2010
1.4.
Requirements
The CTB system and its components have been tested according to following regulations:
IEC 60533: Second edition, 1999; Electrical and electronic installation in ships Electromagnetic
compatibility.
IEC 60945: Fourth edition, 2002; Maritime navigation and radio communication equipment and
systems - General requirements - Methods of testing and required test results.
IACS E10: Corr. 1 July 2003; Unified environmental test specification Testing procedure for electric
control and monitoring , safety and protection, on board computer based systems and peripherals,
loading instruments, internal communication and other electrical equipment as considered appropriate.
System CTB-100V
4.3.1
Operation from STB-1 .......................................................................................................................................................35
4.3.2
Operation from STB-2 .......................................................................................................................................................35
4.3.3
Operation from STB-3 .......................................................................................................................................................36
4.3.4
Operation from STB-5 .......................................................................................................................................................37
4.3.5
Operation from STB-5GN .................................................................................................................................................38
4.3.6
Operation from HE-112M / HE-112MT ..........................................................................................................................38
4.3.7
Operation from VH-10M / VH-10M-T ............................................................................................................................39
4.3.8
Operation from VHM-10 / VHM-10-T ............................................................................................................................39
4.3.9
Operation from NEBB-42EX / EX Loudspeaker............................................................................................................40
5. COMMISSIONING ....................................................................................................................................................... 41
5.1
General ................................................................................................................................................................................41
5.2
Mechanical Inspection .......................................................................................................................................................41
5.3
Cable Inspection .................................................................................................................................................................41
5.4
Check Configurations. .......................................................................................................................................................41
5.5
C500 Nautical Safety ..........................................................................................................................................................41
5.6
Starting up the system........................................................................................................................................................42
5.8
Trouble shooting.................................................................................................................................................................43
6. INSTALLATION DRAWINGS AND DATASHEET ....................................................................................................... 46
6.1
Installation drawings..........................................................................................................................................................46
6.2
Datasheets............................................................................................................................................................................46
ii
System CTB-100V
1. SYSTEM OVERVIEW
2.1.
Introduction
The Command Talk Back System CTB-100V is specially designed for important communication for use in rough
marine environment. Available in 10 and 20 line version.
The CTB system consist of a central unit CU-100 or CU-200 with up to 4 operation panels
for use on bridge console, bridge wings, engine control room etc. and a comprehensive range of substations and
field equipment for use indoor, outdoor and noisy areas.
The system includes many facilities and can operate together with PA-system to increase functionality and fields
of operation.
Operation panel CTB-20W/V01
Line 2
HP-8
MB-30G ETC-1-TB
Signal unit
P-66
HP-8
Signal unit
P-66
Signal unit
Foot-switch
ON
OFF
VPA-120
POWER A MPL IFIER
230/115V AC MAIN
POWER SUPPLY
DC ok
24V DC OUT
24V DC EMERGENCY
Substation STB-2
Line 10
`
Substation STB-2
Line 11
VML-15T
VML-15
Substation VHM-10MT
Line 12
VML-15T
CD-2
Substation VH-10MT
Line 13
VML-15T
HAS-1
ETC-STB5
Substation STB-5GN
Line 18
Substation STB-5
Line 17
Signal unit
10m cable
Signal unit
VML-1520
P-MT7
Substation STB-3
Line 19
P-66
Signal unit
Substation line 20
100V Ex-loudspeaker Ex-push button box
CEAG
GHG 411
Ui 690V
EEx de IIC T6
2.2.
I 16A
Features
10 or 20 line selection
4 Operation panels
Gooseneck or handheld microphone.
Parallel Communication.
All call / Group Call facility
Public Address Operation
AUX / Alarm input
Hands free operation.
2.2.
System CTB-100V
Optional Equipment
MB-30G
ETC-1-TB
P-66
P-66/10
AW8121
AW8241
P-8501
RS-3D
Portable deck loudspeaker 100V w/ callbox and 10M cable and plug
CD-2
VHM-10
VH-10M-T
Portable deck loudspeaker 100V w/ callbox and 10M cable and plug
HE-112M
HE-112M-T
NEBB-42EX
VML-15T
System CTB-100V
2.4.
Functions & User Facilities.
2.4.1 General
The CTB-100 system consist of 1 central unit CU-100 or Cu-200, 1 to 4 operation panels, 1 to 20 substations or
loudspeakers and one 100V power amplifier. On system with more than 1 operation panel, each panel take one
substation line. The system have one speech channel and operation from one operation panel will be indicated in
other operation panels. The operation panels follows a priority hierarchy 1 to 4, that means operation panels with
higher priority can override operation panels with lower priority.
Operation panel CTB-10 & CTB-10W_V01 with 10 line selection, CTB-20 & CTB-20W_V01 with 20 line
selection. CTB-20 used in the presentation.
|
2.4.3
2.4.4
Group call
Group of substations or other operation panels can be selected by
pressing respective number of line buttons. Indicated with steady green
LED.
2.4.5
System CTB-100V
All call
All call message can be distributed from any operation panel to all
substations and other operation panels.
All call message will also activate Public Address System if connected.
Indicated with steady green LED in the ALL push button.
10
2.4.6
11
20
2.4.8
System CTB-100V
Parallel communication
PTT
PTT
SWITC
H
SWITC
H
2.4.9
AUX function
External entertainment, message or alarm can be distributed trough the
CTB system by using push button switch AUX together with line
selection switches.
0dB signal from the external system connected to the CTB system will
be addressed to selected substations.
AUX
10
11
20
System CTB-100V
I
0
Note! Other operation panels with higher priority can override the PAmessage.
ON
OF F
VPA-120
POWER AMPL IFI ER
In order to comply with PA-requirements, two PA call stations are required: The CTB-100V system are designed
for use with up to four operation panels that can be used as Emergency call stations. In addition one or more All
call station (Ex. Lifeboat stations) can be used as Emergency call stations.
Following functions:
Mute of the External Alarm System (General / Fire Alarm)
Operation panel with 1st priority, normally bridge, can override other operation panels.
Type of Operation panels/ Emergency call stations:
CTB-10 Operation panel 10 line selection, indoor use. Hand or gooseneck microphone.
CTB-10W/V01 Operation panel 10 line selection, WP. Handmicrophone only.
CTB-20 Operation panel 20 line selection, indoor use. Hand or gooseneck microphone.
CTB-20W/V01 Operation panel 20 line selection, WP. Handmicrophone only.
VMT-603 All call station WT with handmicrophone.
System CTB-100V
Option 2
Parallel station type STB-6GN with gooseneck microphone MB-30G and
footswitch U2410.
Foot-switch
CENTRAL UNIT CU
JUNCTION BOX
System CTB-100V
230/115V AC MAIN
24V DC EMERGENCY
POWER SUPPLY
DC ok
24V DC OUT
The power supply SPS-4 is designed with power failure contact and
automatic switch over relay.
It means indication and automatic switch over to 24V DC emergency
power supply when mains supply or power module fails.
System CTB-100V
General
For proper installation and operation of the CTB-system we recommend to read this section
thoroughly together with installation drawings in chapter 6.
Make sure that all mounting and cabling are correct before switching on the system
3.2
Mounting & Terminal configuration.
3.2.1 Central unit CU-100 & CU-200
The central unit is the basis of a system. It should be bulkhead mounted in a normal and ventilated indoor
environment with a temperature of max. 550 C. See drawing CU_dd for mounting details.
Note ! Make sure that it is sufficient space for cables and maintenance.
It is equipped with pluggable screw terminals for cables max.2,5mm2
Fig. CU-100 See drawing CU-100_lo for further details.
10
System CTB-100V
Fig. Additional PCB for CU-200 See drawing CU-200_lo for further details.
11
3.2.2
System CTB-100V
The operation panels indoor can be flush or bulkhead mounted in a normal and ventilated indoor environment
with a temperature of 0 - 550 C. See drawing CTB-1020_dd1 for mounting details.
Note ! Make sure that it is sufficient space for cables and maintenance.
It is equipped with 2x cable gland PG-16 and plugable screw terminals for cables max.2,5mm2
See drawing CTB-1020_lo for terminal and
3.2.3
This weather proof operation panels IP-66 is for bulkhead mounting only. Including
external loudspeaker HP-8 Ref. drawing CTB-1020W_dd for mounting details and datasheet for HP-8.
It is equipped with 2x cable gland PG-16 and plugable screw terminals for cables max.2,5mm2
Ref. drawing CTB-1020_lo for lay out terminals drawing CTB-1020W_dd for mounting details and datasheet for
HP-8.
Note ! Make sure that it is sufficient space for cables and maintenance.
3.2.4
A sign plate with directory / substation number for all substations has to be placed close to the CTB-panels.
3.2.5
3.2.6
A sign plate with each substation number has to be placed on or close to each substation.
3.3
Cable requirements
All signal cables have to be approved ship-cable of type twisted pair with outer braided copper screen.
See cable connection drawings in chapter 6 for further details.
The screens must be interconnected in junction boxes and grounded in the central unit only.
Terminal block X8 1-20 terminal no.5 is ground point for each substation screen
Terminal block X1,2,3,4 / no.11 is ground point for each operation panel.
Power cable has to be approved ship cable min. 3 x 1,5mm2
Note! The central unit has to be connected to the vessels central ground.
Proper grounding is essential for reliable operation.
12
3.4
System CTB-100V
3.5
3.6
3.7
13
3.8
System CTB-100V
3.8.1 Substations
System volume for substations can be adjusted by separate trim potentiometer for each group of 5 lines.
Market volume setting line 1-5 6-10 11-15 16-20
System volume is factory adjusted and does not normally require any adjustment.
Volume adjustment for substation line 1 5
Trim potentiometer located on mainboard
3.8.2
Signal is factory adjusted and does not normally require any adjustment.
Input signal for auxiliary can be adjusted by separate trim potentiometer
marked adj. aux.input signal. Required signal 0dB (0,775V)
3.8.3
Call signal
Signal is factory adjusted and does not normally require any adjustment.
Level of Call signal out all lines can be adjusted by trim potentiometer
marked adj. call signal out
14
3.9
System CTB-100V
3.10
Substation STB-1
Default setting is Privacy function, can be set to normal Talk Back
Function.
Talk Back Function; move the jumper J1 on PCB in STB-1
3.11
Substation STB-3
Default setting is for headset, can be set for microphone.
Microphone; move the two jumpers on PCB - STB-3in position M
3.12
Substation STB-5
Default setting is for microphone or handset, loudspeaker can be set to both
loudspeaker and microphone. (Re-entrant speaker)
Re-entrant speaker; move the jumper J1 on PCB in STB-5.
15
System CTB-100V
4. USER INSTRUCTIONS
4.1
Up to 4 operation panels can be connected. Calls can be made from any operation panel to substations.
And calls can be made from any operation panel to another by pressing respective line button.
In this stage the called operation panel act as a substation. Calls from one operation panel will be indicated in
other operation panels. One operation panel is always decided to be a master station with highest priority and can
override operation panels with lower priority.
Figure 2 Operation panel CTB-20
62
51
44
10
Figure 5
Gooseneck
microphone
MB-30G
10
11
Figure 6
Handheld Microphone
with switch
ETC-1-TB
11
13
Figure 7
Handheld Microphone WP
with switch P-66
12
13
Figure 8
Footswitch U2410
PTT SWITCH
PTT SWITCH
16
System CTB-100V
17
4.1.1
System CTB-100V
You can select the substation by pressing desired line push button.
Steady green LED will indicate activated selection.
If desired, the signal button SIGN may be pressed to give a tone signal to selected station. Talk from the operation
panel is performed every time TALK button is pressed. The operation panel unit will be in listening mode as soon
as a station is selected. When communication is finished, press again the selected station button to switch off. The
LED will be switch off to indicate that selected line is turned of.
Operation panel : CTB-10,CTB-20, CTB-10W_V01 or CTB-20W_V01
Press the LINE button, the call is set up. Indicated by steady green LED
ETC-1-TB
PTT SWITCH
PTT SWITCH
18
4.1.2
System CTB-100V
You can select group of substations by pressing respective line buttons from one of the four
Operation panels. Only the operation panels can switch off and end the call
Press the required LINE buttons, the call is set up. Indicated by steady
green LED in selected buttons.
Press all the LINE buttons once more to end the call.
The LED will be switch off.
ETC-1-TB
PTT SWITCH
PTT SWITCH
19
4.1.3
System CTB-100V
All Call
The message and signal from the operation panel will be given to all substations, as a one-way message.
It will be indicated by steady green LED in the ALL button only. Talk back from substations is closed in this
mode.
Press the ALL button, the call is set up. Indicated by steady green LED
in the ALL button.
ETC-1-TB
PTT SWITCH
PTT SWITCH
20
4.1.4
System CTB-100V
Handsfree operation
4.1.5
Substation STB-3, STB-5 and STB-5GN is equipped with relay for activating of extra signal device.
Extra signal device can be flashing beacon, rotary light, alarm horn and bells.
Operation panel
Substation
21
4.1.6
System CTB-100V
A call are indicated with flashing green LED in the push button and a beep tone in the monitor loudspeaker or
extern loudspeaker. Will also activate extra signal unit if installed. Only the operationpanel can switch off and end
the call.
Press the LINE button, the call is set up. Indicated by steady green LED
ETC-1-TB
PTT SWITCH
A call is indicated with flashing green LED in for respective line button,
and signal in the monitor loudspeaker.
(and in extra signal unit if installed.)
PTT SWITCH
22
4.1.7
System CTB-100V
Calls can be received from two or more substations at same time. The operation panel that is set to receive calls
can select between calls from substations.
Calls are indicated with flashing green LED in the push buttons and a beep tone in the monitor loudspeaker
Will also activate extra signal unit if installed. (Only for the first incoming call.)
.
Press the LINE button, the call is set up. Indicated by steady green LED
The the operation panel can select between substation lines and cancel
calls by pressing the respective LINE button once more.
Press the selected LINE buttons once more to end the call.
The LED`s will be switch off.
ETC-1-TB
PTT SWITCH
Calls are indicated with flashing green LED for respective line button,
and signal in monitor loudspeaker.
(And in extra signal unit if installed, Note! only for the first call)
PTT SWITCH
23
System CTB-100V
AUX
ETC-1-TB
PTT SWITCH
Press line and AUX button once more to end the transferring.
PTT SWITCH
24
4.1.9
System CTB-100V
Alarm (or any audio) from external system can be distributed trough the CTB-100 system.
An potentional free contact and 0dB signal from the external system activate the system and the message will be
addressed to all substations and operation panels.
The talk button on the operation panel or PTT button on hand microphone will override the external audio.
Normal talk back functions can not be used in this mode.
External system can be:
Alarm system.
10
11
20
ETC-1-TB
PTT SWITCH
PTT SWITCH
25
System CTB-100V
Press desired LINE button (s), the Public Address call is set up.
Indicated by steady green LED.
Single or group of zones
ETC-1-TB
PTT SWITCH
PTT SWITCH
26
System CTB-100V
CTB-10 Operation panel 10 line selection, indoor use. Hand or gooseneck microphone.
CTB-10W/V01 Operation panel 10 line selection, WP. Handmicrophone only.
CTB-20 Operation panel 20 line selection, indoor use. Hand or gooseneck microphone.
CTB-20W/V01 Operation panel 20 line selection, WP. Handmicrophone only.
VMT-603 All call station WT with handmicrophone.
ON
OF F
VPA-120
POWER AMPL IFI ER
Press the ALL button, the call is set up. Indicated by steady green LED
in the ALL button.
EMERGENCY PABUTTON
27
System CTB-100V
When the PTT SWITCH button is released the CTB-100 system will
be back in normal Talk back mode.
28
System CTB-100V
4.1.12 Volume
By pressing + or - buttons repeatedly, you can increase or decrease the listening volume in the ETB.
This will also affect the volume for a parallel speaker connected to the ETB
29
4.2
System CTB-100V
Parallel communication
Function with operation from parallel microphone / loudspeaker located on bridge wings,
or other locations near the operation panel, where parallel microphone / loudspeaker needed.
Two parallel stations can be connected. Communication is set up by the operationpanel.
Bridge wing unit will be in operation mode as soon as a station is selected on the operationpanel.
Figure 9 Parallel station STB-6
PT
T
SW
ITC
H
WITC
H
30
4.2.1
System CTB-100V
Operation
Note! Line selection and signal have to be set up from the central unit.
Operationpanel
Operationpanel
WIT
CH
Press the desired LINE button, the call is set up. Indicated
by steady green LED
SWIT
CH
Operationpanel
31
4.3
System CTB-100V
Calls can be made from substations to the operation panels by pressing the CALL push button. A call is indicated
by a flashing green LED and a signal in the operation panel. The operation panel confirm the call by pressing
respective line button. The communication is set up. Only the operation panel can switch off and end the call.
Figure 12 Substation STB-2
1. Re-entrant Loudspeaker
For communication from the central unit.
Microphone for communication to the central unit.
2. CALL
Push button switch for call to central unit.
3. TALK
PTT switch for talk to the central unit
1. CALL
Push button switch for call to central unit.
2. Re-entrant Loudspeaker
For communication from the central unit.
Microphone for communication to the central unit.
PTT SWITCH
10m cable
1. Contact
2. Call
3. Loudspeaker
4. Signal device
5. Headset
6. Microphone
32
System CTB-100V
PTT SWITCH
PT
T
1. Loudspeaker
2. Call
3. Contact
4. Handset
5. Microphone
6. Signal device
SW
IT C
H
1. Loudspeaker
2. CALL
3. TALK
4. Signal device
1. Re-entrant Loudspeaker
For communication from the central unit.
Microphone for communication to the central unit.
2. CALL
Push button switch for call to central unit.
33
System CTB-100V
CABINET
PTT SWITCH
10m cable
1. Plugbox
CD-2 for VH-10M
2. CALL
Push button switch for call to the central unit
3. Re-entrant Loudspeaker
For communication from the central unit
Microphone for communication to the central unit.
CEAG
GHG 411
Ui 690V
EEx de IIC T6
IN 16A
PTB Nr.Ex-87.B.1009
34
4.3.1
System CTB-100V
Loudspeaker
4.3.2
Operationpanel
Operationpanel
35
System CTB-100V
Operationpanel
10m cable
PTT SWITCH
36
System CTB-100V
Operationpanel
With microphone
ETC-STB5
PTT SWITCH
Loudspeaker
Loudspeaker
37
System CTB-100V
Operationpanel
Loudspeaker
4.3.6
Loudspeaker
Operationpanel
38
4.3.7
System CTB-100V
4.3.8
Operationpanel
Operationpanel
PTT SWITCH
39
4.3.9
System CTB-100V
Operationpanel
40
System CTB-100V
5. COMMISSIONING
5.1
General
The CTB and CU- units and all sub equipments have been fully tested in our workshop before delivery. To ensure
that everything is correct after installation and configuration of the system, do the following procedure before the
system is ready for use.
Ref. is made to Chapter 3 Installation and configuration procedures and installation drawings.
5.2
5.3
Mechanical Inspection
All equipment is well fastened in console or wall according to pos. 3.2
All cable and cable glands are well tight and fastened according to pos. 3.2
Cable Inspection
All cables are connected according to chapter pos.3.3 and dwg.no. CTB-100_cc1, CTB-100_cc2, CTB-100_cc3,
CTB-100_cc4 and CTB-100_cc05
It is used signal cables 0,75mm2 approved ship-cable of type twisted pair with outer braided copper
screen.The screens are interconnected in junction boxes and grounded in the central unit only
(CU-100,CU-200)
Common ground points:
Terminal block X8-1-20 /no. 5 is ground point for each substation,
Terminal block X1,2,3,4 / no.11 is ground point for each operation panel.
Power cable are 1,5mm2 and is connected to terminal block X7, + to terminal 1, - to terminal 2.
The screen is grounded on terminal 3.
It is used cable 1,5mm2 for power to signal units.
Polarity for extra signal device is connected in according to dwg.CTB_cc3 and CTB_cc4
5.4
Check Configurations.
Ref. Chapter 3 Installation and configuration procedures
5.5
41
5.6
System CTB-100V
The system has no On/Off switch for main power. Power switching is done from external equipment
The system is always powered and ready for use and its only indicated when using the system.
Following procedure has to be completed before end use. Do the test procedure for all equipments in the
installation. Test functions according to User Instructions in Chapter 4.
Basic functions CTB, operation from all CTB-operation panels have to be done.
Pos.
1
2
3
4
5
6
7
8
9
10
Operation Requirement
Commissioning according to chapter 5.2, 5,3, 5.4 and 5.5 is done.
Power on. 24V DC measured on terminal X7 no.1-2 in central unit
Make a call to each substation Ref. 4.1.1
Make a call to group of substations Ref. 4.1.2
All Call Ref. 4.1.3
Give signal to substations with extra signal device. 4.1.5
Receive a Call from an substation Ref. 4.1.6
Receive a Call from two or more substations. Ref. 4.1.7
Volume control of internal loudspeaker Ref. 4.1.12
Dimmer for light in Line button Ref. 4.1.13
Tested, ok
Operation Requirement
Make a call with footswitch, hands free. Ref. 4.1.4
AUX function Ref. 4.1.8
Audio from external system Ref. 4.1.9
Public Address operation of external system Ref. 4.1.10
Emergency Public Address operation Ref. 4.1.11
Tested, ok
Operation Requirement
Operation with STB-6
Operation with STB-6GN
Operation with STB-6GN hands free
Operation with SB-4
Call to two or more substations from parallel station
Tested, ok
Operation Requirement
Operating by 230V AC or 115v AC mains power supply.
24V DC on terminal 3 -4 Green light marked DC ok
Operating with 24V DC emergency power supply.
1. Disconnect 230V AC or 115V AC mains power supply and check if
the auto switch relay switch to emergency 24V DC. 24V DC on
terminal 3 -4
Check if power failure contact marked NC 6-7 is activated.
2. Disconnect cables to + and on the power supply module, and
check if the auto switch relay switch to emergency 24V DC. On
terminal 3 -4
Check if power failure contact marked NC 6-7 is activated.
Tested, ok
Substations
Pos.
23
24
25
26
27
28
29
30
31
Operation Requirement
Operation from STB-1 Ref. 4.3.1
Operation from STB-2 Ref. 4.3.2
Operation from STB-3 Ref. 4.3.3
Operation from STB-5 Ref. 4.3.4
Operation from STB-5GN Ref. 4.3.5
Operation from HE-112M Ref. 4.3.6
Operation from VH-10M Ref. 4.3.7
Operation from VHM-10 Ref. 4.3.8
Operation from NEBB-42EX / EX Loudspeaker Ref. 4.3.9
Tested, ok
42
System CTB-100V
Volume control
Pos.
32
5.8
Operation Requirement
Adjust sound pressure level, to convenient level if necessary
Master volume line 1-5, 6-10, 11-15, 16-20
Ref. chapter 3.8 and dwg.CU-100:lo and CU-200_lo
Tested, ok
Trouble shooting.
Failure event
The whole system is shut
down.
No light indication in CTBpanels.
3.1
7.1
Description / Indication
No voltage measured on terminal block
X7 no.1-2 in the CU-unit
Recommended Action
1.Check 24V DC mains power
supply or power supply SPS-4
43
System CTB-100V
7.2
Instability.
10
11
12
13
Feedback problems
14
14.1
System CTB-100V
Problems when operating from substation or parallel station connected to an operation panel
Pos.
15
Failure event
Operation from an substation
can not be done
Description / Indication
No flashing green LED and a signal in
the CTB monitor loudspeaker for the
selected line.
Recommended Action
1. Check cable and terminal block
in the substation or plug box.
2. Move this terminal block to a
another ext. number.
If still problems, the substation
have to be repaired
If operating is ok, the CU unit
have to be repaired
16
17
Problems when operating from All call stations. Ref DNV C500 Nautical Safety
Pos.
18
Failure event
Operation from one all call
station can not be done.
Description / Indication
No audio in all other operation panels or
substations.
19
20
Sound pressure level does not
fulfil the requirement.
Recommended Action
1. Check connection between the
unit and the junction box.
2. If 24V DC voltage is measured
in the all call station, the unit have
to be repaired. Ref. dwg. CTB-cc6
1. Check connection between the
junction box and the central unit,
and specially the terminal block
connected to X6. Ref. dwg. CTBcc6 If still problems, the central
unit have to be repaired.
Adjust trim potentiometer in the
central unit marked adj. aux.
input signal to satisfactorily
level.see chapter 3.8.2
Note! If recommended actions above do not succeed, further action has to be done in
cooperation wath or by Zenitel personel
45
System CTB-100V
Installation drawings
Item
Description
Doc.no
System drawing............... Single line diagram .............................................................................CTB-100_sl
System drawing............... System block diagram.........................................................................CTB-100_bd
System drawing............... Lay out terminals CTB-10, 20, CTB-10,20 W/01 ..............................CTB-1020_lo
System drawing............... Lay out terminals CU-100 ..................................................................CU-100_lo
System drawing............... Lay out terminals CU-200 ..................................................................CU-200_lo
System drawing............... Connection substation low impedance, options..................................CTB-100_cc1
System drawing............... Connection substation 100V, options .................................................CTB-100_cc5
System drawing............... Connection CU- / CTB with options ..................................................CTB_cc2
System drawing............... Connection power, External PA, alarm & Auxiliary ..........................CTB_cc3
System drawing............... Connection power, PA, alarm & Auxiliary.........................................CTB-100_cc2
System drawing............... Connection CU- substations, line 1-10 ...............................................CTB-100_cc3
System drawing............... Connection Nautical Safety ................................................................CTB-cc6
System drawing............... Connection CU- substations, line 11-20 .............................................CTB-100_cc4
Wiring diagram ............... Powersupply SPS-4 .................................................................SPS-4Ver.2.0_ddwd
Outline drawings
CU-100 & CU-200.......... Central units........................................................................................CU_dd
CTB-10, 20...................... Operator panel 10,20 lines ..................................................................CTB-1020_dd1
WBOKS .......................... Wall mounted box for CTB-10 and 20 ...............................................WBOKS_dd
CTB-10,20 W V01 .......... WP Operator panel 10,20 lines ...........................................................CTB-1020W_dd
HP-8 ................................ Horn loudspeaker, part of CTB-10W V01 and CTB-20W V01 .........HP-8_dd
6.2
Datasheets
HP-8 ................................ Horn loudspeaker, part of CTB-10W V01 and CTB-20W V01 .........HP-8_ds
MB-30G ..................... Gooseneck Microphone with plug for CTB-10/20 .............................MB-30G_ds
ETC-1-TB ....................... Hand microphone with curled cord and plug for CTB-10/20 .............ETC-1-TB_ds
P-66 ................................. Hand microphone with curled cord and plug, WP..............................P-66_ds
P-66/10 ............................ Hand microphone with 10mtr. Cable and plug, WP ...........................P-66/10_ds
AW8121............................ Power amplifier 120W / 100V 220V AC/24V DC ................................. AW8121_ds
AW8241............................ Power amplifier 240W / 100V 220V AC/24V DC ................................. AW8241_ds
P-8501............................... Power amplifier 500W / 100V 220V AC/24V DC ................................. P-8501_ds
RS-3D ............................... Cabinet for power amplifier .................................................................... RS-3D_ds
46
System CTB-100V
Parallel equipment,
STB-6 .............................. Flush mounted substation for handmic. ..............................................STB-6_ds
STB-6GN ........................ Flush mounted substation w/gooseneck mic.......................................STB-6GN_ds
SB-4 ................................ WP Plug box for portable microphone, headset and loudspeaker.......SB-4_ds
Additional equipment
WBOKS .......................... Wall mounted box for CTB-10 and 20 ...............................................WBOKS_ds
STBOKS5 ....................... Wall mounted box for STB-5 and STB-5GN .....................................STBOKS5_ds
STBOKS ......................... Wall mounted box for STB-6 and STB-6GN .....................................STBOKS_ds
VML-1520 ...................... Horn loudspeaker 15W 20ohm IP-65 .................................................VML-1520_ds
VML-15T.......................... Horn loudspeaker 15W 100V IP-65 ........................................................ VML-15T_ds
47
CU-100
Talk-Back Systems
Technical data:
Material / finish:
Mounting:
120
400
400
Description:
Aluminium / black.
Bulkhead with 4 x 4mm
Features
screws
Terminals:
Fuses:
DIP-switches:
Pot.meter:
Protection:
External connections:
IP-22
4x Operation panels, up to
AUX input:
10 substations, AUX, PA
0 dB 0,775V / 600ohm
Alarm contact:
Frequency range:
Temperature operating:
Humidity:
-20 + 550C
5 - 95 %
Power supply:
Power consumption
20 - 32V DC
at 24V DC:
Output power:
2,5 A
Depending on external
Output impedance:
CU-100
*
*
*
*
*
*
Document no.
Article no.
CU-200
Talk-Back Systems
Technical data:
120
400
400
Description:
Material / finish:
Aluminium / black.
Mounting:
Features
Terminals:
Fuses:
DIP-switches:
F1,F2,F3;F4 1A 5 x 20
For PA-zones, set priority, set
Pot.meter:
receive call.
For volume setting line
Weight:
Protection:
Approx. 3,2Kg
IP-22
External connections:
4x Operation panels, up to
20 substations, AUX, PA
AUX input:
Alarm contact:
0 dB 0,775V / 600ohm
Potential free N/O
Frequency range:
Temperature operating:
Humidity:
Power supply:
5 - 95 %
20 - 32V DC
Power consumption
at 24V DC:
5A
Output power:
Depending on external
100V power amplifier
Output impedance:
CU-200
*
Central unit 20 lines for CTB-100V system
*
*
*
*
Signal oscillator
24 VDC power supply
*
*
CTB-10
Talk-Back Systems
Description:
CTB-10
*
Operator panel CTB-10 with 10 lines selection
*
Operates with CU-10 or CU-20 central unit
*
Bridge Wing communciation facility
*
All Call / Group Call facility
*
Re-entrant monitor-speaker / microphone
*
Connector for gooseneck or handheld microphone
*
Dimable panel background light
*
Extension buttons with memory light
*
Buzzer indication of incoming calls
*
Step volume control
*
Signal oscillator
*
Output for extra signal device all lines
Features
240
230
144
134
Technical data:
1
10
ALL
AUX
DIM+
SIGN
Material / finish:
Mounting:
VOLUME
TALK
Terminals:
Mounting holes
Panel cut-out
100
= 4,5 mm
= 224 x 132
30
Cable gland:
Dimension W/H/D mm:
Cut out dimension:
Weight:
Microphone input:
125
External connections:
PG16
Front panel:
Switches:
Loudspeaker:
IP rating:
Document no.
Article no.
Aluminium / black.
Flush with 4 x 4mm screws
Optional Back box for bulkhead
mounting.
Plugable screw terminals
for cable max. 2,5mm2
2x PG-16
240 x 144 x 100
224 x 132
Approx. 1,2Kg
Contact for handheld and
electret gooseneck microphone
Central unit, ext. microphones.
ext.loudspeaker
Graphic front film
Push button type with LED
indication
3W / 8 ohm
IP-47
CTB-20
Talk-Back Systems
Description:
CTB-20
*
Operator panel CTB-20 with 20 lines selection
*
Operates with CU-20 central unit
*
Bridge Wing communication facility
*
All Call / Group Call facility
*
Re-entrant monitor-speaker / microphone
*
Connector for gooseneck or handheld microphone
*
Dimable panel background light
*
Extension buttons with memory light
*
Buzzer indication of incoming calls
*
Step volume control
*
Signal oscillator
*
Output for extra signal device all lines
Features
240
144
134
230
10
11
12
13
14
15
16
17
18
19
20
ALL
AUX
Technical data:
Material / finish:
Mounting:
VOLUME
DIM+
SIGN
Aluminium / black.
Flush with 4 x 4mm screws
Optional Back box for
bulkhead mounting.
Plugable screw terminals
for cable max. 2,5mm2
TALK
Terminals:
Mounting holes
Panel cut-out
100
= 4,5 mm
= 224 x 132
30
Cable gland:
Dimension W/H/D mm:
Cut out dimension:
Weight:
Microphone input:
125
External connections:
PG16
Front panel:
Switches:
Loudspeaker:
IP rating:
Document no.
Article no.
2x PG-16
240 x 144 x 100
224 x 132
Approx. 1,2Kg
Contact for handheld and
elec. gooseneck microphone
Central unit, ext. microphones.
ext.loudspeaker
Graphic front film
Push button type with LED
indication
3W / 8 ohm
IP-47
CTB-10 W / V01
Talk-Back Systems
Description:
CTB-10W / V01
*
Operator panel with 10 lines selection,
and loudspeaker HP-8, bulkhead mounting.
*
Option, microphone P-66 and P-66/10
*
Operates with CU-10 or CU-100 central unit
*
Bridge Wing communication facilty
*
All Call / Group Call facility
*
Re-entrant monitor-speaker/microphone
*
Dimable memory light
*
Line buttons with memory light
*
Buzzer indication of incoming calls
*
Step volume control
*
Signal oscillator
Technical
data:
*
Weather-proof
Features
Technical data:
Material / finish:
Mounting:
Terminals:
Dimension W/H/D mm:
Weight:
External connections:
Front panel:
Switches:
Microphone contact:
WP Microphone:
Loudspeaker:
Protection:
Document no.
Article no.
CTB-20W / V01
Talk-Back Systems
Description:
CTB-20W / V01
*
Operator panel with 20 lines selection,
and loudspeaker HP-8, bulkhead mounting.
*
Option, microphone P-66 and P-66/10
*
Operates with CU-20 or CU-200 central unit
*
Bridge Wing communication facilty
*
All Call / Group Call facility
*
Re-entrant monitor-speaker/microphone
*
Dimable memory light
*
Line buttons with memory light
*
Buzzer indication of incoming calls
*
Step volume control
*
Signal oscillator
Technical data:
*
Weather-proof
Features
Technical data:
Material / finish:
Mounting:
Terminals:
Dimension W/H/D mm:
Weight:
External connections:
Front panel:
Switches:
Microphone contact:
WP Microphone:
Loudspeaker:
Protection:
Document no.
Article no.
VMT-603
Description:
VMT-603:
*
Features
Technical data:
50
220
80
120
VMT-603
Handheld mic.:
62A0005
Connection:
Housing:
ROSE Box
Colour:
IP rating:
IP-65
Dimensions:
Weight:
1,4 kg
PG7
PG21
82
204
Mounting holes diam. 6.0 mm
Document no.
Article no.
HP-8
Loudspeakers
Description:
HP-8
Horn loudspeaker for use on open deck areas, eng room etc.
WP, IP-67.
Features
Technical data:
Manufacturer:
Material / Colour:
Mounting:
Termination:
Weight:
IP-rating (UL Equivalent)
Max. / min. amb. temp:
Impedance:
Rated / max. power:
SPL 1 W / 1 m:
SPL rated power:
Effective freq. range:
Dispersion (-6 dB)1kHz / 4kHz:
Directivity factor, Q :
DNH A/S
Polyamide / RAL 7035
Bracket or flush
0,5m cable
0,75 kg
IP-67
150 C / -50 C
8 ohm
8 W / 15 W
101 dB
110 dB
600 - 7500 Hz
160 / 50
6,0
HP-8T:
Transformer 100V
Primary nominal tappings:
1:2
8,0W
2:3
4,0W
3:4
2,0W
1:3
1,5W
2:4
0,7W
1:4
0,4W
1= Red, 2= Yellow, 3= Green, 4= Blue
Document no.
Article no.
MB-30G
Common Equipment
Description:
36
MB-30G
*
Gooseneck microphone
*
Features
460
Technical data:
Manufacturer:
Paso
Type :
Art.no. :
Electret
MB30G
Impedance:
Freq.response:
2 K ohm
100 - 20000Hz.
Sensitivity:
Supply:
4mv/Pa.
1,1-9V.
10 dB
430mm
Plug:
Accessories:
5 pole din
Sponge windscreen
Dimensions:
Weight:
Document no.
Article no.
ETC-1-TB
Talk-Back Systems
Description:
ETC-1-TB
* Handheld microphone for use with ETB and CTB control
Features
unit panels.
58
102
47
Technical data:
Type :
Art.no. :
Dynamic
ETC-1-TB
Impedance:
Freq.response:
200 ohm
200 - 4500Hz.
Sensitivity:
Polar pattern:
1 mV/Pa.
Non directional
Switch:
Cable:
Plug:
PTT
3-wires coiled cord w/ shield
5 pole din
Accessories:
Dimensions:
Hang-up clip
See dwg. beside
Weight:
0,2 kg
45
36
24
3 mm
Mic. clip-on
Document no.
Article no.
Common Equipment
P-66
Description:
54
54
P-66
* Watertight, salt water resistant handheld microphone-
Features
loudspeaker unit.
Suitable for heavy-duty outdoor operation subject to
noise disturbance.
Delivered with 2 meter flexicable and plug.
72
81
29
Technical data:
Manufacturer:
Holmberg & Co
Type/art.no.:
DC resistance:
Holmco 66 / 84-15-06980
200 ohm
Mic.sensitivity:
0.5 mV/dyne/sq.cm
at 1 kHz
Power capacity:
LS sensitivity:
Working temp.
frequency power.
-30 to +60 C
IP class:
Colour:
IP-66
Black
Dimensions:
Weight:
Document no.
Article no.
Common Equipment
P-66-10
Description:
54
81
P-66/10
* Watertight, salt water resistant handheld microphone-
Features
72
29
loudspeaker unit.
Suitable for heavy-duty outdoor operation subject to
noise disturbance.
Delivered with 10 meter cord and plug.
10 m cable
Technical data:
54
Manufacturer:
Holmberg & Co
Type/art.no.:
Holmco 66 / 84-1506980
DC resistance:
Mic.sensitivity:
200 ohm
0.5 mV/dyne/sq.cm
Power capacity:
at 1 kHz
0.2 W (0.5 W peak)
LS sensitivity:
57 dB/mW at 1 kHz
and 50 cm distance
i.e. 80 dB at 0.2 W
audio- frequency power.
10 m cable
Working temp.
IP class:
-30 to +60 C
IP-66
Colour:
Dimensions:
Black
see dwg. above
Weight:
0,4 kg
Document no.
Article no.
AW8121
Description:
AW8121
* 19 3 HU 120 W power amplifier
*
Features
Technical data:
482,6
SERIES
POWER AMPLIFIER
dB +40 -6
10
+10
10
BASS
CAUTION:
TO REDUCE
THE RISK
OF FIRE
REPLACE
ONLY WITH
SAME TYPE
CAUTION:
DISCONNECT POWER
SUPPLY CORD
BEFO RE CHANGING
FUSE.
TREBLE
FUSE ~
(260W) 24V
...
16
50V
CO M. 8
FUSE ~
RATING
T 2.5 A
120W RMS
100, 70, 50 V
outputs:
Distortion at rated power:
16, 8 ohm
<1%
Tones control:
POWER
Booster input:
Sensitivity / impedance:
REMOTE ALARM
Precedence attenuation: 55 dB
Amplified stand input:
70V 100 V
Black
120 W
S/N ratio:
Frequency response:
V ~
230V ~
10
MASTER VOLUME
1 2 3
FUSE.
Colour:
Power AC:
OVERL. ON
+10
Paso
+1
OUTPUT LEVEL
132
Manufacturer:
CONSUM PT.
450 W
MADE IN ITALY
LEVEL TONE
CHIME
IN
A.P.T.
LEVEL
BASE
Debth: 340
Debth w/ carrying handle: 380
LEVEL
IN
BO OSTE R
OUT
Sensitivity / impedance:
S/N ratio:
Frequency response:
Weight:
Document no.
Article no.
220 mV / 10 Kohm
80 dB
150 - 14 000 Hz
Approx. 14 kg
AW8241
Description:
AW8241
* 19 3 HU 240 W power amplifier
*
Features
Technical data:
482,6
SERIES
POWER AMPLIFIER
dB +40 -6
+1
OUTPUT LEVEL
10
+10
10
BASS
CAUTION:
TO REDUCE
THE RISK
OF FIRE
REPLACE
ONLY WITH
SAME TYPE
CAUTION:
DISCONNECT POWER
SUPPLY CORD
BEFO RE CHANGING
FUSE.
+10
TREBLE
FUSE ~
(260W) 24V
...
16
50V
CO M. 8
Colour:
Power AC:
Black
240 W
100, 70, 50 V
outputs:
Distortion at rated power:
16, 8 ohm
<1%
Tones control:
10
MASTER VOLUME
1 2 3
FUSE.
Paso
OVERL. ON
132
0
Manufacturer:
POWER
Booster input:
Sensitivity / impedance:
S/N ratio:
Frequency response:
REMOTE ALARM
70V 100 V
V ~
FUSE ~
RATING
T 2.5 A
240W RMS
CONSUM PT.
450 W
MADE IN ITALY
LEVEL TONE
CHIME
IN
A.P.T.
LEVEL
BASE
Debth: 340
Debth w/ carrying handle: 380
LEVEL
IN
BO OSTE R
OUT
Precedence attenuation: 55 dB
Amplified stand input:
Sensitivity / impedance:
S/N ratio:
Frequency response:
Weight:
Document no.
Article no.
220 mV / 10 Kohm
80 dB
150 - 14 000 Hz
Approx. 17 kg
P8501
Technical data:
Manufacturer:
Colour:
Dimensions:
Power AC:
Constant voltage outputs:
Constant impedance outputs:
Distortion at rated power:
Tones control:
Paso
Black
482 x 133 x 420 mm
500 W
100, 70, 50, 25 V
20, 9.4, 5, 1.25 ohm
< 0,5 %
Bass ( 100 Hz ) +/- 10 dB
Treble ( 10kHz ) +/- 10 dB
Features
Booster input:
Sensitivity / impedance:
S/N ratio:
Frequency response:
482,6
SERIES
POWER AMPLIFIER
dB -40
-12
-6
0 +1
OUTPUT LEVEL
132
OVERL. POWER
5
ON
10-
+10
10-
BASS
24V ...
CONSUMPT. 800W
+10
TREBLE
10
VOLUME
f ( MHz )
0
0
25V
1,25
50V
5
70V
9,4
100V
20
POWER AMPLIFIER
P 8501
MAINS FUSE ~
OFF
0
10
VOLUME
REMOTE
ALARM
230V ~
RATING CONSUMPT.
950W
MADE IN ITALY
RF
FUSE
32A
ANTENNA
SQUELCH
V ~
CAUTION:
TO REDUCE
THE RISK
OF FIRE
REPLACE
ONLY WITH
SAME TYPE
CAUTION:
DISCONNECT POWER
SUPPLY CORD
BEFORE CHANGING
FUSE.
FUSE.
FUSE ~
LEVEL TONE
CHIME
INPUT
A.P.T.
BASE
LEVEL
OUTPUT
INPUT
BOOSTER
LEVEL
220 mV / 10 Kohm
> 80 dB
50 - 20 000 Hz (0/-3 dB)
Precedence attenuation:
> 40 dB
Amplified stand input:
Sensitivity / impedance:
400 mV / 10 Kohm
S/N ratio:
> 80 dB
Frequency response:
180 - 20 000 Hz ( 0/-3 dB )
Max. current absorption:
200 mA
Power consumption (mains): 950 W / 1150 VA
External DC power supply:
24 V
Current consumption (dc power): Max. 25 A
Operating/ storage temp. range: -10 C to +45 C /
-40 C to +70 C
Relative humidity:
Weight:
< 95 %
25 kg
Description:
P-8501
* 19 3 HU 500 W power amplifier
* 230 Vac / 24 Vdc power supply
Document no.
Article no.
FRONT VIEW
Description:
520
SERIES
dB +40 -6
+1
OUTPUT LEVEL
+10
BASS
10
TREBLE
OVERL. ON
+10
RS-3D
3 HU 19 cabinet, prepared for amplifier
AW8121, AW8241 and P-8501
with all necessary terminals for external 230 Vac /
24 Vdc in and out signals
Features
POWER AMPLIFIER
10
RS-3D
10
MASTER VOLUME
POWER
FRONT VIEW
REAR VIEW
Technical data:
X2
X1
Dimensions (WxHxD):
Mounting:
Weight:
Housing:
Colour:
Cable entry:
Connections:
Operation voltage:
X3
K1
123 45
1 2 3 4 5 6 7 8 9 10 11
123
SIDE VIEW
180
450
250
50
125
100
100
100
100
TOP VIEW
570
MOUNTING HOLES 5,2MM
Document no.
Article no.
STB-1
Talk-Back Systems
Description:
STB-1
*
Talk-Back substation, designed for use in cabins,
Features
96
messrooms, etc.
Delivered for bulkhead mounting
*
*
Technical data:
49
Connections:
Colour:
Screw terminals
Black front
IP rating
Dimensions:
IP-44
See dwg. beside
Weight:
0,35 kg
144
96
47
144
144
96
18
Cable inlet
72
48
Document no.
Article no.
73
STB-2
Talk-Back Systems
Description:
STB-2
*
*
Calling box
Delivered for bulkhead mounting
*
*
Features
Technical data:
2 x PG13,5
28
CALL
80
Connections:
Colour:
Screw terminals
Grey
IP rating
Dimensions:
IP-66
See dwg. beside
Weight:
0,3 kg
63
46
94
110
Mounting hole
diam. 4.5 mm
SCREW TERMINAL
3
4
SS LINE
Document no.
Article no.
EXTERNAL
SPEAKER
STB-3
Talk-Back Systems
Description:
STB-3
38
63
80
*
*
Calling unit
Delivered for bulkhead mounting
*
*
Features
28
46
4 x PG13,5
ON
Connections:
Colour:
Screw terminals
Grey
IP rating
Dimensions:
IP-66
See dwg. beside
Weight:
0,5 kg
CALL
224
208
Mounting hole
diam. 4.5 mm
CALL
HEADSET
Technical data:
SCREW TERMINAL
0V
+24V
0V
+24V
0V
+24V
9
10
SS LINE
SIGNAL DEVICE IN
IN
EXTRA SIGNAL DEVICE
OUT
Document no.
Article no.
EXTERNAL
SPEAKER
P-MT7
Description:
110
P-MT7
*
*
*
Features
Technical data:
10mcable
Connections:
Headset:
Colour:
Peltor MT 7H7A
Black
IP rating:
Dimensions:
IP-54
See dwg. beside
Weight:
Approx. 1,2 kg
60
40
124
95
200
40
Headset holder
10mcable
Document no.
Article no.
STB-5
Talk-Back Systems
Description:
STB-5
*
Talk-Back substation, designed for multipurpose indoor
Features
*
*
devices.
Loudspeaker
Technical data:
30
120
144
134
57
Material / Colour:
Connections:
Aluminium / black
Screw Terminals
Loudspeaker:
Dimensions:
3W
See dwg. above
Weight:
IP rating:
Approx. 0,5 kg
IP-44
PG16
Accessories:
CALL
134
144
SCREW TERMINAL
0V
+24V
0V
+24V
0V
+24V
SS LINE
SIGNAL DEVICE IN
IN
EXTRA SIGNAL DEVICE
OUT
Document no.
Article no.
STB-5GN
Talk-Back Systems
Description:
STB-5GN
Loudspeaker
Gooseneck microphone
Features
Accessories:
Box for bulkhead mounting ( see seperate datasheet )
Technical data:
144
134
Mounting holes 4 mm
Material / Colour:
Connections:
Aluminium / black
Screw Terminals
Loudspeaker:
Dimensions:
3W
See dwg. above
Weight:
IP rating:
Approx. 0,9 kg
IP-44
SIGN
134
144
57
30
Colour:
Black
Length:
Type:
330 mm
Uni-directional cardioid
Freq. response:
microphone ( dynamic )
50 - 16 000 Hz
Sensitivity:
1,5 mV
120
PG16
SCREW TERMINAL
0V
+24V
0V
+24V
0V
+24V
Document no.
Article no.
SS LINE
SIGNAL DEVICE IN
IN
EXTRA SIGNAL DEVICE
OUT
HAS-1
Talk-Back Systems
Description:
HAS-1
*
Handset with cradle designed for use together with
Features
80
220
43
Technical data:
Colour:
Material:
Black
Metal ( cradle ) /
Spiralcord:
plastic ( handset )
Approx. 1,2 m
Plug:
Switch:
5 pin DIN
ON / OFF
Weight:
0,55 kg
60
55
30
Mounting holes
3,5 mm
Document no.
Article no.
ETC-STB5
Talk-Back Systems
Description:
ETC-STB5
* Handheld microphone configurated for substation STB-5
Features
Technical data:
58
102
47
Type :
Art.no. :
Dynamic
ETC-STB5
Impedance:
Freq.response:
200 ohm
200 - 4500Hz.
Sensitivity:
Polar pattern:
1 mV/Pa.
Non directional
Switch:
Cable:
Plug:
PTT
3-wires coiled cord w/ shield
5 pole din
Accessories:
Weight:
Hang-up clip
0,2 kg
45
36
24
3 mm
Mic. clip-on
Document no.
Article no.
VH-10M
Talk-Back System
Description:
VH-10M
* Portable deck loudspeaker with callbox
*
Features
Technical data:
250
Material:
Colour:
ABS ( Speaker )
Black ( Backplate ) / Grey ( Speaker )
145
3,7 kg
64
CALL
10m cable
Accessories:
Plugbox CD-2 ( See separate datasheet )
156
407
410
153
10m cable
Document no.
Article no.
305
VH-10M-T
Talk-Back System
Description:
VH-10M-T
* Portable deck loudspeaker 100V with callbox
*
Features
Technical data:
250
Material:
Colour:
ABS ( Speaker )
Black ( Backplate ) / Grey ( Speaker )
145
3,7 kg
64
CALL
10m cable
Accessories:
Plugbox CD-2 ( See separate datasheet )
156
407
410
153
10m cable
Document no.
Article no.
305
CD-2
Talk-Back Systems
80
24
Description:
CD-2
* Watertight plug box
Features
*
*
PG11
63
27
Technical data:
46
Terminal
strip
A
B
C
1
2
3
94
110
Socket
no.
Mounting hole
diam. 4.5 mm
Connections:
Colour:
Screw terminals
Grey
IP rating:
Dimensions:
IP-66
See dwg. above
Weight:
0,35 kg
Pair 1
Pair 2
Document no.
Article no.
VHM-10
Talk-Back System
Description:
VHM-10
*
Features
Technical data:
Material:
Polycarbonate ( Cabinet )
Colour:
Dimensions:
Grey ( Cabinet )
See dwg. above
IP rating:
Weight:
IP-66
2,5 kg
310
Microphone P-66:
160
215
15
Colour:
Black
IP class:
DC resistance:
IP-66
200 ohm
Mic.sensitivity:
Power capacity:
LS sensitivity:
Dimensions:
audio-frequency power.
54 x 81 x 54
Working temp.
Weight:
-30 to +60 C
0,3 kg
334
275
247
CALL
Document no.
Article no.
75
152
239
VHM-10T
Talk-Back System
Description:
VHM-10T
*
Features
Technical data:
Material:
Polycarbonate ( Cabinet )
Colour:
Dimensions:
Grey ( Cabinet )
See dwg. above
IP rating:
Weight:
IP-66
2,5 kg
310
Microphone P-66:
160
215
15
Colour:
Black
IP class:
DC resistance:
IP-66
200 ohm
Mic.sensitivity:
Power capacity:
LS sensitivity:
Dimensions:
audio-frequency power.
54 x 81 x 54
Working temp.
Weight:
-30 to +60 C
0,3 kg
334
275
247
CALL
Document no.
Article no.
75
152
239
HE-112M
Talk-Back Systems
Description:
HE-112M
* Talk-Back Substation, designed for use in open deck
areas
* Delivered for bulkhead mounting
* Call-button for calling Master unit
Features
Technical data:
10
122
90
Connections:
Screw terminals
Colour:
IP rating:
Dimensions:
Weight:
Grey
IP-66
See dwg. beside
0,4 kg
120
Mounting holes
4 mm
110
90
30
CALL
PG16
20
terminal strip
B
A
Document no.
Article no.
HE-112MT
Talk-Back Systems
Description:
HE-112MT
* Talk-Back Substation, designed for use in open deck areas
* To be used with 100 volt line amplifiers
* Delivered for bulkhead mounting
* Call-button for calling Master unit
Features
Technical data:
122
90
Connections:
Screw terminals
Transformer:
Colour:
IP rating:
Dimensions:
Weight:
120
10
30
CALL
PG16
20
90
110
Mounting holes
4 mm
terminal strip
B
A
Document no.
Article no.
NEBB-42-EX
Talk-Back Systems
85mm
Description:
NEBB-42EX
CEAG
GHG 411
Ui 690V
EEx de IIC T6
Features
*
*
*
*
IN 16A
PTB Nr.Ex-87.B.1009
Technical data:
90mm
120mm
Connections:
Screw terminals
Colour:
Material:
Black
Moulded polyamid
PTB approval:
IP rating:
Dimensions:
IP-67
See dwg. beside
Weight:
0,35 kg
Document no.
Article no.
STB-6
Description:
STB-6
*
Substation for indoor bridge wing
Features
*
*
Technical data:
96
Mounting hole distance: 86 mm
44
144 x 96 x 44
4x 4mm screws
Weight:
Housing:
Approx. 0,350kg
Aluminium elox.
Colour:
IP-rating:
Black
IP-44
Cable entry:
Connections:
PG-16
Screw terminal
Loudspeaker:
3W
28
120
144
4 mm
Dimensions (WxHxD):
Mounting:
Document no.
Article no.
STB-6GN
Description:
STB-6GN
*
Features
Technical data:
144
4 mm
Dimensions (WxHxD):
144 x 96 x 44
Mounting:
Weight:
4x 4mm screws
Approx. 0,850kg
Housing:
Colour:
Aluminium elox.
Black
IP-rating:
Cable entry:
IP-44
PG-16
Connections:
Loudspeaker:
Screw terminal
3W
TALK
96
28
Document no.
Article no.
120
44
SB-4
Talk-Back Systems
Description:
SB-4
*
*
*
*
Features
Technical data:
28
Screw terminals
Colour:
IP rating
Grey
IP-66
Dimensions:
Weight:
2 x PG13,5
80
Connections:
38
63
46
110
94
Mounting hole
diam. 4.5 mm
SCREW TERMINAL
0V
LINE
Document no.
Article no.
3
4
5
6
7
8
TALK
SPEAKER LINE IN
EXTERNAL
SPEAKER
CTBOKS
Talk-Back Sy stems
WBOKS
Talk-Back Systems
240
Description:
5
WBOKS
*
22.5
205
230
100
Features
134
120
144
22.5
Technical data:
Colour:
Material:
Black finish
Aluminium
Dimensions:
Mounting:
Weight:
415 g
Document no.
Article no.
STBOKS5
Description:
STBOKS5
Box for bulkhead mounting of STB-5 & STB-5GN
Features
Technical data:
144
2,5
5
144 x 144 x 59
4x 4mm screws
Weight:
Housing:
Approx. 0,215kg
Aluminium elox.
Colour:
Cable entry:
Black
Rear side
135
115
144
18
Dimensions (WxHxD):
Mounting:
115
135
144
59
Document no.
Article no.
STBOKS
Description:
STBOKS
Box for bulkhead mounting of STB-6 & STB-6GN
Features
Technical data:
4
144
Weight:
Housing:
Approx. 0,1kg
Aluminium elox.
Colour:
Cable entry:
Black
Rear side
50
48
144 x 96 x 47
4x 4mm screws
123
18
Cable inlet
Dimensions (WxHxD):
Mounting:
73
144
47
Document no.
Article no.
VML-1520
Loudspeakers
Description:
VML-1520
* Is a general purpose15 Watt horn loudspeaker
Features
Technical data:
78
270
48
Rated power:
Impedance:
15 Watt RMS
20 ohm
Freq.range:
SPL at 1kHz:
275 - 7.000 Hz
106dB/1W/1m
Colourr/finish:
118Db/15W/1m
Grey
Material:
IP:
ABS
65
Dimensions:
Weight:
Mounting:
Termination:
Cable 0.5m
250
122
24
34,5 34,5
Mounting bracket
Holes: 3 x 11.0 mm
Document no.
Article no.
VML-15T
Loudspeakers
Description:
VML-15T
* Is a general purpose 15 Watt horn loudspeaker w/
transformer for use on deck areas, eng. room etc.
* To be used together with 100V line amplifier
Features
Technical data:
298
106
145
250
Rated power:
Tranf. tapping:
Freq. range:
SPL at 1kHz:
2,5m
122
24
34,5 34,5
Mounting bracket
Holes: 3 x 11.0 mm
Colour / finish:
Material:
IP:
Dimensions:
Weight:
Mounting:
Termination:
15 Watt
See dwg. beside
275 - 7.000 Hz
106dB/1W/1m
118Db/15W/1m
Grey
ABS
67
See dwg. beside
1,9 kg
Bracket (stainless steel
Grade 304)
Cable 2.5m
1kohm / 10W
670ohm / 15W
COM
Document no.
Article no.
SPS-4
Power Supply
Description:
Features
SPS-4 Ver.2.0
Power supply 115/ 230 VAC to 24VDC 4A with autoswitch
relay for main supply fails and powerfailure.
Technical data:
Input voltage AC:
Input voltage DC:
Hold-up time:
Rated Input current:
150
200
Efficiency
:
Output voltage:
250
Relay:
Cabinet Material / Finish:
Terminal:
Fuse:
Document no.
Article no.
BLK5
Common Equipment
Description:
BLK5
*
Optical signalling device of rugged design for indoor and
Features
Technical data:
107
6 mm
PG11
Manufacturer:
Comax
Material:
Case of aluminium
Dome of ABS
Colour:
Dimension:
Weight:
Cable gland:
Approx. 0,7 kg
PG11
IP rating:
Mounting direction:
IP-65
Unlimited
Flash frequency:
Temperatur range:
Flash energy:
5 Joule
130
AC version
Rated voltage:
230 Vac
Rated current:
0,07 A
DC version
Rated voltage:
15 - 32 Vdc
Rated current:
0,3 A
104
Document no.
Article no.
EHS-24
Signal Units
Description:
EHS-24
*
Rotary light for all systems.
Features
Technical data:
220mm
Manufacturer:
Sunbeam
Type / art.no.:
Colour available:
EHS-24
Orange-red-green-blue
Rotation speed:
Operation volt.:
180 rpm
24V DC
Rated current:
Dimensions:
2.6A
See dwg. beside
Weight:
0,9kg
147mm
1200
100mm
Document no.
Article no.
147mm
A-100
Signal Devices
Description:
A-100
* Audible signal device for all systems.
Features
87mm
=6mm
87mm
Technical data:
101mm
114mm
77mm
Manufacturer:
Type/art.no.:
Operation volt.:
Sound pressure:
12-24V DC
100dB at 1 metre
Rated current:
Sound options:
19mA
32 programmable tones
Freq. range:
Protection:
300 - 2900Hz
IP55
Dimensions:
Weight:
Document no.
Article no.
U2410
Talk-Back Systems
Description:
U2410
Cable inlet
198
Features
Technical data:
101
Colour:
Black
Type:
Voltage:
1 pole-switch
250 Vac
Current:
6A
40
Document no.
Article no.
www.vingtor.com
Zenitel Norway AS
DOC NO
A100K10864
support@vingtor.com
STENTOFON and VINGTOR products are developed and marketed by Zenitel Norway AS. The companys Quality Assurance System is certified to meet the requirements in NS-EN ISO 9001:2008. Zenitel Norway AS reserves the right
to modify designs and alter specifications without prior notice, in pursuance of a policy of continuous improvement. 2009 Zenitel Norway AS.