You are on page 1of 17

DOCUMENT No.

6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 1 of 17

ENGINEERING DESIGN BASIS


DESIGN PHILOSOPHY
5.7 ELECTRICAL

THIS DOCUMENT HAS BEEN APPROVED BY IOCL

10.02.05

IOCL Comments incorporated and issued for


implementation

02.11.04

Issued for clients comments/Approval

Rev.
No

Date

Format No. EIL 1641-1924 Rev. 1

Purpose

SA

RCS

AAN

SA

RCS

AAN

Prepared
by

Checked
by

Approved
by

Copyright EIL All rights


reserved

ENGINEERING DESIGN BASIS


ELECTRICAL

 %%$
1.0

Site conditions

2.0

Power Source Details

3.0

Power Supply Distribution System

4.0

Protection - Metering Control

5.0

Substation Design

6.0

Equipment Design

7.0

Cabling System

8.0

Earthing System

9.0

Lighting System

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0
Page 2 of 17

10.0 Electric Heat Tracing System


11.0 Electrical Equipment For Hazardous Areas
12.0 Statutory Approval
13.0 Cable Sizes for MV Motors
14.0 Specific requirements
15.0 Attachments
16.0 Deviation to design philosophy

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 3 of 17

The electrical design data defines the design requirements agreed by owner/clients in addition to
Design philosophy for electrical facilities no: 6-51-0099 Rev 4 (Any additional deviation must be
recorded as part of this document)

1.0

SITE CONDITIONS

A.
B.
C.
D.
E.

: 45C

Soil Resistivity

: Later (after the soil Resistivity test)

Minimum temperature. for battery sizing

: 10C

Equipment design temperature (IS 9676)

per IS-1893)
Altitude above mean sea level

2.0

POWER SOURCE DETAILS

2.1

General

A. Independent system or existing system


2.2

: Independent system

Grid Supply

A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
2.3

: <1000 m

* Refer CPP design basis

Name of sub station / MW

: *

Number of feeders

: *

Length of feeder

:*

Type of conductor/ cable size

: *

mm

Voltage

: *

kV

Frequency

: *

Hz

Minimum/maximum fault level

: *

kA /

KA

Design fault level / Basic Insulation Level

: *

kA /

kV

System neutral earthing

: *

Minimum load power factor stipulated by

: *

Supply authority

:*

Parallel operation of incomers

: *

Yes/No

PLCC requirement

: *

Yes/No

CPP and its configuration

A.
B.
C.
D.
2.4

* Refer CPP Design basis

Number / type of captive generators

: *

/Steam, Gas turbine

Generator rating/Voltage/Power factor

: *

MW/ kV/ 0.8

Parallel operation with grid

: *

Yes /No

Neutral earthing

High resistance earthed

Emergency generator

* Refer CPP design basis (Emergency

A.
B.
C.
D.
E.

Number / type of emergency generator

:*

Generator rating/Voltage/Power factor

:*

kW/ V/ 0.8

Starting

:*

Auto / Manual

Short time para

:*

Yes/No

Paralleling with grid system

:*

Yes /No

power for lighting from existing PREP power plant)

2.5

Details of Existing System

3.0

Refer CPP design basis

POWER SUPPLY DISTRIBUTION SYSTEM

Based on PREP-IOCL design basis and DFR

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 4 of 17

3.1

Voltage and frequency variation


AC System
i.
Voltage
ii.
Frequency

:
:

+6%
+3%

:
:

+ 10%
+%

Primary HV distribution voltage

33KV

Secondary HV distribution voltage

6.6 KV

Primary HV distribution system neutral earthing

Solidly earthed

Secondary HV distribution system Neutral

Resistance earthed

HV motor voltage

6.6KVabove 160KW & </= 6MW

MV motor voltage

415 VAC upto&including 160KW

Auto transfer at 6.6KV bus

Yes

Auto transfer at MV (At PCC Level)

Yes

Continuous Parallel operation of Incomers

B. DC System (at system output terminals)


i.
Electrical Control, Lighting etc.
2
ii.
Instrumentation Power Supplies
3.2

Utilisation voltage and operating philosophy

A.
B.
C.
D.
E.
F.
G.
H.
I.

HV

Yes /No (33KV-Yes, 6.6/11KVNo, 415V-No)

No

Yes/ No

Motors rated below 0.18 kW

240V AC, 1ph/ 415V AC 3ph

Battery chargers incoming power supply

415V AC, 3ph

UPS System incoming power supply

415V AC, 3ph

AC Lighting/Power Panels and Auxiliary


Boards incoming power supply

415V AC, 3ph

J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
3.3

PCC/PMCC
4

Load shedding

Welding Receptacles

415V AC, 3ph

Bulk loads like Process Heaters etc.

415V AC, 3ph

Normal Lighting/Emergency Lighting

240V AC, 1ph

Power factor improvement capacitors

As required

Convenience outlets

240V AC, 1ph

DC Motor

Not envisaged

415V AC, 3ph

Normal Instrumentation power supply

V AC

Critical instrumentation power supply

V AC/ V DC

Shut-down system power supply

V AC/ V DC

Switchgear protection and Critical lighting


power supply

220V, DC

E. DC supply for instrumentation


F. Plant communication system power supply

Independent system

415V, Normal,
backup

G. Fire alarm system power supply

240V AC Normal

Motor operated valves

Utilization voltage for critical supplies

A.
B.
C.
D.

with

battery

(With battery back up)


2

Refer instrument design basis


More than 6MW, the motor shall be connected on 11KV through dedicated transformers
4
Refer DB Document, section 11 of advanced E&I for load shedding
5
Refer instrument design basis for voltage choice for instrument loads
3

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 5 of 17

H. Annunciation panel power supply6


4.0

PROTECTION - METERING CONTROL

4.1

Metering for external power supply incomers

A. Summation metering
B. Trivector meter
4.2

V AC Normal/AC UPS
V DC (No separate Pnl)

Not applicable
:

Yes/No

Yes/No

Protection relays for HV switchgear

On Switchgear panel

HV Switchgear control

Local/ Remote/ ECS

Control Philosophy

A.
B.
C.
D.

Hard wired annunciation panel

No (Part of substation HMI)

:
:
:
:

Yes / No (Not applicable)


Yes
Yes
Yes

Numerical Protection/Monitoring system for

i.
ii.
iii.
iv.

EHV system
HV Switchboard
415V PMCC/PCC
415V MCC

E. Microprocessor based system for control interlocks :

Yes

and monitoring of electrical power system

i.
ii.
iii.

Human machine interface system-HMI :


Yes

Operator console
:
Yes

Engineering console
:
No, use LAP TOP instead
Data concentrator for each substation (Separate for HV and MV system)
8
:
Yes/ No
Interface with higher level control system:
Yes

F. Limiting Conditions for Motor start up


(e.g. starting current limitation or method of Starting)
9

i.
ii.

HV Motors
MV Motors

iii.

Method of starting for large HV motors :

iv.

Method of starting for large MV motors :

:
:

G. Type of power isolation for remote transformers10


i.
Load break switch in switchgear room :
ii.
Push button in transformer bay for tripping:

550% (No tolerance allowed)


600% up to 75KW, 550% above
75KW
Direct on line (refer foot note for
F(i)
Direct on line
No
for all transformers

Remote breaker

Hard wired annunciation panel is not proposed. Annunciation will be part of substation HMI
No grid backup is envisaged as per CPP design basis.
8
Separate data concentrators for HV and MV are not required for same make and type of relays
9
For motors greater than 2.5MW, maximum starting current shall be based on motor startup study
10
As 33KV switchboards are of rating 31.5KA and available in GIS, instead of local isolating panel, it is
suggested to provide push button station with lamp indication for trip of sending end breaker and requires
approval with CEA for implementation.
7

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 6 of 17

4.3

11

Relay protection system


Protection devices for power distribution system shall be as indicated below

Relay
number

51

Relay description

Feeder

IDMTL over-current relay

51N

Transformer

IDMTL earth-fault relay

(Secondary
winding
voltage

(Secondary
winding
voltage

> 3.3 KV)

< 0.433 KV)

Yes

Yes

Yes (7)

51G

51G
backup
earth-fault
(secondary neutral)

relay Yes

99

Motor protection relay with locked


rotor feature
No
(50, 50N,46, 49, 50L/R)

No

Motor
feeder

Outgoing feeder

Incomer

HV

HV

HV

MV
PCC/

MV PCC/
PMCC

PMCC
-

Yes
Yes

Yes

Yes

(4)

(13)

Yes

Yes

(4)

(13)

Yes (4)
Yes

Yes

No

No

No

No

No

Yes

No

Yes (8)

No

No

No

No

No

No

No

64R

Instantaneous restricted earth-fault Yes


relay (secondary side)

50

Instantaneous over-current relay

Yes

Yes

No

No

No

No

50N

Instantaneous earth-fault relay

Yes (6)

Yes

No

No

No

No

87

Differential protection relay

Yes (1)

No

Yes (2)

Yes (3)

No

No

No

86

High speed tripping relay

Yes

Yes

Yes

Yes

Yes

Yes

Yes

95

Trip circuit supervision relay

Yes

Yes

Yes

Yes

No

Yes

No

63

Transformer auxiliary relay

Yes

Yes

No

No

No

No

27/2

Under-voltage relay with timer

No

Yes
(5)

Yes (5)

Yes

Yes(9)

(14)
25

Check synchronisation relay

(9)

NOTES:
1. For transformers rated 5 MVA and above.
2. For motors rated 1500 kW and above.
3. For critical/long feeders and plant feeders connected to main power generation and
distribution bus.
4. These relay functions can be substituted by inherent releases. At remote substations where
DC supply is not envisaged, 415V switchboard shall have inherent releases instead of
relays.
5. Wherever auto-transfer feature is provided.
6. Instantaneous earth fault 50N shall be provided only for transformer with delta primary.
7. Directional IDMTL earth fault 67N shall be provided for transformer with star primary.
8. For motor feeders rated 55 kW and above.
9. For switchgears having bus transfer scheme, where continuous or momentary paralleling is
envisaged, check synchronising relay shall be integrated with overall paralleling scheme.
10. The bus tie feeders in HV switchboards shall be provided with 51, 51N, 86 and 95 relays.
However MV bus tie shall not have any protective relays.
11. HV capacitor bank feeders shall be provided with 51, 51N, 59 (over voltage), 60 (Neutral
displacement), 86 and 95 relays.
12. In case of HV switchboards with parallel operation of incomers, following additional relays
shall be provided:
a. One set of 87B (Bus differential) and 95 B (Bus wire supervision) for each bus
section.
b. 67 and 67N (Directional IDMTL over current & earth fault) relays for the incomers.
13. The following feeders shall be provided with timers for delayed tripping on bus under
voltage while the under voltage relay shall be common for the bus
a. HV and MV capacitor feeders

11

Generator protection requirement shall be covered separately in respective EPCC document.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 7 of 17

14.

15.
16.
17.

4.4

b. HV and MV breaker controlled motor feeders or contactor feeders with DC control


supply.
c. One no. DC supply supervision relay (80) shall be provided for each incoming DC
supply to the switchboard.
One set of bus differential relays (87B) and bus wire supervision relay (95 B) for each bus
section shall be provided for HV switchboards connected directly to generation buses and
those used as extension buses at remote substation.
In case of numerical relays, all relays shall be comprehensive units including all protection,
metering and control unless other wise specified.
Breaker control switch shall be hardwired type in addition to control switch as a part of
numerical relay.
Transformer trouble 63TX relay shall be provided for all transformers and relay shall be
located on MV side in case of remotely located transformers. This function shall be realized
part of numerical relays.

Metering
The metering devices in EHV, HV and MV switchboards shall be as below :

Feeder Type

Hz

PF

MW

MWH

Hour
Run

MVAR

MVAH

MVA

EHV Incomers
EHV Bus Tie
EHV Transformer
EHV Bus P.T.
HV Incomer

(2)
HV Bus Tie

HV Transformer

HV Bus P.T.

HV Plant Feeder

HV Motor

(2)

(2)

(1,2)

kWh
HV Capacitor

PCC/PMCC Incomer

kWh
PCC/PMCC Bus Tie

PCC Bus P.T.

ACB Outgoing

kWh
MV Motor (>55kW)

MCC/ASB Incomer

MCCB/SFU
O/G(250A)

LDB Incomer

DG Set

kW

kWh

kWh

NOTE
1.
2.
3.
4.

:
MVA meter in Grid Incomers shall include maximum demand indication also.
MW, MVAR, MVA, MVAH meters shall be provided for only Grid Incomer feeders.
Field Ammeters are to be provided for all motors rated above 3.7kW.
All metering shall be part of numerical relay in case of electrical system having numerical
relays. Energy meter where provided separately shall be digital type.
5. Indicating lamps in switchboards shall be cluster type LED lamps as per EIL specifications.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

ENGINEERING DESIGN BASIS


ELECTRICAL

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0
Page 8 of 17

5.0

SUBSTATION DESIGN

5.1

EHV Switchyard

Not applicable

A. Type
B. Structure
C. Bus material
5.2

: String bus / Tubular bus


: Galvanised / Painted / RCC
: Aluminium / Copper

HV/MV Substation
Description

HV *

MV

Elevated with trays in cable cellar

Yes

No
12

Raised with internal trenches

Yes

All top cable entry with trays below ceiling

No

No

Yes

Pressurisation against ingress of dust

Yes

Yes13

Air-conditioned room for operator

Yes

No

Roof slab for

Power transformer

No

No

Distribution transformer

No

No

Note:
1. * Substation with long high voltage switchboards having substantial amount of cabling work
2. Battery room shall be preferably located in corner side at first floor of the substation
building.

5.3

Specific Equipment Locations

A. Batteries
Electrical switchgear batteries
UPS batteries

B. Battery charger for electrical system


Battery charger for instrumentation

C.
D.
E.
F.

UPS System

: Air conditioned room in control room

Lead-Acid and Nickel-Cadmium

: In separate rooms

Annunciation panel

Not envisaged/ HMI


annunciation
Operator
substation

Single/Double

Minimum oil/SF6

EQUIPMENT DESIGN

6.1

EHV Switchyard

to have
room
in

NOT APPLICABLE

A. Bus bar system


B. Circuit breaker type
C. Isolator type

: Pantograph/ Semi pantograph/ Centre rotating/ Centre break

HV Switch-board

A.
B.
C.
D.
6.3

: In substation air conditioned room


: In Control room along with UPS.

Variable speed drive panels/Thyristor control panel : Air-conditioned room in substation

6.0

6.2

: Separate room in sub-station


: Separate room in control room

Execution

Drawout (Fixed for GIS-33KV)

Bus bar system

Single/(Double bus for GIS)

Circuit breaker typ

SF6/Vacuum

Motor Control

Breaker/ Vacuum contactor

1/5A

Current Transformer (CT)/potential Transformer (PT)

A. CT Secondary

14

Protection

12

HV cables in cable cellar shall be laid in trenches filled with sand


Pressurization not required for remote MCC room located in safe area
14
1A Protection CT for differential, REF protection; Separate CT for differential/ REF protection
13

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 9 of 17

Metering

B. PT Secondary
6.4

1A (No separate metering CT


except Metering CT for motor
PB stn
:

Transformers (Power/distribution)

110 V AC

15

Transformer

Vector
group

Tap changer

Soak pit

Main power transformer

Yyo/Dy1

OLTC

Yes

Generator unit transformer

Ynd 11

Off-circuit

Yes

Intermediate power transformer

Dyn 11

OLTC/Off-circuit

Yes / No

Dedicated (e.g. for VFD)16

As Reqd.

Off-circuit

Yes / No

Distribution transformer

Dyn 11

Off-circuit

No

Preferred
(kVA)

rating

(< 2000 KVA)

6.5

MV Switchboard

A. Execution
i.

ii.
iii.
iv.
v.

PCC / PMCC
Breaker panels
Contactor feeders
MCC
ASB
LDB
Motors
PMCC
MCC
17
Type of switchboard for package

:Draw out/Single front


:Drawout, single / Double front
:Drawout, single / Double front
:Drawout /Fixed, single/Double Front
:Drawout /Fixed: single/Double Front
: Above 55KW Upto&Including 160kW
: Upto and including 55 kW
: Compartmentalised/Fixed type

vi.
B. Motor Starter Type
i.
Contactor and switch fuse with overload relay: Up to 22 kW
ii.
Contactor, switch fuse and overload relay with: Above 22 up to 55 KW
iii.
iv.
v.
vi.
vii.

CBCT for earth fault protection


Contactor and switch fuse with motor protection relay
:
Above 55 up to 160KW
Air circuit breaker with motor protection
:
No
Contactor and MCCB with overload relay:
No
Contactor, MCCB and overload relay with CBCT:No
for earth fault protection
CT for remote metering
:
Motor rated above 5.5KW

C. Motor Controls18
i.
Auto / Manual switch
: Near motor/Switchgear/control room
ii.
Local/remote switch
: Near motor/Switchgear/control room
iii.
Normal / Standby switch
: Near motor/Switchgear/control room
iv.
Process interlock
: PLC /relay panel/switchgear
v.
Reacceleration equipment
: PLC /relay panel/switchgear
vi.
Control voltage for Contactor Starter :
240V AC
vii.
Control supply for contactor starter
:
Control transformer.
viii.
Separate transformer for each bus section:
Yes/No

15

Rating of Power and intermediate transformers, OLTC requirement including vector grouping of all
transformers shall be decided during basic engineering based on KSLD attached with FEED.
16
To be finalized based on licensors recommendation
17
Package like AC plant MCC, Bagging plant MCC etc
18
6.5C(i to iv): Operating philosophy and location of controls shall be as per process and instrumentation
design basis.
Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 10 of 17

6.6

Motors
Motors

High voltage

415 volts
IP55/IP54

Enclosure:

Indoor

IP55/IP54

Outdoor

IP55

IP55

Insulation class

F (Temp. Rise limited to B)

Terminal box

Phase segregated/ Phase separated / Phase insulated

Anti-condensation heater

Yes

30 kW and Above

Additional canopy (outdoor motors) Yes

Yes

Design
voltage
variation

6 % / 3%

frequency 6 % / 3%

Note: Motors for MOV actuator shall have F class of insulation with temperature rise limited to
class-B.

6.7

UPS System

A.
B.
C.
D.
E.
F.
G.
H.
I.
6.8

: 50% /100%

Type of redundancy

: Parallel redundant/Hot standby

Back-up time

: 120 minutes

Inverter bypass transformer

: Static

Bypass transfer control

: Auto / Manual

Separate fault diagnostic unit

: Yes/No

Battery type

: Lead acid/Ni-Cd/VRLA

Type of UPS

: IGBT/Transistorised

Battery execution

/servo controlled

: Single bank up to 600 Ah/Parallel bank above 600 Ah

Communication System

A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
6.9

Redundancy

Plant Communication System


Telephone System

19

Yes

Yes

Telephone system and plant communication system :

Separate/Integrated

No. of intercom and external P&T lines

Later By IOCL

Battery type for telephone system

Sealed Lead acid (SMF)/ VRLA

Battery type for plant communication system

Sealed Lead acid battery/ VRLA

Battery backup time

120 min for both systems

Interface of Communication system with fire alarm system:

Yes

Interface of PA and telephone system

Yes

Type of communication system

Digital microprocessor based

Fire Detection and Alarm System

A.
B.
C.
D.
E.
F.
G.

Type

: Conventional/Analogue addressable

Name of buildings to be provided with detectors

: All buildings except watch tower

Battery type

:Sealed Lead acid (SMF)/Ni-Cd/VRLA

Battery backup time

:48hrs. (Normal) + 120 minutes. (Alarm)

Detection System

: Break Glass/ Smoke, Heat, linear beam

Type of manual call point

: With/Without call back facility


20

Number of Sirens and location

: 1 Number at Main control room

19

Plant wide Telephone and LAN system shall be common. Refer design basis for LAN system for details.
Siren shall be electronic type with 5 tones (as per IOCL comment clause 2.3.10 (9) on fire and safety
document no. 6556-00-16-47-DB-01), Number and range shall be modified as per the availability.
20

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 11 of 17

H. Power supply for Siren


I. Any specific requirement of range
6.10 DC System
A. Battery type
i.
Switchgear Protection, control
Control and critical lighting
Instrumentation System
Diesel Engine Starting
21
DC Motors

ii.
iii.
iv.

B. Battery back up time


i.
Switchgear Protection
Control, Lighting
Instrumentation
Diesel Engine Starting
DC Motors

ii.
iii.
iv.

: 415 V AC/DC normal supply


: 10 Km diametrical

: Lead acid/Ni-Cd/VRLA
: Lead acid/Ni-Cd/VRLA
: Lead acid/Ni-Cd/VRLA(automotive type)
: Lead acid/Ni-Cd/VRLA
:120 minute when no DG back up and
30 minutes where DG set is available
: 30 /60/120minutes
: 10Starts (FW pumps)& 6 Starts others
: refer foot note

6.11 Variable frequency drive


22
i.
Type of inverter
23
ii.
Number of pulse
iii.
By pass feature required
iv.
VFD rated output voltage

:
:
:
:

See foot note


6/12
Yes
As per licensor/FEED reqt.

6.12 Cables
The power and control cables shall have the following minimum cross sectional areas:

A.
B.
C.
D.
E.

24

Medium voltage power cable

25mm (Al)/2.5 mm (Cu)

Control cables

2.5 mm (Cu)

2.5 mm (Cu)

0.9 mm dia (Cu)

1.5 mm (Cu)

25

Lighting

Communication system

26

Fire alarm system

7.0

CABLING SYSTEM

7.1

Cable details

Design Criteria

High voltage27

Loads located beyond 1 km

1Core/ 3 Core Cable

Cable

Loads located 200-1000 m

1-Core/ 3 Core cable

1-core cable/ 3-core cable

Load located up to 200 m

3 Core Cable

Cable / Bus trunking

Loads beyond 1 kA rating

Bus duct / cable

Bus duct /1 core cable

Recommended limiting size of multi-core


cable (mm)

300

300

Short-circuit withstand time (seconds)

0.2 (Outgoing)/0.60 (Plant)/1.0


(Incomer)

N.A.

Insulation voltage grade

Earthed for both 33KV and


6.6KV system

Earthed

Type of cable insulation

XLPE

PVC

415 volts

21

DC motor application is not envisaged


Licensors recommendation/ EIL equipment specification shall apply
23
6 or 12 pulse rectifier as per manufacturers standard and as required for meeting EIL equipment
specification requirement.
24
Cable for motor above 110KW shall be sized considering copper cable.
25
1.5 mm Cu conductor PVC Insulated wire shall be used in conduit with proper colour coding for building
lighting.
26
Cable sizes for PA and FA systems are indicative. These shall be finalised later as per the manufacturers
recommendation
27
1Core or 3 Core HV cable shall be decided during basic engineering based on load and distance
22

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 12 of 17
High voltage27

415 volts

Fire pump

Yes/No

Yes/No

Plant communication

Yes/No

Armour for cables inside the substation

Yes/No

Yes/No

Design Criteria
28

Fire survival (Resistant) cable

7.2

Cable laying philosophy

A. Process area29
B. Offsite paved area30
C. Offsite unpaved area

:Overhead cable tray /RCC trench-sand filled

D. Type of cable trays


E. Special requirements

:Galvanized prefabricated / Site fabricated and painted

:Above Ground cable tray on sleeper/overhead rack/ RCC trench


:Above Ground cable tray (on sleeper/ overhead rack) / directly
buried. (see footnote against point 7.2 above)
:Cables for fire water system shall be taken on exclusive route
through underground trench starting from main substation in case
applicable

F. Road Crossings for under ground cables31


G. Road Crossings for above ground cables
8.0

:Overhead cable bridge/culvert/ERC

EARTHING SYSTEM

A.
B.
C.
D.
E.

Earth electrode

: GI pipe

Main earth loop material

: GI strip

Substation earth loop

: GI strip

EHV switchyard earth grid

: Not applicable

Lightning system

: As per IS2309

9.0

LIGHTING SYSTEM

9.1

Supply System

A. Centralised with separate transformer32


B. At each substation with separate transformer
C. Separate metering required
9.2

:PVC Pipes /Cable culvert

: Yes/No
: Yes /No
: Yes/No

Control Philosophy

A.
B.
C.
D.
E.
F.

Outdoor yard

: Auto/Manual/centralised (ECS)/Local
33

Street lighting

: Auto/Manual/centralised(ECS)/Local

Outdoor process area

: Auto/Manual/Centralised (ECS) / Local

Process building

: Auto/Manual/centralised/Local

Auto control

: Yes-Synchronous timer/photocell/ No

Lamp type for outdoor lighting

: HPMV-Process area/HPSV-Street light,


FLM/
(Incandescent
type
for
DC/emergency Critical lighting)

G. Panel execution

34

: Lighting transformer fed LDB with OG


feeders for lighting panels

28

Where fire proof MOVs are provided cables shall be fire survival type as per IEC331 or mica insulated
Cables for FA/PA shall be laid in instrument duct where available and shall be in separate trays where ducts
are not available in ISBL.
30
FA and PA cables in offsite area shall be laid in road berm (opposite to berm used for lighting cable). Where
chemical handled are hazardous for PVC insulation, cables shall be laid above ground.In such cases. Cables
shall be laid overhead on pipe rack or above ground on sleeper level depending on availability of pipe rack/
sleeper. Where there is no rack/ sleeper, cable shall be laid in trenches if cables are large and directly buried if
cables are few.
31
Road crossing through PVC pipe or culvert shall be decided based on number of cables.
32
The secondary voltage for lighting transformer shall be 380V.
33
Lighting shall normally be done using 30m flood light mast as per IOCL philosophy. Street light shall be
considered only where considered absolutely necessary.
34
Local control shall be through FLP lighting panel in process area.
29

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 13 of 17

H. ELCB at Incomer of lighting and Power panels35


9.3

AC Emergency Lighting

A. Name of process plants


B. Name of buildings
C. Power supply
9.4

: All process Unit except U&O Pump stn


: All buildings- Plant and non plant
: As per CPP design basis

DC Critical Lighting For Escape

A.
B.
C.
D.
9.5

: Yes/No

Name of process units


36

: All process units

Name of building

: All buildings (see footnote)

Power supply

: 220V DC

DC lighting for remote substation

: (See foot note)

Wiring Type

A. Process plant / Building / Shed


B. Large service building
C. Buildings with false ceiling

: Armoured cable
: Concealed/ surface conduit
: cables/Surface conduit above false
Ceiling

D. Substation (Switchgear Room)


E. Substation (Cable Cellar)
F. Other buildings

9.6

: METSEC channel
: Surface Conduit/armoured cable
: Concealed/Surface, conduit/
cable(armoured/ unarmoured).

Specific Lighting Requirements

A.
B.
C.
D.
E.
F.

Aviation lighting
Navigation lighting

Yes /No

Yes/No

37

Security lighting for peripheral road at boundary wall :

Yes/No

Type of control gear for HPMV/HPSV Lamps

Separate/Integral

Control gear box location

Accessible level if separate

Type of flood light mast

30 m Telescopic fitted tubular

10.0 ELECTRIC HEAT TRACING SYSTEM


A. System Design Basis

: Product Classification /System approach

35

ELCB shall be provided at sub distribution feeder at LDB for lighting panels for AC as well as DC lighting.
All buildings except remote buildings not having DC supply shall be provided with DC lighting for escape.
For buildings where DC supply is not available, portable DC light for escape to be provided.
37
To be provided on watch towers through search light
36

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

ENGINEERING DESIGN BASIS


ELECTRICAL

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0
Page 14 of 17

11.0 ELECTRICAL EQUIPMENT FOR HAZARDOUS AREAS


The electrical equipment for hazardous areas shall be selected as per IS-5571 and petroleum rules
The minimum requirement is summarised below:
Equipment

Zone-1
Gas Group IIA, IIB

Zone-2
Gas Group IIC

Gas Group IIA, IIB

Gas Group IIC


Ex-e/Ex-n

MV Motors

Ex-d

Ex-d

Ex-e/Ex-n

HV Motors

Ex-d / Ex-p

Ex-d/ Ex-p

Ex-p/Ex-e/Ex-n/

Ex-e/Ex-n

Push Button Station

Ex-d

Ex-d

Ex-d

Ex-d

Motor Starters

Ex-d

Ex-d

Ex-d

Ex-d

Plug & Socket

Ex-d

Ex-d

Ex-d

Ex-d

Welding Receptacle

Ex-d

Ex-d

Ex-d

Ex-d

Lighting Fixtures

Ex-d

Ex-d

Div.2 Ltg.

Div.2 Ltg.

(IS-8224)

(IS-8224)

i. Lighting fitting
ii. Control Gear Box

Ex-d

Ex-d

Ex-e/Ex-d

Ex-e/Ex-d

Junction Boxes

Ex-d

Ex-d

Ex-e/Ex-n

Ex-e/Ex-n

i. Light fitting

Ex-d

Ex-d

Ex-d

Ex-d

ii. Transformer Unit

Ex-d

Ex-d

Ex-d

Ex-d

iii. Plug & Socket

Ex-d

Ex-d

Ex-d

Ex-d

Break Glass Unit

Ex-d

Ex-d

Ex-d

Ex-d

Ex-d

Ex-d

Ex-d

Ex-d

Hand Lamps

(Fire Alarm System)


Lighting Panel/Power Panel
Transformers

Hermetically sealed with surface temperature not exceeding 200C

Notes:
1. The electrical equipment for hazardous areas shall generally be suitable for gas group IIB
and temperature classification T3 as applicable to the selected type of explosion protection.
In case of hydrogen or hydrocarbon mixtures having more than 30% hydrogen, the gas
group to be considered shall be IIC.
2. As additional safety features, the following requirements for electrical equipment shall be
followed
a. All electric motors for vertical oil sump pumps including ETP area shall be
flameproof type.
b. Irrespective of the area classification (whether zone-1 or zone-2), all lighting
fixtures within the storage areas shall be flameproof type.
c. All emergency/critical lighting fixtures and associated junction boxes in hazardous
areas (whether zone-1 & zone-2) shall be flameproof type.
3. Even though fired heaters in process units are not considered for area classification, all
electrical equipments associated with fired heaters in process units shall as a minimum be
suitable for installation in Zone-2 area.
4. Where air conditioning system is designed considering ammonia as refrigerant, the room
housing air conditioning equipment shall be adequately ventilated to classify it as safe
area. For additional safety the following shall be considered:
a. 100% standby system for ventilation
b. Location of MCC/local panels in adjacent separate room.
c. Instrumentation to be flameproofs type or hermetically sealed.
d. AC plant room motors with type`e' protection.
e. Lighting in AC plant room suitable for zone-2 area.
5. Compressor sheds in hazardous area shall be designed to allow adequate ventilation to
allow area classification as Zone-2 Lighting equipment, EOT crane etc. in the shed shall be
flameproof type. All other electrical equipment shall be suitable for Zone-1 or Zone-2 area
depending on extent of hazard.
6. Motors fed from variable frequency drive in hazardous area application shall be type tested
as unit with the VFD panel in case of Ex(e) type of motors and provision for tripping the
motor in case temperature rise exceeds the permissible limits ,shall be considered for
flameproof motors as per relevant standards.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0

ENGINEERING DESIGN BASIS


ELECTRICAL

Page 15 of 17

12.0 STATUTORY APPROVAL

Statutory Authority for Electrical Installation


Hazardous area equipment

:
:

Central Electrical Inspectorate


CCE

13.0 CABLE SIZES FOR MV MOTORS


i. Direct on line (D.O.L) start motors (2/4 pole motors)38
Motor Rating

Cable Details
Number of runs

No. of cores
per run

Conductor material

Conductor
mm

Below 3.7 KW

Cu

2.5

3.7 KW

Cu

5.5 KW

Cu

7.5 KW

Cu

10

9.3 KW

Cu

16

11 KW

Cu

16

15 KW

Cu

16

18.5KW

Al

35

22 KW

Al

35

30 KW

Al

50

37 KW

Al

70

45 KW

Al

95

55 KW

Al

120

75 KW

Al

185

90 KW

Al

95

110 KW

Al

120

125/132 KW

Cu

120

160 KW

Cu

120

size

ii. Cable sizes for motors not confirming to above table e.g. for 2/4 poles motors, extended distance,
reduced voltage starting, low speed motors, shall be worked out on case to case basis.

iii. Cables sizes as indicated above are applicable for a distance up to 350m maximum and for 2/4
poles motors fed from MCCs located near PCCs and PMCCs.

iv. Cables for lighting shall be used to allow the following voltage dips

Street lighting

:10%

DC critical lighting

:5%

14.0 SPECIFIC REQUIREMENTS


i.
Canopy shall be provided for all out door equipment.
ii.
Substation shall be sized to ensure 2 nos panel extension on each bus section
iii.
iv.

v.

vi.
vii.

for all HV/ MV switchboards except GIS.


Dummy panel shall be provided in switchboards wherever there is expansion
joint in the building.
If signal cables for DCS interface with substations are envisaged, these shall be
laid in separate trays/ trench. However in exceptional cases signal cables may
be laid in electrical trench, properly cleated on trench wall allowing 300mm gap
with other power cables in the trench.
For building engineering, each office room, in addition to switch/ socket for
lighting design, shall be provided with minimum 2 nos telephone sockets and 2
number LAN socket at two different location as duly approved during detailed
engineering.
Modular type switches/sockets in main control room and all non plant buildings
shall be modular type.
Lamps shall be standardized for the purpose of inventory in hazardous area
lighting as below.

38

Cable sizes given in the table are indicative and standardized for inventory and are the minimum sizes. The
cable size as required to meet voltage drop criteria shall be provided.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

ENGINEERING DESIGN BASIS


ELECTRICAL

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0
Page 16 of 17

Well glass normal Lighting : 70W HPMV lamps for well glass fittings
Flood Lighting
: 250W HPMV lamps for flood lighting
Critical lighting
: 100W GLS lamps

15.0 ATTACHMENTS
Design philosophy for Electrical Facilities

6-51-0099

Rev 4

16.0 DEVIATION TO DESIGN PHILOSOPHY


Document number 6-51-0099 rev 4
The requirement given under engineering design basis document shall be overriding. However
following job specific requirement are highlighted as deviation to Design Philosophy of Electrical
facilities document number 6-51-0099.

16.1 Clause 4.6.1 Voltage drop


i.
b(ii) MCC/Aux switchboard situated remote from PCC/PMCC 2%
ii.
d - Cable between PCC/PMCC to motor- 5% during normal running
16.2 Clause 4.11 DC Power supply
i.
DC power supply system for electrical controls and for critical lighting shall be
separate. For electrical controls and instrumentation, DC system shall be dual
redundant with single set of battery and for critical lighting, DC system shall be
non redundant.

16.3 Clause 4.15.3 Plant communication system-capacity for future expansion


i.
Exchange supplied shall be fully wired for hardware, power supply, software etc
ii.

for the capacity as required with spare capacity of 20% field call stations with no
future modification in exchange hardware/ software.
Exchange shall have required hardware for communication between two
exchange of the same make

16.4 Clause 4.16 Fire detection and alarm system


i.
Cl 4.16.5 : Spare fire alarm loop for future shall be 20% or 1number whichever is
ii.

maximum. Each loop shall be engineered to provide the flexibility to add 20%
additional detectors in future, if required.
Cl 4.16.6 : The status for actuation of fire suppression system shall also be wired
to fire alarm panel to annunciate at central fire alarm monitor.

16.5 Clause 5.3 Switchgear


i.
Cl 5.3.4 : Each HV Switchboard (above 415V and except 33KV) shall have
ii.

minimum 2 numbers spares of each type. (i.e. type like transformer feeder, motor
feeder, plant feeders etc)
Cl 5.3.4 : Each MV Switchboard (Up to 415V) shall have 20% spares of each
type ( Spares in each MCC shall however be 20% subject to 1 number of each
motor feeder module )

16.6 Clause 5.7 Battery charger and Distribution board


i.
Cl 5.7.3 : Each DCDB shall have 20% spare feeder for future use.
ii.
DCDB outgoing feeders for critical lighting shall be provided with ELCB.
16.7 Clause 5.8 Uninterrupted power supply system
i.
Cl 5.8.4: Spare feeders in ACDB shall be 20% for future use with minimum of 1
ii.

number of each rating.


Cl 5.8.5 : UPS shall be sized to have 20% spare capacity on calculated load for
future loads.

16.8 Clause 5.13 Cable and Wires


i.
Cl 5.13.6 : No unarmored cable shall be used.
ii.
Cl 5.13.10 : Control cables shall have 1core spare upto 6core requirement and
20% or 2 core whichever is maximum for cables having requirement above 6
cores.
Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved

ENGINEERING DESIGN BASIS


ELECTRICAL

DOCUMENT No.
6556-00-16-50-DB-01
Rev.0
Page 17 of 17

iii.
iv.

For 4-20mA signal interface between switchboards and DCS, screened cable
shall be used.
Cl 5.13.7 : Cables laid for hazardous area shall not have any joints.

16.9 Clause 5.14 Control stations


i.
Cl 5.14.1 : Each motor shall be provided with local control station. If specified per
process or equipment control requirement, local control station can be part of
local control panel.

16.10 Clause 5.16 Actuators for motor operated valves


i.
MOV shall have separately mounted actuator in area of high vibrations. In
particular the MOVs for Cooling water application shall have separate actuator
located near the valve for local actuation.

16.11 Clause 7.2 Cabling System


i.
Clause 7.2.5: Cable trays shall be sized to allow 20% additional space for future
ii.

cables.
Clause 7.2.14: MCTs shall be provided wherever the entry is above ground. And
where entry is below ground, sleeves (Laid in outward slope to avoid water entry)
shall be provided for electrical cables.

16.12 Clause 7.4 Lighting system


i.
Non-plant buildings such as administrative building, gatehouses etc should be
ii.

provided with energy efficient CFL lamp fixtures.


In plant buildings, control rooms should be provided with energy efficient CFL
lamp fixtures.

Format No. EIL 1641-1924 Rev. 1

Copyright EIL All rights


reserved