Professional Documents
Culture Documents
Contents:
ABB AG
Revision
Document number:
Revision
Date
Description
6/2010
Initial version
05/2011
We reserve all rights in this document and the information containing therein.
Reproduction, use or disclosure to third parties without permission is strictly
forbidden
Copyright 2011 ABB, Mannheim/Germany
ABB AG
III
Contents
Revision ...........................................................................................III
Contents........................................................................................... V
Abbreviations .................................................................................. V
1
Introduction............................................................................ 1-5
1.1
1.2
2.2
2.3
2.4
2.5
2.6
2.7
ABB AG
3.3
3.4
3.5
ABB AG
VI
Abbreviations
ABB AG
CMU
AMI
ASO
BCU
BSI
BSO
CS
Control System
CSC
CS-Command
CRC
CTO
DCO
DMI
DPI
DSO
EPI
GCD
HCI
IED
IIN
Internal Indication
IOC
IOD
IOM
ITI
MFI
MPU
NCC
PB
Peripheral Bus
PBP
PDP
PLC
PPP
PSU
RCO
RTC
SBO
SCADA
VII
ABB AG
SCI
SCO
SEV
System Events
SLC
SOC
SOE
Sequence-of-Event Queue
SPI
STI
TSI
TSO
VIII
1 Introduction
1.1
1.2
Part 1: Overview
ABB AG
1-1
2.1
Indication Processing
There are two types of indications:
Single point input (SPI)
Double point input (DPI)
Figure 2-1 shows the signal definition for SPI and DPI. Double indications are
represented by two sequential bits within a binary input board. The normal state of a DPI
is a non-equivalent bit combination (10 or 01). An intermediate state (00) is given during
the runtime of a unit from one position to the other (e.g. an isolator from OFF to ON).
Signal state
Signal state
ON
OFF
OFF 1
0
ON 1
0
10
OFF
00
01
ON
1
0
0
OFF
11
faulty position
normal position
Figure 2-1:
1
ON
0
OFF
OFF
ON
intermediate position
16 15 14 13 12 11 10 9
DPI 2 DPI 1
The definition of the bit position for ON and OFF can be changed for the whole
configuration. If changed, this definition is also valid for DCO and RCO commands.
Parameter:
(RTU Parameters)
Within an indication board, any type of binary input can be mixed but it has to be
considered that a DPI can start on odd bit-positions only. Inputs not assigned to DPI or
SPI may be configured to indications as pulse counters, digital measured values on bit
string inputs. Digital measured values and bit string inputs must be configured as starting
either with bit position 1 or 9.
ABB AG
2-1
2.1.1
Function Distribution
The process data acquisition functions for indications processed by the RTU560 can be
split into functions handled by the:
I/O controller (IOC) of the binary input boards
process data processing (PDP) part of the CMU
protocol specific communication interface part at a CMU
The data processing functions of the communication interface is described in the
documentation of the specific communication protocol.
Binary input board functions:
Reading input register (every millisecond)
Digital filter (contact bouncing)
Oscillation suppression (signal chattering)
Signal inversion
Time out monitoring for DPI intermediate position
Store events in FIFO with time stamp
CMU - PDP:
Intermediate midpoint position handling for DPI
Command output response
Group signals
Transmission to internal communication
2.1.2
Parameter: Blocked
Digital Filter
The configuration parameter Digital filter specifies how many milliseconds an input has to
be stable before it is accepted as a new signal state. The typical value is 10 ms. Digital
filter is used to prevent ordinary contact bouncing.
Parameter: Digital filter
ABB AG
2-2
If an indication has changed its state and should be transmitted as an event to the PDP,
the time stamp of the event is the time of the last edge before the filter time elapsed.
input channel
1
0
7
6
5
4
3
2
1
0
1ms
time
(a)
Figure 2-2:
ABB AG
2-3
Oscillation Suppression
Indications which change their state very often produce a higher transmission load to
NCC. To prevent a permanent transmission it is possible to specify an automatic
indication blocking if the number of events per time period exceeds a defined value.
Oscillation suppression may be activated or deactivated individually per indication. The
configuration parameter is Maximum chatter frequency
Maximum chatter Frequency is defined to:
number of changes
second
Tosc
2000
[milliseconds ]
MAX CHA FREQ
Tosc is the monitoring period. The maximum value is 100Hz, a typical value is 2.
The binary input board is loaded with the parameter. Each leading edge of 0->1 starts the
monitoring period tosc. Within that time interval each leading edge increments the chatter
counter register of that indication. The third change within that period puts the indication
into the dynamically blocked state. The binary input board informs the PDP by an internal
event. It starts a reset time period (fix to 60 seconds). Within that reset time, each new
start trigger (0->1 edge) starts tosc again. If the indication state is stable for at least this
reset time period, the binary input board informs PDP again by an internal event.
Input channel
1
indication 0
chatter counter
register
60 sec
reset time
3
2
1
0
tosc
tosc
tosc
Figure 2-3:
ABB AG
time
Oscillation Suppression
2-4
2.1.3
ABB AG
2-5
0
OFF 1
0
DPI
1
ON
0
1
OFF
0
DPI
1
ON
DPI
1
OFF
DPI
0
OFF 1
0
DPI
DPI
1
ON
0
1
OFF
0
DPI
DPI
1
ON
1
OFF
0
DPI
Figure 2-4:
ABB AG
2-6
Signal Inversion
After having a stable indication signal, it is possible to define its logical state,
corresponding to the signal voltage level. This function is called the signal inversion. The
inversion is defined by a configuration parameter Invert the input value.
INVERSION = NO
0V
Process Voltage
logical 0 = OFF
logical 1 = ON
Table 2-1:
INVERSION = YES
Process Voltage
0V
Definition of Inversion
All other functions are then based on the signal state given by the inversion parameter.
Parameter: Invert the input value
2.1.4
Error Handling
Binary input board failure
A board can be set "out of service" if:
the board has never been in service
(configuration error)
the board failed during normal operation
(hardware failure, I/O bus failure etc.)
the board has been removed or rack power was lost.
If a board is set out of service the qualifiers of all configured indications are set
INVALID due to board failure. The RTU560 treats all DPI and SPI messages of that
board with qualifiers IV = 1.
A board can be set in service again during runtime if:
the board is replaced
power is turned on again in the rack
the I/O bus is working properly
When this happens, the following sequence recovers the indications:
normalize the binary input board
load all parameters for the configured indications (done by PDP)
read all values (signal state)
Reset qualifier IV to 0 and transmit the actual value and qualifier status to NCC.
ABB AG
2-7
2.2
2.2.1
[digits]
+ 4096
3000
2000
e.g. -20..+20
mA
1000
-20
-100
-15
-10
-5
5
25
10
50
15
75
20 [e.g. mA]
100 [%]
-2000
Input signal
-3000
- 4096
Figure 2-5:
2.2.2
Function Distribution
The process data acquisition functions for analog measured information processed by the
RTU560 can be split into functions handled by:
IOC of the analog input board
Process data processing (PDP) part of the CMU
Protocol specific communication interface at a CMU
The data processing functions of the communication interface is described in the
documentation of the specific communication protocol.
ABB AG
2-8
2.2.3
60 Hz:
16.6 Hz:
The scan frequency is independent from the number of configured channels. The Line
frequency must be equal to the analog input boards hardware setting (board wide
parameter).
Parameter: Line frequency
ABB AG
2-9
The switching detection is a special function of the analog input boards. It is used to force
a value update to PDP if a signal changes only some few percent from/to zero. The
function is only active when threshold supervision with integration is selected. The
threshold supervision on integrator algorithm would need some cycles before the
threshold is exceeded and reported to NCC. This gives a transient situation, e.g. the 380
kV transmission line is switched but the actual current does not change more or less
immediately.
Switching detection operates in that form that every time a signal changes to/from 0 %
from/to more than 2.5 % the new value is transmitted to PDP immediately. If the new
value is below 2.5 % an event is not forced. PDP transmits the received value to NCC
regardless of any other parameter.
Switching detection is a fixed parameter and can not be parameterized
Figure 2-6:
ABB AG
2-10
Smoothing
Unstable input signals may be smoothed to prevent too many CS updates. Smoothing
can be parameterized per input by the configuration parameter Smoothing. No smoothing
can be configured. The smoothing factor is given in binary factors.
Parameter: Smoothing
Figure 2-7:
MWngl
ABB AG
MW MWagl
K
MWagl
MWngl
MW
MWagl
2-11
Figure 2-8:
ABB AG
2-12
threshold base 1s
Threshold / 0.58
12%
60 Hz:
threshold base 1s
Threshold / 0.5
10%
16.6 Hz:
threshold base 1s
Threshold / 1.62
25%
Parameter: Threshold
Line frequency
The periodic update is independent of threshold supervision with integration. That means
a value might be transmitted twice to PDP in a cycle:
caused by threshold exceeding
caused by periodic update
The periodic update time is selectable between 1, 2, 4, 8, 30 and 60 seconds.
ABB AG
2-13
2.2.4
Scaling
The PDP converts the value to a normalized AMI format. The parameter Conversion
factor specifies the percentage of the maximum input signal that is defined as 100 % of
the normalized value.
Parameter: Conversion factor
ABB AG
2-14
Unipolar
Bipolar
100% -100%
-100%
-1
-1
Figure 2-9:
Live Zero
4 40 mA
8 16 24 32 40
20 40 60 80 100
-100
1 5 mA
2 10 mA
4 20 mA
8 40 mA
100%
[mA]
[% Imax]
-1
-1
20 40 60 80 100
[%]
-100
-1
12
20
[mA]
-1
ABB AG
2-15
Input
[%]
new value
100
new value
new value
80
new value
threshold value
60
new value
40
New value transmission to CCI
20
time
periodic
update cycle (uc)
Figure 2-12:
Only one method can be used for threshold supervision. Either the integration method or
nor absolute threshold.
ABB AG
2-16
2.2.5
Error Handling
AMV overflow and/or A/D converter errors
The analog input board checks at start up and during each conversion the functionality of
the A/D converter. If an error is detected the AMIs are marked invalid. The qualifier IV is
set to 1 and transmitted to NCC with the new state.
For AMIs with live zero conversion, a value below 3,5 mA is marked as invalid.
ABB AG
2-17
2.3
ABB AG
2-18
Figure 2-13:
ABB AG
2-19
2.3.1
Parameter: Blocked
Digital filter
The configuration parameter Digital filter specifies how many milliseconds an input must
be stable before it is accepted as a new signal state. The typical value is 10 ms. Digital
filter are used to prevent ordinary contact bouncing.
Parameter: Digital filter
Consistency check
A DMI is a bit pattern of 8 or 16 bit length. The value is valid only if all binary channels of
the DMV are valid and stable for at least the consistency check time. This is given if no
input changed for the parameterized consistency check time. Any change on an input
channel re-triggers the settling time.
The minimum settling time is defined by the PDP parameter Consistency check time. The
minimum consistency time is 100 milliseconds.
Parameter: Consistency check time
2.3.2
ABB AG
2-20
PV
0V
0V
0V
0V
0V
0V
PV
Invert the
sign
= NO
= NO
= YES
= NO
= NO
= YES
= YES
= YES
0V = 0V;
Figure 2-14:
PV = Process voltage;
S = Sign bit
2.3.3
Maximum value
Error Handling
Binary input board failure
Binary input boards can be set "out of service":
the board has never been in service
(configuration error)
the board failed during normal operation
(hardware failure, I/O bus failure etc.)
the board has been removed or subrack power was lost.
If a board is set out of service the configured digital measured values are to the invalid
state. All DMI/STI are set faulty. The RTU560 transmits the DMI/STI values of that board
to the NCC with the corresponding message and the qualifier IV = 1.
Binary input boards can be set in service again during runtime if:
the board is replaced
power is turned on again in the rack
the I/O bus is O.K.
ABB AG
2-21
ABB AG
2-22
2.4
2.4.1
Function Distribution
The data acquisition functions for digital measured values processed by the RTU560 can
be split into functions handled by:
IOC of the binary input board
Process data processing (PDP) part of the CMU
Protocol specific communication interface part at a CMU
The data processing functions of the communication interface is described in the
documentation of the specific communication protocol.
Binary input board functions:
Reading input register (every millisecond)
Digital filter (contact bouncing)
Consistency check
Store events in FIFO with time stamp
CMU - PDP:
Transmission to internal communication
ABB AG
2-23
2.4.2
Digital filter
The configuration parameter Digital filter specifies how many milliseconds an input must
be stable before it is accepted as a new signal state. The typical value is 10 ms. Digital
filter are used to prevent ordinary contact bouncing.
Parameter: Digital filter
Consistency check
A BSI is a bit pattern of 8 or 16 bit length. The value is valid only if all binary channels of
the BSI are valid and stable for at least the consistency check time. This is given if no
input changed for the parameterized consistency check time. Any change on an input
channel re-triggers the settling time.
The minimum settling time is defined by the PDP parameter Consistency check time. The
minimum consistency time is 100 milliseconds.
Parameter: Consistency check time
ABB AG
2-24
2.4.3
Error Handling
Binary Input Board failure
A binary input board can be set "out of service":
the board has never been in service
(configuration error)
the board failed during normal operation
(hardware failure, I/O bus failure etc.)
the board has been removed or rack power was lost.
If a board is set out of service the configured digital measured values are to the invalid
state. All BSI are set faulty. The RTU560 transmits the BSI values of that board to the
NCC with the corresponding message and the qualifier IV = 1.
A binary input board can be set in service again during runtime if:
the board is replaced
power is turned on again in the rack
the I/O bus is O.K.
When this happens, the following sequence recovers the BSIs:
normalize the binary input board
load all parameters for the configured BSIs (done by PDP)
read all values
Reset qualifier IV to 0 and transmit the actual value and qualifier status to NCC.
ABB AG
2-25
2.5
2.5.1
There are two types of integrated total values (ITI) defined in the RTU560:
End of period reading counters (EPR)
Intermediate reading counters (IR)
Both types have only one source and the IR is only an intermediate value of the
corresponding EPR. That means there is one ITI which is transmitted periodically in fixed
periods.
Counts
Period
Intermediate
reading
cycle
Figure 2-15:
Period
End of
IR
Period reading
reading
Period
End of
Period
reading
time
Period
End of
Period
reading
End of
Period
reading
ABB AG
2-26
2.5.2
Function Distribution
The process data acquisition functions for ITIs processed by the RTU560 can be split into
functions handled by:
IOC of the binary input boards
Process data processing (PDP) part of the CMU
Protocol specific communication interface part at a CMU
The data processing functions of the communication interface is described in the
documentation of the specific communication protocol.
23BE23 functions:
Reading input register (every millisecond)
Digital filter (contact bouncing)
Increment integration register
Freeze integration register into relocation register
CMU - PDP:
Freeze and read ITIs periodically
Transmission to internal communication
2.5.3
Digital filter
The configuration parameter Digital filter specifies how many milliseconds an input must
be stable before it is accepted as a new signal state. The typical value is 10 ms. Digital
filter are used to prevent ordinary contact bouncing.
Parameter: Digital filter
ABB AG
2-27
2.5.4
With the PDP parameter Acquisition of intermediate reading ITI the transmission of IR
readings can be switched of or the IR period is specified. With Unit of IR cycle it is
possible to decide whether IR period is defined in second or minute cycles.
Parameter: Acquisition of intermediate reading ITI
Unit of IR cycle
ABB AG
2-28
The flag is set in the first telegram of an intermediate value (IR) and in the first telegram
of an end of period value (EPR). If the EPR telegram comes first the qualifier is not set in
the following IR telegram.
IV = ITI is invalid
This flag is set if the ITI value is not valid because the PDP could not receive the value
from the binary input board.
Figure 2-16:
IT = Invalid time
This flag is set in the time information element of the ITI telegram until the RTU560 has a
valid system time and is synchronized after start up.
ABB AG
2-29
2.5.5
Error Handling
Binary Input Board failure
A binary input board can be set "out of service" if:
the board has never been in service
(configuration error)
the board failed during normal operation
(hardware failure, I/O bus failure etc.)
the board has been removed or rack power was lost.
If a board is set out of service the configured ITIs qualifiers are set to invalid due to
board failure. The RTU560 transmits all ITI messages of that board to the NCC with an
ITI message and the qualifier IV = 1.
A binary input board can be set in service again during runtime if:
the board is replaced
power is turned on again in the rack
the I/O bus is O.K.
When this happens the following sequence recovers the pulse counter values:
normalize the binary input board
load all parameters for the configured channels (done by PDP part of CMU)
read all values and update status
Reset qualifiers IV for affected ITIs
Dynamic Qualifier Changes
An integrated total value can change qualifier status at runtime if:
the binary input board fails (qualifier IV = 1)
ABB AG
2-30
2.6
Measuring Path(s)
Voltage (V)
Current (A)
1, 2, 3, N
Active Power
1, 2, 3,
Reactive Power
Apparent Power
Power Factor
1, 2, 3,
Frequency (Hz)
Phase 1 only
Accumulated values are stored in energy registers of the 560CVT02/10 as long integer
values. On power up these values are reset to zero. The accumulated values are
cyclically transmitted to the RTU560:
Active Energy 3-phase
Apparent Energy 3-phase
Reactive Energy (Ind.) 3-phase
Reactive Energy (Cap.) 3-phase
The 560CVT02/10 provides a measure of the distortion (THD), in each phase voltage and
current waveform, as a percentage deviation from pure 50 Hz or 60 Hz sine waves by
Fast Fourier Transform algorithm (FFT):
U1, U2, U3 % THD
I1, I2, I3 % THD
The measurements (AMI, MFI) are transmitted by the subdevice communication
interface.
While MFIs are handled in the same way, AMIs are treated differently by the 560CVT02
and the 560CVT10. To convert these values into a normalized representation
AMIs are using the parameters primary rated value and measurement range
(560CVT02)
AMIs are using the highest possible value according to the conversion table in the
instruction manual (560CVT10)
All measurements are representing the secondary output of the transformer.
Parameter
ABB AG
(560CVT02 parameter)
(560CVT02 parameter)
(560CVT02 parameter)
(560CVT02 parameter)
(560CVT10 parameter)
(560CVT10 parameter)
2-31
For example:
Secondary rated current
5 Ampere
0.5
Example 120 V
Range = 1,0
Value
- 120 Volt
- 100 %
0 Volt
+ 120 Volt
+ 100 %
Lower Limit
Upper Limit
The Frequency is detected at the phase 1 voltage signal and converted to a normalized
representation, using the parameter nominal frequency:
Parameter:
Nominal frequency (560CVT02 - parameter)
Frequency
Example 50 Hz
Nominal frequency
Value
Nominal frequency * 90 %
45,0 Hz
- 100 %
Nominal frequency
50,0 Hz
55,0 Hz
+ 100 %
Value
- 1,000
- 100 %
+ 1,000
+ 100 %
Value
- 100 %
100,0 %
+ 100 %
All Energy Values are cyclically requested by the RTU560 subdevice communication
interface and transmitted as Integrated Total Information (ITI):
Parameter:
IR / EPR cycle time
(560CVT02/10 - parameter)
ABB AG
(560CVT02/10 - parameter)
2-32
OR group
The output signal of an OR group is set to 1 when at least one input signal is set to 1. The
first signal, which is set to 1, forces the transmission of the OR group signal.
The output signal of an OR group is set to 0, when all input signals are 0. The trailing
edge of the last signal which is set to 0 forces the transmission of the OR group signal.
AND group
The output signal of an AND group is set to 1 when all input signals are set to 1. The last
input signal which is set to 1 forces the transmission of the AND group signal.
The output signal of an AND group is set to 0, when at least one input signal goes to 0.
The trailing edge of this signal forces the transmission of the AND group signal.
NOR group
The output signal of a NOR group is set to 0 when at least one input signal is set to 1.
The first signal which is set to 1 forces the transmission of the NOR group signal.
The output signal of a NOR group is set to 1, when all input signal are 0. The trailing edge
of the last signal which is set to 0 forces the transmission of the NOR group signal.
Dynamic OR group
The output signal of a dynamic OR group is set to 1 every time a input signal is set to 1.
Every signal which is set to 1 forces the transmission of the OR group signal.
ABB AG
2-33
The output signal of a dynamic OR group is set to 0, when all input signal are 0. The
trailing edge of the last signal which is set to 0 forces the transmission of the OR group
signal.
Security indication and Security alarm
These two functions differ from all other logic functions by their input parameters:
Generally, these functions have security events as input parameter.
Security indication
If one ore more input security event occurs, a pulse of approximately 100ms is generated
at the SPI output.
Security alarm
A security alarm is similar to a Security indication, but the output is triggered only if any
input event has occurred several times within a specified supervision time period. The
event count and the supervision time can be configured in RTUtil560.
In case of redundant CMUs the current event count and the current elapsed time will be
reset if the active CMU fails, so it's recommended to monitor security event # 5160 ("RTU
new started") to be able to recognize this situation.
Qualifier for group signals
A group signal qualifier represents the logical OR of the qualifiers of all input signals of
the group information. That means, that if the state of one of the inputs is not equal to
O.K., the output of the logic function is set to this state.
ABB AG
2-34
The following SCADA functions are described for the binary output boards
23BA20, 23BA40 and 23BO61, and the analogue output boards 23AA21 and
23AO60 as well as the binary outputs of the integrated multi input/output board
within the 560CIG10. In addition the functionality of the command supervision
boards 23BA22/23, 23BO62 and the supervision function of the 560CIG10 is
described.
The RTU560 knows following output command types:
Command Output
o
3.1
Function Distribution
Within RTU560, the different output boards and, if requested, the command
supervision board 23BA22/23, are responsible to do the command outputs. They
are coordinated and monitored by the PDP.
The IOCs of the output boards are responsible to switch the output relays or to set
the analog output value. They supervise and monitor also the hardware. Which
kind of output is configured and wired on which channel is loaded by the PDP to
the boards during initialization in a similar form as for the input boards.
3.2
(PDP Parameters)
If the PDP receives a SELECT command, it checks whether the object is available
and if no other object is already reserved. If the check is successful, it
acknowledges the reservation with a positive confirmation. The reservation is valid
for 20 seconds. Within that time window, either the corresponding EXECUTE
Command or a DESELECT command should be received. If not, the PDP clears
the reservation of the object.
If an EXECUTE command is received within the allowed time, it is checked, if the
referring object is equal to the reserved object. If both objects are the same, the
command is executed, otherwise the EXECUTE command is rejected and negative
confirmed. The command procedure is finished, when the activation termination is
transmitted for that command.
ABB AG
3-1
(RTU Parameters)
ABB AG
3-2
3.3
3.3.1
Single object commands can be wired with one relay contact per command (1 pole
connection) or with two relay contacts per command (2 pole connection).
Single Object commands are pulse outputs whereas the pulse duration is specified
by the parameter Command pulse length per command. Only the configured
direction is used for pulse output. The not configured direction is ignored. One
relay is occupied within a binary output board.
Parameter: Command pulse length
Figure 3-1:
ABB AG
3-3
Figure 3-2:
3.3.2
Figure 3-3:
The definition of the bit position for ON and OFF can be changed for the whole
configuration. If changed, this definition is also valid for DPI and RCO commands.
Parameter: Change ON and OFF connection point (RTU Parameters)
ABB AG
3-4
Figure 3-4:
The response indication is a SPI or DPI message. Therefore, only the end
positions (ON/OFF) can stop the command. It is not required that the reported
indication state and the command direction (ON/OFF) do match.
A new command from NCC is accepted only when the command is switched off,
that means after the response delay time and the final termination of the command
with ACTTERM to NCC.
ABB AG
3-5
Process Voltage
Figure 3-5:
ABB AG
3-6
Process Voltage
Figure 3-6:
The coordination of the output board is done by the PDP. The interaction is shown
in Figure 3-7. If a process command is received to switch the selected output
channel, the assigned output board is requested to do the output.
Procedure:
Check if no other output is active etc.
Switch selected output relay
Start output pulse timer
Transmit a positive acknowledge (output active) to the PDP
Switch off output relay when the pulse time has elapsed
Transmit output deactivated to PDP
The PDP monitors the output commands. If it does not receive the acknowledge
information within time, it will stop the output by forcing the output board to stop.
The binary output board acknowledges output active will response the command
with Activation Confirmation to NCC.
ABB AG
3-7
Figure 3-7:
ABB AG
3-8
Figure 3-8:
ABB AG
3-9
Figure 3-9:
ABB AG
3-10
ABB AG
3-11
The coordination between the two output boards is done by the PDP. The
interaction is shown in Figure 3-10. When a process command is received, the
output relay is switched first with a pulse time which is longer than the configured
output pulse duration for that channel. After the output board has acknowledged
that the output relay is switched on, the supervision board is started to check the
output circuit and if positive to do the final output with the configured time for that
channel.
The 23BA22/23 allows checking two different output circuits with different nominal
resistances. But only one channel can be active at the same time (P1 or P2). If the
23BA22/23 receives a request to test and switch a command on P1 or P2 the
following sequence is started:
Check that no other output is active etc.
Select P1 or P2 for checking
Start to measure the resistance in the switched output channel (interposing
relay)
Compare the measured resistance against the parameterized upper and
lower limits
Abort all activities and transmit a negative acknowledge if the resistance is
out of limits
Switch the auxiliary relays from TEST to SWITCH position if the
resistance check is O.K.
Start the output pulse by switching the GO relays which feed the process
voltage to the selected interposing relay
Start output pulse timer
Transmit a positive acknowledge (command running) to PDP
Switch off GO relay when the pulse time elapsed
Switch back to TEST position
Transmit command stopped to PDP
The PDP will then stop the output board by a stop command. The PDP part of the
CPU monitors the output commands. If it does not receive the acknowledge
information within time, it will stop the output by forcing the supervision board to
reset and the output board to stop output.
The assignment between supervision board and the output board and the upper
and lower resistance limits have to be parameterized for each channel on the
command supervision board.
Two command supervision channels CSC (P1/P2) can be defined on each
supervision board. On the 23BA20 board can be selected which command
supervision channel monitors the board. For 1.5 pole connection, two channels can
be selected (relays 1-8 and relays 9-16) .The command supervision is valid for all
SCO and DCO commands on this board.
It must be regarded that channels connected to the same route (R1 / R2) must
have the same supervision channel CSC n.
ABB AG
3-12
3.3.3
ABB AG
Feature
23BA20
23BA40
23BO62
23BO61
560CIG10
1 pole
without
supervision
Yes
Yes
Yes
Yes
Yes
2 pole
without
supervision
Yes
Yes
Yes
1.5 pole
with
supervision
With
23BA22/23
No
With
23BO63
No
Onboard
2 pole
with
supervision
With
23BA22/23
No
With
23BO63
No
Onboard
Yes
Yes
3-13
3.4
3.4.1
Functionality
Regulation step command output (RCO)
can be wired for one and two pole switching, and allows one and two step
commands (select before operate sequence)
cannot be wired with command supervision
cannot be terminated by a response indication
The object command pulse length is described by the parameter PULSE LENGTH.
The pulse duration for HIGHER and LOWER is the same.
Parameter: Command pulse length
Option
RCO
SEL
Start
RCO
ACT
Retrigger Retrigger
RCO
RCO
ACT
ACT
Retrigger Stop
RCO
RCO
DEACT
ACT
Pulse duration
without stop
Nominal
pulse duration
Figure 3-11:
The definition of the bit position for HIGHER and LOWER can be changed for the
whole configuration. If changed, this definition is also valid for DPI and DCO
commands.
Parameter:
ABB AG
(RTU Parameters)
3-14
3.4.2
ABB AG
Feature
23BA20
23BA40
23BO62
23BO61
560CIG10
Regulation
command
Yes
Yes
Yes
Yes
Yes
3-15
3.5
3.5.1
100 %
0%
20 mA (100%)
4 mA (0%)
Output Value
Figure 3-12:
The configuration parameter Output signal type specifies if the output is a bipolar, a
unipolar or a live zero signal. The configuration parameter Output signal range
specifies the hardware setting of the 23AA20 board.
Parameter: Output signal range
Output signal type
ABB AG
3-16
Scaling
The PDP converts the value of a normalized ASO. The configuration parameter
Conversion factor specifies the percentage of the maximum output signal that is
defined as 100 % of the normalized value.
Parameter: Conversion factor
-20
-100
-15
-75
-10
-50
-5
-25
5
25
10
50
15
75
20 [e.g. mA]
100 [% ]
Output signal
- 100 %
Figure 3-13:
ABB AG
3-17
The PDP coordinates the output of the analogue output value and the strobe pulse.
There is a delay of approx. 50 ms between the output of the analogue value and
the strobe. This delay allows the value to become stable. The analogue output
stays stable until a new ASO is received.
Figure 3-14:
ABB AG
3-18
3.5.2
16 15 14 13 12 11 10 9
Conversion by PDP
(a)
(b)
(c)
(d)
(e)
0..9
(f)
0..7
0..9
0..9
0..9
0..9
0..9
0..9
0..9
0..9
0..7
0..9
(g)
S
(h)
(i)
(j)
(k)
S
(l)
Figure 3-15:
ABB AG
3-19
Maximum value
The PDP coordinates the output of the digital output value and the strobe pulse.
There is a delay of approx. 50 ms between the output of the digital value and the
strobe. This delay allows the value to become stable. The digital outputs are
switched off at the end.
Figure 3-16:
ABB AG
3-20
3.5.3
Feature
23AA21
23AO60
Without
Strobe
Yes
Yes
With
Strobe
With
23BA20
Yes
onboard
ABB AG
Feature
23BA20
23BO62
23BO61
560CIG10
8 Bit
Yes
Yes
Yes
Yes
16 Bit
Yes
Yes
Yes
No
Without
Strobe
Yes
Yes
Yes
Yes
With
Strobe
Yes
No
No
No
3-21
3.6
Bit-String Output
3.6.1
Functionality
3.6.2
Error Handling
Output Board Failure
An output board can be set out of service if:
the board has never been in service
(configuration error)
the board failed during normal operation
(hardware failure, I/O bus failure etc.)
the board has been removed or rack power was lost.
If an output board is set out of service, the configured output channels are set
faulty due to board failure in the data base. The RTU560 indicates that to the NCC
with diagnostic message.
An output board can be set in service again during runtime if:
the board is replaced
power is turned on again in the rack
the I/O bus is O.K.
If this happens, the following sequence recovers the output channels:
normalize the output board
load all parameters for configured channels by the PDP
clear faulty state in data base and update NCC
ABB AG
3-22
3.6.3
ABB AG
Feature
23BA20
23BO61/62
560CIG10
1, 2, 8 Bit
Yes
Yes
Yes
16 Bit
Yes
Yes
No
3-23
Note:
We reserve the right to make technical changes or modify the contents of
this document without prior notice With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does not accept any
responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third parties
or utilization of its contents - in whole or in parts is forbidden without prior
written consent of ABB AG.
Copyright 2011 ABB
All rights reserved
ABB AG
3-24