You are on page 1of 7

3

069

RDH10

Room temperature controller


with large LCD
Non-programmable, for heating or cooling systems

Large LCD
Battery-powered: 2 x alkaline batteries type AA, 1.5 V

Use
The RDH10 is used to control the room temperature in heating or cooling systems.
Typical applications:
Homes
Residential buildings
Schools
Offices
The controller is used together with the following equipment:

CE1N3069en
14.12.2007

Thermal valves or zone valves


Combi boilers
Gas or oil burners
Fans
Pumps

Building Technologies

Functions
.
.
.

3031D01

The controller acquires the room temperature with its integrated sensor.
Q14
L1

Function diagram
ON

OFF

T[C]

Room temperature

SD

Switching differential

Room temperature setpoint

L1

Output signal for heating

Room temperature

Y2

3011D02

SD

L1

ON

SD

Switching differential

Room temperature setpoint

L1

Output signal for cooling

OFF

T[C]
SD

Temperature sensor

The RDH10 provides control of the room temperature only.

Display

The digital display shows the actual room temperature and the Comfort temperature
setpoint. When the heating output is active, the triangle symbol appears.

Backup

When taking out the batteries, the setpoints and the information required for operating
mode changeover are retained for maximum 2 minutes.

Ordering
When ordering, please give name and product number: Room temperature controller
RDH10.
Valves and actuators are to be ordered as separate items.
Equipment combinations
Type of unit
Electromotoric actuator
Electrothermal actuator (for radiator valves)
Electrothermal actuator (for small valves 2.5 mm)
2- or 3-port zone valve
Electromotoric actuator for zone valves V..146..
Electric actuator
Air damper actuator
Air damper actuator
Air damper actuator

Product number
SFA21...
STA21...
STP21...
MXI/MVI421
SUA21
SUA11/22
GDB
GSD/GQD
GXD

Data sheet
4863
4877
4878
4867
4830
4832
4624
4606
4622

2/7
Siemens
Building Technologies

Room temperature controllers

CE1N3069en
14.12.2007

Mechanical design
The unit consists of 3 parts:
Plastic housing with digital display accommodating the electronics, operating elements and built-in room temperature sensor
Baseplate (mounting base)

Removable battery compartment

The housing engages in the baseplate and snaps on. The baseplate carries the screw
terminals. There is a reset button on the rear of the unit.

Key

1
2
3
4
5
6

Display of the room temperature in C


Indicates a request for heat
Temperature setting knob
Battery compartment
Comfort temperature setpoint
Indicates low battery power; replace batteries

3/7
Siemens
Building Technologies

Room temperature controllers

CE1N3069en
14.12.2007

Notes
Mount the room temperature controller in a location where the air temperature can be
acquired as accurately as possible without getting adversely affected by direct solar
radiation or other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.

The unit can be fitted to a recessed conduit box.

Mounting, installation
and commissioning

When mounting the unit, fix the baseplate first. Then, make the electrical connections
and fit and secure the controller (also refer to the separate mounting instructions).
Mount the controller on a flat wall and in compliance with local regulations.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.

Maintenance

The controller is maintenance-free.

Change of batteries

If the battery symbol


replaced.

Reset

To reset, press the reset button on the rear of the unit. All individual settings are then
reset to their default values.

appears, the batteries are almost exhausted and must be

4/7
Siemens
Building Technologies

Room temperature controllers

CE1N3069en
14.12.2007

Technical data
Power supply
Sensor inputs
Outputs
Switching outputs
(LX, L1, L2)

Operational data

Electrical connections

Environmental conditions

Standards

Operating voltage
Battery life
Internal:
Thermistor
Relay contacts
Switching voltage
Switching current
At AC 250 V
Contact life at AC 250 V
At 5 A res.
Insulating strength
Between relay contacts and coil
Between relay contacts (same pole)
Switching differential SD
Setpoint setting range
Factory setting comfort setpoint
Resolution of settings and displays
Temperature setpoint
Display of actual temperature value
Connection terminals (via baseplate)
For solid wires
For stranded wires
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
conformity to
EMC directive
Low-voltage directive
C-tick conformity to
Test standards and requirements
Product safety
Automatic electrical controls for
household and similar use
Information technology equipmentSafety-General Requirements
Generic standards-Compliance to
lower power electronic apparatus
Safety class
Pollution degree
Degree of protection of housing
Weight (incl. packaging)
RDH10
Color of housing front
Housing material

DC 3 V (2 x 1.5 V AA alkaline batteries)


>1 year (with AA alkaline batteries)
10 k 1% at 25 C
Max. AC 250 V
Min. AC 24 V
Max. 5 A res., 2 A ind.
Min. 200 mA
Guide value:
1 x 105 cycles
AC 3,750 V
AC 1,000 V
1K
530 C
20 C
0.5 C
0.5 C
Screw terminals
2 x 1.5 mm2
1 x 2.5 mm2 (min. 0.5 mm2)
IEC 721-3-3
Class 3K5
0+40 C
<90% r.h.
IEC 721-3-2
Class 2K3
-25+60 C
<95% r.h.
Class 2M2
IEC 721-3-1
Class 1K3
-10+60 C
<90% r.h.
2004/108/EC
2006/95/EC

N474

General

EN 61000-6-3, AS/NZS 4251.1: 1999


EN 60730-1 and
EN 60730-2-9
EN 60950-1
EN 50371-1
II as per EN 60730
2
IP20
340 g
Signal-white RAL 9003
ABS (LCD lens: PC)

5/7
Siemens
Building Technologies

Room temperature controllers

CE1N3069en
14.12.2007

Connection diagram
3069A01

Lx

Lx, Nx

Live, neutral conductor, AC

24...250 V
Lx, L2

N.C. contact (for N.O. valves)

Lx, L1

N.O. contact (for N.C. valves)

Lx
3V
L2

L1

RDH10

max. 5(2) A

Nx

Application examples

N1
T

T
T

N1

F1
F2

F2

F1

Y2

Y2

M1
2222S01

2222S02

M1

N1

Room temperature controller with direct


control of a gas-fired floor-standing boiler
2264S01

Room temperature controller with direct


control of a gas-fired wall-hung boiler
T

Y1

E1
2222S03

M1
T

N1

Room temperature controller with direct


control of a heating circuit pump (precontrol
by manual mixing valve)

Room temperature controller with direct


control of cooling equipment

F1

Thermal reset limit thermostat

E1

Cooling equipment

F2

Safety limit thermostat

N1

Room temperature controller RDH10

M1

Circulating pump

Y1

3-port valve with manual adjustment

Y2

Magnetic valve

6/7
Siemens
Building Technologies

Room temperature controllers

CE1N3069en
14.12.2007

Dimensions
Room temperature
controller

Baseplate

2007 Siemens Switzerland Ltd

Siemens
Building Technologies

Subject to change
Room temperature controllers

7/7
CE1N3069en
14.12.2007

You might also like