Power Factor

and
Reactive Power

Ward Jewell
Wichita State University
Power Systems Engineering Research Center
(pserc.org)

PSERC

Energy to lift a 5 pound weight


2 feet high:
2 ft x 5 lb = 10 ft-lb
= 0.0000038 kWh
= 0.0033 “calories”
(which are actually kcal)

Value at 10.3 cents per kWh:


(average residential US price, summer 2006)

0.000039 cents
PSERC

Page 1
As dragline bucket lowers, motors
generate, return electricity to source

PSERC

Induction motor with no load


800
735.249

600
energy
to motor
power (watts)

400

200
p ( t)
0
0 energy
200

400
from
− 465.196
600
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018
motor
0 t 0.017

time (seconds)

PSERC

Page 2
Induction motor
800
735.249

600
power (watts)

400
average
p ( t)
200
power:
0

200
130 watts
400

− 465.196
600
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018

0 t 0.017

time (seconds)

PSERC

Incandescent lights
350
306.8

300
power (watts)

250

200
average
p ( t)
150 power:
100
150 watts
50

0
0
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0
0 t 0.017
time (seconds)

PSERC

Page 3
Incandescent Lights

PSERC

Induction motor with no load

PSERC

Page 4
Lights and Motor

Power Current Voltage

Incandescent 0.15 kW 1.3 A 118.0 V


lights

Induction 0.13 kW 5.1 A 117.7 V


motor with
no load

PSERC

Why do the Volts and Amps matter?

PSERC

Page 5
Motors and Resistance Heat:
100 MW

Customer voltage Power lost in wires

Resistance Heat 12.3 kV 1.0 MW


Motors 11.7 kV 2.3 MW

PSERC

Incandescent Lights

PSERC

Page 6
Incandescent lights power:

Power = 118 V x 1.3 A


= 153 W
= 0.15 kW
= power measured by meter

PSERC

Incandescent Lights

PSERC

Page 7
Induction motor with no load

PSERC

Induction motor power:

117.7 V x 5.1 A
= 600 W?
= 0.6 kW?
NOT the power measured by meter

PSERC

Page 8
Induction motor with no load

PSERC

Define some new values:

Apparent power = volts x amps


For the motor:
117.7 V x 5.1 A
= 600 VA
= 0.6 kVA

VA: volt-ampere
PSERC

Page 9
Define some new values:

Power Factor =
Average (“real”) (kW) power
Apparent (kVA) power
For the motor:
pf = 0.13 kW / 0.60 kVA
pf = 0.22

PSERC

Define some new values:


reactive power = 0.58 kVAR
kVA

the power triangle


for the motor:
0.60=

reactive power =
ower

VI2 – average power2


rent p

2 2
( 0.60kVA) − ( 0.13kW) = 0.59 kVAR
Appa

0.58 kVAR
VAR: volt-ampere reactive
real power = 0.13 kW
PSERC

Page 10
Induction motor with no load

PSERC

Lights and Motor


Real Reactive Apparent Power Current Voltage
Power power power factor

Incan- 0.15 0 kVAR 0.15 kVA 1.0 1.3 A 118.0 V


descent kW
lights
Induction 0.13 0.58 0.60 kVA 0.22 5.1 A 117.7 V
motor with kW kVAR
no load

Note: the motor’s reactive power will stay near its


no-load value of 0.58 kVAR as its load and real
power (and thus apparent power and power
factor) vary from no load to full load.

PSERC

Page 11
Power factor and reactive power
are indicators of

„ power losses in wires


„ voltage drop between supply and load

PSERC

Typical Power Factors


Induction motor 0.7-0.8

Resistance heat 1.0

Incandescent lights 1.0

Fluorescent lights 0.6-1.0

Battery Chargers 0.6-1.0

Computers 0.5-1.0

Variable Speed Motor Drives 0.5-1.0

PSERC

Page 12
Power factor:
lagging or leading?

Most loads with lower power factor


are inductive.
Current lags voltage.
Power factor is “lagging.”

PSERC

Induction motor with no load

voltage current

3.6 ms

Current lags voltage by about 3.6 milliseconds


PSERC

Page 13
Another way to calculate power factor

16.7 ms

3.6 ms

One 60 Hz cycle = 1/60 seconds = 16.7 ms


PSERC

Another way to calculate power factor:


“displacement” power factor

(3.6 ms / 16.7 ms) x 360 degrees = 77 degrees


current lags voltage by 77 degrees
cosine (77 degrees) = 0.22
power factor is 0.22 lagging

pf = cos θ
θ = angle between voltage and current

PSERC

Page 14
Incandescent lights

Current and voltage are “in phase.”


PSERC

Incandescent lights:
displacement power factor:
angle between voltage and current
= 0 degrees
pf = cos(0 degrees) = 1.0

true power factor:


pf = 0.15 kW / 0.15 kVA
pf = 1.0
PSERC

Page 15
If voltage and current are sinusoidal
displacement pf (DPF) = true pf (PF)

motor lights

PSERC

Correcting (increasing)
power factor

PSERC

Page 16
Capacitors to improve power factor:
capacitors release energy
when inductors consume
1.2
1

Capacitor 0.5

current iL( t)
0
ic ( t)

Inductor 0.5

current 1
− 1.2
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018

0 t 0.017

PSERC

Induction motor with


power factor correction capacitor

PSERC

Page 17
Induction motor with
power factor correction capacitor

Real Reactive Apparent Power Current Voltage


power power power factor
Induction 0.13 0.58 0.60 0.22 5.1 A 117.7
motor kW kVAR kVA V
Induction 0.13 0.11 0.18 0.96 1.5 A 118.4
motor with kW kVAR kVA V
capacitors

PSERC

Wire losses:
motors with capacitors
Customer voltage Power lost in wires

Motors 11.7 kV 2.3 MW

Motors with power 12.3 kV 1.0 MW


factor correction
capacitor

PSERC

Page 18
Incandescent lights with
power factor correction capacitor

PSERC

Incandescent lights with


power factor correction capacitor

Real Reactive Apparent Power Current Voltage


power power power factor
Incan- 0.15 0 kVAR 0.15 kVA 1.0 1.3 A 118.0 V
descent kW
lights
Lights with 0.15 0.64 0.66 kVA 0.23 5.5 A 119.9 V
capacitors kW kVAR leading

PSERC

Page 19
Wire losses:
lights with capacitors

Customer voltage Power lost in wires

Resistance heat 12.3 kV 1.0 MW


Resistance heat 13.0 kV 2.0 MW
with power factor
correction
capacitors

PSERC

Leading power factor


Current leads voltage in a capacitor.
Too much capacitance causes low leading
power factor.
(just as bad as low lagging power factor)
Leading power factor causes high voltage
and increased wire losses.
Use the correct amount of capacitance.
(more is not better)
Switch capacitors off when motors are off
(just put capacitor on same switch as motor)
PSERC

Page 20
If voltage and current are sinusoidal
displacement pf = true pf

motor lights

PSERC

If waveform is not sinusoidal:


PC voltage and current

PSERC

Page 21
If waveform is not sinusoidal:
PC voltage and current

PSERC

Harmonic distortion

PSERC

Page 22
Low power factor caused by
harmonic distortion cannot be
corrected by capacitors

Harmonic currents are not accompanied by


harmonic voltage, so average (real) power
in harmonics is almost zero.
pf = average power / apparent power
decreases

PSERC

Common harmonic loads


„ computers
„ motor drives
„ battery chargers
„ rectifiers
„ induction heaters
„ arc furnaces

To correct low power factor caused by


distorted current waveforms, the
harmonic currents must be filtered.

PSERC

Page 23
Capacitors can make
harmonic distortion worse:
Lights with power factor correction capacitor

This is rare, but should be considered


in the presence of harmonic loads
PSERC

Summary
„ Induction motors and other inductive equipment load the electric
power system differently than incandescent lights and resistive
heaters
„ Power Factor and Reactive Power are indicators of power lost in
wires and reduced customer voltage
„ Low displacement power factor caused by induction motors (and
other inductive loads) can be corrected with power factor
correction capacitors
„ Power factor correction capacitors must be sized properly
„ Power factor correction capacitors cost much less than utility
power factor charges and will eliminate those charges
„ Power factor correction capacitors should be disconnected when
motors are disconnected
„ Low harmonic power factor is corrected with filters, not capacitors.
Capacitors may make it worse.

PSERC

Page 24
Ward Jewell
316.978.6340
ward.jewell@wichita.edu
pserc.org
(slides are posted under “presentations”)

PSERC