Monitor de Transformador

SEL-2414
Apresentao Tcnica

Copyright SEL 2013

Soluo Integrada em um nico


Equipamento
Regulao de
Tenso
(ANSI 90)
Monitoramento
Trmico e de
Faltas
Passantes

Controle e
Indicao de
Tap

Controle de
Paralelismo

Controle de
Ventilao
Forada

Copyright SEL 2013

SEL-2414 Substitui Outros


Dispositivos
Indicador de temperatura do leo
Indicador de temperatura do

enrolamento
Rels auxiliares para comandos e

intertravamentos
Painis com luzes e chaves

de indicao
Concentrador de sinais digitais e

analgicos
Copyright SEL 2013

Painel Frontal- SEL-2414

Display

Pushbuttons

Labels configurveis
Leds programveis
Copyright SEL 2013

Monitoramento e Controle Completo


de Transformadores
Sincronizao via IRIG-B

Modbus,
DNP3, IEC
61850

10 medies de temperatura via RTD ou termopares


12 RTD

Mdulo de Temperatura

SEL-2600

Link FO

Alarmes

DI
AO
AI

Sensores
Digitais

DI

DO

Sensores
Analgicos
Correntes

Tenses

Status

Controle

Copyright SEL 2013

Condies de Operaes Extremas

Copyright SEL 2013

Dados Analgicos Remotos


Protocolos: DNP, MODBUS E IEC61850
SCADA
S EL

Escreve em variveis
analgicas remotas
usando DNP, Modbus,
IEC 61850, Fast
Message

SEL-3354

S EL

SEL-451-4

SEL-2414

S EL

TCs

S EL

SEL-2600

Estgio da
Ventilao

Executa a
modelagem
trmica com
valores analgicos
remotos

Entrada de
Temperaturas
Copyright SEL 2013

SEL-2414

MONITOR TRMICO
Copyright SEL 2013

ETHERM:=1
Tanque nico - Enrolamento Trifsico

Temperatura Ambiente
Temperatura do leo

SEL-2414

3
Ia, Ib, Ic
Va, Vb, Vc
3

Copyright SEL 2013

ETHERM:=3
Banco de Transformador
SEL-2414

1
1

Ia, Ib, Ic

1
1

Va, Vb, Vc

1
1
Temp. Ambiente
Temp. leo #1
Temp. leo #2
Temp. leo #3

Copyright SEL 2013

ETHERM:= W
Tanque nico e 3 Enrolamentos
3

SEL-2414

Va, Vb, Vc
IW1, IW2, IW3
1

Temperatura Ambiente
Temperatura do leo
Copyright SEL 2013

Monitoramento de Transformador
(IEEE C57.91: 1995, NBR 5416/1997)
Monitoramento trmico
Condies Trmicas em Tempo Real

Gerenciamento do Tempo de Vida


Histrico de Dados para Criao de Curvas

Monitoramento de Faltas Passantes


Indicador das Condies Fsicas do Trafo
Deteriorao da Isolao e dos Condutores
Reduo da Resistncia aos Esforos Mecnicos
Copyright SEL 2013

Modelagem Trmica
Carga do
Transformador
Temperatura
do topo do
leo
Temperatura
ambiente
Estgio da
ventilao
forada

TOILM- Temperatura do
leo medido
TOILC- Temperatura do
leo calculado
HS - Temperatura do
enrolamento

FAA- Fator de acelarao


envelhecimento da
Isolao
RLOL - Perda de vida
diria (%)
TLOL RLOL Acumulado
TLL Tempo de vida
Estimado
Copyright SEL 2013

Monitoramento
NBR 5416/1997
FAA- Fator de acelarao do envelhecimento
da Isolao
FAA= 0.5 - Trafo perdeu metade da vida til

esperada para 1 dia


FAA= 1- Trafo perdeu a vida til esperada para 1 dia
FAA= 2- Trafo perdeu o dobro da vida til esperada

para 1 dia

Vida til do Transformador = 65000 horas

RLOL- Perda de Vida Diria (24 horas) =


0.03692 [%]
Copyright SEL 2013

Relatrio Estado Trmico Atual


Atualizado a cada 1 minuto

Copyright SEL 2013

Relatrio do Estado Trmico por Hora


Armazena ltimas 72 Horas

Copyright SEL 2013

Relatrio do Estado Trmico por Dia


Armazena ltimos 90 dias

Copyright SEL 2013

Visualize Relatrios Trmicos


Transformer Loading

Per Unit

1.5

1.0

0.5

10

15

20

25

Degrees

150
Hot Spot
100

Conductor
Ambient

50

Oil
0

10

15

20

25

Hours

Exportao para Texto em Formato Excel


Copyright SEL 2013

Lgicas Implementadas
Ligar / Desligar Ventilao Forada
Temperatura do Enrolamento
Temperatura do leo

Limites Trmicos (ALARMES) com Tempo

de Retardo
Temperatura do Enrolamento
Temperatura do leo

Falha de RTD
Copyright SEL 2013

Lgicas Adicionais
Monitoramento do
Sistema de Ventilao
Exerccio da

Ventilao
Eficincia da

Ventilao

Copyright SEL 2013

Check da Eficincia da Ventilao

CSE TEMP. LEO MEDIDA > TEMP. LEO CALCULADA

Ventilao Comprometida

CSCM TEMP. LEO MEDIDA < TEMP. LEO CALCULADA

Erros do RTD ou Constantes Trmicas

TnOILM

_
+

T1OILC
T1CSEP
(setting)

(1) +

CSCM_1

_
+

CSE_1

MTOn_OK
Copyright SEL 2013

Monitoramento de Faltas Passantes


Indicao do Estresse Mecnico e
Trmico Causados pelas Icc

Source

HV
LV
Transformer
Breaker
Breaker

Fault

Copyright SEL 2013

Relatrio de Faltas Passantes


Total de Eventos e Efeito por Fase
=>TFE <Enter>
SEL-2414
DEVICE

Date: 03/31/2009

Winding E
Total Number of Transformer Through Faults:
Total Number of A Phase Through Faults:
Total Number of B Phase Through Faults:
Total Number of C Phase Through Faults:

Time: 10:00:00

112
6
112
5

Total Accumulated Percentage of Through-Fault Capability:


A Phase
B Phase
17.54
999.99+

C Phase
17.48

Through-Fault Alarm:

Last Reset: 03/28/2009 05:03:15


..

Copyright SEL 2013

Relatrio de Faltas Passantes


Ultimos 20 eventos com Data e Hora
=>TFE <Enter>

#
Date
1
03/31/2009
2
03/28/2009
3
03/28/2009
4
03/28/2009
5
03/28/2009
6
03/28/2009
7
03/28/2009
8
03/28/2009
9
03/28/2009
10 03/28/2009
11 03/28/2009
12 03/28/2009
13 03/28/2009
14 03/28/2009
..

Time
07:57:21.638
09:52:13.260
09:52:02.255
09:51:51.253
09:51:40.248
09:51:29.243
09:51:18.241
09:51:07.236
09:50:56.231
09:50:45.225
09:50:34.220
09:50:23.215
09:50:12.210
09:50:01.204

Duration IA
IB
IC
(seconds) (Max Primary kA)
0.067
4.82 4.72 4.31
10.108
0.00 3.78 0.00
10.854
0.00 3.78 0.00
10.913
0.00 3.78 0.00
10.883
0.00 3.79 0.00
10.862
0.00 3.78 0.00
10.862
0.00 3.78 0.00
11.042
0.00 3.78 0.00
10.858
0.00 3.77 0.00
10.875
0.00 3.78 0.00
10.858
0.00 3.78 0.00
10.854
0.00 3.77 0.00
10.913
0.00 3.78 0.00
10.892
0.00 3.78 0.00

A
B
C
Alarm
(Increment %)
16.62 17.74 16.61 B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
0.00 99.99 0.00
B
Copyright SEL 2013

Indicadores para Manuteno


10,000

Time (seconds)

1,000
Allowable
Limit
100
Accumulated
Value
10

1
1

10
Full Load Current (pu)

Copyright SEL 2013

SEL-2414

REGULAO DE TENSO
Copyright SEL 2013

Regulao de Tenso Atravs do


SEL 2414
Regulao de tenso

Comutador no Primrio ou Secundrio

Indicao do Tape Atual no Display


Controle do Comutador de Tape

Automtico

Manual

Chave Local/Remota

LEDs para indicao do estado de operao

Bloqueios por Nveis de Tenso e Corrente


Copyright SEL 2013

Algoritmo de Regulao de Tenso


Operao / Bloqueio

Copyright SEL 2013

Algoritmo Regulao de Tenso


Primeira Comutao / Comutao
Subsequente

Copyright SEL 2013

Controle de Tap
Lgicas adicionais
Compensao LDC
Nvel de tenso do transformador dever ser
ajustado para suprir essa queda de tenso ao
longo do sistema de transmisso de energia
VC

VT
I

ZL = R+jX

Carga

VL
VL
jIX

VT

VC
IR

VC = VT-VL

Copyright SEL 2013

Regulao de Tenso
Bloqueio por sobrecarga / faltas
externas
Bloqueio de comutao por sobrecorrente

Contatos normais

Contatos danificados
Copyright SEL 2013

Acessrios da Regulao de Tenso


Monitoramento da Posio de TAP

Matriz de Diodo

Coroa Potenciomtrica / transdutor

Copyright SEL 2013

Paralelismo
Controle individual ou paralelo

Protocolo IEC-61850

Discrepncia de TAPE

Mestre/ Comandado

IEC-61850 GOOSE

Copyright SEL 2013

CARGA

SEL-2414

MONITORAMENTO DE EVENTOS
Copyright SEL 2013

Monitoramento de Eventos
Similar aos Rels Digitais SEL
Perfil de carga
Oscilografia
Sequencial de eventos

Copyright SEL 2013

Sequencial de Eventos

Copyright SEL 2013

Oscilografia
Verifique a atuao da proteo

Copyright SEL 2013

SMT
Sistema de Monitoramento
de Transformadores

Copyright SEL 2013

Transformadores
Equipamentos essenciais para o sistema

eltrico de potncia
Maiores ativos em uma SE
Necessidade de monitoramento on-line e

constante

Copyright SEL 2013

Atualmente
Sistemas de monitoramento so utilizados

em grandes transformadores
Equipamentos de monitoramento

instalados no corpo do transformador:


Fornecidos normalmente pelo fabricante do
transformador

Trabalham de maneira isolada da rede de

comunicao de automao da SE
Requerem softwares especficos para a

aplicao

Copyright SEL 2013

SMT
Fornecido e instalado no corpo do

transformador
Cria interface web para usurio, com

controle acesso por senha


Acesso via navegadores de internet

tradicionais: IE, Mozilla, etc;


Integrao de outros sensores, via

protocolos de comunicao tradicionais


DNP3, MODBUS e IEC 61850 GOOSE
Copyright SEL 2013

Instalao

SCADA
SMT

web
sensores
MANUTENO

sensores
SEL-2414

Copyright SEL 2013

Facilidade de Acesso
Cada transformadores recebe um

endereo de rede IP
Exemplo - TR01: 192.168.1.121

Atravs do navegador de internet:


http://192.168.1.121

Acesso aos dados do transformador de

forma online

Copyright SEL 2013

SMT - IHM

Copyright SEL 2013

SMT - IHM

Copyright SEL 2013

SMT - IHM

Copyright SEL 2013

DVIDAS?