You are on page 1of 7

Presentation on theme: "Indicates primary inverter is inop.

Operational
secondary and auxiliary inverters will Maintain power to all fixed
frequency busses." Presentation transcript:

Slide

Slide 2

Indicates primary inverter is inop. Operational secondary and auxiliary inverters will Maintain power to
all fixed frequency busses.

Slide 3

Indicates secondary inverter is inoperative. Operational primary and auxiliary Inverters will maintain
power to all fixed frequency buses.

Slide 4

Indicates auxiliary inverter is inoperative. Operational primary and secondary Inverters will maintain
power to all fixed frequency buses.

Slide 5

Indicates no power to applicable bus. This is due either to a failure of the 26 volt AC Transformer (26
volt AC services lost), or loss of power at the 115 volt AC fixed Frequency bus ( both 115 volt AC and 26
volt AC services lost.)

Slide 6

Illuminates to indicate horn heater elements are unpowered or failed while system is Activated by a
HEAT selection. During test selection light illuminates for 2 Sec. then Goes out to verify system
function.

Slide 7

GCU has isolated faulty bus due to generator malfunction or bus fault. Will also get A TRU fail
light, PISSWATER gone.

Slide 8

Indicates applicable TRU is off-line or failed. Secondary bus on the failed side will be Cross tied to the
remaining TRU output by logic relays. A single TRU is sufficient to Operate all secondary DC services. A
double TRU failure will cause the logic relays to Tie the secondary buses to the main feeder busses.
This allows the 28 volt DC Generators to provide power for secondary DC services.

Slide 9

Illuminated Flight compartment EMER LIGHTS switch selected off while electrical Power is applied to
the airplane. Light extinguishes when EMER LIGHTS switch Is selected to ARM or ON.

Slide 10

Illuminate to indicate related pitot head heater is deenergized, either by OFF


selection Or power failure.

Slide 11

Illuminate to indicate an overheat condition of the associated windsheild, or side Window, or


temperature controller or temp. sensor malfunction. For a windshield Overheat condition, power is
automatically cut off from the heater elements (light Comes on) until the HEAT switch is selected to
WARM UP (light goes out). After Appropriate cooling the switch may be selected to NORM. For a side
window overheat condition, the FLT WDO/HT switch is selected to OFF. The caution light should go out
as window cools off if the caution light remains Illuminated the FLT WDO/HT circuit breaker should be
pulled.

Slide 12

Indicates overheat of applicable TRU. Select TRU off by pulling L TRU or R TRU Circuit breaker located
on variable frequency AC breaker panel.

Slide 13

Indicates applicable hydraulic system fluid has exceeded a temperature of 109 C As sensed at the
reservoir. The caution light will extinguish if fluid cools to 95 c.

Slide 14

Illuminates to indicate overheat (over 88c) in flight compartment supply duct. Temperature trim valves
are driven to maximum flight compartment cooling Position. When temperature drops below 82c,
normal operation resumes and caution Light goes out. Illuminates to indicate overheat (over 88c) in
cabin supply duct. Pack temperature Control valves are driven to maximum cooling position. When
temperature drops below 82c, normal operation resumes and caution light goes out.

Slide 15

Indicates that the electric motor windings driving the applicable standby pump has a Temperature
exceeding 170c. The caution light will extinguish if motor cools to 160c.

Slide 16

Indicates that applicable battery not connected to its main feeder bus. Normal Indication
when battery is selected off.

Slide 17

Illuminates when system pressure falls below 5.5 psi as sensed at


passenger door Supply line.

Slide 18

Illuminates when the air temperature downstream of the pressure regulator and Shutoff valve (PSRV) in
the bleed air supply duct exceeds 290 c. The affected PSRV And high pressure bleed valve close to cut
off hot air supply to the duct. Bleed air Supply for the de-icing system will be unaffected. When duct
temperature drops below 290c the light will extinguish and bleed air operation in the affected nacelle
will be Restored.

Slide 19

Indicates overheat of applicable DC generator. Select generator off until

light Extinguishes.

Slide 20

Indicates overheat of applicable AC generator. Select generator off until


light Extinguishes.

Slide 21

Illuminate to indicate affected engine ECU fuel scheduling is cancelled and engine Is operating on
Manual HMU fuel schedule.

Slide 22

Engine fuel filter


blocked.

Slide 23

Fuel boost pressure to engine inlet inadequete (less than 5.5 psi) / Boos
ejector Pump failed.

Slide 24

Affected system hydraulic pressure has dropped below 2000 psi. Will illuminate with A pump failure,
hydraulic fluid loss, or engine shutdown/failure.

Slide 25

Indicates applicable 28 volt DC generator is off line or shut down by the GCU due to Generator
malfunction or bus fault. Main feeder bus on the failed side will be cross Tied to the remaining
generator output if indicated generator is off line due to Reasons other than bus fault. A double
generator failure will cause the logic relays To tie the main feeder buses to the secondary buses. This
allows the TRUs to Maintain power to the main and essential busses.

Slide 26

Indicates applicable AC variable generator is off line or shut down by the GCU due to Generator
malfunction. Variable frequency buses on the failed side will be cross tied To the remaining generator
output.

Slide 27

Indicates that the isolation valve on the affected hydraulic system has closed. This Valve isolates the
affected hydraulic systems rudder actuator from the remainder of The hydraulic system. This valve will
close when there is a drop in system fluid level Due to fluid loss (approx. 2/3 fluid left). The rudder
actuator on the affected system Will be able to continue to operate using fluid which is circulated in a
closed system Loop.

Slide 28

Fuel tank quantity in collector tank falls below


130 pounds.

Slide 29

Indicates rudder actuator pressures have either not dropped to 900 psi when Airspedd exceeds 140 kts.
IAS or risen to 1500 psi when airspeed drops below 140 Kts. IAS. There is a 200 kt. IAS limitation
associated with whis light. Usually illuminates in conjunction with #1 RUD HYD or #2 RUD HYD caution
lights. Indicates that a rudder actuator has depressurized and the remaining actuator is Receiving full
system pressure (3000 P.S.I.) There is a 200 Kt. IAS limitation associated With this light.

Slide 30

Indicates that one of the inboard or outboard spoiler lift/dump valves is not Positioned correctly. The
affected spoiler system may not extend upon aircraft Touchdown. Indicates no metered extend
pressure to affected spoiler system actuators. Applicable ROLL SPOILER PRESSURE push off light in
front of F/O should be pushed to Deactivate the malfunctioning system.

Slide 31

Indicates that the applicable rudder actuator is depressurized or that pressure has Fallen below 600
P.S.I. There is a 200 Kt. Limitation associated with these lights.

Slide 32

When illuminated this light indicates that the secondary shafting of the flap system is Experiencing
torque loading associated with the extension or retraction of flaps. Indicates possible failure of primary
flap drive shafting. Hydraulic pressure to the flap drive system has fallen below 1500 P.S.I. Possibility of
Flaps being immobilized in their existing position.

Slide 33

Stall transducer or lift computer on affected side has failed or the system is Deenergized. Nose wheel
steering ECU failure/ Nose wheel in free castor mode.

Slide 34

Anti skid system is unserviceable or system is selected off / Lights illuminate Briefly during test. After
retraction indicates gear door sequence valve failure. Landing gear must not be Extended by normal
DN selection. Use alternate handpump when gear extension is Required.

Slide 35

Illuminates with beacon light selected off.


Parking brake set.

Slide 36

Refuel / Defuel selection made on refuel / defuel control panel Master caution light is not activated
when illuminated Fuel transfer not possible. Indicates failure in a w.o.w sensor. PSEU will continue to
provide WOW signals due to circuit and sensor redundancy.

Slide 37

Oil pressure drops below 40 P.S.I. shutdown engine. Fire in baggage or cargo compartment / smoke
detector self test. Illuminates concurrent with both alarm and Fault conditions. Cabin altitude exceeds
10,000 ft.

Slide 38

Door opened Temperature of applicable battery has exceeded 65 c battery should be disconnected
From DC electrical system and closely monitored.

You might also like