Over load, Under load, Reverse phase, Phase loss, Locked rotor, Unbalance, E/F protection function
Different functions selectable within one device, e.g Direct starter, Reversing starter, Y-D starter, Reactor / Inverter starter
Current indication
R.S.T current
40.26
Malfunction
Prevention cover
Motor condition
Motor start/Stop
Trip reset
Operating mode
Trip analysis
Setting group indication
Main unit
MCT
Motor Protection
Operating condition
Over current
Time
Inverse
1~60S
Definite time
1~60S
Phase loss
Within 1.5S
Unbalance
Within 5S
Reversal phase
Within 0.1s
Under current
Within 3s
Holding
Stall
Within 5s
Lock
Within 0.5s
Earth fault
0.05s~1.0s
Pre-alarm
Indications
Self supervision
Description
Setting Value
O-L
U-C
P-F
P-U
Loc
StL
r-P
g-F
T2-F
OrH
1. IMC-III does not indicate current value on the Phase reversal trip.
2. Ground current is indicated mA on the earth fault trip.
Remark
Indication
Description
Err1
Err2
Err3
Err4
EEPROM
After indicating group you want, ENT button goes to the next group.
In the next group, if you push the ENT button, you can find setting contents.
After showing the contents you want, ENT button goes to the appropriate contents.
After indicating group you want, ENT button goes to the next group.
In the next group, if you push the ENT button, you can find setting contents.
After showing the contents you want, ENT button goes to the appropriate contents.
After changing the setting value, if you push the ENT button, setting values are stored.
After indicating group you want, ENT button goes to the next group.
In the next group, if you push the ENT button, you can find setting contents.
After showing the contents you want, ENT button goes to the appropriate contents.
Operation priority ranking ; LOCAL > MCC > Auto, W/L > Remote
1)
2) MCC MCC operation mode (Motor Control Center) You are able to control by IMC-III of MCC panel. When the
MCC LED blinks by handling L/R button, it is possible to control motor by IMC-III.
3) Auto , W/L PLC auto operation mode IMC-III is able to be auto operation and remote control. When the
Auto/Remote, W/L LED blinks by handling L/R button, it is possible to control motor by IMC-III. By operation
priority, it is possible to control in MCC and IMC-III motor operation mode is changed to MCC.
4) Remote Communication operation mode IMC-III has function of remote monitoring control by Data
communication. When the Auto/Remote LED blinks by handling L/R button, it is possible to do a remote control
and monitoring by RS485, RS422. By operation priority, it is possible to control in MCC and IMC-III motor
operation mode is changed to MCC.
contents
Setting value
Basic values
1. CHR
Operating characteristic
(Inverse/Definite time)
Ind/dEF
Inu
2. O-t
Operating time
1~60/1(S)
60
1~200/1(s)
200
(In case of Inu,
do not indicate)
3. d-t
4. r-C
0.5~6/0.1A
5~60/1(A)
5. Ctr
CT ratio setting
Dir/y-d/
Dir
6/60
6. dru
Operating mode
F-r/Ind/Iut
7. d-t
Y operating time
1~120/1(s)
8. ydt
9. s-t
OFF, 1~10/1(s)
OFF
10 .sd
Re-start time
0~300/1(s)
B-Group
Menu
Contents
Setting value
1.Loc
Lock protection
OFF, 200~700/100(%)
Basic values
OFF
2. StL
Stall protection
OFF, 150,200,300
OFF
3. P-F
OFF/ON
ON
4.P-U
Unbalance Protection
OFF, 30,40,50%
OFF
5.r-P
OFF/ON
OFF
6.U-C
OFF, 30 ~ 70 / 5(%)
OFF
OFF
7.g-F
OFF/ON
8.g-C
0.1,0.2,0.5,1.0,1.5,2.0,2.5(A)
0.1
9.g-t
0.05
10.gd
OFF/ON
OFF
Setting value
Basic values
1. When the INVERTER operates, turn off the earth fault function
2. Phase reversal protection operates only in a starting time.
C-Group
Menu
Contents
1. I-O
Input/Output information
4 SEG indication
2. trt
3. r-t
Operating time
4. srt
OFF, 10~8760/10(H)
5.Cch
Contactor check
OFF/ON
ON
nor
6.n-F
7.tOn
ON DELAY TIMER
0~300/1(s)
8.tOF
0~300/1(s)
9.t-c
Compare timer
0~300/1(s)
10.Ar
Auto - return
OFF, 1~20/1(M)
11.Ad
Communication address
1~255
OFF
1
12.bS
Communication address
96, 192,384
96
13.SP
SWAP
ON/OFF
ON
Sequence Function
Contents
Direct operation
Y-D operation
Operating type
Instantaneous
under voltage
compensation
User contact
point Mode
1~120sec/1sec
Forward/Reverse operation
Reactor
Remarks
Reactor Time
1~120S/1S
Inverter
Compensation time
Bypass circuit
0~300S setting
Normal
Normal mode
Time Delay
ON Delay
0~300S/1S
OFF Delay
ON Delay
Flow Switch
Comparing
time > ON
Delay timer
0~300S/1S
OFF Delay
Comparing timer
Remote control
Local
MCC
Auto
W/L
Water Level
Remote
Modbus/RS-485 communication
Terminal composition
Terminal No. Input/Output
Function
External ON S/W
INPUT
10
11
External trip2
12
13
14
16
17
18
19
20
21
ON DELAY TIMER
22
23
24
25
ZCT input
26
ZCT input
Multiple protection: Over load / Phase failure / Stall /Asymmetry / Phase reverse/ Earth Fault.
n
n
n
Technical Specification
Model No.
Wiring
Panel mount
Operation time
characteristics
Protection
CSMPM06-S/SI/SZ
CSMPM60-S/SI/SZ
Screw type (S)/Tunnel (T)
Unit or Extension Note1)
Select either reverse time characteristics or definite time
Over current
Phase failure
Reverse phase
Asymmetry
Stall
Lock
Under current
Ground fault (for SZ model*)
Short circuit (for SI model*)Note2)
220~240V
380~440V
Delay in starting
Delay in operating
Current
Time
Voltage
Frequency
2-SPST
SPST
Operating power
Note3)
Aux. Contact
OL
AL
Insulation resistance
Surge impulse voltage(IEC1000-4-5)
Fast transient burst(IEC1000-4-4)
Environment
Temperature Operation
Storage
Humidity
Display
7-Segment
Bar-Graph
Mounting type
Note1) In extension type, the Digital Relay is calibrated with combining the display port and main body so,
please cautious not to combine the display part and main body with different part No.
Note2) Instantaneous short circuit protection is optional
Note3) Operational voltage of AC 110V and 50Hz is optional
* Exclusive for each model
Phase loss
Within 3 seconds
R phase
Phase unbalance
Within 5 seconds
S phase
Phase reverse
Within 1seconds
Function enable
T phase
Stall
Within 5 seconds
Lock
Under current
Within 3 seconds
Digital display
4.38
Bar graph
Display button
Set button
Test/Reset button
Time knob
FUNC button
Instantaneous current *
Ground fault *
Setting 100~2500 mA
Current knob
* Optional Protection
Multiple Protection
Function
Function
Selection
Note
Default is Off
Default is Off
Alarm function
(With pre-alarm signal)
Default is Off
Stall function
Default is Off
Lock function
Default is Off
CT ratio
Default is 1:1
Phase failure
Default is On
Function Store
7(F)
25(B)
kt
lt +
+
B
A
30
(A)
100(D)
32(G)
114(E)
D
E
Model
Z - CT D30
30
25
108
100
114
32
32
Z - CT D50
50
25
131
100
122
32
36
Z - CT D65
65
26
143
114
133
39
37
Z - CT D80
80
34
174
160
180
40
40
NOTE :
1) Ratio 200mA/100mV.
2) One Z-CT with suitable ID(A) to be ordered with each CSMPM-06/60 SZ model.
100(I)
108
16.5
40
M4 BOLT
32(H)
48.5
32
ZCT 30
You can finish the setting by pressing the SEL key in the Sto mode
To protect the operation under the motor rotating, setting is allowed only in the TEST
mode.
1) First shift to the TEST mode by press the TEST/RESET button and then set
thefunctions by press the FUNC button.
2) Each time you press the FUNC button, the FUNC mode switches from 1.CHA mode
to S to mode. When the mode that you want to change is displayed, push the Sel
button to select the value you want.
After you select the value, press the FUNC button to finish the settings and it displays
the next mode.
3) If no button is pressed in the SEL mode, it remains in that mode.
4) If you select the inverse time characteristics it skips the mode 2 .dEF and go to the
mode 3.rP.
5) 5. ALT is the alert setting mode. It displays the load rate of the current setting value by
the bar LED (60~110%)
- If the current is higher than the setting value, the bar LED is switched on and off and
the AL relay (07-08) make close and open in 1sec interval until the relay is tripped
(Pre- alarm function).
- If the 5. ALT mode is set to OFF, the AL relay make close after the relay is tripped
(Normal open contact).
6) To finish the settings you have to press the SEL button in the Sto mode.
Dip s/w
1
100
200
500
1000
1500
2000
2500
Multiple protection: Over current / Phase failure / Stall /Asymmetry / Phase reverse.
Technical Specification
Model No.
Type
No. Of CT
Protection
Overcurrent
Phase failure
Stall
Asymmetry
Reverse phase
Current setting range (A)
CSMPA22-2S
CSMPA223S/3SR
2CT
l
l
l
3CT
l
l
l
l
l(3SR)
CSMPA40-2S
CSMPA403S/3SR
Screw Type
2CT
3CT
l
l
l
l
l
l
l(3SR)
0.3~1.5
2CT
l
l
l
3CT
l
l
l
l
l(3SR)
16~80
8~40
4.4~22
Operating time characteristics
Time setting
0~30 sec
Inverse time
CSMPA803S/3SR
4~20
1~5
(Sec)
Tolerance
CSMPA80-2S
Reset time
Current
Time
Control
Voltage
Power
Frequency
Aux. Contact
Contact
Rating
Operate
Insulation resistance
Surge endurance (IEC 1000-4-5)
Fast transient burst (IEC 1000-4-4)
Environment
Operation
-25~70oC
Temperature
Storage
-30~80oC
Relative humidity
Trip indicator
Red LED
Dimension (mm) W x H x D)
Mounting type
10
Red/Green LED
Red LED
53 x 68 x87.5
Separate Mount
(Screw or DIN-Rail)
Red/Green LED
Red LED
2Red LEDs
89 x 77.5 x 97.4
Direct /Separate Mount
(Screw or DIN-Rail)
TEST/RESET
Button
RC(A) Knob
TIME Knob
Set the current by considering the rated current of a motor to protect from the
over current.
n
Check if the rated current of a motor is within the current setting range of
relay.
n
Set the RC(A) (Rated current) knob to the maximum value and then start a
motor.
n
Under normal motor operation, rotate the RC knob to the
counterclockwise until the O.L LED turned ON&OFF. The current at this
point in the 100% current rating under real load.
n
At this point, rotate the RC knob to the clockwise until the O.L LED
turned OFF. In general case the setting value is around 110-120% of the
rated current. (Ex.: When the O.L LED flickering at 20A, the setting
current will be 22A (=20x1.1)
When it is tripped, you can check the causes of the fault by seeing the LED on it
and you can troubleshoot the causes in a short time
Condition
Normal
Off
Over
On &
current
Off
Over
On
current
R
On
On
On
Phase
failure
(3CT)
Trip
Operation
The operating time is set on the base of 600% of the rated current in the
characteristic curve.
n
Set the operating time by considering the operating time and start current
according to the types of the load.
(Ex.: If the start current is 600% of the normal operating current and the
starting is 10sec., set the time knob around 11~12sec. with 10~20%
margin)
n
Operating time range is 0~30sec.
n
If the time knob is set to 10sec, the relay is tripped when the start current
(600% of the rated current) is applied for 10sec.
CAUTION : The relay with inverse time characteristics can be tripped to
protect the motor when the motor is started a few times continuously.
When a motor is frequently changing the rotating direction (forward and
reverse), set the operating time longer. For the crane and hoist use, select
the relay with definite time characteristics.
Phase
On &
failure(2CT)
Off
Reverse
On &
phase(3CT) Off
Note
Off
Off
0.4 second
interval
Off
On &
Off
On &
Off
On &
Off
1 Times for
3 second
2 Times for
3 second
3 Times for
3 second
One after
Off
the other
n
n
n
n
n
n
n
Protection
Time setting
11
CSMPA - 60T
O.L LED
TEST/RESET Button
When you press the TEST button again then the lamp turned off and the
relay reset.
Note : In operation, even though you press the TEST/RESET button, the
relay do not trip.
2. Set the operating time (Definite time characteristics)
n D-TIME (Delay time) : 0.2~30sec.
The motor starting current, which flows when the motor is starting, is
generally 600~800% of the rated current and the delay time varies
according to the load condition. It is the time during which the relay do not
operate by over-current during the starting time.
D-Time Knob
O-Time Knob
RC(A) Knob
In case you do not know the delay time, start the motor by setting the Dtime knob to the max. position and after checking the time during which
the starting current become stable, set the D-TIME (In general pump, the
setting time is 3-5 seconds)
Note : The time delay is forced time delay type, therefore if you make a
mistake to select the time, the motor may burn.
n
The operating time is the time during which the relay tripped by the overcurrent. The relay is tripped after the selected operating time.
Set the operation time by the O-TIME knob.
In special case such as for mechanical shock relay, if you set the O-TIME
to the min value, the relay is tripped at once.
Note : Generally set it to 4~6 seconds.
CSMPA - 60TE
O.L. LED
TEST/RESET Button
TM
Phase failure
If a motor does not rotate under phase failure, the high current may flow.
At this time a motor is protected by the over-current protection function.
12
O-Time Knob
RC(A) Knob
10000
10000
100
1000
1000
100
100
10
Cold
30
30
20
10
10
Cold
Cold
Hot
0.1
100
600
1000
100
600
Hot
1000
1
600
100
Hot
1000
10000
Time(sec)
1000
9
100
60
30
20
10
3
1
1
100
1000
100
150
200
300
400
500
600
Current (%)
Technical Specification
Model No.
Operating time characteristic
Current range (A)
Time Setting(s)
Inverse time
Definite time
D-Time
O-Time
Auto returning time (R-T)
Control Power
Voltage
Frequency
Power Consumption
Output Contact (9Nos) Capacity
Construction
Digital contact
Signal contact
Timer contact
Trip contact
Output Contact (9Nos) Operation input
MC condition signal input
External trip
ZCT
Ratings
Specification
Indication
7-segment
LED
Self supervision
Communication
Installation
Wlthdrawable cable
Weight
Dimension
Main unit
MCT
3a
3a
2a
1a
2a
IMC
Inverse/Definite time
0.125~60A (One device)
1~60sec/1sec (Class)
1~200sec/1sec
1~60sec/1sec
1~20min/1min, OFF (Manual returning)
AC 110V or AC 220V (+15%)
50/60Hz
Under 6W
5A/250VAC
Direct, Reversing, Y-D, Reactor, Inverter starter
Local, Auto, W/L condition
ON Delay, OFF Delay
Fault output
Local, Auto, Water level, Flow switch
Monitoring of sequence (LED)
Emergency, Sequence
200mA/0. 1mA
25, 40, 80
3-phase current, Trip analysis, setting indication
Operation, Trip, System fail, Communication, Remote control
Condition
System Fail LED, Error indication
MODBUS/RS-485
Panel inside installation/Door mounting
Basic cable 2m
0.6kg (MCT 0.35kg)
148(W) x 100(H) x 74(D) mm
151(W) x 55(H) x 33(D) m
13
CSMPA-22/40/80 (2S/3S/3SR)
MCCB
MCCB
FUSE
OFF
(RESET)
TR
MC
ON
MC
TRIP
MC
98
MC
A1
1C
96
Relay
95
97
96
98
95
Relay
A2
A1
A2
For additional
operational
power
Relay
CSMPA-22/40/80(2S/3S/3SR)
(For Y-D Wiring)
CSMPA-22 IN 5A (2S/3S/3SR)
With External Current Transformers
T
R
Contactors for
MCM Magnetic
Power use
Contactors for
MCD Magnetic
motor operation use
MCCB
MCCB
19T Timer
FUSE
FUSE
TR
TR
OFF
(RESET)
OFF
(RESET)
relay
ON
MC
MC
ON
MC
TRIP
19X
19T
19X
MCM
MC
Relay
A1
MCD
95
97
96
98
MCM
MCD
MCS
MCS
19T
19X
MCD
Relay
A2
A1
Z
A2
97
96
98
MCS
Note :
14
95
Relay
CSMPM-06/60-S/SE
R
R
MCCB
AC220V
MCCB
FUSE
AC220V
FUSE
TR
MC
Y
110
100
90
80
70
60%
R
S
T
TEST/RESET
Operational
Power
OFF
(RESET)
TR
MC
OFF
(RESET)
MC
ON
MC
TRIP
MC
TRIP
ON
DISPLAY
TM
MC
S
T
TEST/RESET
110
100
90
80
70
60%
110
100
90
80
70
60%
S
T
95
97
MC
DISPLAY
TEST/RESET
A1 A2
DISPLAY
07
A1 A2 95 96 97 98 07 08
TM
98
96
A2
95
97
07
DIGITAL
Relay
96
98
08
A1
AL
DIGITAL
Relay
08
AL
R
R
T
MCCB
MCCB
AC220V
FUSE
AC220V
OFF
(RESET)
TR
FUSE
OFF
(RESET)
TR
MC
X1
MC
MC
X2
MC
MC
110
100
90
80
70
60%
R
S
T
TEST/RESET
AX1
DISPLAY
MC
AX2
TM
RUN
RUN
OL
TRIP
STOP
GF
TRIP
MC
95
97
TEST/RESET
07
MC
110
100
90
80
70
60%
R
S
A1 A2
ON
ON
DISPLAY
A1
A2
95
R
97
STOP
Z2
TM
OL
GR
OL
AX1
GR
A1 A2 95 96 97 98 07 08
DIGITAL
Relay
96
98
08
DIGITAL
Relay
AX2
96
98
Z1
15
CSMPM-S
52
u
78
48.5
20.5
13.4
CSMPM-SZ
A1 A2 95
96
97
98
07
08
26
M4
70
TEST/RESET
109
U/2/T1
8.5
u
110
100
90
80
70
60%
CSMPM-SI
W/6/T3
V/4/T2
DISPLAY
u
TM
u
u
59.4
76
80
84
97
u
u
95
23
M5.0
u
CSMPM-SI
u
u
96
97
07
98
08
108
U/2/T1
CSMPM-SEZ
26
M4
8.5
48.5
A1 A2 95
76
20
20.5
13.4
CSMPM-SE
W/6/T3
70
V/4/T2
07
08
M3
59.4
76
80
76
97
CSMPM-T
95
84
M5.0
98
97
96
95
A2
23
A1
CSMPM-TZ
109
20.5
12
DISPLAY
26
M4
u
TEST/RESET
80
W/6/T3
V/4/T2
08
110
100
90
80
70
60%
07
98
8.5
U/2/T1
R
97
CSMPM-TI
96
A1 A2 95
52
20
76
CSMPM-TE
96
TM
u
A1 A2 95
98
07
08
108
W/6/T3
20.5
26
M4
u
u
12
80
V/4/T2
U/2/T1
97
8.5
CSMPM-TEI
96
CSMPM-TEZ
97
98
07
08
96
52
M3
CSMPM-SE/S
u
56
96
95
A2
A1
TEST/RESET
37.5
20
50
CSMPM-SEI/SI
20.5
110
100
90
80
70
60%
CSMPM-SEZ/SZ
DISPLAY
CSMPM-TE/T
TM
CSMPM-TEZ/TZ
16
CSMPM-TEI/TI
72
M4
u
u
47
2-012
CSMPA-60TA
9.5u
48.7
23.7
CSMPA-60T
63
05
R2.5
52
44
22
50.5
55
69
1u
62.5
5-M3.5
54.2
72
u
u
CSMPA-22-2S
u
u
u
87.5
u
u u
6-M3.5screw
7
u
40
CSMPA-40-2S
4.
5
68
30.5
44.8
51.6
CSMPA-22-3SR
11
53
10.2
CSMPA-22-3S
CSMPA-40-3S
u
15.7 u
27.7 u
8.2
72
44
7.2
3-M4screw
CSMPA-40-3SR
CSMPA-80-2S
u
u
u
53
77.5
23.5
M4 Mounting hole
5.5
11
2-5
31
43
55
600VAC
4-6
22
74
118
141
6.
3
Insulation Voltage
500~600
8-5.5
51
63
75
5VA
8-INSERT M4
6.
3
75
29
22
74
118
14.5
Panel
70
Mounting
12
48
185
173
161
55
4-6
45
Burden
1.0
Class
Specification
17
Particular
80
Technical Specification
6-M4screw
165
153
141
62.5
20.5
100~400
3 - CT
96
u
95
40
CSMPA-80-3SR
97.4
57
6-M6screw
u u
89
20
CSMPA-80-3S
22
26
22
26
22
34
34
17
Range
Control Voltage AC
Remote Operation
110 V/220 V
Communication through
0.125~60A
Models RS-485/RS-422
Product code
Range
Control Voltage AC
Aux. Contact
0.5 - 6 A
110/ 220 V
2a1b
CSMPM60-S
5 - 60 A
110/ 220 V
2a1b
CSMPM06-SI
0.5 - 6 A
110/ 220 V
2a1b
CSMPM60-SI
5 - 60 A
110/ 220 V
2a1b
CSMPM06-SZ
0.5 - 6 A
110/ 220 V
2a/2b/1a1b
CSMPM60-SZ
5 - 60 A
110/ 220 V
2a/2b/1a1b
0.3 - 1.5A
100 ~ 260 V
1a1b
CSMPA22-2S
1-5A
100 ~ 260 V
1a1b
CSMPA22-2S
4.4 - 22 A
100 ~ 260 V
1a1b
CSMPA22-3S
0.3 - 1.5A
100 ~ 260 V
1a1b
CSMPA22-3S
1-5A
100 ~ 260 V
1a1b
CSMPA22-3S
4.4 - 22 A
100 ~ 260 V
1a1b
CSMPA22-3SR
0.3 - 1.5A
100 ~ 260 V
1a1b
CSMPA22-3SR
1-5A
100 ~ 260 V
1a1b
CSMPA22-3SR
4.4 - 22 A
100 ~ 260 V
1a1b
CSMPA40-2S
4 - 20 A
100 ~ 260 V
1a1b
CSMPA40-2S
8 - 40 A
100 ~ 260 V
1a1b
CSMPA40-3S
4 - 20 A
100 ~ 260 V
1a1b
CSMPA40-3S
8 - 40 A
100 ~ 260 V
1a1b
CSMPA40-3SR
4 - 20 A
100 ~ 260 V
1a1b
CSMPA40-3SR
8 - 40 A
100 ~ 260 V
1a1b
CSMPA80-2S
16 - 80 A
100 ~ 260 V
1a1b
CSMPA80-3S
16 - 80 A
100 ~ 260 V
1a1b
CSMPA80-3SR
16 - 80 A
100 ~ 260 V
1a1b
0.5- 6 A
110/220/415 V
1c
CSMPA60-T
5- 60 A
110/220/415 V
1c
CSMPA60-TE
0.5- 6 A
110/220 V
1c
CSMPA60-TE
5- 60 A
110/220 V
1c
NOTE:
1)
All auxiliary contacts are standard supply with relays indicated above except CSMPM-06/60 SZ model.
Select one of the three options (2a/2b/1a1b)for this model.
2)
All above Motor Protection Relay model CSMP06-S/SI/SZ with current range 0.5-6A / 1-5 A &
CSMPA with current range 0.5 - 6 can be used upto 600 A with suitable ratio CTs* having 5A secondary current,class 1 accuracy.