Professional Documents
Culture Documents
378
TRANSACTIONS
and Mho
Principles
Current Polarization
(Ohm Units)
The torque is the product of the current
polarizing flux times the fluxes from the
opposed I and E poles. Hence the equation for the operating point, which determines the pickup characteristic, is
IlKI-E
cos (-)]-0
(1)
Potential Polarization
(Mho Units)
With potential polarization, the torque
is the product of the potential-polarizing
flux times the fluxes from the opposed /
and E poles. Hence the equation for
pickup is
[/cos (-)-]=0
or -K'E*+EI
(2)
cos ( - 0 ) = ().
DIRECTIONAL
\
UNIT
Dividing
cos (-) =0
/STARTING UNIT
_ J_
.
,/IMPEDANCE
^ t
UNIT
(MHO)
"~^ ^
MHO UNIT
REACTANCE
UNIT
We i
^zJ
EL
rm
I
\
/ \
(A)
Figure 1 .
(B)
Tripping characteristics
A . Impedance unit
B. -Reactance unit
C. M h o unit
The relays trip in the shaded area. Crosses
are conditions for which tripping is undesirable
VOLUME
65
(C)
- CONTACTS
Figure 2.
Schematic diagrams
A.
B.
C.
Impedance unit
Ohm unit
M h o unit
(A)
(3)
and Mho
Principles
Figure
3.
Schematic diagram of
induction cylinder unit
TRANSACTIONS
4-pole
379J
-K'(E+IZb)*+(E+IZb)I*x
(4)
-K'(Z+Zb)*+(Z+Z>)
or
z_
cosfo-)
>Zh
(5)
p POLARIZING
<L
RESTRAINING
OPERATING
POLARIZING(L
,P
(B)
Figure 4
A. Characteristic of ohm unit (blinder)
B. Schematic connections of ohm unit
380
TRANSACTIONS
A typical form of the polarized impedance unit is the 4-pole induction cylinder unit, which is illustrated in Figure 3
and has been used for ten years in the
type GCX reactance relay. The front
and back poles are respectively the current operating and potential restraining.
The fluxes from these poles produce
torque on the induction cylinder by reacting with the currents induced in the
cylinder by the flux from the side poles
which have the polarizing windings. Another sinusoidal torque is produced by the
flux from the polarizing poles reacting
with the currents in the cylinder induced
by the operating and restraining poles.
The second torque is equal to the first
and displaced 90 degrees from it in time
so that the total torque is not sinusoidal
but continuous. This is one of the most
valuable features of the induction cylinder
and induction disc units and is an advantage not enjoyed by any other relay units.
The pickup and dropout of induction
cylinder units are practically the same,
and their characteristic circles are very
close to geometrical perfection.
These units are available in three forms:
the current polarized (ohm) unit, the
potential polarized (mho) unit, and the
offset mho unit in which the potential is
biased from the current circuit. In the
following paragraphs, uses of these units
will be discussed.
^ZCOS(^-90) = K
K-
'-- -
-X
(A)
P POLARIZING
(L
RESTRAINING
OPERATING
n>
POLARIZING!
(8)
tr
.. _
Figure 5
A. Characteristic of reactance unit
B. Schematic connections of reactance unit
ELECTRICAL ENGINEERING
43
cos(0-e)
-R
!-X
(A)
POLARIZINGCT
OPERATING
RESTRAINING
J U N E 1946, VOLUME 65
WarringtonOhm
h POLARIZING
0 I 0
(B)
'
Figure 6
A.
B.
POLARIZINGCT
and Mho
Principles
OPERATING
RESTRAINING
c KB
bpdILARIZING
2b
(B)
Figure 7
A . Offset mho characteristic
B. Schematic connections of offset mho unit
381
A.
B.
OFFSET M H O RELAY
382
TRANSACTIONS
_M|
r,
1 I
F
yM2
fU*
TRIP
* RECEIVER RELAY IF USED WITH CARRIER
Figure 9
D-c connections of 3-step distance relay
A*
BACKUP
/-M
ZONE
.1) | .
(A)
>\
IzONE 3(B) 1
KD
TAP
BREAKER
TRIPON
/FAILED
|BACKUP\
TRIPPED
U-KFAULT
B
(G>-
^>
TAP
LINE
(B)
Figure 10. The reversed backup characteristic
|A. The time zones
B. Tap lines saved
Reclosing
By means of auxiliary relays, reclosing
is prevented after a time-delay trip and
after a trip on loss of synchronism. The
first is accomplished by an auxiliary relay
whose coil is energized whenever the
tripping circuit is completed through the
timing unit contacts and whose contacts
open the reclosing circuit; the connections
of this relay are shown in Figure 5 of the
companion paper. 5 The second is accomplished by an offset mho unit in a manner
already explained earlier in this paper
under the heading "Mho Distance Relay.''
OUT-OF-STEP TRIPPING
REACTANCE RELAYS
(A)
o-
C.T
BUS-TIE
REACTOR
-D
TRIP
ICOIL
WV
COIL
TRipr
REACTANCE RELAYS
(B)
Figure 11
A.
B.
VOLUME 65
When synchronism is lost, the impedance measured by a relay will pass through
the line impedance vector from right to
left if the relay is located at the leading or
fast end of the system and from left to
right if at the lagging end. Two blinders
are arranged to operate an auxiliary relay
if the impedance crosses the characteristic
of one of them before the other, in either
direction. This auxiliary relay can be
arranged to operate an alarm, trip a
breaker, or initiate some form of control.
The advantages of this form of out-ofstep relay are:
1. Its operation is not affected by variation in the location of the electrical center
of the system.
2. It will not trip under any fault conditions.
3. It trips instantly after the first half cycle
of system oscillation. Existing relays require the machine to slip several poles before they will operate.
4. Distinction can be made between speeding up and slowing down of the local generation.
A single-phase relay is adequate for
tripping on out-of-step because the regular protective relays will trip during a
fault. If the swing continues after the
fault has been cleared or if the swing was
caused by switching of load or generation
without a fault, only a single-phase outof-step relay is required for tripping because all three phases act similarly.
Carrier Relaying
The application of ohm relays to carrier has been discussed in previous papers.
The use of mho relays for carrier is the
same in function, but the self-contained
directional and power swing blocking features of the mho unit simplify the d-c
circuits very considerably (Figure 9) and
minimize the possibility of sneak circuits.
Mho carrier alone was described in an
earlier paper. When carrier is added to
mho distance relays, it is necessary only
to add two relays containing ground directional and carrier auxiliary elements. The
TRANSACTIONS
383
TRANSACTIONS
CARRIER BLOCKING ,
BY 3 AT A
/
^ M 2 TRIPPING
\UNIT AT A
M2 TRIPPING
UNIT AT B
OM3 AT A
Figure 1 3 .
8,000 kv
115V3
or
50 kv M
LT =a miles
In other words, the relay is applicable to
The presence of arc resistance will reduce the reach of the mho relay. A small
reduction of the instantaneous zone is acceptable, but the intermediate zone always must reach beyond the next bus,
that is, faults within the section must not
trip in zone 3 time, or selectivity between
stations will not be possible.
In Figure 14A, R is the arc resistance,
Z is the impedance of the protected section, is its phase angle ( t a n - 1 X/R), and
K is the fraction of Z by which the second
zone mho unit M 2 reaches beyond the end
of the section. It is assumed that the
mho unit characteristic is given the same
angle as the line.
The circle in Figure 14A is the characteristic of a mho unit used for the second
distance step and is assumed to reach a
short distance beyond the end of the protected section. It is noted that
a2 + b2 = (diameter)2
therefore,
R2+K2Z2-2KZR
2R2-2KZ2
Rs=
cos <f>+R2+Z2+
2
2ZR cos = (+)
\-2RZ(l-K) cos = 0
2 [Vcos2tf>(l -K)*+4K-(1
-K) cos*]
kv
16V3
115 C.T.
1,000 kv
ohms phase-to-neutral
Appendix I
The characteristic of any ohmic relay on
an impedance diagram is a circle. This is
because the torque from any form of electromagnetic drive is proportional to the square
of the flux or to the product of two fluxes,
and the fluxes in turn are proportional to
the currents or potentials. The torque5
of a relay having current and potential
windings must therefore be of the form
XI
(-0)
KP-K'E*+EIcos
Figure 14
A.
B.
ins mh characteristic
Zcosj0-o)
~ +F
Z2
1 ' /"
fl+4KK'
2K'
+\
2K7"
6 1*
+4KK'
\2K
K')~
CHARACTERISTIC
OF RELAY A T A
(2
Draw a perpendicular through the midThis equation is typical of the offset mho point of RS. From the point K where it
characteristic in Figure 7A.
cuts the relay characteristic, draw lines to
R, S, A, and B. RKS is the angle 0S between the generated electromotive forces
at R and 5 at which the relay at RA will
Appendix II. Power Swing
trip. BKA is the angle between the
Check
terminal voltages at A and B at which the
relay at A will trip, and AK is the impedA simple geometrical construction can be ance it sees.
used to determine whether a relay will
The power swing locus is shown as a
operate during a swing condition. This straight line. This implies equal generated
J U N E 1946, VOLUME 65
WarringtonOhm
Conclusions
and Mho
Principles
TRANSACTIONS
385