You are on page 1of 10

Firmware update MD720-3

Description

Firmware update MD720-3

Firmware update MD720-3

Entry-ID 23067682

Index
Index ................................................................................................................ 2

Generic information........................................................................................ 3

Configuration FTP connection ...................................................................... 4

Establish a FTP connection........................................................................... 8

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Page 2/10

Firmware update MD720-3

Firmware update MD720-3

Entry-ID 23067682

Generic information

About this document


This document describes how to handle a new firmware update of the modem SINAUT MD720-3.

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Requirements

PC with a serial (RS232) interface and Windows XP

Serial modem cable (No cross cabel!)

Paper clip

Firmware files

para.ini

*.bin

!cmdfile

The firewall has to be deactivated temporarily.

Attention

Page 3/10

Firmware update MD720-3

Firmware update MD720-3

Entry-ID 23067682

Configuration FTP connection

Configure the standard 19200 modem connection


Table 3-1

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Step

Action

1.

Open Phone and Modem Options by


Start/Settings/Control-Panel

2.

Select register Modems and click to


button Add..

3.

Select checkbox
Click to button next

4.

Select Standard 19200 bps Modem


Click to button next

5.

Select the com port that is used for


the connection between PC and
MD720-3
Click to button next
Click to button finish

Select just added modem


Click to button Properties

6.

Page 4/10

Commentaries

Firmware update MD720-3

Firmware update MD720-3

7.

Entry-ID 23067682

Select register Modem


Change Maximum port speed to
57600
Click to button OK
Click to button OK

Configure the network connection


Table 3-2

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Step

Action

1.

Open Network connections by


Start/Settings/Control_Panel

2.

Click to button next

3.

Select Connect to the Internet


Click to button next

4.

Select Set up my connection manually


Click to next

Page 5/10

Commentaries

Firmware update MD720-3

Firmware update MD720-3

5.

6.

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

7.

Entry-ID 23067682

Select Connect using a dial-up modem


Click to button next

Select the modem configured in the


previous step
Click to button next

Enter a random name


e.g. MD720-3
Click to button next

8.

Enter the phone number #98


Click to button next

9.

Click to button next

10.

Enter following data:

User name: service

Password: service

Confirm password: service


Activate first check box
Deactivate second check box
Click to button next

Page 6/10

Firmware update MD720-3

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Firmware update MD720-3

Entry-ID 23067682

11.

Click to button Finish

12.

With the right mouse button click to


the just created network connection
MD720-3 an select properties
Click to button configure

Select Maximum speed bps 56700


Deactivate all checkboxes
Click to button ok
Click to button ok

13.

Page 7/10

Firmware update MD720-3

Firmware update MD720-3

Entry-ID 23067682

Establish a FTP connection

Connection modem and PC


Table 4-1

Step

Action

1.

Connect MD720-3 and RS232 interface


of the PC by the modem cable

2.

Switch on the power supply of the modem MD720-3

Commentaries

Configure the standard 19200 modem connection


Table 4-2

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Step

Action

1.

Save the following files on your hard


drive:
para.ini
*.bin
!cmdfile

2.

3.

Press the Reset key (SET) on the


modem MD720-3 by the use of a paper clip until the second LED (Q) is lit
Than remove the paper clip again
Wait until all three LED are blinking

Open Network connections by


Start/Settings/Control_Panel
Double click to the previously configured network connection e.g.
MD720-3

Page 8/10

Commentaries

Firmware update MD720-3

Firmware update MD720-3

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

Step

Entry-ID 23067682

Action

4.

Click to button Dial


Wait until the status of this connection show the status connected

5.

Open run box by Start/Run


Enter cmd
Click to button ok

6.

Enter ftp 192.168.0.8 and confirm


with <RETURN>
Enter user service and confirm
with <RETURN>
Enter <password service and confirm with <RETURN>

7.

8.

9.

Enter put and press space bar


Open Explorer and drag the file
para.ini from its location on the
hard disc and drop it behind the
command put and confirm with
<RETURN>
Wait until the prompt icon ftp>
appears again
Enter put and press space bar
Open Explorer and drag the file
*.bin from its location on the hard
disc and drop it behind the command
put and confirm with <RETURN>
Wait until the prompt icon ftp>
appears again.
This may take 5 minutes!
Enter put and press space bar
Open Explorer and drag the file
!cmdfile from its location on the
hard disc and drop it behind the
command put and confirm with
<RETURN>
Wait until he prompt icon ftp>
apears again

Page 9/10

Commentaries

Firmware update MD720-3

Firmware update MD720-3

Step

Action
The firmware update has been finalized
when:
Q LED is static and C LED is
flashing in case MD720-3 has got a
SIM card
or
S LED is blinking and C LED is
flashing in case MD720-3 has got no
SIM card

Copyright Siemens AG 2006 All rights reserved


FirmwareUpdate_MD720-3_en.doc

10.

Entry-ID 23067682

Page 10/10

Commentaries

You might also like