XMT*608 series Intelligent Temperature Controller

Operation Instruction
Survey
Thanks for your selection of our XMT*608 series intelligent temperature controller.
XMT*608 series intelligent temperature controller,is double row 3-LED display, respectively display
temperature measurement value (PV) and temperature set value (SV) under normal mode;When it is time
temperature control, respectively display temperature measurement value (PV) and running time count down
(SV),and also provide kinds of time control method selection;The controller can input kinds of signal which are
used interchangeably,it adopt ON/OFFP=0 PID control,allowing an easy parameter setting and convenient
inputting,is widely used over temperature automatic control systems of machinerychemicalceramicslight
industrialmetallurgypetrifaction and heat treatment and so on.

Main technical Indexes


1 Measurement deviation0.5FS1additional cold end compensating deviation1
2 Input(can be selected)CU50(-50150)PT100-80600K-30999E-30700
J-30900T199400
3 Relay output (passive) contact capacity Relay
AC250V
240VAC
5A(resistance
3A / 30VDC
load) 1A(resistance load)
period 2120s can be adjusted.
4 Time range0999s or 0999mcan be selected
5 Driving solid relay signal outputDriving electric current 15mA no-load voltage12Vperiod is
about 2S.
6 Work power110V242V50HZ

Power consumption3W

7 Work environment050relative humidity85without corrode and strong electric radiation.

Controller panel
1Controller panelfor reference

2Connectionfor reference

Controllers specific connection should be confirm to the cases connection

Meaning of the model code


XMT 6
1

8
4

1: the external dimension


Blank:

1608085

A:

969680

D:

727280

Installation hole 15676


Installation hole 9292
Installation hole 6868

E:

489675

Installation hole 4492

F:

964875

Installation hole 9244

G: 4848110

Installation hole 4444

S:

8016085

Installation hole 76156

B6012090

Installation hole 56116

LStandard DIN35mm guide way installation


C8012035

wall set installation

2: Operation display method6 3-key gentle push-switch settingdouble row 3-LED digital display
PID control.
3:Additional alarm
0 no alarm
1 upper limit alarmupper deviation alarm when it is time temperature control
4Input: 8 input signal can interchange freeno voltage and current input
5Suffix

Blankrelay output

Inner parameter
Series
First

Attention
0

Menu

TTime control function

Gsolid relay output

Sheet 5-1
Name

Setting range

Description

Ex-factory

Temperature

Determined by

Pressfor 3s can modify the appointed

Random

Appointed

value directly Press or for 3s to

modify the appointed value under

Data

common temperature control


1

Timing

0999

Press for 3s can directly modify

setting

appointed value

Upper limit

The contact conversion output when

alarm

exceeding alarm point, and alarm light is

0100

temperature
Second

deviation alarm,

time

0.

alarm
Measurement

when it is

temperature control it makes sense till

deviation

Random

on it used as temperature upper

upper

menu

Random

Increasing or decreasing this data can

-2020

deviation

modify Measurement value.

amendment
4

When P, proportion function, clash


Proportion
band

0 99.9

200

, but too little will add the heating


time

When P=0, the instrument is ON/OFF


control.

Set integral time so as to unchain

Integral time

residual Deflection caused by proportion


control. To increase it, the static

0999

difference will be reduced, but when it is


too high ,thestatic difference will drift
instability.

240

time

0200

Set differential time to avoid


fluctuation of output so as to improve the
steady of control.

Control

2 120S

When it leaves factory, SSR is 2sRelay

Differential

period
8

Main control

30
10

is 10s.
It makes sense when ON/OFF control.

0.150.0

1.0

by drop in
level
9

close setting itself function

Setting itself

turn on setting itself function.

When choose

, it will do setting

itself for one time when the controller is


under this working condition, and then
automatically switch back
10

Lock

050

When
0can modify all
the parameter

11

lock

050

When
0can modify all
the parameter

12

Input

Display

01

Third

CU50

PT100

Random

E J T
0, no decimal point
1 have decimal point

Precision

13

this parameter will be inexistent


when it is time temperature control

System

0 heating control

01

1 cooling control

function
selection
14

Range lower
limit

15

Random

to
to full

Range upper
limit

Starting point

range
0common temperature control
1 start timing when it reaches the

Time function
16

selection

temperature and the alarm relay output

03
(Time control

after reaching the time, the controller


keep on heating

side be
switched on)

2 start timing when it reaches the


temperature and the alarm relay output
after reaching the time, the controller
stop heating

3 regular temperature control no

alarmtime relay function


start timing when the power is on, alarm
relay attracting after reaching the time .
17

Time unit

01

0unit is secondS

selection

1unit is minuteMin

Attention
Inner parameter sheetSheet51,the parameter with mark should be exit
only when it with time control function .Common 608 temperature controller
without this function; The parameter with markhave different definition when it
is under different control mode, details refer to explanation.

Flow chart

Operation
1 Make the controller link with power supply, sensor and control loop , and make the power on, the controller
will start setting itself for 1S.
2 After completing setting itself ,the controller will enter into normal measuring statethe upper row PV

window display measuring value ,the lower row SV window display set value.
3 The first menu
ATime set value modification
Common temperature control mode: Pressorfor 3s to modify set value ,the upper row PV window
display measurement value ,the lower row SV window display set value , press or to modifylong time to
press can accelerate plus or minus. After modificationpress SET to save and exit. If dont press any key, it will
save and exit automatically after 10s.
Time control modePressfor 3s to enter into temperature set value modification state ,the upper row PV
window display parameter attention

the lower row SV window display parameter valuepress or

to modifylong time to press can accelerate plus or minus. After modificationpress SET to save and exit. If dont
press any key, it will save and exit automatically after 10s.
BTime set value modificationwhen it is time &temperature control
Pressfor 3s to enter into time set value modification statethe upper row PV window display parameter
attention

the lower row SV window display parameter value, press or to modifylong time to press

can accelerate plus or minus. After modificationpress SET to save and exit. If dont press any key, it will save and
exit automatically after 10s.
Inner parameter settingdetailed refer to Sheet51
(1) The second menu
Press SET for 3s to enter into the second menuthe upper row window display parameter code, the lower row
window display parameter valuepress orto modifylong time to press can accelerate plus or minus. After
modificationpress SET to save and exit. If dont press any key, it will save and exit automatically after 10s.
(2) The third menu
Press SET +to enter into the third menusetting method is the same as above.
4 Setting itself
First set the fixed value, and then enter the menu ,set

to

At light is onthe controller enter into

setting itself state, set return difference about 0.51here the controller is ON/OFF controlafter three times
oscillationnew parameter

can be confirmed and savedAT light goes outthe controller be reset and

enter into the control state.


6Time control functionwhen it is time& temperature control
Cut time control side at any timetime will get back to the initial stateWhen getting time control side, the
controller will run according to setting time count down.

Attention
When it is time& temperature control ,it provides multifarious time control
method to select,time function detailed
51,

refer to inner parameter sheetSheet

time function selection partwill not give unnecessary details

here.

Fault Analysis and Clearance


XMT*608 adopt advanced production process, and have the strict test before leaving factory, it improve the
reliability of the meter .The usual fault caused by the wrong operation or parameter setting .If you find the fault
couldnt be cope with, please record it, and contact with the agent or us. Sheet 7-1 is the usual fault of XMT*608
in the daily application
Sheet7-1 Common fault disposal

Fault symptom

Analysis of causes

Abnormal power

Disposal measurement

1poor contact of power

Check the power

cord
2power switch without
lose
Signal display do not correlate

1Sensor model

1check sensor model and meter interior input

with the facts.display HH mismatch

parameter

or L

2check signal wire

2wrong signal connect


ion

Abnormal control output

wrong connection of

Check output connection

output wire

RemarkOur company will improve product technology, design and specification, it is confirm to the object.