You are on page 1of 2

TECHNICAL PARTICULARS

Date : 13th Mar. 2016


Rev. No. : 00

Client's Name : M/s. Descon Integrated Projects (Private) Limited


Ref. No. : SQ 974740 : FWEL Projects
Sr. No.
1.00
1.01
1.02
1.03
1.04
1.05
1.06
2.00
2.01
2.02
2.03
2.04
2.05
2.06
3.00

Description
General
Cable Size
Voltage grade
Ref. standard
Number of cores
Max.operating temp.
Max.short circuit temp.
CONDUCTOR
Material
Nominal area
Minimum no. of wires
Shape
Compaction
Conductor diameter - Approx.
CONDUCTOR SCREEN

Unit

1C x 240mm

kV
kV
Nos.
C
C

1C x 240mm
12/20 (24)
IEC 60502-2
1
90
250

mm
Nos.

mm

3.01 Tape Material applied over Conductor


3.02 Tape Thickness - Approx.

Semiconductive Water Blocking Tape


mm

3.03 Conductor screening shall be of extruded semi conducting layer


3.03
4.00
4.01
4.02
4.03
5.00

Min. thickness of extruded semiconducting layer


INSULATION
Material
Thickness of insulation - Nominal
Thickness- Min at any point
INSULATION SCREEN

0.3
Yes

mm

0.3

mm
mm

XLPE
5.50
4.85

5.01 Insulation screening shall be of extruded semi conducting layer


5.02 Min. thickness of extruded semiconducting layer
Tape Material applied over Extruded Semiconducting
5.03
Insulation Screen
5.04 Tape Thickness - Approx.
5.05 Metallic Insulation Screen Tape Material
5.06 Number of copper tape(s)
5.07 Thickness of copper tape screen - Nominal*

Water Tight Aluminium Conductor


240
34
Round
Yes
18.4

Yes
mm

0.3
Semiconductive Water Blocking Tape

mm

mm

0.3
Copper Tape
1
0.1

(NOTE : * No. of Copper Tape & Thickness may change but shall be suitable to carry Fault Current Rating of 1.1kA for 1Sec.)

Yes (Nonconductive Water Blocking


Tape)

5.08 Tape Over Copper Tape


6.00
6.01
6.02
6.03
6.04
6.05

INNER SHEATH
Material
Thickness of inner sheath - Nominal
Thickness of inner sheath - Minimum
Dia over inner sheath - Approximate
Colour of inner sheath

mm
mm
mm

6.06 Tape (below Armour)


7.00
7.01
7.02
7.03
7.04

ARMOUR
Material of Armour
Diameter of armour wire- Nominal
Number of wires- Approximate
Dia over armour- Approximate

7.05 Tape (above Armour)


7.06 Optional Tape (above Nonconductive Water Blocking Tape)

mm
Nos.
mm

PVC ST 2
1.20
0.76
37.80
Black
Yes (Nonconductive Water Blocking
Tape)
AWA
2.00
52
42.40
Yes (Nonconductive Water Blocking
Tape)
PP Tape or Polyester Tape

TECHNICAL PARTICULARS
Date : 13th Mar. 2016
Rev. No. : 00

Client's Name : M/s. Descon Integrated Projects (Private) Limited


Ref. No. : SQ 974740 : FWEL Projects
Sr. No.
8.00
8.01
8.02
8.03
9.00
9.01
9.02
9.03
9.04
9.05
10.00
10.01

Description
TAPE
Material
Approx. Tape Thickness
Application
OUTER SHEATH
Material
Thickness of outer sheath - Nominal
Thickness of outer sheath - Minimum
Overall dia - Approximate
Colour of sheath
PACKAGING
Standard Drum length ( 5%)

Unit

1C x 240mm

mm

Laminated Aluminium Tape


0.30
Applied Longitudinally

mm
mm
mm

HDPE (ST 7)
2.30
1.64
46.5
Black

mtr

1000
Wooden / Steel drums with Wooden
10.02 Packing material
Lagging
10.03 Approx. Size of drum (H x W)*
mm
2000 x 1140
* Drum dimensions is for guidance only & may change due to non-availability of drum of specified size.
11.00 WEIGHTS (Approx.)
11.01 Finished cable
kg / km
2445
11.02 Net weight
kg
2445
11.03 Gross weight of drum
kg
2705
12.00 ELECTRICAL PARAMETERS
12.01 DC resistance of conductor at 20 C - Maximum
/km
0.125
12.02 AC resistance of conductor at 90 C - Approximate
/km
0.162
12.03 Reactance at 50 Hz - Approximate
/km
0.113
12.04 Impedance at 50 Hz - Approximate
/km
0.198
12.05 Capacitance at 50 Hz - Approximate
F/km
0.313
12.06 Short circuit current rating of conductor for 1 Sec.
kA
22.56
12.07 Current Rating (considering 1C cables laid in trefoil
12.08 formation):
12.08.01 Current rating- in ground at 20 C
A
367
Current rating- in duct at 20 C
12.08.02 (In case of Single core cables, considering 3 Single core cables
A
351
in trefoil formation in One common duct)
12.08.03 Current rating- in air at 30C (Flat Spaced)
A
593
12.08.04 Basic Assumptions
Ambient temp. - 30 C
Ground temp. 20 C
Depth of laying in ground - 0.8 Mtr.
Thermal resistivity of soil -1.5 K. m/W
Thermal resistivity of Earthenware duct = 1.2 K m/W
12.09 Fault current rating of copper screen for 1 sec.
kA
0.256
12.10 Fault current rating of armour for 1 second (Approx.)
kA
12.27
12.11 Charging Current at U0 = 12kV, 50Hz.
A/km
1.180
12.12 Dielectric Loss (at U0 = 12kV)
W/km/ph
56.64
13.00 MISC
13.01 Max pulling tension when pulled by pulling eye
kg
720
13.02 Min. Bending radius
mm
15 x OD of cable
NOTE : Embossing on outer sheath of cable shall be as per the examples given below :
"ELECTRIC CABLE 12/20 KV OMAN CABLES 1 X 240 YEAR"
Sequential length marking shall also be provided on outer sheath of cable at every 1m by printing/indenting/embossing.