You are on page 1of 358

NORMAS TCNICAS PARA REDES

ELCTRICAS SUBTERRNEAS
GAS NATURAL FENOSA

Contenido
NDICE DE TABLAS ............................................................................................................................................................................10
1 PREMBULO .................................................................................................................................................................................13
2 OBJETO ..........................................................................................................................................................................................13
3 CAMPO DE APLICACIN...............................................................................................................................................................13
4 REGLAMENTACIN.......................................................................................................................................................................14
5 CARACTERSTICAS DE CONDUCTORES ......................................................................................................................................15
5.1. CARACTERSTICAS GENERALES DE CONDUCTORES....................................................................................................... 15
5.1.1.

Conductores Media Tensin..................................................................................................................................... 15

5.1.2.

Conductores Baja Tensin ....................................................................................................................................... 19

5.1.3.

Zanjas y Canalizaciones para Media Tensin.......................................................................................................... 21

5.1.4.

Zanjas y Canalizaciones para Baja Tensin ............................................................................................................ 26

5.1.5.

Paralelismos ............................................................................................................................................................. 31

5.1.6.

Cruzamientos............................................................................................................................................................ 34

5.1.7.

Acometidas ............................................................................................................................................................... 36

5.1.8.

Paso de Areo a Subterrneo MT ............................................................................................................................ 36

5.1.9.

Dispositivos de Maniobra y Sistemas de Proteccin MT ........................................................................................ 37

5.1.10.

Empalmes y Terminales MT ................................................................................................................................ 37

5.1.11.

Puesta a Tierra...................................................................................................................................................... 38

5.2. CARACTERSTICAS PARTICULARES DE CONDUCTORES ................................................................................................. 40


5.2.1.

Memoria .................................................................................................................................................................... 40

5.2.2.

Planos........................................................................................................................................................................ 41

6 DETALLE DE CONDUCTORES DE MEDIA TENSIN....................................................................................................................41


6.1. CLCULO ELCTRICO ......................................................................................................................................................... 42
6.1.1.

Resistencia del Conductor ....................................................................................................................................... 42

6.1.2.

Reactancia del Conductor ........................................................................................................................................ 45

6.1.3.

Capacitancia.............................................................................................................................................................. 48

6.1.4.

Prdidas Dielctricas ............................................................................................................................................... 49

6.1.5.

Corriente de Carga Capacitiva ................................................................................................................................. 50

6.1.6.

Intensidad Mxima Admisible .................................................................................................................................. 50

6.1.7.

Intensidades de Cortocircuito Admisibles en los Conductores. ............................................................................ 57

6.1.8.

Intensidades de Cortocircuito Admisibles en las Pantallas. ................................................................................. 58

6.1.9.

Cada de Tensin....................................................................................................................................................... 59

6.1.10.

Potencia a Transportar......................................................................................................................................... 61

6.1.11.

Prdidas de Potencia ............................................................................................................................................ 64

7 DETALLE DE CONDUCTORES DE BAJA TENSIN ......................................................................................................................66


7.1. CLCULO ELCTRICO ......................................................................................................................................................... 66
7.1.1.

Resistencia................................................................................................................................................................ 66

7.1.2.

Reactancia Inductiva ................................................................................................................................................ 68

7.1.3.

Intensidad Mxima Admisible .................................................................................................................................. 69

7.1.4.

Cada de tensin ....................................................................................................................................................... 74

7.1.5.

Potencia a Transportar............................................................................................................................................. 77

7.1.6.

Prdidas de Potencia................................................................................................................................................ 79

7.1.7.

Niveles de Potencia .................................................................................................................................................. 82

7.1.8.

Coeficientes de simultaneidad................................................................................................................................. 82

7.1.9.

Intensidad Mxima de Cortocircuito........................................................................................................................ 82

8 ACOMETIDAS.................................................................................................................................................................................85
8.1. CONDUCTORES .................................................................................................................................................................... 85
8.2. CLCULO ELCTRICO ......................................................................................................................................................... 85
8.3. INSTALACIN ....................................................................................................................................................................... 87
8.4. ACOMETIDAS DE ALUMBRADO PBLICO .......................................................................................................................... 88
9 GRFICOS PARA CONDUCTORES MT..........................................................................................................................................89
9.1. GRFICOS DE CAIDA DE TENSIN ..................................................................................................................................... 89
9.2. GRFICOS DE PERDIDA DE POTENCIA .............................................................................................................................. 93
10 GRFICOS PARA CONDUCTORES BT ..........................................................................................................................................97
10.1. GRFICOS DE CADA DE TENSIN ..................................................................................................................................... 97
10.2. GRFICOS DE POTENCIA DE TRANSPORTE .................................................................................................................... 107
10.3. TABLAS DE SELECCIN DEL CONDUCTOR DE ACOMETIDA.......................................................................................... 141
11 CONDICIONES ESPECFICAS PARA LNEAS ELCTRICAS SUBTERRNEAS .........................................................................143
11.1. EJECUCIN DEL TRABAJO ............................................................................................................................................... 143
11.1.1.

Trazado ................................................................................................................................................................ 143

11.2. APERTURA DE ZANJAS ..................................................................................................................................................... 144


11.3. CANALIZACINES .............................................................................................................................................................. 145
11.3.1.

Cable Directamente Enterrado .......................................................................................................................... 145

11.3.2.

Cable Entubado ................................................................................................................................................... 146

11.3.3.

Cables al Aire, Alojados En Galeras ................................................................................................................. 147

11.4. ARQUETAS .......................................................................................................................................................................... 147

11.5. PARALELISMOS ................................................................................................................................................................. 148


11.5.1.

Media y Baja Tensin .......................................................................................................................................... 148

11.5.2.

Baja Tensin........................................................................................................................................................ 149

11.5.3.

Media Tensin ..................................................................................................................................................... 149

11.5.4.

Cables De Comunicacin.................................................................................................................................... 149

11.5.5.

Agua, Vapor, Etc. ................................................................................................................................................. 149

11.5.6.

Gas ....................................................................................................................................................................... 150

11.5.7.

Alcantarillado ...................................................................................................................................................... 150

11.5.8.

Depsito de Carburante ..................................................................................................................................... 150

11.5.9.

Fundaciones de Otros Servicios......................................................................................................................... 150

11.6. CRUZAMIENTOS CON VIAS DE COMUNICACIN ............................................................................................................. 151


11.6.1.

Con Vas Pblicas................................................................................................................................................ 151

11.6.2.

Con Ferrocarriles ............................................................................................................................................... 151

11.6.3.

Cruzamientos Con Otros Servicios .................................................................................................................... 151

11.7. TRANSPORTE DE BOBINAS DE CABLES.......................................................................................................................... 153


11.8. TENDIDO DE CABLES ........................................................................................................................................................ 154
11.9. PROTECCIN MECNICA .................................................................................................................................................. 157
11.10. SEALIZACIN ................................................................................................................................................................ 157
11.11. IDENTIFCACIN ............................................................................................................................................................... 157
11.12. CIERRE DE ZANJAS ......................................................................................................................................................... 157
11.13. REPOSICIN DE PAVIMENTO.......................................................................................................................................... 158
11.14. PUESTA A TIERRA............................................................................................................................................................ 158
11.15. TENSIONES TRANSFERIDAS EN MT. ............................................................................................................................. 159
11.16. MATERIALES .................................................................................................................................................................... 159
12 CONDICIONES BASICAS PARA CENTROS DE TRANSFORMACIN Y DE MANIOBRAS DE PEDESTAL .................................160
12.1. TENSIONES NOMINALES DE MT. NIVEL DE AISLAMIENTO PARA EL MATERIAL. ........................................................ 160
12.2. TENSIONES NOMINALES DE BT. ...................................................................................................................................... 160
12.3. INTENSIDAD NOMINAL EN MT. NIVEL DE CORTOCIRCUITO.......................................................................................... 161
12.4. TIPOS Y POTENCIAS DE LOS TRANSFORMADORES. ...................................................................................................... 161
12.5. CENTROS DE SECCIONAMIENTO. .................................................................................................................................... 162
13 CARACTERSTICAS ELECTRICAS DE CENTROS DE TRANSFORMACIN Y DE SECCIONAMIENTO .....................................164
13.1. CENTROS DE TRANSFORMACIN .................................................................................................................................... 164
13.1.1.

Trafo Tipo Pad-Mounted Monofsico................................................................................................................. 164

13.1.2.

Trafo Tipo Pad-Mounted Trifsico Fin De Lnea. .............................................................................................. 165

13.1.3.

Trafo Tipo Pad-Mounted Trifsico Entrada-Salida. .......................................................................................... 166

13.2. CONEXIONES DE BAJA TENSIN ..................................................................................................................................... 167


13.3. CENTROS DE SECCIONAMIENTO ..................................................................................................................................... 171
13.2.1.

Seccionamiento Simple Tipo Pad-Mounted 3L1. .............................................................................................. 171

13.2.2.

Seccionamiento de Tres Posiciones Tipo Pad-Mounted 3L3. .......................................................................... 172

13.2.3.

Seccionamiento de Cuatro Posiciones Tipo Pad-Mounted 4L4. ...................................................................... 172

13.2.4.

Seccionamiento de Tres Posiciones 3L3 Con Envolvente De Hormign. ........................................................ 173

13.2.5.

Seccionamiento de Cuatro Posiciones 4L4 Con Envolvente De Hormign. .................................................... 173

14 DISPOSICIN DE LA INSTALACIN DE CENTROS DE TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO.................175


14.1. UBICACIN ......................................................................................................................................................................... 175
14.2. ACCESOS ............................................................................................................................................................................ 175
14.3. INSTALACIN DE EXTERIOR. ............................................................................................................................................ 176
14.3.1.

Foso de Recogida de Aceite ............................................................................................................................... 176

14.3.2.

Distancias de Seguridad ..................................................................................................................................... 177

14.3.3.

Plataforma .......................................................................................................................................................... 180

14.3.4.

Caractersticas Constructivas de la Envolvente de Hormign para Centros de Seccionamiento en SF6. .. 180

14.4. INSTALACIN DE INTERIOR ............................................................................................................................................. 181


14.4.1.

Foso de Recogida de Aceite ............................................................................................................................... 181

14.4.2.

Distancias de Seguridad ..................................................................................................................................... 182

14.4.3.

Caractersticas Constructivas ............................................................................................................................ 182

14.4.4.

Canalizaciones .................................................................................................................................................... 186

14.4.5.

Puertas ................................................................................................................................................................ 187

14.4.6.

Condiciones Acsticas ........................................................................................................................................ 187

14.4.7.

Ventilacin ........................................................................................................................................................... 187

14.4.8.

Equipotencialidad ............................................................................................................................................... 189

14.4.9.

Sealizaciones de Seguridad ............................................................................................................................. 190

15 INSTALACIN DE PUESTA A TIERRA DE CENTROS TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO ....................191


15.1. SISTEMAS DE PUESTA A TIERRA ..................................................................................................................................... 191
15.2. ELEMENTOS CONSTITUTIVOS DE LOS SISTEMAS DE PUESTA A TIERRA ..................................................................... 191
15.2.1.

Lneas de Tierra. ................................................................................................................................................. 191

15.2.2.

Electrodo de Puesta a Tierra ............................................................................................................................. 193

15.3. CONDICIONES DE INSTALACIN DE LOS ELECTRODOS ................................................................................................ 193


15.4. EJECUCIN DE LA PUESTA A TIERRA ............................................................................................................................. 194
15.5. MEDIDAS ADICIONALES DE SEGURIDAD PARA LAS TENSIONES DE PASO Y CONTACTO. ......................................... 195

16 CLCULOS ELCTRICOS PARA CENTROS DE TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO .............................197


16.1. INTENSIDADES NOMINALES ............................................................................................................................................ 197
16.2. INTENSIDADES DE CORTOCIRCUITO ............................................................................................................................... 199
17 CONDICIONES ESPECFICAS PARA CENTROS DE TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO ......................201
17.1. EJECUCIN DEL TRABAJO ............................................................................................................................................... 201
17.2. EMPLAZAMIENTO .............................................................................................................................................................. 201
17.3. EXCAVACIN ...................................................................................................................................................................... 202
17.4. CIMENTACIONES ............................................................................................................................................................... 202
17.4.1.

Arena ................................................................................................................................................................... 202

17.4.2.

Piedra .................................................................................................................................................................. 202

17.4.3.

Cementos ............................................................................................................................................................ 202

17.4.4.

Agua ..................................................................................................................................................................... 202

17.5. SOLERA............................................................................................................................................................................... 203


17.6. MUROS EXTERIORES ......................................................................................................................................................... 203
17.7. TABIQUES ........................................................................................................................................................................... 204
17.8. ENLUCIDO Y PINTURA....................................................................................................................................................... 204
17.9. EVACUACIN Y EXTINCIN DEL ACEITE AISLANTE........................................................................................................ 204
17.10. VENTILACIN ................................................................................................................................................................... 204
17.11. PUERTAS .......................................................................................................................................................................... 205
18 INSTALACIN ELCTRICA DE CENTROS DE TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO ...............................206
18.1. ALIMENTACIN SUBTERRNEA ...................................................................................................................................... 206
18.2. ALUMBRADO ...................................................................................................................................................................... 206
18.3. CONEXIONES DE M.T. ........................................................................................................................................................ 207
18.4. CONEXIONES DE B.T. ........................................................................................................................................................ 207
18.5. PUESTA A TIERRA.............................................................................................................................................................. 207
19 MATERIALES PARA CENTROS DE TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO ................................................209
19.1. RECONOCIMIENTO Y ADMISIN DE MATERIALES .......................................................................................................... 209
19.2. HERRAJES .......................................................................................................................................................................... 209
19.3. ENSAYO DIELCTRICO ...................................................................................................................................................... 209
19.4. INSTALACIN DE PUESTA A TIERRA ............................................................................................................................... 209
19.5. TRANSFORMADORES ........................................................................................................................................................ 209
20 PLANOS .......................................................................................................................................................................................210
21 CAJAS DE DERIVACIN SUBTERRNEA ...................................................................................................................................217
21.1. Introduccin ....................................................................................................................................................................... 217

21.2. Objetivos ............................................................................................................................................................................. 217


21.3. Topologa de Redes............................................................................................................................................................ 217
21.4. Acometidas sin ducto futuro ............................................................................................................................................. 218
21.5. Acometidas con ducto futuro ............................................................................................................................................ 218
21.6. Caja de Derivacin ............................................................................................................................................................. 219
21.7. Consideraciones Generales .............................................................................................................................................. 220
21.8. Montaje de Cajas de Derivacin ........................................................................................................................................ 221
21.9.1.

Capacidad de la caja ........................................................................................................................................... 221

21.9.2.

Montaje ................................................................................................................................................................ 221

21.9. Alimentacin ...................................................................................................................................................................... 223


21.10. Conclusiones .................................................................................................................................................................... 223

NDICE DE TABLAS
Tabla 1. Caractersticas generales conductores de MT................................................................................................................ 16
Tabla 2. Caractersticas elctricas de conductores de 15 kV ....................................................................................................... 17
Tabla 3. Caractersticas elctricas de conductores de 35 kV ....................................................................................................... 18
Tabla 4. Caractersticas generales de conductores de BT ........................................................................................................... 19
Tabla 5. Caractersticas elctricas de conductores BT para lneas y acometidas ...................................................................... 20
Tabla 6. Caractersticas elctricas de conductores BT para acometidas.................................................................................... 21
Tabla 7. Dimensiones mnimas de zanjas para MT ....................................................................................................................... 22
Tabla 8. Ancho de zanja para MT .................................................................................................................................................... 23
Tabla 9. Profundidad de zanjas para MT ........................................................................................................................................ 23
Tabla 10. Ancho de zanja para BT .................................................................................................................................................. 27
Tabla 11. Profundidad de zanja para BT ........................................................................................................................................ 28
Tabla 12. Dimensiones mnimas de zanjas para cables directamente enterrados en BT .......................................................... 29
Tabla 13. Intensidades de defecto para conductor aislado........................................................................................................... 39
Tabla 14. Intensidades de defecto para conductor desnudo ........................................................................................................ 40
Tabla 15. Resistencia de los conductores en lneas trifsicas ..................................................................................................... 44
Tabla 16. Resistencia de los conductores en lneas monofsicas ............................................................................................... 44
Tabla 17. Valores de K segn nmero de alambres ..................................................................................................................... 45
Tabla 18. Reactancias de lneas trifsicas equilibradas ............................................................................................................... 46
Tabla 19. Reactancia de lnea monofsica..................................................................................................................................... 47
Tabla 20. Reactancia de pantalla de lnea monofsica ................................................................................................................. 47
Tabla 21. Capacitancia de conductores.......................................................................................................................................... 48
Tabla 22. Prdidas dielctricas en aislamiento de conductores. ................................................................................................. 49
Tabla 23. Intensidad de carga capacitiva de conductores MT ...................................................................................................... 50
Tabla 24. Intensidad trifsica admisible en conductores MT ....................................................................................................... 51
Tabla 25. Coeficientes de correccin segn temperatura ............................................................................................................ 52
Tabla 26. Coeficientes de correccin para cables sobre bandejas .............................................................................................. 53
Tabla 27. Coeficientes de correccin para cables en estructura de pared. ................................................................................ 54

10

Tabla 28. Coeficiente de correccin segn temperatura de terreno en MT ................................................................................ 55


Tabla 29. Valores de K segn tipo de terreno en MT .................................................................................................................... 56
Tabla 30. Coeficientes de correccin segn resistividad trmica de terreno ............................................................................ 56
Tabla 31. Coeficiente de correccin segn profundidad de instalacin....................................................................................... 56
Tabla 32. Coeficiente de correccin segn nmero de cables ..................................................................................................... 56
Tabla 33. Factor de correccin para cables MT bajo tubo agrupados bajo tierra. ...................................................................... 57
Tabla 34. Corriente de cortocircuito (kA) ....................................................................................................................................... 58
Tabla 35. Intensidad de cortocircuito admisible en la pantalla de cobre (kA) ............................................................................. 58
Tabla 36. Cada de tensin trifsica ............................................................................................................................................... 60
Tabla 37. Cada de tensin monofsica.......................................................................................................................................... 60
Tabla 38. Potencia trifsica a transportar ..................................................................................................................................... 62
Tabla 39. Potencia monofsica mxima a transportar ................................................................................................................. 63
Tabla 40. Prdidas trifsicas de potencia ...................................................................................................................................... 65
Tabla 41. Prdidas monofsicas de potencia ................................................................................................................................ 65
Tabla 42. Resistencia por conductor en BT ................................................................................................................................... 67
Tabla 43. Valor de K segn N de alambres en BT ....................................................................................................................... 69
Tabla 44. Reactancia por conductor para lneas de BT................................................................................................................. 69
Tabla 45. Intensidad mxima admisible de conductores en BT ................................................................................................... 69
Tabla 46. Coeficiente de correccin para temperatura del terreno distinta a 30 C para BT .................................................... 70
Tabla 47. Valores de K segn tipo de terreno en BT ..................................................................................................................... 71
Tabla 48. Coeficientes de correccin para cables de BT segn resistividad trmica de terreno .............................................. 71
Tabla 49. Coeficiente de correccin segn profundidad de conductores de BT ......................................................................... 71
Tabla 50. Coeficiente de correccin segn nmero de cables en BT .......................................................................................... 72
Tabla 51. Coeficientes de correccin de cables BT bajo tubos bajo tierra .................................................................................. 72
Tabla 52. Coeficientes de correccin segn temperatura ambiente. .......................................................................................... 73
Tabla 53. Coeficiente de correccin en funcin del nmero de cables BT, ternas y bandejas .................................................. 74
Tabla 54. Cadas de tensin para conductores de BT ................................................................................................................... 76
Tabla 55. Potencia mxima limitada por intensidad mxima para cables de BT directamente enterrados. ............................ 78
Tabla 56. Potencia mxima limitada por intensidad mxima para cables de BT al aire. ........................................................... 79
Tabla 57. Prdidas de potencia en % ............................................................................................................................................. 81
Tabla 58. Coeficientes de simultaneidad ....................................................................................................................................... 82
Tabla 59. Intensidad mxima de cortocircuito para BT ................................................................................................................ 83
Tabla 60. Seccin mnima admisible en la salida de B.T. del trafo .............................................................................................. 84
Tabla 61. Acometidas conectadas a la red B.T. ........................................................................................................................... 141
Tabla 62. Niveles de aislamiento segn tensin nominal........................................................................................................... 160
Tabla 63. Aislamiento de bornas en BT........................................................................................................................................ 161
Tabla 64. Caractersticas de materiales ...................................................................................................................................... 161
Tabla 65. Nmero de conductores segn potencia de trafo ....................................................................................................... 170
Tabla 66. Secciones de neutro segn trafo.................................................................................................................................. 171
Tabla 67. Resistencia al fuego de materiales .............................................................................................................................. 185
Tabla 68. Intensidades de defecto segn nivel de tensin y tipo de conductor ......................................................................... 192
Tabla 69. Densidad de corriente segn terreno .......................................................................................................................... 194
Tabla 70. Consideraciones para tensiones de paso y contacto .................................................................................................. 196
Tabla 71. Intensidades nominales en BT ..................................................................................................................................... 197
Tabla 72. Intensidades nominales para MT ................................................................................................................................. 198
Tabla 73. Tensiones de cortocircuito para transformadores ..................................................................................................... 199
Tabla 74. Intensidades de cortocircuito nominales en BT .......................................................................................................... 200

11

Tabla 75. Intensidades de cortocircuito nominales en MT ......................................................................................................... 200


Tabla 76. ndice de planos para lneas de MT.............................................................................................................................. 210
Tabla 77. ndice de planos para lneas de BT .............................................................................................................................. 213
Tabla 78. ndice de planos para CT y CS ...................................................................................................................................... 215
Tabla 79. Secciones mnimas de conductores por Transformador ........................................................................................... 221
Tabla 80.Capacidad de conexin de la Caja de Derivacin Subterrnea ................................................................................... 221

12

1 PREMBULO
El presente documento constituye las NORMAS TCNICAS PARA
REDES ELCTRICAS SUBTERRNEAS aplicable a lneas elctricas
subterrneas, centros de transformacin y seccionamiento para
alimentacin mediante red subterrnea de MT-BT.

2 OBJETO
Tienen por objeto las presentes NORMAS TCNICAS, establecer y
justificar todos los datos constructivos que permiten la ejecucin
de cualquier obra que responda a las caractersticas indicadas
anteriormente, sin ms que aportar cada proyecto concreto las
particularidades especficas del mismo tales como: clculos
elctricos, plano de situacin y emplazamiento, relacin de
propietarios, cruzamientos, presupuestos, potencia proyectada,
planos, clculo de la puesta a tierra, alimentacin, etctera.
Por otro lado, el presente documento servir de base genrica
para la tramitacin oficial de cada obra, en cuanto a su
Autorizacin Administrativa, sin ms requisitos que la
presentacin de las caractersticas particulares de la misma,
haciendo constar que su diseo se ha realizado de acuerdo con la
NORMAS TCNICAS PARA REDES ELCTRICAS SUBTERRNEAS.
NOTA: En lo sucesivo, en este documento, a los Centros de
Transformacin se le denominar por las siglas CT, y a los centros
de seccionamiento por las siglas CS.

3 CAMPO DE APLICACIN
Las NORMAS TCNICAS GAS NATURAL FENOSA se aplicarn al
diseo general y clculo de los siguientes elementos:
Lneas elctricas subterrneas de 13,2, y 34,5 kV, con
conductores de aluminio 500 MCM y 4/0 AWG para
circuitos trifsicos y 1/0 AWG para circuitos monofsicos,
frecuencia nominal de 60 Hz y neutro puesto a tierra.
Lneas elctricas subterrneas de baja tensin, con
conductores de aluminio 500 MCM, 4/0 AWG y 1/0 AWG y
frecuencia nominal de 60 Hz. Los niveles de tensin
normalizados sern 120/208 trifsico y 120/240 V.
Centros de Transformacin y seccionamiento tanto de
instalacin en intemperie, como de interior, con
envolvente metlica o de hormign, monofsicos o
trifsicos. Incluye los centros a utilizar en la red de MT a

13

las tensiones nominales de 13,2 kV, y 34,5 kV. Este


Documento definir no solo los tipos de centros a utilizar,
sino
tambin
las
condiciones
de
instalacin,
caractersticas de los locales, plataformas, protecciones,
etc.
Ha de tenerse en cuenta que la potencia a considerar debe ser
aquella que se prevea ha de transportar la lnea, al menos a medio
plazo, determinada por un anteproyecto general o por aumentos
de demanda previsibles.

4 REGLAMENTACIN
En la redaccin de las presentes NORMAS se han tenido en cuenta,
en lo aplicable, la siguiente documentacin tcnica:

National Electrical Code (NEC) Estados Unidos.

National Electrical Safety Code (NESC) Estados Unidos.

American National Standard Institute (ANSI).

American Society for Testing and Materials (ASTM).

14

5 CARACTERSTICAS DE CONDUCTORES
Dividiremos este apartado en dos puntos que se refieren, el
primero a las caractersticas generales de la lnea tipo, y el segundo
a aquellas caractersticas particulares de cada obra concreta, que
debern reflejarse en los proyectos individuales.

5.1.

CARACTERSTICAS GENERALES DE CONDUCTORES


Las caractersticas generales comunes en todos los Proyectos
Especficos que se realicen segn las presentes NORMAS sern
las indicadas a continuacin:

5.1.1.

Conductores Media Tensin

5.1.1.1. Componentes
Los cables a emplear estarn compuestos de alambres de aluminio
arrollados helicoidalmente y compactados, y queda perfectamente
definido en la especificacin tcnica correspondiente. Sus
principales componentes son las siguientes:

Los conductores que se emplearn sern de aluminio,


comprimidos, de seccin circular, constituidos por varios
alambres cableados.

Capa semiconductora sobre el material conductor.

Aislamiento a base de polietileno reticulado (XLPE).

Capa semiconductora sobre el material aislante.

Pantalla metlica constituida por una corona de alambres de


cobre arrollados helicoidalmente, que har las funciones de
neutro.

Capa protectora exterior de poliolefina de color rojo.

Las dimensiones mnimas de cada una de estas capas para los


distintos niveles de tensin y conductor, y para un nivel de
aislamiento del 100% son presentadas en la Tabla 1.

15

Tabla 1. Caractersticas generales conductores de MT


DENOMINACIN DEL
CONDUCTOR
Nivel de Tensin

1/0 AWG
15KV

4/0 AWG

35KV

15KV

35KV

750
MCM

500 MCM
15KV

35KV

15 KV

Conductor
N de alambres
Dimetro del alambre
(mm)
Dimetro nominal
conductor (mm)
Seccin del
conductor(mm2)

19

19

37

61

1,89

2,68

2,95

2,82

9,17

13,01

20,04

24,59

53,5

107,2

253

380

0,06

0,06

Pantalla semiconductora del conductor


Espesor (mm)

0,06

0,06
Aislamiento

Espesor (mm)

4,45

8,76

4,45

8,76

4,45

8,76

4,45

1,02

1,02

1,02

Pantalla semiconductora del aislamiento


Espesor (mm)

0,76

1,02

0,76

1,02

Conductor neutro concntrico (Full)


N de alambres

16

Dimetro del alambre


(mm)

1,628
Conductor neutro concntrico (1/3)

N de alambres

11

16

24

Dimetro del alambre


(mm)

1,628

2,052

2,052

Cubierta
Espesor (mm)

1,27

1,27

1,27

1,27

2,03

2,03

2,03

Dimetro exterior
total (mm)

25,4

34,5

29,2

38,3

39,1

47,8

43,70

Radio mnimo de
curvatura (mm)

300

400

350

450

500

600

600

Peso aproximado
(Kg/Km)

1000

1340

1600

2200

3190

3920

4520

16

5.1.1.2. Caractersticas elctricas


Las tensiones normales de los conductores a utilizar se eligen de
acuerdo con la tensin normal de la red, teniendo en cuenta que en
todos los casos se trata de redes con neutro rgidamente puesto a
tierra en mltiples puntos de las mismas (neutro multiaterrado).
Las caractersticas elctricas principales de los conductores de MT
se indican en la Tabla 2 y la Tabla 3.
Tabla 2. Caractersticas elctricas de conductores de 15 kV

CONDUCTORES CLASE 15 KV
Tensin nominal entre fases (kV)

13,2

Tensin ms elevada de la red (KV)

14,124
90

T max. normal (C)

250

T en cc. max 5 s. (C)

100 %

Aislamiento
Tipo de conductor
Corriente admis. aire a 40C (A)
(Corriente nula por pantalla).
Corriente admis. enterrada a 25C (A)
(Corriente nula por pantalla).
Corriente admis. enterrada bajo tubo en arena
(A) (Corriente nula por pantalla).

1/0 AWG

4/0 AWG

191

291

485

625

192

280

434

534

153

224

354

438

Icc admisible conductor durante 0,2 s. (kA)

11,1

22,2

52,6

79

Icc admisible pantalla durante 0,2 s. (kA)

10,6

7,3

16,9

16,9

Resistencia mx. en continua a 20C (/Km)

0,5378

0,2682

0,1135

0,0759

Capacidad F/Km (Caso trifsico)

0,2047

0,2662

0,3775

0,4492

Coeficiente autoinduccin (H/Km)


(Caso trifsico)
Coeficiente autoinduccin (H/Km)
(Caso monofsico)
Reactancia inductiva (/Km) a 60 Hz.
(Caso trifsico)
Reactancia inductiva (/Km) a 60 Hz.
(Caso monofsico)

500 MCM 750 MCM

3,9710-4 3,5510-4 3,1710-4 3,05 10-4


3,57 10-4

0,1498

0,1340

0,1197

0,1148

0,1344

17

Tabla 3. Caractersticas elctricas de conductores de 35 kV

CONDUCTORES CLASE 35 KV
Tensin nominal entre fases (kV)
Tensin ms elevada de la red (KV)
Aislamiento
T max. normal (C)
T en cc. max 5 s. (C)
Tipo de conductor
Corriente admis. aire a 40C (A)
Corriente nula por pantalla.
Corriente admis. enterrada a 25C (A).
Corriente nula por pantalla.
Corriente admis. enterrada bajo tubo en arena (A)
Corriente nula por pantalla.
Icc admisible conductor durante 0,2 s. (kA)
Icc admisible pantalla durante 0,2 s. (kA)
Resistencia mx. en continua a 20C (/Km)
Capacidad F/Km (Caso trifsico)
Coeficiente autoinduccin (H/Km)
(Caso trifsico)
Coeficiente autoinduccin (H/Km)
Caso monofsico)
Reactancia inductiva (/Km) a 60Hz.
(Caso trifsico)
Reactancia inductiva (/Km) a 60Hz.
(Caso monofsico)

34,5

1/0 AWG

36,915
100 %
90
250
4/0 AWG

500 MCM

196

297

497

190

278

435

157

230

361

11,1
10,6
0,5378
0,1299

22,2
7,3
0,2682
0,1626

52,6
16,9
0,1135
0,2209

4,5810-4

4,110-4

3,6510-4

4,2710-4

0,1728

0,1546

0,1378

0,1613

Los conductores utilizados sern debidamente protegidos contra la


corrosin que pueda provocar el terreno donde se instalen y tendrn
resistencia mecnica suficiente para soportar los esfuerzos a que
pueden estar sometidos.
Los empalmes y conexiones de los conductores subterrneos se
efectuarn siguiendo mtodos o sistemas que garanticen una
perfecta continuidad del conductor y de su aislamiento.
La puesta a tierra se llevar a cabo en cada extremo de la lnea (en
el CT y en el paso de areo- subterrneo) de manera que su
resistencia individual no supere los 20 , y la resistencia de puesta
a tierra global, sea inferior a los 5 . En caso de tramos de
longitud superior a 4 km entre dos puestas a tierra consecutivas,
ser necesario conectar a tierra las pantallas en un empalme
intermedio.

18

5.1.2.

Conductores Baja Tensin

5.1.2.1. Componentes

Los conductores que se emplearn para la red de B.T. subterrnea


sern de aluminio de seccin circular de varios alambres
cableados, y de cobre concntricos.
Los conductores de aluminio sern unipolares, y los concntricos
de cobre tripolares y tetrapolares, y estarn protegidos contra la
corrosin que pueda provocar el terreno en el que se instalen. As
mismo, tendrn la resistencia mecnica suficiente para soportar
los esfuerzos a los que estn sometidos. En la Tabla 4 se
describen los diferentes conductores empleados en el Documento.

Tabla 4. Caractersticas generales de conductores de BT

Caractersticas constructivas
Conductor

Descripcin
Conductores de uso en lneas y acometidas

500 MCM

Conductor aislado XLPE 500 MCM

4/0 AWG

Conductor aislado XLPE 4/0 AWG

1/0 AWG

Conductor aislado XLPE 1/0 AWG


Conductores de uso exclusivo en acometidas

4 #4

Concntrico; Fases y neutro: #4 Cu

3 #4

Concntrico; Fases y neutro: #4 Cu

2 #6

Concntrico; Fases y neutro: #6 Cu

4 #6

Concntrico; Fases y neutro: #6 Cu

3 #6

Concntrico; Fases y neutro: #6 Cu

5.1.2.2. Caractersticas elctricas


Los empalmes y conexiones de los conductores subterrneos se
efectuarn siguiendo mtodos o sistemas que garanticen una
perfecta continuidad del conductor y de su aislamiento.
La seccin del conductor neutro ser la misma que la de los
conductores de fase.

19

El conductor neutro se conectar a tierra en las acometidas, as


como en las derivaciones importantes. De cualquier modo se
asegurar un aterrizaje cada 250 metros como mximo, asegurando
una resistencia global de la puesta a tierra de 5 ohmios como
mximo.
Se indican las principales caractersticas de los conductores
empleados en la presente NORMA en la Tabla 5 y Tabla 6.
Tabla 5. Caractersticas elctricas de conductores BT para lneas y
acometidas

Conductor

DE USO EN LNEAS Y ACOMETIDAS


500 MCM

4/0 AWG

1/0 AWG

253,3

107,2

53,5

37 x 2,95

19 x 2,68

19 x 1,98

Polietileno
reticulado

Polietileno
reticulado

Polietileno
reticulado

Cubierta

PVC

PVC

PVC

Dimetro del conductor (mm)

20,65

13,41

9,45

Dimetro total (mm)

27,25

18,49

14,53

Peso del aluminio (kg/km)

698,5

295,7

147,1

Carga de rotura por (daN)

4031

1794

969

Resistencia elctrica en C.C. a


20 C (/km)

0,1135

0,2682

0,5378

Resistencia elctrica en C.C. a


90 C (/km)

0,1455

0,3438

0,6895

Seccin (mm )
Composicin (n alambres x
en mm)
Aislamiento

20

Tabla 6. Caractersticas elctricas de conductores BT para acometidas


DE USO EXCLUSIVO EN ACOMETIDAS

Conductor
3 #4 AWG

4 #4 AWG 2 # 6 AWG 3 # 6 AWG 4 # 6 AWG

N hilos
Fase

Dimetro hilo (mm)

1,96

1,55

Dimetro fase (mm)

5,88

4,65

Seccin Fase (mm2)

21,15

13,3

Espesor del aislamiento (mm)


N hilos
Neutro

Dimetro hilo (mm)


AWG
2

Seccin (mm )
Dimetro exterior aprox. (mm)
Peso (daN/m)
Resistencia elctrica en C.C. a 20
C (/km)

5.1.3.

1,14
65

103

25

65

104

0,643

0,511

0,813

0,511

0,404

22

24

20

24

26

21,12

13,21

13,21

21,12

13,21

12,8 21,1

22

11,6

11,3 18,2

0,700

0,900

0,325

0,475

0,840

19,1
0,625

1,337

Zanjas y Canalizaciones para Media Tensin

Los cables aislados subterrneos de 13,2, y 34,5 kV podrn


canalizarse de las siguientes formas:

Directamente enterrados
Entubados en zanja
Al aire, alojados en galeras

a) Cables directamente enterrados en zanja


Esta disposicin ser la que se emplee de forma prioritaria,
preferentemente en veredas o zonas ajardinadas, incluso bajo
acera, si no hay otros servicios que impidan esta disposicin
constructiva.
Los cables se tendern en contacto, agrupados en disposicin trbol
si la lnea es trifsica.
Las dimensiones mnimas de las zanjas vienen condicionadas por el
nmero de lneas a tender, segn se indica en la Tabla 7.

21

Tabla 7. Dimensiones mnimas de zanjas para MT

N DE LNEAS*
EN PLANO HORIZONTAL

PROFUNDIDAD
MNIMA (cm)

ANCHURA
MNIMA (cm)

80

40

80

60

80

80

* El nmero de lneas puede referirse tanto a lneas de Media Tensin como de


Baja Tensin combinadas.

Las dimensiones mencionadas se modificarn, en caso necesario,


cuando se encuentren otros servicios en el trazado (ver apartados
5.1.5. Paralelismos y 5.1.6. Cruzamientos), a fin de mantener las
distancias mnimas de seguridad. La anchura de la zanja vendr
tambin condicionada por el tipo de mquina empleada para su
ejecucin.
Los cables irn alojados en general en zanjas lo suficientemente
profundas de forma que en todo momento la profundidad mnima de
la lnea ms prxima a la superficie del suelo, sea de 60 cm.
Cuando se tiendan dos y tres lneas en un mismo plano horizontal
en la misma zanja, ya sean de MT o de BT, la separacin mnima
entre puntos ms prximos de las lneas no debe ser inferior a 25
cm para cualquier nivel de tensin.
La disposicin de los cables en las zanjas ser la siguiente:
En el fondo de la zanja se dispondr una capa de unos 10 cm de
arena fina sobre la que se situarn los cables; por encima ir otra
capa de arena fina de unos 15 cm de espesor, sobre ella se
colocar un tritubo sobre cada lnea, el cual realizar las funciones
de placa de proteccin mecnica y tubo para comunicaciones. Las
caractersticas y dimensiones del tritubo vienen definidas en la
especificacin tcnica correspondiente.
A continuacin se realizar el compactado mecnico,
emplendose el tipo de tierra y las tongadas adecuadas para
conseguir un prctor del 95%, teniendo en cuenta que los tubos de
comunicaciones irn situados por encima de los de energa.
Se colocar una cinta de sealizacin de presencia de cables
elctricos a lo largo de toda la zanja y a una profundidad mnima de
30 cm de la superficie del suelo.

22

b) Cables entubados en zanja.


Este tipo de canalizacin ser el que se utilice generalmente en
aceras o calzadas, especialmente en las que exista multiplicidad de
servicios subterrneos que dificulten el tendido directamente
enterrado o que no permitan mantener las distancias adecuadas en
cruzamientos o paralelismos.
El cable ir en un tubo de plstico de 160 mm de dimetro para
lneas trifsicas y 110 mm para lneas monofsicas, cuyas
caractersticas y dimensiones vienen definidas en la especificacin
tcnica correspondiente.
Las dimensiones mnimas de las zanjas vienen condicionadas por
las dimensiones del tubo, el nmero de tubos a tender, el nmero
de hileras de tubos y por el material de relleno de la zanja, segn se
indica en la Tabla 8 y la Tabla 9
Tabla 8. Ancho de zanja para MT

ANCHURA MNIMA
(SEGN MATERIAL DE RELLENO)

N DE TUBOS
EN PLANO
HORIZONTAL

Arena (cm)

Hormign (cm)

1 tubo 110 mm
1 tubo 160 mm
2 tubos 110 mm
2 tubos 160 mm
3 tubos 110 mm
3 tubos 160 mm
4 tubos 110 mm
4 tubos 160 mm
5 tubos 110 mm

25
25
40
40
60
60
60
80
80

25
40
40
60
60
80
80
-

Tabla 9. Profundidad de zanjas para MT

PROFUNDIDAD MNIMA

N DE HILERAS
DE TUBOS

Arena (cm)

Hormign (cm)

80

80

100

120

23

Anlogamente al caso anterior, las dimensiones mencionadas se


modificarn cuando se encuentren otros servicios en el trazado
de la lnea, a fin de mantener las distancias mnimas de
seguridad, as como por la maquinaria empleada.
En previsin de futuras lneas de comunicacin, tanto propias
como ajenas, se instalar opcionalmente un tritubo sobre el o
los tubos de la lnea. Las caractersticas y dimensiones del
tritubo vienen definidas en la especificacin tcnica
correspondiente.
Los tubos con los conductores se situarn sobre un lecho de
arena de 5 cm de espesor. A continuacin se rellenar toda la
zanja de la misma forma que en el caso anterior, es decir, con
el tipo de tierra y las tongadas adecuadas para conseguir un
prctor del 95%.
Se colocar una cinta de sealizacin de presencia de cables a
lo largo de toda la zanja.
Los tubos irn alojados en general en zanjas lo suficientemente
profundas de forma que en todo momento la profundidad mnima
de la lnea ms prxima a la superficie del suelo sea de 60 cm.
Se guardarn distancias de seguridad con otras lneas y a las
paredes de la zanja. stas son las siguientes:

20 mm a las paredes de la zanja.


40 mm entre tubos.

En los cruzamientos de calzadas y de ferrocarriles los tubos


irn hormigonados en todo su recorrido. Tambin se
hormigonarn los tubos en caso de tendido de varias hileras de
tubos en planos horizontales paralelos. Las distancias que se
deben respetar son las siguientes:

60 mm de hormign del tubo a la pared vertical de la zanja.


60 mm de hormign del tubo al fondo de la zanja.
60 mm de hormign sobre la capa horizontal de tubos.
60 mm de hormign entre tubos.

Si se decide colocar un tritubo, tambin se hormigonar.


En este caso, se estudiar la posibilidad de instalar tubos de
reserva en previsin de nuevas necesidades.

24

c) Cables al aire, alojados en galeras


Se debe evitar en lo posible este tipo de canalizacin,
utilizndose nicamente en el caso de que el nmero de lneas
sea tal que justifique la realizacin de las galeras; o en casos
especiales en que no se pueda realizar otro tipo de
canalizaciones.
En este tipo de canalizaciones, los cables estarn colocados al
aire, agrupados en disposicin trbol y convenientemente fijados
sobre bandejas perforadas, palomillas o abrazaderas.
Cuando se tiendan ms de una lnea, estas se situarn
preferentemente en un mismo plano.
La distancia mnima entre lneas situadas en el mismo plano
horizontal ser 1,5 veces el dimetro exterior del cable. La
separacin mnima entre lneas situadas en el mismo plano
vertical, ser de 4 veces el dimetro exterior del cable. La
separacin entre lneas y pared ser de 0,5 veces el dimetro
exterior del cable.
Los elementos metlicos de sujecin debern conectarse
elctricamente a tierra.
Los cables quedarn colocados y sujetos de manera que no se
desplacen por efectos electrodinmicos.
Los locales o galeras debern estar bien aireados para obtener
una baja temperatura media y evitar accidentes por emanacin
de gases, debiendo adems, disponer de un buen sistema de
drenaje.
No se instalarn cables elctricos en galeras donde existan
conducciones de gases o lquidos inflamables.

5.1.3.1. Dimensionado
El trazado de las lneas se realizar de acuerdo con las siguientes
consideraciones:
- La longitud de la canalizacin ser lo ms corta posible.
- Se ubicar, preferentemente, salvo casos excepcionales, en
terrenos de dominio pblico, bajo acera, evitando los ngulos
pronunciados.

25

- El radio interior de curvatura, despus de colocado el cable, ser,


como mnimo, el indicado en la Tabla 1 del apartado 5.1.1.
- Los cruces de calzadas debern ser perpendiculares a sus ejes,
salvo casos especiales, debiendo realizarse en posicin horizontal
y en lnea recta.
- Las distancias a fachadas estarn de acuerdo con lo especificado
por los reglamentos y ordenanzas municipales correspondientes.
5.1.3.2. Arquetas de registro
Se evitar en la medida de lo posible la construccin de arquetas. Si
fuese necesaria la colocacin de arquetas de registro en las
instalaciones de cables subterrneos, para permitir la instalacin,
empalme, derivacin, reposicin y reparacin de los cables, deber
justificarse su absoluta necesidad.
Las arquetas de registro se construirn rectangulares con paredes
de ladrillo de 24 cm de espesor u hormign armado, con unas
dimensiones interiores suficientes para poder practicar
manipulaciones en los cables con comodidad, de forma que, tanto
durante el tendido como una vez fijados los cables en la arqueta se
respeten los radios mnimos de curvatura de los cables.
Las dimensiones de las arquetas de registro se pueden encontrar de
forma detallada en los planos correspondientes de esta NORMA.

5.1.4.

Zanjas y Canalizaciones para Baja Tensin

5.1.4.1. Dimensionado
El trazado de las lneas se realizar de acuerdo a las siguientes
consideraciones:

La longitud de la canalizacin ser lo ms corta posible.


Se ubicar, preferentemente, salvo casos excepcionales, en
terrenos de dominio pblico, bajo acera, evitando los ngulos
pronunciados.
El radio interior de curvatura, despus de colocado el cable,
ser, como mnimo, de 12 veces el dimetro exterior del cable.
Los cruces de calzadas debern ser perpendiculares a sus
ejes, salvo casos especiales, debiendo realizarse en posicin
horizontal y en lnea recta.

26

Las distancias a fachadas estarn, siempre que sea posible, de


acuerdo con lo especificado por los reglamentos y normativa
local correspondientes.

Los cables aislados subterrneos de baja tensin podrn


canalizarse de las siguientes formas:

a)

Entubados en zanja
Directamente enterrados
Al aire, alojados en galeras
Cables entubados en zanja

Esta configuracin ser la que se emplee de forma prioritaria para


las lneas de distribucin de B.T. y la nica en caso de acometidas.
Las dimensiones mnimas de las zanjas vienen condicionadas por
las dimensiones y nmero de tubos a tender, el nmero de hileras
de tubos y por el material de relleno de la zanja, segn se indica en
la Tabla 10 y Tabla 11.
Tabla 10. Ancho de zanja para BT

ANCHURA MNIMA

N DE TUBOS EN PLANO
HORIZONTAL

Arena (m)

Hormign (m)

1 Tubo de 60 mm

0,25

0,25

2 Tubos de 60 mm

0,25

0,25

3 Tubos de 60 mm

0,25

0,4

1 tubo de 110 mm

0,25

0,25

2 tubos de 110 mm

0,4

0,4

3 tubos de 110 mm

0,6

0,6

4 tubos de 110 mm

0,6

0,8

5 tubos de 110 mm

0,8

* El nmero de lneas puede referirse tanto a lneas de Baja


Tensin como de Media Tensin combinadas.

27

Tabla 11. Profundidad de zanja para BT

N DE
DIMETRO TUBO (MM)
HILERAS

PROFUNDIDAD MNIMA
Arena (m)

Hormign (m)

60

0,60

0,60

110

0,8

0,80

60

0,8

1 hilera de 60 mm + 1
hilera de 110 mm

0,8

110

1,0

110

1,2

Las dimensiones mencionadas se modificarn cuando se


encuentren otros servicios en el trazado de la lnea, a fin de
mantener las distancias mnimas de seguridad, as como por la
maquinaria empleada.
La lnea de distribucin de B.T. tanto trifsica como monofsica, se
canalizar en un tubo de plstico de 110 mm. Para acometidas se
utilizar un tubo de 60 mm. Las caractersticas y dimensiones de
estos tubos quedan definidas en la especificacin tcnica
correspondiente.
Los tubos con los conductores se situarn sobre un lecho de arena
de 5 cm de espesor. A continuacin se cubrirn con arena hasta 5
cm sobre la arista superior del tubo y finalmente se rellenar toda
la zanja con el tipo de tierra y las tongadas adecuadas para
conseguir un prctor del 95%.
Los cables irn alojados en general en zanjas lo suficientemente
profundas de forma que en todo momento la profundidad mnima
del tubo ms prximo a la superficie del suelo sea de 60 cm. Para
lneas de acometida, esta distancia se puede reducir a 45 cm, si
estn suficientemente protegidas. Se guardarn distancias de
seguridad con otros conductores y a las paredes de la zanja. stas
son las siguientes:

20 mm a las paredes de la zanja.


40 mm entre tubos.

28

En los cruzamientos de calzadas y de ferrocarriles los tubos irn


hormigonados en todo su recorrido. Tambin se hormigonarn los
tubos en caso de tendido de varias hileras de tubos en planos
horizontales paralelos. Las distancias que se deben respetar son
las siguientes para las lneas de distribucin de B.T.:

60 mm de hormign del tubo a la pared vertical de la zanja.


60 mm de hormign del tubo al fondo de la zanja.
60 mm de hormign sobre la capa horizontal de tubos.
60 mm de hormign entre tubos.

Si est previsto el tritubo para comunicaciones, tambin se


hormigonar.
En caso de canalizaciones hormigonadas,
se estudiar la
posibilidad de instalar tubos de reserva en previsin de futuras
necesidades.
Se colocar una cinta de sealizacin de presencia de cables a lo
largo de toda la zanja.

b) Cables directamente enterrados en zanja


Esta disposicin se podr utilizar en veredas o zonas ajardinadas,
incluso bajo acera, si no hay otros servicios que impidan esta
disposicin constructiva, y siempre en lneas de distribucin en B.T.,
nunca en acometidas.
Los cables se tendern en contacto, agrupados en disposicin trbol
si la lnea es trifsica.
Las dimensiones mnimas de las zanjas vienen condicionadas por el
nmero de lneas a tender, segn se indica en la Tabla 12:
Tabla 12. Dimensiones mnimas de zanjas para cables directamente
enterrados en BT

N de lneas*
en plano horizontal

Profundidad mnima

Anchura mnima

80

40

80

60

80

80

29

Las dimensiones mencionadas se modificarn, en caso necesario,


cuando se encuentren otros servicios en el trazado (ver apartados
5.1.5 y 5.1.6), a fin de mantener las distancias mnimas de
paralelismo y/o cruzamiento. La anchura de la zanja vendr
tambin condicionada por el tipo de mquina empleada para su
ejecucin.
Los cables irn alojados en general en zanjas lo suficientemente
profundas de forma que en todo momento la profundidad mnima
del cable ms prximo a la superficie del suelo sea de 60 cm.
Cuando se tiendan dos y tres lneas en un mismo plano horizontal
en la misma zanja, ya sean de MT o de BT, la separacin mnima
entre puntos ms prximos de las lneas no debe ser inferior a 25
cm para cualquier nivel de tensin.
La disposicin de los cables en las zanjas ser:
En el fondo de la zanja ir una capa de unos 5 cm de arena fina
sobre la que se situarn los cables; por encima ir otra capa de
arena fina de unos 15 cm de espesor, sobre ella se colocar un
tritubo sobre cada lnea, el cual realizar las funciones de placa de
proteccin mecnica y tubo para comunicaciones. Las
caractersticas y dimensiones del tritubo vienen definidas en la
especificacin tcnica correspondiente.
A continuacin se realizar el compactado mecnico,
emplendose el tipo de tierra y las tongadas adecuadas para
conseguir un prctor del 95%, teniendo en cuenta que los tubos de
comunicaciones irn situados por encima de los de energa.
Se colocar una cinta de sealizacin de presencia de cables
elctricos a lo largo de toda la zanja.
c)

Cables al aire, alojados en galeras

Se debe evitar en lo posible este tipo de canalizacin, utilizndose


nicamente en el caso de que el nmero de lneas sea tal que
justifique la realizacin de las galeras; o en casos especiales en que
no se pueda realizar otro tipo de canalizaciones.
En este tipo de canalizaciones, los cables estarn colocados al aire,
agrupados en disposicin trbol y convenientemente fijados sobre
bandejas perforadas, palomillas o abrazaderas.
Cuando se tiendan ms de una terna, estas se situarn
preferentemente en un mismo plano.

30

La distancia mnima entre ternas situadas en el mismo plano


horizontal ser 1,5 veces el dimetro exterior del cable. La
separacin mnima entre ternas situadas en el mismo plano vertical,
ser de 4 veces el dimetro exterior del cable. La separacin entre
ternas y pared ser de 0,5 veces el dimetro exterior del cable.
Los elementos metlicos
elctricamente a tierra.

de

sujecin

debern

conectarse

Los cables quedarn colocados y sujetos de manera que no se


desplacen por efectos electrodinmicos.
Los locales o galeras debern estar bien aireados para obtener una
baja temperatura media y evitar accidentes por emanacin de gases,
debiendo adems, disponer de un buen sistema de drenaje.
No se instalarn cables elctricos en galeras donde existan
conducciones de gases o lquidos inflamables.

5.1.4.2. Arquetas de registro


Se evitar en la medida de lo posible la construccin de arquetas.
Si fuese necesaria la colocacin de arquetas de registro en las
instalaciones de cables subterrneos, para permitir la instalacin,
empalme, derivacin, reposicin y reparacin de los cables,
deber justificarse su absoluta necesidad.
Las arquetas de registro se construirn rectangulares con paredes
de ladrillo de 24 cm de espesor u hormign armado, con unas
dimensiones interiores suficientes para poder practicar
manipulaciones en los cables con comodidad, de forma que, tanto
durante el tendido como una vez fijados los cables en la arqueta se
respeten los radios mnimos de curvatura de los cables.
5.1.4.3. Sealizacin
La funcin de aviso para evitar el posible deterioro que se pueda
ocasionar al realizar las excavaciones en las proximidades de la
canalizacin la cumplir la cinta de sealizacin.

5.1.5.

Paralelismos

Las lneas de distribucin elctrica subterrneas debern guardar


las siguientes distancias a las diferentes instalaciones existentes.

31

En ningn caso se canalizarn paralelamente por encima o por


debajo de cualquier otra instalacin, con excepcin de las lneas
elctricas, siempre y cuando, stas sean de propiedad de Gas
Natural Fenosa. En tal caso, ambas lneas se canalizarn bajo tubo
y se situar en el nivel superior la lnea de menor tensin.

5.1.5.1. Media y Baja Tensin


Los cables de Baja Tensin se podrn colocar paralelos a cables de
Media Tensin, siempre que entre ellos haya una distancia no
inferior a 25 cm. Cuando no sea posible conseguir esta distancia, se
instalar uno de ellos bajo tubo, manteniendo como mnimo una
distancia de 10 cm entre cable directamente enterrado y tubo.

5.1.5.2. Media Tensin


En el caso de paralelismos de cables de media tensin entre s, se
mantendr una distancia mnima de 25 cm. Si no se pudiera
conseguir esta distancia, se colocar una de ellas bajo tubo,
manteniendo como mnimo una distancia de 10 cm entre cable
directamente enterrado y tubo.

5.1.5.3. Baja Tensin


En el caso de paralelismos de cables de baja tensin entre s, se
mantendr una distancia mnima de 25 cm. Si no se pudiera
conseguir esta distancia, se colocar una de ellas bajo tubo,
manteniendo como mnimo una distancia de 10 cm entre cable
directamente enterrado y tubo.

5.1.5.4. Cables de telecomunicacin


Los cables de media y baja tensin directamente enterrados,
debern estar separados de los de telecomunicacin una distancia
mnima horizontal de 20 cm, en el caso en que los cables de
telecomunicacin vayan tambin enterrados directamente. Cuando
esta distancia no pueda alcanzarse, deber instalarse la lnea
elctrica de media o baja tensin dentro tubos con una resistencia
mecnica apropiada.
En paralelismos con cables telefnicos con cables de media tensin,
deber tenerse en cuenta lo especificado por el correspondiente
acuerdo con las compaas de telecomunicaciones. Solo se podrn

32

realizar paralelismos de ms de 500 m si los cables de


telecomunicacin llevan pantalla electromagntica.
En paralelismos con cables telefnicos con cables de baja tensin,
deber tenerse en cuenta lo especificado por el correspondiente
acuerdo con las compaas de telecomunicaciones.

5.1.5.5. Agua, vapor, etc.


Los cables de media y baja tensin se instalarn separados de las
conducciones de otros servicios (agua, vapor, etc.) a una distancia no
inferior a 25 cm. Si por motivos especiales no se pudiera conseguir
esta distancia, los cables se instalarn dentro tubos.

5.1.5.6. Gas
La distancia entre los cables de energa y las conducciones de gas
ser como mnimo de 50 cm. Adems, para el caso de las
canalizaciones de gas, se asegurar la ventilacin de los conductos,
galeras y registros de los cables para evitar la posibilidad de
acumulacin de gases en ellos.
No se colocar el cable elctrico paralelamente sobre el conducto
de gas, debiendo pasar dicho cable por debajo. Si no fuera posible
conseguir la separacin de 50 cm, se instalarn los cables dentro
tubos.

5.1.5.7. Alcantarillado
En los paralelismos de los cables con conducciones de
alcantarillado de aguas fecales, habr una distancia mnima de 50
cm, debindose instalar los cables bajo tubo cuando no pueda
conseguirse esa distancia. En el caso de paralelismos de los cables
con conducciones de alcantarillado de aguas fluviales, el
tratamiento ser anlogo al de las conducciones de agua.

5.1.5.8. Depsitos de carburante


Entre los cables elctricos y los depsitos de carburante, habr una
distancia mnima de 1,20 m, debiendo, adems, protegerse
apropiadamente el cable de baja tensin. El cable de media tensin
ser instalando bajo tubo hormigonado al menos desde 3 m de
distancia a ambos lados de la zona de paralelismo, tal y como se
muestra en los planos correspondientes en la seccin 20.

33

5.1.5.9. Fundaciones de otros servicios


Cuando prxima a la canalizacin existan soportes de lneas
areas de transporte pblico, telecomunicacin, alumbrado
pblico, etc. el cable se instalar a una distancia de 50 cm como
mnimo de los bordes externos de los soportes o de las
fundaciones. Esta distancia ser de 150 cm en el caso en el que el
soporte est sometido a un esfuerzo de vuelco permanente hacia
la zanja. Cuando esta precaucin no se pueda tomar, se emplear
una proteccin mecnica resistente a lo largo del soporte y de su
fundacin prolongando una longitud de 50 cm a ambos lados de los
bordes extremos de la misma.
5.1.6.

Cruzamientos

5.1.6.1. Media Tensin con Baja Tensin


En los cruzamientos de los cables de Media Tensin con otros de
Baja Tensin, existir una distancia entre ellos de 25 cm como
mnimo. En caso de que no pudiese conseguirse esta distancia se
separarn los cables de Baja Tensin de los de Media Tensin por
medio de tubos, manteniendo como mnimo una distancia de 10 cm
entre cable directamente enterrado y tubo.

5.1.6.2. Media Tensin


En los cruzamientos entre lneas de Media Tensin, la distancia
mnima a respetar ser de 25 cm. Si no fuese posible conseguir esta
distancia, se colocar una de las lneas bajo tubo, manteniendo
como mnimo una distancia de 10 cm entre cable directamente
enterrado y tubo.
5.1.6.3. Baja Tensin
En los cruzamientos entre lneas de Baja Tensin, la distancia
mnima a respetar ser de 25 cm. Si no fuese posible conseguir
esta distancia, se instalar una de las lneas bajo tubo.
5.1.6.4. Con cables de telecomunicacin
En los cruzamientos con cables de telecomunicacin, los cables de
energa elctrica, se colocarn en tubos o conductos de resistencia
mecnica apropiada, a una distancia mnima de la canalizacin de
telecomunicacin de 20 cm. En todo caso, cuando el cruzamiento
sea con cables telefnicos deber tenerse en cuenta lo

34

especificado por el correspondiente acuerdo con la empresa de


telecomunicacin.
5.1.6.5. Vas pblicas
En los cruzamientos con calles y carreteras los cables debern ir
entubados a una profundidad mnima de 80 cm. Los tubos o
conductos sern resistentes, duraderos, estarn hormigonados en
todo su recorrido y tendrn un dimetro que permita deslizar los
cables por su interior fcilmente. En todo caso deber tenerse en
cuenta lo especificado por las normas y ordenanzas vigentes, que
correspondan.
5.1.6.6. Agua, vapor, etc.
En los cruzamientos de una canalizacin con conducciones de otros
servicios (agua, vapor, etc.) se guardar una distancia mnima de 25
cm. Si no fuera posible, se colocar la lnea bajo tubo.
5.1.6.7. Gas
No se realizar el cruce del cable elctrico sobre la proyeccin
vertical de las juntas de la canalizacin de gas.
La distancia a respetar en el caso de cruce con una canalizacin de
gas es de 25 cm.
5.1.6.8. Alcantarillado
En los cruzamientos de cables elctricos con conducciones de
alcantarillado deber evitarse el ataque de la bveda de la
conduccin, debindose mantener en todo caso la distancia mnima
de 50 cm para el caso de conducciones de alcantarillado de aguas
fecales. En el caso de aguas fluviales, el tratamiento ser anlogo al
de conducciones de agua.
5.1.6.9. Depsitos de carburantes
Se evitarn los cruzamientos de cables elctricos sobre depsitos
de carburantes. Los cables de energa elctrica debern bordear el
depsito, adecuadamente protegidos, y quedar a una distancia
mnima de 1,20 m del mismo.

35

5.1.6.10.
errocarriles

Los cruzamientos con ferrocarriles se realizarn en conductos o


tubos perpendiculares a la va y a una profundidad de 1,30 m como
mnimo. Esta profundidad debe considerarse con respecto a la
cara inferior de las traviesas. Se recomienda efectuar el
cruzamiento por los lugares de menor anchura de la zona del
ferrocarril. En todo caso, deber tenerse en cuenta lo especificado
por la correspondiente autorizacin de la compaa de trenes
correspondiente.
5.1.7.

Acometidas

Las acometidas monofsicas bitensin (120/240 V) se realizarn


mediante conductores concntricos de cobre tripolares (3 x #6 3
x #4). Las acometidas trifsicas (120/240 V 120/208 V) se
realizarn mediante conductores concntricos de cobre
tetrapolares (4 x #4). Se permite el uso de otros conductores
normalizados de seccin superior, cuando la potencia necesaria en
la acometida o la cada de tensin en el conductor as lo exijan.
La conexin de la acometida a la lnea de BT se realizar mediante
conectores de derivacin adecuados a las secciones de los
conductores o mediante Cajas de Derivacin Subterrneas
aprobadas por GNF de acuerdo a los criterios de normalizacin
indicados la seccin 21 de este documento.
5.1.8.

Paso de Areo a Subterrneo MT

En el paso de areo a subterrneo MT, se utilizarn los siguientes


elementos: terminales, pararrayos autovlvulas y cortacircuitos
fusibles de expulsin o seccionadores.
Los fusibles de expulsin-seccionadores se utilizarn solamente en
el caso de derivaciones, nunca cuando la lnea subterrnea sea un
tramo de una lnea area que pasa a subterrnea para cruzar una
carretera, va de ferrocarril, o entrar en zonas urbanas.
En el paso de areo a subterrneo el cable deber ir protegido por
tubos de resistencia mecnica adecuada, hasta una altura de 3
metros sobre el suelo como mnimo.

36

5.1.9.

Dispositivos de Maniobra y Sistemas de Proteccin MT

5.1.9.1. Dispositivos de maniobra


Se utilizarn cortacircuitos fusibles de expulsin/seccionadores
accionables por prtiga con una intensidad nominal acorde con las
necesidades de la instalacin.

5.1.9.2. Sistemas de proteccin


Adems de las protecciones existentes en la cabecera de la lnea,
cuyas caractersticas y disposicin se recogern en el proyecto de la
subestacin suministradora, se dispondrn las protecciones contra
sobreintensidades y sobretensiones necesarias en las derivaciones
del final de la lnea area y paso a subterrneo.
a) Proteccin contra sobretensiones
La proteccin contra sobretensiones en Media Tensin se
realizar mediante la instalacin de pararrayos, segn la
correspondiente especificacin tcnica.
Se colocar un juego de pararrayos en la lnea area, en el
mismo herraje que los terminales del cable a proteger y segn
se indica en los planos correspondientes.
Si la lnea subterrnea enlazara dos lneas areas se colocar un
juego de pararrayos en cada uno de los extremos de la misma.
b) Proteccin contra sobreintensidades
En caso necesario, se instalarn cortacircuitos fusibles de
expulsin de acuerdo con la especificacin tcnica
correspondiente.

5.1.10. Empalmes y Terminales MT


En los puntos de unin de los distintos tramos de tendido se
utilizarn empalmes adecuados a las caractersticas de los
conductores a unir. Estos empalmes sern contrctiles en fro. Los
empalmes no debern disminuir en ningn caso las caractersticas
elctricas y mecnicas del cable empalmado debiendo cumplir las
siguientes condiciones:

37

La conductividad de los cables empalmados no puede ser


inferior a la de un slo conductor sin empalmes de la misma
longitud.

- El aislamiento del empalme ha de ser tan efectivo como el


aislamiento propio de los conductores.
- El empalme debe estar protegido para evitar el deterioro
mecnico y la entrada de humedad.
- El empalme debe resistir los esfuerzos electrodinmicos en caso
de cortocircuito, as como el efecto trmico de la corriente, tanto
en rgimen normal como en caso de sobrecargas y
cortocircuitos.
Los terminales de los conductores en su conexin al transformador
sern del tipo enchufables en carga o atornillables sin carga, y en el
paso de areo a subterrneo sern terminaciones contrctiles o
extensibles como estn completamente definidos
en la
especificacin tcnica correspondiente.

5.1.11. Puesta a Tierra


En las redes subterrneas de Media Tensin se conectarn a tierra
los siguientes elementos:

Bastidores de los elementos de maniobra y proteccin.


Apoyos de los pasos areo-subterrneos.
Autovlvulas o pararrayos.
Envolturas o pantallas metlicas de los cables.

Las envolturas o pantallas metlicas de los cables deben ser


convenientemente puestas a tierra en los extremos de dichos
cables, con objeto de disminuir su resistencia global a tierra.
Los elementos que constituyen el sistema de puesta a tierra son:

Lnea de tierra.
Electrodo de puesta a tierra.

a) Lnea de tierra
Est constituida por conductores de cobre. En funcin de la
corriente de defecto y la duracin del mismo, se determinan las
secciones mnimas del conductor a emplear por la lnea de tierra, a

38

efectos de no alcanzar su temperatura mxima. La seccin se


obtendr segn la expresin siguiente:

S Id

En donde:
S: Seccin del conductor (mm2).
Id: Corriente de defecto (A).
t: Tiempo de duracin de la falta (s).

: Para tiempos de duracin de la falta inferiores o iguales a 5 s y


conductores de cobre, = 13.
: 160 para conductor aislado y 180 para conductor desnudo.
Se tomar 16 kA como valor mximo de la intensidad de defecto
para niveles de tensin de 13,2 kV, y 12,5 kA para 24,9 y 34,5 kV. El
sistema de puesta a tierra es multiaterrado, por lo tanto se
considerar un tiempo mximo de duracin de la falta de 0,1 s
0,2s.
Con estos datos se obtienen los resultados que se muestran en la
Tabla 13 y la Tabla 14:

Tabla 13. Intensidades de defecto para conductor aislado

CONDUCTOR AISLADO

(C)

t (s)

Idefecto (kA)

Tensin (kV)

Seccin (mm2)

160

0,1

16

13,2

30,8

160

0,1

12,5

34,5

24

160

0,2

16

13,2

43,5

160

0,2

12,5

34,5

34

39

Tabla 14. Intensidades de defecto para conductor desnudo

CONDUCTOR DESNUDO

(C)

t (s)

Idefecto (kA)

Tensin (kV)

Seccin (mm2)

180

0,1

16

13,2

29,0

180

0,1

12,5

34,5

22,6

180

0,2

16

13,2

41,0

180

0,2

12,5

34,5

32

A la vista de los resultados mostrados en la tabla, la seccin del


conductor de tierra mnimo a utilizar dentro de las secciones
normalizadas para conductores aislados como para desnudos, ser
de seccin #2 AWG (33,62 mm2) de cobre, en caso de que la
duracin de la falta sea 0,1 s. Si la duracin de falta fuera de 0,2 s,
la seccin mnima a utilizar para 13,2 kV ser 1/0 AWG (53,51 mm2).
b) Electrodos de puesta a tierra
Estarn constituidos por picas de acero-cobre, cuyas caractersticas
se definen en la correspondiente Especificacin Tcnica.
5.2.

CARACTERSTICAS PARTICULARES DE CONDUCTORES


Cada proyecto especfico, diseado en base a la presente norma
deber aportar los siguientes documentos caractersticos del
mismo:

5.2.1.

Memoria

El formato de la Memoria del Proyecto Especfico se ajustar al


establecido por Gas Natural Fenosa. En ella se justificar la
finalidad de la instalacin, razonando su necesidad o conveniencia.
A continuacin se describir el trazado de la lnea, indicando los
lugares o localidades afectados.
Se pondrn de manifiesto las caractersticas particulares y la
descripcin de la instalacin indicando la siguiente informacin:

Longitud de la lnea.
Tensin nominal.
Frecuencia.

40

Tipos de conductores.
As mismo se adjuntarn una serie de tablas que mostrarn los
resultados de los clculos elctricos y clculos mecnicos,
indicando la siguiente informacin tcnica:

Longitud de la lnea.
Resistencia y reactancia por unidad de longitud.
Cadas de tensin.
Prdidas de potencia.
En los casos en los que sea necesario se incluir una relacin de
cruzamientos, paralelismos y dems situaciones con los datos
necesarios para su localizacin e identificacin del propietario,
entidad u organismo afectado.

5.2.2.

Planos

5.2.2.1. Plano de situacin y emplazamiento


El plano de situacin representar el trazado de la lnea en un
plano a escala 1:50 000 1:10 000, en donde sea perfectamente
identificable el emplazamiento de la lnea.
El trazado de las lneas se representar en un plano a escala de
1:2 000 1:500 segn las necesidades.
En caso necesario se podrn utilizar otras escalas similares a las
indicadas, que muestren con el detalle necesario las instalaciones,
en funcin de la cartografa disponible en el pas.

5.2.2.2. Otros planos


Cuando sea preceptivo se incluirn planos de los elementos
constructivos que sean necesarios (canalizaciones, arquetas,
puesta a tierra, etc.) Adems, siempre que se empleen
aplicaciones especiales que no estn reflejadas en este documento
y sea necesaria su definicin, se incluirn los correspondientes
planos descriptivos.

6 DETALLE DE CONDUCTORES DE MEDIA TENSIN


Las caractersticas de los conductores normalizados se muestran
en el apartado 5.1.1 del presente documento.

41

En este apartado se desarrollarn los clculos elctricos de la lnea


en funcin de los conductores empleados, de los niveles de tensin y
del nmero de fases de la lnea subterrnea
(trifsica o
monofsica).

6.1.

CLCULO ELCTRICO

6.1.1.

Resistencia del Conductor

La resistencia del conductor empleado, en ohmios por km,


depende de las caractersticas y seccin del mismo y de la
temperatura de trabajo de la lnea.
La temperatura mxima de trabajo prevista es de 90 C para el
conductor y 70 C para la pantalla. El valor de la resistencia en
corriente continua para un conductor cuya temperatura mxima de
trabajo es 90 C, se calcula a partir del valor a 20 C, mediante la
siguiente expresin:
R 90 R 20 1 90 20 (/km)
donde:
R: Resistencia del conductor con corriente continua a la
temperatura C (/km).

: Coeficiente de variacin de la resistividad en funcin de la


temperatura, siendo = 0,00403 para conductores de aluminio y
0,00393 para conductores de cobre (C-1) para una temperatura de
20 C.
En cuanto a la resistencia en corriente alterna, es necesario tener
en cuenta el efecto piel y el efecto proximidad que dan lugar a un
aumento de la resistencia aparente del conductor. El valor de la
resistencia en corriente alterna segn la norma CEI-287 ser:
R ca R cc 1 Ks Kp (/km)
siendo:
Rca: Resistencia del conductor en corriente alterna (/km).
Rcc: Resistencia del conductor en corriente continua (/km).

42

Ks: Coeficiente por efecto piel. Su valor se obtiene mediante la


expresin siguiente:
Ks

3,28 f 2 s 2
2

10 8

donde:
f: Frecuencia de la corriente (60 Hz).
s: Seccin efectiva del conductor (mm2).

: Resistividad del conductor a la temperatura considerada. Para


conductores de aluminio a 90C, = 36,237 (mm2/km), y para
conductores de cobre para 70 C de temperatura, = 20,6288
(mm2/km).
Kp: Coeficiente por efecto proximidad. Su valor se calcula
empleando la siguiente ecuacin:

Kp Ks 2,9 a2
donde:
Ks: Coeficiente por efecto piel.
a: Relacin entre el dimetro del conductor y la distancia entre los
ejes de los conductores ms prximos.

Sustituyendo los valores adecuados en las expresiones mostradas


se obtienen los resultados indicados en la Tabla 15.

43

Tabla 15. Resistencia de los conductores en lneas trifsicas

RESISTENCIA DE LOS CONDUCTORES EN LNEAS TRIFSICAS


Conductor
Rcc a 20 C (/km)
Rcc a 90 C (/km)
Coeficiente Ks
15 kV
Kp (*)
25 kV
35 kV
15 kV
Rca a 90 C 25 kV
(/km)
35 kV

4/0 AWG

500 MCM

750 MCM

0,2682
0,3439
10,2 10-4
5,9 10-4
4,4 10-4
3,4 10-4
0,3444
0,3444
0,3443

0,1135
0,1455
57,7 10-4
47,5 10-4
3,5 10-4
29,4 10-4
0,1470
0,1469
0,1468

0,0759
0,0973
124,710-4
114,510-4
0,0996
-

(*) Para el clculo de Kp y, en consecuencia para el clculo de Rca a 90C, se


considera que los conductores se han instalado en tringulo en contacto mutuo.

En el caso de lneas monofsicas, el conductor utilizado ser


exclusivamente el 1/0 AWG para los tres niveles de tensin. La
resistencia del cable estar limitada por la temperatura mxima
admisible de la pantalla (70 C). En la Tabla 16 se muestran los
resultados.

Tabla 16. Resistencia de los conductores en lneas monofsicas

RESISTENCIA DE
CONDUCTOR Y
PANTALLA EN LNEAS
MONOFSICAS
Rcc a 20 C (/km)
Rcc a 70 C (/km)
Coeficiente Ks
Rca a 70 C (/km)

1/0 AWG

PANTALLA

0,5378
0,6462
2,9 10-4
0,6464

0,5177
0,6194
23,0 10-4
0,6196

44

6.1.2.
6.1.2.1.

Reactancia del Conductor


Lnea trifsica equilibrada

La reactancia de una lnea trifsica, por unidad de longitud y por


fase, para lneas equilibradas, se determinar mediante la
siguiente expresin:
X 2 f (/km)
siendo:
f: Frecuencia de la red (60 Hz).
: Coeficiente de Induccin Mutua por unidad de longitud (H/km).
El coeficiente de induccin por unidad de longitud () vendr dado
por la expresin:

2 Dm 4

K 4,605 log
(H/km)
10
d

donde:
K: Constante que, para conductores masivos es igual a 0,5 y para
conductores cableados toma los valores mostrados en la Tabla 17.
Dm: Distancia media geomtrica entre conductores. Los
conductores se instalarn en tringulo, estando las tres fases en
contacto mutuo, por lo tanto, la distancia media geomtrica
coincide con el dimetro exterior del conductor (mm).
d: Dimetro del conductor (mm).
Sustituyendo para cada caso, obtenemos los valores que se indican
en la Tabla 18.
Tabla 17. Valores de K segn nmero de alambres

CONSTANTE EN FUNCIN DEL NMERO DE ALAMBRES


N de alambres
K

1
0,50

7
0,64

19
0,55

37
0,53

61 o ms
0,51

45

Tabla 18. Reactancias de lneas trifsicas equilibradas

REACTANCIA LNEA TRIFSICA EQUILIBRADA


Reactancia inductiva (/km)
15 kV
35 kV
0,1340
0,1546
0,1197
0,1378
0,1148
-

Conductores
4/0 AWG
500 MCM
750 MCM

6.1.2.2. Lnea monofsica


En el caso de lneas monofsicas, el conductor utilizado ser
exclusivamente el 1/0 AWG para los tres niveles de tensin.
En estas lneas la corriente por la pantalla no es despreciable, por
lo tanto se tendr en cuenta tanto la reactancia del conductor,
como la de la pantalla para su clculo.
La reactancia del conductor de una lnea monofsica, por unidad
de longitud, se determinar mediante la siguiente expresin:

X 2 f (/km)
siendo:
f: Frecuencia de la red (60 Hz).
: Coeficiente de Induccin Mutua por unidad de longitud (H/km).
El coeficiente de induccin por unidad de longitud () vendr dado
por la expresin:

2 10 Ln

2D
(H/km)
d e-1/ 4

donde:
D: Distancia entre el eje del conductor y la pantalla (mm).
d: Dimetro del conductor (mm).
Sustituyendo para cada caso, obtenemos los valores que se indican
en la Tabla 19.

46

Tabla 19. Reactancia de lnea monofsica

REACTANCIA LNEA MONOFSICA


Conductores
1/0 AWG

Reactancia inductiva (/km)


15 kV
35 kV
0,1344
0,1613

Anlogamente se calcula la reactancia de la pantalla. El coeficiente


de induccin en este caso viene dado por la siguiente expresin:

DMG

7
mtua
L 2 10 Ln
(H/km)
DMG

propia

donde:
DMGPROPIA: Distancia media geomtrica propia de la pantalla (mm).
DMGMUTUA: Distancia media geomtrica mutua, que coincide con el
dimetro de la pantalla (mm).
Sustituyendo para cada caso, obtenemos los valores que se indican
en la Tabla 20.

Tabla 20. Reactancia de pantalla de lnea monofsica

REACTANCIA LNEA MONOFSICA


Pantalla
1/0 AWG

Reactancia inductiva (/km)


15 kV
35 kV
0,0383
0,0383

47

6.1.3.

Capacitancia

La capacitancia de cada conductor respecto a la pantalla para


cables con un solo conductor depende de:
a) Las dimensiones del mismo (longitud, dimetro de los
conductores, incluyendo las eventuales capas semiconductoras y
dimetro debajo de la pantalla).
b) La permitividad o constante dielctrica del aislamiento.
Para el caso de los cables de campo radial, la capacidad se obtiene
aplicando la siguiente expresin ser:

0,0241
D
log
d

(F/km)

siendo:

: Constante dielctrica del aislamiento. Para el aislamiento de


polietileno reticulado (XLPE) se utilizar = 2,5
D: Dimetro del conductor sobre el aislante (mm).
d: Dimetro del conductor (incluyendo la capa semiconductora)
(mm).
En la Tabla 21 se muestran las capacidades para los distintos
conductores y sus niveles de tensin.
Tabla 21. Capacitancia de conductores

CONDUCTORES
1/0 AWG
4/0 AWG
500 MCM
750 MCM

CAPACITANCIA (F/km)
15 kV
35 kV
0,2047
0,1299
0,2662
0,1626
0,3775
0,2209
0,4492
-

48

6.1.4.

Prdidas Dielctricas

Las prdidas dielctricas de los conductores se calculan mediante


las expresiones:

W 2 f CU2 tg (W/km)
siendo:
W: Prdidas dielctricas en el aislante (W/km).
f: Frecuencia de la red (60 Hz).
C: Capacidad del cable (F/km).
U: Tensin entre fase y neutro en el caso de clculo de prdidas
monofsicas, y tensin fase-fase para el de prdidas trifsicas
(kV).
tg : ngulo de prdidas o factor dielctrico, que depende del
material del aislamiento. Para el polietileno reticulado (XLPE) este
valor es:
tg = 0,001
Los resultados de estos clculos se muestran en la Tabla 22.

Tabla 22. Prdidas dielctricas en aislamiento de conductores.

PRDIDAS DIELCTRICAS EN EL AISLANTE (W) (W/km)


Conductor
1/0 AWG
4/0 AWG
500 MCM
750 MCM

Trifsicas
13,2 kV
34,5 kV
17,48
72,98
24,80
99,10
29,50
-

Monofsicas
7,6 kV
19,9 kV
4,46
19,40
-

49

6.1.5.

Corriente de Carga Capacitiva

La denominada intensidad de carga (I0) es la corriente capacitiva


que circula por el cable debido a la capacidad existente entre el
conductor y la pantalla. La corriente de carga para una lnea
trifsica equilibrada, como para una lnea monofsica para la
tensin ms elevada de la red ser la que se indica en la siguiente
ecuacin:
Ic

Um

2 f C 10 3

(A/km)

en donde:
Ic: Intensidad de carga capacitiva (A).
f: Frecuencia de la red (60 Hz).
C = Capacidad del cable (F/km).
Um: Tensin ms elevada de la red entre fases para el caso de lnea
trifsica, y tensin ms elevada de la red entre fase y neutro para el
caso de lnea monofsica (kV).
Para los conductores seleccionados los valores obtenidos son los
mostrados la Tabla 23.

6.1.6.

Intensidad Mxima Admisible

El valor de la intensidad mxima admisible para las instalaciones


fijadas se ha determinado de acuerdo con la norma CEI-287, y
teniendo en cuenta que no se pueden superar temperaturas
superiores a 90 C en el aislante, y 70 C en la cubierta. Los
resultados son los que se recogen en la Tabla 24.

Tabla 23. Intensidad de carga capacitiva de conductores MT

INTENSIDAD DE CARGA CAPACITIVA, IC (A/km)


Conductor
1/0 AWG
4/0 AWG
500 MCM
750 MCM

Trifsicas
13,2 kV
34,5 kV
0,8030
1,2826
1,1388
1,7416
1,1349
-

Monofsicas
7,6 kV
19,9 kV
0,3564
0,5911
-

50

Tabla 24. Intensidad trifsica admisible en conductores MT

INTENSIDAD TRIFSICA MXIMA ADMISIBLE (A)


Sin corriente circulando por la pantalla

Tensin
Conductor
Al aire
(kV)
(40C)
4/0 AWG
500 MCM
750 MCM

13,2
34,5
13,2
34,5
13,2

291
297
485
497
625

Instalacin
Direct.
Enterrado bajo tubo
enterrado
Arena Hormign
(25C)
280
224
224
278
230
230
434
354
354
435
361
361
534
438
438

Circulando por la pantalla una corriente 20%In

Conductor

4/0 AWG
500 MCM
750 MCM

Tensin Al aire
(kV)
a
40C
13,2
34,5
13,2
34,5
13,2

278
286
465
478
587

Instalacin
Enterrado bajo
Direct.
tubo
enterrado a
25C

Arena

Hormign

267
266
414
416
500

214
220
337
345
409

214
220
337
345
409

INTENSIDAD MONOFSICA MXIMA ADMISIBLE (A)


Circulando por la pantalla una corriente 100%In

Conductor

1/0 AWG

Tensin
Al
(kV)
aire a
40 C
13,2
34,5

109
118

Instalacin
Enterrado bajo
Direct.
tubo
enterrado a
25 C

Arena

Hormign

107
110

99
103

99
103

La intensidad admisible del cable determinado para la instalacin


tipo, deber corregirse mediante unos coeficientes de correccin
teniendo en cuenta cada una de las caractersticas de la instalacin
real. A continuacin se exponen algunos casos particulares de
instalacin, cuyas caractersticas afectan al valor mximo de la

51

intensidad admisible, indicndose los coeficientes de correccin


que se deban aplicar.
6.1.6.1. Instalacin al aire
a)
Cables instalados al aire en ambientes de temperatura
distinta a 40 C
El coeficiente que se emplear para la correccin de las
intensidades mximas admisibles, cuando la temperatura ambiente
es diferente de 40 C, se calcula mediante la siguiente expresin:
CC

90 a
90 40

siendo:
CC: Coeficiente de correccin.

a: Temperatura ambiente en el lugar de instalacin (C).


En la Tabla 25 se muestran los coeficientes en funcin de la
temperatura ambiente de la instalacin.

b)

Cables instalados al aire en canales o galeras

En estas condiciones de instalacin, el calor disipado por los cables


no puede difundirse libremente y provoca un aumento de la
temperatura del aire. Para realizar los clculos supondremos que
el aumento de la temperatura ambiente, con los conductores
instalados y transportando energa, respecto a la temperatura
ambiente sin los conductores instalados es del orden de 15C. Para
la determinacin de la intensidad admisible en estas condiciones se
emplearn los coeficientes indicados en la tabla anterior.
Otro factor a tener en cuenta a la hora de calcular la intensidad
admisible en los cables, es la instalacin de otros conductores en
las proximidades. En funcin del tipo de instalacin se emplearn
los coeficientes mostrados en la Tabla 26 y Tabla 27.
Tabla 25. Coeficientes de correccin segn temperatura

COEF. DE CORRECCIN PARA INSTALACIN A T DISTINTA DE


40 C
T (C)
15
20
25
30
35
40
45
50
CC

1,22

1,18

1,14

1,10

1,05

1,00

0,95

0,89

52

Tabla 26. Coeficientes de correccin para cables sobre bandejas

COEFICIENTE DE CORRECCIN
CABLES INSTALADOS SOBRE BANDEJAS (*)
N de cables o ternas
N de bandejas
1
2
3
1
1
0,98
0,96
2
1
0,95
0,93
3
1
0,94
0,92
6
1
0,93
0,90

6
0,93
0,90
0,89
0,87

(*) Caractersticas de la instalacin:


- Ternas o cables tendidos sobre bandejas perforadas.
- Separacin entre cables igual al dimetro d de una terna o de un
cable (segn corresponda).
- Distancia a la pared 5 cm.
- Separacin vertical entre bandejas 30 cm.

d
30 cm

5cm

53

Tabla 27. Coeficientes de correccin para cables en estructura de pared.

COEFICIENTE DE CORRECCINTERNAS DE CABLES


INSTALADOS SOBRE ESTRUCTURAS SOBRE PARED (*)
N de cables o ternas
N de ternas
1
2
3
6
9
1
1
0,93
0,90
0,87
0,86
(*) Caractersticas de la instalacin:
- Separacin entre cables igual al dimetro d de una terna o de un
cable (segn corresponda).
- Distancia a la pared 5 cm.

d
d

6.1.6.2. Instalacin enterrada


a)

Cables enterrados en terrenos con temperatura distinta de 25


C.

El coeficiente que se emplear para la correccin de las


intensidades mximas admisibles, cuando la temperatura del
terreno es diferente de 25 C, se calcula mediante la siguiente
expresin:

54

CC

90 a
90 25

siendo:
CC: Coeficiente de correccin.

a: Temperatura ambiente en el lugar de instalacin (C).


Los coeficientes de correccin para temperatura del terreno
distinta a 25 C se muestran en la Tabla 28.
b)
Cables directamente enterrados o en conducciones
enterradas en terrenos de resistividad trmica distinta de 1
Km/W.
Las caractersticas del terreno constituyen un punto importante en
la intensidad admisible en los cables enterrados, si bien su valor es
difcil de determinar dada la falta de uniformidad del propio suelo a
lo largo de la canalizacin.
Por otra parte, para un terreno determinado se ve afectado por las
condiciones de humedad, nivel fretico, vegetacin, etc. La Tabla
29 recoge valores aproximados para algunas clases de terrenos y
la Tabla 30 muestra los coeficientes de correccin segn la
resistencia trmica del terreno.
c)

Cables enterrados en una zanja a diferentes profundidades, ver


Tabla 31.

d) Ternas o cables agrupados bajo tierra, ver Tabla 32.


Tabla 28. Coeficiente de correccin segn temperatura de terreno en MT

T (C)
Coeficiente

10
1,11

COEFICIENTE DE CORRECCIN
15
20
25
30
35
1,07

1,04

1,00

0,96

0,92

40

45

50

0,88

0,83

0,78

55

Tabla 29. Valores de K segn tipo de terreno en MT

Valores de k
(Km/W)
0,4 a 0,5
0,5 a 0,7
0,7 a 1
1,5
2 a 2,5
3

Tipo de terreno
Terreno vegetal muy hmedo
Arena hmeda
Calcreo y tierra vegetal seca
Tierra muy seca
Arena seca
Ceniza escoria

Tabla 30. Coeficientes de correccin segn resistividad trmica de terreno

COEFICIENTE DE CORRECCIN
Resistividad trmica del
0,8
1
1,2
1,5
terreno (Km/W)
Lnea trifsica
1,07
1,00
0,94
0,87
Lnea monofsica

1,09

1,00

0,93

0,85

2,0

2,5

0,78

0,71

0,75

0,68

Tabla 31. Coeficiente de correccin segn profundidad de instalacin

COEFICIENTE DE CORRECCIN
Profundidad de instalacin (cm)
60
80 100 120 150 200
Coeficiente
1,03
1
0,98 0,96 0,94 0,92

Tabla 32. Coeficiente de correccin segn nmero de cables

COEFICIENTES DE CORRECCIN
Nmero de cables o ternas
2
3
4
5
6
Factor de correccin

10

12

20 cm 0,85 0,78 0,72 0,68 0,66 0,6


d
0,85 0,75 0,68 0,64 0,60 0,56 0,53 0,50

56

e)
Cables enterrados en una zanja en el interior de tubos o
similares.
Siempre que la longitud de la instalacin bajo tubo no exceda de 15
m, no se considerar reduccin alguna respecto a la intensidad
admisible por el cable directamente enterrado.
Cuando la longitud bajo tubo supere los 15 m, se recomienda
aplicar el valor para instalaciones bajo tubo indicados en la Tabla
24.

f)
33.

Ternas o cables bajo tubo agrupados bajo tierra, ver Tabla

Tabla 33. Factor de correccin para cables MT bajo tubo agrupados bajo
tierra.

Nmero de cables o ternas


Factor de correccin

6.1.7.

2
3
4
5
6
0,87 0,77 0,72 0,68 0,65

Intensidades de Cortocircuito Admisibles en los Conductores.

Es la intensidad que no provoca ninguna disminucin de las


caractersticas de aislamiento de los conductores, incluso despus
de un nmero elevado de cortocircuitos. Se calcula admitiendo que
el calentamiento de los conductores se realiza en un sistema
adiabtico (a calor constante) y para una temperatura mxima
admitida por el aislamiento de 250C. La intensidad mxima de
cortocircuito para un conductor de seccin S, viene dada por:
Icc K S

1
t

(A)

donde:
Icc: Intensidad mxima de cortocircuito (A).
K: Coeficiente que depende de la naturaleza del conductor, del
aislamiento y de sus temperaturas al principio y al final del
cortocircuito. En este caso se toman como valores 143 para el
cobre y 93 para el aluminio.
S: Seccin del conductor (mm2).

57

t: Tiempo de duracin del cortocircuito (s).


En la Tabla 34, se obtienen las corrientes de cortocircuito para los
valores de las secciones. Se considera una intensidad de
cortocircuito de 16 KA en 13,2 KV y 12,5 KA en 24,9 y 34,5 KV y un
tiempo mnimo de despeje de las faltas de 0,3 s en caso de
interruptores, o de 0,1 s en caso de fusibles. En consecuencia el
cable 1/0 solo podr instalarse en derivaciones o racimos
protegidos con fusibles.
Tabla 34. Corriente de cortocircuito (kA)

Conduct.

Seccin
(mm2)

1/0 AWG
4/0 AWG
500 MCM
750 MCM

53,5
107,2
253,3
380

6.1.8.

0,1
15,7
31,5
74,4
111,8

0,2
11,1
22,2
52,6
79,0

Duracin del cortocircuito (s)


0,3
0,4
0,5
0,6
0,7
0,8
9,0
7,8
7,0
6,4
5,9
5,5
18,2 15,7 14,0 12,8 11,9 11,1
42,9 37,2 33,2 30,3 28,1 26,3
64,5 55,9 50,0 45,6 42,2 39,5

0,9
5,2
10,5
24,8
37,3

1,0
4,9
9,9
23,5
35,3

Intensidades de Cortocircuito Admisibles en las Pantallas.

Las intensidades admisibles en la pantalla de cobre de los


conductores seleccionados, en funcin del tiempo de duracin del
cortocircuito, es la indicada en la Tabla 35.
Estas intensidades se han tomado para una temperatura mxima
en la pantalla de 160 C, segn la Norma CEI-949.

Tabla 35. Intensidad de cortocircuito admisible en la pantalla de cobre (kA)

Cond.

Seccin
(mm2)

1/0 AWG
4/0 AWG
500 MCM
750 MCM

33,3
22,89
52,9
52,9

Duracin del cortocircuito (seg)


0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9
15,3 10,6 8,7 7,5 6,7 6,14 5,7 5,3 5,0
10,3 7,3 5,9 5,1 4,6 4,2 3,9 3,6 3,4
23,9 16,9 13,8 11,9 10,6 9,76 9,04 8,45 7,97
23,9 16,9 13,8 11,9 10,6 9,76 9,04 8,45 7,97

58

1,0
4,8
3,2
7,6
7,6

6.1.9.

Cada de Tensin

Los clculos sern aplicables a un tramo de lnea, siendo la cada


total de tensin la suma de las cadas en cada uno de los tramos
intermedios.
La cada de tensin por resistencia y reactancia de una lnea
trifsica viene dada por la formula:

U = 3 I (R cos + X sen) . L
Donde:

U = Cada de tensin compuesta (V).


I = Intensidad de la lnea (A).
R = Resistencia del conductor en /km para una temperatura de
90C.
X = Reactancia inductiva en /km.
L = Longitud de la lnea en km.
teniendo en cuenta que:

I=

P
3 U cos

donde:
P = Potencia trifsica transportada en kilovatios.
U = Tensin entre dos fases en kilovoltios.
La cada de tensin en tanto por ciento de la tensin compuesta
ser:
U % =P

L
( R + X tg )
10 U2

Sustituyendo los valores conocidos U, R y X tendremos la Tabla 36.

59

Tabla 36. Cada de tensin trifsica


TENSION

SECCION

(kV)

(mm2)

13,2

cos = 0,8

cos = 0,9

cos = 1

107,2

25,5310-5PL 23,4610-5PL 19,7710-5PL

253,3

13,5910-5PL 11,7410-5PL 8,4410-5PL


10,6610-5PL 8,8810-5PL

5,7210-5PL

107,2

3,8710-5PL

3,5210-5PL

2,8910-5PL

253,3

2,110-5PL

1,7910-5PL

1,2310-5PL

380
34,5

CAIDA DE TENSION TRIFSICA (U%)

Para el caso de una lnea monofsica, los clculos sern anlogos,


obtenindose la siguiente expresin:
U % = 2 P

L
( R + X tg )
10 U2

Siendo:
P = Potencia monofsica transportada en kilovatios.
U = Tensin fase-neutro en kilovoltios.
R = Resistencia del conductor en /km.
X = Reactancia inductiva en /km.
L = Longitud de la lnea en km.

Sustituyendo los valores conocidos U, R y X tendremos la Tabla 37.

Tabla 37. Cada de tensin monofsica

CAIDA DE TENSION MONOFSICA (U%)

TENSION

SECCION

(KV)

(MM2)

7,62

53,5

276,310-5PL 262,310-5PL 237,610-5PL

14,38

53,5

78,410-5PL

74,210-5PL

66,710-5PL

19,9

53,5

41,410-5PL

39,010-5PL

34,810-5PL

cos = 0,8

Cos = 0,9

cos = 1

60

6.1.10. Potencia a Transportar

La potencia que puede transportar la lnea trifsica equilibrada nos


viene limitada por la intensidad mxima determinada
anteriormente.
Por lo tanto, la potencia mxima ser:

Pmax = 3 U Imax cos


Donde:
Pmx = Potencia mxima de transporte (kW).
U = Tensin fase-fase en kV.
I = Intensidad mxima en A.
cos = Factor de potencia.
En la Tabla 38 aparecen los valores de potencia mxima para
circuitos trifsicos, limitada nicamente por la intensidad mxima
admisible del conductor, para distintos niveles de tensin y para
factores de potencia de 0,8, 0,9 y 1.

61

Tabla 38. Potencia trifsica a transportar

POTENCIA TRIFSICA MXIMA A TRANSPORTAR (kW)


Sin corriente circulando por la pantalla
Conductor
4/0 AWG
500 MCM
750 MCM

Instalacin al aire

Tensin
(kV)

cos = 0,8

cos = 0,9

Cos = 1

13,2
34,5
13,2
34,5
13,2

5 322
14 198
8 871
23 758
11 431

5 988
15 972
9 979
26 728
12 860

6 653
17 747
11 088
29 698
14 289

Sin corriente circulando por la pantalla


Conductor
4/0 AWG
500 MCM
750 MCM

Instalacin directamente enterrado

Tensin
(kV)

cos = 0,8

cos = 0,9

Cos = 1

13,2
34,5
13,2
34,5
13,2

5 121
13 289
7 938
20 794
9 767

5 761
14 950
8 930
23 394
10 988

6 401
16 612
9 922
25 993
12 208

Sin corriente circulando por la pantalla


Conductor
4/0 AWG
500 MCM
750 MCM

Instalacin enterrado bajo tubo

Tensin
(kV)

cos = 0,8

cos = 0,9

Cos = 1

13,2
34,5
13,2
34,5
13,2

4 097
10 995
6 475
17 257
8 011

4 609
12 369
7 284
19 414
9 013

5 121
13 743
8 093
21 571
10 014

Sin corriente circulando por la pantalla


Tensin
Conductor
(kV)
4/0 AWG
500 MCM
750 MCM

13,2
34,5
13,2
34,5
13,2

Instalacin enterrado bajo tubo


hormigonado
cos = 0,8

cos = 0,9

Cos = 1

4 097
10 995
6 475
17 257
8 011

4 609
12 369
7 284
19 414
9 013

5 121
13 743
8 093
21 571
10 014

Anlogamente para el caso de lneas monofsicas, la potencia


mxima ser:

62

Pmax = U Imax cos


donde:
Pmx = Potencia mxima de transporte (kW).
U = Tensin fase-neutro en kV.
I = Intensidad mxima en A.
cos = Factor de potencia.
En la Tabla 39 aparecen los valores de potencia mxima para
circuitos monofsicos, limitada nicamente por la intensidad
mxima admisible del conductor, para distintos niveles de tensin y
para factores de potencia de 0,8, 0,9 y 1.
Tabla 39. Potencia monofsica mxima a transportar

POTENCIA MONOFSICA MXIMA A TRANSPORTAR (kW)


Sin corriente circulando por la pantalla
Instalacin al aire
Tensin
Conductor
(kV)
cos = 0,8
cos = 0,9
Cos = 1
7,62
1 164
1 310
1 455
19,9
3 120
3 510
3 900
OTENCIA MONOFSICA MXIMA A TRANSPORTAR (kW)
Sin corriente circulando por la pantalla
Instalacin directamente enterrado
Tensin
Conductor
(kV)
Cos = 0,8
cos = 0,9
cos = 1
1/0 AWG

7,62
1 170
1 317
1 463
19,9
3 025
3 403
3 781
Potencia monofsica mxima a transportar (kw)
Sin corriente circulando por la pantalla
Instalacin enterrado bajo tubo
Tensin
Conductor
(kV)
cos = 0,8
cos = 0,9
cos = 1
1/0 AWG

7,62
933
1 049
1 166
19,9
2 499
2 812
3 124
POTENCIA MONOFSICA MXIMA A TRANSPORTAR (kW)
Sin corriente circulando por la pantalla
Instalacin enterrado bajo tubo
Tensin
hormigonado
Conductor
(kV)
1/0 AWG

1/0 AWG

7,62
19,9

cos = 0,8

cos = 0,9

Cos = 1

933
2 499

1 049
2 812

1 166
3 124

63

6.1.11. Prdidas de Potencia


La frmula a aplicar para calcular la prdida de potencia para
lneas trifsicas equilibradas es la siguiente:

P = 3 R LI2
siendo:

P = Prdidas de potencia (W).


R = Resistencia del conductor en /km.
L = Longitud de la lnea en km.
I = Intensidad de la lnea (A).
Teniendo en cuenta que:

3 U cos
siendo:
P= Potencia (KW).
U = Tensin compuesta (KV).
Cos = Factor de potencia.
Se llega a la conclusin de que la prdida de potencia en tanto por
ciento ser:
P % = P L

R
10 U cos 2
2

Sustituyendo los valores conocidos de R y U tenemos la Tabla 40.

64

Tabla 40. Prdidas trifsicas de potencia

Conductor

4/0 AWG

500 MCM
750 MCM

PRDIDAS TRIFSICAS DE POTENCIA EN %


Factor de Potencia
Tensin
(kV)
13,2
24,9
34,5
13,2
24,9
34,5
13,2

Cos = 0,8
-5

30,910 PL
8,710-5PL
4,510-5PL
13.210-5PL
3,710-5PL
1,910-5PL
8,910-5PL

cos = 0,9
-5

24,510 PL
6,8610-5PL
3.610-5PL
10,410-5PL
2,910-5PL
1,510-5PL
7,110-5PL

cos = 1

19,810-5PL
5,610-5PL
2,910-5PL
8,410-5PL
2,410-5PL
1,210-5PL
5,710-5PL

Para el caso de lneas monofsicas, se obtiene de forma anloga


la expresin:
P % = 2 P L

R
10 U2 cos 2

siendo:

P = Prdidas de potencia (%).


R = Resistencia del conductor en /km.
L = Longitud de la lnea en km.
P= Potencia monofsica (KW).
U = Tensin fase-neutro (KV).
Cos = Factor de potencia.

Sustituyendo los valores conocidos de R y U tenemos Tabla 41.


Tabla 41. Prdidas monofsicas de potencia

PRDIDAS MONOFSICAS DE POTENCIA EN %


Factor de Potencia
Tensin
Conductor
(kV)
cos = 0,8
cos = 0,9
cos = 1
1/0 AWG

7,62
14,38
19,9

371,110-5PL 293,210-5PL 237,510-5PL


104,310-5PL 82,410-5PL 66,710-5PL
54,310-5PL 42,310-5PL 34,710-5PL

65

7 DETALLE DE CONDUCTORES DE BAJA TENSIN

7.1.

CLCULO ELCTRICO
En el presente captulo se indican los clculos elctricos a
realizar en cualquier Proyecto Especfico realizado segn las
presentes NORMAS TCNICAS.

7.1.1.

Resistencia

El valor de la resistencia por unidad de longitud, para corriente


continua y a la temperatura (), vendr dado por la siguiente
expresin:
R R20 1 20 20

(/km)

donde:
R: Resistencia del conductor con corriente continua a la
temperatura C (/km).
R20: Resistencia del conductor con corriente continua a la
temperatura de 20 C (/km).

20: Coeficiente de variacin de la resistividad a 20 C en funcin


de la temperatura. Esta variable adopta un valor de 0,00393 para
el cobre suave y 0,00403 para el aluminio (C-1).
: Temperatura de servicio del conductor (C).
Si los conductores van agrupados, es necesario tener en cuenta
adems, el efecto piel y el efecto proximidad que dan lugar a un
aumento de la resistencia aparente del conductor. El valor de la
resistencia en corriente alterna segn la norma CEI-287 ser:
R ca R cc 1 Ks Kp (/km)
siendo:
Rca: Resistencia del conductor en corriente alterna (/km).
Rcc: Resistencia del conductor en corriente continua (/km).
Ks: Coeficiente por efecto piel. Su valor se obtiene mediante la
expresin siguiente:

66

3,28 f 2 s 2

Ks

10 8

donde:
f: Frecuencia de la corriente (60 Hz).
s: Seccin efectiva del conductor (mm2).

: Resistividad del conductor a la temperatura considerada. Para


conductores de aluminio a 90C, = 36,237 (mm2/km), y para
conductores de cobre para 70 C de temperatura, = 20,6288
(mm2/km).
Kp: Coeficiente por efecto proximidad. Su valor se calcula
empleando la siguiente ecuacin:

Kp Ks 2,9 a2
donde:
Ks: Coeficiente por efecto piel.
a: Relacin entre el dimetro del conductor y la distancia entre los
ejes de los conductores ms prximos.
Sustituyendo valores en las expresiones mostradas se obtienen los
resultados indicados en la Tabla 42.
Tabla 42. Resistencia por conductor en BT

Resistencia por conductor


Conductor

500
MCM

4/0
AWG

1/0
AWG

4 # 4 3 # 4 3 # 6
AWG
AWG
AWG

Rcc a 20 C
0,1135 0,2682 0,5378 0,840
(/Km)
Rcc a 90 C
0,1455 0,3438 0,6895 1,071
(/Km)
Coeficiente Ks 0,00961 0,00103 0,00026 0
Coeficiente Kp 0,01600 0,00157 0,00031 0
Rca a 90 C
0,1492 0,3447 0,6899 1,071
(/Km)

0,840

1,337

1,071

1,704

0
0

0
0

1,071

1,704

* Para el clculo de Kp y, en consecuencia para el clculo de Rca a 90 C, se


considera que los conductores se han instalado en tringulo en contacto mutuo.

67

Tanto en los conductores concntricos de cobre como en los


conductores de aluminio, se toma la resistencia del neutro igual a
la de las fases.
Para los clculos del presente Documento despreciamos el efecto
pelicular en el caso de los conductores concntricos, y por lo
tanto, suponemos equivalentes los valores de resistencia del
conductor con corriente continua y con corriente alterna.
7.1.2.

Reactancia Inductiva

La reactancia kilomtrica de una lnea trifsica equilibrada se


calcula segn la expresin:
X = 2 fL /km

y sustituyendo en ella el coeficiente de induccin mutua L por su


valor:
2
L = (K + 4,605 log Dm ) 10-4 H /km
d
Se llega a:
X = 2 f (K + 4,605 log

2 Dm
) 10-4 /km
d

donde:
X=

Reactancia, en ohmios por km.

f=

Frecuencia de la red en hertzios.

Dm= Separacin media geomtrica entre conductores en


mm. Los conductores se instalarn en tringulo, estando las tres
fases en contacto mutuo, por lo tanto, la distancia media
geomtrica coincide con el dimetro exterior del conductor
d=

Dimetro del conductor en mm.

K=
Constante que, para conductores slidos es igual a
0,5 y para conductores cableados toma los valores de la Tabla 43.
Sustituyendo para cada caso, obtenemos los valores que se indican
en la Tabla 44.

68

Tabla 43. Valor de K segn N de alambres en BT

N de alambres

19

37

61

Slido

0,78

0,64

0,55

0,53

0,51

0,5

Tabla 44. Reactancia por conductor para lneas de BT

Conductor
500 MCM
4/0 AWG
1/0 AWG
4 # 4 AWG
3 # 4 AWG
3 # 6 AWG

Reactancia conductor para lnea trifsica


(/km)
0,093
0,097
0,105
0,1*
0,1*
0,1*

* En el caso de los conductores concntricos se adopta el valor de X = 0,1 /Km,


que se puede introducir en los clculos sin error apreciable, debido a que en stos
el valor real de la reactancia ser incluso menor.

7.1.3.

Intensidad Mxima Admisible

El valor de la intensidad que puede circular en rgimen


permanente, sin provocar un calentamiento exagerado del
conductor, depende de la seccin y de la temperatura del terreno y
resistividad trmica del terreno.
En la Tabla 45 se indica las intensidades mximas permanentes
admisibles en los diferentes tipos de cables, para una temperatura
mxima del conductor de 90 C y una temperatura ambiente de 30
C en un terreno de resistividad trmica igual a 1 Km/W:

Tabla 45. Intensidad mxima admisible de conductores en BT

INTENSIDAD MXIMA ADMISIBLE (A)


Conductor
500 MCM
4/0 AWG
1/0 AWG
# 4 AWG
# 6 AWG

DIRECT. ENTERRADO

AL AIRE

350
205
135
75
60

545
315
205
110
80

69

La intensidad admisible del cable determinado para la instalacin


tipo, deber corregirse mediante unos coeficientes de correccin
teniendo en cuenta cada una de las caractersticas de la
instalacin real. A continuacin se exponen algunos casos
particulares de instalacin, cuyas caractersticas afectan al valor
mximo de la intensidad admisible, indicndose los coeficientes de
correccin que se deban aplicar.

7.1.3.1. Instalacin enterrada


a) Cables enterrados en terrenos con temperatura distinta de 30
C.
El coeficiente que se emplear para la correccin de las
intensidades mximas admisibles, cuando la temperatura del
terreno es diferente de 30 C, se calcula mediante la siguiente
expresin:
CC

90 a
90 30

siendo:
CC: Coeficiente de correccin.

a: Temperatura ambiente en el lugar de instalacin (C).


Los resultados de estos clculos se muestran en la Tabla 46.

Tabla 46. Coeficiente de correccin para temperatura del terreno distinta a 30


C para BT

Coeficiente de correccin en funcin de la temperatura del terreno


Temperatura (C)
Coef. de correccin

25
30
35
40
45
50
55
60
1,04 1,00 0,96 0,91 0,87 0,82 0,76 0,71

b) Cables directamente enterrados o en conducciones enterradas


en terrenos de resistividad trmica distinta de 1 Km/W.
Las caractersticas del terreno constituyen un punto importante en
la intensidad admisible en los cables enterrados, si bien su valor es
difcil de determinar dada la falta de uniformidad del propio suelo a
lo largo de la canalizacin.

70

Por otra parte, para un terreno determinado se ve afectado por las


condiciones de humedad, nivel fretico, vegetacin, etc. La Tabla 47
recoge valores aproximados para algunas clases de terrenos y la
Tabla 48 muestra valores de coeficiente de correccin segn
resistividad trmica de terreno.
Tabla 47. Valores de K segn tipo de terreno en BT

Valores de k
(Km/W)
0,4 a 0,5
0,5 a 0,7
0,7 a 1
1,5
2 a 2,5
3

Tipo de terreno
Terreno vegetal muy hmedo
Arena hmeda
Calcreo y tierra vegetal seca
Tierra muy seca
Arena seca
Ceniza escoria

Tabla 48. Coeficientes de correccin para cables de BT segn resistividad


trmica de terreno

Coeficiente de correccin en funcin de la resistividad del terreno


Resistividad
trmica del terreno
(Km/W)
Lnea trifsica
Lnea monofsica
c)

0,8

1,2

1,5

2.5

1,07
1,09

1,00
1,00

0,94
0,93

0,87
0,85

0,78
0,75

0,71
0,68

Cables enterrados en una zanja a diferentes profundidades, ver


Tabla 49.

Tabla 49. Coeficiente de correccin segn profundidad de conductores de BT

Coeficiente de correccin en funcin de la profundidad


Profundidad de
instalacin (cm)
Coef. de correccin

60

80

100

120

150

200

1,03

0,98

0,96

0,94

0,92

71

d)

Ternas o cables agrupados bajo tierra, Tabla 50.

Tabla 50. Coeficiente de correccin segn nmero de cables en BT

Coeficiente de correccin en funcin del nmero de cables o ternas


Nmero de ternas
Coef. de
correccin

20 cm 0,85 0,78 0,72 0,68 0,66


d

10

12

0,6

0,85 0,75 0,68 0,64 0,60 0,56 0,53 0,50

d
e)
Cables enterrados en una zanja en el interior de tubos o
similares.
Para cables enterrados en una zanja en el interior de tubos o
similares no se aplicar coeficiente de correccin si la longitud de
la instalacin tubular no excede de 15 m.
Cuando la longitud del tubo supere los 15 m, se recomienda
aplicar un coeficiente reductor del 0,8 considerando todos los
cables de la lnea instalados en el interior de un mismo tubo.
f)

Ternas o cables bajo tubo agrupados bajo tierra.

Tabla 51. Coeficientes de correccin de cables BT bajo tubos bajo tierra

Nmero de cables o ternas


Coef. de correccin

2
0,87

3
0,77

4
0,72

5
0,68

6
0,65

72

7.1.3.2. Instalacin al aire

a) Cables instalados al aire en ambientes de temperatura distinta a


30 C
El coeficiente que se emplear para la correccin de las
intensidades mximas admisibles, cuando la temperatura
ambiente es diferente de 30 C, se calcula mediante la siguiente
expresin:
CC

90 a
90 30

siendo:
CC: Coeficiente de correccin.

a: Temperatura ambiente en el lugar de instalacin (C).


En la Tabla 52 se muestran los coeficientes en funcin de la
temperatura ambiente de la instalacin.
Tabla 52. Coeficientes de correccin segn temperatura ambiente.

Coeficiente de correccin en funcin de la temperatura


Temperatura (C)
Coef. de correccin

25
30
35
40
45
50
55
60
1,04 1,00 0,96 0,91 0,87 0,82 0,76 0,71

b) Cables instalados al aire en canales o galeras


En estas condiciones de instalacin, el calor disipado por los
cables no puede difundirse libremente y provoca un aumento de
la temperatura del aire. Para realizar los clculos supondremos
que el aumento de la temperatura ambiente, con los
conductores instalados y transportando energa, respecto a la
temperatura ambiente sin los conductores instalados es del
orden de 15C. Para la determinacin de la intensidad admisible
en estas condiciones se emplearn los coeficientes indicados en
la tabla anterior.
Otro factor a tener en cuenta a la hora de calcular la intensidad
admisible en los cables, es la instalacin de otros conductores
en las proximidades. En funcin del tipo de instalacin se
emplearn los coeficientes mostrados en las siguientes tablas.

73

Tabla 53. Coeficiente de correccin en funcin del nmero de cables BT,


ternas y bandejas

Coeficiente de correccin en funcin del nmero de cables, ternas y


bandejas
Nmero de cables o ternas
Nmero de
bandejas
1
2
3
6
1
1
0,98
0,96
0,93
2
1
0,95
0,93
0,90
3
1
0,94
0,92
0,89
6
1
0,93
0,90
0,87
(*) Caractersticas de la instalacin:
- Ternas o cables tendidos sobre bandejas perforadas.
- Separacin entre cables igual al dimetro d de una terna o de un cable (segn
corresponda).
- Distancia a la pared 5 cm.
- Separacin vertical entre bandejas 30 cm.

7.1.4.

Cada de tensin

Dadas las caractersticas particulares de distribucin ser


necesario tener en cuenta la cada de tensin que se produce en la
lnea, debido a la propia resistencia de los conductores.
Los clculos sern aplicables a un tramo de lnea, siendo la cada
total de tensin la suma de las cadas en cada uno de los tramos
intermedios.
La aplicacin de este mtodo permite llegar a resultados
aproximados muy tiles cuando se quieren tantear diferentes
soluciones con distintas configuraciones de lnea. Se supone que la
carga est concentrada en el punto final de cada tramo de lnea.
Podemos expresar la cada de tensin en un tramo de lnea
trifsica equilibrada como:

Ui

Ri X i tg i P L
i

Ui

(V)

La cada de tensin relativa, en tanto por ciento, se obtiene


mediante la siguiente expresin:

e i (%) 100

R i X i tg i P L
Ui

74

siendo:

Ui: Cada de tensin compuesta del tramo i (V).


ei: Cada de tensin relativa del tramo i (%).
Ri: Resistencia del tramo i de conductor (/km).
Xi: Reactancia del tramo i de conductor (/km).

i: Desfase entre tensin e intensidad en el tramo i.


Ui: Tensin compuesta del tramo i (V).
Pi: Potencia consumida por la carga i alimentada por el tramo i de
lnea (kW)
Li: Longitud del tramo de lnea (km).
Al producto Mi= PiLi se le denomina momento elctrico de la carga
Pi, situada a la distancia Li del origen de la energa.
Para una lnea monofsica la cada de tensin se obtendr
mediante la siguiente expresin:

(2

Ri X i tg i P L )
i

Ui

(V)

Y la cada de tensin relativa en tanto por ciento:

e(%) 1 (200

Ri X i tg i P L )
Ui

donde:
U: Cada de tensin compuesta de la lnea(V).
e: Cada de tensin relativa de la lnea (%).
Ri: Resistencia del tramo i de conductor (/km).
Xi: Reactancia del tramo i de conductor (/km).

i: Desfase entre tensin e intensidad del tramo i.

75

Ui: Tensin compuesta del tramo i (V).


Pi: Potencia consumida por la carga i alimentada por el tramo i de
lnea (kW).
Li: Longitud del tramo de lnea (m).
En el caso de las lneas monofsicas bitensin (120/240 V) a tres
hilos se considerar la carga equilibrada y, por lo tanto,
equivalente a una lnea monofsica a 240 V.
En Tabla 54 se muestran los valores de cada de tensin para los
diferentes conductores y tensiones, en funcin de la potencia
consumida por las cargas y de la longitud del tramo de lnea.
Tabla 54. Cadas de tensin para conductores de BT

Conductor
4/0 AWG
1/0 AWG
3# 4 AWG
3# 6 AWG

500 MCM
4/0 AWG
1/0 AWG
4# 4 AWG

Cada de tensin (e%) (*)


Tensin
cos = 0,8
Cos = 0,9
Circuito monofsico
240 V
1,45 PiLi
1,36 PiLi
240 V
2,67 PiLi
2,57 PiLi
240 V
3,98 PiLi
3,89 PiLi
240 V
6,17 PiLi
6,10 PiLi
Circuito trifsico
208 V
0,51 PiLi
0,45 PiLi
240 V
0,38 PiLi
0,34 PiLi
208 V
0,97 PiLi
0,91 PiLi
240 V
0,72PiLi
0,68 PiLi
208 V
1,77 PiLi
1,71 PiLi
240 V
1,33 PiLi
1,28 PiLi
208 V
2,64 PiLi
2,59 PiLi
240 V
1,99 PiLi
1,94 PiLi

cos = 1
1,20 PiLi
2,39 PiLi
3,72 PiLi
5,92 PiLi
0,34 PiLi
0,26 PiLi
0,80 PiLi
0,60 PiLi
1,59 PiLi
1,19 PiLi
2,48 PiLi
1,86 PiLi

(*) Los valores de la impedancia de la lnea (Z) utilizados en la realizacin de


estas tablas se han calculado utilizando el valor de la resistencia del conductor a
90C.

En la seccin 10.1 del presente documento se muestra


grficamente la cada de tensin mxima para un nmero dado de
cargas iguales y equidistantes en funcin de la potencia y la
distancia entre ellas.
El clculo de la cada de tensin en las redes de baja tensin se
puede realizar mediante el programa de clculo desarrollado para
tal fin. Los valores obtenidos mediante este programa tienen en
cuenta la topologa de la red, la tensin de la lnea, el tipo de

76

conductor, el nmero de clientes, longitud de lnea, etc., todo para


cada uno de los tramos.
Mediante el empleo de este programa se simplifica la seleccin
del conductor ms adecuado para cada uno de los tramos que
componen la red, conociendo en cada caso una aproximacin de
la cada de tensin, total y por tramo.
7.1.5.

Potencia a Transportar

La potencia mxima que puede transportar la lnea vendr limitada


por la intensidad mxima admisible del conductor, mostrada en el
apartado 7.1.3, y por la cada de tensin mxima que se ha fijado
en los Criterios de Arquitectura de la Red de Gas Natural Fenosa.
La mxima potencia de transporte de un circuito de una lnea
trifsica equilibrada, limitada por la intensidad mxima admisible,
se determinar mediante la siguiente expresin:
Pmax

3 U Imax cos m
1000

(kW)

siendo:
Pmax: Potencia mxima que puede transportar la lnea (kW).
U: Tensin nominal compuesta de la lnea (V).
Imax: Intensidad mxima admisible del conductor (A).
cos m Factor de potencia medio de las cargas receptoras.
En el caso de una lnea monofsica, la expresin que se utiliza
para calcular la mxima potencia de transporte es la siguiente:
Pmax

U Imax cos m
1000

(kW)

siendo:
Pmax: Potencia mxima que puede transportar la lnea (kW).
U: Tensin nominal de la lnea (V).
Imax: Intensidad mxima admisible del conductor (A).

77

cos m Factor de potencia medio de las cargas receptoras.


Hay que tener en cuenta que el punto crtico de la lnea es el tramo
situado antes de la primera carga, ya que despus de sta, la
intensidad que circular por la lnea ser siempre menor. En el
caso de ramificaciones suceder lo mismo, el punto ms crtico
estar al inicio de la ramificacin.
En la Tabla 55 y Tabla 56 la aparecen los valores de potencia
mxima para circuitos monofsicos y trifsicos, limitada
nicamente por la intensidad mxima admisible del conductor,
para los distintos niveles de tensin y para factores de potencia de
0,8, 0,9 y 1.
Tabla 55. Potencia mxima limitada por intensidad mxima para cables de BT
directamente enterrados.

Potencia mxima limitada por intensidad mxima (kW)


Cables directamente enterrados
Conductor
Tensin
cos = 0,8 cos = 0,9
cos = 1
Circuito monofsico
4/0 AWG
240 V
39,36
44,28
49,20
1/0 AWG
240 V
25,92
29,16
32,40
3 # 4 AWG
240 V
14,4
16,2
18
240 V
11,52
12,96
14,4
3 # 6 AWG
Circuito trifsico
208 V
100,87
113,48
126,09
500 MCM
240 V
116,39
130,94
145,49
208 V
59,08
66,47
73,85
4/0 AWG
240 V
68,17
76,70
85,22
208 V
38,91
43,77
48,64
1/0 AWG
240 V
44,89
50,51
56,12
208 V
21,62
24,31
27
4 # 4 AWG
240 V
24,94
28,05
31,17

78

Tabla 56. Potencia mxima limitada por intensidad mxima para cables de
BT al aire.

Potencia mxima limitada por intensidad mxima (kW)


Cables al aire
Conductor
Tensin
cos = 0,8 cos = 0,9
cos = 1
Circuito monofsico
4/0 AWG
240 V
60,48
68,04
75,60
1/0 AWG
240 V
39,36
44,28
49,20
3 # 4 AWG
240 V
21,12
23,76
26,4
240 V
15,36
17,28
19,2
3 # 6 AWG
Circuito trifsico
208 V
157,08
176,71
196,35
500 MCM
240 V
181,24
203,90
226,55
208 V
90,79
102,14
113,48
4/0 AWG
240 V
104,75
117,85
130,94
208 V
59,08
66,47
73,85
1/0 AWG
240 V
68,17
76,70
85,22
208 V
31,70
35,66
39,63
4 # 4 AWG
240 V
36,58
41,15
45,73

7.1.6.

Prdidas de Potencia

Las prdidas de potencia en una lnea sern las debidas al efecto


Joule causado por la resistencia de los tramos de lnea que la
componen. Para una lnea trifsica o monofsica vendrn dadas,
respectivamente, por las siguientes expresiones:
n

p 3 Ri Li I i

(W)

(W)

p 2 Ri Li I i
1

donde:
p: Prdidas de potencia de la lnea (W).
Ri: Resistencia por kilmetro del tramo i de la lnea (/km).
Li: Longitud del tramo i de la lnea (km).
Ii: Intensidad del tramo i de la lnea (A).

79

El porcentaje de potencia perdida depende de la potencia


transportada por la lnea, que para el caso de una lnea trifsica se
calcula mediante la siguiente frmula:
n

P 3 U i I i cos i (W)
1

Mientras que para una lnea monofsica la expresin se muestra


a continuacin:
n

P U i I i cos i (W)
1

siendo:
P: Potencia transportada por la lnea (W).
Ui: Tensin compuesta de la lnea (V).
Ii: Intensidad de la lnea (A).
cos i: Factor de potencia de la lnea.
El porcentaje de potencia perdida en la lnea vendr dado por el
cociente entre la potencia perdida y la potencia transportada. De
esta manera, para lneas trifsicas se obtiene la siguiente
expresin:
n

P(%)
1

n
pi
100 100
P
1

3 Ri Li I i2
n

(%)

I i cos

Si se suponen cargas iguales y equidistantes, se sustituye el


valor de la intensidad y se ajustan las unidades se deduce la
expresin final:
P (%) 100

PRL
U 2 cos 2

(%)

siendo:
P: Potencia consumida (W).
R: Resistencia de la lnea por kilmetro (/km).

80

L: Longitud de la lnea (m).


U: Tensin compuesta de lnea (V).
cos : Factor de potencia de la lnea.
De forma anloga, para el caso de una lnea monofsica
obtenemos los siguientes resultados:
P (%) 200

PRL
U 2 cos 2

(%)

En la Tabla 57 se muestran los porcentajes de prdida de potencia


en funcin de la potencia y de la distancia, para las dos tensiones
objeto de este proyecto y para varios valores del factor de potencia.
Tabla 57. Prdidas de potencia en %

Porcentaje de potencia prdida


Conductor Tensin cos = 0,8
cos = 0,9
Circuito monofsico
4/0 AWG
240 V
1,8710-3PL
1,4710-3PL
1/0 AWG
240 V
3,7410-3PL
2,9610-3PL
-3
3# 4 AWG 240 V
5,8110 PL
4,5910-3PL
-3
3# 6 AWG 240 V
9,2610 PL
7,3010-3PL
Circuito trifsico
208 V
5,3810-4PL
4,2510-4PL
500 MCM
240 V
4,0410-4PL
3,1910-4PL
-3
208 V
1,2410 PL
9,8310-4PL
4/0 AWG
-4
240 V
9,3510 PL
7,3810-4PL
208 V
2,4910-3PL
1,9610-3PL
1/0 AWG
-3
240 V
1,8710 PL
1,4710-3PL
208
3,8610-3PL
3,0610-3PL
4 # 4 AWG
-3
240
2,9110 PL
2,2910-3PL

cos = 1
1,1610-3PL
2,3910-3PL
3,7210-3PL
5,9210-3PL
3,4410-4PL
2,5910-4PL
7,9610-4PL
5,9810-4PL
1,5910-3PL
1,1910-3PL
2,4710-3PL
1,8610-3PL

(*) En la realizacin de esta tabla se ha utilizado el valor de la resistencia del


conductor a 90 C.

Cuando se tiene una serie de cargas diferentes conectadas a


diferentes intervalos, bastar con tomar la mayor potencia y la mayor
distancia entre cargas para obtener una cota superior de las prdidas
de potencia.
En el apartado 0 del presente documento se indican de forma grfica
las prdidas de potencia.

81

7.1.7.

Niveles de Potencia

Para la realizacin de los clculos para el diseo de las redes de B.T.


se emplearn los niveles de potencia definidos en la siguiente forma:
Nivel de electrificacin:

Bajo: 3,6 kW.

Medio: 4,8 kW.

Alto: 6 kW.
En el caso de existir alguna vivienda o edificio con un grado de
electrificacin especial (mayor de 6 kW), para el clculo se
considerarn las potencias reales.

7.1.8.

Coeficientes de simultaneidad

Para el clculo de las cadas de tensin en las redes subterrneas se


considerarn los coeficientes de simultaneidad en funcin del nmero
de suministro de la lnea. Estos coeficientes son los que muestran la
Tabla 58, y se aplican a cada tramo de la lnea:
Tabla 58. Coeficientes de simultaneidad

Coeficientes de simultaneidad
Nmero de suministros
Ns
7.1.9.

1
1

2a4
0,8

5 a 15
0,6

15
0,4

Intensidad Mxima de Cortocircuito

Es la intensidad que no provoca ninguna disminucin de las


caractersticas mecnicas de los conductores, incluso despus de un
nmero elevado de cortocircuitos. Se calcula admitiendo que el
calentamiento de los conductores se realiza mediante un proceso
adiabtico (a calor constante).
La intensidad mxima de cortocircuito para un conductor de seccin
S, viene dada por:
Icc K S

1
t

(A)

donde:
Icc: Intensidad mxima de cortocircuito (A).

82

K: Coeficiente que depende de la naturaleza del conductor, del


aislamiento y de sus temperaturas al principio y al final del
cortocircuito. En este caso se toman como valores 143 para el
cobre y 93 para el aluminio.
S: Seccin del conductor (mm2).
t: Tiempo de duracin del cortocircuito (s).
Sustituyendo los valores para las secciones normalizadas,
obtenemos los valores representados en la Tabla 59.
Tabla 59. Intensidad mxima de cortocircuito para BT

Intensidad de cortocircuito admisible (A)


Duracin del cortocircuito (s)
Conductor
0,1

0,2

0,3

0,5

1,0

1,5

2,0

2,5

3,0

500 MCM

74493 52675 43009 33314 23557 19234 16657 14899 13601

4/0 AWG

31527 22293 18202 14099 9970 8140 7050 6305 5756

1/0 AWG

15734 11126 9084 7036 4976 4062 3518 3147 2873

# 4 AWG

9564 6763 5522 4277 3024 2469 2139 1913 1746

# 6 AWG

6014 4253 3472 2690 1902 1553 1345 1203 1098

La Tabla 60 muestra la seccin mnima admisible en la salida de


B.T. del trafo. A efectos de clculo, se considerar un tiempo de
duracin del cortocircuito de 0,2 s en caso de proteccin por
fusibles en el secundario y 0,5 s en el caso de proteccin por rel
trmico o fusible en el primario.

83

Tabla 60. Seccin mnima admisible en la salida de B.T. del trafo

TRANSFORMADOR MONOFASICO
SECCIN MNIMA (mm2)
POTENCIA TENSIN
Ucc (%) Icc (A) Con fusible Protecc.
(kV)
B.T, (V)
B.T.
trafo
50
240
3
6944
1/0 AWG
1/0 AWG
100
240
3
13889
4/0 AWG
4/0 AWG
167
240
5
13917
4/0 AWG
4/0 AWG
TRANSFORMADOR TRIFSICO
150
300
500
750

208
208

5
5

8337
16674

1/0 AWG
4/0 AWG

4/0 AWG
500 MCM

208
208

5
5,75

27790
36248

500 MCM
500 MCM
500 MCM 500 MCM(*)

(*) Para el caso del conductor 500 MCM en B.T. del trafo de 750 KVA, el tiempo
mximo de duracin del cortocircuito ser como mximo de 0,42 segundos.

84

8 ACOMETIDAS
La acometida es la parte de la instalacin comprendida entre la
red de distribucin general y la instalacin receptora. Por lo tanto
forman parte de ella, siendo sus extremos, los siguientes
elementos:

Elementos de conexin y anclaje a la lnea.

Los terminales de los conductores de entrada a la proteccin


de la acometida.

La Red de Alumbrado Pblico no puede tener ningn conductor


comn con la Red de distribucin.

8.1.

CONDUCTORES
Los conductores a emplear en las acometidas sern los
normalizados en las presente NORMAS. Se realizarn los clculos
mostrados a continuacin y se elegir el conductor que posea las
caractersticas ms adecuadas.
En las acometidas sern de uso preferente los conductores
concntricos de cobre. Para potencias superiores a las admitidas
por estos conductores se emplear el conductor de aluminio
normalizado adecuado a las mismas.

8.2.

CLCULO ELCTRICO
La seccin de los conductores de la acometida se determinar en
funcin de los criterios expuestos a continuacin:

Con el fin de garantizar que todos los clientes conectados a las


acometidas estn incluidos dentro de los mrgenes de
tolerancia, se asigna un porcentaje de cada de tensin del 0,8
% a la acometida.
La intensidad mxima admisible por el conductor seleccionado
para realizar una acometida, debe ser superior a la intensidad
mxima que se prevea para el suministro.
A continuacin se muestra el proceso de clculo que se debe
seguir.
a) Se calcula la seccin terica necesaria de los conductores.

85

Para la acometida monofsica se utiliza la siguiente expresin:


S

2 P L
e U

(mm2)

En el caso de acometidas trifsicas la ecuacin empleada es la


siguiente:
S

P L
e U

(mm2)

siendo en los dos casos:


S: Seccin terica del conductor (mm2).
P: Potencia demandada (W).
L: Longitud de la acometida (m).

: Conductividad del material (aluminio = 35; cobre =56


m/mm2).
e: Cada de tensin admisible (V).
U: Tensin de servicio. Para acometidas trifsicas se considera
como tensin de servicio la tensin de lnea (V).
b) Se determina la intensidad de corriente del suministro
mediante las siguientes expresiones segn sean acometidas
monofsicas o trifsicas respectivamente:

P
(A)
U cos

P
3 U cos

(A)

donde:
I: Intensidad mxima prevista para el suministro (A).
P: Potencia mxima prevista para el suministro (W).
U: Tensin de servicio. Para acometidas trifsicas se considera
como tensin de servicio la tensin de lnea (V).

86

cos : Factor de potencia medio del suministro.


c) Una vez determinada la seccin se elige el conductor
normalizado adecuado segn las caractersticas mostradas en
el apartado 6.1. del presente Documento. La intensidad mxima
admisible del conductor seleccionado debe ser superior a la
intensidad mxima prevista para el suministro. En caso
contrario se elegir el siguiente conductor normalizado que
posea una intensidad y seccin adecuadas.
Para determinar la seccin necesaria del conductor en una
acometida trifsica, cuando esta tambin alimente a una carga
monofsica, se considerar la intensidad en la fase ms cargada
como suma de la intensidad debida a la potencia trifsica y la
debida a la potencia monofsica. A efectos del clculo de la cada
de tensin, la intensidad en la fase ms cargada ser la suma de la
intensidad debida a la carga trifsica ms la debida a otra carga
trifsica de valor seis veces la potencia de la carga monofsica.
La intensidad correspondiente al suministro ser la suma de las
intensidades del suministro trifsico y del monofsico, calculadas
separadamente.
En las siguientes tablas se muestran las secciones en funcin de
la potencia y de la longitud y la intensidad en funcin de la
potencia.
En la Tabla 61 mostrada en el apartado 10.3. del presente
Documento se muestran los conductores adecuados para cada
acometida en funcin de la tensin, el nivel de potencia y la
longitud del suministro.

8.3.

INSTALACIN
La conexin a la lnea de los conductores se realizar mediante los
conectores de derivacin a compresin debidamente aislados para
evitar la entrada de humedad.
El mdulo de contadores se instalar protegido por una hornacina
o similar a fin de evitar posibles deterioros. La subida de los
conductores al mdulo de contadores se realizar interiormente a
dicha hornacina. En caso de que los conductores no puedan
instalarse empotrados, se canalizarn bajo tubo de acero.

87

8.4.

ACOMETIDAS DE ALUMBRADO PBLICO


La red de Alumbrado Pblico no es objeto del presente
Documento. Sus caractersticas se describen en el
correspondiente Documento.
Estas instalaciones incluirn siempre las protecciones adecuadas.
Cuando las instalaciones de Alumbrado Pblico sean
responsabilidad de la empresa suministradora, estas se realizarn
de acuerdo con el Documento de Instalaciones de Alumbrado
Pblico.

88

9 GRFICOS PARA CONDUCTORES MT


9.1.

GRFICOS DE CAIDA DE TENSIN

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea trifsica


U=13,2 kV 4/0 AWG
60000
50000
40000
30000
20000
10000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

89

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea trifsica


U=34,5 KV 4/0 AWG
400000
350000
300000
250000
200000
150000
100000
50000
0
0

10

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea trifsica


U=13,2 KV 500 MCM
140000
120000
100000
80000
60000
40000
20000
0
0

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

90

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea trifsica


U=34,5 KV 500 MCM
900000
800000
700000
600000
500000
400000
300000
200000
100000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea trifsica


U=13,2 KV 750 MCM
200000
180000
160000
140000
120000
100000
80000
60000
40000
20000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

91

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea monofsica


U=13,2 KV 1/0 AWG
4500
4000
3500
3000
2500
2000
1500
1000
500
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Momento del Transporte (KW*Km)

Grfico cada de Tensin lnea monofsica


U=34,5 KV 1/0 AWG
35000
30000
25000
20000
15000
10000
5000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

92

9.2.

GRFICOS DE PERDIDA DE POTENCIA

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea trifsica


U=13,2 KV 4/0 AWG
60000
50000
40000
30000
20000
10000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea trifsica


U=34,5 KV 4/0 AWG
400000
350000
300000
250000
200000
150000
100000
50000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

93

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea trifsica


U=13,2 KV 500 MCM
140000
120000
100000
80000
60000
40000
20000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea trifsica


U=34,5 KV 500 MCM
900000
800000
700000
600000
500000
400000
300000
200000
100000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

94

4500
4000
3500
3000
2500
2000
1500
1000
500
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

Grfico prdidas de potencia en lnea trifsica


U=13,2 KV 750 MCM
200000
Momento del Transporte (KW*Km)

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea monofsica


U=13,2 KV 1/0 AWG

180000
160000
140000
120000
100000
80000
60000
40000
20000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

95

Momento del Transporte (KW*Km)

Grfico prdidas de potencia en lnea monofsica


U=34,5 KV 1/0 AWG
35000
30000
25000
20000
15000
10000
5000
0
0

10

Cada de Tensin (%)


fdp=0,8

fdp=0,9

fdp=1

96

10 GRFICOS PARA CONDUCTORES BT


10.1. GRFICOS DE CADA DE TENSIN

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea monofsica
4/0 AWG - 240 V

9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

97

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea monofsica
1/0 AWG - 240 V

5000
4000
3000
2000
1000
0
1

10

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea monofsica
3X #4 AWG-240 V

3000
2500
2000
1500
1000
500
0
1

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

98

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea monofsica
3X #6 AWG-240 V

2000
1500
1000
500
0
1

10

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
500 MCM - 208 V

35000
30000
25000
20000
15000
10000
5000
0
1

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

99

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
500 MCM - 240 V

45000
40000
35000
30000
25000
20000
15000
10000
5000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

100

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
4/0 AWG- 240 V

18000
16000
14000
12000
10000
8000
6000
4000
2000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

101

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
4/0 AWG- 208 V

14000
12000
10000
8000
6000
4000
2000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

102

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
1/0 AWG- 208 V

7000
6000
5000
4000
3000
2000
1000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

103

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
1/0 AWG- 240 V

9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

104

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
4X #4 AWG- 208 V

4000
3500
3000
2500
2000
1500
1000
500
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

105

Momento de transporte
(kW x m)

GRFICO CADA DE TENSIN


Lnea trifsica
4X #4 AWG- 240 V

6000
5000
4000
3000
2000
1000
0
1

10

Cada de tensin (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

106

10.2. GRFICOS DE POTENCIA DE TRANSPORTE

45
40
35
30
25
20
15
10
5
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea monofsica - 240 V - cos = 0,8
Pmx = 39,36 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

107

50
40
30
20
10

200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea monofsica - 240 V - cos = 0,9
Pmx = 44,28 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

108

60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea monofsica - 240 V - cos = 1
Pmx = 49,20 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

109

30
25
20
15
10
5
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea monofsica - 240 V - cos = 0,8
Pmx = 25,92 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

110

35
30
25
20
15
10
5
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea monofsica - 240 V - cos = 0,9
Pmx =29,16 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

111

35
30
25
20
15
10
5
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea monofsica - 240 V - cos = 1
Pmx = 32,40 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

112

120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 208 V - cos = 0,8
Pmx = 100,87 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

113

120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 208 V - cos = 0,9
Pmx = 113,48 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

114

140
120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 208 V - cos = 1
Pmx = 126,09 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

115

140
120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 240 V - cos = 0,8
Pmx = 116,39 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

116

140
120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 240 V - cos = 0,9
Pmx = 130,94 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

117

160
140
120
100
80
60
40
20
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


500 MCM - Lnea trifsica - 240 V - cos = 1
Pmx = 145,49 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

118

70
60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea trifsica - 208 V - cos = 0,8
Pmx =59,08 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

119

70
60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea trifsica - 208 V - cos = 0,9
Pmx = 66,47 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

120

80
70
60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea trifsica - 240 V - cos = 0,8
Pmx = 68,17 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

121

90
80
70
60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea trifsica - 240 V - cos = 0,9
Pmx = 76,70 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

122

90
80
70
60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


4/0 AWG - Lnea trifsica - 240 V - cos = 1
Pmx = 85,22 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

123

45
40
35
30
25
20
15
10
5
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 208 V - cos = 0,8
Pmx = 38,91 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

124

200

180

160

140

120

100

80

60

40

20

50
45
40
35
30
25
20
15
10
5
0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 208 V - cos = 0,9
Pmx = 43,77 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

125

60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 208 V - cos = 1
Pmx =48,64 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

126

200

180

160

140

120

100

80

60

40

20

50
45
40
35
30
25
20
15
10
5
0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 240 V - cos = 0,8
Pmx = 44,89 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

127

60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 240 V - cos j = 0,9
Pmx = 50,51 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

128

60
50
40
30
20
10
200

180

160

140

120

100

80

60

40

20

0
0

Potencia mxima de transporte


kW

GRFICO POTENCIA MXIMA DE TRANSPORTE


1/0 AWG - Lnea trifsica - 240 V - cos j = 1
Pmx = 56,12 kW

Longitud de la lnea (m)


U% = 1

U% = 2,5

U% = 4

U% = 5

U% = 7

129

GRFICOS DE PRDIDAS DE POTENCIA

Momento de transporte (W x km)

GRFICO PRDIDA DE POTENCIA


4/0 AWG - Lnea monofsica - 240 V

9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1

10

Prdida de potencia (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

130

Momento de transporte (W x km)

GRFICO PRDIDA DE POTENCIA


1/0 AWG - Lnea monofsica - 240 V

4500
4000
3500
3000
2500
2000
1500
1000
500
0
1

10

Prdida de potencia (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

131

Momento de transporte (W x km)

GRFICO PRDIDA DE POTENCIA


3x #4 AWG - Lnea monofsica - 240 V

3000
2500
2000
1500
1000
500
0
1

10

Prdida de potencia (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

132

Momento de transporte (W x km)

GRFICO PRDIDA DE POTENCIA


3x #6 AWG - Lnea monofsica - 240 V

1800
1600
1400
1200
1000
800
600
400
200
0
1

10

Prdida de potencia (%)


cos fi = 0,8

cos fi = 0,9

cos fi = 1

133

GRFICO PRDIDA DE POTENCIA


500 MCM - Lnea trifsica - 208 V

35000
30000
25000
20000
15000
10000
5000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

134

GRFICO PRDIDA DE POTENCIA


500
4/0 MCM
AWG -- Lnea
Lnea trifsica
trifsica -- 208
240 VV

45000
14000
40000
12000
35000
10000
30000
8000
25000
20000
6000
15000
4000
10000
2000
5000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

135

GRFICO PRDIDA DE POTENCIA


4/0 AWG - Lnea trifsica - 240 V

18000
16000
14000
12000
10000
8000
6000
4000
2000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

136

GRFICO PRDIDA DE POTENCIA


1/0 AWG - Lnea trifsica - 208 V

7000
6000
5000
4000
3000
2000
1000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

137

GRFICO PRDIDA DE POTENCIA


1/0 AWG - Lnea trifsica - 240 V

9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

138

GRFICO PRDIDA DE POTENCIA


4x #4 AWG - Lnea trifsica - 208 V

4000
3500
3000
2500
2000
1500
1000
500
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

139

GRFICO PRDIDA DE POTENCIA


4x #4 AWG - Lnea trifsica - 240 V

6000
5000
4000
3000
2000
1000
0
1

4
cos fi = 0,8

6
cos fi = 0,9

10

cos fi = 1

140

10.3. TABLAS DE SELECCIN DEL CONDUCTOR DE ACOMETIDA


Tabla 61. Acometidas conectadas a la red B.T.

Tensin: 120 V - Circuito Monofsico


Distancia (m)
5
10
15
20
25
30
35
40
45
50
60
70
80
90
100

3,6
3 X #6 AWG

POTENCIA (kW)
4,8
3 X #6 AWG
3 X #4 AWG

6
3 X #6 AWG
3 X #4 AWG

3 X #4 AWG
1/0 AWG
1/0 AWG
1/0 AWG
4/0 AWG
4/0 AWG
4/0 AWG
500 MCM
500 MCM
500 MCM
Tensin: 120/240 V - Circuito Monofsico

Distancia (m)
5
10
15
20
25
30
35
40
45
50
60
70
80
90
100

3,6

POTENCIA (kW)
4,8

3 X #6 AWG
3 X #6 AWG
3 X #6 AWG
3 X #4 AWG
3 X #4 AWG
3 X #4 AWG
1/0 AWG

1/0 AWG

1/0 AWG

141

Tensin: 208 V - Circuito Trifsico


Distancia (m)
5
10
15
20
25
30
35
40
45
50
60
70
80
90
100

3,6

POTENCIA (kW)
4,8

3 X #6 AWG
3 X #6 AWG
3 X #6 AWG

3 X #4 AWG
3 X #4 AWG
3 X #4 AWG

1/0 AWG
1/0 AWG

Tensin: 240 V - Circuito Trifsico


Distancia (m)
5
10
15
20
25
30
35
40
45
50
60
70
80
90
100

3,6

POTENCIA (kW)
4,8

3 X #6 AWG
3 X #6 AWG
3 X #6 AWG

3 X #4 AWG
3 X #4 AWG
3 X #4 AWG

1/0 AWG

142

11 CONDICIONES ESPECFICAS PARA LNEAS


ELCTRICAS SUBTERRNEAS
El presente Pliego de Condiciones determina las condiciones
mnimas aceptables para la ejecucin de las obras de lneas
elctricas subterrneas realizadas segn las presentes NORMAS
TCNICAS.
Este Pliego de Condiciones se refiere al suministro e instalacin de
los materiales necesarios en el montaje de dichas lneas.
Los Pliegos de Condiciones Particulares podrn modificar las
presentes prescripciones.
11.1. EJECUCIN DEL TRABAJO
11.1.1. Trazado
Las canalizaciones, salvo casos de fuerza mayor, se ejecutarn en
terrenos de dominio pblico, bajo las aceras o calzadas, evitando
ngulos pronunciados. El trazado ser lo ms rectilneo posible,
paralelo en toda su longitud a bordillos o fachadas de los edificios
principales.
Antes de comenzar los trabajos, se marcarn en el pavimento las
zonas donde se abrirn las zanjas, marcando tanto su anchura
como su longitud y las zonas donde se contendr el terreno. Si ha
habido posibilidad de conocer las acometidas de otros servicios a
las fincas construidas, se indicarn sus situaciones con el fin de
tomar las precauciones debidas.
Antes de proceder a la apertura de las zanjas se abrirn calas de
reconocimiento para confirmar o rectificar el trazado previsto.
Se estudiar la sealizacin de acuerdo con las normas
municipales y se determinarn las protecciones precisas tanto de
la zanja como de los pasos que sean necesarios para los accesos a
los portales, comercios, garajes, etc. as como las chapas de
hierro que vayan a colocarse sobre la zanja para el paso de
vehculos.
Al marcar el trazado de las zanjas se tendr en cuenta el radio
mnimo que hay que dejar en la curva con arreglo a la seccin del
cable, siendo este radio mnimo 10 (D+d) donde D es el dimetro
exterior del cable y d el dimetro del conductor.

143

11.2. APERTURA DE ZANJAS


La excavacin la realizar una empresa especializada que trabaje
con los planos de trazado suministrados por la Compaa.
Las zanjas se harn verticales hasta la profundidad necesaria,
colocndose entibaciones en los casos que la naturaleza del
terreno lo haga preciso.
Se procurar dejar un paso de 50 cm entre zanja y las tierras
extradas, con el fin de facilitar la circulacin del personal de la
obra y evitar la cada de tierras en la zanja. La tierra excavada y el
pavimento, deben depositarse por separado. La planta de la zanja
debe limpiarse de piedras agudas, que podran daar las cubiertas
exteriores de los cables.
Se deben tomar las precauciones precisas para no tapar con
tierras registro de gas, telfono, bocas de riego, alcantarillas, etc.
Durante la ejecucin de los trabajos en la va pblica se dejarn
pasos suficientes para vehculos y peatones, as como los accesos
a los edificios, comercios y garajes. Si es necesario interrumpir la
circulacin se precisar una autorizacin especial.
Las dimensiones de las zanjas para lneas de MT sern, por lo
general de 0,8 a 1,20 m de profundidad y de 40 a 80 cm de
anchura. Mientras que para lneas de BT las dimensiones de las
zanjas sern, por lo general de 0,8 m de profundidad y 25, 40, 60 u
80 cm de anchura
Si es necesario abrir las zanjas en terreno de relleno o de poca
consistencia debe recurrirse al entibado en previsin de
derrumbes.
Es necesario que el fondo de la zanja est en terreno firme, para
evitar corrimientos en profundidad que sometan a los cables a
esfuerzos por estiramientos.
Cuando en una zanja coincidan cables de distintas tensiones se
situarn en capas horizontales a distinto nivel de forma que en
cada capa se agrupen cables de igual tensin.
En el caso de que ninguna de las lneas vaya entubada, la
separacin entre capas de cables ser como mnimo de 25 cm.

144

La profundidad de las respectivas capas de cables depender de


las tensiones, de forma que la mayor profundidad corresponda a la
mayor tensin.
11.3. CANALIZACINES
Los cruces de vas pblicas o privadas se realizarn con tubos
ajustndose a las siguientes condiciones:
a) Se colocar en posicin horizontal y recta y estarn
hormigonados en toda su longitud.
b) Los extremos de los tubos en los cruces llegarn hasta los
bordillos de las aceras.
c) En las salidas el cable se situar en la parte superior del tubo
sellando los orificios tanto de los tubos ocupados como de los
libres con espuma de poliuretano o similar.
d) Cuando no pueda mantenerse la profundidad mnima prevista
en este Documento, se utilizarn excepcionalmente tubos de
acero galvanizado.
e) Los cruces de vas frreas, cursos de agua, etc. debern
proyectarse con todo detalle.
f)

Deber preverse para futuras ampliaciones un tubo de


reserva.

Se debe evitar la posible acumulacin de agua o gas a lo largo de


la canalizacin situando convenientemente pozos de escape en
relacin al perfil altimtrico.
11.3.1. Cable Directamente Enterrado
En el lecho de la zanja ir una capa de arena de 10 cm de espesor
sobre la que se colocar el cable.
La arena que se utiliza para proteccin de los cables ser limpia,
suelta y spera, exenta de sustancias orgnicas, arcilla o
partculas terrosas, para lo cual se tamizar o lavar
convenientemente si fuera necesario. Se emplear arena de mina
y de ro indistintamente, siempre que rena las condiciones
sealadas anteriormente y las dimensiones de los granos sern de
2 a 3 mm como mximo.

145

Cuando se emplee la arena procedente de la misma zanja, adems


de necesitar la aprobacin del Director de Obra, ser necesario su
cribado.
Cuando los cables de MT se instalan directamente enterrados
deben tener una proteccin situada a 15 cm por encima de los
mismos, consistente en un tritubo, que adems de hacer de
proteccin y sealizacin de presencia de cables permitir
canalizar correctamente cables de comunicacin.
Todos los cables de BT deben tener una proteccin situada a 20 cm
por encima de los cables, que consiste en un tritubo, con la funcin
de canalizar las comunicaciones, proteger y advertir de la
presencia de cables elctricos de Baja Tensin.
11.3.2. Cable Entubado
Para lneas de MT este tipo de canalizacin ser el que se utilice
generalmente en aceras o calzadas, especialmente en las que
exista multiplicidad de servicios subterrneos que dificulten el
tendido directamente enterrado o que no permitan mantener las
distancias adecuadas en cruzamientos o paralelismos.
Para lneas de BT este tipo de canalizacin ser prioritaria para
lneas de distribucin de B.T., y la nica posible para acometidas.
Se utiliza generalmente en aceras o calzadas en las que exista
multiplicidad de servicios subterrneos que dificulten el tendido
directamente enterrado o que no permitan mantener las
distancias adecuadas en cruzamientos o paralelismos.
Para MT los tubos sern de polietileno (PE) de alta densidad de
color rojo y 160 mm de dimetro para las lneas trifsicas, y 110
mm para las monofsicas. Esta canalizacin puede ir acompaada
del correspondiente tritubo para alojar los cables de
comunicaciones, el cual estar situado por encima de los
anteriores. Para BT los tubos sern de polietileno (PE) de alta
densidad y 110 mm de dimetro para lneas de distribucin tanto
monofsica como trifsica de B.T., o 60 mm para acometidas.
En los cruzamientos de calzadas y ferrocarriles los tubos irn
hormigonados en todo su recorrido, as como en caso de tendido
de tubos en varias capas.
No es recomendable que el hormign de proteccin de los tubos
llegue hasta el pavimento de rodadura, pues se facilita la
transmisin de vibraciones. En este caso debe intercalarse entre

146

uno y otro una capa de tierra con las tongadas necesarias para
conseguir un prctor del 95%.
Al construir la canalizacin con tubos se dejar una gua en su
interior que facilite posteriormente el tendido de los mismos.
Los tubos se sellarn en las bocas, mediante espuma de
poliuretano o similar, para evitar que se obturen con tierra o lodo.
11.3.3. Cables al Aire, Alojados En Galeras
Este tipo de canalizacin se evitar en lo posible, utilizndose
nicamente en el caso en que el nmero de conducciones sea tal
que justifique la realizacin de galeras; o en los casos especiales
en que no se puedan utilizar las canalizaciones anteriores.
Los cables se colocarn al aire, fijados sobre bandejas perforadas,
palomillas o abrazaderas, de manera que no se desplacen por
efectos electrodinmicos.
Se conectarn elctricamente a tierra todos los elementos
metlicos de sujecin, siendo independientes las conexiones
cuando existan circuitos de diferentes tensiones.
Los locales o galeras debern estar bien aireados para obtener
una baja temperatura media y evitar accidentes por emanacin de
gases, debiendo adems, disponer de un buen sistema de drenaje.
No se instalarn cables elctricos en galeras con conducciones de
gases o lquidos inflamables.
11.4. ARQUETAS
Deber limitarse al mximo su uso, siendo necesaria una
justificacin de su inexcusable necesidad en el proyecto.
Cuando se construyan arquetas, stas sern de hormign o
ladrillo, siendo sus dimensiones las necesarias para que el radio
de curvatura de tendido sea como mnimo 20 veces el dimetro
exterior del cable.
No se admitirn ngulos inferiores a 90 y an stos se limitarn a
los indispensables. En general los cambios de direccin se harn
con ngulos grandes.
En la arqueta los tubos quedarn a unos 25 cm por encima del
fondo para permitir la colocacin de rodillo en las operaciones de

147

tendido. Una vez tendido el cable los tubos se taponarn con


espuma de poliuretano de forma que el cable quede situado en la
parte superior del tubo. La arqueta se rellenar con arena hasta
cubrir el cable como mnimo. En el suelo o las paredes laterales
se situarn puntos de apoyo de los cables y empalmes, mediante
tacos o mnsulas.
La situacin de los tubos en la arqueta ser la que permita el
mximo radio de curvatura.
Las arquetas sern registrables y, debern tener tapas metlicas o
de hormign armado provistas de argollas o ganchos que faciliten
su apertura. El fondo de estas arquetas ser permeable de forma
que permita la filtracin del agua de lluvia.
Estas arquetas permitirn la presencia de personal para ayuda y
observacin del tendido y colocacin de rodillos a la entrada y
salida de los tubos. Estos rodillos, se colocarn tan elevados
respecto al tubo, como lo permite el dimetro del cable, a fin de
evitar el mximo rozamiento contra l.
Las arquetas abiertas tienen que respetar las medidas de
seguridad, disponiendo barreras y letreros de aviso. No es
recomendable entrar en una arqueta recin abierta,
aconsejndose dejar transcurrir 15 minutos despus de abierta,
con el fin de evitar posibles intoxicaciones de gases.
11.5. PARALELISMOS
Las lneas subterrneas de media tensin debern guardar las
siguientes distancias a las diferentes instalaciones existentes. En
ningn caso se canalizarn paralelamente por encima o por debajo
de cualquier otra instalacin, con excepcin de las lneas
elctricas, siempre y cuando, estas sean de propiedad de Gas
Natural Fenosa. En tal caso, ambas lneas se canalizarn bajo tubo
y se situar en el nivel superior la lnea de menor tensin.

11.5.1. Media y Baja Tensin


Los cables de Media Tensin se podrn colocar paralelos a cables
de Baja Tensin, siempre que entre ellos haya una distancia no
inferior a 25 cm. Cuando no sea posible conseguir esta distancia,
se instalar uno de ellos bajo tubo.

148

11.5.2. Baja Tensin


Los cables de Baja Tensin se podrn colocar paralelos entre s,
siempre que estn instalados bajo tubo. Cuando no sea posible la
instalacin bajo tubo, deber existir entre ellos una distancia no
inferior a 25 cm.
11.5.3. Media Tensin
La distancia a respetar en el caso de paralelismos de lneas
subterrneas de media tensin es 25 cm. Si no fuese posible
conseguir esta distancia, se colocar una de ellas bajo tubo.
11.5.4. Cables De Comunicacin
En el caso de paralelismos entre lneas elctricas subterrneas y
lneas de telecomunicaciones subterrneas, estos cables deben
estar a la mayor distancia posible entre s. Siempre que los cables,
tanto de telecomunicaciones como elctricos, vayan directamente
enterrados, la mnima distancia ser de 20 cm. Cuando esta
distancia no pueda alcanzarse, deber instalarse la lnea de alta
tensin en el interior de tubos con una resistencia mecnica
apropiada.
En todo caso, en paralelismos con cables de comunicacin, deber
tenerse en cuenta lo especificado por los correspondientes
acuerdos con las compaas de telecomunicaciones.
Solo se podrn hacer paralelismos de longitud superior de 500
metros, cuando los cables de telecomunicaciones estn provistos
de pantalla electromagntica.

11.5.5. Agua, Vapor, Etc.


En el paralelismo entre cables de energa y conducciones
metlicas enterradas se debe mantener en todo caso una distancia
mnima en proyeccin horizontal de 0,25 m. Si no se pudiera
conseguir esta distancia, se instalarn los cables dentro de tubos
de resistencia mecnica apropiada.
Siempre que sea posible, en las instalaciones nuevas la distancia
en proyeccin horizontal entre cables de energa y conducciones
metlicas enterradas colocadas paralelamente entre s no debe
ser inferior a:

149

a) 3 metros en el caso de conducciones a presin mxima igual o


superior a 25 atm; dicho mnimo se reduce a 1 metro en el
caso en que el tramo de paralelismo sea inferior a 100 metros.
b) 1 m en el caso de conducciones a presin mxima inferior a 25
atm.
11.5.6. Gas
Cuando se trate de canalizaciones de gas, se tomarn adems las
medidas necesarias para asegurar la ventilacin de los conductos
y registros de los conductores, con el fin de evitar la posible
acumulacin de gases en los mismos, siendo las distancias como
mnimo de 50 cm.
No se colocar el cable elctrico paralelamente sobre la
proyeccin del conducto de gas, debiendo pasar dicho cable por
debajo de la toma de gas. Si no fuera posible conseguir la
separacin de 50 cm, se instalarn los cables dentro de tubos
11.5.7. Alcantarillado
En los paralelismos de los cables con conducciones de
alcantarillado de aguas fecales, se mantendr una distancia
mnima de 50 cm, protegindose adecuadamente los cables
cuando no pueda conseguirse esta distancia. En el caso de
paralelismos de los cables con conducciones de alcantarillado de
aguas fluviales, el tratamiento ser anlogo al de las conducciones
de agua.
11.5.8. Depsito de Carburante
Entre los cables elctricos y los depsitos de carburante, habr
una distancia mnima de 1,2 m, debiendo, adems, protegerse
apropiadamente el cable elctrico.
11.5.9. Fundaciones de Otros Servicios
Cuando en las proximidades de la canalizacin existen soportes de
lneas areas de transporte pblico, telecomunicacin, alumbrado
pblico, etc. el cable se instalar a una distancia a una distancia de
50 cm como mnimo de los bordes externos de los soportes o de
las fundaciones. Esta distancia ser de 150 cm en el caso en el que
el soporte est sometido a un esfuerzo de vuelco permanente
hacia la zanja.
Cuando esta precaucin no se pueda tomar, se emplear una
proteccin mecnica resistente a lo largo del soporte y de su

150

fundacin prolongando una longitud de 50 cm a ambos lados de los


bordes extremos de sta.
11.6. CRUZAMIENTOS CON VIAS DE COMUNICACIN
11.6.1. Con Vas Pblicas
En los cruzamientos con calles y carreteras los cables debern ir
entubados a una profundidad mnima de 80 cm. Los tubos o
conductores sern resistentes, duraderos, estarn hormigonados
en todo su recorrido y tendrn un dimetro que permita deslizar
los cables por su interior fcilmente. En todo caso deber tenerse
en cuenta lo especificado por las normas y ordenanzas vigentes
correspondientes.
11.6.2. Con Ferrocarriles
En el cruce de lneas subterrneas con ferrocarriles o vas frreas
deber realizarse siempre bajo tubo. Dicho tubo rebasar las
instalaciones de servicio en una distancia de 1,30 m. Se
recomienda efectuar el cruzamiento por los lugares de menor
anchura de la zona del ferrocarril.
11.6.3. Cruzamientos Con Otros Servicios
11.6.3.1.

Media y Baja Tensin

En el caso de cruzamientos entre dos lneas elctricas


subterrneas directamente enterradas la distancia mnima a
respetar ser de 0,25 m. En caso de no poder conseguir esta
distancia, se separarn los cables de Media Tensin de los de Baja
Tensin por medio de tubos.
11.6.3.2.

Baja Tensin

En los cruzamientos de dos lneas de Baja Tensin, la distancia


mnima a respetar ser de 0,25 m. Si no fuese posible conseguir
esta distancia, se instalar una de las lneas bajo tubo.
11.6.3.3.

Media tensin

La distancia a respetar entre lneas subterrneas de media tensin


es 25 cm. Si no fuese posible conseguir esta distancia, la nueva
lnea ir entubada.

151

11.6.3.4.

Con cables de telecomunicaciones

En los cruzamientos de una canalizacin con conducciones de


otros servicios (agua, vapor, etc.) se guardar una distancia
mnima de 25 cm. En el caso de no conseguir la citada distancia,
deber instalarse el cable de baja tensin en tubos de adecuada
resistencia mecnica.
El cruzamiento entre cables de energa y conducciones metlicas
enterradas no debe efectuarse sobre la proyeccin vertical de las
uniones no soldadas de la misma conduccin metlica.
11.6.3.5.

Agua, vapor, etc.

El cruzamiento entre cables de energa y conducciones metlicas


enterradas no debe efectuarse sobre la proyeccin vertical de las
uniones no soldadas de la misma conduccin metlica.
La distancia mnima entre la generatriz del cable de energa y la de
la conduccin metlica no debe ser inferior a 0,25 m. En el caso de
no conseguir la citada distancia, deber instalarse en cable de
media tensin en tubos de adecuada resistencia mecnica.
11.6.3.6.

Gas

No se realizar el cruce del cable elctrico sobre la proyeccin


vertical de las juntas de la canalizacin de gas.
La distancia a respetar en el caso de cruce con una canalizacin de
gas es de 25 cm.
11.6.3.7.

Alcantarillado

En los cruzamientos de cables elctricos con conducciones de


alcantarillado deber evitarse daos a la bveda de la conduccin,
debindose mantener en todo caso la distancia mnima de 50 cm
para el caso de conducciones de alcantarillado de aguas fecales. En
el caso de aguas fluviales, el tratamiento ser anlogo al de
conducciones de agua.
11.6.3.8.

Depsitos de carburantes

Se evitarn los cruzamientos de cables elctricos sobre depsitos


de carburantes. Los cables, debidamente protegidos, bordearn el
depsito a una distancia de 1,2 m del mismo.

152

11.7. TRANSPORTE DE BOBINAS DE CABLES


La carga y descarga, sobre camiones o remolques apropiados, se
har siempre mediante una barra adecuada que pase por el
orificio central de la bobina.
Las bobinas de cable se transportarn siempre de pie y nunca
tumbadas sobre una de las tapas.
Cuando las bobinas se colocan llenas en cualquier tipo de
transportador, stas debern quedar en lnea, en contacto una y
otra y bloqueadas firmemente en los extremos y a lo largo de sus
tapas.
El bloqueo de las bobinas se debe hacer con tacos de madera lo
suficientemente largos y duros con un total de largo que cubra
totalmente el ancho de la bobina y puedan apoyarse los perfiles de
las dos tapas. Las caras del taco tienen que ser uniformes para
que las duelas no se puedan romper daando entonces el cable.
En sustitucin de estos tacos tambin se pueden emplear unas
cuas de madera que se colocarn en el perfil de cada tapa y por
ambos lados se clavarn al piso de la plataforma para su
inmovilidad. Estas cuas nunca se pondrn sobre la parte central
de las duelas, sino en los extremos, para que apoyen sobre los
perfiles de las tapas.
Bajo ningn concepto se podr retener la bobina con cuerdas,
cables o cadenas que abracen la bobina y se apoyen sobre la capa
exterior del cable enrollado; asimismo no se podr dejar caer la
bobina al suelo desde un camin o remolque. En caso de no
disponer de elementos de suspensin, se montar una rampa
provisional formada por tablones de madera o vigas, con una
inclinacin no superior al 25%. Debe guiarse la bobina con cables
de retencin. Es aconsejable acumular arena a una altura de 20
cm al final del recorrido, para que acte como freno.
Cuando se desplace la bobina por tierra rodndola, habr que
fijarse en el sentido de rotacin, generalmente indicado con una
flecha, con el fin de evitar que se afloje el cable enrollado en la
misma.
Cuando las bobinas deban trasladarse girndolas sobre el terreno,
debe hacerse todo lo posible para evitar que las bobinas queden o
rueden sobre un suelo u otra superficie que sea accidentada.
Esta operacin ser aceptable nicamente para pequeos
recorridos.

153

En cualquiera de estas maniobras debe cuidarse la integridad de


las duelas de madera con que se tapan las bobinas, ya que las
roturas suelen producir astillas que se introducen hacia el interior
con el consiguiente peligro para el cable.
Siempre que sea posible debe evitarse la colocacin de bobinas de
cable a la intemperie sobre todo si el tiempo de almacenamiento
ha de ser prolongado, pues pueden presentarse deterioros
considerables en la madera (especialmente en las tapas, que
causaran importantes problemas al transportarlas, elevarlas y
girarlas durante el tendido).
Cuando deba almacenarse una bobina de la que se ha utilizado una
parte del cable que contena, han de taponarse los extremos de los
cables, utilizando capuchones retrctiles.
Antes de empezar el tendido del cable se estudiar el lugar ms
adecuado para colocar la bobina con objeto de facilitar el tendido.
En el caso de suelo con pendiente es preferible el tendido en
sentido descendente.
11.8. TENDIDO DE CABLES
La bobina de cable se colocar en el lugar elegido de forma que la
salida del cable se efecte por su parte superior y emplazada de
tal forma que el cable no quede forzado al tomar la alimentacin
del tendido.
Para el tendido la bobina estar siempre elevada y sujeta por gatos
mecnicos y una barra, de dimensiones y resistencia apropiada al
peso de la bobina.
La base de los gatos ser suficientemente amplia para que
garantice la estabilidad de la bobina durante su rotacin.
Al retirar las duelas de proteccin se cuidar hacerlo de forma que
ni ellas, ni el elemento empleado para enclavarla, puedan daar el
cable.
Los cables deben ser siempre desenrollados y puestos en su sitio
con el mayor cuidado evitando que sufran torsin, hagan bucles,
etc. y teniendo siempre en cuenta que el radio de curvatura del
cable debe ser superior a 20 veces su dimetro durante su tendido.
Cuando los cables se tiendan a mano los operarios estarn
distribuidos de una manera uniforme a lo largo de la zanja.

154

Tambin se puede tender mediante cabestrantes tirando del


extremo del cable al que se le habr adaptado una cabeza
apropiada y con un esfuerzo de traccin que no supere del indicado
por el fabricante del mismo. Ser imprescindible la colocacin de
dinammetros para medir dicha traccin.
El tendido se har obligatoriamente por rodillos que puedan girar
libremente y construidos de forma que no daen el cable.
Estos rodillos permitirn un fcil rodamiento con el fin de limitar
el esfuerzo de tiro; dispondrn de una base apropiada que, con o
sin anclaje, impida que se vuelquen, y una garganta por la que
discurra el cable para evitar su salida o cada.
Se distanciarn entre s de acuerdo con las caractersticas del
cable, peso y rigidez mecnica principalmente, de forma que no
permitan un vano pronunciado del cable entre rodillos contiguos,
que dara lugar a ondulaciones perjudiciales. Esta colocacin ser
especialmente estudiada en los puntos del recorrido en que haya
cambios de direccin, donde adems de los rodillos que facilitan el
deslizamiento deben disponerse otros verticales para evitar el
ceido del cable contra el borde de la zanja en el cambio de
sentido.
Para evitar el roce del cable contra el suelo, a la salida de la
bobina, es recomendable la colocacin de un rodillo de mayor
anchura para abarcar las distintas posiciones que adopta el cable.
No se permitir desplazar lateralmente el cable por medio de
palancas u otros tiles; deber hacerse siempre a mano.
Slo de manera excepcional se autorizar desenrollar el cable
fuera de zanja, siempre bajo vigilancia del Director de Obra.
Para la gua del extremo del cable a lo largo del recorrido y con el
fin de salvar ms fcilmente los diversos obstculos que se
encuentren (cruces de alcantarillas, conducciones de agua, gas
electricidad, etc.) y para el enhebrado en los tubos, en
conducciones tubulares, se puede colocar en esa extremidad una
manga tiracables a la que se una cuerda. Es totalmente
desaconsejable situar ms de dos a cinco peones tirando de dicha
cuerda, segn el peso del cable, ya que un excesivo esfuerzo
ejercido sobre los elementos externos del cable produce, en l,
deslizamientos y deformaciones. Si por cualquier circunstancia se
precisara ejercer un esfuerzo de tiro mayor, este se aplicar sobre
los propios conductores usando preferentemente cabezas de tiro
estudiadas para ello.

155

Para evitar que en las distintas paradas que pueden producirse en


el tendido, la bobina siga girando por inercia y desenrollndose
cable que no circula, es conveniente dotarla de un freno, por
improvisado que sea, para evitar en este momento curvaturas
peligrosas para el cable.
La zanja en toda su longitud deber estar cubierta con una capa de
arena fina de unos 10 cm en el fondo antes de proceder al tendido
del cable. En el caso de instalacin entubada, esta distancia podr
reducirse a 5 cm.
No se dejar nunca el cable tendido en una zanja abierta sin haber
tomado antes la precaucin de cubrirlo con una capa de 20 cm de
arena fina y del tritubo.
En ningn caso se dejarn los extremos del cable en la zanja sin
haber asegurado antes una buena estanqueidad de los mismos.
Cuando dos cables que se canalicen vayan a ser empalmados, se
solaparn al menos en una longitud de 0,50 m.
Las zanjas se recorrern con detenimiento antes de tender el
cable para comprobar que se encuentran sin piedras y otros
elementos que puedan daar los cables en su tendido.
Si con motivo de las obras de canalizacin aparecieran
instalaciones de otros servicios, se tomarn todas las
precauciones para no daarlas, dejndolas al terminar los trabajos
en las mismas condiciones en que se encontraban primitivamente.
Si involuntariamente se causara alguna avera en dichos servicios,
se avisar con toda urgencia al Director de Obra y a la Empresa
correspondiente con el fin de que procedan a su reparacin. El
encargado de la obra por parte del Contratista deber conocer la
direccin de los servicios pblicos as como su nmero de telfono
para comunicarse en caso de necesidad.
Si las pendientes son muy pronunciadas y el terreno es rocoso e
impermeable, se corre el riesgo de que la zanja de canalizacin
sirva de drenaje originando un arrastre de la arena que sirve de
lecho a los cables. En este caso se deber entubar la canalizacin
asegurada con cemento en el tramo afectado.
En el caso de canalizaciones con cables unipolares, cada dos
metros envolviendo las tres fases, se colocar una sujecin que
agrupe dichos conductores y los mantenga unidos.

156

Nunca se pasarn dos circuitos, bien cables tripolares o bien


cables unipolares, por un mismo tubo.
Una vez tendido el cable los tubos se taparn de forma que el
cable quede en la parte superior del tubo.
11.9. PROTECCIN MECNICA
Las lneas elctricas subterrneas deben estar protegidas contra
posibles averas producidas por hundimiento de tierras, por
contacto con cuerpos duros y por choque de herramientas
metlicas. Para ello se colocar un tritubo en polietileno de alta
densidad tipo III clase B a lo largo de la longitud de la canalizacin,
cuando sta no est entubada.
11.10. SEALIZACIN
Todo cable o conjunto de cables debe estar sealado por una cinta
de sealizacin colocada como mximo a 0,30 m por debajo del nivel
del suelo. Cuando los cables o conjuntos de cables de categoras de
tensin diferentes estn superpuestos, debe colocarse dicha cinta
encima de cada uno de ellos.
Estas cintas estarn
correspondiente.

de

acuerdo

con

la

especificacin

11.11. IDENTIFCACIN
Los cables debern llevar marcas que indiquen el nombre del
fabricante, el ao de fabricacin y sus caractersticas.
11.12. CIERRE DE ZANJAS
Una vez colocadas al cable las protecciones sealadas
anteriormente, se rellenar toda la zanja con el tipo de tierra y en
las tongadas necesarias para conseguir un prctor del 95%.
Procurando que las primeras capas de tierra por encima de los
elementos de proteccin estn exentas de piedras o cascotes. De
cualquier forma debe tenerse en cuenta que una abundancia de
pequeas piedras o cascotes puede elevar la resistividad trmica
del terreno y disminuir con ello la posibilidad de transporte de
energa del cable.
El cierre de las zanjas deber hacerse por capas sucesivas de 10 cm
de espesor, las cuales sern apisonadas y regadas si fuese
necesario con el fin de conseguir un prctor de 95%.

157

El Contratista ser responsable de los hundimientos que se


produzcan por la deficiente realizacin de esta operacin y, por lo
tanto, sern de su cuenta las posteriores reparaciones que tengan
que ejecutarse.
La carga y transporte a vertederos de las tierras sobrantes est
incluida en la misma unidad de obra que el cierre de las zanjas con
objeto de que el apisonado sea lo mejor posible.
11.13. REPOSICIN DE PAVIMENTO
Los pavimentos sern repuestos de acuerdo con las normas y
disposiciones dictadas por el propietario de los mismos.
Deber lograrse una homogeneidad de forma que quede el
pavimento nuevo lo ms igualado posible al antiguo, haciendo su
reconstruccin por piezas nuevas si est compuesto por losetas,
baldosas, etc.
En general se utilizarn materiales nuevos salvo las losas de piedra,
adoquines, bordillos de granito y otros similares.
11.14. PUESTA A TIERRA
Para la baja tensin el conductor neutro se conectar a tierra en el
Centro de Transformacin, as como en otros puntos de la red, de un
modo eficaz, de acuerdo con las presentes NORMAS TCNICAS.
Las pantallas de los cables deben ser puestas a tierra en los
extremos de cada cable y en los empalmes, con objeto de disminuir
la resistencia global a tierra.
Cuando las tomas de tierra de pararrayos de edificios importantes
se encuentren bajo la acera, prximas a cables elctricos en que las
envueltas no estn conectadas en el interior de los edificios con la
bajada del pararrayos conviene tomar alguna de las precauciones
siguientes:

Interconexin entre la bajada del pararrayos y las envueltas


metlicas de los cables.
Distancia mnima de 0,50 m entre el conductor de toma de tierra
del pararrayos y los cables o bien interposicin entre ellos de
elementos aislantes.

158

11.15. TENSIONES TRANSFERIDAS EN MT.


Con motivo de un defecto a masa lejano y con objeto de evitar la
transmisin de tensiones peligrosas en el tendido de cables por
galera, las pantallas metlicas de los cables se pondrn a tierra al
realizar cada una de las cajas de empalme y en las cajas terminales.
11.16. MATERIALES
Los materiales empleados en la canalizacin sern aportados por el
Contratista siempre que no se especifique lo contrario en el Pliego
de Condiciones Particulares.
No se podrn emplear materiales que no hayan sido aceptados
previamente por el Director de Obra.
Se realizarn cuantos ensayos y anlisis indique el Director de Obra,
aunque no estn indicados en este Pliego de Condiciones.
Los cables instalados sern los que figuran en el Proyecto y debern
estar de acuerdo con la especificacin correspondiente.

159

12 CONDICIONES BASICAS PARA CENTROS DE


TRANSFORMACIN Y DE MANIOBRAS DE PEDESTAL
12.1. TENSIONES NOMINALES DE MT. NIVEL DE AISLAMIENTO PARA
EL MATERIAL.
Dependiendo de la tensin de servicio, la serie y nivel de
aislamiento previsto para el material, es el indicado en la Tabla 62.
Tabla 62. Niveles de aislamiento segn tensin nominal

CLASE TENSIN DE
(kV)
SERVICIO (kV)

TENSIN
TENSIN MX.
CA (60 HZ)
TIPO RAYO
RED FASE1 MIN.
(kV pico)
FASE (kV)
(kV rms)
(BIL)

15

12,47/13,2

14,4

95

34

35

34,5

36,6

150

70

12.2. TENSIONES NOMINALES DE BT.


A los efectos del nivel de aislamiento el material de baja tensin
instalado en el CT, se clasificar de la manera siguiente:
a) Materiales para la conexin entre transformadores y cuadro de
baja tensin, cuadros de baja tensin y salidas de stos hacia la
red de distribucin.
b) Materiales para los servicios propios de CT.
Los materiales contemplados en el apartado a) debern ser
capaces de soportar, por su propia naturaleza tensiones de hasta
10 kV a tierra.
Los materiales contemplados en el apartado b) debern ser
capaces, por su propia naturaleza, por condiciones de instalacin o
mediante dispositivos adecuados, de soportar tensiones de hasta
10 kV a tierra.
Las caractersticas de aislamiento de las bornas de BT se
muestran en la Tabla 63.

160

Tabla 63. Aislamiento de bornas en BT

CLASE (kV)

TENSIN DE
SERVICIO (V)

TENSIN TIPO RAYO


(kV pico) (BIL)

CA (60 HZ)
1 MIN.
(kV rms)

1,2

120/208

30

10

1,2

120-240

30

10

12.3. INTENSIDAD NOMINAL EN MT. NIVEL DE CORTOCIRCUITO.


Las intensidades de cortocircuito y los tiempos de duracin del
defecto sern, en cada caso, determinados por GAS NATURAL
FENOSA.
Los materiales de alta tensin instalados en el CT, debern ser
capaces de soportar dichas solicitaciones. A tal efecto debern
tomarse en consideracin las caractersticas de dichos materiales,
definidas en las correspondientes Especificaciones de Materiales de
GAS NATURAL FENOSA, y expuestas en la Tabla 64.
Tabla 64. Caractersticas de materiales

COMPONENTE
Terminal acodado
enchufable en carga
Terminal atornillable
en T sin carga

CLASE
(kV)

CORRIENTE
NOMINAL (A)

I RMS SIMTRICA
(kA)

15 y 35

200

10 (*)

15 y 35

600

25 (*)

15

600

12,5 (**)

35

400

12,5 (**)

Interruptor
* El tiempo de despeje de falta tomado es de 0,17 s. segn la especificacin tcnica
correspondiente.
** El tiempo de despeje es de 1 s.

12.4. TIPOS Y POTENCIAS DE LOS TRANSFORMADORES.


Los transformadores pueden ser de los tipos y potencias que se
indican a continuacin:
Transformadores monofsicos, tipo Pad-Mounted: Con dos
pasatapas de MT tipo pozo para borna insertable enchufable en
carga de 200 A. y tres bornas de BT segn la especificacin tcnica
correspondiente. Las potencias normalizadas sern: 50, 100 y 167
kVA.

161

Transformadores trifsicos, fin de lnea, tipo Pad-Mounted: Con


tres pasatapas de MT tipo pozo previstos para borna insertable
enchufable en carga de 200 A simple o doble y cuatro bornas de
BT segn la especificacin tcnica correspondiente. Las potencias
normalizadas sern: 150, 300, 500 y 750 kVA. Se utilizar la
potencia de 750 kVA para aquellos casos singulares en los que la
demanda de potencia, de un solo cliente, no pueda ser cubierta con
transformadores hasta 500 kVA y para ampliaciones de potencia de
transformadores de 500 kVA sobrecargados. En caso de demandas
superiores, y a fin de evitar intensidades de cortocircuito
excesivas, se instalarn varias mquinas, sin acoplar en paralelo
la baja tensin, repartiendo la carga total entre las distintas
mquinas.
Transformadores trifsicos con entrada y salida, tipo PadMounted: Con seis pasatapas de MT tipo atornillable sin carga, de
600 A y cuatro bornas de BT segn la especificacin tcnica
correspondiente. Las potencias normalizadas sern: 300, 500 y 750
kVA. Con las mismas consideraciones, respecto a potencias que en
el caso anterior.
12.5. CENTROS DE SECCIONAMIENTO.
Los centros de seccionamiento, incluidos en el presente
Documento, pueden ser con envolvente metlica tipo Pad-Mounted
o con envolvente de hormign, con los esquemas que se indican a
continuacin:
Seccionamiento simple tipo 3L1, metlico Pad-Mounted, con tres
posiciones de lnea, dos para entrada y salida de la lnea principal
con bornas atornillables sin carga de 600 A y la tercera, para
derivada, con tres pasatapas tipo pozo, previstas para borna
insertable en carga de 200 A, simple o doble. Tiene un solo
interruptor de cuatro posiciones tipo T-Blade.
Seccionamiento de tres posiciones tipo 3L3, metlico tipo PadMounted, con tres posiciones de lnea y nueve bornas atornillables
sin carga de 600 A. Tiene tres interruptores de tres posiciones,
Abierto-Cerrado-Tierra, sumergidos en aceite.
Seccionamiento de cuatro posiciones tipo 4L4, metlico PadMounted, con cuatro posiciones de lnea y doce bornas
atornillables sin carga de 600 A. Tiene cuatro interruptores de tres
posiciones, Abierto-Cerrado-Tierra, sumergidos en aceite.
Los seccionamientos tipo 3L3 y 4L4, tambin son admisibles en
versin europea, con celdas en SF6 y envolvente de Hormign.

162

Las caractersticas de todos ellos


especificacin tcnica correspondiente.

estn

fijadas,

en

la

163

13 CARACTERSTICAS ELECTRICAS DE CENTROS DE


TRANSFORMACIN Y DE SECCIONAMIENTO
13.1. CENTROS DE TRANSFORMACIN
13.1.1. Trafo Tipo Pad-Mounted Monofsico.
El transformador tipo Pad-Mounted monofsico consistir en un
tanque con compartimentos para media y baja tensin. Estos
deben estar localizados uno al lado del otro, en un lado del tanque
del transformador. Visto desde el frente, el compartimento de baja
tensin debe estar a la derecha.
Los compartimentos contarn con una puerta de acceso. Dicha
puerta ser del tipo oscilobatiente.
Los compartimentos sern accesibles solamente desde el interior.
El compartimento de MT presentar dos pasatapas de MT tipo
pozo para borna insertable enchufable en carga de 200 A, y el de
BT, tres bornas de BT segn la especificacin tcnica
correspondiente.
Las separaciones entre bornas y la disposicin de los parkings
han sido previstas para la utilizacin de borna insertable doble.
El transformador contar con un indicador de nivel del aceite
localizado en el compartimento de baja tensin. As mismo,
contar tambin con dos vlvulas, una de entrada para el relleno
del aceite, y otra de salida, para el vaciado.
La proteccin del transformador contra sobrecargas, se realizar
mediante un interruptor con proteccin termomagntica en el
primario, instalado en el interior de la cuba.
La proteccin contra cortocircuitos se realizar mediante fusible
interno de alto poder de ruptura tipo limitador de la intensidad
adecuada a la potencia del transformador y coordinado con el
interruptor termomagntico de proteccin contra sobrecargas.
La maniobra del transformador se realizar mediante prtiga,
sobre el mando del interruptor termomagntico del transformador
en carga. Existe tambin la posibilidad de maniobra de la lnea
mediante la operacin en carga con prtiga de los conectores
enchufables.

164

13.1.2. Trafo Tipo Pad-Mounted Trifsico Fin De Lnea.


El diseo del transformador tipo pad-mounted trifsico fin de lnea
consistir en un tanque con compartimentos para media y baja
tensin separados por una barrera de metal u otro material rgido.
Estos deben estar localizados uno al lado del otro, en un lado del
tanque del transformador. Visto desde el frente, el compartimento
de baja tensin debe estar a la derecha.
Cada compartimento debe tener una puerta que se construya de
modo que se d acceso al compartimento de alta tensin slo
cuando est abierta la puerta del lado de baja tensin.
Los compartimentos sern accesibles solamente desde el interior.
El compartimento de MT presenta tres pasatapas de MT tipo pozo
para borna insertable enchufable en carga de 200 A simple o
doble, y el de BT, cuatro bornas de BT segn la especificacin
tcnica correspondiente.
El transformador contar con un indicador de nivel del aceite y
termmetro localizados en el compartimento de media tensin. As
mismo, contar con dos vlvulas, una de entrada para el relleno
del aceite, y otra de salida, para el vaciado, situadas tambin en el
compartimento de media tensin.
Adems incluir una vlvula de sobrepresin situada en el citado
compartimento de media tensin.
El cambio de voltaje se realizar por medio de un conmutador de
cinco posiciones manual localizado en la parte de MT.
La proteccin del transformador contra sobrecargas, se realizar
mediante un interruptor con proteccin termomagntica en el
primario, instalado en el interior de la cuba.
La proteccin contra cortocircuitos se realizar mediante fusibles
internos de alto poder de ruptura tipo limitador de la intensidad
adecuada a la potencia del transformador y coordinados con el
interruptor termomagntico de proteccin contra sobrecargas.
La maniobra del transformador en carga se realizar mediante
prtiga, sobre el mando del interruptor termomagntico. Existe
tambin la posibilidad de operar en carga con prtiga los
conectores enchufables.

165

13.1.3. Trafo Tipo Pad-Mounted Trifsico Entrada-Salida.


El diseo del transformador tipo pad-mounted trifsico entradasalida consistir en un tanque con compartimentos para media y
baja tensin separados por una barrera de metal u otro material
rgido.
Estos deben estar localizados uno al lado del otro, en un lado del
tanque del transformador. Visto desde el frente, el compartimento
de baja tensin debe estar a la derecha.
Cada compartimento debe tener una puerta que se construya de
modo que se d acceso al compartimento de alta tensin slo
cuando est abierta la puerta del lado de baja tensin.
Los compartimentos sern accesibles solamente desde el interior.
El compartimento de MT presenta seis bornas enchufables sin
carga de 600 A, y el de BT, cuatro bornas de BT segn la
especificacin tcnica correspondiente.
El transformador contar con un indicador de nivel del aceite y
termmetro localizados en el compartimento de media tensin. As
mismo, contar con dos vlvulas, una de entrada para el relleno
del aceite, y otra de salida, para el vaciado, situadas tambin en el
compartimento de media tensin.
Adems incluir una vlvula de sobrepresin situada en el citado
compartimento de media tensin.
El cambio de voltaje se realizar por medio de un conmutador de
cinco posiciones manual localizado en la parte de MT.
La proteccin del transformador contra sobrecargas, se realizar
mediante un interruptor con proteccin termomagntica o similar,
instalado en el interior de la cuba y en el primario.
La proteccin contra cortocircuitos se realizar mediante fusible
interno de alto poder de ruptura tipo limitador de la intensidad
adecuada a la potencia del transformador y coordinado con el
interruptor termomagntico de proteccin contra sobrecargas.
La maniobra del transformador en carga se realizar mediante
prtiga, sobre el mando del interruptor termomagntico. Existe
tambin la posibilidad de operar en carga con prtiga los
conectores enchufables.

166

La maniobra de la lnea se realizar mediante un interruptor de


cuatro posiciones tipo T-Blade, sin corte en la lnea durante la
operacin y motorizable para su telecontrol. Este interruptor
permitir alimentar el transformador con la lnea cerrada,
alimentar el transformador por cada uno de los dos lados cuando
la lnea est abierta y tener la lnea cerrada y desconectado el
transformador.

S1

S2
S1/S2-T

S1

S2
S2-T

S1

S2

S1

S1/S2

S2
S1-T

13.2. CONEXIONES DE BAJA TENSIN


Las conexiones entre los transformadores y los puntos de
consumo que se realizarn como se indica en la tabla adjunta,
teniendo en cuenta las siguientes variantes:
a) Conexin trifsica entre las bornas de BT del transformador y el o
los interruptores de los puntos de consumo.

167

CASO 1

TRAN SFORMADOR

INTERRUPTOR

PUNTO DE CONSUMO

INTERRUPTOR

PUNTO DE CONSUMO 1
TRAN SFORMADOR
PUNTO DE CONSUMO 2

PUNTO DE CONSUMO 3

PUNTO DE CONSUMO 4

b) Conexin trifsica entre las bornas de BT del transformador y un


tablero de distribucin desde donde se har el reparto a distintos
puntos de consumo.

CASO 2

TRANSFORMADOR

TABLERO DISTRIBUCIN

c) Conexin monofsica entre las bornas de BT del transformador y el


o los interruptores generales de los puntos de consumo.

168

CASO 3

TRANSFORMADOR

INTERRUPTOR

PUNTO DE CONSUMO

INTERRUPTOR

PUNTO DE CONSUMO 1
TRANSFORMADOR
PUNTO DE CONSUMO 2

PUNTO DE CONSUMO 3

PUNTO DE CONSUMO 4

d) Conexin monofsica entre las bornas de BT del transformador y


un tablero de distribucin desde donde se har el reparto a
distintos puntos de consumo.

CASO 4

TRANSFORMADOR

TABLERO DISTRIBUCIN

169

Segn las posibles situaciones descritas y la potencia del


transformador, las secciones mnimas de los conductores de BT se
muestran en la Tabla 65.
Tabla 65. Nmero de conductores segn potencia de trafo

N DE CONDUCTORES X TIPO DE CONDUCTOR BT


POTENCIA (kVA)
FASES

NEUTRO

TRANSFORMADOR TRIFSICO. (Punto 1)


2 X 500 MCM

2 X 500 MCM

3 X 4/0 AWG

3 X 4/0 AWG

300

3 X 500 MCM

3 X 500 MCM

500

5 X 500 MCM

5 X 500 MCM

750

8 X 500 MCM

8 X 500 MCM

150

TRANSFORMADOR MONOFSICO (punto 3)


3 X 1/0 AWG

3 X 1/0 AWG

2 X 4/0 AWG

2 X 4/0 AWG

4 X 4/0 AWG

4 X 4/0 AWG

3 X 500 MCM

3 X 500 MCM

4 X 500 MCM

4 X 500 MCM

50

100
167

En caso de conexiones, tanto trifsicas como monofsicas, entre


las bornas de BT del transformador y un tablero de distribucin,
la seccin total del neutro puede reducirse como se muestra en
la Tabla 66.

170

Tabla 66. Secciones de neutro segn trafo

N DE CONDUCTORES X TIPO DE CONDUCTOR BT


POTENCIA (kV A)
FASES

NEUTRO

TRANSFORMADOR TRIFSICO. (Punto 2)


150

2 X 500 MCM

1 X 500 MCM

300

3 X 500 MCM

2 X 500 MCM

500

5 X 500 MCM

3 X 500 MCM

750

8 X 500 MCM

4 X 500 MCM

TRANSFORMADOR MONOFSICO (punto 4)


50

2 X 4/0 AWG

1 X 4/0 AWG

100

3 X 500 MCM

2 X 500 MCM

167

4 X 500 MCM

2 X 500 MCM

En cualquier caso de los expuestos, se intentar que la


canalizacin de las lneas de BT se haga de manera que por cada
tubo vaya una terna completa.

13.3. CENTROS DE SECCIONAMIENTO


13.2.1. Seccionamiento Simple Tipo Pad-Mounted 3L1.
El seccionamiento simple tiene tres posiciones de lnea, dos para
entrada y salida de la lnea principal con tres bornas atornillables
sin carga de 600 A cada una, y la tercera, para derivada, con tres
pasatapas tipo pozo, previstas para borna insertable en carga de
200 A, simple o doble.
Las separaciones entre bornas y la disposicin de los parking
han sido previstas para la utilizacin de borna insertable doble
para el caso de dos derivaciones en paralelo.
El centro de seccionamiento contar con un indicador de nivel del
aceite. As mismo, contar con dos vlvulas, una de entrada para
el relleno del aceite, y otra de salida, para el vaciado.
Adems incluir una vlvula de sobrepresin.

171

La operacin de la lnea general y derivacin se realizar


mediante un interruptor de cuatro posiciones tipo T-Blade, sin
corte en la lnea durante las maniobras y motorizable para su
telecontrol. Este interruptor permitir dar alimentacin a la
derivacin con la lnea cerrada, alimentar la derivacin por cada
uno de los dos lados cuando la lnea est abierta, y tener
desconectada la derivacin cuando la lnea est cerrada.

13.2.2. Seccionamiento de Tres Posiciones Tipo Pad-Mounted 3L3.


El seccionamiento de tres posiciones 3L3 es metlico con tres
posiciones de lnea, con tres bornas atornillables sin carga de
600 A por lnea.
El centro de seccionamiento contar con un indicador de nivel de
aceite. As mismo, contar con dos vlvulas, una de entrada para
el relleno del aceite, y otra de salida, para el vaciado.
Adems incluir una vlvula de sobrepresin.
La operacin de cada lnea se realizar mediante un interruptor
de tres posiciones Abierto-Cerrado-Tierra, motorizable para su
telecontrol y sumergido en aceite aislante, expuesto en la
siguiente figura:

C
B

600 A

C
A

600 A

C
A

600 A

13.2.3. Seccionamiento de Cuatro Posiciones Tipo Pad-Mounted 4L4.


El seccionamiento de cuatro posiciones 4L4 es metlico con
cuatro posiciones de lnea, con tres bornas atornillables sin
carga de 600 A por lnea.

172

El centro de seccionamiento contar con un indicador de nivel de


aceite. As mismo, contar con dos vlvulas, una de entrada para
el relleno del aceite, y otra de salida, para el vaciado.
Adems incluir una vlvula de sobrepresin.
La operacin de cada lnea se realizar mediante un interruptor
de tres posiciones Abierto-Cerrado-Tierra, motorizable para su
telecontrol y sumergido en aceite aislante.
C
B

600 A

C
A

600 A

C
A

600 A

C
A

600 A

13.2.4. Seccionamiento de Tres Posiciones 3L3 Con Envolvente De


Hormign.
El seccionamiento de tres posiciones 3L3 con envolvente
metlica consistir en tres celdas de lnea modulares o
compactas, con tres bornas atornillables sin carga de 600 A por
lnea, dentro de una envolvente prefabricada de hormign
armado.
El aislamiento ser en SF6.
La operacin de cada lnea se realizar mediante un interruptorseccionador de tres posiciones, que permite comunicar el
embarrado del conjunto de celdas con los cables, cortar la
corriente asignada, seccionar esta unin o poner a tierra
simultneamente las tres bornas de los cables de Media Tensin.
Cada celda tendr un indicador de presencia/no presencia de
tensin.
13.2.5. Seccionamiento de Cuatro Posiciones 4L4 Con Envolvente De
Hormign.
El seccionamiento de cuatro posiciones 4L4 con envolvente
metlica consistir en cuatro celdas de lnea modulares o
compactas, con tres bornas atornillables sin carga de 600 A por

173

lnea, dentro de una envolvente prefabricada de hormign


armado.
El aislamiento ser en SF6.
La operacin de cada lnea se realizar mediante un interruptorseccionador de tres posiciones, que permite comunicar el
embarrado del conjunto de celdas con los cables, cortar la
corriente asignada, seccionar esta unin o poner a tierra
simultneamente las tres bornas de los cables de Media Tensin.
Cada celda tendr un indicador de presencia/no presencia de
tensin.

174

14 DISPOSICIN DE LA INSTALACIN DE CENTROS DE


TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO
14.1. UBICACIN
La ubicacin del CT y CS se determinar de acuerdo entre el
peticionario y Gas Natural Fenosa, teniendo en cuenta las
consideraciones de orden elctrico y otras relacionadas con la
explotacin y mantenimiento de dicho Centro.
Tanto el CT como el CS pueden ser:
a) De exterior: situado en espacios abiertos entre edificios, zonas
ajardinadas, etc.
b)

De interior: cuando se aloja en el interior de un edificio destinado


a otros fines en local reservado exclusivamente para su
instalacin.
Debiendo en cualquier caso cumplir lo siguiente respecto a su
ubicacin:

En caso de que el Centro sea subterrneo, el nivel fretico ms


alto se encontrar a 0,3 m por debajo del nivel inferior de la
solera ms profunda del Centro. Si no fuera as, se tomarn las
medidas oportunas para evitar problemas de humedades
(impermeabilizacin de CT, drenajes perimetrales, etc.).
En el caso de ubicacin en edificio para otros usos no podr
instalarse por debajo del primer stano, y tendr unas
condiciones de estanqueidad al agua de paredes, techos,
cubierta y suelo anlogas a las de un edificio destinado a
vivienda.
El paramento de la puerta, estar situado preferentemente en
lnea de fachada a una va pblica o privada, debiendo
cumplirse las condiciones de acceso del apartado 14.2.
14.2. ACCESOS
Como norma general se podr acceder al CT o al CS desde la va
pblica, o desde una va privada siendo sta accesible con su
correspondiente servidumbre de paso.
La ubicacin y los accesos debern permitir:

175

El movimiento y colocacin de los elementos y maquinaria


necesarios para la realizacin adecuada de la instalacin con
los medios disponibles.
Ejecutar las maniobras propias de su explotacin en
condiciones ptimas de seguridad para las personas que lo
realicen.
El mantenimiento y sustitucin del material que compone el
mismo.
El acceso al interior tanto del CT como del CS ser exclusivo para
el personal de Gas Natural Fenosa. Cuando este acceso tenga que
efectuarse forzosamente a travs de trampillas, etc., no podr
situarse en zona que haya de dejarse permanentemente libre,
tales como paso de bomberos, salidas de urgencia o socorro, etc.
Para permitir un desplazamiento y manejo fciles de elementos
pesados del Centro, los accesos por va privada tendrn la
correspondiente sealizacin de prohibido aparcar.
El emplazamiento elegido para el Centro, deber permitir el
tendido, a partir de las vas pblicas o galeras de servicio, de las
canalizaciones subterrneas. Todos los cables subterrneos
podrn tenderse hasta una profundidad de 0,6 m, como mnimo.
No se permitirn emplazamientos que obliguen a cruzar espacios
privados o comunes situados en el interior de la edificacin.

14.3. INSTALACIN DE EXTERIOR.


Los centros de transformacin y centros de seccionamiento de
exterior que se realizarn sern los siguientes:

Centros de transformacin tipo pad-mounted (monofsico,


trifsico fin de lnea y trifsico de entrada y salida) con
envolvente metlica.
Centros de seccionamiento tipo pad-mounted (3L1, 3L3 y 4L4)
con envolvente metlica.
Centros de seccionamiento con celdas en SF6 (3L3 y 4L4) con
envolvente de hormign.

14.3.1. Foso de Recogida de Aceite


En centros de transformacin o seccionamiento de exterior, se
dispondr de pozo de recogida de aceite, con revestimiento

176

resistente al fuego y estanco, que tengan la resistencia estructural


adecuada para las condiciones de empleo.
Para su diseo y dimensionamiento, se tendr en cuenta el volumen
de aceite que pueda recibir. En dicho depsito o cubeta se
dispondrn cortafuegos tales como: lechos de guijarros, sifones en
el caso de instalaciones con colector nico, etc.
El foso podr suprimirse siempre que:

La tierra contaminada pueda retirarse fcilmente, y no haya


riesgo de que el aceite aislante pueda derramarse en cauces
superficiales o subterrneos o canalizaciones de abastecimiento
de aguas o de evacuacin de aguas residuales.

El lquido aislante sea totalmente biodegradable.

14.3.2. Distancias de Seguridad


14.3.2.1.

Espacio mnimo libre para trabajo e inspeccin

Como mnimo una distancia de 2 metros delante de la zona frontal


del Centro, debe estar libre de obstculos para poder realizar la
apertura de las puertas, y cualquier tarea normal de maniobra.
Anlogamente, debe existir alrededor del Centro un espacio libre
mnimo de 0,6 metros de distancia a las paredes de la envolvente
metlica del Centro, para poder realizar inspecciones del mismo.
En zonas de aparcamiento de vehculos, cuando el CS o el CT se
encuentren prximos al borde de la calzada, y pueda sufrir por
ello riesgo de golpes por vehculos durante la maniobra de
aparcamiento, se colocarn pilares de proteccin para delimitar la
zona de trabajo e inspeccin mnima, y proteger asimismo el
Centro. Estos pilares tendrn una separacin mxima de 1,5
metros que impida la entrada de un vehculo entre ellos, y distarn
del borde de la acera, como mnimo 20 cm, para evitar as, la
colisin de los pilares y los vehculos al estacionar. La altura de
los pilares ser al menos de 1 metro.

177

14.3.2.2.

Distancia a edificios

0,6 m

0,6 m

0,6 m

MAX. 1,5 m

2m
0,2 m

0,2 m
Se debe guardar como mnimo, una distancia de 60 cm entre la
parte posterior y lateral del CT o el CS, y la pared del edificio ms
cercano.
14.3.2.3.

Distancia a puertas y ventanas

Cualquier punto del CT o del CS se encontrar a una distancia


horizontal mnima de 2 metros de una puerta o acceso de
personas.
Cuando el Centro est situado a una distancia del edifico entre 0,6
y 2 m respecto a las paredes trasera o lateral del CT o CS, no se
podr abrir hueco alguno (puerta o ventana) a una altura inferior a
6 metros sobre el nivel del suelo. Esta distancia no necesita
cumplirse, en caso de que el CT y el CS:
No contenga aceite,
El aceite tenga una resistencia a la flamabilidad superior a 300
C.
Se encuentre separado de la pared, ms de 2 metros.

178

6m

2m

2m

2m

0,6 - 2 m

14.3.2.4.

Distancia a bordillos

La distancia mnima que debe existir entre un bordillo situado


paralelo y frente a las puertas de acceso al CT o al CS, ser de 2
metros, con la intencin de mantener el rea mnima de
maniobra. Esta distancia ser de 0,6 metros respecto de las
paredes laterales y posteriores.

179

14.3.2.5.

Distancia a escaleras

Cualquier punto del CT o del CS se encontrar a una distancia


mnima de 2 metros del acceso a una escalera.
14.3.2.6.

Distancia a depsito de combustible

Un depsito de combustible debe encontrarse como mnimo, a una


distancia de 6 metros de cualquier punto del CT o del CS.

14.3.2.7.

Distancia a contenedores de basura.

Tanto los CT como los CS, deben guardar una distancia mnima de
5 metros entre las puertas de acceso al Centro y los contenedores
de basura, pudindose reducir dicha distancia a 0,7 metros en caso
de existir una pared o muro entre ambos, respetando los 0,6 m de
inspeccin entre el muro y las paredes lateral y posterior de CS o
CT. La altura del muro de separacin ser al menos 20 cm
superior a la altura mxima entre el CS o CT, y el contenedor de
basuras.
14.3.3. Plataforma
La plataforma de hormign para los CT y CS tipo pad-mounted
tendr una altura no menor a 10 cm sobre el nivel del suelo o piso
terminado. El borde de la plataforma ser como mnimo de 10 cm
ms de la planta del equipo.

14.3.4. Caractersticas Constructivas de la Envolvente de Hormign


para Centros de Seccionamiento en SF6.
El material a emplear en la fabricacin ser hormign armado,
que tendr una resistencia a la compresin a los 28 das igual o
superior a 250 kg/cm2.
Todas las partes de hormign prefabricadas que constituyen
envolvente, tendrn grabadas la marca del fabricante y su ao de
fabricacin.
La presin que la envolvente ejerza sobre el terreno no exceder
de 1 kg/cm2.
El piso ser capaz de soportar sobrecargas verticales de 400
kg/m2.

180

Las paredes sern capaces de soportar los esfuerzos verticales de


su propio peso, ms el de la cubierta y las sobrecargas de sta,
simultneamente con una presin horizontal de 100 kg/m2.
La cubierta ser capaz de soportar sobrecargas de 100 kg/m2.
Estarn diseadas de forma que impidan la acumulacin de agua
sobre ellas y desagen directamente al exterior desde su
permetro. Se construir de manera que se consiga una perfecta
estanqueidad que evite todo riesgo de filtraciones.
Los materiales externos que constituyan la envolvente sern
resistentes a las variaciones de temperatura y a los rayos
ultravioletas.
Las puertas sern abatibles a 180, y con sistema de bloqueo a
90.
Los grados de proteccin de la parte exterior de la envolvente ser
IP 239.
14.4. INSTALACIN DE INTERIOR
Los centros de transformacin y centros de seccionamiento de
interior que se realizarn sern los siguientes:

Centros de transformacin tipo pad-mounted (monofsico,


trifsico fin de lnea y trifsico de entrada y salida) con
envolvente metlica.
Centros de seccionamiento tipo pad-mounted (3L1, 3L3 y 4L4)
con envolvente metlica.
Centros de seccionamiento con celdas en SF6 (3L3 y 4L4).

14.4.1. Foso de Recogida de Aceite


En los centros de transformacin o seccionamiento que contengan
aceite mineral u otro lquido refrigerante, se dispondr de un
sistema de recogida del mismo para caso de derrame. Para ello se
proceder como sigue:

Bajo el depsito o cuba que contiene el aceite refrigerante el


suelo dispondr de la una pendiente mnima de 2 % para que
el lquido derramado vierta hacia el sumidero. Este estar
comunicado
al depsito de recogida mediante una
canalizacin adecuada.

181

Entre el sumidero y el depsito se instalar una pantalla


cortafuegos a base de lechos de guijarros, sifones en el caso
de instalaciones con colector nico, etc.

Tanto la canalizacin como el depsito de recogida estarn


construidos con revestimiento resistente al fuego y sern
estancos.

El depsito de recogida puede estar ubicado inmediatamente


debajo del transformador, o en otro lugar unido al sumidero
mediante la correspondiente canalizacin.

Cuando el lquido contenido en el transformador o centro de


seccionamiento exceda los 50 litros, se exigir un grado de
flamabilidad igual o superior a 300 C. No podrn utilizarse
lquidos que contengan PCB.

14.4.2. Distancias de Seguridad


14.4.2.1.

Espacio mnimo libre para trabajo e inspeccin

Las dimensiones del Centro debern permitir:


a) El movimiento y colocacin en su interior de los elementos y
maquinaria necesarios para la realizacin adecuada de la
instalacin elctrica.
b) La ejecucin de las maniobras propias de su explotacin y
operaciones de mantenimiento en condiciones ptimas de
seguridad para las personas que lo realicen.
Como mnimo una distancia de 2 metros delante a la zona frontal
del Centro, debe estar libre de obstculos para poder realizar la
apertura de las puertas, y cualquier tarea de operacin. Esta
distancia se puede reducir siempre que con las puertas del local
abiertas, se asegure la misma superficie libre de maniobra y
permita la apertura de las puertas del Centro.
La distancia mnima de las paredes del recinto a la parte posterior
y los laterales del Centro, ser de 0,6 metros.
14.4.3. Caractersticas Constructivas
El CT y el CS debern cumplir las siguientes condiciones:

No contendrn canalizaciones ajenas al Centro, tales como


agua, aire, gas, telfonos, etc.

182

Sern construidos
combustibles.

14.4.3.1.

enteramente

con

materiales

no

Comportamiento ante el fuego

Los elementos delimitadores del Centro (muros, tabiques,


cubiertas, etc.), as como los estructurales en l contenidos (vigas,
pilares, etc.) tendrn una resistencia al fuego adecuada. Esto
supone cumplir las siguientes exigencias en ese intervalo de
tiempo:
a) Estabilidad o capacidad portante
b) Ausencia de emisin de gases inflamables por la cara
expuesta
c) Estanqueidad al paso de llamas o gases calientes
d) Resistencia trmica
En la

183

Tabla 67 se presentan los grosores del muro o tabique necesarios


en funcin de distintos materiales, para conseguir la resistencia al
fuego necesaria.
Para soluciones constructivas con dos o ms hojas puede
adoptarse como valor de resistencia al fuego del conjunto la suma
de los valores correspondientes a cada hoja.
14.4.3.2.

Muros o tabiques de cierre del local

Se construirn de forma que sus caractersticas mecnicas estn


de acuerdo con el resto del edificio. Para el dimensionamiento de
los espesores, tambin se tendr en cuenta lo expuesto en el
apartado 3.4.6 (condiciones acsticas) cuando se trate de
separaciones con otros locales.

184

Tabla 67. Resistencia al fuego de materiales

RESISTENCIA AL FUEGO (RF)

Material
Hormign sin revestir
Ladrillo macizo revestido por la cara interior
Bloque de hormign silicio con cmara doble.
Revestimiento interior
Bloque de hormign volcnico con cmara doble.
Revestimiento interior
Ladrillo
interior
Ladrillo cermico hueco doble pared.
Cmara
Revestimiento interior con cmara.
Ladrillo
exterior

14.4.3.3.

Espesor
min. del
muro
(cm)
16
12
20
20
8
4
12

Forjado superior

En el caso de que el Centro est ubicado de forma que sobre l se


prevean cargas excepcionales (zonas de circulacin o
aparcamiento de vehculos) las caractersticas mecnicas se
adecuarn a estas circunstancias.
14.4.3.4.

Suelo

El acabado de la solera se har con una capa de mortero de


cemento de una composicin adecuada para evitar la formacin de
polvo y ser resistente a la abrasin, estar elevada 0,2 metros
sobre el nivel mximo de aguas exterior conocido cuando ste sea
inundable.
Al realizar el suelo y, en general la obra civil, se deber tener en
cuenta el empotramiento de herrajes, colocacin de tubos,
registros, canalizaciones de cables, mallas de tierra, etc.
14.4.3.5.

Acabados

El acabado de la albailera tendr las caractersticas siguientes:

Parmetros interiores: raseo con mortero de cemento


fratasado y pintado, estando prohibido el acabado con yeso.

185

Parmetros exteriores: se realizar de acuerdo con el resto


del edifico.
El pavimento ser de cemento continuo bruido y ruleteado.

El acabado de los elementos metlicos que intervengan en la


construccin del Centro deber garantizar un adecuado
comportamiento frente a la oxidacin.
14.4.3.6.

Carpintera y cerrajera

La carpintera podr ser metlica de la suficiente rigidez, y


protegida mediante galvanizado en caliente, u otro recubrimiento
antioxidante. Asimismo, podr ser de material orgnico, tal como
polister con fibra de vidrio, resistente a la intemperie. Su
resistencia mecnica ser la adecuada a su situacin y a la
ubicacin y caractersticas de Centro.
El local del Centro contar con los dispositivos necesarios para
permanecer habitualmente cerrado, evitando el acceso a personas
ajenas al servicio.
Los elementos delimitadores del Centro, puertas, ventanas,
rejillas, etc., tendrn una resistencia adecuada al fuego.
14.4.3.7.

Escaleras

El acceso para el personal a Centros subterrneos, se podr


realizar mediante una escalera, con separacin de peldaos no
superior a 25 cm, constituida por perfiles metlicos u otro material
suficientemente resistente.
14.4.4. Canalizaciones
Las canalizaciones subterrneas enlazarn con el CS o el CT de
forma que permitan el tendido directo a cables a partir de la va de
acceso o galera de servicios.
Los cables de alta tensin entrarn bajo tubo en el Centro,
llegando por canal o tubo. Estos tendrn superficie interna lisa.
En los tubos no se admitirn curvaturas. En los canales, los radios
de curvatura sern como mnimo de 0,60 m.
De acuerdo con este Documento, las bocas de los tubos se
sellarn mediante espuma de poliuretano expandido tanto si llevan
cables como si son tubos de reserva para cables futuros.

186

En los CT, se establecer un sistema de fosos o canales, para


facilitar el acceso de los cables de alta tensin a los terminales del
Centro.
14.4.5. Puertas
Las puertas sern de 2 metros de ancho. Se abrirn hacia el
exterior un ngulo de al menos 90 grados, y cuando lo hagan
sobre vas pblicas, se debern poder abatir sobre el muro de la
fachada reduciendo al mnimo el saliente.
As mismo estarn equipadas con un mecanismo de enclavamiento
capaz de mantenerlas en posicin abierta a 90.
En los Centros subterrneos, la trampilla de acceso de personal,
cuando se encuentre abierta, incorporar una barandilla
perimetral para proteccin de los transentes.
14.4.6. Condiciones Acsticas
Los Centros tendrn un aislamiento acstico de forma que no
transmitan niveles sonoros superiores a los permitidos en las
distintas legislaciones de la zona.
Caso de sobrepasar estos lmites, se tomarn medidas
correctoras, tales como sobredimensionar los espesores de los
muros o tabiques de separacin del Centro y/o emplear
amortiguadores para aislar las vibraciones producidas por el
transformador.
14.4.7. Ventilacin
Para la renovacin del calor generado en el interior del CT, deber
posibilitarse una circulacin de aire.
Cuando se prevean transmisiones de calor en ambos sentidos de
las paredes y/o techos que puedan perjudicar a los locales
colindantes o al propio CT, debern aislarse trmicamente estos
cerramientos.
Las rejas de ventilacin debern situarse en fachada o va pblica,
nunca hacia un patio de luces o zona cerrada que acte como
chimenea en caso de incendio.
Rejillas para ventilacin: los huecos de ventilacin tendrn un
sistema de rejillas que impidan la entrada de agua y en su caso,
tendrn una tela metlica que impida la entrada de insectos.

187

Estarn constituidos por un marco y un sistema de lamas o


angulares, con disposicin laberntica y resistencia adecuada para
garantizar el grado de proteccin IP 339.
La ventilacin de los locales ser preferentemente por conveccin
natural. Solamente en casos excepcionales se admitir la
ventilacin forzada.
14.4.7.1.

Ventilacin natural

Para renovacin del aire en el interior de CT, se establecern


huecos de ventilacin que permitan la admisin de aire fro del
exterior, situndose stos en la parte inferior prxima a
transformadores.
La evacuacin del aire caliente, (en virtud de su menor densidad)
se efectuar mediante salidas situadas en la parte superior de los
CT.
Los huecos de ventilacin de entrada y salida de aire estarn a una
altura mnima sobre el suelo de 0,30 y 2,30 m respectivamente,
con una separacin vertical de 1,30 m.
Se mantendr una distancia mnima de 2 metros entre el Centro y
las rejillas de Ventilacin.
14.4.7.2.

Ventilacin forzada

Cuando por caractersticas de ubicacin del Centro, sea imposible


la ventilacin natural, ya sea porque no pudiera disponerse de
estas superficies para ventilacin natural, excepcionalmente, se
instalar un sistema de ventilacin forzada que garantizar el
caudal de aire necesario para la evacuacin del calor del Centro.
Se mantendr una distancia mnima de 2 metros entre el sistema
de aire acondicionado y el Centro.
En el sistema de ventilacin forzada se respetarn las condiciones
acsticas expuestas en el apartado 14.4.6.
Los conductos de ventilacin forzada del CT, debern ser
totalmente independientes de otros conductos de ventilacin del
edificio.

188

14.4.8. Equipotencialidad
El Centro, cuando las operaciones de explotacin y mantenimiento
se realicen desde el interior del mismo, estar construido de
manera que su interior presente una superficie equipotencial. Para
ello se seguirn las instrucciones siguientes:
14.4.8.1.

Piso

En el piso, a una profundidad mxima de 0,10 m, se instalar un


enrejado de hierros redondos de 4 mm de dimetro como mnimo,
formando malla no mayor de 0,30 x 0,30 m, nudos soldados.
Dicha malla se unir elctricamente a la lnea de tierra de las
masas mediante soldadura.
14.4.8.2.

Puertas y rejillas

Las puertas y rejillas metlicas que den al exterior del Centro,


sern recibidas en la pared de manera que no exista contacto
elctrico con las masas conductoras interiores, incluidas
estructuras metlicas de la albailera. Las rejillas estarn
solamente incluidas en el caso de centros de transformacin.
Si la estructura del muro exterior est armada y las puertas y
rejillas son metlicas, se instalar un piso no conductor en el
exterior, delante de las mismas, hasta 1 metro de distancia.
Se podr omitir la superficie no conductora si el piso exterior del
Centro est unido equipotencialmente al piso de ste, en cuyo
caso la transferencia de tensiones a otros puntos alejados del
Centro tendr que ser especialmente considerada al proyectar.
14.4.8.3.

Muros exteriores

Los muros entre sus paramentos, al mes de su construccin,


tendrn una resistencia mnima de 10.000 ohmios. La medicin de
esta resistencia se realizar aplicando una tensin de 500 V entre
dos placas de 200 cm2 cada una.
En el caso de existir en el paramento interior armadura metlica,
sta estar unida a la estructura metlica del piso.
Cuando se quiera prever la existencia de transmisiones de
tensiones elctricas, las paredes sern de doble tabique con
cmara de separacin, o en su defecto, el pavimento exterior
estar realizado con revestimiento aislante (asfalto, betunes, etc.).

189

La superficie mnima de revestimiento ser tal que cualquier punto


de su permetro diste, por lo menos 1 m de la pared.
Ningn herraje o elemento metlico unido al sistema equipotencial
podr ser accesible desde el exterior del local.
14.4.9. Sealizaciones de Seguridad
Los Centros cumplirn con las siguientes prescripciones:
a) La puerta de acceso al Centro llevar la marca registrada de la
empresa en el pas.
Las puertas de acceso al Centro llevarn el cartel de con la
correspondiente seal triangular distintiva de riesgo elctrico.
b) En un lugar bien visible del interior del Centro se situar un cartel
de instrucciones de primeros auxilios a prestar en caso de
accidente y su contenido se referir a la respiracin boca a boca y
masaje cardiaco. Su tamao ser como mnimo DIN A-3.
c) Salvo que en los propios aparatos figuren las instrucciones de
maniobra, en el CT, y en lugar correspondiente habr un cartel con
citadas instrucciones.
No ser necesario que los Centros estn equipados con prtiga, si
la prtiga a utilizar es nica en el equipamiento habitual de los
equipos de operaciones.

190

15 INSTALACIN DE PUESTA A TIERRA DE CENTROS


TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO
El CT y el CS estarn provistos de una instalacin de puesta a
tierra, con objeto de limitar las tensiones de defecto a tierra que se
pueden originar en la propia instalacin. Esta instalacin deber
asegurar la descarga a tierra de la intensidad de defecto,
contribuyendo, de esta manera, a la eliminacin del riesgo
elctrico debido a la aparicin de tensiones peligrosas de paso y de
contacto con las masas eventualmente en tensin.
15.1. SISTEMAS DE PUESTA A TIERRA
Se conectarn a una instalacin de tierra general (de proteccin y
de servicio), los siguientes elementos:

Envolturas o pantallas metlicas de los cables.


Cuba metlica de los transformadores
Pararrayos de alta tensin si los hubiera.
Bornas de tierra de detectores de tensin.
Neutro del transformador.
Bornas para la puesta a tierra de los dispositivos porttiles
de puesta a tierra.
Envolvente metlica

15.2. ELEMENTOS CONSTITUTIVOS DE LOS SISTEMAS DE PUESTA A


TIERRA
Los elementos que constituyen el sistema de puesta a tierra en
Centro son:
a) Lnea de tierra
b) Electrodos de puesta a tierra
15.2.1. Lneas de Tierra.
Estarn constituidas por conductores de cobre o su seccin
equivalente en otro tipo de material. En funcin de la intensidad de
defecto y la duracin del mismo, las secciones mnimas (S) del
conductor a emplear por cada lnea de tierra a efectos de no
alcanzar una temperatura elevada se deducirn a partir de la
expresin:

Id
t

191

donde:
Id = Intensidad de defecto en Amperios
t = Tiempo de duracin de la falta en segundos.
(para t 5 seg.) = 4,5 para conductor de acero
(para t 5 seg.) = 13 para conductor de cobre.
= 160 C para conductor aislado
= 180 C para conductor desnudo
Se tomar 16 kA como valor mximo de la intensidad de defecto
para niveles de tensin de 13,2 kV, y 12,5 kA para 34,5 kV. Se
considerar un tiempo mximo de duracin de la falta de 0,1 s
0,2s.
Con estos datos se obtienen los resultados que se muestran en la
Tabla 68.
Tabla 68. Intensidades de defecto segn nivel de tensin y tipo de
conductor

CONDUCTOR AISLADO

(C)
160
160
160
160

t (s)
0,1
0,1
0,2
0,2

Idefecto (kA)
16
12,5
16
12,5

Tensin (kV)
13,2
34,5
13,2
34,5

Seccin (mm2)
30,8
24
43,5
34

CONDUCTOR DESNUDO

(C)
180
180
180
180

t (s)
0,1
0,1
0,2
0,2

Idefecto (kA)
16
12,5
16
12,5

Tensin (kV)
13,2
34,5
13,2
34,5

Seccin (mm2)
29,0
22,6
41,0
32

A la vista de los resultados mostrados en la tabla, la seccin del


conductor de tierra mnimo a utilizar dentro de las secciones
normalizadas para conductores aislados como para desnudos, ser
de seccin #2 AWG (33,62 mm2) de cobre, en caso de que la
duracin de la falta sea 0,1 s. Si la duracin de falta fuera de 0,2 s,
la seccin mnima a utilizar para 13,2 kV sera 1/0 AWG (53,51 mm2).

192

15.2.2. Electrodo de Puesta a Tierra


Estarn constituidos por cualquiera de los siguientes elementos:
a) Conductores enterrados horizontalmente
b) Picas (Picas de acero con recubrimiento de cobre).
15.3. CONDICIONES DE INSTALACIN DE LOS ELECTRODOS
Las picas se hincarn verticalmente quedando la parte superior a
una profundidad no inferior a 0,5 m.
Los electrodos horizontales se enterrarn a una profundidad igual
a la parte superior de las picas.
El valor mnimo de la superficie total del electrodo ser tal que la
densidad de corriente disipada (que es igual al cociente entre la
intensidad de defecto y la superficie total del electrodo de puesta a
tierra) sea inferior al valor dado por la expresin:

11600

(A/m2)

en la que:

: Densidad de corriente disipada (A/m2).


: Resistividad del terreno (m).
t: Tiempo de duracin del defecto (s).
Los resultados de este clculo para diferentes tipos de terreno se
presentan en la Tabla 69.

193

Tabla 69. Densidad de corriente segn terreno

TIPO DE TERRENO
Terreno pantanoso
Arcilla plstica
Arena arcillosa
Arena silcea
Suelo pedregoso
cubierto de csped
Suelo pedregoso
desnudo
Calizas blandas
Calizas compactas
Pizarra
Rocas de mica y cuarzo

(m)

t (s)

DENSIDAD DE
CORRIENTE
(A/m2)

5-30

16404-6697

50

5187

50-500

5187-1640

200-3000

2593-669

300-500

2117-1640
0,1

1500-3000

947-669

100-300

3668-2117

1000-5000

1160-518

50-300

5187-2117

800

1296

15.4. EJECUCIN DE LA PUESTA A TIERRA


En el caso de Centros de exterior, la base del Centro estar
rodeada por un electrodo horizontal compuesto por un conductor
de seccin adecuada, de forma cuadrada o rectangular a una
distancia mnima del Centro de 0,5 metros, complementado con un
nmero suficiente de picas para conseguir la resistencia de tierra
prevista, procurando que la separacin entre las picas sea al
menos 1,5 veces la longitud de las mismas.
En la instalacin de puesta a tierra de masas y elementos a ella
conectados, se cumplirn las siguientes condiciones:
a) Llevarn un borne accesible para la medida de la resistencia
de tierra.
b) Todos los elementos que constituyen la instalacin de puesta a
tierra, estarn protegidos, adecuadamente, contra deterioros
por acciones mecnicas o de cualquier otra ndole.
c) Los elementos conectados a tierra, no estarn intercalados en
el circuito como elementos elctricos en serie, sino que su
conexin al mismo se efectuar mediante derivaciones
individuales.
d) Para asegurar el correcto contacto elctrico de todas las
masas y la lnea de tierra, se verificar que la resistencia
elctrica entre cualquier punto de la masa o cualquier
elemento metlico unido a ella y el conductor de la lnea de
tierra, en el punto de penetracin en el terreno, ser tal que el

194

producto de la misma por la intensidad de defecto mxima sea


igual o inferior a 50 V.
e) En caso de CS en caseta prefabricada de hormign, no se unir
a la instalacin de puesta a tierra, ningn elemento metlico
situado en los paramentos exteriores.
La lnea de tierra del neutro de baja tensin, se instalar siempre,
antes del dispositivo de seccionamiento de baja tensin (si lo
hubiera) y preferentemente partiendo de la borna del neutro del
transformador o junto a ella.
15.5. MEDIDAS ADICIONALES DE SEGURIDAD PARA LAS TENSIONES
DE PASO Y CONTACTO.
Adems de las resistencias de puesta a tierra anteriormente
exigidas, las instalaciones de tierra se han de realizar de forma
que no se superen los valores de las tensiones mximas de paso y
contacto indicados en la publicacin IEEE Gua para la seguridad
en la puesta a tierra en subestaciones de corriente alterna, es
decir:
Vp

Vc

157 6 s
1
(V)
ts 1000

157 1,5 s
1
(V)
ts 1000

Siendo:
Vp: Tensin de paso mxima admisible (V).
Vc: Tensin de contacto mxima admisible (V).
ts: Duracin de la corriente de cortocircuito (s).

s: Resistividad superficial del terreno (m).

Se ha de tener en consideracin la Tabla 70:

195

Tabla 70. Consideraciones para tensiones de paso y contacto

PROCEDIMIENTO
1 Reducir el valor de la
resistencia de puesta a tierra,
aumentando la longitud del
electrodo y/o disminuyendo la
resistividad del terreno.
2 Realizar aceras aislantes de
1 m de anchura mnima
3 Situar el punto superior del
electrodo a mayor profundidad
de 0, 50 m indicada en el
apartado 4.3

EFECTO SOBRE

Tensiones de paso y contacto

Tensin de contacto

Tensin de paso

196

16 CLCULOS ELCTRICOS PARA CENTROS DE


TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO
16.1. INTENSIDADES NOMINALES
Las configuraciones empleadas para el clculo de las intensidades
nominales son las indicadas en los Criterios de Arquitectura de
Red de Gas Natural Fenosa.
Las intensidades en el secundario para un transformador trifsico
se calculan mediante la siguiente expresin:
Pn 103

(A)
U BT 3
Para un transformador monofsico, la intensidad nominal en el
secundario ser:
I BT

I BT

3 Pn 10 3
U BT

(A)

siendo:
IBT: Intensidad nominal de lnea en B.T. (A).
Pn: Potencia aparente nominal del transformador (kVA).
Ul: Tensin nominal secundaria entre fases del transformador (V).
Aplicando esta expresin obtenemos la Tabla 71 en funcin de la
tensin nominal entre fases de la lnea:
Tabla 71. Intensidades nominales en BT

Potencia nominal del


transformador monofsico
(kVA)
50
100
167
Potencia nominal del
transformador trifsico (kVA)
150
300
500
750

Intensidades nominales en el
circuito de B.T. 240 V (A)
361
722
1205
Intensidades nominales en el
circuito de B.T. 208 V (A)
417
833
1388
2082

197

De forma anloga, se obtienen las corrientes en el primario del


transformador.
Para un transformador trifsico se calculan mediante la siguiente
expresin:

I MT

Pn
U MT 3

(A)

Para un transformador monofsico, la intensidad nominal en el


primario ser:
I MT

Pn 3
U MT

(A)

donde:
IMT: Intensidad nominal que circula por el devanado primario (A).
Pn: Potencia aparente nominal del transformador (kVA).
UMT: Tensin nominal primaria de lnea (entre fases) del
transformador (kV).

Aplicando esta expresin obtenemos la Tabla 72 en funcin de la


tensin nominal entre fases de la lnea:
Tabla 72. Intensidades nominales para MT

POTENCIA
NOMINAL
DEL TRAFO
(kVA)
50
100
167
150
300
500
750

IN EN EL CIRCUITO DE M.T (A)


13,2 kV

34,5 kV

TRANSFORMADOR MONOFSICO
6,56
2,51
13,12
5,02
21,91
8,38
TRANSFORMADOR TRIFSICO
6,56
2,51
13,12
5,02
21,87
8,37
32,80
12,55

198

16.2. INTENSIDADES DE CORTOCIRCUITO


Para poder dimensionar y coordinar las protecciones para cada
configuracin y potencia se realizan los clculos de las
intensidades de cortocircuito en la salida del transformador.
La intensidad para cortocircuito en bornas de B.T. se calcula de la
siguiente forma:
Icc

100 In
(A)
Ucc

siendo:
Icc: Intensidad de cortocircuito (A).
In: Intensidad nominal (A).
Ucc: Tensin de cortocircuito (%). Se tomarn los valores
mostrados a continuacin:

Tabla 73. Tensiones de cortocircuito para transformadores

POTENCIA (kV)

TENSIN DE CORTOCIRCUITO (%)

TRANSFORMADOR MONOFSICO
3
3
5
TRANSFORMADOR TRIFSICO
150
4
300
5
500
5
750
5,75
50
100
167

199

De acuerdo con las potencias de los transformadores y sus


intensidades nominales se obtienen los resultados mostrados en
la Tabla 74.
Tabla 74. Intensidades de cortocircuito nominales en BT

Potencia nominal del


transformador monofsico
(kVA)
50
100
167
Potencia nominal del
transformador trifsico (kVA)
100
300
500
750

Intensidades de cortocircuito
en el circuito de B.T. 240 V
(A)
12 034
24 067
24 100
Intensidades de cortocircuito
en el circuito de B.T. 208 V
(A)
10 425
16 660
27 760
36 209

Estas corrientes de cortocircuito en el secundario, transfieren en


el primario como las corrientes de cortocircuito presentadas en la
Tabla 75.
Tabla 75. Intensidades de cortocircuito nominales en MT

POTENCIA
NOMINAL
DEL TRAFO
(kVA)
50
100
167
150
300
500
750

ICC EN EL CIRCUITO DE M.T. (A)


13,2 kV

34,5 kV

TRANSFORMADOR MONOFASICO
219
437
438
TRANSFORMADOR TRIFASICO
164
263
438
571

84
168
168
63
101
168
219

200

17 CONDICIONES ESPECFICAS PARA CENTROS DE


TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO
Este Pliego de Condiciones determina las condiciones mnimas
aceptables para la ejecucin de las obras de montaje de un centro
de transformacin o un centro de seccionamiento tipo padmounted.
Estas obras contemplan el suministro y montaje de los materiales
necesarios en la construccin del Centro, as como la puesta en
servicio de las mismas.
Los pliegos de condiciones particulares podrn modificar las
presentes prescripciones.
17.1. EJECUCIN DEL TRABAJO
Corresponde al Contratista la responsabilidad en la ejecucin de
los trabajos.
17.2. EMPLAZAMIENTO
El lugar elegido para la construccin del Centro debe permitir la
colocacin y reposicin de todos los elementos del mismo,
concretamente los que son pesados y grandes, como
transformadores. Los accesos al Centro deben tener las
dimensiones adecuadas para permitir el paso de dichos
elementos.
El emplazamiento del Centro debe ser tal que est protegido de
inundaciones y filtraciones.
En el caso de terrenos inundables el suelo del Centro debe estar,
como mnimo 0,20 m por encima del mximo nivel de aguas
conocido, o si no al Centro debe proporcionrsele una
estanqueidad perfecta hasta dicha cota.
El local que contiene el Centro debe estar construido en su
totalidad con materiales incombustibles.

201

17.3. EXCAVACIN
Se efectuar la excavacin con arreglo a las dimensiones y
caractersticas del Centro y hasta la cota necesaria indicada en el
Proyecto.
La carga y transporte a vertedero de las tierras sobrantes ser por
cuenta del Contratista.
17.4. CIMENTACIONES
Se realizarn de acuerdo con las caractersticas del Centro; si la
obra se fbrica de ladrillo, tendr normalmente una profundidad de
0,6 m. Esta podr reducirse cuando el Centro se construya sobre un
terreno rocoso. Por el contrario, si la consistencia del terreno lo
exige, se tomarn las medidas convenientes para que quede
asegurada la estanqueidad de la edificacin.
17.4.1. Arena
Puede proceder de ro, canteras, etc. Debe ser limpia y no
contener impurezas arcillosas u orgnicas. Ser preferible la que
tenga superficie spera y de origen cuarzos, desechando la de
procedencia de terrenos que contengan mica o feldespato.
17.4.2. Piedra
Podr proceder de canteras o de graveras de ro. Siempre se
suministrar limpia. Sus dimensiones podrn estar entre 1 y 5 cm.
Se prohbe el empleo de revoltn, es decir, piedras y arena unidas
sin dosificacin, as como cascotes o materiales blandos. En los
apoyos metlicos, siempre previa autorizacin de GAS NATURAL
FENOSA o del Director de Obra, podr utilizar hormign ciclpeo.
17.4.3. Cementos
El cemento ser de tipo Portland P-350.
En el caso de terreno yesoso se emplear cemento puzolnico.
17.4.4. Agua
Se emplear agua de ro o manantial sancionadas como
aceptables por la prctica, quedando prohibido el empleo de aguas
cinagas.

202

Deben rechazarse las aguas en las que se aprecie la presencia de


hidratos de carbono, aceites o grasas.
17.5. SOLERA
Para el caso de Centros de interior, los suelos sern de hormign
armado y estarn provistos para cargas fijas y rodantes que
implique el material.
Salvo los casos que el Centro disponga del pavimento adecuado, se
formar una solera de hormign incluido mallazo de reparto
apoyada sobre las fundaciones y descansando sobe una base de
grava. Esta solera estar cubierta por una capa de mortero de
cemento ruleteado. El hormign en masa ser de 150 kg/m2 de
resistencia caracterstica. Se prohbe el empleo de la arena de
escorias.
Se prevern, en los lugares apropiados del Centro, orificios para el
paso de interior al exterior del local de los cables destinados a la
toma de tierra de masas y de neutros de los transformadores y
cables de B.T. y
M.T. Los orificios estarn inclinados y
desembocarn hacia el exterior a una profundidad de 0,4 m del
suelo como mnimo.
Tambin se prevern los agujeros de empotramiento para herrajes
de equipo elctrico y el emplazamiento de los carriles de
rodamiento de los transformadores. As mismo, se tendrn en
cuenta los pozos de aceite, sus conductos de drenaje, las tuberas
de gres o similares para conductores de tierra, registros para las
toma de tierra y canales para los cables de M.T. y B.T.
En los lugares de paso los canales estarn cubiertos de losas
amovibles.
17.6. MUROS EXTERIORES
Los muros exteriores de los Centros de interior, estarn de
acuerdo con las caractersticas mecnicas del resto del edificio.
El revestido interior se realizar con mortero de cemento
Portland.
El acabado exterior del Centro ser de acuerdo con el resto del
edifico.

203

17.7. TABIQUES
Sern de ladrillo o de hormign armado. Los tabiques de ladrillo
de 8 cm de espesor como mnimo y los de hormign armado, se
constituirn de forma que sus cantos queden terminados con
perfiles U empotrados en los muros y en el suelo.
Al ejecutar los tabiques se tomarn las disposiciones convenientes
para prever los emplazamientos de los herrajes o el paso de
canalizaciones.
17.8. ENLUCIDO Y PINTURA
En los tabiques, orificios para empotramiento se efectuarn antes
de dar enlucido.
Si es necesario, los muros interiores recibirn un enlucido con
mortero de cemento. Se prohben los enlucidos de yeso. Las
puestas y recuadros metlicos estarn protegidos contra la
oxidacin.
17.9. EVACUACIN Y EXTINCIN DEL ACEITE AISLANTE
Las paredes y techo de la cuba que han de alojar aparatos con
bao de aceite, podrn estar construidas con materiales
resistentes al fuego, que tengan la resistencia estructural
adecuada para las condiciones de empleo.
Con el fin de permitir la evacuacin y extincin del aislante se
podrn prever pozos a fondo perdido o con revestimiento estanco.
Se tendr en cuenta para estos ltimos el volumen de aceite que
puedan recibir. En todos los pozos se prevern apagafuegos
superiores, tales como lechos de guijarros de 5 cm de dimetro
aproximadamente, sifones en caso de varios pozos con colector
nico, etc. Se recomienda que los pozos sean exteriores a la cuba
del trafo o de los CS y adems inspeccionables.
Cuando se empleen aparatos en bao de lquidos incombustibles,
podrn disponerse en celdas que no cumplan la anterior
prescripcin.
17.10. VENTILACIN
Los locales para Centros de interior estarn provistos de
ventilacin para evitar la condensacin.

204

Normalmente se recurrir a la ventilacin natural que consistir


en una o varias tomas de aire exterior, situadas a 0,20 m del suelo
como mnimo, y en la parte opuesta a la salida, situadas lo ms
altas posible. Podr utilizarse tambin la ventilacin forzada.
Las aberturas no darn sobre locales a temperatura elevada o que
contengan polvo perjudicial, vapores corrosivos, lquidos, gases,
vapores o polvos inflamables.
Las aberturas superiores de ventilacin llevarn una persiana que
impida la entrada de agua y junto a la misma, un dispositivo que
impida el paso de insectos.
Las aberturas inferiores llevarn, adems, una contrapersiana y
se situarn preferentemente del lado del compartimento que
contiene el trafo de potencia.
17.11. PUERTAS
Las puertas de acceso al Centro desde el exterior sern
incombustibles y suficientemente rgidas, abriendo hacia fuera de
forma que puedan abatirse sobre el muro de fachada.

205

18 INSTALACIN ELCTRICA DE CENTROS DE


TRANSFORMACIN Y CENTROS DE SECCIONAMIENTO
18.1. ALIMENTACIN SUBTERRNEA
Los cables de alimentacin subterrnea entrarn en el Centro,
alcanzando las bornas de M.T., por un canal o tubo. Las secciones
de estos canales o tubos permitirn la colocacin de los cables con
la mayor facilidad posible. Los tubos sern de superficie interna
lisa, siendo su dimetro 1,6 veces el dimetro del cable como
mnimo, y preferentemente de 160 mm. La disposicin de los
canales y tubos sern tal que los radios de curvatura a que deban
someterse los cables sern como mnimo igual a 10 veces su
dimetro.
Despus de colocados los cables se obstruir el orificio de paso
por un tapn al que, para evitar la entrada de roedores, se
incorporarn materiales duros que no daen el cable.
En el exterior del Centro los cables estarn directamente
enterrados, excepto si atraviesan otros locales para el caso de
Centros de interior, en cuyo caso se colocarn en tubos o canales.
Se tomarn las medidas necesarias para asegurar en todo
momento la proteccin mecnica de los cables y su fcil
identificacin. Por otra parte se tendr en cuenta, la posible
presencia de sustancias que pudieran perjudicarles.
18.2. ALUMBRADO
El alumbrado artificial, siempre obligatorio para Centros de
interior, ser de incandescencia.
Los focos luminosos estarn colocados sobre soportes rgidos y
dispuestos de manera que los aparatos de seccionamiento no
queden en una zona de sombra; permitirn adems la lectura
correcta de los aparatos de medida. Se situarn de tal manera que
la sustitucin de lmparas pueda efectuarse sin necesidad de
interrumpir la media tensin y sin peligro para el operario.
Los interruptores de alumbrado se situarn en la proximidad de
las puertas de acceso.

206

18.3. CONEXIONES DE M.T.


Las conexiones de M.T. se realizarn mediante conectores
enchufables en carga para 200 A, y mediante conectores
atornillables sin carga para 600 A.
18.4. CONEXIONES DE B.T.
Las conexiones de B.T. se realizarn mediante terminaciones
bimetlicas tipo pletina con un taladro de .
18.5. PUESTA A TIERRA
Condiciones de los circuitos de puesta a tierra:
1. No se unirn al circuito de puesta a tierra, ni las puertas de
acceso ni las ventanas metlicas de ventilacin del Centro de
interior.
2. En ninguno de los circuitos de puesta a tierra se colocarn
elementos de seccionamiento.
3. Cada circuito de puesta a tierra llevar un borne para la medida
de la resistencia de tierra, situado en un punto fcilmente
accesible.
4. Los circuitos de tierra se establecern de manera que se eviten
los deterioros debidos a acciones mecnicas, qumicas o de otra
ndole.
5. La conexin del conductor de tierra con la toma de tierra se
efectuar de manera que no haya peligro de aflojarse o soltarse.
6. Los circuitos de puesta a tierra formarn una lnea continua en la
que no podrn incluirse en serie las masas del Centro. Siempre
la conexin de las masas se efectuar por derivacin.
7. Los conductores de tierra enterrados sern de cobre y su
seccin no inferior a 33,62 mm2 (para un despeje de la falta de
0,1 s).
8. Como la alimentacin a un Centro se efecta por medio de
cables subterrneos provistos de cubierta metlica que hace las
veces de neutro, se asegurar la continuidad de sta. La cubierta
metlica se unir al circuito de puesta a tierra.

207

9. La continuidad elctrica entre un punto cualquiera de la masa y


el conductor de puesta a tierra, en el punto de penetracin en el
suelo, satisfar la condicin de que la resistencia elctrica
correspondiente sea inferior a 0,4 ohmios.
La puesta a tierra ser nica y a ella se unirn:

Neutro del transformador.


Todas las partes metlicas del CT

208

19 MATERIALES PARA CENTROS DE TRANSFORMACIN Y


CENTROS DE SECCIONAMIENTO
19.1. RECONOCIMIENTO Y ADMISIN DE MATERIALES
No se podrn emplear materiales que no hayan sido aceptados
previamente por el Director de Obra.
Se realizarn cuantos ensayos y anlisis indique el Director de Obra
aunque no estn indicados en este Pliego de Condiciones.
19.2. HERRAJES
Los herrajes que sirvan de sujecin a los elementos y aparatos de
los Centros, estarn constituidos por perfiles de acero laminado. Su
forma, dimensiones, modo de sujecin, etc., se determinarn en
funcin de los esfuerzos a los que deban estar sometidos.
19.3. ENSAYO DIELCTRICO
Todo el material que forma parte del equipo elctrico del CT deber
haber soportado por separado las tensiones de prueba a frecuencia
industrial y a impulso tipo rayo.
Adems de todo el equipo elctrico M.T., deber soportar durante un
minuto, sin perforacin ni contorneamiento, la tensin a frecuencia
industrial correspondiente al nivel de aislamiento del Centro.
Los ensayos se realizarn aplicando la tensin entre cada fase y
masa, quedando las fases no ensayadas conectadas a masa.
19.4. INSTALACIN DE PUESTA A TIERRA
Se comprobar la medida de las resistencias de tierra, y las
tensiones de contacto y de paso.
19.5. TRANSFORMADORES
Se medir la acidez y rigidez dielctrica del aceite del
Transformador.

209

20 PLANOS
Los ndices de los planos de referencia son presentados a
continuacin:

Tabla 76. ndice de planos para lneas de MT

CDIGO

TTULO

Grupo 010: Canalizaciones


PL010100
PL010200
PL010300
PL010400
PL010500
PL010600
PL010700
Grupo
PL020100

Canalizacin de lnea monofsica directamente enterrada


Canalizacin de lnea trifsica directamente enterrada
Canalizacin de lnea monofsica bajo tubo en arena
Canalizacin de lnea trifsica bajo tubo en arena
Canalizacin de lnea monofsica bajo tubo hormigonada
Canalizacin de lnea trifsica bajo tubo hormigonada
Canalizacin de lneas M.T. bajo tubo hormigonada (varias capas)

020: Paralelismos
Paralelismo de lnea de B.T. y lnea de M.T. directamente
enterradas.

PL020200
PL020300
PL020350
PL020400

Paralelismo de lneas M.T. directamente enterradas.


Paralelismo de lnea de B.T. y lnea de M.T. bajo tubo en arena.
Paralelismo de lneas M.T. bajo tubo en arena.
Paralelismo de lnea M.T. con lnea de comunicaciones
directamente enterrada.

PL020450

Paralelismo de lnea M.T. con lnea de comunicaciones bajo en


arena

PL020500

Paralelismo con canalizacin de alcantarillado directamente


enterrada.

PL020550

Paralelismo con canalizacin de alcantarillado bajo tubo en


arena.

PL020600

Paralelismo con canalizacin de agua o vapor de agua


directamente enterrada.

PL020650
PL020700
PL020750
PL020800

Paralelismo con canalizacin de agua o vapor de agua bajo tubo


en arena.
Paralelismo con canalizacin de gas directamente enterrada.
Paralelismo con canalizacin de gas bajo tubo en arena.
Paralelismo con fundaciones de otros servicios directamente
enterrado

PL020850

Paralelismo con fundaciones de otros servicios bajo tubo en


arena.

PL020900

Paralelismo con depsitos de carburante bajo tubo hormigonada

210

Grupo 021: Cruzamientos


PL021100

Cruzamientos de lnea M.T. con vas pblicas bajo tubo


hormigonada.
Cruzamiento de lnea M.T. con vas de ferrocarril bajo tubo

PL021200
PL021300
PL021400
PL021500
PL021600
PL021700

hormigonada
Cruzamiento de lnea M.T. con lnea B.T. directamente enterrada.
Cruzamiento de lnea M.T. con lnea B.T. bajo tubo en arena.
Cruzamiento de lnea M.T. con lnea M.T. directamente enterrada.
Cruzamiento de lnea M.T. con lnea M.T. bajo tubo en arena.
Cruzamiento de lnea M.T. con lnea de comunicaciones bajo tubo
en arena.

PL021800

Cruzamiento con canalizacin de gas o agua directamente


enterrada

PL021850
PL021900

Cruzamiento con canalizacin de gas o agua bajo tubo en arena


Cruzamiento con canalizacin de alcantarillado directamente
enterrada
Cruzamiento con canalizacin de alcantarillado bajo tubo en

PL021950

arena

Grupo 030: Empalmes y terminales


PL030100

Empalme contrctil en fro para conductores con aislamiento


seco para 15, 25 y 35 KV.

PL030200
PL030300
PL030400
PL030500
PL030600

Terminacin exterior contrctil en fro para 15 KV.


Terminacin exterior contrctil en fro para 25 KV.
Terminacin exterior contrctil en fro para 35 KV.
Terminacin interior contrctil en fro para 15 KV y 25 KV
Terminacin interior contrctil en fro para 35 KV.

211

Grupo 040: Conectores enchufables


PL040100
PL040200
PL040300
PL040400
PL040500

Terminal acodado enchufable en carga. 15 KV 200 A


Terminal acodado enchufable en carga. 25 y 35 KV 200 A
Terminal atornillable en T sin carga. 15, 25 y 35 KV 600 A
Terminal atornillable en T sin carga con reductor 600/200 A
15 y 25 KV 600 A
Terminal atornillable en T sin carga con reductor 600/200 A
35 KV 600 A
Borna insertable para terminal enchufable en carga. 15, 25 y 35

PL040600
PL040700
PL040800
PL040900

KV 200 A.
Borna insertable doble para terminal enchufable en carga. 15, 25
y 35 KV 200 A.
Borna de reduccin 600-200 A para 15, 25 y 35 KV
Borna de unin para terminal atornillable en T sin carga. 15, 25 y
35 KV 600 A

PL041000
PL041100
PL041200
PL041300
PL041400

Tapn de cierre aislante. 15, 25 y 35 KV Serie 200 A


Tapn de cierre aislante. 15, 25 y 35 KV Serie 600 A
Barra tres bornas enchufables en carga. 15, 25 y 35 KV 200 A
Barra tres bornas atornillables en carga. 15, 25 y 35 KV 600 A
Borna parking insertable para terminal enchufable 15, 25 y 35 KV
Serie 200 A.
Borna parking insertable para terminal atornillable 15, 25 y 35 KV

PL041500
PL041600

Serie 600 A.
Borna parking doble insertable para terminal enchufable 15, 25 y
35 KV Serie 200 A.
Borna parking insertable con p.a.t. para terminal enchufable 15,

PL041700
PL041800

25 y 35 KV Serie 200 A.
Borna parking insertable con p.a.t. para terminal atornillable
15, 25 y 35 KV Serie 600 A.

Grupo 050: Paso areo subterrneo


PL050100 Paso areo-subterrneo trifsico 13,2 kV
PL050200 Paso areo-subterrneo trifsico 24,9 y 34,5 kV
PL050300 Derivacin area-subterrnea trifsica 13,2 kV con proteccin
PL050400
PL050500

Derivacin area-subterrnea trifsica 24,9 y 34,5 kV


con proteccin
Derivacin area-subterrnea monofsica 13,2 kV con
proteccin
Derivacin area-subterrnea monofsica 24,9 y 34,5 kV con

PL050600 proteccin

Nota: Numeracin de los planos


PL AAA B 00
PL: Plano
AAA: Grupo
B: Nmero correlativo del grupo

212

Tabla 77. ndice de planos para lneas de BT

CDIGO
Grupo
PL010100
PL010150
PL010200
PL010300
PL010350
PL010400
PL010500
PL010550
PL010600
Grupo
PL020100

TTULO
010: Canalizaciones
Canalizacin de lnea monofsica directamente enterrada
Canalizacin de lnea trifsica directamente enterrada
Canalizacin de acometida bajo tubo en arena
Canalizacin de lnea monofsica bajo tubo en arena
Canalizacin de lnea trifsica bajo tubo en arena
Canalizacin de acometida bajo tubo hormigonada
Canalizacin de lnea monofsica bajo tubo hormigonada
Canalizacin de lnea trifsica bajo tubo hormigonada
Canalizacin de lneas bajo tubo hormigonada (varias capas)

020: Paralelismos
Paralelismo de lnea de B.T. y lnea de M.T. directamente
enterradas.

PL020200
PL020300
PL020350
PL020400

Paralelismo de lneas B.T. directamente enterradas.


Paralelismo de lnea de M.T. y lnea de B.T. bajo tubo en arena.
Paralelismo de lneas B.T. bajo tubo en arena.
Paralelismo de lnea B.T. con lnea de comunicaciones
directamente enterrada.

PL020450

Paralelismo de lnea B.T. con lnea de comunicaciones bajo tubo


en arena

PL020500

Paralelismo con canalizacin de alcantarillado directamente


enterrada.

PL020550

Paralelismo con canalizacin de alcantarillado bajo tubo en


arena.

PL020600

Paralelismo con canalizacin de agua o vapor de agua


directamente enterrada.

PL020650
PL020700
PL020750
PL020800

Paralelismo con canalizacin de agua o vapor de agua bajo tubo


en arena.
Paralelismo con canalizacin de gas directamente enterrada.
Paralelismo con canalizacin de gas bajo tubo en arena.
Paralelismo con fundaciones de otros servicios directamente
enterrado

PL020850

Paralelismo con fundaciones de otros servicios bajo tubo en


arena.

PL020900

Paralelismo con depsitos de carburante bajo tubo hormigonada

213

Grupo 021: Cruzamientos


PL021100

Cruzamientos de lnea B.T. con vas pblicas bajo tubo


hormigonada.

PL021200

Cruzamiento de lnea B.T. con vas de ferrocarril bajo tubo


hormigonada

PL021300
PL021400
PL021500
PL021600
PL021700

Cruzamiento de lnea B.T. con lnea M.T. directamente enterrada.


Cruzamiento de lnea B.T. con lnea M.T. bajo tubo en arena.
Cruzamiento de lnea B.T. con lnea B.T. directamente enterrada.
Cruzamiento de lnea B.T. con lnea B.T. bajo tubo en arena.
Cruzamiento de lnea B.T. con lnea de comunicaciones bajo tubo
en arena.

PL021800

Cruzamiento con canalizacin de gas o agua directamente


enterrada

PL021850

Cruzamiento con canalizacin de gas o agua bajo tubo en arena


Cruzamiento con canalizacin de alcantarillado directamente

PL021900
PL021950

enterrada
Cruzamiento con canalizacin de alcantarillado bajo tubo en
arena

Grupo 030: Empalmes y terminales


PL030100
PL030200
PL030300
PL030400
PL030500
PL030600

Terminal compresin bimetlico tipo pletina para lneas


subterrneas de BT.
Manguito de unin para lneas subterrneas de BT.

Grupo 040: Paso areo subterrneo


PL040100
PL040200

Nota: Numeracin de los planos


PL AAA B CC
PL: Plano
AAA: Grupo
B: Nmero correlativo del grupo
CC: Versin del plano

214

Tabla 78. ndice de planos para CT y CS

CDIGO
TTULO
Grupo 010: CT y CS tipo Pad- Mounted de exterior
PL010100
Plataforma con depsito de recogida de aceite
PL010200
Plataforma sin depsito de recogida de aceite
CT monofsico Pad-Mounted 13,2, 24,9 y 34,5 kV - 50/100/167 kVA

PL010300(A) Envolvente metlica


PL010300(B) Centro de transformacin
PL010300(C) Esquema unifilar
CT trifsico fin de lnea tipo Pad-Mounted 13,2, 24,9 y 34,5 kV - 150/300kVA

PL010400(A) Envolvente metlica


PL010400(B) Centro de transformacin
PL010400(C) Esquema unifilar
CT trifsico fin de lnea tipo Pad-Mounted 13,2, 24,9 y 34,5 kV - 500/750 kVA

PL010450(A) Envolvente metlica


PL010450(B) Centro de transformacin
PL010450(C) Esquema unifilar
CT trifsico entrada-salida tipo Pad-Mounted 13,2, 24,9 y 34,5 kV-150/300kVA

PL010500(A) Envolvente metlica


PL010500(B) Centro de transformacin
PL010500(C) Esquema unifilar
CT trifsico entrada-salida tipo Pad-Mounted 13,2, 24,9 y 34,5 kV -500/750 kVA

PL010550(A) Envolvente metlica


PL010550(B) Centro de transformacin
PL010550(C) Esquema unifilar
CS simple tipo Pad-Mounted para 13,2 kV -600 A, 24,9 y 34,5 kV - 400 A

PL010600(A) Envolvente metlica.


PL010600(B) Centro de seccionamiento
PL010600(C) Esquema unifilar
CS 3L3 tipo Pad-Mounted para 13,2 kV - 600 A, 24,9 y 34,5 kV - 400 A.

PL010700(A) Envolvente metlica.


PL010700(B) Centro de seccionamiento
PL010700(C) Esquema unifilar
CS 4L4 tipo Pad-Mounted para 13,2 kV - 600 A, 24,9 y 34,5 kV - 400 A.

PL010800(A) Envolvente metlica.


PL010800(B) Centro de seccionamiento
PL010800(C) Esquema unifilar

215

Grupo 020: CS con envolvente de hormign


CS 3L3 con envolvente de hormign para 13,2 - 600 A, 24,9 y 34,5 kV - 400 A.

PL020100(A) Centro de seccionamiento


PL020100(B) Esquema unifilar
CS 4L4 con envolvente de hormign para 13,2 kV - 600 A, 24,9 y 34,5 kV - 400 A.

PL020200(A) Centro de seccionamiento


PL020200(B) Esquema unifilar
Grupo 030: Distancias de seguridad
PL030100
Delimitacin de la zona de trabajo e inspeccin.
PL030200
Proteccin del CT o CS en zona de Parking
PL030300
Distancias a edificios, bordillos, ventanas y puertas.
PL030400
Distancias a depsitos de combustible
PL030500
Distancia a contenedores de basuras
Grupo 040: Disposicin del CT o CS de interior
PL040100
CT o CS de interior
PL040200
Puerta de acceso a CT CS de interior
PL040300
Modulo de ventilacin
Gr upo 050: Bornas M.T.
PL050100
Borna atornillable 600 A-13,2, 24,9 y 34,5 kV
PL050200
Borna tipo pozo (Bushing-well) 200 A-13,2, 24,9 y 34,5 kV

Nota: Numeracin de los planos PL AAA B CC


PL: Plano
AAA: grupo
B: nmero correlativo del grupo
CC: versin del plano

216

21 CAJAS DE DERIVACIN SUBTERRNEA


21.1. Introduccin
La presente seccin contiene los criterios empleados para la
normalizacin de la Caja de Derivacin Subterrnea. Esta caja
ser utilizada en todas las lotificaciones y/o urbanizaciones
subterrneas que se desarrollen en la Zona de Concesin de Gas
Natural Fenosa.
En particular las redes subterrneas de BT que utilicen cajas de
derivacin subterrnea estarn compuestas de lneas BT que se
conectan a la caja mediante conectores pletina y de las acometidas
proyectadas a servir por el diseo. Como mximo se permitirn 9
acometidas conectadas a la caja.
En lotificaciones solo se proyectara la red hasta la caja de
derivacin, dejando provisto ductos sellados con una longitud de
50 cm desde la paredilla donde se ubicara la caja de derivacin
para su posterior interconexin con las diferentes acometidas.
21.2. Objetivos
El objetivo de este informe es establecer de forma prioritaria el
uso de las cajas de derivacin en los diseo de Urbanizaciones y/o
Lotificaciones que se proyectan con Red Subterrnea.
En conclusin las redes que emplean cajas de derivacin
Subterrnea nos ofrecen, entre sus mltiples ventajas,
confiabilidad y segura con la mnima cantidad de elementos y obra
civil, lo cual facilita el desarrollo y mantenimiento de los diferentes
proyectos.
21.3. Topologa de Redes
A continuacin se analizaran las diferentes topologas de redes
que pueden en un momento en particular ser empleadas para el
diseo de una Urbanizacin y/o Lotificacin.
Cada topologa ha sido evaluada tomando como referencia la peor
condicin posible en campo, es decir:
1. Las acometidas se dirigen en diferente direccin.
2. La longitud desde el punto de alimentacin y el punto de
entrega son iguales para cada acometida.

217

3. Los conductores a emplear para cada acometida sern de


igual calibre para cada condicin y unipolares.
21.4. Acometidas sin ducto futuro
Figura 1, esta configuracin consiste en que todas las acometidas
se derivaran directamente de las bornas de baja tensin del
transformador, sin incluir un ducto libre para futuras
ampliaciones. Las longitudes acometidas que han sido analizadas
son 10, 30, 50 y 70 metros desde el transformador hasta el punto
de entrega (terminales de fuente del medido o el Interruptor
principal).

Figura 1

21.5. Acometidas con ducto futuro


Figura 2, esta configuracin consiste en que todas las acometidas
se derivaran directamente de las bornas de baja tensin del
transformador, y cada canalizacin incluye un ducto libre para
futuras ampliaciones. Las longitudes acometidas que han sido
analizadas son 10, 30, 50 y 70 metros desde el transformador
hasta el punto de entrega (terminales de fuente del medido o el
Interruptor principal).

218

Figura 2

21.6. Caja de Derivacin


Figura 3, esta configuracin consiste en acometida que se derivan
de la caja de derivacin subterrnea. La ubicacin de la Caja para
la peor condicin se estima a la mitad del recorrido del circuito, es
decir, desde el transformador hasta el punto de entrega. Las
longitudes que han sido analizadas son 5, 15, 25 y 35 metros de
acometida desde la caja de hasta el punto de entrega (terminales
de fuente del medidor o el Interruptor principal) mas la longitud de
la red de BT con canalizacin libre para futuras ampliaciones.

219

Figura 3

21.7. Consideraciones Generales


Los conductores normalizados para redes y acometidas
subterrneas de BT son #2, 1/0, 4/0 y 500 MCM. El uso de estos
conductores, de acuerdo con las topologas de redes antes
expuestas, quedara definido por la intensidad mxima permisible
del conductor y el transformador, es decir que la intensidad
mxima del transformador no debe superar la del conductor en un
periodo definido.
En vista de lo antes mencionado al realizar los clculos de
intensidad para los transformadores normalizados obtenemos lo
siguiente:

220

Tabla 79. Secciones mnimas de conductores por Transformador

Como podemos apreciaren la Tabla 79 dependiendo del


transformador, se define la seccin mnima del conductor que
puede ser conectado directamente a las bornas, lo cual nos indica
que para conductores de menor seccin se debe emplear la caja
de derivacin subterrnea.
21.8. Montaje de Cajas de Derivacin
21.9.1. Capacidad de la caja
La caja de derivacin subterrnea es una caja resistente a la
intemperie que presenta las siguientes dimensiones 800 x 600 x
300 mm. Mas que sus limitaciones en cuanto a capacidad, por las
barras de 400 y 800 amperios utilizadas para derivar las diferentes
acometidas.
La caja de derivacin subterrnea presenta
limitaciones en cuanto a la cantidad de ductos o acometidas que
pueden conectarse a est, debido a ello el nmero de ductos a
conectar ser el mostrado en la Tabla 80:
Tabla 80.Capacidad de conexin de la Caja de Derivacin Subterrnea

Ductos de Alimentadores
2 x 110 mm (4)
2 x 110 mm (4)
3 x 110 mm (4)
3 x 110 mm (4)

Nmero mximo de acometidas


9 x 60 mm (2)
8 x 110 mm (4)
9 X 60 mm (2)
6 x 110 mm (4)

21.9.2. Montaje
La Caja de Derivacin se debe instalar en una paredilla de
hormign de acuerdo al a siguiente figura:

221

FECHA

NOMBRE

Dibujado

UNION FENOSA
ESCALAS:

internacional

Proyectado
Comprobado
EL AUTOR DEL PROYECTO:

CODIGO MATERIAL

N PLANO
PROY. TIPO
REV.

HOJA

Figura 4.

La Caja de Derivacin Subterrnea debe ser instalada en un punto


cercano a las diferentes cargas. Esta debe ser ubicada dentro de
la servidumbre pblica y puede ser monofsica o trifsica de
acuerdo con las necesidades.
Durante el montaje de la caja de derivacin subterrnea se debe
contemplar todas las salidas o acometidas a alimentar de est, es
decir, se deben instalar todos los ductos a utilizar para su
posterior conexin con las diferentes acometidas o ductos
llegante.

222

Las conexiones de la Red de BT se realizarn en las tres (3)


primeras perforaciones a mano izquierda de acuerdo con la figura
1 y se fijan mediante arandela, pernos de x 2 de acero
inoxidable y terminales tipo pletina.
Las acometidas se
interconectaran en las siguientes nueve (9) perforaciones de igual
forma manteniendo un orden de conexionado de izquierda a
derecha.
21.9. Alimentacin
La alimentacin de la Caja de Derivacin de Subterrnea ser por
medio de conductores unipolares de aluminio 500 MCM, el cual se
conecta directamente al trafo mediante conectores tipo pletina de
un hueco. Dependiendo de la capacidad requerida se emplearan 1
o dos conductores por fase para alimentar las barras de la caja de
derivacin manteniendo un ducto libre como futuro.
La ampacidad de la barra quedara determinado de acuerdo con la
carga de diseo suministrada y los coeficiente de simultaneidad
esbozados en el PP.TT de lneas subterrneas de baja tensin.
21.10. Conclusiones
1. Eliminar el ducto libre como futuro en las acometidas.
2. Todo proyecto subterrneo donde se pretenda suministrar servicio
a 5 acometidas se derivara de la caja de derivacin subterrnea, de
lo contrario se debe derivar directamente del transformador sin
ducto libre.
3. La caja de derivacin subterrnea debe ubicarse lo ms prxima a
los puntos de consumo, reduciendo al mximo las longitudes de
las acometidas.
4. Los interruptores principales hasta 200 amperios o menos podrn
ser conectados a la caja de derivacin subterrnea

223

300

CINTA SEALIZADORA
600

COMPACTACIN MECNICA
PROCTOR 95 %
TRITUBO

150

ARENA TIERRA TAMIZADA


100

CANALIZACIN DE LNEA MONOFSICA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010100

300

CINTA SEALIZADORA
600

COMPACTACIN MECNICA
PROCTOR 95 %
TRITUBO

150

ARENA TIERRA TAMIZADA


100

CANALIZACIN DE LNEA TRIFSICA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010150

300

CINTA SEALIZADORA
COMPACTACIN MECNICA
PROCTOR 95 %
50

ARENA TIERRA TAMIZADA

50

CANALIZACIN DE ACOMETIDA
BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010200

300

CINTA SEALIZADORA
600

COMPACTACIN MECNICA
PROCTOR 95 %

50

ARENA TIERRA TAMIZADA


50

CANALIZACIN DE LNEA MONOFSICA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010300

300

CINTA SEALIZADORA

600

COMPACTACIN MECNICA
PROCTOR 95%

50

ARENA O TIERRA TAMIZADA

50

CANALIZACIN DE LNEA TRIFSICA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010350

COMPACTACIN MECNICA
PROCTOR 95 %
CINTA SEALIZADORA

HORMIGN

60

60

CANALIZACIN DE ACOMETIDA
BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010400

CINTA SEALIZADORA
COMPACTACIN MECNICA
PROCTOR 95 %

60

HORMIGN

60

CANALIZACIN DE LINEA MONOFSICA


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010500

CINTA SEALIZADORA
COMPACTACIN MECNICA
PROCTOR 95%

60 min.

HORMIGN
60 min.

CANALIZACIN DE LNEA TRIFSICA


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010550

COMPACTACIN MECNICA
PROCTOR 95 %
CINTA SEALIZADORA

60

HORMIGN

60

60

60

60

60

CANALIZACIN DE LNEAS B.T.


BAJO TUBO HORMIGONADAS (VARIAS CAPAS)
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL010600

250

PARALELISMO DE LNEA B.T. Y LNEA M.T.


DIRECTAMENTE ENTERRADAS
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020100

250

PARALELISMO DE LNEAS B.T.


DIRECTAMENTE ENTERRADAS
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020200

100
min.

< 250

PARALELISMO DE LNEA M.T. Y LNEA B.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020300

100

< 250

PARALELISMO DE LNEAS B.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020350

200

PARALELISMO DE LNEA B.T. CON LNEA DE COMUNICACIONES


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020400

< 200

PARALELISMO DE LNEA B.T. CON LNEA DE COMUNICACIONES


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020450

PLUVIALES

FECALES

<250

< 500

PARALELISMO CON CANALIZACIN DE ALCANTARILLADO


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020550

PLUVIALES

FECALES

<250

< 500

PARALELISMO CON CANALIZACIN DE ALCANTARILLADO


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020550

250

PARALELISMO CON CANALIZACIN DE AGUA O VAPOR DE AGUA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020600

< 250

PARALELISMO CON CANALIZACIN DE AGUA O VAPOR DE AGUA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020650

500

PARALELISMO CON CANALIZACIN DE GAS


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020700

< 500

PARALELISMO CON CANALIZACIN DE GAS


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020750

500
1500

PARALELISMO CON FUNDACIONES DE OTROS SERVICIOS


DIRECTAMENTE ENTERRADO
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020800

< 500

< 1500

PARALELISMO CON FUNDACIONES DE OTROS SERVICIOS


BAJO TUBO EN ARENA
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020850

DEPOSITO
DE CARBURANTE

1200

PARALELISMO CON DEPSITOS DE CARBURANTE


BAJO TUBO HORMIGONADA
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020900

800

CRUZAMIENTO DE LNEA B.T. CON VAS PBLICAS


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021100

NIVEL INFERIOR TRAVIESA

1300

CRUZAMIENTO DE LNEA B.T. CON VAS DE FERROCARRIL


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021200

250

CRUZAMIENTO DE LNEA B.T. CON LNEA B.T.


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEA DE B.T.
ZONA CARIBE

PL021300

< 250

CRUZAMIENTO DE LNEA B.T. CON LNEA B.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEA DE B.T.
ZONA CARIBE

PL021400

250

CRUZAMIENTO DE LNEA B.T. CON LNEA B.T.


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021500

< 250

CRUZAMIENTO DE LNEA B.T. CON LNEA B.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021600

200

CRUZAMIENTO DE LNEA B.T. CON LNEA DE COMUNICACIONES


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021700

250

CRUZAMIENTO CON CANALIZACIN DE GAS O AGUA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021800

< 250

CRUZAMIENTO CON CANALIZACIN DE GAS O AGUA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEA DE B.T.
ZONA CARIBE

PL021850

DEPOSITO
DE CARBURANTE

1200

PARALELISMO CON DEPSITOS DE CARBURANTE


BAJO TUBO HORMIGONADA
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL020900

PLUVIALES

< 250

< 500

FECALES

CRUZAMIENTO CON CANALIZACIN DE ALCANTARILLADO


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

PL021950

FECHA

NOMBRE

Dibujado

UNION FENOSA
ESCALAS:

1/10

Proyectado
Comprobado

TERMINAL COMPRESION TIPO PLETINA

EL AUTOR DEL PROYECTO:

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

N PLANO
PROY. TIPO

552096-98

REV.

PL030100
HOJA

SIGUE

FECHA

NOMBRE

Dibujado

UNION FENOSA
ESCALAS:

1/1

MANGUITO DE UNION

Proyectado
Comprobado
EL AUTOR DEL PROYECTO:

552093-95

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE B.T.
ZONA CARIBE

N PLANO
PROY. TIPO
REV.

PL030200
HOJA

SIGUE

1700
150

100 400

900

100

150

500

650

300

250

150

1600
A

A'

350

2000

1300

B'

350

150

FOSO RECOGIDA
ACEITE
40

110
40

40

700
200

300

150

TUBO EVACUADOR
DE AGUA

750

300

200
50

SECCIN B-B'

ENTRADA
CABLES

SECCIN A-A'

PLATAFORMA CON DEPSITO DE RECOGIDA DE ACEITE EXTERIOR


1/30

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010100

PLANTA

1800

1100
1620

370
150

1500
150

150

1620
1100

520

160

360

100

150

700
550

50

SECCION B-B'

PLATAFORMA SIN DEPSITO DE RECOGIDA DE ACEITE


1/30

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010200

19,13,2 ( 34 81 ")

304,8

279 (11") min


317,512,5

A min

254

177,8 (7")

114,3
76,2

457,2 (18") min

76,2
R1

67,3 min

50,812,7 ( 2 2 ")
1

50,812,7 ( 2 2 ")
139,7 ( 5 21") min

88,9 ( 3.5 ") min

6015

114,3min

12725,4
B

127,525,4
B
317,5

749,325,4

152,4 (6") min

203,225,4

101,6

254 (10")

SIN
ESCALA

Tensin primario (kV)

A min

C min

D min

E min

12,47,13,2 y 24,9

330,2

127

101,6

82,55

34,5

406,4

152,4

146,05

101,6

B min

CT MONOF. PAD-MOUNTED
13,2, 24,9 Y 34,5 kV - 50/100/167 kVA
CENTRO DE TRANSFORMACIN
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010300-A
1

SIN
ESCALA

POTENCIA
(kVA)

A
(mm)

B
(mm)

C
(mm)

50 -100

775

1025

925

167

167

1300

925

CT MONOF. PAD-MOUNTED
13,2, 24,9 Y 34,5 kV - 50/100/167 kVA
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010300-B
2

1- TRANSFORMADOR
2- INTERRUPTOR TERMOMAGNTICO INTERNO
3- FUSIBLE LIMITADOR INTERNO
4- BORNAS ENCHUFABLES 200 A

SIN
ESCALA

CT MONOF. PAD-MOUNTED
13,2, 24,9 Y 34,5 kV - 50/100/167 kVA
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010300-C
3

76,2
(3")

247,65
(9-3/4")
min.

292,1
(11-1/2")
min.

152,4
(6")

152,4
(6")

152,4
(6")

101,6
(4")

254

247,65
(9-3/4")
min.

152,4
(6")

101,6 101,6
(4")
(4")
min. min.

685,8
(27")
min.

292,1
(11-1/2")
min.

292,1
(11-1/2")
min.

101,6
(4")
min.

127
(5")
min.

268
min.

1/15

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
CENTRO DE TRANSFORMACIN
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010400-A
1

1700

1500

1950

1760 L 1860
536 D 650

1651

1/20

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010400-B
2

1- TRANSFORMADOR
2- INTERRUPTOR TERMOMAGNTICO INTERNO
3- FUSIBLE LIMITADOR INTERNO
4- BORNAS ENCHUFABLES 200 A

SIN
ESCALA

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010400-C
3

76,2
(3")

247,65
(9-3/4")
min.

292,1
(11-1/2")
min.

152,4
(6")

152,4
(6")

152,4
(6")

101,6
(4")

254

247,65
(9-3/4")
min.

152,4
(6")

101,6 101,6
(4")
(4")
min. min.

685,8
(27")
min.

292,1
(11-1/2")
min.

292,1
(11-1/2")
min.

101,6
(4")
min.

127
(5")
min.

268
min.

1/15

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
CENTRO DE TRANSFORMACIN
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010450-A
1

1700

1500

1950

1760 L 1860
536 D 650

1651

1/20

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010450-B
2

1- TRANSFORMADOR
2- INTERRUPTOR TERMOMAGNTICO INTERNO
3- FUSIBLE LIMITADOR INTERNO
4- BORNAS ENCHUFABLES 200 A

SIN
ESCALA

CT TRIF. FIN DE LNEA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010450-C
3

76,2
(3")

152,4
(6")

152,4
(6")

152,4
(6")

101,6
(4")

254

152,4
(6")

127
(5")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

127
(5")
min.

685,8
(27")
min.

268
min.

1/15

CT TRIF. ENTRADA-SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
CENTRO DE TRANSFORMACIN
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010500-A
1

1700

1500

1950

1760 L 1860
536 D 650

1651

1/20

CT TRIF. ENTRADA-SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010500-B
2

TRAFO

1
LNEA A

LNEA B
TRAFO

2
LNEA A

LNEA B
TRAFO

LNEA A

LNEA B
TRAFO

LNEA A

LNEA B

POSICIONES DEL INTERRUPTOR


T-BLADE
LNEA A

LNEA B

1- TRANSFORMADOR
2- INTERRUPTOR TERMOMAGNTICO INTERNO
3- FUSIBLE LIMITADOR INTERNO
4- INTERRUPTOR T-BLADE DE 4 POSICIONES TRIPOLAR

SIN
ESCALA

CT TRIF. ENTRADA SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 150-300 kVA
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010500-C
3

76,2
(3")

152,4
(6")

152,4
(6")

152,4
(6")

101,6
(4")

254

152,4
(6")

127
(5")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

152,4
(6")
min.

127
(5")
min.

685,8
(27")
min.

268
min.

1/15

CT TRIF. ENTRADA-SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
CENTRO DE TRANSFORMACIN
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010550-A
1

1700

1500

1950

1760 L 1860
536 D 650

1651

1/20

CT TRIF. ENTRADA-SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010550-B
2

TRAFO

1
LNEA A

LNEA B
TRAFO

2
LNEA A

LNEA B
TRAFO

LNEA A

LNEA B
TRAFO

LNEA A

LNEA B

POSICIONES DEL INTERRUPTOR


T-BLADE
LNEA A

LNEA B

1- TRANSFORMADOR
2- INTERRUPTOR TERMOMAGNTICO INTERNO
3- FUSIBLE LIMITADOR INTERNO
4- INTERRUPTOR T-BLADE DE 4 POSICIONES TRIPOLAR

SIN
ESCALA

CT TRIF. ENTRADA SALIDA PAD-MOUNTED


13,2, 24,9 Y 34,5 kV - 500-750 kVA
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010550-C
3

152,4
(6") min.
152,4
(6") min.
101,6
(4") min.
127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
127
(5")
88,9 (5")
min. (3-1/2") min.
min.

127
(5")
min.

127
(5")
min.

127
76,2
(5")
88,9 (3")
min. (3-1/2")min.
min.

203,2
(8") min.

685,8
(27") min.

7/16"

A
600 A

B
600 A
C
200 A

1/15

CS SIMPLE TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
CENTRO DE SECCIONAMIENTO
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010600-A
1

1700

1500

1950

536 D 650

1651

1/20

CS SIMPLE TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010600-B
2

LNEA A

LNEA C

LNEA B

LNEA A

LNEA C

LNEA B

LNEA A

LNEA C

LNEA B

LNEA A

LNEA C

LNEA B

LNEA A

LNEA C

LNEA B

POSICIONES DEL INTERRUPTOR


T-BLADE

1- INTERRUPTOR T-BLADE

SIN
ESCALA

CS SIMPLE TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010600-C
3

152,4
(6") min.
101,6
(4") min.
127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

203,2
(8")
min.

685,8
(27")
min.

7/16"

C
A

600 A

1/15

C
A

C
A

600 A

600 A

CS 3L3 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
CENTRO DE SECCIONAMIENTO
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010700-A
1

1700

1500

1950

536 D 650

1651

1/20

CS 3L3 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010700-B
2

LNEA A

LNEA B

LNEA C

1- INTERRUPTOR DE 3 POSICIONES (BLADE-CENTER)

SIN
ESCALA

CS . 3L3 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010700-C
3

152,4
(6") min.
152,4
(6") min.
101,6
(4") min.
127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

127
(5")
min.

203,2
(8")
min.

685,8
(27")
min.

7/16"

C
A

600 A

1/15

C
A

600 A

C
A

600 A

C
A

600 A

CS 4L4 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
CENTRO DE SECCIONAMIENTO
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010800-A
1

1700

1500

1950

536 D 650

1651

1/20

CS 4L4 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ENVOLVENTE METLICA
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010800-B
2

LNEA A

LNEA B

LNEA C

LNEA D

1- INTERRUPTOR DE 3 POSICIONES (BLADE-CENTER)

SIN
ESCALA

CS . 4L4 TIPO PAD-MOUNTED


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010800-C
3

1217

1460

1500
2050

550
100
1360

1070

1660

1370

A'
1072

1200

1/40

SECCION A-A'

CS 3L3 CON ENVOLVENTE DE HORMIGN


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
CENTRO DE SECCIONAMIENTO
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL020100-A
1

CELDA1

SIN
ESCALA

CELDA2

CELDA3

CS 3L3 CON ENVOLVENTE DE HORMIGN


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL020100-B
2

1243
2000

1523
2147

625

A'

SECCION A-A'
A

1/40

CS 4L4 CON ENVOLVENTE DE HORMIGN


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
CENTRO DE SECCIONAMIENTO
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL020200-A
1

CELDA1

SIN
ESCALA

CELDA2

CELDA3

CELDA4

CS 4L4 CON ENVOLVENTE DE HORMIGN


13,2kV - 600 A, 24,9 Y 34,5 kV - 400 A
ESQUEMA UNIFILAR
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL020200-B
2

0,6 m
0,6 m

0,6 m

2m

AREA DE TRABAJO
AREA DE INSPECCIN

DELIMITACIN DE LA ZONA DE TRABAJO E INSPECCIN


1/25

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL030100

MAX. 1,5 m

0,2 m
0,2 m

PROTECCIN DEL CT O CS EN ZONA DE PARKING


1/45

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL030200

2m

100 mm
0,6 - 2 m

6m

2m

SIN
ESCALA

2m

DISTANCIAS A EDIFICIOS, BORDILLOS,


VENTANAS Y PUERTAS
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL030300

6000
(19')

DISTANCIA A DEPSITOS DE COMBUSTIBLE


SIN
ESCALA

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL030400

700
(27-9/16")

600
(23-5/8")

MURO INTERMEDIO

5000
(16')

SIN MURO

DISTANCIA A CONTENEDORES DE BASURAS


SIN
ESCALA

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL030500

DISTANCIA MINIMA DE VENTILACION


A LAS VENTANAS MAS PROXIMAS
(EN PLANO VERTICAL)

2000

600
2420
(min.)

600

2370
(min.)

2420
3220
DETALLE 1

50

50

UPN 120

800
2300

250

2580

815,5

FACHADA

815,5

1500
3131

SECCION A-A'

364

1000

100 436

SECCION B-B'
B

ESPARRAGO
16 X 35

40
35

600

600

600
96,5

A'

PARTE INFERIOR
DEL C.T.

DETALLE 1
ESCALA 1/10

100 10
NOTA: LOS CARRILES IRAN
EMPOTRADOS EN EL HORMIGON

1000
40

UPN 120

94,5

12 T. 110 B.T.

3 T. 160 M.T.

120

C'

15/07/02

SECCION C-C'
CT CS DE INTERIOR SOBRE SUELO

2300
1/50
1/10

B'

PLANTA

PROYECTO TIPO
CT Y SEC. PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL040100

P.T.B.

CERCO
164
55

967

55

2392

967

PLETINA 40x4

55
129

2260
2300

VISTA EXTERIOR
20

106
55

556

40

967

556

CERRADURA
STANDARD
55
2384

40

556
1045

967

40

556
55
179
20
1083
20

20 20
4
2250

1083

20

PUERTA DE ACCESO A CT O CS DE INTERIOR


1/30

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL040200

1151
DETALLE A

1078

624

SECCIN A-A'

554 591

A'
1081
1118

16,5
17
1,5
ANGULO DE
30 X 30 X 1,5

23,01
20,1

27 LAMINAS
624 591

DETALLE A
E:1/2
15

MODULO DE VENTILACIN
1/2
1/10

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL040300

TRAFO

BORNA ATORNILLABLE 600 A


13,2, 24,9 Y 34,5 kV
1/3

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL050100

TRAFO

1/3

BORNA TIPO POZO 200 A


(BUSHING-WELL)
13,2, 24,9 Y 34,5 kV
PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL050200

1700
150

100 400

900

100

150

500

650

300

250

150

1600
A

A'

350

2000

1300

B'

350

150

FOSO RECOGIDA
ACEITE
40

110
40

40

700
200

300

150

TUBO EVACUADOR
DE AGUA

750

300

200
50

SECCIN B-B'

ENTRADA
CABLES

SECCIN A-A'

PLATAFORMA CON DEPSITO DE RECOGIDA DE ACEITE EXTERIOR


1/30

PROYECTO TIPO
CT Y SEC.PARA ALIMENTACIN MEDIANTE RED SUBT. M.T.
ZONA CARIBE

PL010100

300

CINTA SEALIZADORA
600

COMPACTACIN MECNICA
PROCTOR 95 %
TRITUBO
150

ARENA TIERRA TAMIZADA


100

CANALIZACIN DE LNEA TRIFSICA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010200

300

CINTA SEALIZADORA
600

COMPACTACIN MECNICA
PROCTOR 95 %

50

ARENA TIERRA TAMIZADA

50

CANALIZACIN DE LNEA MONOFSICA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010300

300

CINTA SEALIZADORA

600

COMPACTACIN MECNICA
PROCTOR 95 %

50

ARENA TIERRA TAMIZADA

50

CANALIZACIN DE LNEA TRIFSICA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010400

CINTA SEALIZADORA
COMPACTACIN MECNICA
PROCTOR 95 %

60

HORMIGN
60

CANALIZACIN DE LNEA MONOFSICA


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010500

COMPACTACIN MECNICA
PROCTOR 95 %
CINTA SEALIZADORA

60

HORMIGN
60

CANALIZACIN DE LNEA TRIFSICA


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010600

COMPACTACIN MECNICA
PROCTOR 95 %
CINTA SEALIZADORA

60

60

HORMIGN

60

60

60
60

CANALIZACIN DE LNEAS M.T.


BAJO TUBO HORMIGONADAS (VARIAS CAPAS)
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL010700

250

PARALELISMO DE LNEA B.T. Y LNEA M.T.


DIRECTAMENTE ENTERRADAS
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020100

250

PARALELISMO DE LNEAS M.T.


DIRECTAMENTE ENTERRADAS
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020200

100

< 250

PARALELISMO DE LNEA B.T. Y LNEA M.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020300

100

< 250

PARALELISMO DE LNEAS M.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020350

200

PARALELISMO DE LNEA M.T. CON LNEA DE COMUNICACIONES


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020400

< 200

PARALELISMO DE LNEA M.T. CON LNEA DE COMUNICACIONES


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO

PL020450

PLUVIALES

FECALES

250

500

PARALELISMO CON CANALIZACIN DE ALCANTARILLADO


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020500

PLUVIALES

FECALES

< 250

< 500

PARALELISMO CON CANALIZACIN DE ALCANTARILLADO


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020550

250

PARALELISMO CON CANALIZACIN DE AGUA O VAPOR DE AGUA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020600

< 250

PARALELISMO CON CANALIZACIN DE AGUA O VAPOR DE AGUA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020650

500

PARALELISMO CON CANALIZACIN DE GAS


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020700

< 500

PARALELISMO CON CANALIZACIN DE GAS


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020750

500
1500

PARALELISMO CON FUNDACIONES DE OTROS SERVICIOS


DIRECTAMENTE ENTERRADO
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020800

< 500

< 1500

PARALELISMO CON FUNDACIONES DE OTROS SERVICIOS


BAJO TUBO EN ARENA
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020850

DEPOSITO
DE CARBURANTE

1200

PARALELISMO CON DEPSITOS DE CARBURANTE


BAJO TUBO HORMIGONADA
1/20

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL020900

800

CRUZAMIENTO DE LNEA M.T. CON VAS PBLICAS


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021100

NIVEL INFERIOR TRAVIESA

1300

CRUZAMIENTO DE LNEA M.T. CON VAS DE FERROCARRIL


BAJO TUBO HORMIGONADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021200

250

CRUZAMIENTO DE LNEA M.T. CON LNEA B.T.


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021300

< 250

CRUZAMIENTO DE LNEA M.T. CON LNEA B.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021400

250

CRUZAMIENTO DE LNEA M.T. CON LNEA M.T.


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021500

< 250

CRUZAMIENTO DE LNEA M.T. CON LNEA M.T.


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021600

200

CRUZAMIENTO DE LNEA M.T. CON LNEA DE COMUNICACIONES


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021700

250

CRUZAMIENTO CON CANALIZACIN DE GAS O AGUA


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021800

< 250

CRUZAMIENTO CON CANALIZACIN DE GAS O AGUA


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021850

PLUVIALES

250

500

FECALES

CRUZAMIENTO CON CANALIZACIN DE ALCANTARILLADO


DIRECTAMENTE ENTERRADA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021900

PLUVIALES

< 250

< 500

FECALES

CRUZAMIENTO CON CANALIZACIN DE ALCANTARILLADO


BAJO TUBO EN ARENA
1/10

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL021950

EMPALME CONTRCTIL EN FRIO


PARA CONDUCTORES CON AISLAMIENTO SECO
15,25 Y35 kV
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL030100

TERMINACIN EXTERIOR
CONTRCTIL EN FRIO PARA 15 kV
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL030200

TERMINACIN EXTERIOR
CONTRCTIL EN FRIO PARA 25 kV
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL030300

TERMINACIN EXTERIOR
CONTRCTIL EN FRIO PARA 35 kV
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL030400

TERMINAL ACODADO ENCHUFABLE


EN CARGA 200A 15kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040100

TERMINAL ACODADO ENCHUFABLE EN CARGA


200A 25 Y 35kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040200

TERMINAL ATORNILLABLE EN " T "


SIN CARGA 600A 15, 25 Y 35kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040300

02-05-02

1/4

TERMINAL ATORNILLABLE EN T
SIN CARGA CON REDUCTOR
15 Y 25kV
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL040400
.

A.R.S.

02-05-02

TERMINAL ATORNILLABLE EN T SIN CARGA


CON REDUCTOR
35kV-600A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL040500
.

A.R.S.

1/2

BORNA INSERTABLE
PARA TERMINAL ENCHUFABLE EN CARGA
15,25 Y 35 kV ( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040600

1/2

BORNA INSERTABLE DOBLE


PARA TERMINAL ENCHUFABLE EN CARGA
15,25 Y 35 kV( IEEE STD 386-1985 )
PROYECTO TIPO
LINEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040700

1/2

BORNA DE REDUCCIN
600 - 200 A
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040800

1/2

BORNA DE UNION PARA TERMINAL ATORNILLABLE EN "T"


SIN CARGA 600A 15 ,25 Y 35kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL040900

02-05-02

TAPON DE CIERRE AISLANTE


15,25 Y 35kV-200A
1/2

PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041000
.

A.R.S.

02-05-02

TAPON DE CIERRE AISLANTE


15,25 Y 35kV-600A
1/2

PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041100
.

A.R.S.

1/5

BARRA TRES BORNAS ENCHUFABLES


EN CARGA 200A 15 ,25 Y 35kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL041200

1/5

BARRA TRES BORNAS ATORNILLABLES


SIN CARGA 600A 15 ,25 Y 35kV
( IEEE STD 386-1985 )
PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRNEAS DE M.T.
ZONA CARIBE

PL041300

02-05-02

1/2

BORNA PARKING INSERTABLE


PARA TERMINAL ENCHUFABLE
15,25 Y 35kV-200A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041400
.

A.R.S.

02-05-02

1/2

BORNA PARKING INSERTABLE


PARA TERMINAL ATORNILLABLE
15,25 Y 35kV-600A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041500
.

A.R.S.

02-05-02

1/2

BORNA PARKING DOBLE INSERTABLE


PARA TERMINAL ENCHUFABLE
15,25 Y 35kV-200A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041600
.

A.R.S.

02-05-02

1/2

BORNA PARKING INSERTABLE CON P.A.T.


PARA TERMINAL ENCHUFABLE
15,25 Y 35kV-200A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041700
.

A.R.S.

02-05-02

1/2

BORNA PARKING INSERTABLE CON P.A.T.


PARA TERMINAL ENCHUFABLE
15,25 Y 35kV-600A
PROYECTO TIPO
LNEAS ELCTRICAS AREAS DE 13,2, 24,9 Y 34,5 kV
ZONA CARIBE

PL041800
.

A.R.S.

15/05/02

PASO AEREO-SUBTERANEO TRIFSICO 13,2 kV


1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS M.T.
ZONA CARIBE

PL050100

P.T.B.

15/05/02

PASO AEREO-SUBTERANEO TRIFSICO 24,9 Y 34,5 kV


1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS M.T.
ZONA CARIBE

PL050200

P.T.B.

4 Y 5 TALADRO

609

7 Y 8 TALADRO

6 Y 7 TALADRO

609

9 Y 10 TALADRO

15/05/02

DERIVACIN AEREA-SUBTERANEA TRIFSICA 13,2 kV


CON PROTECCIN
1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS DE M.T.
ZONA CARIBE

PL050300

P.T.B.

6 Y 7 TALADRO

812
10 Y 11 TALADRO
6 Y 7 TALADRO

10 Y 11 TALADRO

15/05/02

DERIVACIN AEREA-SUBTERANEA TRIFSICA24,9 Y 34,5 kV


CON PROTECCIN
1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS DE M.T.
ZONA CARIBE

PL050400

P.T.B.

15/05/02

DERIVACIN AEREA-SUBTERANEA MONOFSICA 13,2 kV


CON PROTECCIN
1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS DE M.T.
ZONA CARIBE

PL050500

P.T.B.

15/05/02

DERIVACIN AEREA-SUBTERANEA MONOFSICA 24,9 Y 34,5 kV


CON PROTECCIN
1/30

PROYECTO TIPO
LNEAS ELCTRICAS SUBTERRANEAS DE M.T.
ZONA CARIBE

PL050600

P.T.B.