Professional Documents
Culture Documents
Ananyo Sengupta
1 / 77
Outline
Introduction
Overcurrent Relay
Differential Protection
Busbar Protection
Transformer Protection
Circuit Breakers
2 / 77
Faults include
short or low impedance circuits
open circuits
power swings
overvoltages
elevated temperature
off-nominal frequency operations
3 / 77
ground faults. Faults involving two or more phase conductors, with or without g
called
phasefaults.
faults.
areare
called
phase
Power systems have been in operation for over a hundred years now. Accumul
Power
systems have been in operation for over a hundred years now. Accum
is a fall in voltage throughout the power system. If the fault is a metallic fault, the voltageexperience
shows that all faults are not equally likely. Single line to ground faults (
experience shows that all faults are not equally likely. Single line to ground faults
at the fault location is zero. The voltage at the terminals of the generator will also drop,are the most likely whereas the fault due to simultaneous short circuit between all
the most
the fault due
to simultaneous
circuitThis
between
though not drastically. If the source is ideal, there will be no drop in voltage atare
thethree
lines, likely
knownwhereas
as the three-phase
fault
(L-L-L), is the short
least likely.
is depi
seen
generator terminals. Normally the relay is away from the fault location. Thus, as three
lines, known as the three-phase fault (L-L-L), is the least likely. This is de
from the relay location, a fault is characterized by a build-up of current, and to a certainin Table 1.1
1.1
in
Table
extent, collapse of voltage.
Table 1.1 Fault statistics with reference to type of fault
Figure 1.3 depicts various ground faults a s well as phase faults.
Table 1.1 Fault statistics with reference to type of fault
of Power Systen~Protectio~l
6 Fu~~da~,rentaLs
Fault
Severity
(a) L-Gfault
Fault
L-G
L-G
L-L
L-L-G
L-L
L-L-L
L-L-G
Total
L-L-L
Table
1.2 system
Faultelement
statistics with reference toProbabiliw
power system
Power
of faultselements
(9%)
Overhead
lines
50 of faults (9%)
Power
system
element
Probabiliw
9
Underground cables
iI Overhead
lines
Transformers
1050
i
Underground
cables
Generators
79
Transformers
Switchgem
1210
127
CT, PT relays, control equipment, etc
Generators
Total
100%
12
I,; Switchgem
12
CT, PT relays, control equipment, etc
magnitude of the f
The 1severity
Totalof the fault can be expressed in terms of the
100%
current and hence its potential for causing damage. In the power system, the three-ph
fault is the most severe whereas the single line-to-ground fault is the least severe.
The severity of the fault can be expressed in terms of the magnitude of the
current and hence its potential for causing damage. In the power system, the three
1.3.2
Diagram
of Voltages
and Currentsfault
During
Various
Fa
fault is thePhasor
most severe
whereas
the single line-to-ground
is the
least sever
( d ) L-L-L fault
1.3
.-..
, ,
,, .
. ,.
Relay Connection
~.!~~~ia~~o
l fe nPower
r o l s Sysrrnl Prvieclior~
Step-up
transformer
Breaker
contact
I
CT
HV
line
DT
Current
Trip battely
Trip coil
Relay
I 2
Relay t r i r
contact
Voltage
Trip
1 output
I
1
5 / 77
the relay designer from the actual value of primary current. Secondly, it isolates the relay
circuitry from the high voltage of the EHV system. A conventional electromagnetic
current transformer is shown in Figure 1.10. Ideally, the current transformer should
faithfully transform the current without any errors. I n practice, there is always some
error. The error creeps in, both in magnitude and in phase angle. These errors are known
I,i
as raho error and phase angle error.
16 F ~ ~ n c i a ~ ~ ~ eof
i l t Power
ols
Svsre~nProrection
Current Transformer
A
-
Transformer
CT Ratio = 1000/5
CT
&t
l000A
Source -
-- .
Bus
i/
Pr~mary
"E
*i
Secondary
Measurement CT
operating point
m
5
-5
51
.---------.-----.---..---Fault
Jt
Protective CT
operating point
5A
--f
Excitation, H(AT/m)
5A"
Relay
Output
Protective CT
output
s
Slope =
..
14
I
Figure 1.10 Current transformer.
Cm
Metering CT output
I l l l i l I ' 1 '
Full- I
7
load 4i-
; current
Max~mumfaultcurrent
Steps
downs
the
to the relay
level
I t may
be pointed
out here,
that current
current transformers
are used circuit
for metering
purposes
= 20 to 30 times
as well. However, there is a very important difference between a metering CT and a
full-load current
(1A
or
5A)
protection CT. A metering CT is so designecl (proportioned) that in case of faults, it will
Figure 1.11 Protective CT vs measurement CT.
saturate and thus save the instrument connected to its secondary from damage due to
excessive
current Onthe
the other
hand,
a protective
CT actual
is designedHV
to faithfully
reproduce
Isolates
relay
circuit
from
system
1.7.2
Voltage Transformer
the largest fault current. The operating po~nts,on the excitation charactenstics,
for the
given
in transformer steps down the high voltage of the line to a level safe eno
two types of CTs are shown in Figure 1.11. Further treatment of CT errors is
The
voltage
Should
operate in the linear zone during faultthe relaying
Appendix
1
system (pressure coil of relay) and personnel to handle. The s
current
Normal State
Abnormal
State
Action
State
Restorative
State
Outage
State
7 / 77
Threshold
Quantity
Normal State
Abnormal
State
Restorative
State
Metered
Quantity
Comparison
Element
Decision
Element
Action
Element
Outage
State
8 / 77
Evolution of Relays
Electromechanical Relay
First generation relays
Operates on the regulation force generated through the flow of current in windings on a
magnetic core
Advantages
1
Reliable
Disadvantages
1
9 / 77
Evolution of Relays
Static Relay
Second generation relays (came into operation in 1950s)
Made by semiconductors devices such as diode, transistors, ICs
No moving part
Advantages
Disadvantages
Less burden
Compact in size
4
6
Greater sensitivity
Costlier
10 / 77
Evolution of Relays
Digital Relay
Third generation relays (came into operation in 1980s)
Microprocessor based relays. Consists of hybrid analog and digital circuits.
Advantages
1
Less burden
Disadvantages
1
Sensitive to transients
11 / 77
Zones of Protection
Chapter 1
nce
tly,
ect
lity
on-
na
of
is
sly
h a
ber
ual,
if
12 / 77
Design Criteria
Sensitivity
It is the ability to operate correctly to the faults or abnormal conditions inside the zone
of protection
It refers to the minimum level of fault current at which the relay operates
Selectivity
Ability to isolate the faulty element causing minimum disruption to the system
Speed
Ability to detect and remove the faulty part as faster as possible
Reliability
1
Dependibility
degree of certainty of correct operation in response to system trouble
Security
degree of certainty that a relay will not operate incorrectly
13 / 77
of the hack-up protection should be equal to the operating time of primary protection plus
the operating time of the primary circuit breaker.
Primary
and the
Backup
Protection
Consider
radial system
shown in Figure 1.16. Relay B, in conjunction with circuit
breaker CBB, provides primary protection to the line section B-C. Relay A with circuit
breaker CBA provides back-up protection to the section B-C. Consider a fault in section
B-C as shown in Figure 1.16.
14 / 77
breakers. In other words, the operating time of the back-up protection must be delayed
disruption
to theprotection.
loads also
longer.
by an appropriate amount over
that of the primary
Thus, lasts
the operating
time
of the hack-up protection should be equal to the operating time of primary protection plus
the operating time of the primary circuit breaker.
Fault
Consider the radial system shown in Figure
1.16. Relay B, in conjunction with circuit
instant
breaker CBB, provides primary protection to the line section B-C. Relay A with circuit
breaker CBA provides back-up protection to the section B-C. Consider a fault in section
B-C as shown in Figure 1.16.
Primary relay RB
operates
When a fault takes place, both the primary relay RB and the back-up relay ItA, szart
ting simultaneously. i n case the primary protection (provided by RB + CBB) operates
ssfully, the line B-C gets de-energized but the loads on buses A and B remain
ected. Therefore, the back-up protectior 'provided by RA + CBAj resets without
g a trip command. The sequence of events in such a case is depicted in Figure 1.17.
ver, in case the primary protection fails to operate, the back-up which is already
oring the fault, waits for the time in which the primary would have cleared the fault
hen issues the trip command to its allied circuit breakers.
hen the back-up operates, the time for which the fault persists is longer and
ption to the loads also lasts longer.
P-
Fault
instant
I)
Primary
Primary CB
operating time
Primary relay RB
operates
P-
Primary
Primary CB
operating time
'
'
by an appropriate amount over that of the primary protection. Thus, the operating time
of the hack-up protection should be equal to the operating time of primary protection plus
the operating time of the primary circuit breaker.
Consider the radial system shown in Figure 1.16. Relay B, in conjunction with circuit
breaker CBB, provides primary protection to the line section B-C. Relay A with circuit
breaker CBA provides back-up protection to the section B-C. Consider a fault in section
B-C as shown in Figure 1.16.
Maloperation
Primary CB
operating time?
Primary
relaying time
22
F~~ncla~nenrals
of Power Sysrem Prorection
1.7.8 Maloperations
There should be proper coordination between the operating time of primary and back-up
protection. Figure 1.18 shows an instance of loss of selectivity between the primary and .
back-up protection. It can be seen that the back-up protection in this case issues trip
command to its breaker without waiting for the primary protection to do its job. This
results in operation of both the primary and the back-up, resulting in a longer and
unnecessary disruption to the system. It is said that with every additional relay used,
there is an increase in the probability of maloperation.
4+
Time
Primary CB
operating time?
Primary
relaying time
4+
Back-up CB
operating timeJ
t.
'
'
'
'
16 / 77
Overcurrent Relay
Irelay
PS
Relay trips is
PSM > 1
PS can be of the order of 50-200% of the relay rated current, and the time setting
ranges form 0.1-1s, 1-10s, 6-60s etc.
Widely used foor the protection of radial (distribution) lines
17 / 77
F ~ ~ ~ r c l r ~ r r ~o ef ~Po~ver
~ t a l s Sj~sreti7P,vr?crior~
Instantaneous
Overcurrent Relay
-
F ~ ~ ~ r c l r ~ r r ~o ef ~Po~ver
~ t:
a:
l s Sj~sreti7P,vr?crior~
4.2
-E::
0
a,
.-
-Ed.--E
.-E0
.-Eam,
.m..-CE
0
Operating lime
Operating lime
Current (amperes)
Pick-up value
Definite
Time
Relay relay characteristic.
Instantaneous over-current
Figure
2.4 Over-current
A
m
Current
-m
.-E
Plug setting
C
.t.-mE
@'
@'
Time setting
Trip output
d-
Plug setting
0m
C
.-
Time setting
-----f
-Pick-upr -value
Current
Operating time
f
+
+
-.
..
.-.
t =
a
(PSM ) 1
aExtremely Inverse Time Overcurrent Relay
I
80(TMS )
(PSM ) 1
where PSM is the plug-setting multiplier and TMS is the time-multiplier setting of the
relay. Thus, the operating timeopis directly proportional to the TMS and inversely
2
proportional to the PSM. The characteristics of the IDMT relay are shown in
Figure 2.6.
j.
j.1
t
.-
(, 1
?
J.
0----- r - - -
initial part, which tends to a definite minimum operating time as the current becomes
very high. The reason for the operating time becoming definite minimum, a t high values
of current, is that in the electromechanical relays the flux saturates at high values of
I the relay operating torque, which is proportional to the square of the flux,
current and
does not increase substantially after the saturation sets in. Such a characteristic came
about because of the limitation of the electromechanical technology Ideally, we may
op
demand Ithat the operating time be inverse in nature throughout the operating range. The
mathematical relation between the current and the operating time of IDMT characteristic
can be written as
13.5(TMS )
efinite time over-current relay can be adjusted to issue a trip output at a definite (and
ustable)
amount ofTime
time, after
it picks up. Thus,
it has a time-setting adjustment and
4.2 Definite
Over-current
Relay
pick-up adjustment. The characteristic and the block diagram are shown in
definite
2.9. time over-current relay can be adjusted to issue a trip output at a definite (and
ure
justable) amount of time,
after
it
picks
up.
Thus,
it has a time-setting adjustment and
A
pick-up adjustment. The characteristic and the block diagram are shown in
..
gure 2.9.
Time setting
4.3
.-m
J.
1i
i
(, 1
18 / 77
skOvercurrent
understand the working of an induction disk type relay; let u s first see how
be produced by two alternating fluxes acting on a common metallic but nonotor. Figure 2.7 shows two alternating fluxes
and @2 having a phase
of 0 between them.
Induced flux
f
hernating fluxes
Ed<-. -
aluminiurn disc
m1 sin t
m2 sin(t + )
dt
i 1
m1 cos t
i 2
m2 cos(t + )
m1 m2 sin t cos(t + )
F2 = 2 i1
m1 m2 sin(t + ) cos t
m1 m2 sin
19 / 77
Overcurrent
Relay
using
Disk
of Power
S y s t eInduction
~ Protr.crioll
f~
34 F~rrirln~ne~~tals
ThlS adjustment dial
Movable contact
..
---------,------ 5
,
20 / 77
Consider the network shown above. Let x be the fault distance (in percent) from bus 2.
Input to Relay R1 : V2 and I23 , to Relay R2 : V3 and I32
x = -100%
x = -50%
x = 50%
x = 200%
0.315
-1.246
0.187
-1.478
0.273
-4.218
0.597
-2.361
1.17
110.56
1.389
110.32
-72.474
1.109
-70.56
0.63
-1.245
0.561
-1.478
0.298
-2.36
0.298
-2.361
1.17
-69.443
1.389
-69.676
2.219
-70.56
1.109
109.44
Torque (K = 1)
x = - 100%
x = - 50%
x = 50%
x =200%
0.6617457
20
15
10
0
100
50
50
100
Distance (in percent)
150
200
22 / 77
Current
0.5
0.4
0.3
0.2
0.1
2.5
1.5
1
-100
0
100
200
Distance (in percent)
0.6
0
-100
3
Voltage (magnitude in p.u.)
0.7
50
0
-50
-100
-150
-100
0
100
200
Distance (in percent)
0
100
200
Distance (in percent)
Torque (for K = 1)
150
-1
-2
-3
-4
-5
-6
-100
0
100
200
Distance (in percent)
1
0.8
100
0.6
50
Torque
0.4
0.2
0
-50
-100
-100
-0.2
0
100
200
Distance (in percent)
-0.4
-100
0
100
200
Distance (in percent)
23 / 77
Current
0.5
0.4
0.3
0.2
0.1
3
2.5
2
1.5
1
-100
0
100
200
Distance (in percent)
0.6
0
-100
3.5
Voltage (magnitude in p.u.)
0.7
50
0
-50
-100
-150
-100
0
100
200
Distance (in percent)
0
100
200
Distance (in percent)
Torque (for K = 1)
150
-1
-1.5
-2
-2.5
-3
-3.5
-100
0
100
200
Distance (in percent)
1
0.8
100
0.6
50
Torque
-0.5
0.4
0.2
0
-50
-100
-100
-0.2
0
100
200
Distance (in percent)
-0.4
-100
0
100
200
Distance (in percent)
24 / 77
m positive torque when the current and voltage supplied to the current coil and
sure coil are in phase. If we define the maximum torque angle (MTA) as the angle
the voltage and current at which the relay develops maximum torque, then a
er can be called a directional relay with MTA of zero degree.
phasor diagram for a directional relay is depicted in Figure 2.23.
Directional OC Relay
Operating Principle
!
From CT
Toperating
PC CC sin( + PC )
. .~
i
'
I.
1 ;
..
Reverse fault
cos ( 8 - 7)
= K2 \ipc ICc cos ( 9 - T)
@pC @CC
ki
ng
oc
Bl
el
ay
igure 2.23 Phasor diagram for a directional relay based on induction principle.
, ,
zo
ne
Operating torque = K ,
Forward fault
is the voltage applied to the pressure coil. The current drawn by the pressure coil
the voltage by a large angle BPc
he fault moves from the forward to the reverse direction, the current undergoes
change in its phase whereas the phase of the voltage does not change substantially.
'1
I'.
' b
I
i
i1
:/ .,
-11 ,
,i
,I
25 / 77
0.6
Torque
0.4
Restraining torque
(spring torque)
Operating torque
0.2
0.2
Dead zone of relay 1
Dead zone of relay 2
0.4
100
50
50
Distance (in percent)
100
150
200
26 / 77
Figure 2.17
Ovrr-cxrrenr Proreerio~~
of Transmission L111rs 43
Fault
CT ratio n : 1
a-R
b-g
c-g
a-b
b-c
c-a
a-6-g
b-c-g
c-a-g
a-6-c
a-6-c-g
scheme shown in Figure 2.17. A little thought will show that if we connect an OC
In the residual current path a s shown in Figure 2.18, it will be blind to the load cu
(which is balanced three-phase current) and see only the ground fault currents
current in this path will be zero or near zero during normal balanced load conditio
Figure 2.17
27 / 77
4 Fl~?zdnn~entals
of Power Systen~Protection
well as during a three-phase fault. Thus, the setting of this relay, which is in the residual
urrent path, can be made independent of load current and can indeed be much smaller
han the load current.
Further, as illustrated in Figure 2.18, it is not necessary to use all the three relays
or detection and protection against phase faults. We can get rid of any one phase fault
elay without affecting the performance of the scheme. In Figure 2.18, the relay in the
hase b has been removed.
.
-
Figure 2.17
scheme shown in Figure 2.17. A little thought will show that if we connect an OC
In the residual current path a s shown in Figure 2.18, it will be blind to the load cu
(which is balanced three-phase current) and see only the ground fault currents
current in this path will be zero or near zero during normal balanced load conditio
T r ~ pcolt
Trlp
battery
R, Rg R'
Ground fault
OC relay R,
contacts
Figure 2.18 Two-phase fault relays and one ground fault relay for OC protection
of a three-phase feeder.
Table 2.2 shows the operation of relays for all the 11 shunt faults for OC schemes of
Figure 2.17 and Figure 2.18, which shows that all the 11 shunt faults are catered for by
hese schemes.
@ i
:i
.i
t
2
.I
. !I
28 / 77
Ground fault OC
29 / 77
PlPU
pick
/
relav!
ZS = constant
Fault current
of OC
UP
T
w
; Distance from
relay location
r------------_---------------
PlPU
pick
/
relav!
ZS = constant
Fault current
of OC
UP
T
w
; Distance from
relay location
r------------_---------------
PlPU
pick
/
relav!
ZS = constant
Fault current
of OC
UP
T
w
; Distance from
relay location
r------------_---------------
61
!
IpU
pick-up
of OC relay;
I
Three-phase
fault
62
!
!
Fault of I
same type I
I
I
I
L----------------
..
I Distance from
I relay location
21
33 / 77
are available through a CT and a PT, whose ratios have been assumed as 1: 1 for the sake
of simplicity. The reach of the distance relay is thus made equal to Z,,,. The line is
Introduction
Distance
Relay
modelled as a to
series
R-L circuit
for the purpose of relaying without much loss of accuracy,
as shown in Figure 6.3(b).
A
Reach point fault
Reach = Z,,,) Internal fault
1 External fault
.l
PT
Trip;
'R 4
E rv
nm
't
VR
RL
XL
i
(b)
34 / 77
B. Assume that the proposed relay is located at end A, where the local current and voltage
are available through a CT and a PT, whose ratios have been assumed as 1: 1 for the sake
Introduction
to Distance Relay
of simplicity. The reach of the distance relay is thus made equal to Z,,,. The line is
modelled as a series R-L circuit for the purpose of relaying without much loss of accuracy,
as shown in Figure 6.3(b).
'R 4
A
Reach point fault
Reach = RL
Z,,,) - XL
Internal fault
1 External fault
.l rv PT
E
't
VR
Trip;
nm
i
(b)
Consider three faults: an internal fault Fl, an external fault F3, and a fault at reach
point fault F2. Now, let us compare the relay voltage VR with the product of relay current
IRand Z, as shown in Table 6.1 for all the three faults.
r,
F3, External
F,, Reach point
E
F,, Internal
Current
at relay
location,' IR
183
IRZ
rv IRI
'R 4 Compare
Voltage
1v ~ l: ~
at relay
location, V R
't
VR,
VRZ
v ~ VR
l
RL >
IV831
'
XLIZsetI
lI~31
Thus, we can see from Table 6.1 that the trip law that emerges is;
nm
(b)
'
Desired
response
~ ~ ~ o fL
relay
Restrain
Verge of operation
Trip
1
iI
1
i
1
35 / 77
Fl117dfl1nenmls
of Power Systrn~Prorectrorr
Trip
F3
Assume that the proposed relay is located at end A, where the local current and voltage
: 1 for thethe
sakearc .resistance, the fault characteristic of the transmissi
e available through a CT and a PT, whose ratios have been assumed
When as
we1consider
simplicity. The reach of the distance relay is thus made
to Z,,,.from
Thethe
line
is
getsequal
modified
straight
lineI. with a slope of tan-'(AIR) to an area as sh
odelled as a series R-L circuit for the purpose of relaying without
much loss of accuracy,
Figure 6.6.
shown in Figure 6.3(b).
t
A
Reach point fault
Reach = Z,,,) Internal fault
1 External fault
.l
PT
-
Trip;
-R
't
X = lm(VI1)
E rv
nm
VR
Fault characteristic
RL
of XL
the line
Restrain
6.3
(b)
Operating characteristic
Restram
183
VR,
IV831
> lI~31IZsetI
Restrain
36 / 77
on the soft iron armature in 3uch a way that it :ends to close the rip
voltage coil, on the other hand, tends to keep the trip contacts open, thus
restraining torque. The controI spring keeps the contacts open when t
unenergized condition.
simple
impedance
relay
or,
IR
T > 0,
r
|VR |
k1
<
|IR |
k2
aa
Trip output
Restraining
torque
Restraining
quantity
VR
IR
Zseen
VL
PTR
IL
CTR
!
!
VL CTR
IL
PTR
0--1
VR
Soft iron
armature
Spring
Voltage
coil
Operating
torque
r-+--o
coil
quantity
( 1 ~ 1 and
~ the restraining torq
Reactance Relay
Structure
The implementation of the reactance relay using the four-pole induction cup str
shown in Figure 6.13.
of Power Sysren~Prorecriorr
130 Frrrida~~re~~tals
--
Trio
Restra~ning
Operating
I Principle
I
k1 > 0, k3 < 0, k2IZ,=
0, k 0,
h = 90o
,nJ ce -4 T) < -
Polarizing
K3
current coil
o = X,,, we get
If we set the MTA of the2directional element to be 90, and let (kl/k,)
IZ,,,/ cos
(6'-
. ,
,,
90") < Xn
Since JZ,,,, cos|V( 9 90") = JZ,,,, sin 0 = JX,,,, k1, which is the reactive part of the
o
R|
1
impedance seen by the relay, we finally get the trip law as:
|IR |
k3
If X
1 < X 1 thenotrip; elsek1restrain
or,
cos( 90 ) <
or, |Zseen | cos( 90 ) < k
3 impedance seen, and trips if
The relay is thus sensitive only to the reactive part of the
the reactive part is less than a particular
X,,.Hence, such a relay is called a
or, |Z operating
| sincharacteristic
< kk13setofvalue
reactance relay. Theseen
the relay on the R-X plane is a:~traight
line with intercept of X, on the reactance axis. The entire area below this straight line
or, the X
< Thus,
Xsetthe area occupied is too large. This is shown in
represents
trip
region.
seen
Figure 6.12.
~~
."
41
i
r;
:.'4
"
,i
,
t
1I
1
-4
characteristic
Figure 6.13 Implementation of reactance relay using the four-pole induction cup st
/////////,///////
X"
<
t R
Trip
Trip
The current
through one of the coils is shifted in phase so that th
Structure
proportional to I2 is produced by the interaction of the fluxes created by the two
The current through the pressure coiI is made to flow nearly in phase with the
coil voltage by connecting a resistance whose value is much large compare
pressure coil inductance. This makes the phase angle of pressure coil nearly equa
making the maximum torque angle r equal to 90" (since MTA = 90" - phase
pressure coil).
38 / 77
relay
his is clearly unacceptable. Therefore, the reactance relay cannot be used
byoccupies areas in both these quadrants, it does not exhibit any directional property
Thus a reactance relay which is set to protect the line section AB, a s shown in
tection of the transmission line but needs to be supewised from another relay
Figure
ts operation on load. A question may arise in the readers' mind at this stage. 6.16, in the forward direction also responds in the reverse direction for a n
unlimited distance. This again, is not a desirable feature. Therefore, we should use the
her about a relay which cannot even restrain on load? The answer lies in
the
reactance relay in conjunction with a directional relay or another distance relay having
rformance of the relay in the face of fault resistance. This is discussed
in
the directional
feature like the h010 relay.
.4.
Reactance Relay
Reverse c
-4Forward
Ii
shows a line section A-B being protected using a reactance relay. Let there
t the end of the protected line section, at point B, with a resistance equal to
Figure 6.14 Reactance relay operates during normal load flow.
be seen that the tip of the impedance seen phasor AC, still remains within
normal
load in spite of the i
ion. Thus,Figure:
the reachPerformance
of the reactance under
relay remains
unaffected
fect
of Arc Resistance
ontoReach
of Reactance
Relay
arc resistance.
This is only
be expected,
as the relay
measures only the 4
a
V and
I.
rtshows
of the
ratiosection
of phasors
a line
A-B being
protected
using a reactance relay. Let there
Restrain
..
Ii
I
?
Restrain
/
Restrain
/
I I
I I I / J / /
I/
* I
'
Forward faults
(First quadrant)
Trip
Trip
7 > 1 1 , , 1 1 ,
Setting = X,,
<
Restrain
7 > 1 1 , , 1 1 ,
Impedance seen
Setting = X,,
<
Reactance seen
Figure 6.16
Reactance seen
Trip
Trip
A
Impedance
seen of reactance relay.
Figure 6.15 Effect of arc resistance
on reach
Figure: Effect
of arcTrip
resistance on reach
Trip
39 / 77
relay
his is clearly unacceptable. Therefore, the reactance relay cannot be used
byoccupies areas in both these quadrants, it does not exhibit any directional property
Thus a reactance relay which is set to protect the line section AB, a s shown in
tection of the transmission line but needs to be supewised from another relay
Figure
ts operation on load. A question may arise in the readers' mind at this stage. 6.16, in the forward direction also responds in the reverse direction for a n
unlimited distance. This again, is not a desirable feature. Therefore, we should use the
her about a relay which cannot even restrain on load? The answer lies in
the
reactance relay in conjunction with a directional relay or another distance relay having
rformance of the relay in the face of fault resistance. This is discussed
in
the directional
feature like the h010 relay.
.4.
Reactance Relay
Reverse c
-4Forward
Ii
shows a line section A-B being protected using a reactance relay. Let there
t the end of the protected line section, at point B, with a resistance equal to
Figure 6.14 Reactance relay operates during normal load flow.
be seen that the tip of the impedance seen phasor AC, still remains within
normal
load in spite of the i
ion. Thus,Figure:
the reachPerformance
of the reactance under
relay remains
unaffected
fect
of Arc Resistance
ontoReach
of Reactance
Relay
arc resistance.
This is only
be expected,
as the relay
measures only the 4
a
V and
I.
rtshows
of the
ratiosection
of phasors
a line
A-B being
protected
using a reactance relay. Let there
Restrain
..
Ii
I
?
Restrain
/
Restrain
/
I I
I I I / J / /
I/
* I
'
Forward faults
(First quadrant)
Trip
Trip
7 > 1 1 , , 1 1 ,
Setting = X,,
<
Restrain
7 > 1 1 , , 1 1 ,
Impedance seen
Setting = X,,
<
Reactance seen
Figure 6.16
Reactance seen
Trip
Trip
A
Impedance
seen of reactance relay.
Figure 6.15 Effect of arc resistance
on reach
Figure: Effect
of arcTrip
resistance on reach
Trip
40 / 77
1 If IZ,
Mho Relay
i1
2,
where 9 is the phase angle between the voltage and current fed to the relay. The relay
characteristic is as shown in Figure 6.18.
if 2, < 2, cos (0
Operating Principle
k3 > 0, k2 < 0, k1 = 0, k4 0
For
T > 0,
k2 |VR |2 < k3 |VR ||IR | cos( )
I
|VR | k3
<
cos( )
|IR |
k2
or,
6.5.2
Figure: Characteristics
nofr aPower
ls
Svsrrnt
Prurecrion
implementation
Mho
Relay
Using
136 F ~ o l d a ~ ~ ~ eof
?.
6.5.3
Ld/
It can be seen from Figure 6.20 that the impedance seen by the relay during normal
IR outside the trip region of the characteristic. Thus, the
load (double-end-fed system) is well
Induction cup
relay is stable during load conditions.
XL
Polarizing
voltage coil
41 / 77
Mho Relay
Under-reach = AB
Percentage under-reach
<
Recall that the simple impedance relay also suffers from under-reach due to fault
relay
tance.
If we compare the under-reach of the two relays for the same fault resistance
?I,'
Figure 6.23 Directional property of rnho relay.
we find that the percentage under-reach of the mho relay
is slightly more than that
,,d, .:
Figure: Directional property of mho relay
1::;
e simple impedance relay.
kl
.'; It
6.5.6 Performance of Mho Relav Durina Power Swina
The mho relay bccupies a much smaller area on the R-X plane. To that extent
X
,
42 / 77
t2
t1
RA
t3
RB
80 %
10 %
50 %
R
Figure: Three-Stepped Distance Protection
43 / 77
50%
RA
80%
RB
44 / 77
45 / 77
while CT, has an actual ratio of nz and phase angle error of 8,. The difference between
these two currents,
up as spill current,
as shown in Figure 3.9. Since both
Actual Behaviour
oftherefore,
Simpleends
Differential
Scheme
the ratio and phase angle errors aggravate as primary current increases, the spill current
builds up as the 'through fault' current goes on increasing.
/P
= lr, eil
n:1
Equipment under
protection
A
,,
.-
Ip
- --
If, ex1
n :I
U
.
Spill current
\
?
External
fault
11, ext
.
?
n = nominal CT ratio
Primary current
'P
current
c u r rbecause
e n t because
errors
Figure:
current
of of
CTCTerrors
Figure Spill
3.9 Spill
46 / 77
pick-up value of the over-current relay in the spill path. This causes the relay to operate,
disconnecting
equipmentDifferential
under protectionRelay
from rest of the system. This is clearly a
Characteristics
oftheSimple
case of maloperation, since the relay has tripped on external fault. In such instances, the
differential scheme is said to have lost stability. To signify the ability of the differential
scheme to restrain from tripping on external faults, we define 'through fault stability
limit' as the maximum 'through fault' current beyond which the scheme loses stability.
In Figure 3.10, 'through fault stability limit' is shown as Istab
. .
I
>
External fault
characteristics
So
Pick-up value of OC
relay in spill path
1/
-1
Trip
f'
Through
fault current
Through
-2
fault stability
/'
<
/rob
FigureCharacteristics
3.10 Characteristics
of simple
differential
relay.
Figure:
of Simple
Differential
Relay
Compare this with the situation of an internal fault. The minimum internal fault
current required for the scheme to operate, correctly in this case, is decided by pick-up
value of the over-current relay in the spill path. To signify the spread between the
minimum internal fault current at which the scheme operates and the maximum 'through
f a a t ' current beyond which the scheme (mal)operates, we define a term called stability
ratio as:
47 / 77
'P
>
-*
CT
n : l
ir 1
CB
CB
Equipment under
/ Trip
protection
\
,
?
Trip,
Restraining coil
rn
'&
1,
12
Armature
Spring
rid output
(N,IN,) and an intercept KOon the y-axis. All points above the straight line will represent
the condition where the operating torque is greater than the restraining torque and hence
will fall in the trip region of the relay. All points below the straight line belong to the
restraining region. The operating characteristics of the percentage differential relay are
shown in Figure 3.14.
:..
'
Internal fault
characteristic
200% slope
,..
External fault
characteristic
Minlrnurn Internal
I
I
I
Figure 3.14
'
(";")
,
!
Thus, the spill current must be greater than a definite percentage of the 'through
fault' current for the relay to operate. Hence, the name percentage differential relay. The
slope of the relay is customarily expqessed as a percentage. Thus, a slope of 0.4 is
expressed as 40% slope.
49 / 77
'"1
QA
CBB, CBc
NO = Normally open
r m
OC
relav o u t ~ u t
Trip battery
Figure 5.2 Wrong method of selection of CT ratios for differential protection of busbars.
5.2.2
50 / 77
Method
Differential Protection Busbar
Figure 5.3 shows the correct method of setting the CT ratios for the busbar differential
protection. It can be seen that the CT ratios of all the CTs are equal and are based on
the
primaryofcurrent
of that feeder which carries the maximum current. Thus, all the CT
Selection
CT Ratios
'"1
5.3
CTA or CTB. In all likelihood, CTc will therefore become saturated. We can, therefore, no
CTc willFault
faithfully transform the fault current. For the sake of
onger
assumeand
thatInternal
External
llustration, we have assumed that the secondary current of CTc is only 4 A instead of
10 A. I t can be seen from Figure 5.4 that this results into a spill current of 6 A, causing
he scheme to maloperate, i.e. lose stability on external fault.
".
CT, and CT. are unsaturated
J4A
o
I
Plug setting -+
A
.
.
10A
R OC relay
A
-1
.
?
External fault
1iiiii.:
I
4A
In the worst case scenario, CTAand CTB continue to transform faithfully as per their
ameplate CT ratio but CTc, which carries the total fault current, gets completely
aturated. This clearly indicates the occurrence of an imbalance in transformed secondary
urrents, resulting in substantial spill current. This situation most likely will cause the52 / 77
CTc is concerned. This is depicted in Figure 5.5, wherein it can be seen that CTc now
oesExternal
not carry any
current
(assuming a single-end-fed system with source on leftandfault
Internal
Fault
and side). Since CTA and CTB are not carrying excessive primary currents, they
ansform the current without too much error. There is thus a spill current in the spill
ath and the scheme operates as expected.
No source
10A
Zero
The maloperation of the busbar differential scheme on external faults is caused due
non-ideal behaviour of a CT carrying excessive primary current. I t will, therefore, be
rtinent, at this point to take a closer look at the actual behaviour of protective current
nsformers.
53 / 77
Actual 106
Behavious
of a Protective CT
F~rnda~tlentais
of Power Svste~nProtection
54 / 77
near the zero-crossings of the primary current. This is shown in Figure 5.8
be seen that in order to reach the peak of the sinusoidal flux waveform, the
ristics is passed, any further increase in flux demand causes adeep
disproportionately
into saturation. Due t o flatness of the excitation curve in this region
crease in the magnetizing current requirement of the CT. This
is illustrated
in current is demanded by the CT The waveform of the ex
amount
of exciting
5.7. It may also be noted that I, is no longer sinusoidal and its
waveform
has a and is, in fact, very peaky in nature.
becomes distorted
I
nt peak.
4 Flux @
i'
Time
Magnetizing current
'10
Figure 5.7 Operation of the CT beyond the knee point of the B-H curve.
55 / 77
circuit to signify the fact that the magnetizing branch is taking up all the seconda
Actual
of a Protective
CT
current
andBehavious
none is available
to the burden.
IplN
Rb
>Ii:
Xb
RS
I, =
Xs
zero
1s
Burden
lo = /,IN
f
ru"
CT ratio = N : l
.
c
),
lo
= Ip/N
Burden
ru"
...
%-
.,.~
..".
56 / 77
CTc
Saturated CT
Rb
I
I
I
I
Rb
I Short circuit
I-----------_______----.
OC relay
Figure 5.10 Secondary equivalent circuit with one CT fully saturated during external fau
57 / 77
plug
setting = ,I
CTA
10.4
1,
, - - 1,
'c -
- .IOC
Rb
CTc
Rs
RL
- .
Po
CTB
OC relay
p~ck-up
58 / 77
ected side carry the line currents I* IB, IC, while the windings on the delta side
phase currents whose magnitudes are
as shown in the phasor diagram in Figure 4.2. Each line current on the delta s
phasor sum of two of the phase currents. Hence, there is a phase shift of 30" be
line currents on the two sides of the star-delta transformer. Figure 4.2 s
schematic representation of the transformer connection with all voltages and
Primary
Secondary
Core
\
A
Figure 4.1 Construction of a three-phase transformer.
59 / 77
3. Line currents on the star side are determined. These are same as
Percentage
Differential Protection
of I,.Transformer
I,, Ib and
pment
of Connections
4. Line currents on the delta side are then determined. These are (Ic
with
Delta-star transformer
A7
Figure 4.8 Determination of the line currents on the two sides of the t
; Zero
., .
, _ _ _ _ _ _ _ _ - - _ _ _ _ _ A
1
\
Figure 4.9 Final connections of percentage differential relay under normal load flow or
external balanced fault.
61 / 77
-I
c-g
exerna faull
62 / 77
Transjorn~erProrecrion
35
there is no fault current through the primaries of the CTs on the scar side. The path of
the fault current 1s shown in bold lines. It can be seen from the figure that the fault
current flows through the spill path in two of the percentage differential units causlng
them to operate, thus tripping out the transformer.
, _ . _ _ _ _ _ _ _ _ _ _ ---.
Percentage differential relay
Figure 4.11 Phase c-to-ground (c-g) internal fault.
63 / 77
Il - I2
'P
>
-*
CT
n : l
ir 1
CB
CB
Equipment under
/ Trip
protection
\
,
?
Trip,
Restraining coil
rn
'&
1,
:..
Internal fault
characteristic
200% slope
,..
12
'
Minlrnurn Internal
Armature
Spring
I
I
I
Figure 3.14
rid output
External fault
characteristic
'
(";")
,
!
Thus, the spill current must be greater than a definite percentage of the 'th
fault' current for the relay to operate. Hence, the name percentage differential relay
slope of the relay is customarily expqessed as a percentage. Thus, a slope of
expressed as 40% slope.
The percentage differential relay does not have a fixed pick-up value. The
automatically adapts its pick-up value to the 'through fault' current. As the 'through
current goes on increasing, we are in effect asking the relay to take it easy, by introd
a restraining torque proportional to the circulatillg current. I t can be seen
Figure 3.14,that the 'through fault' stability and the stability ratio of the perce
Inrush Current
Therefor., when voltage is passing through zero and becoming positive the flux
should be at its negative maxima and increasing as shcwn in Figure 4.13. In a time equal
to T!2 (half cycle), the flux changes from -$, to + 6, as shown in Figure 4.14. The
change in flux is therefore 2 q , in TI2 seconds. This is the steady-state picture.
Transient flux
flux
i 10
Steady-state
magnetizing current
H(AT1rn)
: 810
Inrush current
Time
65 / 77
.I,
Inrush Current
= Vm
v = Vmv sin
( w tsin
+ 8)( w t
8)
(4.3)
. i,I ,
,
(4.3) a."
a."
The The
variable
8 in the
expression
controlscontrols
the switching
instant. instant.
variable
8 inabove
the above
expression
the switching
Let @
b ethe
value of
the flux.
Then
weThen
can write:
Let
@ binstantaneous
ethe instantaneous
value
of the
flux.
we can write:
d @=
+
(21(21
- sin ( w t 8) dt
sin ( w t + 8) dt
d @=
The value of K can be found out from the initial condition, i.e. when t = 0,
@ = @R = residual flux. Substituting this initial condition in Eq. (4.4), we get
@, = -(&)coso
+K
(4.5)
which gives K as
which gives K as
@,
-(&)coso
+K
(4.5)
'
Vm
K = 9, + (x;-)cos8
'
Vm
K = 9, + (x;-)cos8
66 / 77
Inrush Current
'
Thus the expression for flux in the transformer in the initial moments Just after
switching can be written as
' v,"
, , (t)cos~
=
- (xjcos(Wt
+ e)
We can write (VmINw)as p,, the peak value of the flux, giving
Sj'stettr Protecrio~l
Thus, the flux in 90
the Fltt~~/n~rrc.~tinl,r
transformerqfisPob~!er
a function
of the following three factors:
1. Residual flux gR
Table 4.1 Harmonic content of inrush waveform
2. Instant of switching e
Frequency
Magnitude
3. Magnetic properties of core, i.e. the
amount
Fundamentalof magnetizing current
100% required to
produce a given amount of flux.
DC
!
;
1
I
40-60%
+gm, harmonic
the flux attains an amplitude
of 34, at
Thus, we see that for 0 = 0 and qR =Second
30-70s
OJ t = n radians. To satisfy a flux demand of 34,, the transformer primary draws a very
Third
harmonic
10-30%
large magnetizing current with a peaky non-sinusoidal waveform.
Fourthare
harmonic
than 5%voltage
Inrush is also experienced whenever there
sudden changes in Less
the system
such as sudden recovery of system voltage
clearing of a fault, Less
somewhere
Fifthonharmonic
than 5% in the
system.
Sixth harmonic
Less than 5 6
While an unloaded transformer, whichSeventh
is being
switched on, experiences
harmonic
Less thanan5%inrush,
an adjacent transformer, which is in service, may also experience a smaller degree of
inrush. This is known as sympathetic inrush.
Figure 4.15 shows the conceptual scheme of a harmonic restraint diff
Further, as such a high current flows only on one side of the transformer (on the side
The fundamental component of spill current is segregated with the help of
which is being connected to the supply), it looks like an internal fault to the differential
used to develop the tripping torque. The non-fundamental component of th
scheme and ends up as spill current.
aids the unfiltered circulating current in developing the restraining torqu
As seen in Section 4.3, a short circuit at the terminals of a transformer causes similar
the relay stable on inrush while at the same time not affecting its operat
magnitudes of currents to flow. Hence, the percentage differential relay is likely to
genuine internal faults.
maloperate on magnetizing inrush.
67 / 77
I:
1.I Restrain
Percentage Differential Relay with Harmonic
Sixth harmonic
Seventh harmonic
Less than 5 6
Less than 5%
Transf~7rmerProrecrron
I
(17
- 12)
Fundamental
component
1 :
91
CT
j.
\,
CT secondaw
currents I,, 1;
Transformer
Filter
Unfiltered
All harmon~w
I I
Fundamental +
all harmonics
i
> '
Operating
torque
-Relay
Fundamental
Harmonics
circulating current
Conceptual representation of harmonic restraint percentage differential
relay.
. .
harmonics
spill current
All
.
Fundamental
spill current
A percentage differential relay has a certain minimum value of pick-up for internal faults.
Faults with fault current below this value are not detected by the percentage differential
68 /h77
~gh
relay. Winding-to-core faults, which are of the single phase-to-ground type, involving
High resistance ground fault may not be detected by the percentage differential relay \
Reach of restricted
thus it requires more sensitive relaying scheme.
earth fault protection
OC relay
Figure 4.17
protection for
delta transformer;
side of delta-star transformer.
The reach of such a protection must be restricted
to Earth
thefault
winding
ofthethe
otherwise it may operate for any ground fault,
in the
system
- restricted
Since anywhere
this is a current balance
scheme,
it is independent
of the load current and hen
can be made as sensitive as desired.
earth fault protection.
92
Figure 4.18 shows the restricted earth fault protection whose reach is limited to the st
side of the transformer. Ground faults beyond the star side CTs, anywhere in the syste
do cause current to flow on the secondary of the CTs. However, the currents circula
through the CT in the neutral path and the CT in faulted phase. Thus, no spill curre
flows and the scheme remains stable on external faults.
Transformer
I
OC relay
Reach of restricted
earth fault protection
Figure 4.17 Earth fault protection for the delta side of delta-star transformer.
Figure 4.18! Restricted earth fault protection for star side of delta-star transformer.
Since this is a current balance scheme, it is independent of the load current and hence
can be made as sensitive as desired.
I . ,,_ ',
,,
.,. ,<,
, ,
'
69 / 77
from the transformer terminals, the reflected current can be quite small. This can be
Inter-turn faults
heavy current
to flow
within4.19.
the shorted turns. However, seen
fromcause
simplified
analysis
of Figure
Inter-turn
Faults
inthe
Transformer
from the
transformer
terminals, the reflected current can be quite small. This can be seen
from the simplified analysis of Figure 4.19.
d
Figure 4.19 Calculation of terminal current for an inter-turn fault.
-kV
(I,)
-kV
(I,)
lo3)
= 25 kW
= ( 5 V)(5000 A)
= ( 5 V)(5000 A)
The current that circulates within the short-circuited turns is 5000 A whereas at
400 kV terminals the current is only of the order of 0.11 A. Thus, inter-turn faults
difficult
to detect
using
over-current
or differential
principles
of relaying.
The current
that
circulates
within
the
short-circuited
turn
is is
5000
The current
that
circulates
within
the
short-circuited
turns
5000A.
A whereas
at theHowever, t
can the
cause
severeishot
spots
resulting
in 0.11
deterioration
insulation.
400 kV terminals
current
only
of the
order of
A. Thus, of
inter-turn
faults are
Whereas
at
the
400
kV
terminals
the
current
is
of
the
order
of
0.11
A.
This has
led to theordevelopment
of Buchholz
relay which
makesthey
use of the h
difficult to detect using
over-current
differential principles
of relaying.
However,
generated
and
the consequent
decomposition
of oil or
to differential
sense the fault
by purely
can cause
severe
hot spots
resulting
deterioration
of insulation.
Thus
inter-turn
faults
are
difficult
toindetect
using
over-current
principles
of n
electrical
This has led
to themeans.
development of Buchholz relay which makes use of the heat
relaying.
generated and the consequent decomposition of oil to sense the fault by purely nonelectrical means.
4.10 Incipient Faults in Transformers
70 / 77
against
faults - relay
insulation
faults
onceptual Protection
diagram of the
inner minor
workinginternal
of the Buchholz
is shown
in between turns, breakdown
1. When an
incipient
such asetc.
a winding-to-core fault or an inter-turn fault
core,
corefault
heating
the transformer winding, there is severe heating of the oil. This causes gases
rated fromDuring
the oil around
is a build-up
of oil pressure
causing oil
these350C.
faultsThere
transformer
insulating
oil decomposes
in different hydrocarbon
nto the conservator. A vane is placed in the path of surge of oil between the
gases,
CO,
CO
.
2
er and the conservator. A set of contacts, operated by this vane, is used as trip
of the Buchholz relay This output of Buchholz relay may be used to trip the
er.
,
of
:t.
>.
To consewator
tank
Buchhalz trip
Figure 4.21 Construction of the Buchholz relay.
Lower circuit is for more sever faults - such as short circuit between phases or to earth,
Buchholz relay also has another set of contacts operated by a float. These
tay open faults
when the
transformer
tank is equipments.
filled with oil. However, in case of
in the
tap changing
oil or decomposition of oil, the float sinks causing the contacts to close. Loss
no doubt cause the transformer temperature to rise but does not warrant
71 / 77
73 / 77
74 / 77
75 / 77
76 / 77
77 / 77