XMP2-32 Series Combined HMI/PLC Unit MANUAL

XMP2-32R-E

16 Digital Inputs (PNP), 16 Digital Outputs


Relay PLC, 7 colour TFT Touch Screen - 220VAC

XMP2-32R-C

16 Digital Inputs(PNP), 16 Digital Outputs


Relay PLC, 7 colour TFT Touch Screen - 24VDC

XMP2-32T-E

16 Digital Inputs, 16 Digital Outputs


Transistor PLC, 7 colour TFT Touch Screen - 220VAC

XMP2-32T-C

16 Digital Inputs, 16 Digital Outputs


Transistor PLC, 7 colour TFT Touch Screen - 24VDC

Doc Ref: LMAN009_R2V2

XMP2-32 with colour touch screen

Index

Page

Chapter 1 XMP2-32R/T introduction


1-1 Performance and characteristics
1-2 Specs
1-2-1 General specs
1-2-2 HMI specs
1-2-3 PLC specs
1-3 Part name
1-3-1 LED display
1-3-2 Download port
1-3-3 Com port
1-3-4 Port A and B
1-4 Dimensions

4
5
6
7
9
9
9
9
10

Chapter 2 In/out specs and external layout


2-1 Input specs and layout
2-2 Output specs and layout

12
13

Chapter 3 PLC function and use


3-1
3-2
3-3
3-4

PLC instructions
Soft component range
Build a project
Communication function
3-4-1 Com port
3-4-2 Communication parameters
3-4-3 Communication mode

16
18
20
23
24
25

Chapter 4 HMI function and use


4-1 Online
4-2 Build a project

28
30

Chapter 5 The extension ability


5-1 Summarization
5-2 Extend MA model
3-4-1 Summarization
3-4-2 Model specs
3-4-3 Model connection

32
33
34
35

XMP2-32 Combined Unit Manual

Page 2 of 36

LMAN009_R2V2

XMP2-32 Introduction

XMP2-32R/T introduction

Model

Function

XMP2-32R-E

16 DI, 16 DO Relay PLC, with a 7" colour TFT touch screen and
26 function keys, AC220V

XMP2-32R-C

16 DI, 16 DO Relay PLC, with a 7" colour TFT touch screen and
26 function keys, DC24V

XMP2-32T-E

16 DI, 16 DO Transistor PLC, with a 7" colour TFT touch screen


and 26 function keys, AC220V

XMP2-32T-C

16 DI, 16 DO Transistor PLC, with a 7" colour TFT touch screen


and 26 function keys, DC24V

1-1 Performance and characteristics


1-2Specs

1-3 Parameters

1-4 Dimensions

XMP2-32 Combined Unit Manual

Page 3 of 36

LMAN009_R2V2

1-1 Performance and characteristics

XMP2-32 family is PLC+HMI integrators. This family has 4 models as listed above. The 4 models
have the same aspect. Besides fulfilling the control requirements, XMP2-32 models can replace
the common HMI and PLC in the control system. The compact shape saves space and also
convenient for the maintenance engineer.

XMP2-32 MP760-T + XC2-32.


Integrate logic control, analogue input/output, HMI in one body
Digital Input: 16 points.
Digital Output: 16 points.
Brief and simple program interface.
HMI Part: 7" touch screen, true colour TFT, 256 colour, 480234 pixel, LCD life can reach
50,000 hours.
26 Function Keys, sensitive and precise.
Supports high speed count, high speed pulse, external interruption.
Multi-function download port: Uses the same cable to download HMI and PLC
program.
Waterproof level: IP20.
Compact size, saves space in the electric control cabinet.

XMP2-32 Combined Unit Manual

Page 4 of 36

LMAN009_R2V2

1-2 Installation steps


1-2-1

General specs

Input Voltage

AC220V

Power Consumption

Less than 10W (TYP2.0W)

Momentary Power-Off
Allowance

Less than 20ms

Voltage Endurance

AC1000V-10mA 1minute (between signal and ground)

Insulated Impedance

DC500V about 10M (between signal and ground)

Operating Temperature

0~50

Storage Temperature

10~60

Ambient Temperature

20~85% (No Dew)

Vibration

10~25Hz (X, Y, Z each direction 30 minutes 2G)

Anti-interference

Voltage Noise: 1000Vp-p

Ambient Condition

No corrosive gas

Protection Level

IP20

XMP2-32 Combined Unit Manual

Page 5 of 36

LMAN009_R2V2

1-2-2

HMI specs

Screen Property

Type

TFT 256-colour LCD

Screen Dimension

7 inch

Use Life

Over 50000 hours, 25 , 24 hours


running

Display Area

480*234

Contrast

Not modifiable

Character setting

English, Japanese,

Character size

Free size and font

Touch mode

Digital mode touch

Picture

8KB

Data

4KB

Register

XMP2-32 Combined Unit Manual

Page 6 of 36

LMAN009_R2V2

1-2-3

PLC specs

Item

Specs
XMP2-32R/T-E

Program executing format

Loop scan format, time scan format

Program format

Instruction, C language and ladder chart

Processing speed

0.5us

Power -off Retentive

Use Flash ROM and Li battery

User programs capacity

128KB

I/O points

16 digital input, 16 digital output

Internal coil (M) number

8512

Points
Timer (T)

640
100mS timerSet time 0.1~3276.7 seconds

Specs

10mS timerSet time 0.01~327.67 seconds


1mS timerSet time 0.001~32.767 seconds

Points
Counter (C)

640
16 bits counterset value K0~32767

Specs
32 bits counterset value -2147483648~2147483647
Data Register (D)

2512 words

Flash ROM Register (FD)

512 words

High speed processing function High speed countpulse outputexternal interrupt


Time Scan Interval Setting

0~99mS

Password protection

6 bits ASCII

Self-diagnose function

Power on self-diagnoseMonitor timergrammar check

XMP2-32 Combined Unit Manual

Page 7 of 36

LMAN009_R2V2

1-3 Part names

Display and
touch area

Number keys

Function keys

USB CJ45 port


Product label

Com Port

Power point

Download Port

Output point

XMP2-32 Combined Unit Manual

Page 8 of 36

Input point

LMAN009_R2V2

1-3-1

LED display

PWR: Power supply light


RUN: program control light
STOP: program control light

1-3-2

Download port

The port is RS-232 standard and able to download PLC program and HMI screen.
Pin2
Pin3
Pin5

RXD
TXD
GND

Used as RS-485 com port: for HMI connecting with slave device
Pin1

Pin9

B
PRT (when HMI connecting with slave device, short pin
5&6)
DOWNLOAD (short pin 5&8 to force-download HMI
screen)

Pin6
Pin8

Cable connection figure:

Attention:
1 Do not switch off when downloading, or you have to download again
2 The cable for downloading the HMI screen is the same as downloading PLC program
3 Do not download when XCPPro and TP software are both open
RS-232 download port is only used to download

1-3-3

Com port

The port is RS-232 standard, is used to connect PC and HMI.


Pin2
Pin3
Pin5

1-3-4

RXD
TXD
GND

Port A and B

The port is RS-485 standard, is used to connect meter, inverter, extension model, etc.

XMP2-32 Combined Unit Manual

Page 9 of 36

LMAN009_R2V2


Attention:
A, B port and RS-232 COM port is the same port, and cannot be used at the same time.

1-4 Open and close XCP Pro

Outline dimension (mm):

Install dimension (mm):

XMP2-32 Combined Unit Manual

Page 10 of 36

LMAN009_R2V2

In/out specs and external layout

2-1 Input specs and layout

2-2Output specs and layout

XMP2-32 Combined Unit Manual

Page 11 of 36

LMAN009_R2V2

2-1 Input specs and layout


Input specs:
Input signal voltage

DC24V10%

Input signal current

7mA/DC24V

Input ON current

Above 4.5mA

Input OFF current

Below 1.5mA

Input response time

About 10ms

Input signal format

Point input or NPN collector


open transistor

Circuit insulation

Photoelectric coupling
isolation

Input connection figure:

Input point arrangement:

XMP2-32 Combined Unit Manual

Page 12 of 36

LMAN009_R2V2

2-2 Output specs and layout


Relay output:
Internal power

Below AC250VDC30V

Circuit insulation

Machine insulation

Action indication

LED light

Max load

Resistor load

3A

Induction load

80VA

Light load

100W

Open circuit current

No

Minimum load

DC5V 2mA
OFFON

10ms

ONOFF

10ms

Response time

Transistor output:
Internal power

Below DC5~30V

Circuit insulation

Optical coupling insulation

Action indication

LED light

Max load

Resistor load

0.8A

Induction load

12w/DC24V

Light load

1.5W/DC24V

Open circuit current

< 0.1 mA

Minimum load

DC5V 2mA
OFFON

0.2ms

ONOFF

0.2ms

Response time

XMP2-32 Combined Unit Manual

Page 13 of 36

LMAN009_R2V2


Output connection figure:
Relay output:

Transistor output connection

Output point arrangement:

XMP2-32 Combined Unit Manual

Page 14 of 36

LMAN009_R2V2

PLC functions and use

3-1 PLC instructions

3-2Soft component range

3-3 Build a project

3-4 Communication function

XMP2-32 Combined Unit Manual

Page 15 of 36

LMAN009_R2V2

3-1 PLC instructions


XMP2-32R/T-E series product uses XC2 series PLC (the PLC instructions are the same as XC232). It contains SFC instructions, applied instructions and special function instructions. Please
refer to XC Series PLC Operating Manual:
I/O point definition and distribution.
1. High speed count
(1) Increment mode: 5 channels

Channel

Input

Counter

Highest frequency

CHL1

X0

C600

80KHZ

CHL2

X1

C602

80KHZ

CHL3

X3

C604

10KHZ

CHL4

X6

C606

10KHZ

CHL5

X11

C608

10KHZ

Counter

Highest frequency

(2) Pulse + direction mode: 3 channels

Channel
Pulse

Input
Direction

CHL1

X0

X1

C620

80KHZ

CHL2

X3

X4

C622

10KHZ

CHL3

X6

X7

C624

10KHZ

(3) AB phase mode: 3 channels

Channel

Phase B

CHL1

X0

CHL2
CHL3

Input
Phase A

Counter

Highest frequency

X1

C630

80KHZ

X3

X4

C632

5KHZ

X6

X7

C634

5KHZ

XMP2-32 Combined Unit Manual

Page 16 of 36

LMAN009_R2V2

2. High speed pulse output


a) T type: Y0, Y1 available, the highest frequency is 400KHz
b) RT type: Y0, Y1 available, the highest frequency is 400KHz
c) R type: unavailable
3. Interrupt function
Channel

Input

Pointer tag

Disable interruption
Rising interruption Falling interruption instruction

CHL1
CHL2
CHL3

X2
X5
X10

I0000
I0100
I0200

I0001
I0101
I0201

M8050
M8051
M8052

4. Frequency measurement
The point is X1, X11, and X12.
5. Pulse width modulation
The point is Y0, Y1.
1T type: Y0, Y1 available
2RT type: Y0, Y1 available
3R type: unavailable
6. Precision timer
32-bit precise timer, the timer range is T600 to T618, matching with 10-interruption tag.

XMP2-32 Combined Unit Manual

Page 17 of 36

LMAN009_R2V2

3-2 Soft component range

Soft component Name

Range

Point

Input point

X000~X017 (octal)

16

Output point

Y000~Y017 (octal)

16

Auxiliary relay

Status

Timer

Counter

Data register

FD

Flash ROM
Register

M0~ M2999
M3000~M7999

8000

M8000~M8511

512

S0~ S511
S512~M1023

1024

T0~T99100ms not accumulation


T100~T199100ms accumulation
T200~T29910ms not accumulation
T300~T39910ms accumulation
T400~T4991ms not accumulation
T500~T5991ms accumulation
T600~T6181ms with interruption precise time

40

T620~T639vacant
C0~C29916 bits forward counter
C300~C31832 bits forward/back counter
C320~C59832 bits forward/back counter
C600~C618one phase high speed counter
C620~C628Pulse + direction high speed
counter
C630~C638AB phase high speed counter
D0~D999
D4000~D4999

640

2000

For special using D8000~D8511

512

FD0~FD255

256

For special use


FD8000~FD8255

256

NOTE:
The memory area in is the defaulted power failure retentive area, the power failure
retentive area of soft components D, M, S, T, C can be set via FD register. For details,
please see the following table.
Flash ROM register neednt be set for power failure retentive area,
The serial number of input coil and output relay are octal data, other memory number are all
decimal data.

XMP2-32 Combined Unit Manual

Page 18 of 36

LMAN009_R2V2

Address
type

Default value

Power failure memory


area

Area

Function

FD8202

First address of the power


failure memory area of D

4000

D4000~D4999

FD8203

First address of the power


failure memory area of M

3000

M3000~M7999

FD8204

First address of the power


failure memory area of T

640

No set

FD8205

First address of the power


failure memory area of C

320

C320~C639

FD8206

First address of the power


failure memory area of S

512

S512~S1023

NOTE:
Users can set the power failure memory area.

XMP2-32 Combined Unit Manual

Page 19 of 36

LMAN009_R2V2

3-3 Build a project


XMP2-32R/T-E series products are integrated with XC series PLC and HMI. When editing the
PLC program, please use XCP Pro software, which is the same as XC series PLC.
1. Select the product type
Open XCPPro, click file---change PLC model:

Select XMP2-32:
2. Editing the PLC program
After selecting the type, user can edit the program in the software. The editing specs and
operating details please refer to XC Series PLC Edit Software XCPPro Manual.
The interface of software is as below:

XMP2-32 Combined Unit Manual

Page 20 of 36

LMAN009_R2V2


3. Download program
After editing and saving the program, the user needs to download them to the XMP. Before
downloading, ensure the XMP has connected with computer successfully. Click
software serial port configuration

to open

When below window shows, it means the connecting is successful. Click OK to continue.

If the connection is not successful, the window will show communication error. Please check the
serial port and the cable.

to download the PLC program. If the PLC is running, it will


After successful connection, click
pop up the stop running window. Click OK to continue downloading.

XMP2-32 Combined Unit Manual

Page 21 of 36

LMAN009_R2V2

After downloading, click

to run the PLC program.

4. Upload the program


If you want to check the PLC program in XP/XMP, click
Then click

to upload the program to the PC.

to save the program.

XMP2-32 Combined Unit Manual

Page 22 of 36

LMAN009_R2V2

3-4 Communication function


XMP2-32R/T series supports Modbus and free format communication.
For instructions please refer to XC Series PLC User Manual.

3-4-1

Com port

XMP2-32R/T series product has program port (DB9 pins port), RS-232 COM port (DB9 pins port)
and RS-485 COM port (A and B point). Program port can only be used to download PLC program
and HMI pictures. However, RS-232 and RS-485 COM port can be used to communicate with
other devices. The communication parameters (baud rate, data bit, etc) can be set via software.
RS-485 COM port point A means + signal, point B means - signal.
Attention:
RS-485 and RS-232 COM port are the same; do not use them at the same time.

XMP2-32 Combined Unit Manual

Page 23 of 36

LMAN009_R2V2

3-4-2

Communication parameters

Communication parameters of RS-232 and RS-485 COM port can be set via FLASH register in
the XMP.
The defaulted parameters:
Station 1, baud rate 19200bps, 8 data bits, 1 stop bit, even check

Station No.

Modbus station No.: 1-254, 255(FF) is for free format


communication

Baud rate

300bps~115.2Kbps

Data bit

8 or 7 bits

Stop bit

2 or 1 bits

Check

Even, odd, no check

Communication parameters setting are as below table:


Note:
After changing the parameters in Flash register, a reboot is required
.
Number

Function

Description

FD8220

Communication mode

255 is free format,

(Station number)

1~254 is modbus station number

Communication format

Baud rate, data bit, stop bit, check

ASC timeout judgment time

Unit: ms, 0 means no timeout waiting

FD8223

Reply timeout judgment time

Unit: ms, 0 means no timeout waiting

FD8224

Start symbol

High 8 bits invalid

FD8225

End symbol

FD8226

Free format setting

High 8 bits invalid


8/16 bits cushion,
With/without start bit,
With/without stop bit

FD8221
COM Port FD8222

XMP2-32 Combined Unit Manual

Page 24 of 36

LMAN009_R2V2


Setting up communication

FD8221:
15

14

13

12

11

10

0No check
1Odd
check
2Even
check

0300bps
1600bps
21200 bps
32400 bps
44800 bps
59600 bps
619.2K bps
738.4K bps
857.6K bps
9115.2K bps

02 stop bits
21stop bit

08bits data
17bits data

FD8226:
15

14

13

12

11

10

0:8 bits communication


1:16 bits communication

Reserved

0: without start symbol


1: with start symbol
0: without end symbol
1: with end symbol

XMP2-32 Combined Unit Manual

Page 25 of 36

LMAN009_R2V2

3-4-3

Communication mode

Modbus communication
XMP series product support master and slave mode of Modbus communication.
Master format: When PLC is set to be master station, PLC sends request to other slave station
devices via Modbus instructions, other devices respond to the master station.
Slave format: When PLC is set to be slave station, it can only respond to other master devices.
The defaulted status of XMP is Modbus slave mode.

Communication address
The internal soft units numbers of XMP correspond with Modbus station address numbers.
Please see the following table:
Coil space: (Modbus address prefix is 0x )
Bit component address

Modbus address (Decimal K) Modbus address (Hex H)

M0~M7999

0~7999

0~1F3F

X0~X511

16384~16895

4000~41FF

Y0~Y511

18432~18943

4800~49FF

S0~S1023

20480~21503

5000~53FF

M8000~M8511

24576~25087

6000~61FF

T0~T618

25600~26218

6400~666A

C0~C634

27648~28282

6C00~6E7A

Register space: (Modbus address prefix is 4x )


Word component address Modbus address (Decimal K) Modbus address (Hex H)
D0~D7999

0~7999

0~1F3F

TD0~TD618

12288~12906

3000~326A

CD0~CD634

14336~14970

3800~3A7A

D8000~D8511

16384~16895

4000~41FF

FD0~FD5000

18432~23432

4800~5B88

26624~27135

6800~69FF

FD8000~FD8511

Free format communication


Free format communication transfer data in the format of data block, each block can transfer 128
bytes at most. Meanwhile each block can set a start symbol and an end symbol.
When communicating in free format mode, FD8220 should be 255.

XMP2-32 Combined Unit Manual

Page 26 of 36

LMAN009_R2V2

HMI function and use

4-1HMI function

4-2 Building a project

XMP2-32 Combined Unit Manual

Page 27 of 36

LMAN009_R2V2

4-1 HMI function


The HMI part of XMP2-32R/T-E series product is integrated with MP-760T touch screen.
The faceplate key-presses are as below:

Key

Function
Running the program, LED indication light
Stop running the program, LED indication light
Default main menu or most used screen.
Turn the screen to the last page
Turn the screen to the next page

Inquiry, jump to the user appointed screen

To write the modified value in the register and continue


modifying next register.
Alarming list key. After setting the function of alarming list,
press this key to jump to the alarm list screen.
Clear the selected area when modifying the register data.
Set the positive or negative of the data when modifying the
register data.
Number key 0-9.

Function key F1-F6

NOTE:
Besides the function listed in the previous table, all the keys can be defined as the function of
force ON, force OFF, reverse or momentary ON.

XMP2-32 Combined Unit Manual

Page 28 of 36

LMAN009_R2V2


Please see below picture. Open TouchWin software, put a button or function button in the
screen. Press, enter in the window, all the key-presses can be found in this menu. The user can
set the key function as they need.

XMP2-32 Combined Unit Manual

Page 29 of 36

LMAN009_R2V2

4-2 Building a project


Use the Touchwin software.
1.
2.
3.
4.

to build a new project.


Open the software, click File New or click
Choose MP760-T (XMP-32) in the panel window:
Click next; choose XC Series for PLC port device:
Click next; choose XC Series for download port device:

Click next to complete the building.

The editing interface is as below:

Note:
For software user details please refer to TP Touch Screen User Manual.

After completing the project editing and saving, connect the download port of the XMP and
computer serial port with the downloading cable. Make sure the XMP power is on. Click
File Download to start downloading data, the download window is as below:

or

If it appears the item connection overtime, check cable, please download again.

XMP2-32 Combined Unit Manual

Page 30 of 36

LMAN009_R2V2


The downloading is completed when it shows the below window:

Attention:
(1) Do not cut the power when downloading, or you have to download again.
(2) The downloading cable for the TouchWin screen is the same as the downloading PLC
program.
(3) Do not download when XCPPro and TouchWin software are both open.

XMP2-32 Combined Unit Manual

Page 31 of 36

LMAN009_R2V2

The extension ability

5-1 Summarization

5-2Extend MA model

5-1 Summarization
XMP2-32R/T series product cannot extend BD board.
For extending other devices, use RS-232 or RS-485 (point A and B) COM port.
RS-232 COM port can connect with the computer, HMI to monitor the program.
RS-485 COM port can connect with meter, inverter, function model, etc. It can extend 32 external
devices at most.
Attention:
The connection method is Bus mode, transmission line should start from station 1 to station 2,
and then from station 2 to station 3connect in this sequence until the last station. Star mode or
ring mode connections are not permitted.

XMP2-32 Combined Unit Manual

Page 32 of 36

LMAN009_R2V2

5-2 Extend MA model

XMP2-32R/T series product can extend MA model via RS-485 COM port (A and B point) in order
to control and measure analog signals.
The type and specs of MA model are as below:

5-2-1 MA model type

Type

Function

MA-8DA

8 channels analog output, voltage 0-5V or 0-10V, current 0-20mA or 4-20mA

MA-7PT-P

7 channels PT100 temperature measurement control, PID adjustment inside

MA-8TC-P

8 channels K type thermocouple temperature measurement control, PID


adjustment

XMP2-32 Combined Unit Manual

Page 33 of 36

LMAN009_R2V2


5-2-2 MA model specs
MA-8DA:
Item

Voltage Output

Current Output

Analogue input range

DC0~5V0~10V

DC0~20mA4~20mA

(External load resistor


2K~1M)

(External load resistor less than


500)

Digital output range

10 bits binary data

Resolution

1/1024(10 bits)

Integrated Precision

0.8%

Scan speed

2ms per channel

COM port

RS-485

Power supply for


analogue usage

DC24V10%, 100mA

Insulation Format

DC/DC convert, optical coupling insulation

Installation format

Can fix with M4 screw or install on DIN46277 (width: 35mm) track

Dimension

140W73H90D

MA-7PT-P:
Item

Content

Analogue input signal

Pt100 platinum resistor

Temperature
measurement range

-100 ~350

Digital output range

-1000~3500, 16 bits with symbol, binary

Control precision

0.5

Accuracy

0.1

Integrated precision

0.8% (relative max value)

Scan speed

100ms7 channels

Power supply for analog DC24V10%50mA


Installation Format

Fix with M4 screws or install on DIN46277 (width 35mm) track

Dimension

63mm102mm73.3mm

XMP2-32 Combined Unit Manual

Page 34 of 36

LMAN009_R2V2


MA-8TC-P:
Item

Content

Analogue input signal

K type thermocouple

Temperature measurement range

0 ~1000

Digital output range

0~1000016 bits with symbol, binary

Control precision

0.5

Accuracy

0.1

Integrated precision

0.8% (relative max value)

Scan speed

100ms8 channels

Power supply for analog

DC24V10%50mA

Installation Format

Fix with M3 screws or install on DIN46277 (width 35mm) track

Dimension

63mm102mm73.3mm

5-2-3 MA model connection


XMP2-32R/T product can connect with MA model via RS-485 COM port (A and B point). It can
extend 8 MA models via setting DIP switches.
Please see the connection figure:
The details and method please refer to MA Model Manual.

XMP2-32 Combined Unit Manual

Page 35 of 36

LMAN009_R2V2

Documentation Reference
Document Number
LMAN

009

R2

Revision Date
V2

17/07/2012

XINJE IS A REGISTERED TRADEMARK OF XINJE ELECTRICAL CO.LTD.


REPLICATION OF THE INFORMATION CONTAINED WITHIN THIS DOCUMENT
WITHOUT PRIOR NOTIFICATION AND AGREEMENT IS PROHIBITED.

For help and support regarding your XINJE products visit the online
Support Centre or contact us on: support@listo-ltd.com.

www.listo-ltd.com
www.xinje-support-centre-listo.com

International partners with:

XMP2-32 Combined Unit Manual

Page 36 of 36

LMAN009_R2V2