You are on page 1of 158

Technical Data

1756 ControlLogix I/O Modules

Catalog Numbers 1756 series


Topic

Page

Available 1756 I/O Modules

page 2

Environmental Specifications - 1756 I/O Modules

page 3

Digital I/O Modules

page 3

Analog I/O Modules

page 5

Specialty I/O Modules

page 6

Module Specifications

page 7

ControlLogix I/O Accessories

page 156

The ControlLogix architecture provides a wide range of input and output


modules to span many applications, from high-speed digital to process control.
The ControlLogix architecture uses Producer-Consumer technology, which
allows input information and output status to be shared among multiple
ControlLogix controllers.

ControlLogix
Controllers
Output Modules
Input Modules

Each ControlLogix I/O module mounts in a ControlLogix chassis and


requires either a removable terminal block (RTB) or a 1492 interface module
(IFM) to connect all field-side wiring. RTBs and IFMs are not included with
the I/O modules. They must be ordered separately.

1756 ControlLogix I/O Modules

Available 1756 I/O Modules

I/O Type

Catalog Number

AC digital

1756-IA8D
1756-IA16
1756-IA16I
1756-IA32
1756-IM16I
1756-IN16

page 7
page 9
page 11
page 13
page 57
page 59

1756-OA8
1756-OA8D
1756-OA8E
1756-OA16
1756-OA16I
1756-ON8

page 76
page 79
page 82
page 85
page 88
page 130

DC digital

1756-IB16
1756-IB16D
1756-IB16I
1756-IB16ISOE
1756-IC16
1756-IG16
1756-IH16I
1756-IH16ISOE
1756-IV16
1756-IV32

page 15
page 17
page 19
page 21
page 26
page 50
page 53
page 55
page 71
page 73

1756-OB8
1756-OB8EI
1756-OB8I
1756-OB16D
1756-OB16E
1756-OB16I
1756-OB16IS
1756-OB32
1756-OC8
1756-OG16
1756-OH8I
1756-OV16E
1756-OV32E

page 91
page 93
page 96
page 98
page 101
page 103
page 105
page 107
page 109
page 125
page 128
page 133
page 136

Contact

1756-OW16I

page 139

1756-OX8I

page 142

Analog

1756-IF6CIS
1756-IF6I
1756-IF8
1756-IF16
1756-IF4FXOF2F
1756-IR6I
1756-IT6I
1756-IT6I2

page 28
page 32
page 36
page 43
page 47
page 61
page 65
page 68

1756-OF4
1756-OF6CI
1756-OF6VI
1756-OF8

page 111
page 114
page 117
page 119

HART interface

1756-IF8H

page 40

1756-OF8H

page 122

Specialty

1756-CFM
1756-HSC

page 145
page 149

1756-PLS

page 152

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Environmental Specifications - 1756 I/O Modules


Attribute

Value

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

060 C (32140 F)

Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-4085 C (-40185 F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat)

595% noncondensing

Vibration
IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Digital I/O Modules

The 1756 digital I/O modules support these features:


Variety of voltage interface capabilities
Isolated and nonisolated module types
Point-level output fault states
Direct-connect or rack-optimized communication
Field-side diagnostics on select modules
In addition, you can select these types of digital I/O modules.

Digital I/O Type

Description

Diagnostic

These modules provide diagnostic features to the point level. These modules have a D at
the end of the catalog number.

Electronic fusing

These modules have internal electronic fusing to prevent too much current from flowing
through the module. These modules have an E at the end of the catalog number.

Individually isolated

These modules have individually isolated inputs or outputs.


These modules have an I at the end of the catalog number.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type
1756 digital AC input modules

Features
Change of state: Software configurable
Timestamp of inputs: 200 s
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital AC output modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the


Coordinated System Time
Fault states per point: Hold last state, on or off (off is default)
States in Program mode per point: Hold last state, on or off (off is default)
Fusing:
1756-OA8D, 1756-OA8E: Electronically fused per point
1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A
interruption current, Littelfuse p/n H2153.15
All other modules: Not protected. A fused IFM is recommended to protect outputs
(see publication 1492-2.12)
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital DC input modules

Reverse polarity protection: All modules except 1756-IG16 module


Change of state: Software configurable
Timestamp of inputs:
100 s for sequence of events modules
200 s for all other modules
Module keying: Electronic, software configurable
RTB Keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type
1756 digital DC output modules

Features
Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the
Coordinated System Time
Fault states per point: Hold last state, on or off (off is default)
States in Program mode per point: Hold last state, on or off (off is default)
Fusing:
1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OV16E, 1756-OV32E: Electronically
fused per point
All other modules. Not protected. A fused IFM is recommended to protect outputs
(see publication 1492-2.12)
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 digital contact modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the


Coordinated System Time
Configurable fault states per point: Hold last state, on or off (off is default)
Configurable states in Program mode per point: Hold last state, on or off (off is default)
Fusing: Not protected. A fused IFM is recommended to protect outputs (See
publication 1492-2.12)
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

Analog I/O Modules


Module Type
1756 analog input modules

The 1756 digital I/O modules support these features:


Features
On-board data alarming
Scaling to engineering units
Real-time channel sampling
Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Module conversion method: Sigma-Delta

1756 analog output modules

Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Module conversion method: R-Ladder DAC, monotonicity with no missing codes
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type
1756 high-speed analog combination module

Features
Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Input conversion method: Successive approximation
Output conversion method: R-Ladder DAC, monotonicity with no missing codes
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 analog RTD and thermocouple modules

Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Module conversion method: Sigma-Delta
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756 analog modules with HART interface

Data format: Integer mode (left justified, 2s complement), Floating point IEEE 32 bit
Input conversion method: Successive approximation
Output conversion method: R-Ladder DAC, monotonicity with no missing codes
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

Specialty I/O Modules

These specialty modules are available:

Module Type

Features

1756-CFM configurable flow meter module

The 1756-CFM module provides Totalizer mode for metering applications, or high-speed
frequency measurements for speed or rate control applications, on two channels
connected to flowmeters.
Totalizer fill and prover
High-resolution 100 kHz max
Frequency 0.0005 Hz resolution
Reverse polarity protection: Outputs only
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical

1756-HSC high-speed counter module

The 1756-HSC module provides four high-speed, output-switching, on-off windows. The
module uses pulses for counting and frequency.
Counter: 1 MHz max
Rate Measurement: 500 kHz max
Encoder: 250 kHz max
Debounce filter: 70 Hz max
Module keying: Electronic, software configurable
RTB keying: User-defined mechanical keying

1756-PLS programmable limit switch module

The 1756-PLS module supports enhanced packaging applications.


Requires three contiguous slots in chassis
RTB keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA8D
ControlLogix AC (79...132V) diagnostic input module
1756-IA8D

Simplified Schematic
+5V

10

12

11

14

13

16

15

18

17

20

19

Not Used
Daisy Chain to
Other RTBs

Input
Display
GND

GND

+5V ControlLogix
Backplane Interface
Open Wire
Display

ControlLogix
Backplane Interface

L1-0 Loss of Field Power

L2-0

IN-0

L2-0
Group 0

IN-1

L2-0

IN-2

L2-0

IN-3

L2-1

47 k, 1/2 W
5% Resistor

IN-4

L2-1
Group 1

Group
0

IN-5

L2-1

IN-6

Group
1

47 k, 1/2 W,
5% Resistor

IN-7

L2-1
L2-1

L1-1 Loss of Field Power

L2
L1

Diagnostics - 1756-IA8D

AC INPUT
ST 0 1 2 3 4 5 6 7 O
FLT 0 1 2 3 4 5 6 7 K

Attribute

1756-IA8D

Open wire

Off-state leakage current 1.5 mA min

Loss of power

Transition range 4685V AC

Timestamp of diagnostics

1 ms

Technical Specifications - 1756-IA8D


Attribute

1756-IA8D

Inputs

8 diagnostic (4 points/group)

Voltage category

120V AC

Operating voltage range

79132V AC,
4763 Hz

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Power dissipation, max

4.5 W @ 60 C

Thermal dissipation

15.35 BTU/hr

DIAGNOSTIC

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IA8D

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

16 mA @ 132V AC

Inrush current, max

250 mA

Input impedance, max

8.25 k @ 132V AC, 60 Hz

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA8D
Certification(1)

1756-IA8D

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA16
ControlLogix AC (79...132V) input module
1756-IA16

Simplified Schematic

10

12

11

14

13

16

15

18

17

20

19

IN-1

+5V

IN-O

Daisy
Chain to
Other
RTBs

L2-0

IN-0

Group 0

GND

IN-3

IN-2

IN-5

IN-4

IN-7

IN-6

L2-0

ControlLogix Display
Backplane
Interface

L2-0

IN-9

IN-8

IN-11
Group 1

IN-10

IN-13

IN-12

IN-15

L2-1

L2

ST 0 1 2 3 4 5 6 7 O
FLT 0 1 2 3 4 5 6 7 K

DIAGNOSTIC

Publication 1756-TD002A-EN-E - May 2009

Group 1

IN-14

L2-1

AC INPUT

Group 0

L1

Technical Specifications - 1756-IA16


Attribute

1756-IA16

Inputs

16 (8 points/group)

Voltage category

120V AC

Operating voltage range

74132V AC,
4763 Hz

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

105 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.8 W @ 60 C

Thermal dissipation

18.41 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

13 mA @ 132V AC

1756 ControlLogix I/O Modules

Attribute

1756-IA16

Inrush current, max

250 mA peak (decaying to <37% in 22 ms, without


activation)

Input impedance, max

10.15 k @ 132V AC, 60 Hz

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA16
Certification(1)

1756-IA16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

10

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA16I
ControlLogix AC (79...132V) isolated input module
Simplified Schematic

L2-0

+5V

IN-O

1756-IA16I

Isolated
Wiring

L2-2

L2-0
L2-4

GND
ControlLogix Display
Backplane
Interface

Jumper Bar
(Cut to Length)

Nonisolated
Wiring

The jumper bar part number is 97739201


and is included with the module.
L2

L2-0

IN-0

L2-1

IN-1

L2-2

IN-2

L2-3

IN-3

L2-4

10

IN-4

L2-5

12 11

IN-5

L2-6

14 13

IN-6

L2-7

16 15

IN-7

L2-8

18 17

IN-8

L2-9

20 19

IN-9

L2-10

22 21

IN-10

L2-11

24 23

IN-11

L2-12

26 25

IN-12

L2-13

28 27

IN-13

L2-14

30 29

IN-14

L2-15

32 31

IN-15

L2-15
Not used

34 33

Not Used
Not Used

36 35

L1-0
L1-2
L1-4

L1

Daisy Chain to
Other RTBs

Technical Specifications - 1756-IA16I


AC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IA16I

Inputs

16 individually isolated

Voltage category

120V AC

Operating voltage range

79132V AC,
4763 Hz

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

125 mA

Current draw @ 24V

3 mA

Power dissipation, max

4.9 W @ 60 C

Thermal dissipation

16.71 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 79V AC, 4763 Hz

On-state current, max

15 mA @ 132V AC, 4763 Hz

Inrush current, max

250 mA

11

1756 ControlLogix I/O Modules

Attribute

1756-IA16I

Input impedance, max

8.8 k @ 132V AC, 60Hz

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA16I
Certification(1)

1756-IA16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

12

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA32
ControlLogix AC (74...132V) input module
Simplified Schematic

1756-IA32

+5V

IN-O
L2-0

Group 0

GND

Daisy Chain
to Other RTBs

ControlLogix Display
Backplane
Interface

Group 1

IN-1
IN-3
IN-5
IN-7
IN-9
IN-11
IN-13
IN-15
L2-0
IN-17
IN-19
IN-21
IN-23
IN-25
IN-27
IN-29
IN-31
L2-1

10

12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

IN-0
IN-2
IN-4
IN-6
IN-8
IN-10
IN-12
IN-14
L2-0
IN-16
IN-18
IN-20
IN-22
IN-24
IN-26
IN-28
IN-30
L2-1

Group 0

Group 1

L1

L2

Technical Specifications - 1756-IA32


AC INPUT
ST 0 1 2 3 4 5 6 7

1
ST 8 9 0
1 1 1
ST 6 7 8
2 2 2
ST 4 5 6

1
1
1
9
2
7

1
2
2
0
2
8

1
3
2
1
2
9

1
4
2
2
3
0

1 O
5
K
2
3
3
1

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IA32

Inputs

32 diagnostic (4 points/group)

Voltage category

120V AC

Operating voltage range

74132V AC,
4763 Hz

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

Power dissipation, max

6.1 W @ 60 C

Thermal dissipation

20.8 BTU/hr

Off-state voltage, max

20V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 74V AC

On-state current, max

15 mA @ 132V AC

Inrush current, max

390 mA

Input impedance, max

14.0 k @ 132V AC, 60 Hz

13

1756 ControlLogix I/O Modules

Attribute

1756-IA32

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous
I/O group to group, I/O to system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA32
Certification(1)

1756-IA32

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

14

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16
ControlLogix DC (10...31.2V) input module
1756-IB16

Simplified Schematic
+5V

IN-0

IN-1

IN-0

Group 0

IN-2

IN-3

GND-0

Daisy Chain
to Other
RTBs

GND

IN-4

IN-5

IN-6

IN-7

ControlLogix
Backplane
Interface

Display

GND-0

GND-0
IN-9

IN-8
IN-10

IN-11

Group 1

Group 0

IN-12

IN-13
IN-15

Group 1

IN14
GND-1

GND-1

DC COM

Technical Specifications - 1756-IB16


DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IB16

Inputs

16 (8 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10...31.2V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

2 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.1 W @ 60 C

Thermal dissipation

17.39 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

10 mA @ 31.2V DC

15

1756 ControlLogix I/O Modules

Attribute

1756-IB16

Inrush current, max

250 mA peak (decaying to < 37% in 22 ms, without


activation)

Input impedance, max

3.12 k @ 31.2V DC

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16
Certification(1)

1756-IB16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

16

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16D
ControlLogix DC (10...30V) diagnostic input module
Simplified Schematic
Input +5V
IN-0

ControlLogix
Backplane
Interface Display

Daisy Chain to Other RTBs

Group 0

Group 1

GND-0
GND

Group 2

Open Wire

Group 3

1756-IB16D

GND-0

IN-0

GND-0
GND-0

IN-1
IN-2

GND-0

IN-3

GND-1
GND-1

10 9
12 11

IN-4
IN-5

GND-1

14 13

IN-6

GND-1

16 15

IN-7

GND-2

18 17

IN-8

GND-2
GND-2

20 19

IN-9
IN-10

GND-2
GND-3

24 23
26 25

IN-11
IN-12

GND-3

28 27

IN-13

GND-3
GND-3
GND-3

30 29

34 33

IN-14
IN-15
Not Used

Not Used

36 35

Not Used

22 21

32 31

14.3 k, 1/4 W
2% Resistor

Group

Group

14.3 k, 1/4 W
2% Resistor

Group

Group 3

DC COM

Diagnostics - 1756-IB16D
Attribute

1756-IB16D

Open wire

Off-state leakage current 1.2 mA min

Timestamp of diagnostics

1 ms

Technical Specifications - 1756-IB16D


DC INPUT
ST 0 1 2 3 4 5 6 7
FLT 0 1 2 3 4 5 6 7 O
K
ST 8 9 10 11 12 13 14 15
FLT 8 9 10 11 12 13 14 15
DIAGNOSTIC

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IB16D

Inputs

16 diagnostic (4 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10...30V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

4 ms + filter

Current draw @ 5.1V

150 mA

Current draw @ 24V

3 mA

Power dissipation, max

5.8 W @ 60 C

Thermal dissipation

19.78 BTU/hr

Off-state voltage, max

5V

17

1756 ControlLogix I/O Modules

Attribute

1756-IB16D

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

13 mA @ 30V DC

Inrush current, max

250 mA

Input impedance, max

2.31 k @ 30V DC

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16D
Certifications(1)

1756-IB16D

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

18

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16I
ControlLogix DC (10...30V) isolated input module
1756-IB16I

Simplified Schematic
+5V
IN-0
GND-0

Isolated
Wiring

DC-0 (-)
DC-1 (-)

GND
ControlLogix Display
Backplane
Interface

Jumper Bar (Cut to Length)

Nonisolated
wWi
ring

DC (-)

IN-0

DC-0 (+)

IN-1

DC-1 (+)

GND-2

IN-2

IN-3

GND-3

Source Input Wiring


DC-5 (-)
DC-6 (-)

GND-0
GND-1

GND-4

10

IN-4

GND-5

12 11

IN-5

GND-6

14 13

IN-6

GND-7

16 15

IN-7

GND-8

18 17

IN-8

GND-9

20 19

IN-9

GND-10

22 21

IN-10

GND-11

24 23

IN-11

GND-12

26 25

IN-12

GND-13
GND-14

28 27

IN-13

30 29

IN-14

GND-15

32 31

IN-15

GND-15
Not Used

34 33

Not Used
Not Used

36 35

(+) DC-5 (+)


(+) DC-6 (+)

Sink Input
Wiring

DC (+)

Daisy Chain to Other RTBs

Technical Specifications 1756-IB16I


DC INPUT

ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IB16I

Inputs

16 individually isolated

Voltage category

12/24V DC sink/source

Operating voltage range

10...30V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

4 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Power dissipation, max

5 W @ 60 C

Thermal dissipation

17.05 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10 V DC

On-state current, max

10 mA @ 30V DC

Inrush current, max

250 mA peak (decaying to < 37% in 22 ms, without


activation)

19

1756 ControlLogix I/O Modules

Attribute

1756-IB16I

Input impedance, max

3 k @ 30V DC

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16I
Certification(1)

1756-IB16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

20

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16ISOE
ControlLogix DC (10...55V) sequence of events input module
Simplified Schematic
Electronic Current
Limit Circuit

1756-IB16ISOE

Isolated Wiring
GND-0
GND-1
GND-2
GND-3
Source Input Wiring GND-4
DC-5 (-)
GND-5
GND-6
DC-6 (-)
GND-7
GND-8
Jumper Bar
GND-9
Display (Cut to Length)
GND-10
GND-11
Nonisolated
GND-12
Wiring
GND-13
GND-14
GND-15
GND-15
DC (-)
Not Used
DC-0 (-)

+5V
IN-0

GND-0
ControlLogix
Backplane
Interface

10 9
12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

Sink Input Wiring


IN-0
DC-0 (+)
IN-1
DC-1 (+)
IN-2
IN-3
Source Input Wiring
IN-4
DC-5 (+)
IN-5
IN-6
DC - 6 ( + )
IN-7
IN-8
Sink Input Wiring
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
Not Used
DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IB16ISOE


SOE INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IB16ISOE(1)

Inputs

16 individually isolated, sequence of events

Voltage category

24/48V DC sink/source

Operating voltage range

10...55V DC

Digital filter, off to on

050 ms

Input delay, off to on

Hardware delay (10 s nominal/20 s max)


+ Firmware scan (up to 25 s)
+ Input filter time (user selectable time: 0ms...50ms)
+ ASIC delay (175 s - FIFO/625 s - Coordinated System
Time per point)

Input delay, on to off

Hardware delay (25 s nominal/50 s max)


+ Firmware scan (up to 25 s)
+ Input filter time (user selectable time: 0ms...50ms)
+ ASIC delay (175 s - FIFO/625 s - Coordinated System
Time per point)

Current draw @ 5.1V

320 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.5 W @ 60 C

Thermal dissipation

17.22 BTU/hr

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2.0 mA @ 9V DC

On-state current, max

5.1 mA @ 4855V DC

21

1756 ControlLogix I/O Modules

Attribute

1756-IB16ISOE(1)

Input impedance, max

10.8 k @ 55V DC

Cyclic update time

250 s...750 ms

Isolation voltage

250V continuous, inputs to system


125V continuous, channel to channel

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink
module to coordinate system time.
(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16ISOE
Certification(1)

1756-IB16ISOE

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

22

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB32
ControlLogix DC (10...31.2V) input module
1756-IB32

Simplified Schematic
+5V
IN-0
GND-0

Group 0

GND

Daisy Chain
to Other RTBs

ControlLogix
Backplane
Interface

Display

Group 1

IN-21
IN-23
IN-25
IN-27
IN-29
IN-31

24 23

34 33

IN-0
IN-2
IN-4
IN-6
IN-8
IN-10
IN-12
IN-14
GND-0
IN-16
IN-18
IN-20
IN-22
IN-24
IN-26
IN-28
IN-30

GND-1

36 35

GND-1

IN-1
IN-3
IN-5
IN-7
IN-9
IN-11
IN-13
IN-15
GND-0
IN-17
IN-19

10

12 11
14 13
16 15
18 17
20 19
22 21

26 25
28 27
30 29
32 31

DC COM

Group 0

Group 1

Diagnostics - 1756-IB32
Attribute

1756-IB32

Change of state

Software configurable

Timestamp of diagnostics

200 s

Technical Specifications - 1756-IB32


DC INPUT
ST 0 1 2 3 4 5 6 7

ST 8 9
1
ST 6
2
ST 4

1
7
2
5

1
0
1
8
2
6

1
1
1
9
2
7

1
2
2
0
2
8

1
3
2
1
2
9

1
4
2
2
3
0

1 O
5
K
2
3
3
1

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IB32

Inputs

32 (16 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10...31.2V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

380 s + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

420 s + filter

Current draw @ 5.1V

120 mA

Current draw @ 24V

2 mA

23

1756 ControlLogix I/O Modules

Attribute

1756-IB32

Power dissipation, max

6.2 W @ 60 C

Thermal dissipation

21.1 BTU/hr @ 60 C

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA

On-state current, max

5.5 mA

Inrush current, max

250 mA (decaying to < 37% in 22 ms, without activation)

Input impedance, max

5.67 k @ 31.2V DC

Cyclic update time

100 s...750 ms

Isolation voltage

250V (continuous), Reinforced Insulation Type between


Input group to system
250V (continuous), Basic insulation type between Input
group to Input group
Routine tested at 1900V AC for 2 s, between Input group
to Input group and Input group to system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module Location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1 - on signal ports(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

24

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IB32
Certification(1)

1756-IB32

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

25

1756 ControlLogix I/O Modules

1756-IC16
ControlLogix DC (30...60V) input module
1756-IC16

Simplified Schematic

10

12

11

14

13

16

15

18

17

20

19

IN-0

IN-1

+5V

IN-0

IN-3

GND-0

Group 0

IN-2

IN-5

IN-4

IN-7

GND

IN-6

GND-0

ControlLogix Display
Backplane
Interface

GND-0

IN-9

IN-8

IN-11
Group 1

Group 0

IN-10
IN-11

IN-13

Group 1

IN-14

IN-15

GND-1

GND-1

Daisy Chain to
Other RTBs

DC COM

Technical Specifications - 1756-IC16


DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

26

Attribute

1756-IC16

Inputs

16 (8 points/group)

Voltage category

48V DC sink

Operating voltage range

30...55V DC @ 60 C
30...60V DC @ 55 C

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

4 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Power dissipation, max

5.2 W @ 60 C

Thermal dissipation

17.73 BTU/hr

Off-state voltage, max

10V

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 30V DC

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IC16

On-state current, max

7 mA @ 60V DC

Inrush current, max

250 mA

Input impedance, max

8.57 k @ 60V DC

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IC16
Certification(1)

1756-IC16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

27

1756 ControlLogix I/O Modules

1756-IF6CIS
ControlLogix sourcing current loop analog input module
1756-IF6CIS 2-wire Transmitter Connected to the Module and the
Module Providing 24V DC Loop Power
2

IN-0/I
6

2-wire
Transmitter

IN-1/I

i
RTN-0

RTN-1
8

VOUT-2
10

IN-2/I
12

11

14

13

Shield Ground

RTN-2

RTN-3

Not Used

Not Used
16

15

VOUT-4

VOUT-5
18

17

IN-4/I

IN-5/I
20

VOUT-0
4

IN-1/I

IN-0/I

10

12

11

14

13

16

15

18

17

19

20

19

RTN-4

Do not connect more than two wires to any single terminal.


Place additional loop devices (e.g. strip chart recorders) at
either A location in the current loop.

VOUT-2

IN-3/I

IN-2/I

RTN-3

Shield Ground

RTN-2

Not Used

Not Used

VOUT-5

VOUT-4

IN-5/I
RTN-5

2-wire
Transmitter

24V DC

RTN-0
8

VOUT-3

IN-3/I

VOUT-1

RTN-1

VOUT-3

RTN-5

+
VOUT-0

VOUT-1

1756-IF6CIS 2-wire Transmitter Connected to the Module and an


External, User-provided Power Supply Providing 24V DC Loop Power

IN-4/I
RTN-4

If separate power sources are used, do not exceed the


specified isolation voltage.
Do not connect more than two wires to any single terminal.
Place additional loop devices (such as strip chart recorders) at
either A location in the current loop.

28

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF6CIS 4-wire Transmitter Connected to the Module and an


External, User-provided Power Supply Providing 24V DC Loop Power
2

VOUT-1

VOUT-0
4

IN-0/I

IN-1/I
6

RTN-1

RTN-0
8

10

12

11

14

13

16

15

18

17

20

19

+
4-wire
Transmitter

24V DC

VOUT-2

VOUT-3

IN-2/I

IN-3/I
RTN-3

Shield Ground

RTN-2

Not Used

Not Used
VOUT-4

VOUT-5
IN-5/I

IN-4/I
RTN-4

RTN-5

If separate power sources are used, do not exceed the specified


isolation voltage.
Do not connect more than two wires to any single terminal.
Place additional loop devices (such as strip chart recorders) at
either A location in the current loop.

Input Signal to User Count Conversion - 1756-IF6CIS


Range

Low Signal and User Counts

High Signal and User Counts

020 mA

0 mA

21.09376 mA

-32768 counts

32767 counts

Technical Specifications - 1756-IF6CIS


ANALOG INPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IF6CIS

Inputs

6 individually isolated current sourcing

Input range

021 mA

Resolution

16 bits
0.34 A/bit

Current draw @ 5.1V

250 mA

Current draw @ 24V

275 mA

Power dissipation, max

5.1 W @ 60 C

Thermal dissipation

17.4 BTU/hr

29

1756 ControlLogix I/O Modules

Attribute

1756-IF6CIS

Input impedance

215 , approx

Open circuit detection time

Zero reading within 5 s

Overvoltage protection, max

30V AC/DC with PTC and sense resistor

Normal mode noise rejection

60 dB @ 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

3262 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy 25 C

Better than 0.1% of range

Calibration interval

12 months

Offset drift

200 A/C

Gain drift with temperature

17 ppm/C, 35 ppm/C max


0.36 A/C, 0.74 A/C max

Module error

0.2% of range

Module input scan time, min

25 ms min floating point


10 ms min integer

Isolation voltage

250V continuous
Tested at 1900V DC for 60 s, channel to channel
Tested at 3250V DC for 60 s, channels to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

30

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IF6CIS
Certification(1)

1756-IF6CIS

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

31

1756 ControlLogix I/O Modules

1756-IF6I
ControlLogix isolated voltage/current analog input module
1756-IF6I Current 2-wire
2

IN-1/V

IN-1/I

IN-0/I
6

10

RET-1

IN-0/V
4

i
A

2-wire
Transmitter

IN-2/I
12

11

RET-3

RET-2
14

13

Not Used

Not Used
16

15

IN-5/V
18

10

12

11

RET-0

19

IN-3/I

4-wire
Transmitter

IN-2/I

RET-3

RET-2
14

13

16

15

18

17

20

19

Not Used

RET-5

IN-2/V

Shield Ground

Not Used
IN-4/V

IN-5/I

IN-4/I
RET-4

RET-4

Place additional loop devices (such as strip chart recorders) at


either A location.

32

IN-5/V

17

+
IN-0/I

IN-3/V

IN-4/I
20

IN-1/I

IN-4/V

IN-5/I

IN-0/V
4

A
IN-2/V

IN-3/I

IN-1/V

RET-1

RET-0

IN-3/V

RET-5

1756-IF6I Current 4-wire

Place additional loop devices (such as strip chart recorders) at


either A location.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF6I Voltage
Voltage Input
2

User Analog
Input Device

IN-0/I

IN-1/I
6

RET-0

RET-1

Device
External
Power

IN-2/V

IN-3/V
10

12

11

14

13

16

15

18

17

20

19

IN-2/I

IN-3/I

RET-2

RET-3

Not Used

Not Used

IN-4/V

IN-5/V

Shield Ground

IN-4/I

IN-5/I
RET-5

IN-0/V

IN-1/V

RET-4

Do not connect more than 2 wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF6I


Range

Low Signal and User Counts

High Signal and User Counts

10V

-10.54688V

10.54688V

-32768 counts

32767 counts

0V

10.54688V

-32768 counts

32767 counts

0V

5.27344V

-32768 counts

32767 counts

0 mA

21.09376V

-32768 counts

32767 counts

010V
05V
020 mA

Publication 1756-TD002A-EN-E - May 2009

33

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IF6I


ANALOG INPUT
CAL
OK

34

Attribute

1756-IF6I

Inputs

6 individually isolated

Input range

10.5V
010.5V
05.25V
021 mA

Resolution

16 bits
10.5V: 343 V/bit
010.5V: 171 V/bit
05.25V: 86 V/bit
021 mA: 0.34 A/bit

Current draw @ 5.1V

250 mA

Current draw @ 24V

100 mA

Power dissipation, max

Voltage: 3.7 W
Current: 4.3 W

Thermal dissipation

Voltage: 12.62 BTU/hr


Current: 14.32 BTU/hr

Input impedance

Voltage: > 10 M
Current: 249

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

Voltage: 120V AC/DC


Current: 8V AC/DC (with on-board current resistor)

Normal mode noise rejection

60 dB @ 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy 25 C

Better than 0.1% of range

Calibration interval

6 months

Offset drift

2 V/C

Gain drift with temperature

Voltage: 35 ppm/C, 80 ppm/C max


Current: 45 ppm/C, 90 ppm/C max

Module error

0.54% of range

Module input scan time, min

25 ms min floating point


10 ms min integer(1)

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, channels
to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

2(3)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IF6I

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF6I
Certification(1)

1756-IF6I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

35

1756 ControlLogix I/O Modules

1756-IF8
ControlLogix voltage/current analog input module
1756-IF8 Differential Voltage

1756-IF8 Differential Current


Channel 0
Channel 0

IN-0

i RTN-0

IN-1

i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN

10

RTN

IN-4

12 11

i RTN-4

IN-5

14 13

i RTN-5

IN-6

16 15

i RTN-6

IN-7

18 17

i RTN-7

Not Used
Not Used

20 19
22 21

Not Used
Not Used

Not Used

Not Used

24 23

Not Used

Not Used

Not Used

26 25

Not Used

26 25

Not Used

Not Used

28 27

Not Used

Not Used

28 27

Not Used

Not Used

30 29

Not Used

Not Used

30 29

Not Used

Not Used

32 31

Not Used

Not Used

32 31

Not Used

Not Used

34 33

Not Used

Not Used

34 33

Not Used

Not Used

36 35

Not Used

Not Used

36 35

Not Used

IN-0

i RTN-0

IN-1

i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN

10

RTN

IN-4

12 11

i RTN-4

IN-5

14 13

i RTN-5

IN-6

16 15

i RTN-6

IN-7

18 17

i RTN-7

Not Used

20 19

Not Used

Not Used

22 21

Not Used

24 23

Not Used

Shield
Ground
Channel 3
2-wire
Transmitter

i
A

Use this table when wiring your module in differential mode.

Jumper
Wires

Shield Ground

Channel 3

Shield Ground

Use this table when wiring your module in differential mode.

This channel

Uses these terminals

This channel

Uses these terminals

Channel 0

IN-0 (+), IN-1 (-), i RTN-0

Channel 0

IN-0 (+), IN-1 (-)

Channel 1

IN-2 (+), IN-3 (-), i RTN-2

Channel 1

IN-2 (+), IN-3 (-)

Channel 2

IN-4 (+), IN-5 (-), i RTN-4

Channel 2

IN-4 (+), IN-5 (-)

Channel 3

IN-6 (+), IN-7 (-), i RTN-6

Channel 3

IN-6 (+), IN-7 (-)

All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

A 249-current loop resistor is located between IN-x and i RTN-x


terminals.

If multiple (+) or multiple (-) terminals are tied together, connect


that tie point to a RTN terminal to maintain the modules
accuracy.

If multiple (+) or multiple (-) terminals are tied together, connect


that tie point to a RTN terminal to maintain the modules
accuracy.
Place additional loop devices (such as strip chart recorders) at
the A location in the current loop.
Do not connect more than two wires to any single terminal.

Terminals marked RTN or iRTN are not used for differential


voltage wiring.
Do not connect more than two wires to any single terminal.
IMPORTANT: When operating in 2 channel, High Speed mode, only use
channels 0 and 2.

IMPORTANT: When operating in 2 channel, High Speed mode, only use


channels 0 and 2.

36

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF8 Single-ended Voltage

1756-IF8 Single-ended Current


Channel 0

Shield Ground
Channel 5

i
2-wire
Transmitter

IN-0

i RTN-0

IN-1

i RTN-1

i RTN-0

IN-1

i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN

10

RTN

IN-4

12

11

i RTN-4

IN-5

14

13

i RTN-5

IN-6

16

15

i RTN-6

IN-7

18

17

i RTN-7

Not Used

20

19

Not Used

Not Used

22

21

Not Used

Not Used

24

23

Not Used

Not Used

Not Used

26

25

Not Used

Not Used

Not Used

28

27

Not Used

Not Used

Not Used

30

29

Not Used

Not Used

32

31

Not Used

Not Used

34

33

Not Used

Not Used

36

35

Not Used

IN-3

RTN

10

IN-4

12 11

i RTN-4

IN-5

14 13

i RTN-5

IN-6

16 15

i RTN-6

i RTN-2

RTN

18 17
20 19

Not Used

22 21

Not Used

Not Used

24 23

Not Used

Not Used
Not Used
Not Used
Not Used

Shield Ground
Channel 1

Not Used

26 25
28 27
30 29
32 31

Shield Ground

Not Used

34 33

Not Used

36 35

i RTN-7

Not Used

Not Used

Jumper
Wires

i RTN-3

Not Used

Not Used

+
IN-0

IN-2

IN-7

Channel 0

All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

For current applications, all terminals marked iRTN must be


wired to terminals marked RTN.

Terminals marked iRTN are not used for single-ended voltage


wiring.

A -49 current loop resistor is located between IN-x and i RTN-x


terminals.

Do not connect more than two wires to any single terminal.

Place additional loop devices (such as strip chart recorders) at


the A location in the current loop.
Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF8


Range

Low Signal and User Counts

High Signal and User Counts

10V

-10.25V

10.25V

-32768 counts

32767 counts

0V

10.25V

-32768 counts

32767 counts

0V

5.125V

-32768 counts

32767 counts

0 mA

20.58V

-32768 counts

32767 counts

010V
05V
020 mA

Publication 1756-TD002A-EN-E - May 2009

37

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IF8


ANALOG INPUT
CAL

Attribute

1756-IF8

Inputs

8 single-ended
4 differential
2 high-speed differential

Input range

10.25V
0...10.25V
0...5.125V
020.5 mA

Resolution

10.25V: 320 V/cnt (15 bits plus sign bipolar)


010.25V: 160 V/cnt (16 bits)
05.125V: 80 /V cnt (16 bits)
020.5mA: 0.32 A/cnt (16 bits)

Current draw @ 5.1V

150 mA

Current draw @ 24V

40 mA

Power dissipation, max

Voltage: 1.73 W
Current: 2.33 W

Thermal dissipation

Voltage: 5.88 BTU/hr


Current: 7.92 BTU/hr

Input impedance

Voltage: >1 M
Current: 249

Open circuit detection time

Differential voltage: Positive full scale reading within 5 s


Single-ended/diff. current: Negative full scale reading
within 5 s
Single-ended voltage: Even numbered channels go to
positive full scale reading within 5 s, odd numbered
channels go to negative full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC
Current: 8V DC

Normal mode noise rejection

>80 dB @ 50/60 Hz(1)

Common mode noise rejection

>100 dB @ 50/60 Hz

Calibrated accuracy 25 C

Voltage: Better than 0.05% of range


Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

45 V/C

Gain drift with temperature

Voltage: 15 ppm/C
Current: 20 ppm/C

Module error

Voltage: 0.1% of range


Current: 0.3% of range

Module input scan time, min

8 pt single-ended (floating point): 16488 ms


4 pt differential (floating point): 8244 ms
2 pt differential (floating point): 5122 m(1)

Isolation voltage

Tested at 2500V DC for 1 s, field-side to system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

OK

38

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IF8

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF8
Certification(1)

1756-IF8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

39

1756 ControlLogix I/O Modules

1756-IF8H
ControlLogix voltage/current analog input module with HART protocol
1756-IF8H Current

1756-IF8H Voltage

Voltage Input
+V

2-wire Current Input

-V

2 Wire
XMTR

24V DC
Power
Supply

+
-

+-

4-wire Current Input

+ +4 Wire +
XMTR
- - -

24V DC
Power
Supply

IN0+

I RTN-0

IN0-

NC

IN1+

I RTN-1

NC

IN0+

I RTN-0

IN1-

IN0-

NC

RTN

10 9

RTN

IN1+

I RTN-1

IN1-

IN2+

12 11

NC

I RTN-2

RTN

10 9

RTN

IN2-

14 13

NC

IN2+

12 11

I RTN-2

IN3+

16 15

I RTN-3

IN2-

14 13

NC

IN3-

18 17

NC

IN3+

16 15

I RTN-3

IN4+

20 19

I RTN-4

IN3-

18 17

NC

IN4-

22 21

NC

IN4+

20 19

I RTN-4

IN5+

24 23

I RTN-5

IN5-

26 25

NC

28 27

RTN

IN4-

22 21

NC

IN5+

24 23

I RTN-5

RTN

IN5-

26 25

NC

IN6+

30 29

I RTN-6

RTN

28 27

RTN

IN6-

32 31

NC

IN6+

30 29

I RTN-6

IN7+

34 33

I RTN-7

IN7-

36 35

NC

IN6-

32 31

NC

IN7+

34 33

I RTN-7

IN7-

36 35

NC

Input Signal to User Count Conversion - 1756-IF8H


Range

Low Signal and User Counts

High Signal and User Counts

10V

-10.25V

10.25V

-32768 counts

32767 counts

0V

10.25V

-32768 counts

32767 counts

0V

5.125V

-32768 counts

32767 counts

0 mA

20.58V

-32768 counts

32767 counts

010V
05V
020 mA

Technical Specifications - 1756-IF8H


ANALOG OUTPUT
CAL
OK

Attribute

1756-IF8H

Inputs

8 differential voltage or current

Input range

10V
0...5V
15V
0...10V
020 mA
420 mA

Resolution

1621 bits

Current draw @ 5V

300 mA

Current draw @ 24V

70 mA

Power dissipation, max

Voltage: 3.21 W
Current: 4.01 W

Thermal dissipation

Voltage: 11.0 BTU/hr


Current: 13.7 BTU/hr

HART

40

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IF8H

Input impedance

> 1 M voltage
250 current

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

Voltage: 30V DC
Current: 8V DC

Normal mode noise rejection

> 80 dB @ 50/60 Hz

Common mode noise rejection

> 100 dB @ 50/60 Hz

Calibrated accuracy

Voltage: Better than 0.05% of range


Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

90 V/C

Gain drift with temperature

Voltage: 10 ppm/C
Current: 20 ppm/C

Module error

Voltage: 0.1% of range


Current: 0.3% of range

Module input scan time, min

18...488 ms (filter dependent)

Module HART scan time

Typically 1 s per HART channel enabled. Estimate 10 s if


all 8 channels have HART enabled
Pass through messages, handheld communicators,
secondary masters, communication errors, or
configuration changes can significantly increase the
update time

Isolation voltage

50 V (continuous), Basic Insulation Type


Tested at 1500V AC for 60 s, I/O to backplane

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2 - on signal ports(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

41

1756 ControlLogix I/O Modules

Certifications - 1756-IF8H
Certification(1)

1756-IF8H

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

42

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF16
ControlLogix voltage/current analog input module
1756-IF16 Differential Voltage

1756-IF16 Differential Current


Channel 0

Channel 0

i
A

Shield
Ground
Channel 3
2-wire
Transmitter

i
A

IN-0
IN-1

2
4

i RTN-0
i RTN-1

IN-2

i RTN-2

IN-3

RTN
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9

10

IN-10
IN-11
RTN
IN-12
IN-13

24 23

IN-14

34 33

IN-15

36 35

7
9

12 11
14 13
16 15
18 17
20 19
22 21

26 25
28 27
30 29
32 31

i RTN-3

Jumper
Wires Shield Ground

RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-7
i RTN-8
i RTN-9

Channel 3

Shield Ground

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13
i RTN-14
i RTN-15

Use this table when wiring your module in differential mode.

IN-0
IN-1

i RTN-0
i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9

10

RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-7
i RTN-8
i RTN-9

IN-10
IN-11
RTN
IN-12
IN-13

24 23

32 31

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13

IN-14

34 33

i RTN-14

IN-15

36 35

i RTN-15

12 11
14 13
16 15
18 17
20 19
22 21

26 25
28 27
30 29

Use this table when wiring your module in differential mode.

This channel

Uses these terminals

This channel

Uses these terminals

Channel 0

IN-0 (+), IN-1 (-), i RTN-0

Channel 0

IN-0 (+), IN-1 (-)

Channel 1

IN-2 (+), IN-3 (-), i RTN-2

Channel 1

IN-2 (+), IN-3 (-)

Channel 2

IN-4 (+), IN-5 (-), i RTN-4

Channel 2

IN-4 (+), IN-5 (-)

Channel 3

IN-6 (+), IN-7 (-), i RTN-6

Channel 3

IN-6 (+), IN-7 (-)

Channel 4

IN-8 (+), IN-9 (-), i RTN-8

Channel 4

IN-8 (+), IN-9 (-)

Channel 5

IN-10 (+), IN-11 (-), i RTN-10

Channel 5

IN-10 (+), IN-11 (-)

Channel 6

IN-12 (+), IN-13 (-), i RTN-12

Channel 6

IN-12 (+), IN-13 (-)

Channel 7

IN-14 (+), IN-15 (-), i RTN-14

Channel 7

IN-14 (+), IN-15 (-)

All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

A 249-current loop resistor is located between IN-x and i RTN-x


terminals.

If multiple (+) or multiple (-) terminals are tied together, conne


that tie point to a RTN terminal to maintain the modules
accuracy.

If multiple (+) or multiple (-) terminals are tied together, connect


that tie point to a RTN terminal to maintain the modules
accuracy.
Place additional loop devices (such as strip chart recorders) at
the A location in the current loop.
Do not connect more than two wires to any single terminal.

Terminals marked RTN or iRTN are not used for differential


voltage wiring.
Do not connect more than two wires to any single terminal.
IMPORTANT: When operating in 4 channel, High Speed mode, only us
channels 0, 2, 4 and 6.

IMPORTANT: When operating in 4 channel, High Speed mode, only use


channels 0, 2, 4 and 6.

Publication 1756-TD002A-EN-E - May 2009

43

1756 ControlLogix I/O Modules

1756-IF16 Single-ended Current

1756-IF16 Single-ended Voltage

Shield
Ground
2-wire
Transmitter

i
A

IN-0
IN-1

i RTN-0
i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9

10

RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-7
i RTN-8
i RTN-9

IN-10
IN-11
RTN
IN-12
IN-13

24 23

12 11
14 13
16 15
18 17
20 19
22 21

Jumper
Wires
Shield
Ground

i RTN-0
i RTN-1

IN-2

i RTN-2

IN-3

i RTN-3

RTN
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9

10

RTN
i RTN-4
i RTN-5
i RTN-6
i RTN-7
i RTN-8
i RTN-9

IN-10
IN-11
RTN
IN-12
IN-13

24 23

32 31

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13

IN-0
IN-1

12 11
14 13
16 15
18 17
20 19
22 21

32 31

i RTN-10
i RTN-11
RTN
i RTN-12
i RTN-13

IN-14

34 33

i RTN-14

IN-14

34 33

i RTN-14

IN-15

36 35

i RTN-15

IN-15

36 35

i RTN-15

26 25
28 27
30 29

Shield
Ground

26 25
28 27
30 29

All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

For current applications, all terminals marked iRTN must be


wired to terminals marked RTN.

Terminals marked iRTN are not used for single-ended voltage


wiring.

A 249-current loop resistor is located between IN-x and i RTN-x


terminals.

Do not connect more than two wires to any single terminal.

Place additional loop devices (such as strip chart recorders) at


the A location in the current loop.
Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF16


Range

Low Signal and User Counts

High Signal and User Counts

10V

-10.25V

10.25V

-32768 counts

32767 counts

0V

10.25V

-32768 counts

32767 counts

0V

5.125V

-32768 counts

32767 counts

0 mA

20.58V

-32768 counts

32767 counts

010V
05V
020 mA

44

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

ANALOG INPUT
CAL

Technical Specifications - 1756-IF16


Attribute

1756-IF16

Inputs

16 single ended, 8 differential or 4 differential (high


speed)

Input range

10.5V
010.5V
05.25V
021 mA

Resolution

16 bits
10.5V: 343 V/bit
010.5V: 171 V/bit
05.25V: 86 V/bit
021 mA: 0.34 A/bit

Current draw @ 5.1V

250 mA

Current draw @ 24V

100 mA

Power dissipation, max

Voltage: 3.7 W
Current: 4.3 W

Thermal dissipation

Voltage: 12.62 BTU/hr


Current: 14.32 BTU/hr

Input impedance

Voltage: >10 M
Current: 249

Open circuit detection time

Positive full scale reading within 5 s

Overvoltage protection, max

Voltage: 120V AC/DC


Current: 8V AC/DC (with on-board current resistor)

Normal mode noise rejection

60 dB @ 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy 25 C

Better than 0.1% of range

Calibration interval

6 months

Offset drift

2 V/C

Gain drift with temperature

Voltage: 35 ppm/C, 80 ppm/C max


Current: 45 ppm/C, 90 ppm/C max

Module error

0.54% of range

Module input scan time, min

25 ms min floating point


10 ms min integer(1)

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, channels
to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

OK
HART

Publication 1756-TD002A-EN-E - May 2009

45

1756 ControlLogix I/O Modules

Attribute

1756-IF16

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF16
Certification(1)

1756-IF16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

46

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
1756-IF4FXOF2F Current
(-) i

(+)

2-wire
A
Transmitter
A

1756-IF4FXOF2F Voltage
(+)

(+)
User
Analog
Input
Device

+IN-1/V
IN-1/I
-IN-1

2
4

1
3

+IN-3/V

8 7
10 9
12 11

+IN-2/V
IN-2/I
-IN-2

14 13
16 15
18 17

Not Used
Not Used
V OUT-0 i

IN-3/I
-IN-3
Not Used
Not Used
V OUT-1
I OUT-1
RTN-1
Not Used
Not Used
Not Used
Not Used

20 19
22
24
26
28

21
23
25
27

Not Used

30 29
32 31
34 33

Not Used

36 35

Not Used

+IN-0/V
IN-0/I
-IN-0

(-)
Shield
Ground

Curren
Output
Load

I OUT-0
RTN-0
Not Used
Not Used

Shield
Ground

Not Used
Not Used
Not Used
Not Used
Not Used

+IN-1/V
IN-1/I

+IN-0/V
IN-0/I

-IN-1

-IN-0

+IN-3/V
IN-3/I
-IN-3

+IN-2/V

10 9

IN-2/I

12 11

-IN-2

Not Used

14 13

Not Used

Not Used
V OUT-1

16 15

Not Used

18 17

V OUT-0

I OUT-1

20 19

I OUT-0

RTN-1

22 21

Not Used

24 23

RTN-0
Not Used (-)

Not Used

26 25

Not Used

Not Used

28 27

Not Used

Not Used

30 29

Not Used

Not Used
Not Used

32 31

Not Used

34 33

Not Used

Not Used

36 35

Not Used

(+)

Shield
Ground

A = Inline field device (such as a strip chart recorder or meter)

Technical Specifications - 1756-IF4FXOF2F


ANALOG INPUT
ANALOG OUTPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IF4FXOF2

Inputs

4 high-speed, sub-millisecond, differential

Outputs

2 high-speed voltage or current

Current draw at 5.1V

375 mA

Current draw at 24V

100 mA

Power dissipation, max

Voltage: 4.3 W
Current: 4.7 W

Thermal dissipation, max

Voltage: 14.66 BTU/hr


Current: 16.02 BTU/hr

Isolation voltage

250V (continuous), Basic Insulation Type


125V (continuous), Reinforced Insulation Type
Type Tested at 3100V DC for 60 s, I/O to system
Routine Tested at 2121V DC for 2 s, I/O to system
No isolation between channels

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

47

1756 ControlLogix I/O Modules

Attribute

1756-IF4FXOF2

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2(2)

Wire type

Copper

North American temperature code

T4A

IEC temperature code

T4

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-IF4FXOF2F Input and Output Specifications


Attribute

Inputs

Outputs

Number

4 high-speed, sub-millisecond, differential

2 high-speed voltage or current

Output range

10.5V
010.5V
05.25V
021 mA

10.4V
021 mA

Resolution

Approx. 14 bits across 10V DC (21V total)


10V: 1.3 mV/bit, 14-bit effective
010.5V: 1.3 mV/bit, 13-bit effective
05.25V: 1.3 mV/bit, 12-bit effective
Approx. 12 bits across 21 mA
021 mA: 5.25 A/bit

13 bits across 21 mA = 2.8 A/bit


14 bits across 21.8V = 1.3 mV/bit

Impedance

Voltage: >1 M
Current: 249

Open circuit detection

Positive full-scale reading within 1 s

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

Voltage: 30V DC
Current: 8V AC/DC

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

Voltage: >2000
Current: 0750

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy @ 25 C

0.05% of range immediately after calibration


Better than 0.1% of range within calibration interval

Calibration interval

12 months

Offset drift

50 V/ C
1 A/ C

Gain drift with temperature

Voltage: 25 ppm/C max


Current: 35 ppm/C max

Voltage: 25 ppm/C max


Current: 50 ppm/C max

Module error

0.2% of range

Voltage: 0.2% of range


Current: 0.3% of range

Module scan time

300 s min(1)

(1)

48

300 s min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F, Series A, firmware revision 1.x.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IF4FXOF2F
Certification(1)

1756-IF4FXOF2

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

49

1756 ControlLogix I/O Modules

1756-IG16
ControlLogix TTL input module
Standard Wiring

CE Compliant Wiring
1756-IG16

1756-IG16
DC

2
2

IN-1

IN-0
4

IN-3

5V DC

IN-2
6

10

IN-4

IN-7

DC Power Wire

DC-0(+)

IN-2

12

11

14

13

16

15

18

17

5V DC Power

IN-12

IN-13

12

11

14

13

16

15

DC COM 0

IN-8
IN-10
IN-12

IN-13
18

17

20

19

DC-1(+)

19

TTL Input
Device

Capacitor
0.01 F Typical
(See notes below.)

IN-14

IN-15

IN-14

IN-15

10

DC-0(+)

IN-11

IN-10

I/O Wire

IN-6

IN-9
IN-8

IN-11

IN-4

IN-7

DC COM 0

IN-9

DC-1(+)

IN-6

20

IN-5

IN-5

+ DC

IN-0

IN-3

I/O Wire

IN-1

DC COM 1

DC COM 1

Simplified Schematic
+5 DC
1.5 K
IN

1K

74HCT14

1K

74HCT14

560

1.5 K
IN

560

DC COM

Low to True Format - 1756-IG16


-0.20.8V = Input guaranteed to be in on-state
0.82.0V = Input state not guaranteed
2.05.5V = Input guaranteed to be in off-state

50

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IG16


DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Attribute

1756-IG16

Inputs

16 (8 points/group)

Voltage category

5V DC TTL source (Low=True)(1)

Operating voltage range

4.5...5.5V DC
50 mV P-P ripple max

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

450 s + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

700 s + filter

Current draw @ 5.1V

110 mA

Current draw @ 24V

2 mA

Power dissipation, max

1.4 W @ 60 C

Thermal dissipation

4.8 BTU/hr @ 60 C

Off-state voltage, max

2V

Off-state current, max

4.1 mA

On-state current, min

3.7 mA @ 5V DC

On-state current, max

4.1 mA @ 5V DC

Input impedance, max

1.4 k min
1.5 k typical

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to
convert to traditional True - High logic.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

51

1756 ControlLogix I/O Modules

Certifications - 1756-IG16
Certification(1)

1756-IG16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

52

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IH16I
ControlLogix DC (90...146V) isolated input module
1756-IH16I

Simplified Schematic
+5V
IN-0

DC-0 (-)
Isolated
Wiring

GND-0

IN-0

GND-1
GND-2

IN-1
IN-2

DC-3 (-)

GND-3

IN-3

GND-4
GND-5
GND-6

10 9

IN-4
IN-5
IN-6

GND-7
GND-8

16 15

GND-9
GND-10
GND-11

20 19

GND-12
GND-13

26 25
28 27

GND-14
GND-15

30 29
32 31

IN-12
IN-13
IN-14
IN-15

GND-15

34 33

Not Used

Not Used

36 35

Not Ysed

GND-0
GND

DC-7 (-)

ControlLogix Display
Backplane
Interface

Jumper Bar
(Cut to Length)

Nonisolated
Wiring

DC (-)

12 11
14 13
18 17
22 21
24 23

IN-7
IN-8

DC-0 (+)

DC-3 (+)

D C-7 (+ )

IN-9
IN-10
IN-11

DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IH16I


DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IH16I

Inputs

16 individually isolated

Voltage category

125V DC sink/source

Operating voltage range

90...146V DC(1)

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

2 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

6 ms + filter

Current draw @ 5.1V

125 mA

Current draw @ 24V

3 mA

Power dissipation, max

5 W @ 60 C

Thermal dissipation

17.05 BTU/hr

Off-state voltage, max

20V DC

Off-state current, max

0.8 mA

On-state current, min

1 mA @ 90V DC

On-state current, max

3 mA @ 146V DC

Inrush current, max

250 mA

Input impedance, max

48.67 k @ 146V DC

Cyclic update time

200 s...750 ms

53

1756 ControlLogix I/O Modules

Attribute

1756-IH16I

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

90...146V DC @ 50C,12 channels on


90...132V DC @ 55C, 14 channels on
90...125V DC @ 60C, 16 channels on
90...146V DC @ 30C, 16 channels on.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IH16I
Certification(1)

1756-IH16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

54

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IH16ISOE
ControlLogix DC (90...140V) sequence of events input module
1756-IH16ISOE

Simplified Schematic

Isolated Wiring

+5V
IN-0

GND-0

ControlLogix
Backplane
Interface

GND-0
GND-1
GND-2
GND-3
Source Input Wiring GND-4
DC-5 (-)
GND-5
GND-6
DC-6 (-)
GND-7
GND-8
Display Jumper Bar
GND-9
(Cut to Length)
GND-10
GND-11
Nonisolated
GND-12
Wiring
GND-13
GND-14
GND-15
GND-15
DC (-)
Not Used
DC-0 (-)

10 9
12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

Sink Input Wiring


IN-0
DC-0 (+)
IN-1
DC-1 (+)
IN-2
IN-3
Source Input Wiring
IN-4
DC-5 (+)
IN-5
IN-6
DC - 6 ( + )
IN-7
IN-8
Sink Input Wiring
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Not Used
Not Used
DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IH16ISOE


SOE INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IH16ISOE(1)

Inputs

16 individually isolated, sequence of events

Voltage category

125V DC sink/source

Operating voltage range

90...140V DC

Digital filter, off to on

050 ms

Input delay, off to on

20 s

Digital filter, on to off

0...50 ms

Input delay, on to off

75 s

Current draw @ 5.1V

275 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.5 W @ 60 C

Thermal dissipation

17.22 BTU/hr

Off-state voltage, max

20V

Off-state current, max

0.3 mA

On-state current, min

1.15 mA @ 90V DC

On-state current, max

1.85 mA @ 140V DC

Input impedance, max

74.8 k

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous, channel to channel, channels to


system

Removable terminal block

1756-TBCH
1756-TBS6H

55

1756 ControlLogix I/O Modules

Attribute

1756-IH16ISOE(1)

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)
If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink
module to coordinate system time.
(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IH16ISOE
Certification(1)

1756-IH16ISOE

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

56

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IM16I
ControlLogix AC (159...265V) input module
1756-IM16I

Simplified Schematic
Isolated Wiring
L2-0

+5V

IN-O

L2-2

L2-0
L2-4

GND
ControlLogix Display
Backplane
Interface

Jumper Bar
(Cut to Length)

Nonisolated
Wiring

L2

L2-0

IN-0

L2-1

IN-1

L2-2

IN-2

L2-3

IN-3

L2-4

10

IN-4

L2-5

12 11

IN-5

L2-6

14 13

IN-6

L2-7

16 15

IN-7

L2-8

18 17

IN-8

L2-9

20 19

IN-9

L2-10

22 21

IN-10

L2-11

24 23

IN-11

L2-12

26 25

IN-12

L2-13
L2-14

28 27
30 29

IN-13
IN-14

L2-15

32 31

IN-15

L2-15
Not Used

34 33

Not Used
Not Used

36 35

L1-0
L1-2
L1-4

L1
Daisy Chain to Other RTBs

Technical Specifications - 1756-IM16I


AC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IM16I

Inputs

16 individually isolated

Voltage category

240V AC

Operating voltage range

159265V AC,
4763 Hz(1)

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

3 mA

Power dissipation, max

5.8 W @ 60 C

Thermal dissipation

19.78 BTU/hr

Off-state voltage, max

40V

Off-state current, max

2.5 mA

On-state current, min

5 mA @ 159V AC, 60 Hz

On-state current, max

13 mA @ 265V AC, 60 Hz

Inrush current, max

250 mA

Input impedance, max

20.38 k @ 265V AC, 60 Hz

57

1756 ControlLogix I/O Modules

Attribute

1756-IM16I

Cyclic update time

200 s...750 ms

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

159265V AC, 4763Hz @ 30C all channels on


159265V AC, 4763Hz @ 40C 8 points on
159253V AC, 4763Hz @ 45C all channels on
159242V AC, 4763Hz @ 60C all channels on.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IM16I
Certification(1)

1756-IM16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

58

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IN16
ControlLogix AC (10...30V) input module
1756-IN16

Simplified Schematic
+5V

IN-O

IN-1

L2-0

L1

IN-0

IN-3

GND

IN-2

IN-5
L2

Group 0

IN-4

IN-7

ControlLogix Display
Backplane
Interface

10

12

11

14

13

16

15

L2-0

L2-0

IN-9

IN-8

IN-11
Group 1

Group 0
IN-6

IN-10

IN-13

IN-12
18

17

20

19

IN-15

Group 1

IN-14

L2-1

L2-1

Daisy Chain to
Other RTBs

Technical Specifications - 1756-IN16


AC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IN16

Inputs

16 (8 points/group)

Voltage category

24V AC

Operating voltage range

1030V AC,
4763 Hz

Digital filter, off to on

1 or 2 ms

Input delay, off to on

10 ms + filter

Digital filter, on to off

9 or 18 ms

Input delay, on to off

8 ms + filter

Current draw @ 5.1V

100 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.1 W @ 60 C

Thermal dissipation

17.39 BTU/hr

Off-state voltage, max

5V

Off-state current, max

2.75 mA

On-state current, min

5 mA @ 10V AC, 60 Hz

On-state current, max

1.2 mA @ 30V AC, 60 Hz

Inrush current, max

250 mA

59

1756 ControlLogix I/O Modules

Attribute

1756-IN16

Input impedance, max

2.5 k @ 30V AC, 60 Hz

Cyclic update time

200 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IN16
Certification(1)

1756-IN16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

60

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IR6I
ControlLogix temperature sensing analog input module
1756-IR6I 3-wire RTD
2

IN-1/A

IN-0/A
4

IN-1/B

IN-0/B

RTN-1/C

RTN-0/C

IN-3/A
10

12

11

14

13

16

15

18

17

20

19

IN-3/B

IN-2/B

RTN-3/C

RTN-2/C

Not used

Shield Ground

Not used
IN-4/A

IN-5/A
IN-5/B
RTN-5/C

3-wire RTD
IN-2/A

IN-4/B
RTN-4/C

Do not connect more than two wires to any single terminal.


IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and
RTN-x/C are shorted together as shown.

Publication 1756-TD002A-EN-E - May 2009

61

1756 ControlLogix I/O Modules

1756-IR6I 4-wire RTD

IN-1/A

IN-0/A
4

IN-1/B

IN-0/B

RTN-1/C

RTN-0/C

IN-3/A

4-wire RTD
IN-2/A

10

IN-3/B

IN-2/B
12

11

14

13

16

15

18

17

20

19

RTN-2/C

RTN-3/C
Not used

Shield Ground

Not used

IN-5/A

IN-4/A
IN-4/B

IN-5/B
RTN-5/C

RTN-4/C

Do not connect more than two wires to any single terminal.


Wiring is exactly the same as the 3-wire RTD with one wire left open.

Input Signal to User Count Conversion - 1756-IR6I


Range

Low Signal and User Counts

High Signal and User Counts

1...487

0.859068653

507.862

-32768 counts

32767 counts

1016.502

-32768 counts

32767 counts

2033.780

-32768 counts

32767 counts

4068.392

-32768 counts

32767 counts

2...1000
4...2000
8...4020

62

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IR6I


ANALOG INPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IR6I

Inputs

6 individually isolated RTD

Input range

1487
21000
42000
84020

Resolution

16 bits
1487 : 7.7 m/bit
21000 :15 m/bit
42000 :30 m/bit
84020 :60 m/bit

Sensors supported

100, 200, 500, 1000 Platinum, alpha=385


100, 200, 500, 1000 Platinum, alpha=3916
120 Nickel, alpha=672
100, 120, 200, 500 Nickel, alpha=618
10 Copper

Current draw @ 5.1V

250 mA

Current draw @ 24V

125 mA

Power dissipation, max

4.3 W

Thermal dissipation

14.66 BTU/hr

Open circuit detection time

Negative full scale reading within 5 s with any


combination of lost wires, except input terminal A alone.
If input terminal A is lost by itself, the module reads a
positive full scale reading within 5 s

Overvoltage protection, max

24V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 C

Better than 0.1% of range

Calibration interval

6 months

Offset drift

10 M/C

Gain drift with temperature

50 ppm/C, 90 ppm/C max

Module error

0.54% of range

Module scan time

25 ms min floating point (ohms)


50 ms min floating point (temperature)
10 ms min integer (ohms)(1)

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, channels
to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

63

1756 ControlLogix I/O Modules

Attribute

1756-IR6I

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IR6I
Certification(1)

1756-IR6I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

64

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IT6I
ControlLogix temperature sensing analog input module
1756-IT6I
2

IN-0

IN-0
4

Not Used

Not Used
Cold
Junction
Sensor
Lug

RTN-0

RTN-1

IN-2

IN-3
10

12

11

14

13

16

15

18

17

Thermocouple

Not Used

CJC+

RTN-2

RTN-3

Not Used

CJC-

Wire

IN-4

IN-5

Not Used

Not Used
20

19

RTN-4

RTN-5

Do not connect more than two wires to any single terminal.


One CJC, part number 94238301, is shipped with the module. A
replacement can be ordered as RP-94238301.

Input Signal to User Count Conversion - 1756-IT6I


Range

Low Signal and User Counts

High Signal and User Counts

-12...30 mV

-15.80323 mV

31.396 mV

-32768 counts

32767 counts

-15.15836 mV

79.241 mV

-32768 counts

32767 counts

-12...78 mV

Publication 1756-TD002A-EN-E - May 2009

65

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IT6I


ANALOG INPUT
CAL

Attribute

1756-IT6I

Inputs

6 individually isolated thermocouple


1 CJC

Input range

-1278 mV
-1230 mV

Resolution

16 bits
-12...78 mV: 1.4 V/bit
-12...30 mV: 0.7 V/bit

Thermocouples

B, E, J, K, R, S, T, N, C

Current draw @ 5.1V

250 mA

Current draw @ 24V

125 mA

Power dissipation, max

4.3 W

Thermal dissipation

14.66 BTU/hr

Input impedance

>10 M

Open circuit detection time

Positive full scale reading within 2 s

Overvoltage protection, max

120V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

120 dB @ 60 Hz
100 dB @ 50 Hz

Channel bandwidth

15 Hz (-3 dB)(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 C

Better than 0.1% of range

Calibration interval

6 months

Local CJC sensor accuracy

0.33.2 C, depending on channel

Remote CJC sensor accuracy

0.3 C

Offset drift

0.5 V/C

Gain drift with temperature

65 ppm/C, 80 ppm/C max

Module error

0.5% of range

Module scan time

25 ms min floating point (millivolt)


50 ms min floating point (temperature)
10 ms min integer (millivolt)(1)

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, channels
to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

OK

66

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IT6I

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IT6I
Certification(1)

1756-IF4FXOF2

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

67

1756 ControlLogix I/O Modules

1756-IT6I2
ControlLogix enhanced thermocouple analog input module
1756-IT6I Cold Junction Sensor

Spade Lug

Wire

Not Used

Not Used
CJC

CJC+

RTN-0

IN-0

RTN-1

IN-1

RTN-

IN-2

RTN-3

IN-3

RTN-

IN-4

RTN-5

IN-5

CJC

CJC+

Thermocouple

Not used

Wire

Not used

Cold Junction
Sensor

Spade Lug

Do not connect more than two wires to any single terminal.


Two CJCs, part number 94286501, are shipped with the module.
Replacements can be ordered as RP-94286501.

Input Signal to User Count Conversion - 1756-IT6I2


Range

Low Signal and User Counts

High Signal and User Counts

-12...30 mV

-15.80323 mV

31.396 mV

-32768 counts

32767 counts

-15.15836 mV

79.241 mV

-32768 counts

32767 counts

-12...78 mV

Analog Input
CAL

Technical Specifications - 1756-IT6I2


Attribute

1756-IT6I2

Inputs

6 individually isolated thermocouple


2 CJC

Input range

-1278 mV (1.4 V per bit)


-1230 mV (0.7 V per bit high resolution range)

Resolution

16 bits
-12...78 mV: 1.4 V/bit
-12...30 mV: 0.7 V/bit

OK

68

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-IT6I2

Thermocouples

B, E, J, K, R, S, T, N, C, D, L (TXK/XK)

Current draw @ 5.1V

200 mA

Current draw @ 24V

150 mA

Power dissipation, max

4.6 W

Thermal dissipation

15.7 BTU/hr

Open circuit detection time

Positive full scale reading within 2 s

Overvoltage protection, max

120V AC/DC

Normal mode noise rejection

60 dB at 60 Hz(1)

Common mode noise rejection

160 dB min, tested at 600V AC/60 Hz applied with 100


differential resistance

Channel bandwidth

15 Hz(1)

Settling time

<80 ms to 5% of full scale(1)

Calibrated accuracy @ 25 C

Better than 0.1% of range

Calibration interval

12 months

Local CJC sensor accuracy

0.3 C

Remote CJC sensor accuracy

0.3 C

Offset drift

0.5 V/C

Gain drift with temperature

15 ppm/C, 25 ppm/C max


1.4 V/C, 2.3 V/C max, -1278 mV
0.6 V/C, 1.1 V/C max, -1230 mV

Module error

0.15% of range

Module scan time

25 ms min floating point (millivolt)


50 ms min floating point (temperature)
10 ms min integer (millivolt)(1)

Isolation voltage

250V (continuous), Reinforced Insulation Type, user to


system, tested at 3250V DC for 60 s
250V (continuous), Reinforced Insulation Type, group to
group, tested at 1900V DC for 60 s

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

2(3)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Notch filter dependent.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

69

1756 ControlLogix I/O Modules

Certifications - 1756-IT6I2
Certification(1)

1756-IT6I2

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

TV

TV Certified for Functional Safety: up to and including SIL 2

(1)

70

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IV16
ControlLogix DC (10...30V) sourcing input module
1756-IV16

Simplified Schematic

IN-0

IN-1

+5V
DC-0+

IN-2

IN-3
Group 0

IN-0

Group 0
IN-4

IN-5
8

10

12

11

14

13

16

15

18

17

20

19

IN-6

IN-7

GND
ControlLogix Display
Backplane
Interface

DC-0 +

DC-0 +

IN-8

IN-9

IN-10

IN-11
Group 1

IN-12

IN-13

Group 1

IN-14

IN-15
DC-1 +

DC-1 +

DC COM

Daisy Chain to Other RTBs

Technical Specifications - 1756-IV16


DC INPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 111213 1415 K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IV16

Inputs

16 (8 points/group)

Voltage category

12/24V DC source

Operating voltage range

10...30V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

2 ms + filter

Current draw @ 5.1V

110 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.41 W @ 60 C

Thermal dissipation

18.47 BTU/hr

Off-state voltage, max

5V DC

Off-state current, max

1.5 mA

On-state current, min

2 mA @ 10V DC

On-state current, max

10 mA @ 30V DC

Inrush current, max

250 mA

71

1756 ControlLogix I/O Modules

Attribute

1756-IV16

Input impedance, max

3.2 k @ 30V DC

Cyclic update time

100 s...750 ms

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block housing

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IV16
Certification(1)

1756-IV16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

72

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IV32
ControlLogix DC (10...30V) sourcing input module
1756-IV32

Simplified Schematic
+5V
DC-0+
Group 0

IN-0

GND
ControlLogix Display
Backplane
Interface

Daisy
Chain to
Other
RTBs

Jumper
Wire

Group 1

IN-1

IN-0

IN-3

IN-2

IN-5

IN-4

IN-7

IN-6

IN-9

10

IN-8

IN-11

12 11

IN-10

IN-13

14 13

IN-12

IN-15

16 15

IN-14

DC-0 (+)

18 17

DC-0 (+)

IN-17
IN-19

20 19

IN-16

22 21

IN-18

IN-21

24 23

IN-20

IN-23

26 25

IN-22

IN-25

28 27

IN-24

IN-27

30 29

IN-26

IN-29

32 31

IN-28

IN-31

34 33

IN-30

DC-1 (+)

36 35

DC-1 (+)

Group 0

Group 1

DC COM

Diagnostics - 1756-IV32

DC INPUT
ST 0 1 2
1
ST 8 9 0
11 1
ST 6 7 8
22 2
ST 4 5 6

3
1
1
1
9
2
7

4
1
2
2
0
2
8

5
1
3
2
1
2
9

6
1
4
2
2
3
0

7
1 O
5
K
2
3
3
1

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-IV32

Change of state

Software configurable

Timestamp of diagnostics

200 s

Technical Specifications - 1756-IV32


Attribute

1756-IV32

Inputs

32 (16 points/group)

Voltage category

12/24V DC source

Operating voltage range

10...30V DC

Digital filter, off to on

0, 1, or 2 ms

Input delay, off to on

1 ms + filter

Digital filter, on to off

0, 1, 2, 9, or 18 ms

Input delay, on to off

2 ms + filter

Current draw @ 5.1V

120 mA

Current draw @ 24V

2 mA

73

1756 ControlLogix I/O Modules

Attribute

1756-IV32

Power dissipation, max

4.1 W @ 60 C

Thermal dissipation

14 BTU/hr @ 60 C

Off-state voltage, max

5V

Off-state current, max

1.5 mA

On-state current, min

2 mA

On-state current, max

3.5 mA

Inrush current, max

250 mA (decaying to <37% in 22 ms, without activation)

Input impedance, max

8.6 k @ 30V DC

Cyclic update time

100 s...750 ms

Isolation voltage

250V (continuous), Reinforced Insulation Type between


Input group to system
250V (continuous), Basic insulation type between Input
group to Input group
Routine tested at 1900V AC for 2 s, between Input group
to Input group and Input group to system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module Location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1 - on signal ports(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

74

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IV32
Certification(1)

1756-IV32

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

75

1756 ControlLogix I/O Modules

1756-OA8
ControlLogix AC (74...265V) output module
Simplified Schematic

1756-OA8

+5V

L1-0
2

10

12

11

14

13

16

15

OUT-0

L1-0

OUT-1

L1-0

OUT-0

Group 0

ControlLogix Backplane Interface


Display

OUT-2

L1-0

OUT-3

L1-0

Not used

L1-0

Surge Current Chart

OUT-4

L1-1

Surge

20 A

OUT-5

L1-1

Current

Group 1

Group 1

OUT-6

L1-1
18

17

20

19

OUT-7

L1-1

2A

Group 0

Not Used

L1-1

L2

Time

43 ms
Daisy Chain to
Other RTBs
L1

Technical Specifications - 1756-OA8


AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

76

Attribute

1756-OA8

Outputs

8 (4 points/group)

Voltage category

120/240V AC

Operating voltage range

79265V AC
4763 Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.1 W @ 60 C

Thermal dissipation, max

17.39 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A
6V peak @ <50 mA

Current per point, max

2 A @ 60 C (linear derating)

Current per module, max

5 A @ 30 C (linear derating)
4 A @ 60 C (linear derating)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OA8

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 C

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA


0.2V/s for loads < 50 mA(1)

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Inhibit voltage, max

Zero crossing 60V peak

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA.
The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the
commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is
exceeded in the 1050 mA range, a resistor may be added across the output and L2. The purpose of this resistor is
to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be
at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

77

1756 ControlLogix I/O Modules

Certifications - 1756-OA8
Certification(1)

1756-OA8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

78

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OA8D
ControlLogix AC (74...132V) diagnostic output module
Simplified Schematic

1756-OA8D

Diagnostic Control Block with


Opto and Transformer Isolation

ControlLogix
Backplane
Interface

L1

VAC
Group 0

Verify/
No Load

Current

10

12

11

14

13

16

15

18

17

L2-0

L1-0

OUT-1

L1-0

Loss of Field Power

Surge @ 30 C

OUT-3

L1-1

OUT-4

L1-1

OUT-5

L1-1

OUT-6

Group 1

Surge @ 60 C

5A

L1-1

Continuous @ 30 C
Continuous @ 60 C

1A
500 mA

Group 0

OUT-2

L1-0
Daisy
Chain to
Other
RTBs

Surge Current Chart


8A

OUT-0

OUT
L2

Display

L1-0

GATE

Short

Not Used

Group 1
OUT-7

20

19

L1-1

L2-1
L2

43 ms
Time

Daisy Chain to
Other RTBs
L1

Diagnostics - 1756-OA8D
Attribute

1756-OA8D

Short trip, min

12 A for 500 s

No load

Off-state detection only

Output verification

On-state detection only

Pulse test

Configurable maximum width and max time delay from


zero cross

Field power loss (zero cross)

Detects at 25V peak min (firmware phase locked loop)

Time stamp of diagnostics

1 ms

Technical Specifications - 1756-OA8D


AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K
FLT 0 1 2 3 4 5 6 7

Attribute

1756-OA8D

Outputs

8 diagnostic, electronic fusing (4 points/group)

Voltage category

120V AC

Operating voltage range

74132V AC
4763 Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

DIAGNOSTIC

Publication 1756-TD002A-EN-E - May 2009

79

1756 ControlLogix I/O Modules

Attribute

1756-OA8D

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Current draw @ 5.1V

175 mA

Current draw @ 24V

250 mA

Power dissipation, max

5.3 W @ 60 C

Thermal dissipation, max

18.0 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

2.5V peak @ 0.5 A


3V peak @ 1 A

Current per point, max

1 A @ 30 C (linear derating)
0.5 A @ 60 C (linear derating)

Current per module, max

8 A @ 30 C (linear derating)
4 A @ 60 C (linear derating)

Surge current per point

8 A for 43 ms per point, repeatable every 2 s @ 30 C


5 A for 43 ms per point, repeatable every 1 s @ 60 C

Load current, min

10 mA per point

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Inhibit voltage, max

Zero crossing 25V peak

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

80

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OA8D
Certification(1)

1756-OA8D

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

81

1756 ControlLogix I/O Modules

1756-OA8E
ControlLogix AC (74...132V) electronically-fused output module
Simplified Schematic

1756-OA8E

Opto and Transformer Isolation

ControlLogix
Backplane
Interface

L1

VAC
Short

Group 0

10

12

11

14

13

16

15

18

17

20

19

L2-0

L1-0

OUT-1

OUT-3
OUT-4

L1-1

OUT-5

L1-1

OUT-6

Current

L1-1
Group 1

Group 0

OUT-2

L1-0
Daisy
Chain to
Other
RTBs

Surge

OUT-0

L1-0

Loss of Field Power

Surge Current Chart


20 A

L1-0

GATE

OUT
L2
Display

Not Used

OUT-7

L1-1

Group 1

L2-1

L1-1

2A

L2

Time

Daisy Chain to
Other RTBs

43 ms

L1

Diagnostics - 1756-OA8E
Attribute

1756-OA8E

Short trip, min

>20 A for 100 ms

Field power loss (zero cross)

Detects at 25V peak min (firmware phase locked loop)

Time stamp of diagnostics

1 ms

Technical Specifications - 1756-OA8E


AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
FUSE 0 1 2 3 4 5 6 7K

ELECTRONICALLY FUSED

82

Attribute

1756-OA8E

Outputs

8 electronic fusing (4 points/group)

Voltage category

120V AC

Operating voltage range

74132V AC
4763 Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

250 mA

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OA8E

Power dissipation, max

5.5 W @ 60 C

Thermal dissipation, max

18.76 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

4V peak @ 2 A

Current per point, max

2 A @ 60 C

Current per module, max

8 A @ 30 C (linear derating)
4 A @ 60 C (linear derating)

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 C

Load current, min

10 mA per point

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Inhibit voltage, max

Zero crossing 25V peak

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

83

1756 ControlLogix I/O Modules

Certifications - 1756-OA8E
Certification(1)

1756-OA8E

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

84

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OA16
ControlLogix AC (74...265V) output module
Simplified Schematic

1756-OA16

L1-0

ControlLogix
Backplane +5V
Interface

OUT-1
Group 0
Daisy Chain
to Other
RTBs

(Fused per Group)


Display

OUT-0

OUT-3

OUT-2

OUT-5

OUT-4
8

10

12

11

14

13

16

15

18

17

20

19

OUT-7

OUT-6

L1-0

OUT-0

L2-0

OUT-9

ControlLogix Backplane Interface

OUT-8

OUT-11
Group 1

OUT-10

OUT-13

OUT-12

Surge Current Chart

Current

20 A

Per Group

Group 1

L1
OUT-14

OUT-15

Surge

Group 0

L2-1

L1-1

Per Group

5A
2A
500 mA

L1

L2

43 ms
Time

Diagnostics - 1756-OA16
Attribute

1756-OA16

Time stamp of diagnostics

1 ms

Fuse blown

1 fuse and indicator/group

Technical Specifications - 1756-OA16


AC OUTPUT
ST 0 1 2 3 4 5 6 7
FUSE
ST 8 9 10 11 12 13 14 15

O
K

FUSE

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OA16

Outputs

16 mechanically fused/group (8 points/group)

Voltage category

120/240V AC

Operating voltage range

74265V AC
4763 Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

85

1756 ControlLogix I/O Modules

Attribute

1756-OA16

Current draw @ 5.1V

400 mA

Current draw @ 24V

2 mA

Power dissipation, max

6.5 W @ 60 C

Thermal dissipation, max

22.17 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V @ 0.5 A
5.7V @ load current < 50 mA

Current per point, max

0.5 A @ 60 C

Current per module, max

4 A @ 60 C

Surge current per point

5 A for 43 ms per point, repeatable every 2 s @ 60 C

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA


0.2V/s for loads < 50 mA(1)

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Inhibit voltage, max

Zero crossing 60V peak

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA.
The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the
commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is
exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor
is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at
fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

86

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OA16
Certification(1)

1756-OA16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

87

1756 ControlLogix I/O Modules

1756-OA16I
ControlLogix AC (74...265V) isolated output module
Simplified Schematic
1756-OA16I
Isolated Wiring

+5V

L1-0

L1-0
L1-2
L1-4

OUT-0
ControlLogix Backplane Interface
Display

Jumper Bar (Cut to Length)

Surge Current Chart


Nonisolated
Wiring

Current

20 A

L1

Continuous @ 30C
Continuous @ 60C

2A
1A
0

L1-0

OUT-0

L1-1

OUT-1

L1-2

OUT-2

L1-3

OUT-3

L1-4

10

OUT-4

L1-5

12 11

OUT-5

L1-6

14 13

OUT-6

L1-7

16 15

OUT-7

L1-8

18 17

OUT-8

L1-9

20 19

OUT-9

L1-10

22 21

OUT-10

L1-11

24 23

OUT-11

L1-12

26 25

OUT-12

L1-13
L1-14

28 27
30 29

OUT-13
OUT-14

L1-15

32 31

OUT-15

L1-15
Not Used

34 33

Not Used
Not Used

36 35

L2-0
L2-2
L2-4

L2

43 ms
Time
Daisy Chain to Other RTBs

Technical Specifications - 1756-OA16I


AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15 K

88

Attribute

1756-OA16I

Outputs

16 individually isolated

Voltage category

120/240V AC

Operating voltage range

74265V AC
4763 Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Current draw @ 5.1V

300 mA

Current draw @ 24V

2.5 mA

Power dissipation, max

5.5 W @ 60 C

Thermal dissipation, max

18.76 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A
6V peak @ load current < 50 mA

Current per point, max

2 A @ 30 C (linear derating)
1 A @ 60 C (linear derating)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OA16I

Current per module, max

5 A @ 30 C (linear derating)
4 A @ 60 C (linear derating)

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 C

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA


0.2V/s for loads < 50 mA(1)

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, channel to channel, I/O to
system

Inhibit voltage, max

Zero crossing 60V peak

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA.
The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the
commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is
exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor
is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at
fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

89

1756 ControlLogix I/O Modules

Certifications - 1756-OA16I
Certification(1)

1756-OA16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

90

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB8
ControlLogix DC (10...30V) output module
Simplified Schematic

1756-OB8

Daisy Chain to
Other RTBs

DC-0(+)

+5V

10

12

11

14

13

16

15

18

17

20

19

DC-0 (+)

OUT-0
Group 0

OUT-0

DC-0 (+)

OUT-1

DC-0 (+)

RTN
OUT-0

ControlLogix Backplane Interface

OUT-2

DC-0 (+)

OUT-3

Display
RTN OUT-0

RTN OUT-0

Surge Current Chart


DC-1 (+)

OUT-4

Surge

4A

DC-1 (+)

OUT-5

Current

Group 1

Continuous @ 60o C

Group 1

DC-1 (+)

OUT-6

2A
DC-1 (+)

OUT-7

RTN OUT-1

Group 0

RTN OUT-1

10 ms
Daisy Chain to
Other RTBs

Time

DC COM

Technical Specifications - 1756-OB8


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OB8

Outputs

8 electronically fused, individually isolated

Voltage category

12/24V DC source

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

250 mA

Current draw @ 24V

2 mA

Power dissipation, max

4.7 W @ 60 C

Thermal dissipation, max

16.03 BTU/hr

Off-state leakage current, max

1 mA per point

On-state voltage drop, max

1.2V DC @ 2A

Current per point, max

2 A @ 60 C

Current per module, max

16 A @ 55 C (linear derating)
10 A @ 60 C

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

91

1756 ControlLogix I/O Modules

Attribute

1756-OB8

Load current, min

3 mA per point

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB8
Certification(1)

1756-OB8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

92

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB8EI
ControlLogix DC (10...30V) electronically-fused, isolated output module
1756-OB8EI

+5V

Simplified Schematic
+

DC-0(+)

Isolated
Wiring

OUT-0

OUT-0
Display
ControlLogix Backplane
Interface

RTN
OUT-0

Output
Device

Nonisolated
Wiring

Surge Current Chart

Daisy Chain to
Other RTBs

Surge

4A
Current

Daisy Chain to
Other RTBs

DC-0 (+)

OUT-0

RTN OUT-0

OUT-0

DC-1 (+)

OUT-1

RTN OUT-1

OUT-1

10

OUT-2

RTN OUT-2

12 11

OUT-2

DC-3 (+)

14 13

OUT-3

RTN OUT-3

16 15

OUT-3

DC-4 (+)

18 17

OUT-4

RTN OUT-4
DC-5 (+)

20 19

OUT-4

22 21

OUT-5

RTN OUT-5

24 23

OUT-5

DC-6 (+)

26 25

OUT-6

RTN OUT-6

28 27

OUT-6

DC-7 (+)

30 29

OUT-7

RTN OUT-7

32 31

OUT-7

Not Used

34 33

Not Used

Not Used

36 35

Not Used

DC-2 (+)

Continuous @ 60o C

2A

10 ms

Time

DC COM

Diagnostics - 1756-OB8EI
Attribute

1756-OB8EI

Short trip

> 4.5 A for 500 s max (output on, then short)


> 4.5 A for 1.5 ms max (output on into short)

Timestamp of diagnostics

1 ms

Technical Specifications - 1756-OB8EI


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
FUSE 0 1 2 3 4 5 6 7 K

ELECTRONICALLY FUSED

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OB8EI

Outputs

8 individually isolated

Voltage category

12/24V DC source

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

93

1756 ControlLogix I/O Modules

Attribute

1756-OB8EI

Power dissipation, max

4.6W A @ 60 C

Thermal dissipation, max

15.70 BTU/hr

Off-state leakage current, max

0.5 mA per point

On-state voltage drop, max

0.5V DC @ 2 A

Current per point, max

2 A @ 60 C

Current per module, max

16 A @ 60 C

Surge current per point

4 A for 10 ms each, repeatable every 1 s @ 60 C

Load current, min

2 mA

Isolation voltage

250V user to backplane, Reinforced Insulation Type


250V channel to channel, Basic Insulation Type
Tested to withstand 1900V DC for 2 s user to backplane
Tested to withstand 1900V DC for 2 s channel to channel

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

94

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OB8EI
Certification(1)

1756-OB8EI

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

95

1756 ControlLogix I/O Modules

1756-OB8I
ControlLogix DC (10...30V) isolated output module
+5V

1756-OBI

Simplified Schematic
DC-0(+)
Isolated
Wiring

OUT-0
OUT-0
Display
ControlLogix Backplane
Interface

RTN
OUT-0

Output
Device

Surge Current Chart


Surge

4A
Current

Nonisolated
Wiring

Continuous @ 60 oC

2A

Daisy
Chain to
Other
RTBs

Daisy
Chain to
Other
RTBs

DC-0 (+)
RTN OUT-0
DC-1 (+)
RTN OUT-1
DC-2 (+)
RTN OUT-2
DC-3 (+)
RTN OUT-3
DC-4 (+)
RTN OUT-4
DC-5 (+)
RTN OUT-5
DC-6 (+)
RTN OUT-6
DC-7 (+)
RTN OUT-7
Not Used
Not Used

10 9
12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

OUT-0
OUT-0
OUT-1
OUT-1
OUT-2
OUT-2
OUT-3
OUT-3
OUT-4
OUT-4
OUT-5
OUT-5
OUT-6
OUT-6
OUT-7
OUT-7
Not Used
Not Used

10 ms
Time

Technical Specifications - 1756-OB8I


DC OUTPUT
ST

96

01234567 O
K

Attribute

1756-OB8I

Outputs

8 individually isolated

Voltage category

12/24V DC source

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

Power dissipation, max

4.6W A @ 60 C

Thermal dissipation, max

15.70 BTU/hr

Off-state leakage current, max

0.5 mA per point

On-state voltage drop, max

0.5V DC @ 2 A

Current per point, max

2 A @ 60 C

Current per module, max

16 A @ 60 C

Surge current per point

4 A for 10 ms each, repeatable every 1 s @ 60 C

Load current, min

2 mA

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OB8I

Isolation voltage

250V user to backplane, Reinforced Insulation Type


250V channel to channel, Basic Insulation Type
Tested to withstand 1900V DC for 2 s user to backplane
Tested to withstand 1900V DC for 2 s channel to channel

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB8I
Certification(1)

1756-OB8I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

97

1756 ControlLogix I/O Modules

1756-OB16D
ControlLogix DC (19.2...30V) diagnostic output module
Simplified schematic
+5V +5V

Short Circuit
Detect
Optoisolation

+5V

Group 0

OUT
ControlLogix
Backplane
Interface

RTN

Display Output Verify/No Load


Surge Current Chart
Surge

Current

4A

Group 1

Continuous @ 30 C

2A

1756-OB16D

Daisy Chain to Other RTBs

+ DC

Continuous @ 60 C

+DC-0

OUT-0

+DC-0

OUT-1

+DC-0

OUT-2

+DC-0

OUT-3

+DC-0

10

OUT-4

+DC-0

12

11

OUT-5

+DC-0

14

13

OUT-6

GND-0

16

15

OUT-7

+DC-1

18

17

OUT-8

+DC-1
+DC-1

20

19

OUT-9

22

21

OUT-10

+DC-1

24

23

OUT-11

+DC-1

26

25

OUT-12

+DC-1

28

27

OUT-13

+DC-1

30

29

OUT-14

GND-1

32

31

OUT-15

GND-1

34

33

Not Used

Not Used

36

35

Not Used

Group 0

Group 1

Daisy Chain
to Other RTBs

10 ms

Time

DC COM

Diagnostics - 1756-OB16D
Attribute

1756-OB16D

Short trip

8 A for 180 ms
10 A for 120 ms

No load

Off-state detection only

Output verification

On-state detection only

Pulse test

Configurable maximum pulse width

Time stamp of diagnostics

1 ms

Technical Specifications - 1756-OB16D


DC OUTPUT
Attribute

1756-OB16D

O
FLT 0 1 2 3 4 5 6 7
K
ST 8 9 10 11 12 13 14 15

Outputs

16 diagnostic (8 points/group)

Voltage category

24V DC source

FLT 8 9 10 11 12 13 14 15

Operating voltage range

19.2...30V DC

Output delay, off to on

1 ms

Output delay, on to off

5 ms

ST 0 1 2 3 4 5 6 7

DIAGNOSTIC

98

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OB16D

Current draw @ 5.1V

250 mA

Current draw @ 24V

140 mA

Power dissipation, max

3.3 W @ 60 C

Thermal dissipation, max

11.25 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

1.2V DC @ 2A

Current per point, max

2 A @ 30 C (linear derating)
1 A @ 60 C (linear derating)

Current per module, max

8 A @ 30 C (linear derating)
4 A @ 60 C (linear derating)

Surge current per point

4 A for 10 ms per point, repeatable every 1 s

Load current, min

3 mA per point

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Slot width

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

99

1756 ControlLogix I/O Modules

Certifications - 1756-OB16D
Certification(1)

1756-OB16D

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

100

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16E
ControlLogix DC (10...31.2V) electronically-fused output module
1756-OB16E

Simplified Schematic
Optoisolation

Display

DC-0(+)

10

12

11

14

13

16

15

18

17

OUT-0

OUT-1
Group 0

OUT-0
ControlLogix
Backplane
Interface

Daisy Chain to
Other RTBs

RTN
OUT-0

Electronic
Fuse Circuitry

OUT-2

OUT-3

OUT-4

OUT-5

OUT-6

OUT-7

RTN OUT-0

DC-0(+)

OUT-8

OUT-9

Surge Current Chart

OUT-10

OUT-11

OUT-12

OUT-13

2A
Current

Group 1

Surge

Group 1
OUT-14

OUT-15

Continuous @ 60o C

1A
0

20

19

RTN OUT-1

DC-1(+)

10 ms

Group 0

DC COM

Time

Technical Specifications - 1756-OB16E


DC OUTPUT
ST 0 1 2 3 4 5 6 7
O
FUSE
K
ST 8 9 10 11 12 13 14 15
FUSE

Attribute

1756-OB16E

Outputs

16 electronically fused (8 points/group)

Voltage category

12/24V DC source

Operating voltage range

10...31.2V DC

Output delay, off to on

1 ms

Output delay, on to off

1 ms

Current draw @ 5.1V

250 mA

Current draw @ 24V

2 mA

Power dissipation, max

4.1 W @ 60 C

Thermal dissipation, max

13.98 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

400 mV DC @ 1 A

Current per point, max

1 A @ 60 C

Current per module, max

8 A @ 60 C

Surge current per point

2 A for 10 ms per point, repeatable every 2 s @ 60 C

Load current, min

3 mA per point

ELECTRONICALLY FUSED

Publication 1756-TD002A-EN-E - May 2009

101

1756 ControlLogix I/O Modules

Attribute

1756-OB16E

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Slot width

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16E
Certification(1)

1756-OB16E

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

102

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16I
ControlLogix DC (10...30V) isolated output module
1756-OB16I

Simplified Schematic

Isolated Sourcing
Output Wiring

Isolated Wiring

DC-0(+)

DC-0 (+)

+5V

DC-2 (+)

OUT-0

Sinking Output Wiring


DC-6 (+)

ControlLogix Backplane Interface


Jumper Bar
(Cut to Length)

Display

Surge Current Chart

Nonisolated
Wiring

Surge

4A
Current

Continuous @ 30o C

2A

DC(+)

DC-0 (+)

OUT-0

DC-1 (+)

OUT-1

DC-2 (+)

OUT-2

DC-3 (+)

OUT-3

DC-4 (+)

10

OUT-4

DC-5 (+)

12

11

OUT-5

DC-6 (+)

14

13

OUT-6

DC-7 (+)

16

15

OUT-7

DC-8 (+)

18

17

OUT-8

DC-9 (+)

20

19

OUT-9

DC-10 (+)

22

21

OUT-10

DC-11 (+)

24

23

OUT-11

DC-12 (+)

26

25

OUT-12

DC-13 (+)

28

27

OUT-13

DC-14 (+)

30

29

OUT-14

DC-15 (+)

32

31

OUT-15

DC-15 (+)
Not Used

34

33

36

35

Not Used
Not Used

DC-0 (-)
DC-2 (-)

DC-6 (-)

Nonisolated
Sourcing
Output
Wiring

DC(-)

Continuous @ 60o C
Daisy Chain to Other RTBs

10 ms
Time

Technical Specifications - 1756-OB16I


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OB16I

Outputs

16 individually isolated

Voltage category

12/24V DC sink/source

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

350 mA

Current draw @ 24V

2.5 mA

Power dissipation, max

3.6 W @ 60 C

Thermal dissipation, max

12.28 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

On-state voltage drop, max

1.2V DC @ 2 A

Current per point, max

2 A @ 30 C
1 A @ 60 C

Current per module, max

8 A @ 30 C
4 A @ 60 C

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

103

1756 ControlLogix I/O Modules

Attribute

1756-OB16I

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, channel to channel, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Slot width

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16I
Certification(1)

1756-OB16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

104

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16IS
ControlLogix DC (10...30V) scheduled, isolated output module
Simplified Schematic

1756-OB16IS
Isolated Wiring

DC-0(+)
+5V

OUT-0
ControlLogix Backplane Interface
Display

Surge Current Chart


Surge

Current

4A

Continuous @ 30o C

2A

DC-0 (+)
DC-1 (+)
DC-2 (+)
DC-2 (+)
DC-3 (+)
DC-4 (+)
Sinking Output Wiring DC-5 (+)
DC-6 (+)
DC-6 (+)
+
DC-7 (+)
Jumper Bar
DC-8 (+)
(Cut to Length)
DC-9 (+)
DC-10 (+)
DC-11 (+)
Nonisolated
DC-12 (+)
Wiring
DC-13 (+)
DC-14 (+)
DC-15 (+)
DC(+)
DC-15 (+)
Not Used
DC-0 (+)

10

12

11

14

13

16

15

18

17

20

19

22

21

24

23

26

25

28

27

30

29

32

31

34

33

36

35

OUT-0
OUT-1
OUT-2
OUT-3
OUT-4
OUT-5
OUT-6
OUT-7
OUT-8
OUT-9
OUT-10
OUT-11
OUT-12
OUT-13
OUT-14
OUT-15

Isolated Sourcing
Output Wiring
DC-0 (-)
DC-2 (-)

DC-6 (-)

Nonisolated
Sourcing
Output
Wiring

Not Used
Not Used
DC(-)

Continuous @ 60o C
Daisy Chain to Other RTBs

10 ms
Time

Technical Specifications - 1756-OB16IS


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OB16IS

Outputs

16 individually isolated, 8 scheduled

Voltage category

12/24V DC sink/source

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

350 mA

Current draw @ 24V

2.5 mA

Power dissipation, max

3.6 W @ 60 C

Thermal dissipation, max

12.28 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

On-state voltage drop, max

1.2V DC @ 2 A

Current per point, max

2 A @ 30 C
1 A @ 60 C

Current per module, max

8 A @ 30 C
4 A @ 60 C

Surge current per point

4 A for 10 ms per point, repeatable every 2 s

Load current, min

1 mA per point

105

1756 ControlLogix I/O Modules

Attribute

1756-OB16IS

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, channel to channel, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Slot width

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16IS
Certification(1)

1756-OB16IS

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

106

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB32
ControlLogix DC (10...31.2V) output module
1756-OB32

Simplified Schematic

DC-0(+

+5V
OUT-0
RTN OUT-0
ControlLogix Backplane Interface

Group 0

Daisy Chain
to Other
RTBs

Display

Surge Current Chart


Surge

1A
Current

Group 1

Continuous @ 60o C
0.5 A
0

10 ms

OUT-1
OUT-3
OUT-5
OUT-7
OUT-9
OUT-11

10

OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10

12 11

OUT-13
OUT-15
DC-0(+)

14 13

OUT-17
OUT-19
OUT-21
OUT-23
OUT-25
OUT-27

20 19

OUT-29
OUT-31
DC-1(+)

32 31

16 15
18 17

OUT-16
OUT-18
OUT-20
OUT-22
OUT-24
OUT-26

22 21
24 23
26 25
28 27
30 29

Group 1

OUT-28
OUT-30
RTN OUT-1

34 33
36 35

Time

Group 0

OUT-12
OUT-14
RTN OUT-0

DC COM

Technical Specifications - 1756-OB32


DC OUTPUT
ST 0 1 2
1
ST 8 9 0
1 1 1
ST 6 7 8
2 2 2
ST 4 5 6

3 4
11
12
12
90
22
78

5 6
11
3 4
22
1 2
23
9 0

7
1 O
5
K
2
3
3
1

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OB32

Outputs

32 (16 points/group)

Voltage category

12/24V DC source

Operating voltage range

10...31.2V DC

Output delay, off to on

1 ms

Output delay, on to off

1 ms

Current draw @ 5.1V

300 mA

Current draw @ 24V

2 mA

Power dissipation, max

4.8 W @ 60 C

Thermal dissipation, max

16.37 BTU/hr

Off-state leakage current per point, max

0.5 mA per point

On-state voltage drop, max

200 mV DC @ 0.5 A

Current per point, max

0.5 A @ 50 C (linear derating)


0.35 A @ 60 C

Current per module, max

16 A @ 50 C (linear derating)
10 A @ 60 C

Surge current per point

1 A for 10 ms per point, repeatable every 2 s @ 60 C

Load current, min

3 mA per point

107

1756 ControlLogix I/O Modules

Attribute

1756-OB32

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module Location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

Certifications

c-UL-us, CE, CSA, C-Tick, FM, ATEX

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB32
Certification(1)

1756-OB32

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

108

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OC8
ControlLogix DC (30...60V) output module
Simplified Schematic

1756-OC8

Daisy Chain to Other RTBs

DC-0(+

+5V

DC-0 (+)

OUT-0

OUT-0

DC-0 (+)

RTN OUT-0

OUT-1

Group 0

Group 0

DC-0 (+)

ControlLogix Backplane Interface

OUT-2
8

10

12

11

14

13

16

15

DC-0 (+)

Display

OUT-3

RTN OUT-0

RTN OUT-0

DC-1(+)

Surge Current Chart

DC-1(+)

OUT-5

Group 1

Surge

4A

OUT-4

Group 1

DC-1(+)

OUT-6
18

17

20

19

Current

DC-1(+)

OUT-7

Continuous @ 60o C

2A

RTN OUT-1

RTN OUT-1

10 ms

Daisy Chain to
Other RTBs

DC COM

Time

Technical Specifications - 1756-OC8


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OC8

Outputs

8 (4 points/group)

Voltage category

48V DC source

Operating voltage range

30...60V DC

Output delay, off to on

1 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

165 mA

Current draw @ 24V

2 mA

Power dissipation, max

4.9 W @ 60 C

Thermal dissipation, max

16.71 BTU/hr

Off-state leakage current, max

1 mA per point

On-state voltage drop, max

2V DC @ 2 A

Current per point, max

2 A @ 60 C

Current per module, max

8 A @ 60 C

Surge current per point

4 A for 10 ms per point, repeatable every 1 s @ 60 C

Load current, min

2 mA per point

109

1756 ControlLogix I/O Modules

Attribute

1756-OC8

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE. Maximum wire size requires extended
housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OC8
Certification(1)

1756-OC8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

110

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF4
ControlLogix voltage/current output analog module
1756-OF4 Voltage

1756-OF4 Current
2

Not Used

VOUT-0
4

Not Used

IOUT-0
6

RTN

Current
Output
Load

RTN
8

11

12

Shield
Ground

VOUT-2
14

13

16

15

18

17

20

19

Not Used

10

VOUT-1

Place additional loop devices (such as strip chart recorders) at


the A location noted above.
Do not connect more than two wires to any single terminal.

Shield
Ground

IOUT-1
12

11

14

13

16

15

18

17

20

19

Not Used

VOUT-2
IOUT-2
RTN
VOUT-3

Not Used

IOUT-3

RTN

Not Used

VOUT-3

Not Used

IOUT-0

RTN

RTN

Not Used

Not Used

IOUT-2

RTN

Not Used

IOUT-1

Not Used

RTN

Not Used

Not Used

VOUT-1
10

VOUT-0

Not Used

Not Used

Not Used

IOUT-3

Do not connect more than two wires to any single terminal.


All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

Input Signal to User Count Conversion - 1756-OF4


Range

Low Signal and User Counts

High Signal and User Counts

0...20 mA

0 mA

21.2916 mA

-32768 counts

32767 counts

-10.4336V

10.4336V

-32768 counts

32767 counts

10V

Technical Specifications - 1756-OF4


ANALOG OUTPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OF4

Outputs

8 voltage or current

Output range

10.4V
021 mA

Resolution

Voltage: 15 bits across 10.5V, 320 V/bit


Current: 15 bits across 21mA, 650 nA/bit

Current draw @ 5.1V

150 mA

111

1756 ControlLogix I/O Modules

Attribute

1756-OF4

Current draw @ 24V

120 mA

Power dissipation, max

3.25 W, 4 channel current

Thermal dissipation

10.91 BTU/hr

Open circuit detection

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21mA or less

Drive capability

Voltage: >2000
Current: 0750

Settling time

<2 ms to 95% of final value with resistive loads

Calibrated accuracy

421 mA, -10.410.4V: Better than 0.05% of range @


25 C

Calibration interval

12 months

Offset drift

50 V/ C
100 nA/C

Gain drift with temperature

Voltage: 25 ppm/C, 520 V/C


Current: 50 ppm/C, 1050 A/C

Module error

Voltage: 0.15% of range


Current: 0.3% of range

Module scan time

12 ms floating point
8 ms integer

Isolation voltage

Tested at 2550V DC for 1 s, I/O to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2(2)

Wire type

Copper

Enclosure type rating

None (open-style)

Certifications

c-UL-us, CE, CSA, C-Tick, FM, ATEX

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

112

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OF4
Certification(1)

1756-OF4

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

113

1756 ControlLogix I/O Modules

1756-OF6CI
ControlLogix current loop output analog module
1756-OF6CI 551...1000

1756-OF6CI 0...550
2

OUT-0

OUT-1
4

User Analog
Output Device

RTN-0
8

10

12

11

14

13

OUT-4
18

17

20

19

12

11

14

13

OUT-2

ALT-2
RTN-2
Shield Ground
Not Used
16

15

18

17

20

19

OUT-4

ALT-5

RTN-4

RTN-5

10

RTN-0

OUT-5

ALT-4

ALT-5

Not Used

15

OUT-5

RTN-3
Shield
Ground

Not Used

Not Used

ALT-3

RTN-2

RTN-3

OUT-3

ALT-2

ALT-3

User Analog
Output Device

ALT-0

RTN-1

OUT-2

OUT-3

ALT-1

RTN-1

16

OUT-0

ALT-0

ALT-1

OUT-1

ALT-4
RTN-4

RTN-5

Place additional devices anywhere in the loop.

Place additional devices anywhere in the loop.

Do not connect more than two wires to any single terminal.

Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-OF6CI

ANALOG OUTPUT
CAL
OK

114

Range

Low Signal and User Counts

High Signal and User Counts

0...20 mA

0 mA

21.074 mA

-32768 counts

32767 counts

Technical Specifications - 1756-OF6CI


Attribute

1756-OF6CI

Outputs

6 individually isolated

Output range

021 mA

Resolution

13 bits across 21 mA (2.7 A)

Current draw @ 5.1V

250 mA for 0...550 W loads terminated on OUTs and


RTNs
(Total backplane power in this range 6.7 W)
250 mA for 551...1000 W loads terminated on OUTs and
ALTs
(Total backplane power in this range 8.5 W)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OF6CI

Current draw @ 24V

225 mA for 0...550 W loads terminated on OUTs and


RTNs
(Total backplane power in this range 6.7 W)
300 mA for 551...1000 W loads terminated on OUTs and
ALTs
(Total backplane power in this range 8.5 W)

Power dissipation, max

5.5 W (0550 loads)


6.1 W (5511000 loads)

Thermal dissipation

18.76 BTU/hr (0550 loads)


20.80 BTU/hr (5511000 loads)

Open circuit detection

None

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21mA or less

Drive capability

01000
Separate field terminations for 0550 and
5511000

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy

421 mA: Better than 0.1% of range @ 25 C

Calibration interval

6 months

Offset drift

1 A/C

Gain drift with temperature

60 ppm/C, 100 ppm/C max

Module error

0.6% of range

Module scan time

25 ms max floating point


10 ms max integer

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

115

1756 ControlLogix I/O Modules

Certifications - 1756-OF6CI
Certification(1)

1756-OF6CI

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

116

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF6VI
ControlLogix voltage loop output analog module
1756-OF6VI
2

OUT-1

OUT-0
4

Not Used

User Analog
Output Device

Not Used
6

RTN-1

RTN-0

OUT-3

OUT-2
10

12

11

14

13

16

15

18

17

20

19

Not Used

Not Used

RTN-3

RTN-2

Not Used

Shield Ground
Not Used

OUT-5

OUT-4

Not Used

Not Used

RTN-5

RTN-4

Place additional devices anywhere in the loop.


Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-OF6V


Range

Low Signal and User Counts

High Signal and User Counts

10V

-10.517V

10.517V

-32768 counts

32767 counts

Technical Specifications - 1756-OF6VI


ANALOG OUTPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OF6VI

Outputs

6 individually isolated

Output range

10.5V

Resolution

14 bits across 21V (1.3 mV)


(13 bits across 10.5V +sign bit)

Current draw @ 5.1V

250 mA

Current draw @ 24V

175 mA

Power dissipation, max

4.85 W

Thermal dissipation

16.54 BTU/hr

Output impedance

<1

Open circuit detection

None

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited

Drive capability

> 1000 loads, 10 mA

117

1756 ControlLogix I/O Modules

Attribute

1756-OF6VI

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy

421 mA: Better than 0.1% of range @ 25 C

Calibration interval

6 months

Offset drift

60 V/ C

Gain drift with temperature

50 ppm/C, 80 ppm/C max

Module error

0.5% of range

Module scan time

25 ms floating point
10 ms integer

Isolation voltage

250V continuous
Tested at 1700V DC for 1 s, channel to channel, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

2(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OF6VI
Certification(1)

1756-OF6VI

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

118

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF8
ControlLogix voltage/current output analog module
1756-OF8 Voltage

1756-OF8 Current
2

VOUT-4

VOUT-0
4

IOUT-4

IOUT-0
6

RTN

RTN
8

VOUT-1
10

12

11

IOUT-5

Shield Ground
VOUT-2

14

13

16

15

18

17

IOUT-6

20

10

Shield Ground
IOUT-1

12

11

14

13

16

15

18

17

20

19

VOUT-2
IOUT-2
RTN

RTN

VOUT-3

VOUT-7

19

IOUT-3

IOUT-3

IOUT-7

Place additional loop devices (such as strip chart recorders) at


the A location noted above.

VOUT-1

IOUT-5

VOUT-3

IOUT-7

IOUT-6

RTN

VOUT-7

VOUT-6

IOUT-2

RTN

VOUT-5

IOUT-1

VOUT-6

RTN

VOUT-5

VOUT-0
IOUT-0

Current IOUT-4
Output
RTN
Load

VOUT-4

Do not connect more than two wires to any single terminal.


All terminals marked RTN are connected internally.

Do not connect more than two wires to any single terminal.


All terminals marked RTN are connected internally.

Input Signal to User Count Conversion - 1756-OF8


Range

Low Signal and User Counts

High Signal and User Counts

0...20 mA

0 mA

21.2916 mA

-32768 counts

32767 counts

-10.4336V

10.4336V

-32768 counts

32767 counts

10V

ANALOG OUTPUT
CAL
OK

Publication 1756-TD002A-EN-E - May 2009

Technical Specifications - 1756-OF8


Attribute

1756-OF8

Outputs

8 voltage or current

Output range

10.4V
021 mA

Resolution

15 bits across 21 mA - 650 nA/bit


15 bits across 10.4V - 320 V/bit

Current draw @ 5.1V

150 mA

119

1756 ControlLogix I/O Modules

Attribute

1756-OF8

Current draw @ 24V

210 mA

Power dissipation, max

4.92 W, 4 channel current

Thermal dissipation

16.78 BTU/hr

Open circuit detection

Current output only (Output must be set to >0.1 mA)

Overvoltage protection

24V DC

Short circuit protection

Electronically current limited to 21 mA or less

Drive capability

Voltage: > 2000


Current: 0750

Settling time

< 2 ms to 95% of final value with resistive loads

Calibrated accuracy

421 mA, -10.410.4V: Better than 0.05% of range @


25 C

Calibration interval

12 months

Offset drift

50 V/C
100 nA/C1 A/C

Gain drift with temperature

Voltage: 25 ppm/C max


Current: 50 ppm/C max

Module error

Voltage: 0.15% of range


Current: 0.3% of range

Module scan time

12 ms min floating point


8 ms min integer

Isolation voltage

Tested at 2550V DC for 1 s, I/O to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

120

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OF8
Certification(1)

1756-OF8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

121

1756 ControlLogix I/O Modules

1756-OF8H
ControlLogix voltage/current output analog module with HART protocol
1756-OF8H

Input Signal to User Count Conversion - 1756-OF8


Range

Low Signal and User Counts

High Signal and User Counts

0...20 mA

0 mA

21.2916 mA

-32768 counts

32767 counts

-10.4336V

10.4336V

-32768 counts

32767 counts

10V

Technical Specifications - 1756-OF8H


ANALOG OUTPUT
CAL
OK
HART

122

Attribute

1756-OF8H

Outputs

8 voltage or current

Output range

10.4V
020 mA
420 mA

Resolution

1516 bits

Current draw @ 5V

200 mA

Current draw @ 24V

230 mA

Power dissipation, max

4.92 W, 8 channel current

Thermal dissipation

16.78 BTU/hr

Output impedance

Voltage: >2 k @ 10.4V


Current: 50750 drive

Open circuit detection time

Current output only (output must be set to < 0.1mA)

Overvoltage protection, max

24V DC

Drive capability

Voltage: > 2000 @ 10.4V


Current: 50750 with short circuit survival current

Load reactance

Voltage: 1 F
Current: 10 H

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OF8H

Settling time

Current (no HART): < 23 ms to 95% with resistive loads


Current (with HART): < 37 ms to 95% with resistive loads
Voltage: < 8.5 ms to 95% with resistive loads

Calibrated accuracy

Voltage: Better than 0.05% of range


Current: Better than 0.15% of range

Calibration interval

12 months

Offset drift

100 V/C typical


200 nA/C typical

Gain drift with temperature

Voltage: 20 ppm/C
Current: 35 ppm/C

Module error

Voltage: 0.15% of range


Current: 0.3% of range

Module output scan time, min

12 ms floating point

Module HART scan time

Typically 1 s per HART channel enabled


Estimate 10 s if all 8 channels have HART enabled
Pass through messages, handheld communicators,
secondary masters, communication errors, or
configuration changes can significantly increase the
update time

Isolation voltage

50 V (continuous), Basic Insulation Type


Tested at 1500V AC for 60 s, I/O to backplane

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

2(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

123

1756 ControlLogix I/O Modules

Certifications - 1756-OF8H
Certification(1)

1756-OF8H

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

124

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OG16
ControlLogix TTL output module
Standard Wiring

CE Compliant Wiring
1756-OG16

1756-OG16
DC
+
2

OUT-1

OUT-0
4

+5 V DC

OUT-3

OUT-4
8

OUT-6
10

12

11

14

13

16

15

18

17

20

19

DC COM 0

OUT-9

TTL
Output
Device

OUT-10

OUT-15

OUT-12

I/O Wire

10

12

11

14

13

16

15

18

17

20

19

OUT-4

OUT-7

OUT-6
DC COM 0

OUT-9

OUT-8
OUT-10

OUT-13

OUT-12

OUT-15
DC COM 1

OUT-0
OUT-2

OUT-11
Capacitor
0.01 F Typical
(See notes below.)

OUT-14

DC-1(+)

DC-0(+)

OUT-8

OUT-11

OUT-5

DC-0(+)

OUT-3

OUT-7

OUT-1

OUT-2
6

OUT-13

DC Power Wire

OUT-5

+ DC

5V DC
Power

OUT-14

DC-1(+)

DC COM 1

Simplified Schematic
+5 DC
74AC14
OUT

74AC14
OUT

DC COM

Low to True Format - 1756-OG16


00.4V DC = Output guaranteed to be in on-state
0.44.5V DC = Output state not guaranteed
4.55.5V DC = Output guaranteed to be in off-state

Publication 1756-TD002A-EN-E - May 2009

125

1756 ControlLogix I/O Modules

Technical Specifications - 1756-OG16


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Attribute

1756-OG16

Outputs

16 (8 points/group)

Voltage category

5V DC TTL(1)

Operating voltage range

4.5...5.5V DC source
50 mV P-P ripple max

Output delay, off to on

450 s

Output delay, on to off

700 s

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

Power dissipation, max

1.5 W @ 60 C

Thermal dissipation, max

5.2 BTU/hr @ 60 C

Off-state leakage current per point, max

0.1 mA per point

On-state voltage drop, max

0.4V DC

Current per point, max

24 mA @ 60 C

Current per module, max

384 mA @ 60 C

Load current, min

0.15 mA per point

Isolation voltage

250V continuous, I/O group to group, I/O to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(2)

Wire category

2(3)

Wire type

Copper

Slot width

None (open-style)

(1)

TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in your program to
convert to traditional True - High logic.
(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

126

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OG16
Certification(1)

1756-OG16

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

127

1756 ControlLogix I/O Modules

1756-OH8I
ControlLogix DC (90...146V) isolated output module
Simplified Schematic
+5V

OUT-0

RTN
OUT-0

ControlLogix Backplane Interface


Display
Non-Isolated
Wiring

Surge Current Chart


Surge

Current

4A

Continuous @ 60o C
2A

Time

1756-OH8I

Isolated Wiring

DC-0

Daisy
chain to
other
RTBs

Daisy
chain to
other
RTBs

10 ms

DC-0 (+)

OUT-0

RTN OUT-0

OUT-0

DC-1 (+)

OUT-1

RTN OUT-1
DC-2 (+)

10

OUT-1
OUT-2

RTN OUT-2

12 11

OUT-2

DC-3 (+)

14 13

OUT-3

RTN OUT-3

16 15

OUT-3

DC-4 (+)

18 17

OUT-4

RTN OUT-4

20 19

OUT-4

DC-5 (+)

22 21

OUT-5

RTN OUT-5

24 23

OUT-5

DC-6 (+)

26 25

OUT-6

RTN OUT-6

28 27

OUT-6

DC-7 (+)

30 29

OUT-7

RTN OUT-7

32 31

OUT-7

Not used

34 33

Not used

Not used

36 35

Not used

DC COM

Technical Specifications - 1756-OH8I


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

128

Attribute

1756-OH8I

Outputs

8 individually isolated

Voltage category

120V DC sink/source

Operating voltage range

90...146V DC

Output delay, off to on

2 ms

Output delay, on to off

2 ms

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

Power dissipation, max

3.3 W @ 60 C

Thermal dissipation, max

11.25 BTU/hr

Off-state leakage current, max

1 mA per point

On-state voltage drop, max

2V DC @ 2 A

Current per point, max

2 A @ 60 C

Current per module, max

8 A @ 60 C

Surge current per point

4 A for 10 ms per point, repeatable every 1 s @ 60 C

Load current, min

2 mA per point

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OH8I

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O channel to channel, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OH8I
Certification(1)

1756-OH8I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

129

1756 ControlLogix I/O Modules

1756-ON8
ControlLogix AC (10...30V) output module
Simplified Schematic
+5V

1756-ON8

Daisy Chain to Other RTBs

L1-0

10

12

11

14

13

16

15

L1-0

OUT-0

L1-0

OUT-0

Group 0

ControlLogix Backplane Interface

OUT-1

L1-0

OUT-2

L1-0

Display

OUT-3

L1-0

Surge Current Chart

Not Used

L1-1

Surge

20 A

OUT-4

L1-1

Current

Group 1

OUT-5

L1-1
18

17

20

19

OUT-7

L1-1

Time

Group 1
OUT-6

L1-1

2A

Group 0

Not Used

L2

43 ms
L1

Technical Specifications - 1756-ON8


AC OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

130

Attribute

1756-ON8

Outputs

8 (4 points/group)

Voltage category

24V AC

Operating voltage range

1030V AC, current >50 mA, 4763Hz


1630V AC, current <50 mA, 4763Hz

Output delay, off to on

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Output delay, on to off

9.3 ms @ 60 Hz
11 ms @ 50 Hz

Current draw @ 5.1V

200 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.1 W @ 60 C

Thermal dissipation, max

17.39 BTU/hr

Off-state leakage current, max

3 mA per point

On-state voltage drop, max

1.5V peak @ 2 A
6V peak @ < 50 mA

Current per point, max

2 A @ 60 C

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-ON8

Current per module, max

5 A @ 30 C
4 A @ 60 C (linear derating)

Surge current per point

20 A for 43 ms per point, repeatable every 2 s @ 60 C

Load current, min

10 mA per point

Commutating voltage

4V/s for loads > 50 mA


0.2V/s for loads < 50 mA(1)

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(2)

Wire category

1(3)

Wire type

Copper

Enclosure type rating

None (open style)

(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA.
The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the
commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is
exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor
is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be
at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections.

(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)
Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

131

1756 ControlLogix I/O Modules

Certifications - 1756-ON8
Certification(1)

1756-ON8

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

132

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OV16E
ControlLogix DC (10...30V) electronically-fused, sinking output module
1756-OV16E

Simplified Schematic
Display

Optoisolation

DC-0(+)

Group 0

Electronic
Fuse Circuitry

OUT-0

OUT-3

OUT-0

ControlLogix
Backplane
Interface

OUT-1

OUT-2

10

12

11

14

13

16

15

18

17

20

19

OUT-7

RTN
OUT-0

OUT-6
RTN OUT-0

DC-0(+)

OUT-8

OUT-9
OUT-11

Surge Current Chart


Group 1

Current

OUT-10

OUT-13

OUT-12

RTN OUT-1

DC-1(+)

Continuous @ 60o C

1A

10 ms

Group 1

OUT-14

OUT-15

Surge

2A

Group 0

OUT-4

OUT-5

Time

DC COM

Daisy Chain to Other RTBs

Daisy Chain to Other RTBs

Diagnostics - 1756-OV16E
Attribute

1756-OV16E

Short trip

5 A for 20 ms @ 24V DC (output on, then short)


5 A for 20 ms @ 24V DC (output on into short)

Time stamp of diagnostics

1 ms

Technical Specifications - 1756-OV16E


DC OUTPUT
ST 0 1 2 3 4 5 6 7

O
K
ST 8 9 10111213 1415

FUSE
FUSE

ELECTRONICALLYFUSED

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OV16E

Outputs

16 electronically fused (8 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10...30V DC

Output delay, off to on

1 ms

Output delay, on to off

1 ms

Current draw @ 5.1V

210 mA

Current draw @ 24V

2 mA

133

1756 ControlLogix I/O Modules

Attribute

1756-OV16E

Power dissipation, max

6.72 W @ 60 C

Thermal dissipation, max

22.94 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

700 mV DC @ 1 A

Current per point, max

1 A @ 60 C

Current per module, max

8 A @ 60 C

Surge current per point

2 A for 10 ms per Point, repeatable every 2 s @ 60 C

Load current, min

2 mA per point

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Slot width

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

134

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OV16E
Certification(1)

1756-OV16E

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

135

1756 ControlLogix I/O Modules

1756-OV32E
ControlLogix DC (10...30V) electronically-fused, sinking output module
Simplified Schematic
Display

Optoisolation

DC-0(+)
OUT-0

Group 0

ControlLogix
Backplane
Interface

Electronic
Fuse Circuitry

RTN
OUT-0

Surge Current Chart


Group 1

Surge

Current

2A

Continuous @ 60o C

1A
0

1756-OV32E

Daisy Chain to
Other RTBs
OUT-1
OUT-3
OUT-5

OUT-7
OUT-9
OUT-11

10

OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10

12 11

OUT-13
OUT-15
DC-0(+)

14 13

OUT-17
OUT-19
OUT-21

20 19

OUT-23
OUT-25
OUT-27

26 25

OUT-29
OUT-31
DC-1(+)

32 31

Group 0

OUT-12
OUT-14
RTN OUT-0

16 15
18 17

OUT-16
OUT-18
OUT-20

22 21
24 23

OUT-22
OUT-24
OUT-26

28 27
30 29

Group 1

OUT-28
OUT-30
RTN OUT-1

34 33
36 35

10 ms

Daisy Chain to
Other RTBs

Time

DC COM

Diagnostics - 1756-OV32E
Attribute

1756-OV32E

Short trip

5 A for 20 ms @ 24V DC (output on then short)


5 A for 20 ms @ 24V DC (output into short)

Time stamp of diagnostics

1 ms

Technical Specifications - 1756-OV32E


DC OUTPUT
ST 0 1 2
1
ST 8 9 0
1 1 1
ST 6 7 8
2 2 2
ST 4 5 6

3
1
1
1
9
2
7

4
1
2
2
0
2
8

5 6
11
3 4
22
1 2
23
9 0

7
1
5
2
3
3
1

F
0
O
K
F
1

ELECTRONIC FUSING

136

Attribute

1756-OV32E

Outputs

32 electronically fused (16 points/group)

Voltage category

12/24V DC sink

Operating voltage range

10...30V DC

Output delay, off to on

300 s

Output delay, on to off

1 ms

Current draw @ 5.1V

390 mA

Current draw @ 24V

2 mA

Power dissipation, max

5.88 W @ 60 C

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OV32E

Thermal dissipation, max

20.1 BTU/hr

Off-state leakage current per point, max

1 mA per point

On-state voltage drop, max

350 mV DC @ 0.5 A

Current per point, max

0.5 A @ 50 C (linear derating)


0.35 A @ 60 C

Current per module, max

16 A @ 50 C (linear derating)
10 A @ 60 C

Surge current per point

2 A for 10 ms per point, repeatable every 2 s @ 60 C

Load current, min

2 mA per output

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module Location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

137

1756 ControlLogix I/O Modules

Certifications - 1756-OV32E
Certification(1)

1756-OV32E

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

138

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OW16I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
1756-OW16I

Simplified Schematic

Isolated Wiring

+24V

L1-0

L1

Display
ControlLogix
Backplane
Interface

OUT

L1-0
L1-1
L1-2
L1-2
L1-3
DC-4 (+)
L1-4
L1-5
L1-6
L1-7
Jumper Bar
L1-8
(Cut to Length)
L1-9
L1-10
L1-11
Nonisolated
L1-12
Wiring
L1-13
L1-14
L1-15
L1-15
L1
Not Used

10

12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

L2-0

OUT-0
OUT-1 N.O.
OUT-2 N.O.
OUT-3 N.O.
OUT-4 N.O.
OUT-5 N.O.
OUT-6 N.O.
OUT-7 N.O.
OUT-8 N.O.
OUT-9 N.O.
OUT-10 N.O.
OUT-11 N.O.
OUT-12 N.O.
OUT-13 N.O.
OUT-14 N.O.
OUT-15 N.O
Not Used
Not Used

L2-2
DC-4 (-)

L2
Daisy Chain
to Other RTBs

Technical Specifications - 1756-OW16I


RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O
ST 8 9 10 11 12 13 14 15K

Publication 1756-TD002A-EN-E - May 2009

Attribute

1756-OW16I

Outputs

16 N.O. individually isolated

Operating voltage range

5...150V DC
10...265V AC

Load dependent output voltage range

530V DC @ 2 A resistive
48V DC @ 0.5 A resistive
125V DC @ 0.25 A resistive
125V AC @ 2 A resistive
240V AC @ 2 A resistive

Resistive output current rating (at rated power)

2 A @ 530V DC
0.5 A @ 48V DC
0.25 A @ 125V DC
2 A @ 125/240V AC

Inductive output current rating (at rated power)

2 A steady state @ 530V DC


0.5 A steady state @ 48V DC
0.25 A steady state @ 125V DC
2 A steady state, 15 A make @ 125V AC
2 A steady state, 15 A make @ 240 V AC

Power rating (steady state), max

250 W for 125V AC resistive output


480 W for 240V AC resistive output
60 W for 30V DC resistive output
24 W for 48V DC resistive output
31 W for 125V DC resistive output
250VA for 125V AC inductive output
480VA for 240V AC inductive output
60VA for 30V DC inductive output
24VA for 48V DC inductive output
31VA for 125V DC inductive output

139

1756 ControlLogix I/O Modules

Attribute

1756-OW16I

Output delay, off to on

13 ms

Output delay, on to off

13 ms

Current draw @ 5.1V

150 mA

Current draw @ 24V

150 mA

Power dissipation, max

4.5 W @ 60 C

Thermal dissipation, max

15.35 BTU/hr

Off-state leakage current per point, max

1.5 mA per point

Initial contact resistance, max

30 M

Switching frequency, max

1 operation/3 s (0.3 Hz at rated load)

Bounce time, mean

1.2 ms

Expected contact life

300 K cycles resistive


100 K cycles inductive

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, channel to channel, I/O to
system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64


in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

140

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OW16I
Certification(1)

1756-OW16I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

141

1756 ControlLogix I/O Modules

1756-OX8I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
1756-OX8I

Simplified Schematic
+24V
L1-0

ControlLogix
Backplane
Interface

OUT-0 N.C.

OUT-0 N.O.

Display

Isolated Wiring

L1-0

L1-0
L1-0
L1-1
L1-1
DC-2 (+)
L1-2
L1-2
L1-3
Jumper Bar (Cut to Length) L1-3
(Part number 97739201) L1-4
L1-4
L1-5
L1-5
L1-6
Nonisolated
Wiring
L1-6
L1-7
L1-7
L1-7
L1
Not Used

10

12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35

OUT-0 N.C.
OUT-0 N.O.
OUT-1 N.C.
OUT-1 N.O.
OUT-2 N.C.
OUT-2 N.O.
OUT-3 N.C.
OUT-3 N.O.
OUT-4 N.C.
OUT-4 N.O.
OUT-5 N.C.
OUT-5 N.O.
OUT-6 N.C.
OUT-6 N.O.
OUT-7 N.C.
OUT-7 N.O
Not Used
Not Used

L2-0

DC-2 (-)

L2
Daisy Chain to Other RTBs

Technical Specifications - 1756-OX8I


RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O
K

142

Attribute

1756-OX8I

Outputs

8 N.O.
8 N.C. individually isolated (2 points/group)

Operating voltage range

5...150V DC
10...265V AC @ 4763

Load dependent output voltage range

530V DC @ 2 A resistive
48V DC @ 0.5 A resistive
125V DC @ 0.25 A resistive
125V AC @ 2 A resistive
240V AC @ 2 A resistive

Resistive output current rating (at rated power)

2 A @ 530V DC
0.5 A @ 48V DC
0.25 A @ 125V DC
2 A @ 125/240V AC

Inductive output current rating (at rated power)

2 A steady state @ 530V DC


0.5 A steady state @ 48V DC
0.25 A steady state @ 125V DC
2 A steady state, 15 A make @ 125V AC
2 A steady state, 15 A make @ 240 V AC

Power rating (steady state), max

250 W for 125V AC resistive output


480 W for 240V AC resistive output
60 W for 30V DC resistive output
24 W for 48V DC resistive output
31 W for 125V DC resistive output
250VA for 125V AC inductive output
480VA for 240V AC inductive output
60VA for 30V DC inductive output
24VA for 48V DC inductive output
31VA for 125V DC inductive output

Output delay, off to on

13 ms

Output delay, on to off

13 ms

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-OX8I

Current draw @ 5.1V

100 mA

Current draw @ 24V

100 mA

Power dissipation, max

3.1 W @ 60 C

Thermal dissipation, max

10.57 BTU/hr

Off-state leakage current per point, max

0 mA

Initial contact resistance, max

100 M @ 6V 1 A

Switching frequency, max

1 operation/3 s (0.3 Hz at rated load)

Bounce time, mean

1.2 ms

Expected contact life

300 K cycles resistive


100 K cycles inductive

Isolation voltage

265V continuous
Tested at 2546V DC for 1 s, channel to channel, I/O to system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

143

1756 ControlLogix I/O Modules

Certifications - 1756-OX8I
Certification(1)

1756-OX8I

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

FM

FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

(1)

144

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-CFM
ControlLogix configurable flow meter module
1756-CFM Standard Magnetic Pickup
2

Z0 12-24V DC
4

12

11

F0 Return

Shield
Ground

14

Not Used
15

18

17

20

19

Output 0

Customer VCC

10

12

11

14

13

16

15

18

17

20

19

Z1 RET
F1
F1 Return
Not Used
Not Used

Output 0

Customer
Common
Customer
Common

Not Used

Output 1

Customer VCC

Z1 5V DC

Not Used

13

16

F0 Return

Not Used

Not Used

F0

F1 Return

Not Used

Z0 Return

F1
10

Z1 12-24V DC
4

Z0 5V DC

Z1 RET

F0

Z0 12-24V DC

Z1 5V DC

Z0 Return

Z1 12-24V DC

Z0 5V DC

Input
Device

1756-CFM Standard Output

Output 1

Customer VCC

Customer VCC

Load

Customer
Common
Customer
Common

+
Load

This wiring diagram can be used in applications with 50 mV


(magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds.
You must use RSLogix 5000 software to choose the appropriate
threshold level for your specific application.

If separate power sources are used, do not exceed the specified


isolation voltage.

If separate power sources are used, do not exceed the specified


isolation voltage.

Publication 1756-TD002A-EN-E - May 2009

145

1756 ControlLogix I/O Modules

1756-CFM Standard Prover/Store Count

12-24V DC

Z0 12-24V DC

10

12

11

14

13

16

15

18

17

20

19

Z1 5V DC

Z0 5V DC
Shield Ground

Input
Device

F0

F0 Return
Shield rGound

Z1 RET

Z0 Return

Z1 1224V DC

F1
F1 Return
Not Used

Not Used
Not Used

Not Used

Output 0

Output 1

Customer VCC

Customer
Common
Customer
Common

Customer VCC

Detectors 1 and 2 must be wired in parallel.


Customer VCC may be used to power detectors. In this case, though, the maximum current on the
wiring arm must be less than 4 A.
The wiring example above shows a 12-24V DC standard prover connected to the module. If you use a
5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such as Z0 5V DC).
If separate power sources are used, do not exceed the specified isolation voltage.

Technical Specifications - 1756-CFM


METERING
F
0

Z
0

F
1

O O
0 1

DC I/O

146

Z
1

O
K

Attribute

1756-CFM

Inputs

4 (2 per channel)

Inputs per channel

2 Flowmeter (F) inputs used for all modes


2 Gate inputs used in Totalizer mode for prover/store
count

Outputs

2 current sourcing

Current draw at 5.1V

300 mA

Current draw at 24V

6 mA

Backplane power, total

1.7 W

Power dissipation, max

6 W @ 60 C

Thermal dissipation, max

20.4 BTU/hr

Isolation voltage

125V continuous
Tested at 1700V DC, I/O group to group, I/O to system

Removable terminal block

1756-TBNH
1756-TBSH

Slot width

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute

1756-CFM

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C,


1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.)


insulation(1)

Wire category

1(2)

Wire type

Belden 8761 or equivalent

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-CFM Input Specifications

Publication 1756-TD002A-EN-E - May 2009

Attributes

Value

Inputs

4 (2 per channel)

Inputs per channel

2 Flowmeter (F) inputs used for all modes


2 Gate inputs used in Totalizer mode for prover/store count

Input type

IEC Type 2 (630 mA) @ 24V DC

Count range, max

2,147,483,647

Input frequency, max

100 kHz @ flowmeter inputs (overrange occurs at 100 kHz)

Flowmeter input voltage

30V, selectable input thresholds of 50 mV, 1.3V and 4V:


30V peak unterminated open circuit voltage, magnetic pickup
TTL compatible, input voltage >1.3V DC is Logic 1 and -0.71.3V DC is
Logic 0
1224V DC powered preamp output, 4V DC threshold

Flowmeter input impedance

5 k 30% resistive

Filtering (inputs F0 & F1)

Firmware selectable: High-speed 100 kHz or low-pass filter for frequencies


< 70 Hz

Gate input voltage range

5V operation: 4.55.5V DC
12/24V operation: 1031.2V DC

Gate input on-state current, min

4 mA

Gate input on-state current, nom

15 mA

Mechanical filter debouncing (Z0


& Z1 Inputs)

Software selectable

Input sampling period

User Selectable

147

1756 ControlLogix I/O Modules

1756-CFM Output Specifications


Attribute

Value

Outputs

2 current sourcing

Output voltage source

Customer supplied

Output voltage range

5V operation: 4.55.5V DC for 320 mA load per point


12/24V operation: 1031.2V DC for 40 mA1 A load per point

Output type

IEC 1A 24V DC

Output Current per point

1 A @ 1031.2V DC
20 mA @ 4.55.5V DC(1)

Surge current, max

2 A for 50 ms, repeatable every 2 s

Off-state leakage current, max

< 300 A @ 31.2V DC

On-state voltage drop, max

0.6 x current

Output control

Any number of outputs is assignable to any of 2 flowmeter channels


Each output can have 2 turn-on and turn-off preset values

Output switching time

< 50 s turn on, <300 s turn off


Outputs triggered by Total; all other turn-on and turn-off times <1ms

Overload current

Electronic (< 4A)

Output short circuit protection

Electronic (No indication of fault. Remove overload and toggle output


on/off to restore.)

Output reverse polarity protection

Yes (If wired incorrectly, module outputs may be permanently disabled.)

(1)

All outputs can be on simultaneously without derating.

Certifications - 1756-CFM
Certification(1)

1756-CFM

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

148

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-HSC
ControlLogix high-speed counter module
1756-HSC to Allen-Bradley 845 Incremental Encoder

Z0 (12...24V)

Z1 (12...24V)

Z0 (5V)
Z0 (RET)
B0 (12..24V)
B0 (5V)

10

Z1 (5V)
Z1 (RET)
B1 (12...24V)
B1 (5V)

B0 (RET)
A0 (12...24V)
A0 (5V)

12 11
14 13
16 15

A0 (RET)
Not Used
Not Used

18 17

Not Used
Out 0
Out 1

24 23

COMMON 0
COMMON 0
COMMON 0

30 29

DC-0(+)

36 35

20 19
22 21

26 25
28 27

32 31
34 33

B1 (RET)
A1 (12...24V)
A1 (5V)
A1 (RET)
Not Used
Not Used

1756-HSC to Allen-Bradley Series 10,000 Photoelectric Sensor

Allen-Bradley
Bulletin 845
Incremental
Encoder

Green
Black
Blue
Black
White
Black

Differential Line
Driver Output

Not Used
Out 2
Out 3
COMMON 1
COMMON 1
COMMON 1
DC-1(+)

Z0 (12...24V)
Z0 (5V)
Z0 (RET)
B0 (12...24V)
B0 (5V)

10

B0 (RET)
A0 (12...24V)
A0 (5V)

12 11

A0 (RET)
Not Used
Not Used

18 17

Not Used
Out 0
Out 1

24 23

COMMON 0
COMMON 0
COMMON 0

30 29

DC-0(+)

36 35

Z1 (12...24V)

Whit

Photoswitch
Series
10,000

Z1 (5V)
Blue
Z1 (RET)
B1 (12...24V)
B1 (5V)

10-30V DC
Not Used

B1 (RET)
A1 (12...24V)
Black
A1 (5V)

14 13
16 15

A1 (RET)
Not Used
Not Used

20 19
22 21

Jumper
12...24V

Not Used
Out 2

26 25

Out 3
COMMON 1
COMMON 1
COMMON 1
DC-1(+)

28 27

32 31
34 33

1756-HSC to Allen-Bradley 8723-wire DC Proximity Sensor

Allen-Bradley
Bulletin 872
3-wire DC
Proximity
Jumpers
Sensor

12...24V DC

12...24V DC
Return

Publication 1756-TD002A-EN-E - May 2009

Z0 (12...24V)

Z1 (12...24V)

Z0 (5V)
Z0 (RET)
B0 (12...24V)
B0 (5V)

10

Z1 (5V)
Z1 (RET)
B1 (12...24V)
B1 (5V)

B0 (RET)
Black
A0 (12...24V)
A0 (5V)
Blue
A0 (RET)
Not Used
Not Used

12 11
14 13
16 15
18 17
20 19
22 21

Not Used
Out 0
Out 1

24 23

COMMON 0
COMMON 0
COMMON 0

30 29

DC-0(+)

36 35

26 25
28 27

32 31
34 33

B1 (RET)
A1 (12...24V)
A1 (5V)
A1 (RET)
Not Used
Not Used
Not Used
Out 2
Out 3
COMMON 1
COMMON 1
COMMON 1
DC-1(+)

149

1756 ControlLogix I/O Modules

1756-HSC Technical Specifications


COUNTER
A B Z
0 0 0
O O
0 1

A B Z
1 1 1 O
K
O O
2 3

DC I/O

Attribute

1756-HSC

Number of counters

Inputs per counter

3 (A, B, Z for gate/reset)

Outputs

4 (2 points/group)

Operating voltage range

5V operation: 4.55.5V DC
12/24V operation: 1031.2V DC

Current draw at 5.1V

300 mA

Current draw at 24V

3 mA

Backplane power, total

1.9 W

Power dissipation, max

5.6 W @ 60C

Thermal dissipation, max

19.1 BTU/hr

Isolation voltage

125V (continuous), basic insulation type between input group to system


30V (continuous), basic insulation type between input group to input group
Routine tested at 1700V DC for 1 s, between input group to input group and
input group to system

Removable terminal block

1756-TBCH
1756-TBS6H

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B,


1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1)

Wire category

1(2)

Wire type

Copper

Enclosure type rating

None (open-style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-HSC Input Specifications

150

Attribute

Value

Number of counters

Inputs per counter

3 (A, B, Z for gate/reset)

Input frequency, max

1 MHz in counter modes (A input)


500 kHz in rate measurement mode (A input)
250 kHz in encoder mode (A/B inputs, X1 or X4)
70 Hz with filter enabled

Count range

016, 777, 214

Counting frequency, max

1000 kHz

Input current, min

4 mA

Input current, nom

15 mA

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-HSC Output Specifications


Attribute

Value

Outputs

4 (2 per common)

Output delay, off to on

20 s typical, 50 s max

Output delay, on to off

60 s typical, 300 s max

Off-state leakage current per


point, max

300 A

On-state voltage drop, max

0.55V

Output current rating, per point

20 mA @ 4.55.5V DC
1.0 A @ 1031.2V DC

Current limit

<9A

Surge current per point

2 A for 10 ms every 1s @ 60 C

Load current per point, min

5V operation: 3 mA
12/24V operation: 40 mA

Output control

Any number of output channels is assignable to each counter channel


Each output can have 2 "turn-on" and "turn-off" preset values

Short circuit protection

Electronic (Remove overload and toggle On/Off to restore.)

Reverse polarity protection

Yes (If wired incorrectly, module outputs may be permanently disabled.)

Certifications - 1756-HSC
Certification(1)

1756-HSC

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

ATEX

European Union 94/9/EC ATEX Directive, compliant with:


EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2)

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

151

1756 ControlLogix I/O Modules

1756-PLS
ControlLogix programmable limit switch module
1756-PLS Outputs - Right Side

1756-PLS Inputs - Left Side


2

OUTPUT 0
4

10

12

11

14

13

16

15

18

17

20

19

OUTPUT 1

INPUT 2

OUTPUT 3

INPUT 3

DC PWR 0...3

INPUT 6

OUTPUT 7

INPUT 7

10

12

11

14

13

16

15

18

17

20

19

INPUT 8
INPUT 9
INPUT 10

OUTPUT 11

INPUT 11

DC PWR 8...11

10...30V DC

DC COM 8...11

OUTPUT 12

INPUT 12

OUTPUT 13

INPUT 5

OUTPUT 6

OUTPUT 10

INPUT 4

OUTPUT 5

DC PWR 4...7

DC COM 0...3

OUTPUT 4

OUTPUT 9

INPUT 1

OUTPUT 2

OUTPUT 8

INPUT 0

INPUT 13
INPUT 14

OUTPUT 14
OUTPUT 15

INPUT 15

DC PWR 12...15

DC COM 4-...7

DC COM 12...15

+
_

1756-PLS Resolver

10

12

11

14

13

16

15

18

17

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Do Not Use

Allen-Bradley Resolver
846-SJDA1CG-R3-C

F (S3)
D (S1)
E (S2)
G (S4)

152

Do Not Use

Sine +

Do Not Use

Sine
Cosine +

Reference +
20

Cosine

19

Reference

A (R1)
B (R2)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-PLS


Indicator for Left
Slot I/O Module
PROG. LIMIT SWITCH

Indicator for Resolver Module

Indicator for Right


Slot I/O Module

PROG. LIMIT SWITCH

PROG. LIMIT SWITCH

OUT 0 1 2 3 4 5 6 7

O
K

O
IN 0 1 2 3 4 5 6 7 K

DC I/O

RESOLVER

OUT 8 9 10 11 12 13 14 15

O
IN 8 9 10 11 12 13 14 15 K

DC I/O

Attribute

1756-PLS

Module configuration

Left section: 2 groups of 4 outputs and 4 inputs each


Center section: resolver interface and I/O control
Right section: 2 groups of 4 outputs and 4 inputs each

Current draw at 5.1V

1000 mA

Current draw at 24V

125 mA

Power dissipation, max

25.7 W @ 30 C
21.3 W @ 60 C

Thermal dissipation, max

87.74 BTU/hr @ 30 C
72.72 BTU/hr @ 60 C

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to
system

Removable terminal block

Requires 3 RTBs: 1756-TBNH or 1756-TBSH

Slot width

Module location

Chassis-based, any slot

Chassis

1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17

Power supply, standard

1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B,


1756-PC75/B, 1756-PH75/B

Power supply, redundant

1756-PA75R, 1756-PB75R, 1756-PSCA2

Wire size

Center: Alpha Cable #6054C (use 3 of 4 twisted pairs)


Left and right: 2 mm2 (2214 AWG) stranded, 1.2 mm
(3/64 in.) insulation(1)

Wire category

2 - Center slot
1 - Left & right slots(2)

Wire type

Left and right: Copper

Enclosure type rating

None (open style)

(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level
installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

153

1756 ControlLogix I/O Modules

1756-PLS Resolver Specifications


Attribute

Value

Resolver location

Center section

Compatible resolver

Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options)

Resolver interface

2V rms, reference output (differential pair)


2V rms, sine and cosine inputs (2 differential pairs)

Reference voltage

2V rms 20%

Reference frequency

5 kHz 20%

Digital resolution

12 bits (4096 counts from hardware)

Angular resolution

0.088 /bit

Digital count range

04095 (decimal)

Maximum tracking rate

1800 RPM

Repeatability

0.0488% of full scale

Accuracy

0.0976% of full scale

Isolation voltage

100% tested at 1700V DC for 1 s

1756-PLS Input Specifications


Attribute

Value

Inputs

16 (2 groups of 4 per I/O section)

Voltage category

12/24V DC

Operating voltage range

10.831.2V DC

Input delay, off to on

< 15 s @ 30 C
< 150 s @ 60 C

Input delay, on to off

< 30 s @ 30 C
< 200 s @ 60 C

Power dissipation, inputs, max

2.8 W @ 60C

Thermal dissipation, inputs, max

9.56 BTU/hr

Off-state voltage, max

5V DC

Off-state current, max

1.5 mA

On-state current, min

3 mA

On-state current, max

10 mA

Input impedance, max

3.3 k @ 24V DC

Reverse polarity protection

Yes

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to system

1756-PLS Output Specifications

154

Attribute

Value

Outputs

16 (2 groups of 4 per I/O section)

Voltage category

12/24V DC

Operating voltage range

1031.2V DC

Output delay, off to on

< 15 s @ 60 C

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-PLS Output Specifications


Attribute

Value

Output delay, on to off

< 25 s @ 60 C

Power dissipation, outputs, max

6 W @ 30 C
3.8 W @ 60 C

Thermal dissipation, outputs, max

21.48 BTU/hr @ 30 C
11.93 BTU/hr @ 60 C

Off-state leakage current per


point, max

300 A @ 60 C

On-state voltage drop, max

0.55V DC

Current per point, max

1 A @ 30 C(1)

Current per module, max

8 A @ 30 C(2)

Current limit

< 4A

Surge current per point

2 A for 10 ms every 1s @ 60 C

Load current per point, min

40 mA

Output switching time

Switching 1 A @ 24V DC

Short circuit protection

Electronic (No indication of fault. Remove load and toggle on/off to


restore.)

Reverse polarity protection

Yes, current limited. (If wired incorrectly, outputs may be permanently


disabled.)

Isolation voltage

250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O to system

(1)

Derate 16.7 mA/ C above 30 C: 0.5 A @ 60 C.

(2)

Derate 133.6 mA/ C above 30 C: 4 A @ 60 C.

Certifications - 1756-PLS
Certification(1)

1756-PLS

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.


CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File
LR69960C.

CE

European Union 2004/108/IEC EMC Directive, compliant with:


EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:


AS/NZS CISPR 11; Industrial Emissions

(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

155

1756 ControlLogix I/O Modules

ControlLogix I/O
Accessories

1756 Removable Terminal Blocks


Removable terminal blocks (RTBs) provide a flexible interconnection between
your plant wiring and 1756 I/O modules. The RTB plugs into the front of the
I/O module. The type of module determines which RTB you need. You can
choose screw-clamp or spring-clamp RTBs.
RTBs are not shipped with I/O modules. You must order them separately. The
standard housing on the front of the wiring arm is not deep enough for 2.5
mm2 (14 AWG) wiring. If you plan to use 2.5 mm2 (14 AWG) wiring, also
order the extended housing.

Attribute

1756-TBNH

1756-TBSH

1756-TBCH

1756-TBS6H

1756-TBE

Description

20-position NEMA
screw-clamp removable
block

20-pin spring-clamp
removable terminal block
with standard housing

36-pin cage-clamp
removable terminal block
with standard housing

36-pin spring-clamp
removable terminal block
with standard housing

Extended depth terminal


block housing

Screw torque

0.81 Nm
79 lbin

Screwdriver width

8 mm (5/16 in.) max

0.4 Nm
4.4 lbin

Wiring Systems
As an alternative to buying RTBs and connecting the wires yourself, you can
buy a wiring system of:
interface modules (IFMs) that provide the output terminal blocks for
digital I/O modules. Use the pre-wired cables that match the I/O
module to the IFM.
analog interface modules (AIFMs) that provide the output terminal
blocks for analog I/O modules. Use the pre-wired cables that match the
I/O module to the AIFM.
I/O module-ready cables. One end of the cable assembly is an RTB that
plugs into the front of the I/O module. The other end has individually
color-coded conductors that connect to a standard terminal block.

156

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

PanelConnect Modules
A PanelConnect module and its sensor connection system connect sensors
directly to I/O modules by using convenient pre-built cables and connectors.
The PanelConnect module mounts on the enclosure and creates the correct
seal for the entry of the sensor connections. You do not need to seal the
opening where the sensor cables enter the enclosure, create custom
connectors, or wire to those custom connectors.

Publication 1756-TD002A-EN-E - May 2009

157

Rockwell Automation
Support

Rockwell Automation provides technical information on the Web to assist you in using
its products. At http://support.rockwellautomation.com, you can find technical
manuals, a knowledge base of FAQs, technical and application notes, sample code and
links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com.

Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States

1.440.646.3434
Monday Friday, 8am 5pm EST

Outside United
States

Please contact your local Rockwell Automation representative for any


technical support issues.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
United States

Contact your distributor. You must provide a Customer Support case


number (call the phone number above to obtain one) to your distributor
in order to complete the return process.

Outside United
States

Please contact your local Rockwell Automation representative for the


return procedure.

Allen-Bradley, Rockwell Automation, and ControlLogix are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1756-TD002A-EN-E - May 2009


Copyright 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like