SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the unit will automatically
lock the compressor out of operation. Manual reset will
be required to restart the compressor.
INSTALLATION
Step 1 Provide Unit Support
ROOF CURB Assemble and install accessory roof curb
or horizontal adapter roof curb in accordance with instructions shipped with the curb or horizontal adapter. Accessory
roof curb and horizontal adapter roof curb and information
required to field fabricate a roof curb or horizontal adapter
roof curb are shown in Fig. 1 and 2. Install insulation, cant
strips, roofing, and counter flashing as shown. Ductwork can
be secured to roof curb before unit is set in place.
IMPORTANT: The gasketing of the unit to the roof
curb or adapter roof curb is critical for a leak-proof
seal. Install gasket supplied with the roof curb or adapter
roof curb as shown in Fig. 1. Improperly applied gasket can result in air leaks and poor unit performance.
Curb or adapter roof curb should be level. This is necessary to permit unit drain to function properly. Unit leveling
tolerance is 6 116 in. per linear ft in any direction. Refer to
Accessory Roof Curb or Horizontal Adapter Roof Curb Installation Instructions for additional information as required.
ALTERNATE UNIT SUPPORT When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support area. If sleepers cannot be used, support long
sides of unit with a minimum of 3 equally spaced 4-in. x
4-in. pads on each side.
Step 2 Rig and Place Unit Inspect unit for transportation damage. File any claim with transportation agency.
Keep unit upright, and do not drop. Use spreader bars over
unit to prevent sling or cable damage. Rollers may be used
to move unit across a roof. Level by using unit frame as a
reference; leveling tolerance is 6 116 in. per linear ft in any
direction. See Fig. 3 for additional information. Unit weight
is shown in Table 1.
Four lifting holes are provided in ends of unit base rails
as shown in Fig. 3. Refer to rigging instructions on unit.
POSITIONING Provide clearance around and above unit
for airflow, safety, and service access (Fig. 4 and 5).
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
ROOF MOUNT Check building codes for weight distribution requirements.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111
Catalog No. 565-135
Printed in U.S.A.
Form 50TJ-14SI
Pg 1
10-98
Replaces: 50TJ-13SI
Tab 1b
PKG.
NO. REF.
50PQ900221
CURB
HEIGHT
18-29
(305)
50PQ900141
28-09
(610)
50PQ900151
28-09
(610)
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 129 thick neoprene coated 2 lb density.
3. Dimensions in ( ) are in millimeters.
DESCRIPTION
Standard Curb
149 High
Standard Curb
for Units
Requiring High
Installation
Side Supply
and Return Kit
for High Installation
4.
Direction of airflow.
UNIT
50TJ
A
DEG.
.28
B
IN.
.45
DEG.
.28
IN.
.43
UNIT
50TJ
016
020
024
028
DIMENSIONS
MAXIMUM
SHIPPING WEIGHT
lb
1550
1650
1700
1850
kg
703
748
771
839
A
ft-in.
6-1112
6-1112
6-1112
6-1112
B
mm
2121
2121
2121
2121
ft-in.
4- 0
3-10
3- 7
3- 5
mm
1219
1168
1092
1041
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Refer to Fig. 4 and 5 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner
post from packaging to protect coil from damage. Use bumper boards
for spreader bars.
5. Weights do not include optional economizer. See Fig. 4 and 5 for
economizer weight.
6. Weights given are for aluminum evaporator and condenser coil
plate fins.
UNIT
STD UNIT
WEIGHT
ECONOMIZER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
DIM A
DIM B
DIM C
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
ft-in.
mm
ft-in.
mm
ft-in.
mm
50TJ016
1550
703
110
50
391
177
365
166
384
174
410
186
3-5
1041
3-6
1067
1-10
559
50TJ020
1650
748
110
50
399
181
384
174
402
182
439
199
3-4
1016
3-6
1067
1- 8
508
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.
Center of Gravity.
4.
4
Fig. 4 Base Unit Dimensions, 50TJ016,020
Direction of airflow.
UNIT
STD UNIT
WEIGHT
Lb
ECONOMIZER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
110
50
419
190
394
179
425
193
463
110
50
428
194
412
187
511
232
499
Kg
DIM A
DIM B
ft-in.
mm
DIM C
ft-in.
mm
ft-in. mm
210
3-4
1016
3-5
1041
1-8
508
226
3-2
965
3-7
1092
1-8
508
NOTES:
1. Refer to print for roof curb accessory dimensions.
2. Dimensions in ( ) are in millimeters.
3.
Center of Gravity.
4.
5
Fig. 5 Base Unit Dimensions, 50TJ024,028
Direction of airflow.
016
208/230, 380, 460 v
15
1550
2...ZR94KC
2
81, 81
Low-Medium Static
High Static
020
575 v
024
18
20
1650
1700
Scroll, Copeland
1...ZR108KC,
1...ZR125KC,
1...ZR94KC
1...ZR108KC
2
2
106, 81
106, 106
R-22
TXV
028
25
1850
1...ZR16M3,
1...ZR125KC
2
136, 106
10-10
15-5
16-0
20-13
10-10
12-3
13-6
13- 0
Cross-Hatched 38-in. Copper Tubes, Aluminum Lanced,
Aluminum Pre-Coated, or Copper Plate Fins
2...17
3...15
3...15
4...15
21.7
21.7
21.7
21.7
Propeller Type
10,500
10,500
14,200
14,200
3...22
3...22
2...30
2...30
12...1050
12...1050
1...1075
1...1075
1100
1100
3400
3400
Cross-Hatched 38-in. Copper Tubes, Aluminum Lanced or
Copper Plate Fins, Face Split
2...17
3...15
3...15
4...15
17.5
17.5
17.5
17.5
Centrifugal Type
2...10 x 10
2...10 x 10 2...12 x 12
2...12 x 12
2...12 x 12
Belt
Belt
Belt
Belt
Belt
6000
6000
7200
8000
10,000
3.7
3.0
5
7.5
10
1725
1725
1745
1745
1740
8.7
[208/230,
575
v]
10.2
[208/230,
575 v]
4.25
3.45
5.90
9.5 [380, 460 v]
11.8 [460 v]
56H
56H
184T
213T
215T
891-1179
1159-1429
910-1095
1002-1225
1066-1283
1227-1550
1069-1287
1193-1458
1332-1550
Ball
Ball
Ball
Ball
Ball
1550
1550
1550
1550
1550
3.1/4.1
4.3/5.3
4.9/5.9
5.4/6.6
4.9/5.9
3.7/4.7
4.9/5.9
5.4/6.6
4.9/5.9
7 8
7 8
1 1 8
138
1 3 8
6.0
6.4
9.4
9.4
8.0
5.2
8.0
7.9
6.4
3
3
7
7
1 16
1 16
1 16
1 16
1716
1...BX...42
1...BX...45 1...BX...50
1...BX...53
2...BX...50
1...BX...42
1...BX...48
1...BX...50
2...BX...47
13.5-15.5
13.5-15.5
13.3-14.8
14.6-15.4
14.6-15.4
48
44
37
37
36
55
34
44
45
5
5
5
5
5
3.5
3.5
3.5
3.5
3.5
1035
1296
1002
1120
1182
1389
1178
1328
1470
1316
1316
1716
1716
1716
426
320
27
44
30 5
45 5
Cleanable
2...20 X 25 X 1
1...20 X 20 X 1
Throwaway**
4...20 x 20 x 2
4...16 x 20 x 2
12 Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
LEGEND
Bhp Brake Horsepower
TXV Thermostatic Expansion Valve
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and
Circuit 2 uses the upper portion of both coils.
The 50TJ028 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min
(such as American Air Filter no. 5700 or equivalent).
NOTE: The 50TJ016-028 units have a low-pressure switch (standard) located on the suction side.
1-3/8"
DRAIN HOLES
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG
insulated wire (35 C minimum). For over 75 ft, use no. 14
AWG insulated wire (35 C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the
thermostat.
Set heat anticipator settings as indicated in Table 3. Settings may be changed slightly to provide a greater degree of
comfort for a particular installation.
Refer to accessory remote control instructions as
required.
UNIT
50TJ
All
208/230,380
350 kcmil
VOLTAGE
460
2/0
575
2/0
LEGEND
EQUIP Equipment
GND
Ground
kcmil Thousand Circular
Mils
Maximum deviation is 7 v.
Determine the percentage of voltage imbalance:
7
Percentage of Voltage Imbalance = 100 x
457
= 1.53%
UNIT LOW-VOLTAGE CONNECTIONS
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
NOMINAL VOLTAGE
COMPRESSOR
OFM
IFM
VOLTAGE RANGE
No.
1
No. 2
(3 Ph,
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp
FLA
60 Hz)
208/230
187
253
28.8
195
28.8
195
0.5
1.7
380
342
418
15.0
123
15.0
123
0.5
1.7
460
414
508
14.7
95
14.7
95
0.5
0.8
575
518
633
10.8
80
10.8
80
0.5
0.75
208/230
187
253
30.1
225
28.8
195
0.5
1.7
460
414
508
15.5
114
14.7
95
0.5
0.8
575
518
633
12.1
80
10.8
80
0.5
0.75
208/230
187
253
37.8
239
30.1
225
6.6
380
342
418
21.2
145
16.7
140
3.9
460
414
508
17.2
125
15.5
114
3.3
575
518
633
12.4
80
12.1
80
3.4
016
(15 Tons)
020
(18 Tons)
024
(20 Tons)
POWER
EXHAUST
FLA
4.6
4.6
3.7 10.5/11.0
4.6
4.6
2.3
3.7
3.9
2.3
2.3
2.3
2.3
3.7
4.8
2.3
2.3
2.1
3.0
3.9
2.1
4.6
4.6
5.0 15.8/15.8
4.8
4.6
2.3
2.3
5.0
7.9
2.3
2.3
5.0
6.0
2.1
4.6
4.6
7.5 25.0/25.0
4.6
4.6
2.3
7.5
15.0
2.3
2.3
2.3
2.3
7.5
13.0
2.3
2.3
7.5
10.0
2.1
LRA
18.8
18.8
18.8
18.8
6.0
6.0
6.0
6.0
6.0
6.0
6.0
4.8
4.8
18.8
18.8
18.8
18.8
6.0
6.0
6.0
6.0
4.8
18.8
18.8
18.8
18.8
6.0
6.0
6.0
6.0
6.0
6.0
6.0
4.8
ELECTRIC
HEAT*
kW
26/34
26/34
42/56
42/56
56/75**
56/75**
20
20
35
35
32
32
55
55
80**
80**
50**
50**
26/34
26/34
42/56
42/56
56/75**
56/75**
32
32
55
55
80**
80**
26/34
26/34
42/56
42/56
56/75**
56/75**
20
20
35
35
32
32
55
55
80**
80**
FLA
71/82
71/82
117/135
117/135
156/180
156/180
30
30
52
52
39
39
66
66
96
96
48
48
71/82
71/82
117/135
117/135
156/180
156/180
39
39
66
66
96
96
71/82
71/82
117/135
117/135
156/180
156/180
30
30
52
52
39
39
66
66
96
96
POWER
SUPPLY
MCA
81/81
85/86
102/116
108/122
159/149
165/155
169/194
175/200
43
45
43
46
70
73
40
43
55
58
72
75
102
105
30
32
67
70
87/87
92/92
109/122
114/128
166/155
172/161
176/200
182/206
44
47
59
61
76
79
106
109
34
36
116/116
120/120
120/134
126/140
178/166
183/172
187/211
193/217
66
68
66
68
84
87
57
59
65
68
82
85
112
115
44
46
MOCP*
100/100
110/110
110/125
110/125
175/175
175/175
200/225
200/225
50
60
50
60
80
80
50
50
60
60
80
80
110
110
40
40
70
70
110/110
110/110
110/125
125/150
175/175
175/175
200/225
200/225
50
60
60
70
90
90
125
125
40
40
150/150
150/150
150/150
150/150
200/175
200/175
200/225
200/225
80
80
80
80
90
90
70
70
70
70
90
90
125
125
50
50
028
(25 Tons)
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
NOMINAL VOLTAGE
COMPRESSOR
OFM
VOLTAGE RANGE
No.
1
No. 2
(3 Ph,
Min Max RLA LRA RLA LRA Qty Hp FLA (ea)
60 Hz)
208/230
187
253
41.0
350
37.8
239
6.6
380
342
418
21.8
151
21.2
145
3.9
460
414
508
21.8
158
17.2
125
2.8
575
518
633
17.3
125
12.4
80
3.4
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Outdoor (Condenser) Fan Motor
Rated Load Amps
IFM
Hp
FLA
POWER
EXHAUST
FLA
4.6
4.6
10.0 28.0/28.0
4.6
4.6
2.3
10.0
17.0
2.3
2.3
2.3
2.3
10.0
14.6
2.3
2.3
10.0
13.0
2.1
LRA
18.8
18.8
18.8
18.8
6.0
6.0
6.0
6.0
6.0
6.0
6.0
4.8
ELECTRIC
HEAT*
kW
26/34
26/34
42/56
42/56
56/75**
56/75**
20
20
35
35
32
32
55
55
80**
80**
FLA
71/82
71/82
117/135
117/135
156/180
156/180
30
30
52
52
39
39
66
66
96
96
POWER
SUPPLY
MCA
130/130
135/135
130/138
135/143
181/170
187/176
191/215
197/221
73
76
73
76
87
90
66
68
67
70
84
87
114
117
54
56
MOCP
150/150
175/175
150/150
175/175
200/175
200/200
200/225
200/225
90
90
90
90
90
90
80
80
80
80
90
100
125
125
70
70
= 457
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance =
max voltage deviation from average voltage
100 x
average voltage
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
10
UNIT
50TJ
UNIT
VOLTAGES
208/230-3-60
016-028
380-3-60
460-3-60
OPTIONAL ECONOMIZER
Economizer Motor Control Module (Fig. 14-16) Set to
the D setting (Fig. 15). The control module is located on
the economizer motor. See Fig. 14 and 16.
Damper Vent Position Setting
1. Set fan switch at ON position (continuous fan operation)
and close night switch if used.
2. Set system selector switch to OFF position.
3. Turn adjustment screw slowly until dampers assume desired vent position. Do not manually operate economizer
motor since damage to motor will result.
575-3-60
kW*
STAGE 1
STAGE 2
26/34
42/56
56/75
20
35
32
55
80
50
.40
.66
.66
.40
.40
.40
.40
.66
.66
.66
.40
.66
.40
.66
.40
.66
.66
.66
LEGEND
LED Light-Emitting Diode
11
12
LOWER FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD SIDE
PANELS (2)
HOOD TOP
PANEL
BAFFLE
(028 ONLY)
LOWER
FILTER
RETAINER
FILTER SUPPORT
BRACKET
HOOD DRAIN PAN
UPPER FILTER RETAINER
ENTHALPY SENSOR
13
POINT
CONTROL CONTROL
(approx Deg)
CURVE
AT 50% RH
A
73
B
68
C
63
D
58
LEGEND
RH Relative Humidity
SENSOR
LOCATION
SENSOR
LOCATION
HAIRPIN END
50TJ016
HAIRPIN END
50TJ020
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
NOTE: Dimensions in (
) are in mm.
14
discharge line, and one on the liquid line. In addition Schradertype valves are located underneath the low-pressure switches.
Be sure that caps on the ports are tight.
SENSOR
LOCATION
SENSOR
LOCATION
HAIRPIN END
50TJ024
HAIRPIN END
50TJ028
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
START-UP
Use the following information and Start-Up Checklist on
page CL-1 to check out unit PRIOR to start-up.
UNIT
50TJ
016
020
024
028
MINIMUM CFM
MAXIMUM CFM
4500
5400
6000
7000
7,500
9,000
10,000
11,250
Compressor Mounting Compressors are internally spring mounted. Do not loosen or remove compressor
holddown bolts.
Refrigerant Service Ports Each refrigerant system has a total of 3 Schrader-type service gage ports. One
port is located on the suction line, one on the compressor
15
Rpm
684
715
747
779
812
845
878
912
946
981
1016
0.2
Bhp
1.28
1.47
1.67
1.90
2.14
2.40
2.68
2.98
3.29
3.63
3.99
Watts
1102
1265
1442
1635
1844
2068
2309
2566
2841
3133
3443
Rpm
791
817
844
872
901
931
961
992
1023
1055
1087
0.4
Bhp
1.49
1.68
1.89
2.12
2.37
2.64
2.92
3.22
3.55
3.89
4.25
Rpm
1285
1297
1311
1326
1342
1359
Watts
1283
1451
1633
1831
2044
2273
2518
2780
3059
3355
3669
(in. wg)
Watts
1652
1828
2019
2226
2448
2685
2939
3209
3496
Rpm
1061
1078
1097
1117
1138
1160
1183
1207
1232
1.0
Bhp
2.13
2.34
2.57
2.81
3.07
3.35
3.65
3.97
4.31
Watts
1841
2021
2216
2426
2652
2893
3151
3425
3716
Rpm
1139
1155
1171
1189
1209
1229
1250
1273
1.2
Bhp
2.36
2.57
2.80
3.05
3.31
3.60
3.90
4.22
Watts
2034
2217
2416
2629
2858
3103
3365
3642
Rpm
1214
1228
1243
1259
1277
1295
1315
1.4
Bhp
2.59
2.80
3.04
3.29
3.56
3.84
4.15
Watts
2230
2417
2618
2835
3067
3316
3580
LEGEND
Bhp Brake Horsepower
FIOP Factory-Installed Option
Watts Input Watts to Motor
*Standard low-medium static drive range is 891 to 1179 rpm (for 208/
230-460 v units) or 1159 to 1429 rpm (for 575-v units). Alternate highstatic drive range is 1227 to 1550 (for 208/230-460 v units). The alternate high-static drive is not available for 50TJ016 575-v units. Other
rpms require a field-supplied drive.
wg)
1.9
Bhp
3.17
3.40
3.64
3.90
4.17
Watts
2736
2928
3136
3360
3600
Rpm
1418
1428
1439
1452
1466
2.0
Bhp
3.29
3.52
3.76
4.02
4.30
Watts
2839
3033
3242
3467
3708
2. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 8 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the
full horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Carrier representative for details.
NOTES:
1. Maximum continuous bhp is 4.25 (208/230-460 v) or 3.45 (575 v)
and the maximum continuous watts are 3775 (208/230-460 v) or
3065 (575 v). Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
16
Rpm
682
730
778
828
878
928
979
1030
1082
1134
0.2
Bhp
1.99
2.38
2.82
3.31
3.84
4.42
5.05
5.73
6.46
7.25
Watts
1675
2005
2373
2780
3227
3715
4245
4817
5433
6093
Rpm
760
802
846
892
938
985
1033
1082
1131
1180
0.4
Bhp
2.29
2.68
3.13
3.62
4.15
4.74
5.38
6.06
6.80
7.59
Watts
1922
2257
2630
3042
3494
3986
4521
5098
5718
6382
(in. wg)
Watts
2441
2783
3164
3583
4043
4544
5086
5671
6299
6971
Rpm
965
997
1031
1067
1105
1144
1185
1227
1270
1313
1.0
Bhp
3.22
3.63
4.09
4.59
5.14
5.74
6.39
7.09
7.84
8.65
Watts
2712
3057
3440
3863
4326
4830
5375
5964
6595
7271
Rpm
1027
1056
1087
1121
1156
1194
1232
1272
1313
1356
1.2
Bhp
3.56
3.97
4.43
4.93
5.49
6.09
6.74
7.44
8.20
9.01
Watts
2990
3337
3722
4148
4613
5120
5669
6260
6895
7574
Rpm
1086
1112
1142
1173
1207
1242
1279
1317
1356
1397
1.4
Bhp
3.89
4.31
4.77
5.28
5.83
6.44
7.10
7.80
8.56
9.37
Watts
3275
3623
4010
4438
4906
5415
5966
6561
7198
7881
Rpm
1142
1167
1194
1224
1255
1289
1324
1360
1398
1438
Available
1.6
Bhp Watts
4.24 3567
4.66 3915
5.12 4304
5.63 4733
6.19 5203
6.80 5714
7.45 6268
8.16 6865
8.93 7505
9.74 8190
External Static
1.8
Rpm Bhp
1197
4.59
1219
5.01
1245
5.47
1273
5.98
1302
6.55
1334
7.16
1368
7.82
1403
8.53
1440
9.29
1477 10.11
LEGEND
Bhp Brake Horsepower
FIOP Factory-Installed Option
Watts Input Watts to Motor
Standard low-medium static drive range for the 020 size is 910 to
1095 rpm. Standard low-medium static drive range for the 024 size
is 1002 to 1225 rpm. Alternate high-static drive range for the 020 size
is 1069 to 1287. Alternate high-static drive range for the 024 size is
1193 to 1458 rpm. Other rpms require a field-supplied drive.
2.
3.
4.
5.
NOTES:
1. Maximum continuous bhp for the 020 size is 5.90. Maximum continuous bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (380,
460 v). The maximum continuous watts for the 020 size is 5180.
The maximum continuous watts for the 024 size is 7915 (208/230,
575 v) or 8640 (380, 460 v). Do not adjust motor rpm such that
6.
17
Watts
4015
4364
4754
5184
5657
6171
6728
7328
7972
Rpm
1249
1270
1294
1320
1348
1379
1411
1445
1480
2.0
Bhp
4.96
5.37
5.83
6.35
6.91
7.52
8.18
8.90
9.67
Watts
4167
4516
4906
5337
5810
6325
6883
7484
8129
Rpm
845
896
948
1001
1053
1106
1159
1213
1266
1293
Watts
5191
5703
6263
6873
7534
8247
9014
9835
LEGEND
Bhp Brake Horsepower
FIOP Factory-Installed Option
Watts Input Watts to Motor
*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-static drive range is 1332 to 1550. Other rpms require a
field-supplied drive.
2. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 9 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the
full horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Carrier representative for details.
NOTES:
1. Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (380,
460 v) and the maximum continuous watts are 9510 (208/230,
575 v) or 11,000 (380, 460 v). Do not adjust motor rpm such that
motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
18
4500
0.04
0.22
5000
0.05
0.26
CFM
6000
0.07
0.35
7200
0.09
0.44
7500
0.10
0.46
0.06
0.06
0.06
0.07
0.07
0.09
0.07
0.09
0.09
0.07
0.07
0.07
0.08
0.08
0.10
0.08
0.10
0.10
0.09
0.09
0.09
0.12
0.12
0.15
0.12
0.15
0.15
0.11
0.11
0.11
0.15
0.16
0.20
0.15
0.20
0.20
0.12
0.12
0.12
0.17
0.17
0.21
0.17
0.21
0.21
LEGEND
FIOP Factory-Installed Option
NOTES:
1. The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance tables to determine blower
rpm and watts.
2. Heaters are rated at 240 v, 480 v, and 600 v.
COMPONENT
Economizer
Glycol Coil
Electric Heat (kW)
26/34
32
42/56
55
56/75
80
5400
0.06
0.30
6000
0.07
0.35
7200
0.09
0.44
9000
0.11
0.58
10,000
0.12
0.66
11,250
0.14
0.77
0.08
0.08
0.11
0.11
0.14
0.14
0.09
0.09
0.12
0.12
0.15
0.15
0.11
0.11
0.15
0.15
0.20
0.20
0.15
0.15
0.19
0.19
0.24
0.24
0.17
0.17
0.21
0.21
0.26
0.26
0.20
0.20
0.24
0.24
0.29
0.29
LEGEND
FIOP Factory-Installed Option
NOTES:
1. The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance tables to determine blower
rpm and watts.
2, Heaters are rated at 240 v and 480 v. There are no 575-v heaters.
12
1
1179
1559
1429
1095
1287
1225
1458
1283
112
1150
1522
1403
1077
1265
1209
1434
1269
2
1121
1488
1376
1058
1243
1187
1407
1247
1551
19
412
978
1323
1242
965
1134
1076
1275
1138
1415
5
949
1289
1215
947
1112
1053
1248
1116
1388
512
920
1256
1188
928
1091
1031
1222
1095
1361
6
891
1227
1159
910
1069
1002
1193
1066
1332
HEATING, UNITS WITHOUT ECONOMIZER (If Accessory or Optional Heater is Installed) Upon a call for heating through terminal W1, IFC and heater contactor no. 1 (HC1)
are energized. On units equipped for 2 stages of heat, when
additional heat is needed, HC2 is energized through W2.
COOLING, UNITS WITH ECONOMIZER Upon a call
for cooling, when outdoor ambient temperature is above the
outdoor-air temperature control setting, the evaporator and
condenser fans and compressor energize. The economizer
damper moves to VENT position.
Upon a first-stage call for cooling, when outdoor ambient
temperature is below the temperature control setting, the evaporator fan starts and economizer damper modulates to maintain mixed-air temperature. The compressor(s) remains off.
Upon a second-stage call for cooling, compressor no. 1 is
energized and mechanical cooling is integrated with economizer cooling. Compressor no. 2 is locked out. If the outdoorair temperature is below 50 F, a cooling lockout switch prevents the compressor(s) from running.
When supply-air temperature drops below a fixed set point,
the economizer damper modulates to maintain the temperature at the fixed set point.
Lubrication
COMPRESSORS Each compressor is charged with the
correct amount of oil at the factory. Conventional white oil
(Sontext 200LT) is used. White oil is compatible with 3GS
oil, and 3GS oil may be used if the addition of oil is required. See compressor nameplate for original oil charge. A
complete recharge should be four ounces less than the original oil charge. When a compressor is exchanged in the field
it is possible that a major portion of the oil from the replaced
compressor may still be in the system. While this will not
affect the reliability of the replacement compressor, the extra oil will add rotor drag and increase power usage. To remove this excess oil, an access valve may be added to the
lower portion of the suction line at the inlet of the compressor. The compressor should then be run for 10 minutes, shut
down, and the access valve opened until no oil flows. This
should be repeated twice to make sure the proper oil level
has been achieved.
FAN SHAFT BEARINGS For size 016 units, bearings
are permanently lubricated. No field lubrication is required.
For size 020-028 units, the bearings are of the pillow block
type and have grease fittings. The bearing opposite the motor end has an extended tube line so it can be lubricated from
the motor side. Lubricate the bearings twice annually.
FREEZE PROTECTION THERMOSTAT(S) A freeze protection thermostat (FPT) is located on the top and bottom of
the evaporator coil. It detects frost build-up and turns off the
compressor, allowing the coil to clear. Once frost has melted,
the compressor can be reenergized by resetting the compressor lockout.
HEATING, UNITS WITH ECONOMIZER (If Accessory
or Optional Heater is Installed) The outdoor air damper
stays at VENT position while the evaporator fan is operating. Upon a call for heating through terminal W1, the indoor
(evaporator) fan contactor (IFC) and heater contactor no. 1
(HC1) are energized. On units equipped for 2 stages of heat,
when additional heat is needed, HC2 is energized through
W2.
SERVICE
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Turn off accessory heater power switch if applicable. Electrical shock
could cause personal injury.
LUBRICANT
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS The condenser and evaporator-fan motors have
permanently-sealed bearings, so no field lubrication is
necessary.
Cleaning Inspect unit interior at beginning of each heating and cooling season and as operating conditions require.
Remove unit top panel and/or side panels for access to unit
interior.
20
21
Condenser-Fan Adjustment
50TJ016,020 UNITS (Fig. 28)
1. Shut off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed across
the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
50TJ024,028 UNITS (Fig. 29)
1. Shut off unit power supply.
2. Remove fan top-grille assembly and loosen fan hub screws.
3. Adjust fan height on unit, using a straightedge placed across
the fan orifice.
4. Tighten setscrews and replace rubber hubcap to prevent
hub from rusting to motor shaft.
5. Fill hub recess with permagum if rubber hubcap is
missing.
NOTE: A 312-in. bolt and threaded plate are included in the installers
packet. They should be added to the motor support channel below
the motor mounting plate to aid in raising the motor. The plate part
number is 50DP503842. The adjustment bolt is 38 - 16 x 134-in. LG.
22
RESULTS
RESULTS
RESULTS
BOTH CIRCUITS
ALL OUTDOOR FANS MUST BE OPERATING
5. Set the outdoor-air thermostat (OAT) located in the economizer section of the unit (see Fig. 14) to 75 F.
6. If the outdoor temperature is below 75 F, the economizer will control the mixed air with the mixed-air sensor. If the outdoor air is above 75 F, place a jumper around
the contacts of the OAT.
7. Jumper terminal T to terminal T1 on the module (see
Fig. 15). The economizer will go to the full open position. The outdoor-air damper will go to the full open
position, and the return-air damper will go to the full
closed position.
8. Adjust mechanical linkage, if necessary, for correct positioning. It may be necessary to remove the filters to
adjust the linkage.
140
120
ADD CHARGE IF ABOVE CURVE
100
80
40
50
150
100
200
250
350
300
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
400
Protective Devices
COMPRESSOR PROTECTION
Overtemperature Each compressor has an internal protector to protect it against excessively high discharge gas
temperatures.
Overcurrent Each compressor has internal line break motor protection, except the circuit no. 1 on the 50TJ028 unit.
Compressor no. 1 on the 50TJ028 unit uses an electronic
module located with the compressor junction box, to provide motor protection. This electronic module monitors winding and discharge temperatures. If these temperatures reach
the trip values, the module interrupts the control line and
causes the compressor to switch off.
Crankcase Heater Only the 50TJ028 unit is equipped with
a 70-watt crankcase heater to prevent absorption of liquid
refrigerant by oil in the crankcase when the compressor is
idle. The crankcase heater is energized whenever there is a
main power to the unit and the compressor is not energized.
Relief Devices All units have relief devices to protect against damage from excessive pressures (e.g., fire). These
devices protect the high and low side.
IMPORTANT: After prolonged shutdown or servicing, energize the crankcase heaters for 24 hours before
starting the compressors.
Control Circuit, 24-V This control circuit is protected against overcurrent by a 3.2-amp circuit breaker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.
24
IFC
IFCB
IFM
IFR
L
LOR
LPS
LS
MAT
OAT
OFC
OFM
OP
PL
PRI
QT
SR
SW
TB
TC
Indoor-Fan Contactor
Indoor-Fan Circuit Breaker
Indoor-Fan Motor
Indoor-Fan Relay
Light
Lockout Relay
Low-Pressure Switch
Limit Switch
Mixed-Air Thermostat
Outdoor-Air Thermostat
Outdoor-Fan Contactor
Outdoor-Fan Motor
Overcurrent Protector
Plug Assembly
Primary
Quadruple Terminal
Solenoid Relay
Switch
Terminal Block
Thermostat Cooling
TH
Thermostat Heating
TRAN Transformer
Terminal (Marked)
NOTES:
1. Compressor and fan motors thermally protected; 3-phase motors protected against
primary single-phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with
type 90 C wire or its equivalent.
3. Jumpers are omitted when unit is equipped with economizer.
4. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices.
5. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally-closed contact. A plain (no line) number signifies a normallyopen contact.
26
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
Field Wiring
To Indicate Common
Potential Only, Not
To Represent Wiring
Option/Accessory Wiring
27
TROUBLESHOOTING
Refer to Table 13 for troubleshooting details.
Table 13 Cooling Service Analysis
PROBLEM
Compressor and
condenser fan
will not start.
Compressor cycles
(other than normally
satisfying thermostat).
Compressor operates
continuously.
CAUSE
Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer, or control
relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in compressor circuit.
Compressor motor burned out, seized, or internal
overload open.
Defective overload.
Compressor locked out.
One leg of 3-phase power dead.
Refrigerant overcharge or undercharge.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective overload.
Defective thermostat.
Faulty condenser-fan motor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Air in system.
Condenser coil dirty or restricted.
Dirty air filter.
Dirty condenser coil.
Refrigerant overcharged.
Faulty TXV.
Air in system.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Restriction in liquid tube.
High heat load.
Faulty TXV.
Refrigerant overcharged.
Dirty air filter.
Low refrigerant charge.
Metering device or low side restricted.
Faulty TXV.
Insufficient evaporator airflow.
Compressor no. 2
will not run.
28
REMEDY
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Determine cause for safety trip and reset lockout.
Replace fuse or reset circuit breaker.
Determine cause.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace filter.
Clean coil.
Recover excess refrigerant.
1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks, repair, and recharge.
Remove restriction.
Check for source and eliminate.
1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Recover excess refrigerant.
Replace filter.
Check for leaks, repair, and recharge.
Remove source of restriction.
1. Check TXV bulb mounting and secure tightly to
suction line.
2. Replace TXV if stuck open or closed.
Increase air quantity. Check filter and replace if
necessary.
Reset thermostat.
Replace.
Proper operation; no remedy necessary.
MODEL NO.:
SERIAL NO.:
DATE:
TECHNICIAN:
PRE-START-UP:
M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
M VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJUSTMENT BOLT (016 UNITS) OR ADJUSTMENT
BOLT AND PLATE (020-028 UNITS)
M OPEN ALL SERVICE VALVES (SUCTION, DISCHARGE, AND LIQUID)
M VERIFY INSTALLATION OF ECONOMIZER HOOD
M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
M VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
M CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE
M VERIFY THAT UNIT IS LEVEL
M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW
IS TIGHT
M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
M VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
START-UP:
ELECTRICAL
SUPPLY VOLTAGE
L1-L2
L2-L3
L3-L1
L1
L2
L3
L1
L2
L3
L1
L2
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
DB (Dry-Bulb)
RETURN-AIR TEMPERATURE
DB
L3
WB (Wet-Bulb)
PRESSURES
REFRIGERANT SUCTION
CIRCUIT NO. 1
PSIG
PSIG
REFRIGERANT DISCHARGE
CIRCUIT NO. 1
PSIG
PSIG
START-UP CHECKLIST