You are on page 1of 25

The content of this document remains the full property of Larsen & Toubro.

The document may neither be reproduced nor communicated to third party in any form, nor used for own purpose, particularly for the execution of what is herein represented, without the written authorisation of Larsen & Toubro.

DRAWING ISSUED FOR


APPROVAL
REFERENCE/INFORMATION
CONSTRUCTION
DISTRIBUTION

04.04.2016

Rev.

Date

First Submission.
JS
Prepared

PCP
Checked

PCP
Approved

Remarks/Reasons for Revision

CLIENT :

HINDUSTAN ZINC LIMITED

CONSULTANT:

DEVELOPMENT CONSULTANTS PVT. LTD.

TITLE :

SHORT CIRCUIT CALCULATION

PLANT : 1.5 MTPA LEAD-ZINC BENEFICIATION PLANT


AT S.K.MINES, RAJASTHAN
L&T DOC. No.
DRA DOC. No.

Sheet (A4) :

Rev. No. 0

Larsen & Toubro Limited

PROJECT: S.K.Mines(Mill) Dariba


CUSTOMER: : HINDUSTAN ZINC LIMITED

Short Circuit Calculation Report


The short circuit calculation report is generated with ETAP 11.1.1 version.
Short circuit calculation is worked out considering the following conditions:
1. We have considered 1000MVA as source fault level of grid as IS 2026-I,1977
2. Cables are not considered, however this will reduce further SC level.
3. Lumped load at 0.415kV bus is derived from Latest load list.
4. SC calculations are done in accordance with IEC 60909
Detailed short circuit calculation result for each bus is indicated as below:

Sr. No.
1
2

Bus levels
6.6kV, {with 33 kV I/C-2 open &6.6kV
Bus coupler closed}
6.6kv {with 33kV I/C -2 Closed & 6.6kV
bus coupler open}

L&T Document No.:


PREPARED BY
NAME
: JS
DATE
: 04.04. 2016

Rated Fault level


(RMS)
40
40

Type of Fault
Symmetrical 3
phase
Symmetrical 3
phase

Rev. No. 0
REVIEWED BY
NAME
: PCP
DATE
: 04.04.2016

Attained
Fault Level
as per
calculation
23.16 KA
20.9 KA

One-Line Diagram - OLV1 (Short-Circuit Analysis)


U4
1000 MVAsc

U3
1000 MVAsc

Case-1
33kV I/C-2 open , with 6.6kV bus coupler closed

333.19
kV

30.2
8 kV
26.9

Open

33 kV

3.19

Open
T10
20 MVA

6.6 kV
0.512

T14
20 MVA

15.96
0.512

0.512

0.327

2.31
0.601

float air blower -1

750 kW

2.25

0
0 kV

6.6 kV

23.1
6 kA
-83.
5

0.303

0.36

0.36

0.512

0.162

2850 kW

regrind mill
375 kW

Secondary cone crusher

TR#4
2 MVA

Float air blower-2


750 kW

TR#7
2 MVA

TR#2
2 MVA
TR#3

TR#8
2 MVA

TR#6
2 MVA

TR#5
2 MVA

BusDuct15

2 MVA

2 MVA

0.327

ball mill

200 kW

TR#1

0.601

BusDuct12

BusDuct11

BusDuct14

BusDuct10
BusDuct7

1.8
kV 4
0.05

BusDuct8

2.74
5.48
2.74
0.433 kV
0.433 kV

7.8

BusDuct9

5.48
0.433 kV

Open

7.8

2.74 kV
0.433

1.2
kV 4
7
0
.
0

page 1

1.8
kV 4
0.05

0.433 kV
1.8
kV 4
0.05

2.74

Open

7.8
7.8

1.2
kV 4
0.07

2.74

1.8
kV 4
0.05

2.74

0.433 kV
1.8
kV 4
5
0
.
0

0.433 kV

PMCC-1
MAIN PROCESS-EPR

Open

1.8
kV 4
5
0
.
0

2.74

7.8
0.433 kV Open

7.8
Lump1
1.5 MVA

Lump2
0.5 MVA

Lump3
0.5 MVA

PMCC-2

Lump4
1.5 MVA

0.433 kV

MAIN PROCESS -ECR

1.2
kV 4
1.2
7
0
.
0
kV 4
0.07

2.74

Open
0.433 kV 4.99
4.99

7.8
7.8

2
kV 4
0.040.433 kV

4.99
4.99

0.433 kV
PMCC-3
SER/TER HOUSE

Lump5
1.5 MVA

11:29:47

Apr 05, 2016

Project File: SK Mines HZL

Lump6
0.5 MVA

Lump7
0.5 MVA

Lump8
1.5 MVA

Lump9
900 kVA

Lump10
900 kVA

2
kV 4
0.04

One-Line Diagram - OLV1 (Short-Circuit Analysis)


U4
1000 MVAsc

U3
1000 MVAsc

Case-2
33kV I/C-2closed

333.19
kV

30.2
8 kV
26.9

, with 6.6kV bus coupler open

Open

33 kV

3.19

T10
20 MVA

T14
20 MVA

Open
6.6 kV
0.512

0
0 kV

15.96
0.512

0.512

0.327

0.601

float air blower -1

750 kW

2.25

6.6 kV

20.9
kA 84.7

0.303

ball mill

2850 kW

regrind mill
375 kW

Secondary cone crusher

200 kW

TR#4
2 MVA
TR#1

TR#7
2 MVA

TR#2
2 MVA
TR#3

BusDuct15

2 MVA

2 MVA

TR#8
2 MVA

TR#6
2 MVA

TR#5
2 MVA

BusDuct12

BusDuct11

BusDuct14

BusDuct10
BusDuct7

BusDuct8

BusDuct9

0.433 kV
0.433 kV

7.8

0.433 kV
Open

7.8

0.433 kV

1.2
kV 4
7
0
.
0

page 1

0.433 kV

Open

7.8
7.8

1.2
kV 4
0.07

0.433 kV
0.433 kV

PMCC-1
MAIN PROCESS-EPR

Open
Open

7.8

Lump2
0.5 MVA

Lump3
0.5 MVA

PMCC-2

Lump4
1.5 MVA

0.433 kV

0.433 kV 4.99
4.99

0.433 kV Open

7.8
Lump1
1.5 MVA

1.2
kV 4
7
0
.
0

2
kV 4
0.040.433 kV

0.433 kV

MAIN PROCESS -ECR


PMCC-3
SER/TER HOUSE

Lump5
1.5 MVA

11:40:44

Apr 05, 2016

Project File: SK Mines HZL

Float air blower-2


750 kW

Lump6
0.5 MVA

Lump7
0.5 MVA

Lump8
1.5 MVA

Lump9
900 kVA

Lump10
900 kVA

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents

Swing

V-Control

Load

Total

15

17

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

10

15

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

Number of Machines:

10

17

System Frequency:

50.00 Hz

Unit System:

English

Project Filename:

SK Mines HZL

Output Filename:

C:\ETAP 1111\SK Mines HZL\Untitled.SI2

Number of Buses:

Number of Branches:

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Percent

Apply

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Global

20

Cable Resistance:

Yes

Global

20

Temperature Correction

Degree C

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Bus Input Data

Bus
ID
Bus20

Type

Initial Voltage
Nom. kV

SWNG

Bus22

Load

Bus24

SWNG

Bus25

33.000

Base kV

Sub-sys

%Mag.

Ang.

33.000

100.00

0.00
-30.00

6.600

6.600

100.00

33.000

33.000

100.00

0.00

Load

6.600

6.600

100.00

-30.00

Bus26

Load

0.433

0.433

100.00

0.00

Bus27

Load

0.433

0.433

100.00

0.00

Bus28

Load

0.433

0.433

100.00

0.00

Bus29

Load

0.433

0.433

100.00

0.00

Bus30

Load

0.433

0.433

100.00

0.00

Bus31

Load

0.433

0.433

100.00

0.00

Bus32

Load

0.433

0.433

100.00

0.00

Bus33

Load

0.433

0.433

100.00

0.00

Bus34

Load

0.433

0.433

100.00

0.00

Bus35

Load

0.433

0.433

100.00

0.00

Bus36

Load

0.433

0.433

100.00

0.00

Bus37

Load

0.433

0.433

100.00

0.00

T14~

Load

6.600

6.600

100.00

0.00

17 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID
T10

Rating
MVA

Prim. kV

Sec. kV

Z Variation
%Z

X/R

% Tap Setting

+ 5%

- 5%

% Tol.

Prim.

Sec.

Phase Shift

Adjusted
%Z

Type

Angle

20.000

33.000

6.600

10.00

20.00

10.0000

Dyn

30.000

TR#1

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#2

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#3

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#4

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#5

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#6

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#7

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#8

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

20.000

33.000

6.600

10.00

20.00

10.0000

Dyn

-30.000

T14

2-Winding Transformer Grounding Input Data


Grounding
Transformer
ID
T10

Rating
MVA

Prim. kV

Conn.
Sec. kV

Type

Primary
Type

kV

Secondary
Amp

Ohm

Type

kV

Amp

Ohm

20.000

33.000

6.600

D/Y

Solid

TR#1

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#2

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#3

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#4

2.000

6.600

0.433

D/Y

Resistor

TR#5

2.000

6.600

0.433

D/Y

Resistor

TR#6

2.000

6.600

0.433

D/Y

Resistor

75.00000

TR#7

2.000

6.600

0.433

D/Y

Resistor

75.00000

2.000

6.600

0.433

D/Y

Resistor

20.000

33.000

6.600

D/Y

Solid

TR#8
T14

75.00000
3.3

3.3

75.00000

75.00000

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch
ID

Connected Bus ID
Type

From Bus

% Impedance, Pos. Seq., 100 MVAb


To Bus

T10

2W XFMR

Bus20

Bus22

2.46

49.23

49.30

TR#1

2W XFMR

Bus22

Bus26

49.42

296.51

300.60

TR#2

2W XFMR

Bus25

Bus30

49.42

296.51

300.60

TR#3

2W XFMR

Bus22

Bus28

49.42

296.51

300.60

TR#4

2W XFMR

Bus22

Bus31

49.42

296.51

300.60

TR#5

2W XFMR

Bus25

Bus32

49.42

296.51

300.60

TR#6

2W XFMR

Bus25

Bus34

49.42

296.51

300.60

TR#7

2W XFMR

Bus22

Bus36

49.42

296.51

300.60

TR#8

2W XFMR

Bus25

Bus37

49.42

296.51

300.60

T14

2W XFMR

T14~

Bus25

61.54

1230.86

1232.40

CB66

Tie Breakr

Bus30

Bus27

CB69

Tie Breakr

Bus30

Bus29

CB71

Tie Breakr

Bus32

Bus33

CB73

Tie Breakr

Bus32

Bus35

CB82

Tie Breakr

Bus22

Bus25

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Power Grid Input Data

Power Grid

Connected Bus

ID

ID

% Impedance
100 MVA Base

Rating
MVASC

kV

X"

Grounding
R/X"

Type

U3

Bus20

1000.000

33.000

0.71247

9.97459

0.07

Wye - Solid

U4

Bus24

1000.000

33.000

0.71247

9.97459

0.07

Wye - Solid

Total Connected Power Grids ( = 2 ): 2000.000 MVA

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Induction Machine Input Data

Induction Machine
ID

Connected Bus
Type

Qty

PosSeqImp (Mtr Base)

Rating

ID

HP/kW

kVA

kV

Amp

PF

%R

% X"

float air blower -1

Motor

Bus22

750.00

867.66

6.600

75.90

92.37

2.16

13.72

ball mill

Motor

Bus22

2850.00

3253.59

6.600

284.61

92.92

1.49

regrind mill

Motor

Bus22

375.00

436.83

6.600

38.21

92.09

2.62

R/X"

Grounding
Conn.

Type

mFact.
Amp

MW/PP

0.16

Wye

Open

0.38

13.81

0.11

Wye

Open

1.43

13.64

0.19

Wye

Open

0.19

Float air blower-2

Motor

Bus25

750.00

867.66

6.600

75.90

92.37

2.16

13.72

0.16

Wye

Open

0.38

Secondary cone crusher

Motor

Bus25

200.00

234.44

6.600

20.51

91.83

3.12

13.53

0.23

Wye

Open

0.10

Total Connected Induction Machines ( = 5 ): 5660.2 kVA

Lumped Load Input Data


Motor Loads
Lumped Load
Rating

Lumped Load
ID

% Impedance

kVA

kV

% Load

Loading

Machine Base

Amp

% PF

MTR

STAT

kW

kvar

X"

Grounding

R/X"

Conn.

Type

mFact.
Amp

MW/PP

Lump1

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump2

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump3

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump4

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump5

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump6

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump7

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump8

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump9

900.0

0.433

1200.04

85.00

70

30

535.50

331.87

6.46

15.37

0.42

Delta

0.54

Lump10

900.0

0.433

1200.04

85.00

70

30

535.50

331.87

6.46

15.37

0.42

Delta

0.54

Total Connected Lumped Loads ( = 10 ): 9800.0 kVA

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

SHORT- CIRCUIT REPORT

Fault at bus:
Nominal kV
Voltage c Factor

Bus22
= 6.600
= 1.10 (Maximum If)
Contribution

From Bus
ID

3-Phase Fault
To Bus
ID

%V
From Bus

kA
Symm. rms

Positive & Zero Sequence Impedances


Looking into "From Bus"

Line-To-Ground Fault
% Voltage at From Bus
Va
Vb
Vc

kA Symm. rms
Ia
3I0

R1

% Impedance on 100 MVA base


X1
R0

X0

Bus22

Total

0.00

23.162

0.00

104.37

100.85

21.986

21.986

4.67E+000

4.13E+001

2.37E+000

4.73E+001

Bus20

Bus22

81.76

15.959

91.64

100.12

91.22

17.245

21.140 *

3.25E+000

6.02E+001

2.46E+000

4.92E+001

Bus26

Bus22

15.98

0.512

66.38

100.56

62.11

0.327

0.000

6.64E+002

1.76E+003

Bus28

Bus22

15.98

0.512

66.38

100.56

62.11

0.327

0.000

6.64E+002

1.76E+003

Bus31

Bus22

15.98

0.512

66.38

100.56

62.11

0.327

0.000

6.64E+002

1.76E+003

Bus36

Bus22

10.23

0.327

64.16

100.60

60.53

0.209

0.000

1.07E+003

2.74E+003

float air blower -1

Bus22

100.00

0.601

100.00

100.00

100.00

0.364

0.000

2.49E+002

1.58E+003

ball mill

Bus22

100.00

2.254

100.00

100.00

100.00

1.367

0.000

4.59E+001

4.24E+002

regrind mill

Bus22

100.00

0.303

100.00

100.00

100.00

0.169

0.000

6.00E+002

3.12E+003

Bus30

Bus25

11.24

0.360

64.55

100.59

60.79

0.230

0.000

9.72E+002

2.49E+003

Bus32

Bus25

11.24

0.360

64.55

100.59

60.79

0.230

0.000

9.72E+002

2.49E+003

Bus34

Bus25

15.98

0.512

66.38

100.56

62.11

0.327

0.000

6.64E+002

1.76E+003

Bus37

Bus25

10.23

0.327

64.16

100.60

60.53

0.209

0.000

1.07E+003

2.74E+003

T14~

Bus25

0.00

0.000

58.23

60.26

100.66

0.282

0.846 *

6.15E+001

1.23E+003

Float air blower-2

Bus25

100.00

0.601

100.00

100.00

100.00

0.364

0.000

2.49E+002

1.58E+003

Secondary cone
crusher

Bus25

100.00

0.162

100.00

100.00

100.00

0.090

0.000

1.33E+003

5.77E+003

Bus25

Bus22

0.00

2.312

0.00

104.37

100.85

1.721

0.846

Bus27

Bus30

11.24

2.742

64.55

100.59

60.79

1.520

0.000

Bus29

Bus30

11.24

2.742

64.55

100.59

60.79

1.520

0.000

Bus33

Bus32

11.24

2.742

64.55

100.59

60.79

1.520

0.000

Bus35

Bus32

11.24

2.742

64.55

100.59

60.79

1.520

0.000

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

(Cont.)

Fault at bus:
Nominal kV
Voltage c Factor

Bus22
= 6.600
= 1.10 (Maximum If)
Contribution

From Bus
ID

Initial Symmetrical Current (kA, rms)


Peak Current (kA), Method C
Breaking Current (kA, rms, symm)
Steady State Current (kA, rms)

3-Phase Fault
To Bus
ID

:
:
:
:

%V
From Bus
3-Phase
23.162
57.414
15.959

kA
Symm. rms

Positive & Zero Sequence Impedances


Looking into "From Bus"

Line-To-Ground Fault
% Voltage at From Bus
Va
Vb
Vc
L-G
21.986
54.500
21.986
21.986

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

L-L
19.852
49.209
19.852
19.852

kA Symm. rms
Ia
3I0
L-L-G
22.975
56.952
22.975
22.975

R1

% Impedance on 100 MVA base


X1
R0

X0

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

10

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents
Bus
ID
Bus22

3-Phase Fault
kV
6.600

I"k
23.162

Line-to-Ground Fault

ip
57.414

Ik
15.959

All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.

I"k
21.986

ip
54.500

Ib
21.986

Line-to-Line Fault
Ik
21.986

I"k
19.852

ip
49.209

Ib
19.852

*Line-to-Line-to-Ground
Ik
19.852

I"k
22.975

ip
56.952

Ib
22.975

Ik
22.975

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

11

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Sequence Impedance Summary Report


Bus
ID
Bus22

Positive Seq. Imp. (ohm)


kV
6.600

Negative Seq. Imp. (ohm)

Zero Seq. Imp. (ohm)

Fault Zf (ohm)

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

0.02036

0.17982

0.18097

0.02019

0.18364

0.18474

0.01031

0.20622

0.20647

0.00000

0.00000

0.00000

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents

Swing

V-Control

Load

Total

14

16

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

10

14

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

Number of Machines:

10

17

System Frequency:

50.00 Hz

Unit System:

English

Project Filename:

SK Mines HZL

Output Filename:

C:\ETAP 1111\SK Mines HZL\Untitled.SI2

Number of Buses:

Number of Branches:

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Percent

Apply

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Global

20

Cable Resistance:

Yes

Global

20

Temperature Correction

Degree C

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Bus Input Data

Bus
ID
Bus20

Type

Initial Voltage
Nom. kV

SWNG

Bus22

Load

Bus24

SWNG

Bus25

33.000

Base kV

Sub-sys

%Mag.

Ang.

33.000

100.00

0.00
-30.00

6.600

6.600

100.00

33.000

33.000

100.00

0.00

Load

6.600

6.600

100.00

30.00

Bus26

Load

0.433

0.433

100.00

0.00

Bus27

Load

0.433

0.433

100.00

60.00

Bus28

Load

0.433

0.433

100.00

0.00

Bus29

Load

0.433

0.433

100.00

60.00

Bus30

Load

0.433

0.433

100.00

60.00

Bus31

Load

0.433

0.433

100.00

0.00

Bus32

Load

0.433

0.433

100.00

60.00

Bus33

Load

0.433

0.433

100.00

60.00

Bus34

Load

0.433

0.433

100.00

60.00

Bus35

Load

0.433

0.433

100.00

60.00

Bus36

Load

0.433

0.433

100.00

0.00

Bus37

Load

0.433

0.433

100.00

60.00

16 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID

Rating
MVA

Prim. kV

Sec. kV

Z Variation
%Z

X/R

% Tap Setting

+ 5%

- 5%

% Tol.

Prim.

Sec.

Phase Shift

Adjusted
%Z

Type

Angle

T10

20.000

33.000

6.600

10.00

20.00

10.0000

Dyn

30.000

T14

20.000

33.000

6.600

10.00

20.00

10.0000

Dyn

-30.000

TR#1

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#2

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#3

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#4

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#5

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#6

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#7

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

TR#8

2.000

6.600

0.433

6.25

6.00

6.2500

Dyn

-30.000

2-Winding Transformer Grounding Input Data


Grounding
Transformer
ID

Rating
MVA

Prim. kV

Conn.
Sec. kV

Type

Primary
Type

kV

Secondary
Amp

Ohm

Type

kV

Amp

Ohm

T10

20.000

33.000

6.600

D/Y

Solid

T14

20.000

33.000

6.600

D/Y

Solid

TR#1

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#2

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#3

2.000

6.600

0.433

D/Y

Resistor

3.3

75.00000

TR#4

2.000

6.600

0.433

D/Y

Resistor

TR#5

2.000

6.600

0.433

D/Y

Resistor

TR#6

2.000

6.600

0.433

D/Y

Resistor

TR#7

2.000

6.600

0.433

D/Y

Resistor

TR#8

2.000

6.600

0.433

D/Y

Resistor

75.00000
3.3

75.00000
75.00000
75.00000

3.3

75.00000

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch
ID

Connected Bus ID
Type

From Bus

% Impedance, Pos. Seq., 100 MVAb


To Bus

R
2.46

49.23

49.30

T10

2W XFMR

Bus20

Bus22

T14

2W XFMR

Bus24

Bus25

2.46

49.23

49.30

TR#1

2W XFMR

Bus22

Bus26

49.42

296.51

300.60

TR#2

2W XFMR

Bus25

Bus30

49.42

296.51

300.60

TR#3

2W XFMR

Bus22

Bus28

49.42

296.51

300.60

TR#4

2W XFMR

Bus22

Bus31

49.42

296.51

300.60

TR#5

2W XFMR

Bus25

Bus32

49.42

296.51

300.60

TR#6

2W XFMR

Bus25

Bus34

49.42

296.51

300.60

TR#7

2W XFMR

Bus22

Bus36

49.42

296.51

300.60

TR#8

2W XFMR

Bus25

Bus37

49.42

296.51

300.60

CB66

Tie Breakr

Bus30

Bus27

CB69

Tie Breakr

Bus30

Bus29

CB71

Tie Breakr

Bus32

Bus33

CB73

Tie Breakr

Bus32

Bus35

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Power Grid Input Data

Power Grid

Connected Bus

ID

ID

% Impedance
100 MVA Base

Rating
MVASC

kV

X"

Grounding
R/X"

Type

U3

Bus20

1000.000

33.000

0.71247

9.97459

0.07

Wye - Solid

U4

Bus24

1000.000

33.000

0.71247

9.97459

0.07

Wye - Solid

Total Connected Power Grids ( = 2 ): 2000.000 MVA

Project:

ETAP

SC calculation

Location:

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Induction Machine Input Data

Induction Machine
ID

Connected Bus
Type

Qty

PosSeqImp (Mtr Base)

Rating

ID

HP/kW

kVA

kV

Amp

PF

%R

% X"

float air blower -1

Motor

Bus22

750.00

867.66

6.600

75.90

92.37

2.16

13.72

ball mill

Motor

Bus22

2850.00

3253.59

6.600

284.61

92.92

1.49

regrind mill

Motor

Bus22

375.00

436.83

6.600

38.21

92.09

2.62

R/X"

Grounding
Conn.

Type

mFact.
Amp

MW/PP

0.16

Wye

Open

0.38

13.81

0.11

Wye

Open

1.43

13.64

0.19

Wye

Open

0.19

Float air blower-2

Motor

Bus25

750.00

867.66

6.600

75.90

92.37

2.16

13.72

0.16

Wye

Open

0.38

Secondary cone crusher

Motor

Bus25

200.00

234.44

6.600

20.51

91.83

3.12

13.53

0.23

Wye

Open

0.10

Total Connected Induction Machines ( = 5 ): 5660.2 kVA

Lumped Load Input Data


Motor Loads
Lumped Load
Rating

Lumped Load
ID

% Impedance

kVA

kV

% Load

Loading

Machine Base

Amp

% PF

MTR

STAT

kW

kvar

X"

Grounding

R/X"

Conn.

Type

mFact.
Amp

MW/PP

Lump1

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump2

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump3

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump4

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump5

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump6

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump7

500.0

0.433

666.69

85.00

70

30

297.50

184.37

6.46

15.37

0.42

Delta

0.30

Lump8

1500.0

0.433

2000.06

85.00

70

30

892.50

553.12

6.46

15.37

0.42

Delta

0.89

Lump9

900.0

0.433

1200.04

85.00

70

30

535.50

331.87

6.46

15.37

0.42

Delta

0.54

Lump10

900.0

0.433

1200.04

85.00

70

30

535.50

331.87

6.46

15.37

0.42

Delta

0.54

Total Connected Lumped Loads ( = 10 ): 9800.0 kVA

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

SHORT- CIRCUIT REPORT

Fault at bus:
Nominal kV
Voltage c Factor

Bus22
= 6.600
= 1.10 (Maximum If)
Contribution

From Bus
ID

3-Phase Fault
To Bus
ID

%V
From Bus

kA
Symm. rms

Positive & Zero Sequence Impedances


Looking into "From Bus"

Line-To-Ground Fault
% Voltage at From Bus
Va
Vb
Vc

kA Symm. rms
Ia
3I0

R1

% Impedance on 100 MVA base


X1
R0

X0

Bus22

Total

0.00

20.897

0.00

102.58

100.30

20.302

20.302

4.22E+000

4.59E+001

2.46E+000

4.92E+001

Bus20

Bus22

81.76

15.959

91.41

100.11

91.07

17.194

20.302 *

3.25E+000

6.02E+001

2.46E+000

4.92E+001

Bus26

Bus22

15.98

0.512

65.47

100.49

61.67

0.334

0.000

6.64E+002

1.76E+003

Bus28

Bus22

15.98

0.512

65.47

100.49

61.67

0.334

0.000

6.64E+002

1.76E+003

Bus31

Bus22

15.98

0.512

65.47

100.49

61.67

0.334

0.000

6.64E+002

1.76E+003

Bus36

Bus22

10.23

0.327

63.20

100.52

60.12

0.214

0.000

1.07E+003

2.74E+003

float air blower -1

Bus22

100.00

0.601

100.00

100.00

100.00

0.372

0.000

2.49E+002

1.58E+003

ball mill

Bus22

100.00

2.254

100.00

100.00

100.00

1.398

0.000

4.59E+001

4.24E+002

regrind mill

Bus22

100.00

0.303

100.00

100.00

100.00

0.172

0.000

6.00E+002

3.12E+003

Initial Symmetrical Current (kA, rms)


Peak Current (kA), Method C
Breaking Current (kA, rms, symm)
Steady State Current (kA, rms)

:
:
:
:

3-Phase
20.897
52.917
15.959

L-G
20.302
51.412
20.302
20.302

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

L-L
17.937
45.421
17.937
17.937

L-L-G
20.831
52.751
20.831
20.831

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents
Bus
ID
Bus22

3-Phase Fault
kV
6.600

I"k
20.897

Line-to-Ground Fault

ip
52.917

Ik
15.959

All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.

I"k
20.302

ip
51.412

Ib
20.302

Line-to-Line Fault
Ik
20.302

I"k
17.937

ip
45.421

Ib
17.937

*Line-to-Line-to-Ground
Ik
17.937

I"k
20.831

ip
52.751

Ib
20.831

Ik
20.831

Project:
Location:

ETAP

SC calculation

11.1.1C

SK Mines

Contract:
Engineer:

Jigyesh Sharma

Filename:

SK Mines HZL

Study Case: CASE-1

Page:

10

Date:

04-05-2016

SN:

LARTOUMUM

Revision:

Base

Config.:

Normal

Sequence Impedance Summary Report


Bus
ID
Bus22

Positive Seq. Imp. (ohm)


kV
6.600

Negative Seq. Imp. (ohm)

Zero Seq. Imp. (ohm)

Fault Zf (ohm)

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

0.01837

0.19974

0.20059

0.01813

0.20337

0.20418

0.01072

0.21447

0.21473

0.00000

0.00000

0.00000

You might also like