You are on page 1of 80

CewePrometer

User Manual
BGX501-856-R02

Copyright 2013, SIHPL


Other product names are trademarks or registered trademarks of their respective owners.
.

Page 2 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Table of Contents
1

Introduction ................................................................................................................................. 5

1.1

About this user manual.............................................................................................................................5

1.2

Contacting us ...........................................................................................................................................5

Product Description .................................................................................................................... 6

2.1

Sealing of CewePrometer-W ....................................................................................................................8

2.2

Sealing of CewePrometer-R .....................................................................................................................9

2.3

Connections .............................................................................................................................................9

2.4

Mechanical design ................................................................................................................................. 12

2.5

Function modules................................................................................................................................... 15

2.6

Measuring principles .............................................................................................................................. 15

Configuration, Reading and Maintenance ............................................................................... 16

3.1

Connecting to CewePrometer................................................................................................................. 16

3.2

Basic configuration................................................................................................................................. 18

3.3

Overview of functions ............................................................................................................................. 19

3.4

Changing configuration .......................................................................................................................... 20

3.5

Working with configurations.................................................................................................................... 21

3.6

Reading ................................................................................................................................................. 22

3.7

Information about the meter ................................................................................................................... 23

3.8

Versions and version conflicts ................................................................................................................ 23

3.9

Updating firmware .................................................................................................................................. 23

3.10 Language ............................................................................................................................................... 24


3.11 Resetting registers and logs ................................................................................................................... 24

Functions ................................................................................................................................... 25

4.1

Meter clock ............................................................................................................................................ 25

4.2

Energy registers ..................................................................................................................................... 26

4.3

Instant values......................................................................................................................................... 27

4.4

Digital inputs and outputs ....................................................................................................................... 29

4.5

Display sequences ................................................................................................................................. 32

4.6

Communications and security................................................................................................................. 32

4.7

Loggers ................................................................................................................................................. 34

4.8

Alarms ................................................................................................................................................... 36

4.9

Event log................................................................................................................................................ 38

4.10 Configuration log .................................................................................................................................... 38


4.11 Maximum demand ................................................................................................................................. 38
4.12 Historical registers ................................................................................................................................. 40
4.13 Time of use ............................................................................................................................................ 41
4.14 Transformer compensation..................................................................................................................... 42
Public

BGX501-856-R02, CewePrometer User Manual

Page 3 of 80

4.15 Power quality ......................................................................................................................................... 43


4.16 Miscellaneous ........................................................................................................................................ 44

Using the Display ...................................................................................................................... 46

5.1

Voltage order display layout ................................................................................................................... 46

5.2

Navigating in display sequences ............................................................................................................ 47

5.3

Display layouts with choices ................................................................................................................... 47

5.4

Using the display for communication diagnostics .................................................................................... 49

Appendix A - Display Layouts ........................................................................................................ 50


Appendix B - Events and Configuration Log ................................................................................ 58
Appendix C - Communication Ports .............................................................................................. 61
Appendix D Module Block Diagram ............................................................................................ 66
Appendix E Frequently Asked Questions .................................................................................. 67
Appendix F Calculation Principles ............................................................................................. 69
Appendix G Material Declaration ................................................................................................ 74
Appendix H Connection and General Details ............................................................................. 75
Appendix I Approvals and Certificates ....................................................................................... 77
Appendix J Cewe Config settings ............................................................................................... 78
Notes ................................................................................................................................................ 79

Page 4 of 80

BGX501-856-R02, CewePrometer User Manual

Public

1 Introduction
Thank you for choosing the CewePrometer.
The CewePrometer is a multi-functional, electronic, electricity energy meter. It provides very high accuracy in
measuring electrical energy and also in measuring instantaneous quantities such as current, voltage, power,
frequency etc. CewePrometers extensive configurable functional features together with the high accuracy
enable application areas more numerous than for traditional electric meters. Besides having well-designed
traditional features such as meter registers, data logging and tariff capability, there are also extensive functions
for monitoring alarm conditions, harmonics, measuring sags and swells and other power quality quantities.

1.1

About this user manual

This user manual describes the CewePrometers functions and provides the information needed to configure
and use the meter. The manual covers all versions of the CewePrometer-R (rack-mounted) and CewePrometerW (wall-mounted). Some of the described functional properties can be missing in certain meter versions. The
CewePrometer is complemented with CeweConfig, a PC program for configuring, manual reading and
maintenance.

1.2

Contacting us

For more information and technical support, please contact Cewe Instrument.
Internet

www.ceweinstrument.se

E-mail technical support

support@ceweinstrument.se

E-mail order and product information

marknad@ceweinstrument.se

Telephone

+46 (0)155 77500

Address

Cewe Instrument AB
Box 1006
SE-611 29 Nykping
Sweden

Public

BGX501-856-R02, CewePrometer User Manual

Page 5 of 80

2 Product Description

15

14
13
12

11
10
3

Figure 1: CewePrometer-W

10
15
14

13

12

11

16
Figure 2: CewePrometer-R

Page 6 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Display

Optical communication port


The optical port communicates in accordance with IEC62056-21/IEC1107.

Alarm LED
The alarm LED flashes when an alarm state has occurred. For alarms, such as for high
or low voltage, phase balance or similar external errors, the LED stops flashing when
the alarm state has passed. If the meter has had an internal error, the alarm must be
acknowledged and manually reset.

Calibration LED for active energy


The LED is the source of the energy signal for accuracy testing of active energy. The
light pulses have a 50% pulse width and a frequency proportional to the measured
active power. A constant that specifies the total number of pulses per kWh can be
configured. The same constant applies to active and reactive energy.

Auxiliary power LED


When the CewePrometer is receiving auxiliary power, the green LED turns on to
indicate that the meter's power supply is working.

Sealing points for terminal cover


The terminal cover can be sealed with lead seals (or comparable seals) and sealing
wire through the sealing points.

Terminal cover

Sealing points for front panel window


The front panel exterior window can be sealed with lead seals (or comparable seals)
and sealing wire through the sealing points. The seal prevents access to the fourth
button (sealed button) and the optional backup battery for the real-time clock.

Meter cover

10

Front panel window


The front panel window has hooks for attaching the meter label. In addition, the window
is provided with a pocket for inserting an extra label. The extra label can be used when
transformer ratios are changed.

11

Calibration LED for reactive energy


The LED is the source of the energy signal for accuracy testing of reactive energy. The
light pulses have a 50% pulse width and a frequency proportional to the measured
reactive power. A constant that specifies the total number of pulses per kvarh can be
configured. The same constant applies to active and reactive energy.

12

Sealed button
The button is hidden under the front panel window and provides access to a fifth
configurable display sequence. Holding down the button for about two seconds opens a
system menu.

13

Step backward
The button is used to step backward to a previous display layout in the selected display
sequence, or to step downwards in a menu.

14

Menu/Apply
The Menu/Apply button is used to open the menu where one of four configurable
display sequences can be chosen. The button confirms choices made or initiates other
activities depending on the current display layout.

Public

BGX501-856-R02, CewePrometer User Manual

Page 7 of 80

15

Step forward
The button is used to step forward to the following display layout in the selected display
sequence, or to step upwards in a menu.

16

Sealing points for rack mounting


The rack mounting bracket for the CewePrometer-R can be sealed with lead seals (or
comparable seals) and sealing wire through the sealing points.

2.1

Sealing of CewePrometer-W

See Figure 1: CewePrometer-W for location of the sealing points. The front panel window can be sealed with
lead seals (or comparable seals) and sealing wire through the sealing points. The seal prevents access to the
fourth sealed button and the optional backup battery for the real-time clock.

Battery cover

Sealed button

Figure 3: Under the front panel window is a fourth button and backup battery for the real-time clock.

The terminal cover can be sealed with lead seals (or comparable seals) and sealing wire through the sealing
points.
The meter cover can be sealed with lead seals (or comparable seals) and sealing wire through the two sealing
points under the terminal cover.
Sealing point

Figure 4: The meter cover can be sealed at the sealing rings on both sides under the terminal cover.

Page 8 of 80

BGX501-856-R02, CewePrometer User Manual

Public

2.2

Sealing of CewePrometer-R

See Figure 2: CewePrometer-R for location of sealing points. The enclosure permits the meter to be sealed at
three points. The top and bottom covers are normally each sealed with a lead seal and with sealing wire through
a sealing screw and a fixed hole on the cover at the rear of the meter. The exterior window on the meter front
can be sealed on a sealing point with a lead seal and sealing wire. In this way, the meter can be sealed so that
it cannot be opened without breaking all the seals. One of the buttons on the front is protected from access
behind the sealed exterior window.

Battery
Sealed button

Under the front panel window is a fourth button and backup battery for the real-time clock.

2.3

Connections

Connections to the CewePrometer-W are made on the meter terminal under the terminal cover. Connections to
the CewePrometer-R are made on the rear panel of the meter subrack. The connections are: measuring
voltages, measuring currents, relay outputs, optically isolated digital inputs, separate auxiliary power and
connections to communication modules, if any.
Digital outputs

Digital inputs

Output #8

Output #1

I'L1 UL1

IL1

I'L2 UL2

IL2

I'L3 UL3

Input #1

IL3

Input #4

N
Separate aux. power
(Uaux)

Connections for CewePrometer-W

Public

BGX501-856-R02, CewePrometer User Manual

Page 9 of 80

Connections

Digital I/O variants


6 outputs, 4 inputs
C0, C5
C1, C6
C2, C7
D0, D5
D1, D6
D2, D7

IN1
IN2
IN3
IN4

2.3.1

C0, C5
C1, C6
C2, C7
D0, D5
D1, D6
D2, D7
D3, D8
D4, D9
B7, B8
B4, B9

IN1
IN2

Uaux1
Uaux2

B5
B6

I1 in
I1 out
I2 in
I2 out
I3 in
I3 out

A01
A1
A02
A2
A03
A3

12 outputs, 0 inputs
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12

C4, C9
C3, C8
D4, D9
D3, D8

10 outputs, 2 inputs
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10

B1
B2
B3
B0

Current, voltage and auxiliary power


connections for CewePrometer-R.

Connections for CewePrometer-R

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6

UL1
UL2
UL3
N

C4, C9
C3, C8

C0, C5
C1, C6
C2, C7
D0, D5
D1, D6
D2, D7
D3, D8
D4, D9
B7, B8
B4, B9
C3, C8
C4, C9

Connector for CewePrometer-R

A standardised Entrelec Essailec plug-in connector is used, of the same type as for other meters according to
standard DIN 43862. The cable connection is made in the subrack. The meter is connected via the contact pins
after insertion. The connector has a short-circuit protection feature for electrical circuits, permitting the meter to
be withdrawn and inserted into the subrack during operation.

2.3.2

Auxiliary power

The CewePrometer is supplied with separate auxiliary power. Auxiliary power can be supplied both with
alternating current and polarity-independent direct current within a specified range. Auxiliary power can be self
powered (internal), CewePrometer-R can also be configured with dual auxiliary.

2.3.3

Digital outputs

The CewePrometer's outputs are solid-state MOS-FET bipolar semiconductor relays, with normally open
contact function. Internal current limit protects the relay from being damaged by excessively high current.

Page 10 of 80

BGX501-856-R02, CewePrometer User Manual

Public

2.3.4

Digital inputs

The optically isolated digital inputs consist of opto couplers, where the LED is powered from an external voltage
signal through series resistance to limit the current. This means that an external voltage must be connected
between the passive pulse and level transmitter and the opto coupler's LED, or the transmitter must deliver an
active voltage signal to send pulses that are detected by the optical input. The optically isolated inputs are
unaffected by reverse polarity. Both DC and 50/60 Hz AC can be used.

2.3.5

Communication ports {Ethernet (IP), Serial (RS232, RS422, RS485)}

The CewePrometer is equipped with one optical port and up to two additional communication ports, Ethernet or
serial (RS232 or RS422. RS422 can also be used as RS485)
Communications through the infrared IEC62056-21/IEC1107 optical port are transferred via an optical
read/write adapter, an optical head. The optical head is positioned and secured over the optical port
by a magnet on the head and a steel plate around the opening of the optical port.
The RS232 standard communication port is used to connect communication equipment (computers,
modems) through a serial cable with a standard D-sub, 9-pin connector.
The RS422 serial communication port is intended to be used to connect the CewePrometer to a
network for multi-drop communications. The CewePrometer is connected to the communication
equipment (RS422 converter) with two twisted-pair wires connected to a 5-pole connector. The
RS422 port can also be used for single twisted-pair RS485 bus.
The Ethernet communication port is used to connect to the meter over TCP/IP based network.
For information on pin configuration, see Appendix C - Communication Ports (pg.61).

Numbering of the communication ports from right to left on the CewePrometer-W.

Numbering of the communication ports on the CewePrometer-R.


Note that 2 communication ports is the default configuration on a rack meter.
Public

BGX501-856-R02, CewePrometer User Manual

Page 11 of 80

2.4

Mechanical design

Alternative
mounting

Dimensions for CewePrometer-W

Page 12 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Dimensions for CewePrometer-R

Public

BGX501-856-R02, CewePrometer User Manual

Page 13 of 80

Dimensions for CewePrometer-R subrack


The subrack is also available in alternative connector versions that will fit other brands of meters with the same
type of connector. Contact Cewe Instrument for more information.

2.4.1

Enclosure and protective earth

CewePrometer-W
The enclosure consists of a meter base, meter cover, terminal cover and a plastic exterior window. The meter is
not connected with protective earth. There is also an optional 19 inch rack/panel mounting kit available for to
CewPrometer-W to be mounted side by side.
CewePrometer-R
Enclosure fits for installation of two meters in a 19" subrack in compliance with DIN438862. The enclosure
consists of a box made of surface-finished steel sheet and a front with a plastic window. The meter is designed
for protective earthing through the 19" subrack.

2.4.2

Isolation and personal safety

The electronic circuits are isolated from all connections to the supply mains with transformers. Digital I/O
connections are isolated with opto couplers and solid state relays. The communication ports are also isolated
but for a lower voltage.

Page 14 of 80

BGX501-856-R02, CewePrometer User Manual

Public

2.5
2.5.1

Function modules
Modulisation

The CewePrometer is made up of function modules. Modulisation is primarily used to make it easy to produce
different versions with the same basic design, and to enable development of new modules for the basic design
to add or replace functions. Modulisation is not primarily intended for being able to switch plug-in modules in the
field the meter must be opened and the seals broken to switch modules.

2.5.2

Modules

The CewePrometer consists of the following basic modules, which are necessary for a functioning meter in its
simplest version:
Measurement module
Power module
Display and register module
Moreover, the meter is normally equipped with the following modules for additional functionality:
Digital I/O module
Communication module
There is also space for additional function modules for expansion of function properties to meet future market
needs.
For more information, see Appendix D Module Block Diagram (pg.66).

2.6

Measuring principles

The measuring circuit in CewePrometer consists of current and voltage transformers that provide signals to six
parallel AD converters (analogue to digital converters) that are synchronised by a common clock signal. The
digital signals are thereafter processed by a DSP. Using voltage transformers makes the electronics in the
meter galvanically isolated from the measurement voltage, which provides good personal safety and protection
for connected equipment, such as modems.

2.6.1

Calculation flow

All values are calculated in the CewePrometer based on calibrated current and voltage values. Current and
voltage amplitudes and phase angles are fully compensated in regards to accuracy, harmonics, frequency and
temperature. Adjustments for accuracy are made throughout the dynamic range for both voltage and current.
Based on these individually compensated current and voltage signals, power, energy, power factor and all other
quantities that the CewePrometer can present, are subsequently calculated. This means that accuracy for
instant values is good and that active and reactive power are correctly calculated, including harmonic power.
For more information on calculation principles and the formulas used, see Appendix F Calculation Principles
(pg. 69).

2.6.2

3-element meter

On the 3-element CewePrometer, phase voltages and neutral wires are connected to the meter. The voltages
measured are phase voltages. Power and energy are calculated from three phase voltages and three currents.
Harmonic measurement, alarm monitoring and transformer corrections are made on phase voltages. The line to
line voltage is calculated from the phase voltages.

2.6.3

2-element meter

On the 2-element CewePrometer, the neutral conductor is not connected to the meter and the three voltages
are internally D-connected. The voltages measured are subsequently line to line voltages. Power and energy
are calculated based on two line to line voltages (U12 and U23) and two currents (I1 and I3) according to the 2watt meter method. The 2-element meter is primarily used for D-connected systems (3-wire). Harmonic
measurement, alarm monitoring and transformer corrections are made on line to line voltages.
Public

BGX501-856-R02, CewePrometer User Manual

Page 15 of 80

3 Configuration, Reading and Maintenance


CeweConfig is a PC program that makes all CewePrometer functions available. With CeweConfig, you can:
Configure
Configuring means that parameters affecting meter function or parameters configuration as per
customer metering application can be set. Examples of parameters that can be configured are: energy,
rate and MD registers, transformer ratios, logging interval and limits for alarms.
Reading
Examples of information that can be read are: registers, logged values, alarms and harmonics. The
information can be printed out or saved to a file.
Maintenance
Examples of maintenance tasks are: resetting the event log and updating the firmware in the meter.
Menu

Structure tree

3.1

Toolbar

Status bar

Configuration form

Connecting to CewePrometer

To be able to configure or read values in the CewePrometer, CeweConfig must be connected and have
authorisation to access the meter. The meter has five different authorisation levels that can be configured with
passwords. See the section Communications and security (pg. 32). With the meter's usual factory settings, no
password is configured, and subsequently no password is necessary when you connect.
To communicate with a meter, the PC must be physically connected to the CewePrometer in one of the
following ways:
PC Optical head Meter
PC Crossed serial cable (null modem) Meter
PC Straight serial cable RS422 converter Daisy chained meters
PC straight serial cable RS485 converter Daisy chained Meters
Page 16 of 80

BGX501-856-R02, CewePrometer User Manual

Public

PC Modem Modem Meter


PC Ethernet (straight) Meter

How to connect to the meter


1. Connect to Meter
Choose Connect to Meter from the File menu or by clicking the toolbar button.
2. Communication channel
Click the Settings tab and choose either, Optical Port, Serial Port (RS232/RS422), Serial Port (RS485) or
Modem. If the serial port or a modem is used, the baud rate must be selected. For meters with factory settings,
the baud rate is 9600. When the optical port is used, CeweConfig adapts itself to the baud rate the meter is
configured for, making selection of the baud rate unnecessary.
Note: The selectable communication ports can be changed by changing the XML file Settings.xml that is in
CeweConfig's installation directory.
3. Serial Port (RS485)
If a connection over RS485 uses a RS485 converter relying on the RTS signal for switching between transmit
and receive, an RTS off delay may have to be defined. The time is given in milliseconds, and defines for how
long the converted data is kept in transmit mode after last character has been sent on the communication port.
Time may vary depending on PC performance and baud rate. Typical time is 20 ms for 9600 baud.
4. Modem
If a modem connection is used, a modem must be chosen. The modems available are those installed in
Windows. Click the Common tab and enter the telephone number to be called.
5. Password
Click the Common tab. A password is entered if one is configured in the meter. With the meter's factory
settings, no password is configured, and subsequently no password is necessary when you connect.
6. Serial number
Serial number is only required if a special meter is to be addressed when several meters are connected
together with RS422.
7. Trace to file
Public

BGX501-856-R02, CewePrometer User Manual

Page 17 of 80

Under the Settings tab, a box can be checked to activate tracing to a file. A file named SerialTrace.log is then
created in CeweConfig's installation directory. All communications between CeweConfig and the meter are
presented in the file. The function can be used to analyse communication problems.
8.

Click the Connect button.

Note: For Ethernet communication, the Serial Port (RS232/RS422) option should be selected.

3.1.1

Problems with connecting

If the meter cannot be connected, an error message is displayed. Depending on the reason, the message can
suggest corrective actions, such as changing the port or port baud rate.
Tip: When communication problems occur, the trace feature on the meter's display can be used to see if that
which has been sent has been registered by the meter. See the section Using the display for communication
diagnostics (pg.49).

3.2

Basic configuration

Some basic settings may be required before the CewePrometer will be able to measure and operate correctly in
a system.
Note: Settings are only necessary if they have not been made at the factory prior to delivery.
Meters supplied without backup batteries retain the time setting for a maximum of three days. For timedependent functions such as logging and event logging to work, the clock may need to be adjusted.
To change the configuration for a meter, you must be connected to it. Click the Configuration folder in the
structure tree to the left in CeweConfig to display the various functions that can be configured. For more
information see the section Changing configuration (pg. 20).
Tip: You can save a configuration from a meter to a file. A summary of the configuration can also be printed out.
You can also create a configuration without being connected to a meter. For more information, see Working with
configurations (pg.21).

Meter clock: To configure the meter clock, choose the node Meter Configuration - Clock in the
structure tree. Find out how the meter clock works and how it can be configured in the section Meter
clock (pg. 25).

Page 18 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Transformer ratios: For the meter to measure accurately, the ratios must be correct. To configure the
transformer ratio in CeweConfig, choose the node Meter Configuration Measuring in the structure
tree. Click the General tab in the window that opens. Fill in the primary and secondary values for
current and voltage.
Note 1: The values you choose as primary and secondary values will be considered as the nominal
values. These nominal values are used by several functions in the meter: alarms, voltage monitoring
and transformer compensation.
Any change to measuring configuration is logged in the configuration log (see section Configuration
log).
Presentation format for energy registers: To configure the presentation format for energy registers,
choose the node Meter Configuration Measuring in the structure tree. Choose the prefix and
number of decimals for energy registers. Based on the nominal values, a capacity is calculated for how
long the meter can measure without registers resetting. Read about energy registers in the section
Energy registers (pg. 26).
Pulse constants for pulse outputs (Digital I/O): To configure pulse constants for pulse outputs in
CeweConfig, choose the node Meter Configuration Digital I/O in the structure tree. Find out how
Digital I/O works and how it can be configured in the section Digital inputs and outputs (pg. 29).
Display sequences: To configure display sequences in CeweConfig, choose the node Meter
Configuration Display sequences in the structure tree. Find out how display sequences work and
how they can be configured in the section Display sequences (pg. 32).

3.3

Overview of functions

The following is a brief overview of the functions available in CewePrometer. All functions in the meter can be
both configured and read in CeweConfig. In many cases, CeweConfig can also export data to a file or print out
data.
Function
Communication speed
Set the baud rate for the meter's
optical or serial port.
Passwords
Regulate access to data in 5
levels with passwords or
hardware strap.
Data logging
Log energy or instant values.

Public

Configuration location in
CeweConfig
Meter Configuration
Communication
Meter Configuration
Communication

Meter Configuration Loggers

Section in handbook describing


the function.
Communications and security (pg.
32)
Communications and security (pg.
32)
Loggers (pg. 34)

BGX501-856-R02, CewePrometer User Manual

Page 19 of 80

Alarms
Activate alarms for events such
as voltage unbalance. Determine
how alarms will be presented.
Maximum demand
Determine values that are to be
stored as maximum average
values.
Historical registers
Choose how a historical period
will be finished.
Time of use
Determine how rates shift over
the course of a day and which
registers will be divided by rates.
Transformer compensation
Compensate errors and losses for
instrument and power
transformers.
Power quality
Activate monitoring of voltage
sags, swells and interrupts.
Language on display
Choose between several
available languages for the
display.
Information texts
Enter information texts that can
be read on the display and via
communications.
Calibration LED
Set a pulse constant for the
calibration LED. This is used to
test meter accuracy.
Accumulate incoming pulses
Configure registers to accumulate
pulses representing a selectable
quantity.
Indicate alarms via pulse
output
Choose a pulse output to be
activated in case of alarms.
Synchronise clock via
incoming pulse
Set an interval that the clock shall
be synchronised to upon
incoming pulses.
Adjusting the clock for daylight
saving time
Set date and time for daylight
saving time.

3.4

Meter Configuration Alarm

Alarms (pg. 36)

Meter Configuration
Maximum Demand

Maximum demand (pg. 38)

Meter Configuration
Historical Registers

Historical registers (pg. 40)

Meter Configuration Time of


use

Time of use (pg. 41)

Meter Configuration
Measuring, Transformer
Compensation tab

Transformer compensation (pg.


42)

Meter Configuration
Measuring, Power Quality tab

Power quality (pg. 43)

Meter Configuration Misc.

Miscellaneous (pg. 44)

Meter Configuration Misc.

Miscellaneous (pg. 44)

Meter Configuration
Measuring, General tab

Product Description (pg.6)

Meter Configuration Digital


I/O, Inputs tab

Digital inputs and outputs (pg. 29)

Meter Configuration Digital


I/O, Outputs tab

Digital inputs and outputs (pg. 29)

Meter Configuration Clock


Meter Configuration Digital
I/O, Inputs tab

Meter clock (pg. 25)


Digital inputs and outputs (pg. 29)

Meter Configuration Clock

Meter clock (pg. 25)

Changing configuration

Page 20 of 80

BGX501-856-R02, CewePrometer User Manual

Public

To open a configuration form, click the folder Configuration in the structure tree and then click one of the
nodes: Display Sequences, Measuring, Clock, etc. Configuration changes can be made in all configuration
form. In the lower right corner, there is an Apply button. If a meter is connected and you click Apply, changes
to the configuration will be immediately transferred to the meter. If the changes affect registers or measurement,
a warning dialog will be displayed. You can choose not to send a portion of the configuration by clearing
checkboxes in the dialog.

Warning dialog displayed sometimes when configurations are sent to the meter.

3.5

Working with configurations

In CeweConfig, you can work with configurations as a collection of CewePrometer's settings and save them in a
file. On CeweConfig's File menu, are the commands Save configuration, Open configuration and New
configuration. A configuration can either be for a 2- or 3-element meter. You cannot transfer a 2-element
configuration to a 3-element meter or vice versa. Transformer corrections or passwords are not saved in
configuration files. On the File menu, there is a command for creating a configuration summary. Below is a list
of how you can use CeweConfig's functions to work with configurations.
Creating a configuration file without being connected to a meter
Choose New configuration when CeweConfig is not connected to create a configuration file offline.
The configuration file can be either of the 2- or 3-element type. Make all settings that are to be included
in the configuration file and save the file. The file's configuration can later be transferred to a meter.
Saving a meter's configuration to a file
Choose Save configuration when CeweConfig is connected to a meter to save the meter's
configuration to a file. The configuration file can later be used as a backup or be transferred to another
meter.
Transferring a configuration file to a meter
Choose Open configuration when CeweConfig is connected to a meter to transfer a configuration file
to the meter. The changes in configuration cause a dialog to open. The dialog shows all parameters
that can be updated in the meter. You can select some parameters which will not be updated, e.g.
transformer ratio, that might be specific for each meter. If you want an exact copy, all parameters must
be selected

Public

BGX501-856-R02, CewePrometer User Manual

Page 21 of 80

Printing out a summary of a meter's configuration


Choose View configuration Configuration summary when CeweConfig is connected to a meter to
create a summary of the meter's entire configuration. Now choose Print.
Printing out a summary of a configuration file
Open a configuration file and choose View Configuration summary to create a summary of the
configuration that is in the file. Now choose Print.
Note: Choosing New configuration or Open configuration when CeweConfig is connected to a meter opens a
warning dialog box with the message that the configuration in the meter will be written over if you continue.

3.6

Reading

If you are connected to a CewePrometer with an authorisation level between 1 and 5, several alternatives will
be available in the structure tree under the node Reading. For the alternatives Instant Values and Time,
displayed values are constantly updated. The others are only updated when the window is opened or when the
Update button is clicked. Read values can be printed out and often also saved to files, this can be done with the
help of Print and Save buttons.

Page 22 of 80

BGX501-856-R02, CewePrometer User Manual

Public

3.7

Information about the meter

Information about the connected meter can be obtained by choosing View Information about the meter.
Some of the information displayed is the same as what appears on the meter plate. Additionally, there is
information on when the meter was manufactured and when the most recent configuration change was made.
Under the Modules heading, the firmware currently used in the meter is listed. See the section Updating
firmware (pg. 23).

3.8

Versions and version conflicts

The latest version of CeweConfig can be used with all firmware versions of CewePrometer-R/W. The version
number for CeweConfig is displayed on the application's title bar or under About on the Help menu. The
version number for the meter's firmware can be viewed under View information about the meter on the View
menu.
CewePrometer and CeweConfig have three-digit version numbers according to the format main version.subversion.build number. As long as the main version and sub-version are the same, CeweConfig and the meter
are compatible. If the meter is of a newer version than CeweConfig and the main version and/or sub-version are
different, CeweConfig will display a message that connection is not possible. CeweConfig must be updated.

3.9

Updating firmware

CewePrometer is designed with a number of modules that each have their own processors and their own
firmware. The module firmware is distributed in a package file (.pkg) which is transferred to the meter using
CeweConfig. Newly developed and improved functions can thus be added in a meter that lacked these functions
when delivered.
Note: Be sure to update CeweConfig to the latest version before updating the meter. There is otherwise the risk
that CeweConfig will no longer be version-compliant after firmware updating.

Public

BGX501-856-R02, CewePrometer User Manual

Page 23 of 80

On the Tools menu, there is an Update firmware command when the meter is connected with authorisation
level 4 or higher. Begin by choosing the file that contains the update. The file name and version number will
then be displayed, and sometimes a message. Click the Advanced button to view CeweConfig's version
number by module for both the file and the meter. Additionally, you can force modules to be updated even if the
file has the same version number. Click Update to begin updating.
During the time the update is being installed, the meter stops measuring and registering energy. Depending on
the size of the file to be transferred and the baud rate, the time for updating can vary from a few minutes to a
half hour at the highest baud rate. If possible, connect at the highest baud rate (19200 bps) to speed updating.
After updating, the meter is restarted to complete installation of the meter's new firmware.
Updating can be performed via a modem but this should be avoided since reliability for this method of
communication is too low. An interrupted update can leave a meter with incomplete firmware that cannot
measure at all. If an update via a modem has failed, the next update must be made via RS232/422 or the optical
head.

3.9.1

Restrictions

Firmware updates can only be made to a firmware version with the same major version number as the firmware
present in the meter. Example: It is not possible to update from 2.1.0 to 3.0.0. It is possible to update from 2.0.1
to 2.1.0.

3.10 Language
CeweConfig can be set to different languages. The available languages can be seen under Language on the
View menu.

3.11 Resetting registers and logs


CewePrometer's various registers and log data can be reset with CeweConfig if a meter is connected and you
are connected with a sufficiently high authorisation level. You will find a number of choices under Reset on the
Tools menu. Some options may be marked in grey if your authorisation level is not high enough. To reset
energy registers, authorisation level 5 is required, and level 3 for other options. A warning dialog box opens
before resetting.

Page 24 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4 Functions
4.1

Meter clock

The CewePrometer has an integrated real-time clock for time-dependent functions. Information about time
adjustment and daylight saving time status is recorded with tags on the logged values; see Loggers (pg.34).
Time adjustments are also noted as an event in the event log; see Appendix B - Events and Configuration Log
(pg.58).

4.1.1

Instantaneous adjustment

The meters date and time can be set to an absolute point in time. Instantaneous adjustment of the meters time
can influence logged values. To avoid this, the meter's log memory is reset when doing instantaneous
adjustment. For this reason, instantaneous adjustment of the meter clock is primarily intended for use at initial
configuration of the meter.

4.1.2

Sliding adjustment

The meters time can be adjusted successively. Instead of the meter adjusting the clock instantaneously, the
total adjustment is spread out over a longer period. A speed of adjustment can be chosen in the 140% range.
With 40%-adjustment, the clock is adjusted 24 seconds for each minute until the total adjustment has been
made.

4.1.3

Daylight saving time

CewePrometer offers the alternative of letting the meter clock follow daylight savings time. At a specified date,
the meter clock is adjusted forward, and at another, adjusted backward. CewePrometer can store ten (10) years
of DST configuration.
Example: On 28 March the clock is to be adjusted forward, from 02:00 to 03:00. The adjustment back to
standard time is to occur on 31 October at 3:00 (daylight savings time) when the clock is to be set back to
02:00. The following is set in the meters: Begin March, 28, 02:00. End October, 31, 03:00 and the standard time
is to be adjusted by 60 minutes.

4.1.4

External synchronisation

The meter time can be adjusted by a pulse on one of the meters digital inputs. When a pulse is registered, the
clock is adjusted to the closest multiple of a specified synchronisation interval. If the synchronisation interval is,
for example, one hour and the time is 13:29, a pulse will adjust the clock to 13:00. If the time had instead been
13:31, the clock would have been adjusted to 14:00. Synchronisation is made by sliding the time 30% (18s per
minute).
Available synchronisation intervals are:
10, 15, 20 and 30 minutes
1 hour
Times 12:00 and 00:00
Time 00:00
Besides specifying that the meter clock will synchronise via external pulses, a digital input must also be
configured for clock synchronisation; see the section Digital inputs and outputs (pg. 29).
4.1.4.1

Battery monitoring

The battery is used to backup the real time clock. The battery monitoring function estimates the time left of the
battery. At installation of a battery the monitoring function must be restarted via CeweConfig.

Public

BGX501-856-R02, CewePrometer User Manual

Page 25 of 80

4.2

Energy registers

Energy registers in the CewePrometer are electronic counters that accumulate energy. Prefixes and number of
decimals are configured which apply to all energy registers. Energy registers have a width of nine digits,
regardless of the total number of decimals and the prefix configured. When an energy register has reached its
maximum figure (for example, 999999.999 kWh), it resets to zero. Fewer decimals and larger prefixes give the
energy registers space for more energy without resetting. Read more about how energy is calculated and
defined by quadrants in Appendix F Calculation Principles (pg.69).

4.2.1

Overview

The table shows the energy registers available in the meter.


Energy type

Energy direction

Total values

Active energy

Import, export

Yes

Reactive energy

Import, export,
quadrants I-IV,
capacitive,
inductive
Import, export

Apparent energy

Active power export


(-)

Reactive power
import (+)

II

Total number

Yes

Per phase
values
Yes (3-element
meter only)
No

Yes

No

8
8

Active power import


(+)

I
S

Capacitive
Q

P
Inductive
Reactive power
export (-)

III

IV

Quadrants
I
II

Phase angle
0 to 90
90 to 180

Current relative to voltage


Lagging
Leading

III
IV

-180 to -90
-90 to 0

Lagging
Leading

4.2.2

Storage in non-volatile memory

All registers are saved in non-volatile memory once per second. Loss of auxiliary voltage therefore results in no
more than one second of lost historical energy measurement data. For optimal safekeeping, all registers are
saved in three alternating memory areas.

Page 26 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.2.3

Delta values on meter Display

Delta values can be seen under logger channels display, only when selected in any of logger channel.

4.2.4

Integration period (IP) of Delta values

Integration period of delta values can be set by the time period of logger 2 using CeweConfig tool.

As per above picture, time interval of logger can be set to 1, 2, 3, 4, 5, 10, 15, 20, 30 or 60 minutes. Default time
period of logger is 1 minute which is also the default IP of all delta energy values.
Logger 2 time interval will only affect the IP of delta energy values; it will not log them unless the values are
selected as logger channel in any of the logger.

4.3

Instant values

Besides energy, the CewePrometer can also measure instant values. Instant values are constantly changing
values such as current, voltage, power and harmonics. The formulas and definitions used to calculate the
values are presented in Appendix F Calculation Principles (pg.69).

4.3.1

Overview

This table provides an overview of the instant values that can be read on the meter. Readings can be viewed
with CeweConfig, on the display and with other software that has implemented CewePrometers communication
protocol. Most instant values can be logged; for more information, see section Loggers (pg. 34).
Instant value
Frequency
Power factor total
Power factor per phase
Active power total
Active power per phase
Reactive power total
Reactive power per phase
Apparent power total
Apparent power per phase
Line to line voltage L12, L23, L31
Phase voltage
THD voltage
Amplitude voltage harmonics (231)4
Phase symmetry voltage

Public

Available on 3-element
meter
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
1
Yes (calculated)
Yes
Yes (phase volt.)
Yes (phase volt.)
Yes (phase volt.)

Available on 2-element
meter
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes (line to line volt.)2
Yes (line to line volt.)2
Yes (line to line volt.)

BGX501-856-R02, CewePrometer User Manual

Page 27 of 80

Current
THD current
Amplitude current harmonics (231)4
Phase symmetry current
Phase angle total
Phase angle per phase
Voltage unbalance

4.3.2

Yes (L1, L2, L3)


Yes (L1, L2, L3)
Yes (L1, L2, L3)
Yes
Yes
Yes
Yes

Yes (L1, L3)


Yes (L1, L3)
Yes (L1, L3)
4
Yes
Yes
No
Yes

Update frequency

The update frequency for instant values is proportional to the frequency of the measuring voltage. With a 50 Hz
measuring voltage, updating occurs 12.5 times per second, and at 60 Hz, 15 times per second. Instant values
can be read up to twice per second via the serial port when it is set to 19200 baud.

4.3.3

Accuracy

The table shows typical accuracy for a CewePrometer with accuracy class 0.2 for a selection of instant values.
Instant value
Voltage amplitude
Current amplitude
Current amplitude
Frequency
Power

Range
Umin - Umax
5 % of Imax - Imax
15% of Imax
4763 Hz
1 % of Imax - Imax

Power factor

At PF=0.5 and current 5% of


Imax - Imax
>=1% of Un

Voltage amplitude,
harmonics
Voltage amplitude,
harmonics
Current amplitude,
harmonics
Current amplitude,
harmonics
Voltage unbalance

Accuracy better than:


0.1% of reading
0.1 % of reading
0.05 % of Imax
0.02 % of reading
Corresponds to meters class
according to energy measurement
standard
0.1 % of reading
5% of reading

<1% of Un

0,05% of Un

>=3% of In

5% of reading

<3% of In

0,15% of In

Umin - Umax

0.5 %

Calculated from the voltages fundamental vectors.

The harmonics for voltage on the 2-element meter are to be seen from the standpoint of the voltages being Dconnected internally.
3

Current L2 is calculated internally in the 2-element meter for monitoring.

The value can be read in CeweConfig and via the communication protocol but cannot currently be presented
on the display (meter firmware 1.2.0).
Page 28 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.3.4

Prefix for units in the display

The presentation for units and the number of decimals depends on the magnitude of the value.

4.3.5

Harmonics measurement

Harmonics numbers 2 to 31 are measured for all currents and voltages. At a fundamental frequency of 50 Hz,
the second harmonic is 100 Hz, the third harmonic is 150 Hz, etc. Both the harmonics amplitude and phase
angle are measured and included in the calculation of power and energy, and can be read via the meters
communication protocols. In CeweConfig, harmonic amplitudes are presented with a diagram.

4.3.6

THD

THD stands for Total Harmonics Distortion and is a measurement of the amount of harmonics present in a
signal. Voltages and currents THD can be read via CeweConfig and on the display.

4.3.7

Harmonics on 2-element meter

The harmonics measurements of voltage on the 2-element meters should be seen from the standpoint of the
voltages being D-connected internally in the meter. The harmonics measured are the vector sums of the
phases harmonics.

4.4

Digital inputs and outputs

The CewePrometer has several inputs and outputs that can be configured to perform various tasks. Both inputs
and outputs are protected against over voltages by varistors. They also have an isolated interface between the
electronics and the surroundings to ensure personal safety. For electrical data on the meters inputs and
outputs, see Appendix H Connection and General Details (pg.75).

4.4.1

Inputs

The inputs can be configured as follows:


Not used
The input is not used.
Finish historical period
An incoming pulse will result in the present period ending and registers being copied to historical
registers. For a pulse to finish historical period, it is also necessary that the historical registers be
configured to allow this. For more information, see the section Historical registers (pg. 40).
Pulse input
To register pulses from pulse-producing units, such as energy meters or water meters, pulse inputs are
used. Incoming pulses are accumulated in registers called external registers. There is an external
register connected to each input on the meter. For external registers, a factor is configured by which the
number of incoming pulses is multiplied. Prefixes and the number of decimals can also be configured for
the registers. Moreover, the registers can be configured with descriptive texts.
Time synchronisation
When incoming pulses are received, the meters clock is synchronised at a specific interval For
available synchronisation intervals and more detailed information on time synchronisation, see the
section Meter clock (pg. 25).
Rate input
Up to three digital inputs can be configured to control the active rate. Each input will correspond to a bit
and the significance is also defined for the digital input. A high level on the input will signify that the bit is
1 while a low level will signify 0. How the digital input levels are mapped to rates is defined in the
Time of use panel (pg. 41).
4.4.1.1

Registration of pulses

The meter registers pulses on positive or negative flanks, depending on if the input is set to inverted or not. A
pulse must be at least 16 ms long to be guaranteed of being detected by the meter. The maximum pulse width
that the meter can handle is 60 s. By setting limits for maximum and minimum pulse lengths, the meter can be
Public

BGX501-856-R02, CewePrometer User Manual

Page 29 of 80

limited as to what it detects as a valid pulse. Pulses with lengths beyond the established limits are ignored. The
occurrence of too long or too short pulses can also be configured to be recorded in the event log.
VCC

GND

Pulse
length
Pulse length
(inverted input)

The figure shows pulse lengths when an input is inverted or non-inverted, respectively.

4.4.2

Outputs

The outputs can be configured as follows:


Not used
The output is not used.
Pulse output
The output is used to pulse an energy type that the meter is measuring. A pulse constant is specified for
the output as pulses/unit, primary or secondary, and the pulse length is specified for all pulse outputs.
The shortest possible pulse length is 40ms. Pulses are not allowed not come too often, and because of
this, there is a relationship between the pulse length and the specified pulse constant that maximises
the pulse frequency to 1000/(pulse length(ms) * 2).

Pulse

Gap

Maximum pulse frequency at outputs limited so that the gap is at least as long as the pulse length.
Remote control
With this function, the output can be made active or inactive by sending commands to the meter via the
IEC62056-21/IEC1107 protocol. This functions could be used control anything that can be controlled
with a digital relay output.
Alarm output
When an output is set to functions as an alarm output, one or more of the user-defined alarms can be
chosen to indicate at the output. When an alarm occurs, the output switches to active, and when the
alarm state ceases, the output returns to inactive. In the section Alarms (pg. 36), user-defined alarms
are described and how they can be configured.
In contrast to the other selectable functions for outputs, alarm outputs can be inverted. Note that outputs
are inverted via firmware. If the meter loses its auxiliary power, the relay will open, regardless of it is
inverted or not.
End of MD period (maximum demand period)
At the end of a set MD period, the output will go active for one second before returning to the inactive
state. See the section Maximum demand (pg. 38).

Page 30 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.4.2.1

Output states

An active output means a closed relay when the output is not inverted. When the output is inverted, the active
relay is open. The output can only be inverted when used as an alarm or pulse output The CewePrometer
outputs are of the solid-state type and when the meter is turned off, they are open.
4.4.2.2

Meter variants

inputs/outputs

CewePrometer-W

CewePrometer-R

0/0

0/12

2/10

4/6

4/8

Public

BGX501-856-R02, CewePrometer User Manual

Page 31 of 80

4.5

Display sequences

The following is a description of the function properties of CewePrometers display sequences. The section
Display sequences (pg.32) describes how to navigate in the display sequences via the meters buttons, and
Appendix A - Display Layouts (pg.50) lists all of the CewePrometers available display layouts.

Menu for choosing one of the four display sequences. The names of the sequences can be configured.
The CewePrometer is equipped with a graphic display that can show the information available in the meter. To
organise the information, there can be up to five display sequences with a maximum of 40 selectable display
layouts in each. Each display sequence can be given a name that will be presented on the display.
Display sequence five is only accessible via the sealed button under the front panel window. The front panel
window can be sealed to provide additional security. For this reason, it is appropriate that display layouts with
sensitive information and sensitive functions be placed in display sequence five.

4.5.1

Automatic display cycling

Automatic display cycling means that the display layouts in one or more display sequences are automatically
cycled by the meter. If, for example, display sequences 1 and 3 are configured for automatic display layout
cycling, the meter will first cycle the display layouts in sequence 1 from the first to last layout, and then continue
with sequence 3. After the last layout in sequence 3, cycling restarts with the first layout in sequence 1. The
display layouts cycle with a configurable delay of 1 to 30 seconds. If a user manually navigates in the display
sequences via the meter's buttons, cycling automatically stops and continues again after one minute.

4.5.2

Passwords and security

The display sequences can be configured to be password protected to limit access for various users. When a
user chooses a password-protected display sequence via the meters buttons, a password entry field is
displayed. Only a correctly entered password gives access to the display sequence and to the display layouts
that are included in it. A password can be up to six characters long and include the characters A-Z, 0-9 and
:;<>=?@. Passwords are not case-sensitive.
Note1: Password cannot be used on the first active display sequence.
Note2: If a password-protected display sequence is configured for automatic display layout cycling, password
protection is deactivated.

4.5.3

Automatic return to first display layout

One minute after a user has stopped navigating in the display sequences, the CewePrometer returns to the first
display layout in display sequence 1 if automatic display layout cycling is not activated for any display sequence.

4.5.4

Locked (required) display sequence

The meter can be configured to not allow any changes of display sequence 4. This setting (Block configuration
of display sequence 4) is available in the Communication and Security form. The setting can only be changed at
access level 5.
Since access level 5 typically requires the security hardware jumper, this feature can be used to enforce a
display sequence that cannot be changed or deactivated using CeweConfig.

4.6

Communications and security

All CewePrometers are equipped with an optical port for communication. The meter can be optionally equipped
with one or two (three on the rack meter) additional communication ports with RS232, RS422 (RS485) or
Ethernet interfaces. CewePrometer supports the IEC62056-21 (formerly IEC 1107) and on the additional ports

Page 32 of 80

BGX501-856-R02, CewePrometer User Manual

Public

also the DLMS/COSEM protocol. For more information on protocol support, see the document CewePrometer
meter reading.

4.6.1

Communication speed

The meters optical port always starts with a baud rate of 300 bps, regardless of what is configured, before
shifting over to the specified communication speed. This means that software (for example, CeweConfig) that
communicates with the meter via the optical port does not need to know the speed that the meters optical port
is set to. The optional ports designated as communication ports #1 and #2 differ in this respect. They start at the
specified baud rate from the beginning, which means that connected software must be aware of the speed to be
able to communicate. Communication port #1 can be set at a speed of between 300 bps and 19200 bps, and
communication port #2 can be set at a speed of between 1200 and 19200 bps. The optical port can be set at a
speed of between 300 and 9600 bps.

4.6.2

Modem initiation

If a modem is connected to one of the optional ports, a modem initiation string can be configured that the meter
sends via the serial port. The initiation string can be used to set the correct communication settings for the
modem and can consist of AT-Commands. The meter sends the initiation string when the meter is turned on
and thereafter every tenth minute. During ongoing communications, the meter waits to send the initiation string
until communications has stopped.

4.6.3

Bus address

A bus address can be defined for any serial communication port in the meter and shall have a value of 16 or
higher. This setting is only used for the DLSM/COSEM protocol. See the document CewePrometer meter
reading for more details.

4.6.4

Security

The meter has five authorisation levels that can limit access to the meter during communication via any of the
meters communication ports. Authorisation levels 1 and 2 are password-protected. Authorisation levels 3 to 5
may be protected by passwords or by a circuit board jumper.
Authorisation levels
1

Provides access to reading.

Provides access to everything in level 1 plus access to set the clock and
finish historical periods (also resets maximum demand values).

Provides access to everything in level 2 plus access to configure the


meter.

Provides access to everything in level 3 plus access to transfer new


firmware to the meter.

Provides access to everything in level 4 plus access to calibrate the


meter, reset registers and change certain security setting.

4.6.4.1

Limitation of total access attempts

The meter limits the total number of access attempts to six when incorrect passwords are entered. At the
seventh attempt, the meter blocks access whether the password is correct or not. The block is in effect until the
next hour shift. After that, new password attempts may be made.
4.6.4.2

Passwords

A password consists of up to 12 case insensitive alpha-numerical characters. The authorisation check may be
deactivated for a level by deleting the password. When connecting to the meter, access is granted to the highest
level that is lacking password regardless of the password given by the user.
If the setting Require COP password compliance (min length 6) is activated, a new password is required to be
at least 6 characters. The setting can only be changed at access level 5.

Public

BGX501-856-R02, CewePrometer User Manual

Page 33 of 80

4.6.4.3

Security settings

The following security settings modify what can be configured at what access level. The settings are of the type
active/not active, and can only be changed at access level 5.

Permit measuring configuration only at level 5

Block configuration of transformer compensation

Block configuration of display sequence 4

4.6.4.4

If this setting is active, settings in the


measurement form can only be changed at
access level 5.
If this setting is active, transformer compensation
cannot be changed at all.
If this setting is active, it is not possible to change
the content of display sequence 4, or change its
name or activation.

Access restriction via circuit board jumper

Inside the CewePrometer, there is space for a circuit board jumper that provides access to authorisation level 5
when fitted. If the meter is connected with authorisation at level 5, the function of the jumper can be modified.
Security can be heightened by requiring the jumper even for lower authorisation levels down to level 3. Security
can also be relaxed by making authorisation level 5 accessible via a password. Cewe Instrument can provide a
technical fact sheet, tfcr0004, that describes the procedure for opening the meter and fitting the jumper.
4.6.4.5

Access restriction for measurement configuration

Generally the meter allows to be reconfigured at access level 3. This function requires level 5 for measuring
configuration.

4.7

Loggers

The CewePrometer has two identical, parallel and individually configurable loggers. That which is described in
this section applies both to logger 1 and logger 2.

4.7.1

Overview

A logger in a CewePrometer can log values for instant quantities, energy registers and external registers. Some
quantities can be logged both by phase and as total values for all three phases, others only as total values. The
table provides an overview of quantities that can be logged. Certain instant values in the table are not available
in 2-element meters and thus cannot be logged; see the section Instant values (pg. 27).
Quantity

By phase

Total

Active energy import


Active energy export
Reactive energy import
Reactive energy export
Reactive energy inductive
Reactive energy capacitive
Reactive energy QI
Reactive energy QII
Reactive energy QIII
Reactive energy QIV
Apparent energy import
Apparent energy export
Phase voltage
Line to line voltage
Current
Active power
Reactive power
Apparent power

Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

Page 34 of 80

Instant
values
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes

BGX501-856-R02, CewePrometer User Manual

Public

Frequency
Phase angle
Power factor
THD voltage
THD current
External registers 18
Voltage harmonic 1-31
Current harmonic 1-31
Voltage unbalance
Active energy import Delta
Active energy export Delta
Reactive energy import Delta
Reactive energy export Delta
Reactive energy inductive Delta
Reactive energy capacitive Delta
Reactive energy QI Delta
Reactive energy QII Delta
Reactive energy QIII Delta
Reactive energy QIV Delta
Apparent energy import Delta
Apparent energy export Delta

Not applicable
Yes
Yes
Yes
Yes
Not applicable
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No

Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No

Energy is logged as register values, i.e. at each logging occasion the current registers values is logged. Based
on these register values, the reading software can present the energy as register values, periodic energy or as
average power. CeweConfig provides all three alternatives.
Instant values can be logged as average, maximum or minimum value during the logging interval or as the
instantaneous value at the end of the logging interval. Maximums and minimums are detected based on 1 sec.
interval snapshots, and average is calculated based on 1 sec. interval snapshots.

4.7.2

Logging interval and total channels

A logger can store data in 1 to 50 channels. Common for all channels in a logger is that the logging interval that
can be configured from one minute up to one hour. A loggers capacity is dependent on number of channels and
logging interval. When the logger is full, the oldest values will be written over. The table shows the capacity in
number of days before the oldest value is written over.
Capacity in days
Number of logging channels
Logging
interval (min)

4.7.3

10

30

50

21

14

10

8.6

7.2

6.2

5.4

4.8

4.3

3.9

1.4

0.8

43

28

21

17

14

12

10

9.6

8.6

7.9

2.8

1.7

108

72

54

43

36

31

27

24

21

19

7.0

4.2

10

217

144

108

86

72

62

54

48

43

39

14

8.5

15

326

217

163

130

108

93

81

72

65

59

21

12

20

435

290

217

174

145

124

109

97

87

79

28

17

30

652

434

326

260

217

186

163

144

130

118

42

25

60

1304

869

652

521

434

372

326

289

260

237

84

51

Storage of logged values

Logged values are saved with time stamps, tariff information and flags that indicate events that have occurred
during the logging interval.
Public

BGX501-856-R02, CewePrometer User Manual

Page 35 of 80

The time stamp indicates the end-time. If the logging interval is configured to one hour, a value with the
time stamp 15:00 refers to the period 14:00 to 15:00.
Tariff information indicates active rates for energy and power during the past interval.
To indicate events or states during an interval, a logged value can be stored with one or more flags.

Event or state
Time adjusted
Disturbed

Alarm

Parameter
changed
Incorrect energy
direction
Daylight savings
time
Voltage
loss/missing
Invalid value

Battery
Power loss

Name of flag Explanation


T
During the past interval, the meter clock has been adjusted either instantaneous
or a sliding adjustment is in progress.
D
The past interval is incomplete. For example, an interval shortened by the meter
being without auxiliary power or if the logging memory has been reset. The first
value after the logging memory having been configured will thus always be
indicated with "Faulty value (the logging me mory is reset in conjunction with
reconfiguration).
A
In conjunction with user-defined alarms being configured, it may be specified that
an alarm will also be indicated with logged values. When a user-defined alarm has
triggered during the past interval, this is indicated with the flag Alarm.
P
The CewePrometers configuration, calibration or initiation has changed. Which of
these three the flag refers to can be seen in the event log.
R
The CewePrometer can be configured for a normal energy direction, import or
export. If the meters energy direction deviates from this, this is indicated with the
flag Incorrect energy direction.
S
Daylight saving time has been in effect during the past interval.
V

During the past interval all measuring voltages have been lost or missing.

To be able to guarantee that a logged value is correct, it is logged with a control


sum. If the check sum is incorrect when the value is read, this is indicated with
Invalid value. This is a rare event, but could occur if the meter is subjected to
powerful, external electromagnetic interference.
Estimated battery lifetime is up.
During the past interval have the meter been without auxiliary power.

B
O

For several of the flags, additional information can be viewed in the event log. A more exact time for events
is specified in the log.
Note: When power is calculated from logged energy values, the resulting values will be somewhat more precise
than when power is logged directly. This is because power is logged as an average value of instant values. The
instant values are read twice per second, while energy is accumulated continuously.

4.7.4

Behaviour after power loss

When the meter starts again after loss of auxiliary power, any energy accumulated up to the power loss will be
stored with a time stamp immediately following the power loss.
The incomplete log record before the power loss will have the following limitations:
If any instant values were configured to be logged, they will be recorded as 0.
The only notification flags that are handled are D, S and O.
If tariff is controlled using rate input, tariff will be recorded as 1.

4.8

Alarms

The CewePrometer is equipped with alarms to be able to indicate when measured quantities are over or under
a configurable limit value. The meter enters the alarm state when the limit value is reached. An alarm is
generated only after the alarm state has continued for a configurable time (delay). Alarms are configurable by
the user and are therefore called user-defined alarms. For the CewePrometer 1.2.0 or earlier, the maximum
delay is 64 seconds.
Note: There are alarms and events that cannot be configured, but instead, are always active. Examples of such
alarms are indication that the clock has been changed or that an auxiliary power loss has occurred. For more
information, see the section Event log (pg. 38).
Page 36 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.8.1

Overview

For most user-defined alarms, the limit value is specified as a percentage of the nominal value, which is the
configured, nominal primary value (current, voltage or power). For 3-element meters, the limit value corresponds
to phase voltage, and for 2-element meters, line to line voltage. The following table provides an overview of
available alarms.
Alarm
Low voltage

High voltage
Low power factor
Voltage unbalance

Current unbalance

Low active power


High active power
High THD voltage
High THD current
High harmonic voltage

High harmonic current

Reverse energy direction

Voltage phase missing

Internal error
Current without voltage

4.8.2

Alarm state applies when


The average value of the voltages is
beneath the nominal voltage (limit value)
Note:
No alarm applies when all phases are
unavailable and all phases are missing
checkbox is checked.
The average value of the voltages is above
the nominal voltage limit value.
The power factor for the 3-phase system is
beneath the limit value.
A voltage deviates percentage-wise from the
average value of all voltages more than the
limit value. See definition on pg. 69
A current deviates percentage-wise from the
average value of all currents more than the
limit value.
The 3-phase systems total power is
beneath the nominal power limit value.
The 3-phase systems total power is above
the nominal power limit value.
The average value of THD for all voltage
phases exceeds the limit value.
The average value of THD for all current
phases exceeds the limit value.
An overtone (2nd to 31st) relative to the
basic tone on same voltage phase exceeds
the limit value.
An overtone (2nd to 31st) relative to the
basic tone on same current phase exceeds
the limit value.
The phase angle for a phase deviates by
more than 90 degrees from another phase.

One or more voltage phases are missing.


Note:
No alarm applies when all phases are
unavailable and all phases are missing
checkbox is checked.
See the section Event log (pg. 38).
Current is flowing above pre-defined limit
through a particular phase but voltage is
missing

Comments

The event log identifies the


phase and harmonic no.
The event log identifies the
phase and harmonic no.
The event log identifies the
phase with the deviating
energy direction. This alarm
is not available on 2-element
meters.
The event log identifies the
missing phase or phases.

The event log identifies the


current through a particular
phase but voltage is missing

Indication

Alarms are always stored in the event log. Alarms can also be configured to indicate in one or more of the
following ways:
Alarm LED on meter front
Changed digital output level
Indication of a logged value with a flag
Public

BGX501-856-R02, CewePrometer User Manual

Page 37 of 80

The alarm LED stops flashing and the digital output returns to inactive low after the alarm state passes.

4.9

Event log

The CewePrometer has a number of defined events and alarms that are stored in the meters event log when
they occur. The event log can contain a maximum of 100 events. Thereafter, the oldest will be removed to make
room for the new. The meter has a counter for the total number of events that have occurred since the latest
reset.
An event is represented by a time stamp and a code that indicates what has occurred. See Appendix B - Events
and Configuration Log (pg.58) for a complete list of all events. For certain events, data is also stored for the
events, for example, which phase the event concerns.
Events are divided into three categories:
User-defined alarms
The meter has a number of alarms that when they occur, generate an event in the event log. The
alarms each have an individual configuration that determines the conditions for when an alarm is to be
activated. See the section Alarms (pg. 36).
Meter events
The meter is also equipped with a number of alarms that are not configurable by the user, so-called
meter events. These have set conditions and are stored only in the event log. Examples of meter events
are auxiliary power loss and clock resetting. A complete list of meter events is in Appendix B - Events
and Configuration Log (pg.58)
Internal errors
The contents of the internal data structures, such as configuration and energy registers, are checked by
the meter. If an error is detected in one of the data structures, it is designated as an internal error. If an
internal error is indicated, the event log should be checked for related information, and suitable actions
should be taken. Internal errors are listed in Appendix B - Events and Configuration Log (pg.58).

4.9.1

Display of events

The event log can be viewed on the meters display if the display layout Events is configured to be included in
one of the meters display sequences. Only the time stamp and event code are shown on the display. A more
detailed description of the meter's events can be viewed in CeweConfig, which converts the code into plain text
and displays any related data. Via CeweConfig, the event log can also be printed out or saved to a file.

4.10 Configuration log


Any changes to measurement configuration are logged in the meters configuration log. The configuration log
can contain a maximum of 100 changes. Any further changes will be denied, until the configuration log is
cleared. Clearing of the configuration log can be done with the command Tool/Reset/Event log(configuration),
and requires access level 5.
The configuration log can be viewed in CeweConfig. Each entry describes which setting was changed, and lists
the old value (hexadecimally encoded). The configuration log can also be included in a display sequence on the
meter.

4.11 Maximum demand


Maximum demand is the highest average value of, for example, active power during a historical period. The
average value is calculated for an interval and compared with a previously stored value. If the new average
value exceeds the previously stored value, it becomes the new value for maximum demand. When a historical
period ends, the current maximum demand values are copied to historical registers and then reset. The
CewePrometer always stores the three highest average values from three different days.

Page 38 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.11.1 Overview
Up to eight quantities can be saved in the maximum demand registers, which makes a total of 24 values with
time stamps for when they occurred. The table shows the types of energy that can produce maximum demand
values.
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Reactive energy inductive
Reactive energy capacitive
Reactive energy QI
Reactive energy QII
Reactive energy QIII
Reactive energy QIV
Apparent energy import
Apparent energy export

The calculation interval for average values determines the period during which average values are calculated.
At the end of the interval, the new average value is compared with the previous and possibly stored as a new
maximum demand value. The calculation interval can be chosen between 1 and 60 minutes in the following
predefined steps: 1, 2, 3, 4, 5, 10, 15, 20, 30 and 60 minutes.
Example: A historical period has just been finished and all maximum demand values have been reset. The
meter is configured with a calculation interval of 30 minutes and active power as the quantity for which to
calculate the average value. The table is read from top to bottom and illustrates what will be stored in the
maximum demand registers at the various times.

Point in time

Average
power

12:59, 4 July

Highest value

Second highest

Third highest

13:00, 4 July

90 kW

90 kW 07-04 13:00

13:30

89 kW

90 kW 07-04 13:00

14:00

91 kW

91 kW 07-04 14:00

00:00, 5 July

75 kW

91 kW 07-004 14:00

75 kW 07-05 00:00

00:30

95 kW

95 kW 07-05 00:30

91 kW 07-04 14:00

00:00, 6 July

93 kW

95 kW 07-05 00:30

93 kW 07-06 00:00

91 kW 07-04 14:00

16:00, 7 July

94 kW

95 kW 07-05 00:30

94 kW 07-07 16:00

93 kW 07-06 00:00

Note: There is never more than one maximum demand value for one day.
4.11.1.1 Cumulative Maximum Demand
For each MD value there is an associated accumulating register. When a historical period is finished, the MD
values are accumulated to these registers.

Public

BGX501-856-R02, CewePrometer User Manual

Page 39 of 80

4.11.1.2 Rising Demand


CewePrometer has a function to show the Rising Demand in the display. The value is presented as a
continuously increasing demand until the end of the MD period. During the demand period the display also
shows the elapsed time of the period. When the MD period ends this counter is set to zero.

4.12 Historical registers


Historical registers are used by the CewePrometer to store current register values at defined points so as to be
able to read them later. Stored in historical registers are all maximum demand values, external registers, TOU
registers and energy registers, with the exception of energy registers by phase. The historical registers are time
stamped to indicate when storage occurred. The CewePrometer can store up to 15 historical registers.
Date and time
Energy registers

Maximum demand
values

Time of use registers

External registers

Historical register includes a number of stored registers, and dates/times when they were stored.
4.12.1.1 Finish historical period
By finishing a historical period, the current registers values are stored in historical registers and the maximum
demand values are reset. When a period is finished, an event is stored in the meters event log. Periods can be
finished in various ways:
Via meter button

The period is finished when the meters Menu/Apply button is held


down for more than two seconds when the display layout Finish
period is active.
This requires both that the historical registers are configured to
permit finish via the meter button and that a display layout for this
is entered in a display sequence.

Via CeweConfig

At the end of the month

Via digital input.

The period is finished when a command is given from


CeweConfig or third-party software.
The period is finished when the meter clock reaches the end of
the month.
The period ends when a pulse is received at a digital input on the
meter.
This requires both that the historical registers are configured to
permit ending via a digital input and that an input is configured for
this purpose.

Note: The display layout Finish period will only work if the meter is configured to permit ending a period via a
button.
4.12.1.2 Lock out time for finish historical period
The Lock out time prevents the user to create a new historical period within a configurated time.

Page 40 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.13 Time of use


Time of use is a function that enables energy to be divided up into various registers depending on the rate that
applied when the energy was measured. In the CewePrometer, tariff structures can be stored that switch rates
at predetermined times according to a configurable pattern. A tariff structure consists of seasons, day types and
special days or rate input. The maximum number of rates is eight.
Day types specify how rates change during a 24-hour day.
Seasons specify the day types that apply during the days of the week, Monday to Sunday.
Special days specify the day type that applies on a certain date.
Rate input can be used to control active rate depending on the state of digital input signals.

4.13.1 Tariff structures


In the CewePrometer, there are two separate tariff structures. Both tariff structures have a set of day types,
seasons and special days. By setting a starting date for a tariff structure, it can be configured before it goes into
force.

4.13.2 Day type


In the CewePrometer, there are 16 day types (AP). A day type specifies witch rate, from a maximum of eight,
should apply when during the day. 16 changing points per day may be specified. A day type can be connected
to a day of the week in a season or to a special day.

4.13.3 Season
A season refers to a period. During this period, the season defines the day types that will apply during the days
of the week. In the CewePrometer, there are 16 seasons per tariff structure. The seasons are arranged in a
sequence where one season replaces the previous at a predetermined date.

4.13.4 Special days


Days that change rates according to a pattern that is not covered by linking day types to seasons (such as
holidays) are called special days. A special day specifies the day type that applies on a certain date. Special
days can be configured to apply every year on the same date or for a single year. In the CewePrometer, up to
30 special days per tariff structure can be configured.

4.13.5 Rate input


Rate input structures are the only option in Time of use except TOU registers if Rate input are chosen in digital
input. It is not possible to combine Rate input with other types of rates. Two to eight different rates can be
configured for the energy registers and maximum demand. The rates for the energy register and maximum
demand can be configured independently of each other.

4.13.6 TOU registers


An energy register or external register that is chosen to be divided into the rates is a TOU register. There are
eight TOU registers and each TOU register has separate registers for eight rates.

4.13.7 Maximum demand values and tariffs


Maximum demand values are stored together with information on which rate applied when registered. For one
and the same day, there can be separate day types for energy and maximum demand values.
Example: The conditions are Monday to Saturday, rate 2 applies from 7:00 in the morning until 17:00 in the
afternoon. For the rest of the day, rate 1 applies. On Sundays, rate 1 applies around the clock. During the
summer months, 1June to 31 August, rate 1 applies around the clock. On Christmas Eve, 24 December, rate 1
applies around the clock. For maximum demand values, rate 3 always applies. It is active energy import that is
divided in to different rates.

Public

BGX501-856-R02, CewePrometer User Manual

Page 41 of 80

Day types
Three day types must be configured. Day type A to apply to energy during the autumn, winter and spring. Day
type B to apply during the summer months, and day type C for maximum demand values throughout the year.
Day type A
00:00
Rate 1
07:00
Rate 2
17:00
Rate 1

Day type B
00:00 Rate 1

Day type C
00:00 Rate 3

Seasons
Two seasons must be configured. The first season will apply during the summer period and the second the rest
of the year. The season that applies from 1 September will also apply from 1 January to 31 May.
06-01

Energy
MD

A
C

A
C

A
C

A
C

A
C

A
C

B
C

09-01

Energy
MD

B
C

B
C

B
C

B
C

B
C

B
C

B
C

Special day
For rate 1 to apply all of Christmas Eve, a special day must be configured. Because no year is specified, the
special day will apply every year.
12-24

Energy
MD

C
C

TOU register
A TOU register is configured to accumulate active energy in several registers for the different rates.

4.14 Transformer compensation


Transformer compensation is a function for compensating for measurement errors in instrument transformers
and for losses in power transformers. The function enables the CewePrometer to present measurement values
for which errors and losses have been compensated. The formulas used in the meter are presented in Appendix
F Calculation Principles (pg. 69).
Changing the transformer compensation can be blocked by the security setting Block configuration of
transformer compensation. This setting can only be changed at access level 5.

4.14.1 Overview
The tables present an overview of the transformer compensations in CewePrometer.
Instrument transformer compensations
Name
Value to entered
Voltage error L1, L2, L3
Amplitude error as percent
Phase angle in minutes
Current error L1, L2, L3
Amplitude error as percent
Phase angle in minutes
Power transformer compensations
Name
Copper losses, Total values
Iron losses, Total values

Page 42 of 80

Value to entered
Active loss as percent of nominal power
Reactive loss as percent of nominal power
Active loss as percent of nominal power
Reactive loss as percent of nominal power

BGX501-856-R02, CewePrometer User Manual

Public

4.14.2 Instrument transformer compensations


To compensate for errors in instrument transformers, their amplitude error in percent and phase angle error in
minutes are configured in the meter. One minute is equal to the angle 1/60. The errors can be specified
separately for all voltages and currents. When instrument transformer compensations are used, current and
voltage are affected, as well as all quantities that arise from these: power, energy, etc.

4.14.3 2-element meter


When voltage errors are compensated on a 2-element meter, this is done on line to line voltages L12, L23 and
L31 instead of on phase voltages. Only L12 and L23 are included in the calculation of power and energy.
Compensation of L31 has no significance in this respect. In compensation of current errors for 2-element
meters, only L1 and L3 can be compensated for because they are the only currents measured.

4.14.4 Power transformer losses


Power transformer losses consist of copper and iron losses. They are expressed as percentages of nominal
power. One value is specified for active loss and one for reactive. When compensation of losses is configured,
power, energy, power factor, etc. are affected but not current and voltage.
When copper loss are added per phase, the resulting copper loss is the average of the value.

Calculating loss values


Based on the nominal total power and the measured loss value in watts, a loss value can be calculated as a
percentage of nominal power. It is the loss value that is configured in the meter. Nominal power is calculated
with configured nominal current and voltage.
Nominal power:

Powernom

Loss value: Loss value

Currentnom Line voltagenom

Loss / Powernom 100

4.15 Power quality


Power quality encompasses voltage monitoring and harmonics measurement. Harmonics measurement is
described in the section Instant values (pg. 27).

4.15.1 Voltage monitoring


Voltage monitoring monitors three states: swells (overvoltage), sags (undervoltage) and interrupts. Monitoring is
activated by configuring the limit values for sags and swells, and is deactivated by setting the limits to zero. The
limits are expressed as percentages of configured nominal voltage.
Example: For an upper limit of 110% and a lower limit of 90%, and the configured nominal primary voltage of 10
kV, the limits attained are 9 kV and 11 kV primary.
For 3-element meters, the average value for phase voltage is monitored, and for 2-element meters, the average
value for line to line voltage is monitored.
4.15.1.1 Sags and swells
Sags and swells shorter than one second are registered by accumulating registers. If the state lasts longer than
one second, it is instead registered in the event log with a time stamp and duration. The accumulating counters
and the event log can be read in CeweConfig.
4.15.1.2 Interrupts
When the average value for voltage falls to under 10% of the configured nominal voltage, this is registered as
an interrupt in the event log with a time stamp and duration. Duration for an interrupt of less than three seconds,
and down to 160 ms, is presented as "< 3 s".

Public

BGX501-856-R02, CewePrometer User Manual

Page 43 of 80

State
Sags and swells

Duration
160 ms5 1 s

Registered in
Accumulating counter

Duration presented as
Duration not specified

Sags and swells


Interrupt

> 1s
5
160 ms 3 s

Event log
Event log

Duration of state
<3s

Interrupt

>3s

Event log

Duration of state

4.15.2 Hysteresis
Hysteresis means that the limit for a state and the limit for when it is restored are different. This to avoid several
states being registered when the voltage level varies around a limit. The hysteresis limit is always midway
between the low or high limit and nominal voltage.
Primary voltage (example)

Percent

11 kV

110%

10,5 kV

105%

10 kV

100%

9,5 kV

95%

9 kV

90%

Limit for swells


Hysteresis limit
Nominal voltage
Hysteresis limit
Limit for sags

Duration sag

1 kV

10%

Limit for interrupt

Duration
interrupt

4.16 Miscellaneous
4.16.1 General information texts
General information texts are used in the CewePrometer for all types of information, such as the name of the
station where the meter is installed. The information texts can be shown on the meter's display and read with
CeweConfig. There are four information texts that consist of a label and an associated text. Both the label and
text can be up to 17 characters long. To present information texts on the display, display layouts for this can be
entered in a display sequence.

Example of general information texts where the label is "Owner" and the text "Cewe Instrument".

Applies to basic frequency 50 Hz. Corresponding time at 60 Hz is 130 ms.

Page 44 of 80

BGX501-856-R02, CewePrometer User Manual

Public

4.16.2 Language on display


The CewePrometers display can present texts in a number of languages. The following languages are available
in meter version 1.2.0 onwards.
Swedish
English
German
French
Italia

Public

BGX501-856-R02, CewePrometer User Manual

Page 45 of 80

5 Using the Display


This section describes how the CewePrometers display can be used to read measurement values and also to
control certain functions in the meter. The display layouts are arranged in display sequences. For details on
display sequences, see Display sequences (pg. 32). A complete listing of display layouts is presented in (pg.
50).
Quadrant indicator
In most display layouts, a quadrant indicator is shown in the lower-right corner. The quadrant indicator shows
the quadrant in which energy is currently being measured. See Appendix F Calculation Principles (pg. 69) for
a definition of quadrants.

Quantity

Unit

Quadrant I

Phase

Quadrant II
Quadrant III

Measurement value Quadrant indicator

Quadrant IV

Display layout
Import/Export
For quantities that can be Import or Export, a setting in the Display Sequence form controls whether Import is
shown as Imp or +, and correspondingly, whether Export is shown as Exp or -.

5.1

Voltage order display layout

When the CewePrometer starts, the display layout Voltage Order is always shown for about 15 seconds. The
display layout shows the order of the connected measurement voltages. If the voltage order is correct, the
current direction is indicated with a + or a -. If not all voltages are connected, Phase missing is shown on the
display. The current direction is indicated with a + if the currents phase angle is following its voltage with a
maximum deviation of 90; if it is not, a - is displayed.

Correct voltage order and current direction.

Reversed current direction on phase 1.

Reversed voltage order (no current direction shown).

Page 46 of 80

BGX501-856-R02, CewePrometer User Manual

Public

5.2

Navigating in display sequences

Use the buttons on the front of the CewePrometer to step through the display sequences. For more information,
see the Product Description (pg. 6) section for button placement.
Step forward
Step to next layout in the display sequence or moves upward in a menu.
Menu/Apply
The Menu/Apply button is used to open the menu where one of four configurable display sequences can be
chosen. The button is used to confirm choices or initiate other activities depending on the current display layout.
Step backward
Step to previous layout in the display sequence or moves downward in a menu.
Sealed button
A Short press to the sealed button provides access to the fifth display sequence. Press the button for about two
seconds to open the system menu. From the system menu, you can view program versions for all modules and
activate the trace function for the communication ports. For more information, see Using the display for
communication diagnostics (pg. 49)

5.3

Display layouts with choices

In certain CewePrometer display layouts, active choices can be made.

5.3.1

Time of Use

TOU register 2 of 8, rate 1


To choose between rates, press the Menu/Apply button for about two seconds. Use the step buttons to change
rates and Menu/Apply to confirm your choice. The rate will continue to apply for other display layouts that show
TOU registers.

5.3.2

Finish historical periods

Layout for finishing historical periods. #5 indicates total number of previously finished periods.
Finish a historical period means that all registers are saved and maximum demand values are reset. The meter
may be configured so that periods may be finished by pressing a button on the meter. For more information, see
the section Historical registers (pg. 40). Additionally, the display layout shown above must be included in a
display sequence. To finish a period, press the Menu/Apply button for about two seconds.

5.3.3

Public

Historical registers

BGX501-856-R02, CewePrometer User Manual

Page 47 of 80

Historical register period 02, finished 12 July 2005, 14:14.


There are display layouts for viewing historical energy registers, external registers and maximum demand
registers. The title line with the date indicates that the display layout is showing a historical register. To step
between periods, the Menu/Apply button must first be pressed for about two seconds. The step buttons are then
used to change periods. Press Menu/Apply to return to stepping between display layouts. The period will
continue to apply for other display layouts. See Historical registers (pg. 40).

5.3.4

Historical TOU registers

Historical TOU register

Switching historical periods

Switching rates

Historical registers also contain TOU registers, and for these, rates also can be changed. Choose historical
period and then press Menu/Apply to be able to change rate with the step buttons. Press Menu/Apply to return
to stepping between display layouts.

5.3.5

Logger

Press Apply for about two seconds


to browse through logger items.

Logger

There are display layouts for viewing logger 1 and logger 2. Press Menu/Apply for about two seconds to view a
list of all logger items. Each item starts with date and time, followed by a row showing the notification flags for
that item. Then follows a row for every active channel in the logger, with value and unit.

5.3.6

Events

No of events.

Press Apply for about two


seconds to browse through the
events.

The meter registers different types of events; see the section Event log (pg. 38). This display layout shows how
many events are saved in the meter. Press Menu/Apply for about two seconds to view a list of events in
chronological order with ID numbers. Explanations of these IDs are in Appendix B - Events and Configuration
Log (pg. 58).

5.3.7

Configuration log

No of changes.

Press Apply for about two

Page 48 of 80

BGX501-856-R02, CewePrometer User Manual

Public

seconds to browse through the


changes.
The configuration log records changes to measurement configuration. This display layout shows the number of
changes that has been recorded. Press Menu/Apply for about two seconds to view a list of changes in
chronological order. Every entry is shown with time, ID of the changed configuration and the old value. A list of
the configuration changes monitored by the configuration log, and corresponding IDs are in Appendix B - Events
and Configuration Log (pg. 58).

5.3.8

Confirming alarms

By pressing Apply for about two seconds, alarms of the type internal error in the meter can be
confirmed/acknowledged. For more information on internal errors, see section Event log (pg. 38).

5.4

Using the display for communication diagnostics

To facilitate troubleshooting of communications with the meter, there is a trace function integrated into the
CewePrometer. The incoming characters that the meter registers are presented on the display. The function can
be chosen from the system menu, accessible by pressing the sealed button for about two seconds. Use the step
buttons to choose one of the three communication ports: trace opto, trace port 1 or trace port 2. Confirm with the
Menu/Apply button and an empty display with a cursor at the upper-left corner will be shown.
Note that the procedure described here assumes the IEC62056-21/IEC1107 protocol.

Layout for Trace to file for communications with the meter.


To check if communication is working:
Open an empty display.
Connect a PC or other meter reading unit to the meter.
Check the display after the call to the meter: /?sssssss!CRLFAK0Z1CRLF. The sssssss string
represents the meters serial number and it is only included when the meter must be addressed. Z can
be a digit between 0 and 7.

Functioning communications with the meter.


If you do not attain these results, try one or more of the following:
Check the cabling and connections between the meter and reading unit.
Check that the meter and the reading unit have the same baud rate.
With RS422 communications, it is important that there is a termination resistor installed on the
communication cable. Problems arise if the resistor is not installed or incorrectly located. For more
information, see the handbook for the RS422 converter.
Public

BGX501-856-R02, CewePrometer User Manual

Page 49 of 80

Appendix A - Display Layouts


This appendix presents the layouts that can be viewed in the CewePrometers display sequences.

Instant Values

Page 50 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Energy Registers

Graphs

Public

BGX501-856-R02, CewePrometer User Manual

Page 51 of 80

Maximum Demand Values

From top to bottom, the highest


to the third-highest maximum
demand value for the period is
displayed. R1 indicates the rate
that was active when the
maximum demand value
occurred.

This register adds one extra


decimal compared to energy
presentation.

The time is the elapsed time of


the demand period.

Historical Registers

Example of historical register


active energy import. Title line
with date and time shows that it
is a historical register.

Press Apply for about two


seconds to finish the period. #5
shows the no. of periods that
have been finished.

Historical TOU register.

Press Apply for about 2 seconds


to switch historical period.

Press Apply once more to


change rate.

Time of Use

TOU register 2 of 8.

Page 52 of 80

Current season S1. Active rate for energy


Egy and for maximum demand value MD.
Active day types for energy and maximum
demand value.

BGX501-856-R02, CewePrometer User Manual

Public

\Miscellaneous

One of four display layouts for


general information texts with
label Owner: and text Cewe
Instrument.

Total events.

Press Apply for about two


seconds to browse through the
events.

No of configuration changes.

Press Apply for about two


seconds to browse through the
configuration changes.

Logger

Press Apply for about two


seconds to browse through
logger items.

Constants for calibration LEDs


presented as secondary values.

Constants for calibration LEDs


presented as primary values.

Correct voltage order and current


direction.

Incorrect voltage order.

Incorrect energy direction on


L1.

Public

BGX501-856-R02, CewePrometer User Manual

Page 53 of 80

Ratios for current and voltage


transformers CT and VT.

Transformer Compensation

Pictures with OBIS Codes


Energy registers
For pictures containing rate (E 0), hold down Apply for two second to enter rate switching mode, where mode
can be changed by using up/down buttons. Push Apply again to leave the rate switching mode.

Active energy import.

Active energy export.

Reactive energy import.

Reactive energy export.

TI5 active energy import.

TI5 active energy export.

TI5 reactive energy import.

TI5 reactive energy export.

Active import with rate, here


showing rate 4.

Page 54 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Active export with rate, here


showing rate 4.

Reactive import with rate, here


showing rate 2.

Reactive export with rate, here


showing rate 6.

Historical Registers
In display pictures where a star is present (where the number to the right of the star signifies a certain historical
period, element F of the OBIS code), it is possible to switch between periods by holding down the Apply button
for two seconds, and then using up/down buttons. This mode is indicated by the top row in the display being
black. Push the Apply button again to return to normal mode.
In display pictures with both historical period and rate, the period can be changed as described above. By
pushing the Apply button again, the bottom row in the display turns black. This indicates a mode where the rate
can be switched by using the up/down buttons. Push the Apply button a third time to return to normal mode.

Historical Period Counter (VZ).

Historical period timestamp, here


showing historical period with VZ
= 1.

Active energy import for


historical period with VZ = 1.

Active energy export.

Reactive energy import.

Reactive energy export.

Active energy import by rate.


Here showing rate 1 for historical
period with VZ = 1.

Active energy export by rate.


Here showing rate 1 for historical
period with VZ = 1.

Reactive energy import by rate.

Reactive energy export by rate.

Historical Maximum Demand for


active energy import.

Historical Maximum Demand


for active energy export.

Public

BGX501-856-R02, CewePrometer User Manual

Page 55 of 80

External registers
An external register must have been configured for pulse input in the Digital I/O form to be available.
Furthermore, a rate register must be allocated for the external register for it to be available in rated version (E
0).
In rate pictures, hold down Apply for two seconds to be able to switch between rate 1 8 using up/down
buttons. Push Apply again to leave the switching mode.

External register #1 rate version,


here showing rate 2.

External register #2 rate version,


here showing rate 4.

External register #1, sum of all


rates (E = 0).

External register #1, sum of all


rates (E = 0).

Maximum Demand

Maximum demand for active


energy import.

Maximum demand for active


energy export.

Cumulative Demand

Cumulative demand for active


energy import.

Page 56 of 80

Cumulative demand for active


energy export.

BGX501-856-R02, CewePrometer User Manual

Public

Rising Demand

Rising demand for active energy


import.

Rising demand for active energy


export.

Miscellaneous

Logger #1 (Logger #2 not


available with OBIS codes).

Values of logger #1.

Present date.

Meter serial number.

Public

BGX501-856-R02, CewePrometer User Manual

Present time.

Page 57 of 80

Appendix B - Events and Configuration Log


Events
This appendix lists the events that can appear in the CewePrometer event log.
ID indicates the code that is displayed for an event on the meter's display. Category indicates one of the
following:
H

Meter event

User-defined alarm

Internal error

%1 and %2 represents data that is stored for the event.

Event

Data

Category

ID

Phase (%1) has reversed energy direction.

%1 indicates phase with reversed


energy direction.

The meters internal clock is changed to %1.

%1 indicates the time that the meter


was changed to. The time stamp for
the event indicates the time before
adjustment.

Energy registers have been reseted.

None

Logger #%1 is reset.

%1 indicates logger that is reset.

Auxiliary power loss on meter

None

Historical register reset.

None

Registers are transferred to historical period.


Maximum demand value reset.

None

Maximum demand registers has been reconfigured and therefore reset.

None

Logger #%1 has been re-configured and


therefore reset.

%1 indicates logger that has been


re-configured and reset.

Measurement voltage interrupt (duration %1). %1 indicates duration of the


interrupt.

14

Sag (duration %1).

%1 indicates sag duration.

15

Swell (duration %1).

%1 indicates swell duration.

16

Alarm for low measuring voltage.

None

17

Alarm for high measuring voltage.

None

18

Alarm for low power factor.

None

19

Alarm for voltage unbalance.

None

20

Alarm for current unbalance.

None

21

Alarm for low active power.

None

22

Alarm for high active power.

None

23

Alarm for high THD, voltage.

None

24

Page 58 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Alarm for high THD, current.

None

25

Alarm for high voltage harmonic #%1 on


phase %2

%1 indicates harmonics order


A
number.
%2 indicates the phase on which the
harmonic exceeded the limit value.

26

Alarm for high current harmonic #%1 on


phase %2

%1 indicates harmonics order


A
number.
%2 indicates the phase on which the
harmonic exceeded the limit value.

27

Alarm for long pulse at input #%1.

%1 indicates inputs order number.

28

Alarm for short pulse at input #%1.

%1 indicates inputs order number.

29

Alarm for missing voltage phases %1.

%1 indicates one more missing


voltage phases.

30

Configuration changed.

None

42

Calibration changed.

None

43

Initiation changed.

None

44

Energy direction is opposite of normal


direction on phase %1.

%1 indicates one or more phases


H
where the energy direction is not the
normal.

45

Meters firmware has been upgraded.

None

46

The estimated battery lifetime is up.

None

47

Current without voltage

None

49

Configuration parameters in the


communication module have been reset after
discovering that they were corrupt.

None

1001

Configuration parameters in the I/O module


have been reset after discovering that they
were corrupt.

None

1002

Configuration parameters in the


measurement module have been reset after
discovering that they were corrupt.

None

1003

Initiation parameters in the measurement


None
module have been reset after discovering that
they were corrupt.

1004

Calibration parameters in the measurement


None
module have been reset after discovering that
they were corrupt.

1005

Configuration parameters in the display and


register module have been reset after
discovering that they were corrupt.

None

1006

A historical period has been reset after


discovering that is was corrupt.

None

1007

MD registers have been reset after


discovering that they were corrupt.

None

1008

Measurement module missing or cannot be


started.

None

1009

Public

BGX501-856-R02, CewePrometer User Manual

Page 59 of 80

Configuration Log
The following configuration changes are registered in the configuration log. The parameter ID is shown to the
right of date and time in the meter display picture.

ID

Parameter

CT ratio

VT ratio

Secondary Voltage

Secondary Current

Watt seconds per LED pulse

Normal energy direction (0=both, 1=import, 2=export)

Number of decimals in energy registers

Energy registers prefix

Page 60 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Appendix C - Communication Ports


Serial Communication Port RS232
The PIN configuration is compatible with a standard PC COM port, 9-pin, D-sub connector with a few
exceptions. Some of the handshaking pins are not used.
Hardware

RS232 serial communication port

Contact in meter

D-Sub, 9 pin, male contact

Communication protocol

IEC62056-21/IEC1107 Mode C, programming mode


or DLMS/COSEM

Handshaking

RTS always active, CTS never active

Data format

IEC62056-21/IEC1107: 1 start bit, 7 data bits, 1 stop bit,


even parity
DLMS: 1 start bit, 8 data bits, 1 stop bit, no parity

Baud rate

Port #1 30019200 bps, Port #2 120019200 bps


1
2
3
4
5

RD
TD
Signal GND

6
7
8
9

RTS
CTS
-

PIN configuration for RS232 connector on


meter

Serial Communication Port RS422/RS485


A twisted pair of wires is used as the receiving bus that all meters monitor, and another pair is used as a
transmitting bus that all meters send on. The communication equipment uses an RS422/RS485 port or an
RS232 port through an RS232-to-RS422/RS485 converter. The converter must be designed for 4-wire
communications (RS422, full duplex) or 2-wire (RS485, half duplex). Recommended converters are Westermo
MA45, MD45 and MDW45.
Hardware

RS422 serial communication port

Connector in meter

5-pole connector (Phnix)

Communication protocol

IEC62056-21/IEC1107 Mode C, programming mode


or DLMS/COSEM

Data format

IEC62056-21/IEC1107: 1 start bit, 7 data bits, 1 stop bit,


even parity
DLMS: 1 start bit, 8 data bits, 1 stop bit, no parity

Baud rate

Port #1 30019200 bps, Port #2 120019200 bps


5
4
3
2
1

Public

Signal GND
TX+
TXRXRX+

BGX501-856-R02, CewePrometer User Manual

Page 61 of 80

PIN configuration for RS422 connector on


meter

IEC62056-21/IEC1107 optical communication port optical port


Place the optical head so that the IR receiver and transmitter are in the optimum positions for exchanging
signals. This position is attained when the optical head is centred over the optical port with the cable hanging
straight down. Visible ambient light (daylight, light bulbs and fluorescent lamps) can interfere with the transfer of
IR signals if the light is strong, and cause communications to fail. Visible light from most light sources contains a
certain amount of IR light that can cause interference. To ensure reliable communications, avoid installing the
meter where it can be subjected to strong ambient light when communications via the optical port are required.

Hardware

IEC62056-21/IEC1107 optical communication port

Communication protocol

IEC62056-21/IEC1107 Mode C, programming mode

Data format

1 start bit, 7 data bits, 1 stop bit, even parity

Baud rate

3009600 bps

Ethernet Communication Port


The Ethernet communication port is used from the PC with a virtual com port that tunnels serial protocols
(IEC62056-21/IEC1107 or DLMS/COSEM) over IP. See the section below for details on how to install the virtual
com port and how to configure the Ethernet port in the meter.

Hardware

Ethernet RJ-45

Communication protocol

IEC62056-21/IEC1107 Mode C, programming mode


or DLMS/COSEM

Data format

IEC62056-21/IEC1107: 1 start bit, 7 data bits, 1 stop bit,


even parity
DLMS: 1 start bit, 8 data bits, 1 stop bit, no parity

Baud rate

Port #1 30019200 bps, Port #2 120019200 bps

Configure the Ethernet adapter


Search the www.lantronix.com for the latest version of the Device installer. Download it and install the program
on your computer.
Start the program Device Installer on your menu. The device needs to get the correct IP on your network. This
procedure is fully described in the Lantronix pdfs DeviceInstaller User Guide and XPort User Guide but also
in short here.
Click on the Assign IP button and choose Assign a specific IP address. Set the new IP address to the device
and also subnet mask. Follow the instructions in the program.

Page 62 of 80

BGX501-856-R02, CewePrometer User Manual

Public

When Device Installer has found the device on your LAN, highlight it and click on Web configuration.

Click external browser to open a www-window. The device does not have any password. Just click OK when the
question about password is given.
Configure the Serial Settings screen as below.

By default, the baud rate in the CewePrometer is set at 9600 baud. If you choose to set it to another you also
need to change it for the appropriate port via CeweConfig software.
Public

BGX501-856-R02, CewePrometer User Manual

Page 63 of 80

Click OK on the bottom of the page.


Observe:

IEC62056-21(IEC 1107) Data bits =7, Parity=Even and Stop Bits =1


DLMS/COSEM

Data bits=8, Parity=No and Stop Bits=1

Change to screen Connection. Check that its as on the picture below.

To save the new configuration, click the Apply Settings tag on the left menu.

Install a virtual comport


The CeweConfig software needs a comport to be assigned to the CewePrometer. To be able to communicate
over the LAN you need to install the Lantronix Redirector software.
Download the Redirector file from ftp://ftp.lantronix.com/pub/old_rel/redirector/3.1.0.1/ There are newer versions
of this software but this is needed to work with the functions within CeweConfig.
Start the program Configuration on your menu. The device needs to get the correct IP on your network. The
following steps are also described in detail in the included Help section of the program.
Select an appropriate COM port from the drop-down list.
Click Add IP and type in the IP for the XPort. Also type in 10001 for the TCPPort.
Page 64 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Click Port Settings and set the boxes Timeout reconnect, Server Reconnect and Raw Mode. Also check that
reconnect limit is set to 0.
Click Save and close.
Launch CeweConfig and connect to the meter on the appropriate Com port.

Specifications
Cable: Unshielded Twisted Pair (UTP) in categories 1 to 5e.

Public

BGX501-856-R02, CewePrometer User Manual

Page 65 of 80

Appendix D Module Block Diagram

Communications between modules


The intelligent function modules that make up the CewePrometer are autonomous units with their own microcontrollers and own firmware. These are connected in an internal network through an internal bus. For internal
communications, information transfer is via a CAN bus. This bus is designed for reliable operation in harsh
electrical environments, primarily in motor vehicles, and has high transfer reliability and error detection.

Page 66 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Appendix E Frequently Asked Questions


Display Sequences
Which information is not available via the CewePrometer's display?
Graphs for discrete harmonics, vector graphs on 2-element meters, logged values and counters for short sags
and swells. This information cannot presently (meter version 1.2.0) be read via the meter's display. The
information is accessible via CeweConfig and via the communication protocol.

Meter Clock
What happens if a new successive adjustment is made when one is already underway?
The current adjustment will be stopped and the new begun.

What happens if the meter time is set within an hour before the change from daylight savings time to
standard time?
If the meter time is set to daylight savings time before the change, it will be set back to standard time
automatically at the approaching time change. If the meter time is set to standard time before the change, it will
not be affected at the approaching time change.

If you set the meter to use DST during the summer period, will the meter clock then change time to
DST?
No, the meter will always have the same time regardless when you set DST.

When summer time starts, the clock jumps one hour. What happens if the user sets the meter to a time
within that hour?
The mter will ignore the new time because that hour does not exist.

When the DST ends the clock will move backwards one hour. What happens if one set the time in the
meter to that hour? Will there be four or two occasions of that hour?
The meter assumes that the time is in DST if it is during that period and assumes it is in normal time when it is
in that period. The meter will not shift twice.

What happens if more than one input is used for clock synchronisation?
Several inputs can be used simultaneously to receive synchronising pulses even if this is unlikely.

How are logged values affected by the daylight savings time change?
According to the example:
Change from standard to daylight savings time
2005-03-28 01:30

3467.4 kWh

2005-03-28 03:00

3523.2 kWh

2005-03-28 03:30

3602.5 kWh

Change from daylight savings to standard time


2005-10-31 02:30
Public

3345.4 kWh
BGX501-856-R02, CewePrometer User Manual

Page 67 of 80

2005-10-31 02:00

3756.7 kWh

2005-10-31 02:30

4132.8 kWh

2005-10-31 03:00

4583.1 kWh

Logged values during daylight savings time are labelled with the flag S. S means that the timestamp is in DST.

What are the possible consequences of adjusting the meter clock immediately?
Because CeweConfig does not permit the clock to be adjusted immediately without simultaneously resetting the
logging memory, this is purely hypothetical. If it were to be allowed, then if the clock is adjusted forward over
one or more interval limits, there will be empty spaces in the logging memory and values will be lacking for one
or more intervals.
It the clock is adjusted backward over one or more interval limits, one or more values will exist with the same
time stamps. In the worst event, this can result in data read from the meter not matching the expected period.

Page 68 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Appendix F Calculation Principles


Current and Voltage
RMS values for current and voltage are calculated as the root of the sum of squares for the harmonic
components up to the 31th harmonic.

I1

The currents first harmonic component (fundamental) specified as peak value.

I2

The currents second harmonic component specified as peak value, has doubled frequency compared
to the first harmonic.

( I 12

I RMS

I 22

...I 312 )

Calculated Line to Line voltage


Line to Line voltage is calculated from the phase voltages fundamental vectors. This calculation is only made in
the 3-element meter; in the 2-element meter, the line to line voltage is measured.

(U112 U 212

U121

2 U11 U 21 cos(U11 p U 21 p)

Calculated I2
In the 2-element meter, I2 is not measured but is calculated for monitoring purposes. It is calculated from the
currents fundamental vectors.

I 21

Current I2s fundamental harmonic.

I 21

( I11

I 31 cos(I11 p I 31 p))2

( I 3 sin( I11 p I 31 p))2

Voltage unbalance
Class A
The basic measurement of voltage harmonics, for class A, is defined in IEC 61000-4-7 class I. That standard
shall be used to determine a 10/12-cycle gapless harmonic subgroup measurement, denoted Uisg,h in IEC
61000-4-7.

Power
Harmonic component power
The calculations below are for active power, the calculations for reactive are identical except for that cosfunctions are replaced with sin-functions.

P1n

Active power in L1 is calculated for harmonic component n.

Pn

Total active power is calculated for harmonic component n.

Phase angle between harmonic component U1n and I1n

3-element meter:

P1n

Public

U 1n I1n cos(

BGX501-856-R02, CewePrometer User Manual

Page 69 of 80

2-element meter:
For 2-element meters, only the total power is calculated in each harmonic component.

1n

Phase angle between harmonic component U12 n and I1n

2n

Phase angle between harmonic component U 32 n and I 3 n

Pn

U 12 n I1n cos( 1n ) U 32 n I 3n cos( 2 n )

Active and reactive power


Active and reactive power is calculated as the sum of harmonic component power up to 31st harmonic. The
calculation is made with plus and minus signs, where negative power represents export direction and positive
represents import direction.

Total active power

P1

Active power in L1

Total reactive power

Q1

Reactive power in L1

P1 P2 P3

Q1 Q2 Q3

For 2-element meters, two elements are added instead of three.

Apparent power

Total apparent power

S1

Apparent power in L1

S
S1

P2

Q2

P12

Q12

Energy
Energy is calculated by integrating power (P, Q and S) over time.
Definition of quadrants
The term phase angle is described under its own heading below.
Quadrant I: phase angle 190
Quadrant II: phase angle 90180
Quadrant III: phase angle -180(-90)
Quadrant IV: phase angle (-90)0

Active energy
Active energy is calculated for import and export. The direction is controlled by the sign for active power
(+ import, export).
Active energy import: quadrant I and IV
Page 70 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Active energy export: quadrant II and III

Reactive energy
Reactive energy is calculated for four quadrants. The quadrant is controlled by the sign for active and reactive
power (e.g., active power >= 0 and reactive power >= 0 corresponding to quadrant I).
Reactive energy import: quadrant I and II
Active energy export: quadrant III and IV

Reactive energy inductive: quadrant I and III


Reactive energy capacitive: quadrant II and IV

Apparent energy
Apparent energy is calculated for import and export. The direction is controlled by the sign for active power;
apparent energy is registered for the direction that the active energy has during the same period.
Apparent energy import: quadrant I and IV
Apparent energy export: quadrant II and III

Power Factor

pf ( L1)

P1/ S1

pf (Tot)

P/ S

The power factor is calculated without signs and is thus always positive.

Phase angle
( L1) U1 p I1 p
Phase angle for an element is calculated from the fundamental phase angles.

(Tot )

arctan( P1 fund / Q1 fund )

Total phase angle is calculated from fundamental power.


Phase angle values specified between 180 and 180 .

THD
Total harmonic distortion

THDeur

I 22

I 32 ...I n2

I12

I 22 ...I n2 1

100%

Where I 1 I n are the currents harmonic components. The calculation is made in the same ways for current
and voltage.

Public

BGX501-856-R02, CewePrometer User Manual

Page 71 of 80

Transformer Compensations
Instrument transformer compensations
Instrument transformer compensations are specified as error in percent for amplitude, and as error in minutes
(one-sixtieth of a degree) for phase angle. These errors can be specified separately for all voltages and
currents.

AmpErr

Amplitude error as percent

PhaseErr

Phase angle error in minutes

u meas

Measured voltage

Compensated voltage

Amplitude compensation

u meas /(1 AmpErr )

Phase angle compensation

up

upmeas

PhaseErr

In 3-element meters, phase voltages are compensated and in 2-element meters, line to line voltages. The same
calculation is used for all currents and voltages.

Power transformer losses


Power transformer losses consist of copper and iron losses. They are expressed as percentages of nominal
power. One value is specified for active loss and one for reactive.

Iron loss

FeLoss

Active iron loss as percent of nominal power.

P1meas

Measured power.

P1

Compensated power.

Nom

Nominal power per phase

P1

P1meas

FeLoss Nom

Copper loss

CuLoss

Active copper loss as percent of nominal power.

Phase current.

inom

Nominal current.

P1

P1meas

(i / inom ) 2 CuLoss Nom

Corresponding calculations made for active and reactive power.

Definition of phase order


Correct phase order (123) corresponds to phase position:

U1 p

Phase position for U1

U1p

Page 72 of 80

BGX501-856-R02, CewePrometer User Manual

Public

U2p

120

U 3p 120
The same system is represented graphically below. The vectors rotate in an anti-clockwise direction.

Public

BGX501-856-R02, CewePrometer User Manual

Page 73 of 80

Appendix G Material Declaration


CewePrometer-R
Enclosure
Front plate

Steel sheet, galvanised, chromated

Rear panel

Steel sheet, galvanised, chromated

Side plates

Stainless steel sheet

Top & bottom plates

Stainless steel sheet

Handle

Steel, chrome plated

Plastic parts
Inner window

Polycarbonate V0

Outer window

Polycarbonate V0

Side pieces

Polycarbonate/ABS V0

Battery cover

Polycarbonate/ABS V0

CewePrometer-W
Enclosure
Bottom plate

Polycarbonate/ABS V0

Meter cover

Polycarbonate/ABS V0

Inner window

Polycarbonate V0

Outer window

Polycarbonate V0

Battery cover

Polycarbonate/ABS V0

Terminal cover

Polycarbonate/ABS V0

Connection terminal, current/voltage


Terminal body

PPO + 10 % GF V0

Terminals

Brass

Screws

Steel

Page 74 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Appendix H Connection and General Details


Safety
Isolation voltage according to IEC 62052-11, IEC 62053-22, IEC 62053-23
WARNING: Live parts inside meter cover. Always disconnect all wires carrying dangerous voltages
before opening the meter.

Current circuit
Measurement current (In)

1- 10 A configurable

Measuring range

1 1000% of In

Burden

0.7 mVA/phase at 1 A
0.03 VA/phase at 5 A

Max overload current

2xIn continuously, 10xIn during 10s, 40xIn during 1s

Starting current

<0.1% of In

Voltage circuit
Measuring voltage (Un)

3-wire system:

3x100240 V

4-wire system:

3x57/99240/415 V

Measuring range

80% - Un 115%

Frequency range

50 Hz or 60 Hz +/- 5 %

Burden

5 mVA/phase at 57.7 V
17 mVA/phase at 120 V
67 mVA/phase at 240 V

Max overload voltage

1.3xUn continuously, 2xUn 0.5s

Auxiliary power
CewePrometer-W
Internal auxiliary voltage/ Self Powered
Separate auxiliary voltage Uaux

40 276 VAC/DC

Power Consumption

Typically 6-8 VA
Max 14 VA (With additional communication module)

CewePrometer-R

Power Consumption

40 276 VAC/DC

Single supply

2 x 40 276 VAC/DC

Dual supply

Typically 6-8 VA
Max 14 VA (With additional communication module)

Accuracy
CewePrometer-W

Public

Class 0.2s, 0.5s, 1s

BGX501-856-R02, CewePrometer User Manual

Page 75 of 80

CewePrometer-R

Class 0.2s, 0.5s

Temperature range
Working temperature range

-20C - +55C

Limit temperature range

-40C - +70C

Storage temperature range

-40C - +80C

Temperature coefficient

<0.3%/10C

Protection Class
CewePrometer-W

IP51 according to IEC529

CewePrometer-R

IP51 according to IEC529

Humidity
Non Condensing

Mounting Arrangement
CewePrometer-W

Wall or Panel Mounted/ Indoor or Closed Location

CewePrometer-R

Rack Mounted

Mechanical Environment
As per IEC standard & Category M1 as per EN standard

Vibration and Shock

Electromagnetic Environment
As per IEC standard & Category E1 & E2 as per EN standard

Digital outputs
Type

Solid-state relay (MOSFET, bi-directional)

Relay performance

0.2 A, 110 V AC/DC (varistor protected)

Digital inputs
Type

Optical switch

Voltage (AC or DC)

48220 V

Incoming resistance

20k ohm

Page 76 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Appendix I Approvals and Certificates


Performed by the SP, Technical Re-search Institute of Sweden
SP
Box 857
S-501 15 BORS
SWEDEN

To the following standards:


EN62052-11:2003 and 62053-22:2003 class 0.2S and 0.5S
Alternating current static watt-hour meters for active energy
EN62052-11:2003 and 62053-23:2003 Class 2
Alternating current static var-hour meters for reactive energy

Tests have also been done in part for the following standards:
EN61038:1996 Time switches for tariff and load control. Applicable parts according to
accuracy requirements for the real time clock.

Certificates:
SP - Sweden
Certificate no. 22 00 04. CewePrometer-R Electronic watt-hour and var-hour meter
Certificate no. 22 00 05. CewePrometer-W Electronic watt-hour and var-hour meter

Performed by Ofgem - UK
Certificate no. 983. CewePrometer-R Electronic watt-hour and var-hour meter. Class 0.2S, 0.5S, 1
Certificate no. 999. CewePrometer-W Electronic watt-hour and var-hour meter. Class 0.2S, 0.5S

Performed by SGS - UK
Compliance with Code of Practise 1, 2, 3 &5
CewePrometer-R and CewePrometer-W

Performed by Justervesenet - Norway


Certificate no. 08/2005. CewePrometer-R and W Electronic watt-hour and var-hour meter

Performed by BRML - Romania


Certificate no. 212/23.09.2005

Performed by PTB - Germany


Certificate no. PTB- 2.3-4054853, 5 march 2012

Performed by METAS - Switzerland


Certificate no. EC2 594, 4 February 2013

Public

BGX501-856-R02, CewePrometer User Manual

Page 77 of 80

Appendix J Cewe Config settings


Startup parameters
Adding a combination of arguments from the list below will pass this on to CeweConfig at startup. i.e a short cut
to CeweConfig with the arguments, can connect directly to the meter.

Argument
-d

Devicetype [modem|serialPort|opticalPort]

-b

Baudrate

-p

Port

-n

Phonenumber

-w

Password

-s

Serialnumber

-t

Trace

Page 78 of 80

BGX501-856-R02, CewePrometer User Manual

Public

Notes

Public

BGX501-856-R02, CewePrometer User Manual

Page 79 of 80

Cewe Instrument AB
Box 1006,
SE 611 29 Nykping
Sweden

t: +46 155 775 00


f: +46 155 775 97

You might also like