Professional Documents
Culture Documents
User Manual
BGX501-856-R02
Page 2 of 80
Public
Table of Contents
1
Introduction ................................................................................................................................. 5
1.1
1.2
Contacting us ...........................................................................................................................................5
2.1
2.2
2.3
Connections .............................................................................................................................................9
2.4
2.5
Function modules................................................................................................................................... 15
2.6
3.1
Connecting to CewePrometer................................................................................................................. 16
3.2
Basic configuration................................................................................................................................. 18
3.3
3.4
3.5
3.6
Reading ................................................................................................................................................. 22
3.7
3.8
3.9
Functions ................................................................................................................................... 25
4.1
4.2
4.3
Instant values......................................................................................................................................... 27
4.4
4.5
4.6
4.7
Loggers ................................................................................................................................................. 34
4.8
Alarms ................................................................................................................................................... 36
4.9
Event log................................................................................................................................................ 38
Page 3 of 80
5.1
5.2
5.3
5.4
Page 4 of 80
Public
1 Introduction
Thank you for choosing the CewePrometer.
The CewePrometer is a multi-functional, electronic, electricity energy meter. It provides very high accuracy in
measuring electrical energy and also in measuring instantaneous quantities such as current, voltage, power,
frequency etc. CewePrometers extensive configurable functional features together with the high accuracy
enable application areas more numerous than for traditional electric meters. Besides having well-designed
traditional features such as meter registers, data logging and tariff capability, there are also extensive functions
for monitoring alarm conditions, harmonics, measuring sags and swells and other power quality quantities.
1.1
This user manual describes the CewePrometers functions and provides the information needed to configure
and use the meter. The manual covers all versions of the CewePrometer-R (rack-mounted) and CewePrometerW (wall-mounted). Some of the described functional properties can be missing in certain meter versions. The
CewePrometer is complemented with CeweConfig, a PC program for configuring, manual reading and
maintenance.
1.2
Contacting us
For more information and technical support, please contact Cewe Instrument.
Internet
www.ceweinstrument.se
support@ceweinstrument.se
marknad@ceweinstrument.se
Telephone
Address
Cewe Instrument AB
Box 1006
SE-611 29 Nykping
Sweden
Public
Page 5 of 80
2 Product Description
15
14
13
12
11
10
3
Figure 1: CewePrometer-W
10
15
14
13
12
11
16
Figure 2: CewePrometer-R
Page 6 of 80
Public
Display
Alarm LED
The alarm LED flashes when an alarm state has occurred. For alarms, such as for high
or low voltage, phase balance or similar external errors, the LED stops flashing when
the alarm state has passed. If the meter has had an internal error, the alarm must be
acknowledged and manually reset.
Terminal cover
Meter cover
10
11
12
Sealed button
The button is hidden under the front panel window and provides access to a fifth
configurable display sequence. Holding down the button for about two seconds opens a
system menu.
13
Step backward
The button is used to step backward to a previous display layout in the selected display
sequence, or to step downwards in a menu.
14
Menu/Apply
The Menu/Apply button is used to open the menu where one of four configurable
display sequences can be chosen. The button confirms choices made or initiates other
activities depending on the current display layout.
Public
Page 7 of 80
15
Step forward
The button is used to step forward to the following display layout in the selected display
sequence, or to step upwards in a menu.
16
2.1
Sealing of CewePrometer-W
See Figure 1: CewePrometer-W for location of the sealing points. The front panel window can be sealed with
lead seals (or comparable seals) and sealing wire through the sealing points. The seal prevents access to the
fourth sealed button and the optional backup battery for the real-time clock.
Battery cover
Sealed button
Figure 3: Under the front panel window is a fourth button and backup battery for the real-time clock.
The terminal cover can be sealed with lead seals (or comparable seals) and sealing wire through the sealing
points.
The meter cover can be sealed with lead seals (or comparable seals) and sealing wire through the two sealing
points under the terminal cover.
Sealing point
Figure 4: The meter cover can be sealed at the sealing rings on both sides under the terminal cover.
Page 8 of 80
Public
2.2
Sealing of CewePrometer-R
See Figure 2: CewePrometer-R for location of sealing points. The enclosure permits the meter to be sealed at
three points. The top and bottom covers are normally each sealed with a lead seal and with sealing wire through
a sealing screw and a fixed hole on the cover at the rear of the meter. The exterior window on the meter front
can be sealed on a sealing point with a lead seal and sealing wire. In this way, the meter can be sealed so that
it cannot be opened without breaking all the seals. One of the buttons on the front is protected from access
behind the sealed exterior window.
Battery
Sealed button
Under the front panel window is a fourth button and backup battery for the real-time clock.
2.3
Connections
Connections to the CewePrometer-W are made on the meter terminal under the terminal cover. Connections to
the CewePrometer-R are made on the rear panel of the meter subrack. The connections are: measuring
voltages, measuring currents, relay outputs, optically isolated digital inputs, separate auxiliary power and
connections to communication modules, if any.
Digital outputs
Digital inputs
Output #8
Output #1
I'L1 UL1
IL1
I'L2 UL2
IL2
I'L3 UL3
Input #1
IL3
Input #4
N
Separate aux. power
(Uaux)
Public
Page 9 of 80
Connections
IN1
IN2
IN3
IN4
2.3.1
C0, C5
C1, C6
C2, C7
D0, D5
D1, D6
D2, D7
D3, D8
D4, D9
B7, B8
B4, B9
IN1
IN2
Uaux1
Uaux2
B5
B6
I1 in
I1 out
I2 in
I2 out
I3 in
I3 out
A01
A1
A02
A2
A03
A3
12 outputs, 0 inputs
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
C4, C9
C3, C8
D4, D9
D3, D8
10 outputs, 2 inputs
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
B1
B2
B3
B0
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
UL1
UL2
UL3
N
C4, C9
C3, C8
C0, C5
C1, C6
C2, C7
D0, D5
D1, D6
D2, D7
D3, D8
D4, D9
B7, B8
B4, B9
C3, C8
C4, C9
A standardised Entrelec Essailec plug-in connector is used, of the same type as for other meters according to
standard DIN 43862. The cable connection is made in the subrack. The meter is connected via the contact pins
after insertion. The connector has a short-circuit protection feature for electrical circuits, permitting the meter to
be withdrawn and inserted into the subrack during operation.
2.3.2
Auxiliary power
The CewePrometer is supplied with separate auxiliary power. Auxiliary power can be supplied both with
alternating current and polarity-independent direct current within a specified range. Auxiliary power can be self
powered (internal), CewePrometer-R can also be configured with dual auxiliary.
2.3.3
Digital outputs
The CewePrometer's outputs are solid-state MOS-FET bipolar semiconductor relays, with normally open
contact function. Internal current limit protects the relay from being damaged by excessively high current.
Page 10 of 80
Public
2.3.4
Digital inputs
The optically isolated digital inputs consist of opto couplers, where the LED is powered from an external voltage
signal through series resistance to limit the current. This means that an external voltage must be connected
between the passive pulse and level transmitter and the opto coupler's LED, or the transmitter must deliver an
active voltage signal to send pulses that are detected by the optical input. The optically isolated inputs are
unaffected by reverse polarity. Both DC and 50/60 Hz AC can be used.
2.3.5
The CewePrometer is equipped with one optical port and up to two additional communication ports, Ethernet or
serial (RS232 or RS422. RS422 can also be used as RS485)
Communications through the infrared IEC62056-21/IEC1107 optical port are transferred via an optical
read/write adapter, an optical head. The optical head is positioned and secured over the optical port
by a magnet on the head and a steel plate around the opening of the optical port.
The RS232 standard communication port is used to connect communication equipment (computers,
modems) through a serial cable with a standard D-sub, 9-pin connector.
The RS422 serial communication port is intended to be used to connect the CewePrometer to a
network for multi-drop communications. The CewePrometer is connected to the communication
equipment (RS422 converter) with two twisted-pair wires connected to a 5-pole connector. The
RS422 port can also be used for single twisted-pair RS485 bus.
The Ethernet communication port is used to connect to the meter over TCP/IP based network.
For information on pin configuration, see Appendix C - Communication Ports (pg.61).
Page 11 of 80
2.4
Mechanical design
Alternative
mounting
Page 12 of 80
Public
Public
Page 13 of 80
2.4.1
CewePrometer-W
The enclosure consists of a meter base, meter cover, terminal cover and a plastic exterior window. The meter is
not connected with protective earth. There is also an optional 19 inch rack/panel mounting kit available for to
CewPrometer-W to be mounted side by side.
CewePrometer-R
Enclosure fits for installation of two meters in a 19" subrack in compliance with DIN438862. The enclosure
consists of a box made of surface-finished steel sheet and a front with a plastic window. The meter is designed
for protective earthing through the 19" subrack.
2.4.2
The electronic circuits are isolated from all connections to the supply mains with transformers. Digital I/O
connections are isolated with opto couplers and solid state relays. The communication ports are also isolated
but for a lower voltage.
Page 14 of 80
Public
2.5
2.5.1
Function modules
Modulisation
The CewePrometer is made up of function modules. Modulisation is primarily used to make it easy to produce
different versions with the same basic design, and to enable development of new modules for the basic design
to add or replace functions. Modulisation is not primarily intended for being able to switch plug-in modules in the
field the meter must be opened and the seals broken to switch modules.
2.5.2
Modules
The CewePrometer consists of the following basic modules, which are necessary for a functioning meter in its
simplest version:
Measurement module
Power module
Display and register module
Moreover, the meter is normally equipped with the following modules for additional functionality:
Digital I/O module
Communication module
There is also space for additional function modules for expansion of function properties to meet future market
needs.
For more information, see Appendix D Module Block Diagram (pg.66).
2.6
Measuring principles
The measuring circuit in CewePrometer consists of current and voltage transformers that provide signals to six
parallel AD converters (analogue to digital converters) that are synchronised by a common clock signal. The
digital signals are thereafter processed by a DSP. Using voltage transformers makes the electronics in the
meter galvanically isolated from the measurement voltage, which provides good personal safety and protection
for connected equipment, such as modems.
2.6.1
Calculation flow
All values are calculated in the CewePrometer based on calibrated current and voltage values. Current and
voltage amplitudes and phase angles are fully compensated in regards to accuracy, harmonics, frequency and
temperature. Adjustments for accuracy are made throughout the dynamic range for both voltage and current.
Based on these individually compensated current and voltage signals, power, energy, power factor and all other
quantities that the CewePrometer can present, are subsequently calculated. This means that accuracy for
instant values is good and that active and reactive power are correctly calculated, including harmonic power.
For more information on calculation principles and the formulas used, see Appendix F Calculation Principles
(pg. 69).
2.6.2
3-element meter
On the 3-element CewePrometer, phase voltages and neutral wires are connected to the meter. The voltages
measured are phase voltages. Power and energy are calculated from three phase voltages and three currents.
Harmonic measurement, alarm monitoring and transformer corrections are made on phase voltages. The line to
line voltage is calculated from the phase voltages.
2.6.3
2-element meter
On the 2-element CewePrometer, the neutral conductor is not connected to the meter and the three voltages
are internally D-connected. The voltages measured are subsequently line to line voltages. Power and energy
are calculated based on two line to line voltages (U12 and U23) and two currents (I1 and I3) according to the 2watt meter method. The 2-element meter is primarily used for D-connected systems (3-wire). Harmonic
measurement, alarm monitoring and transformer corrections are made on line to line voltages.
Public
Page 15 of 80
Structure tree
3.1
Toolbar
Status bar
Configuration form
Connecting to CewePrometer
To be able to configure or read values in the CewePrometer, CeweConfig must be connected and have
authorisation to access the meter. The meter has five different authorisation levels that can be configured with
passwords. See the section Communications and security (pg. 32). With the meter's usual factory settings, no
password is configured, and subsequently no password is necessary when you connect.
To communicate with a meter, the PC must be physically connected to the CewePrometer in one of the
following ways:
PC Optical head Meter
PC Crossed serial cable (null modem) Meter
PC Straight serial cable RS422 converter Daisy chained meters
PC straight serial cable RS485 converter Daisy chained Meters
Page 16 of 80
Public
Page 17 of 80
Under the Settings tab, a box can be checked to activate tracing to a file. A file named SerialTrace.log is then
created in CeweConfig's installation directory. All communications between CeweConfig and the meter are
presented in the file. The function can be used to analyse communication problems.
8.
Note: For Ethernet communication, the Serial Port (RS232/RS422) option should be selected.
3.1.1
If the meter cannot be connected, an error message is displayed. Depending on the reason, the message can
suggest corrective actions, such as changing the port or port baud rate.
Tip: When communication problems occur, the trace feature on the meter's display can be used to see if that
which has been sent has been registered by the meter. See the section Using the display for communication
diagnostics (pg.49).
3.2
Basic configuration
Some basic settings may be required before the CewePrometer will be able to measure and operate correctly in
a system.
Note: Settings are only necessary if they have not been made at the factory prior to delivery.
Meters supplied without backup batteries retain the time setting for a maximum of three days. For timedependent functions such as logging and event logging to work, the clock may need to be adjusted.
To change the configuration for a meter, you must be connected to it. Click the Configuration folder in the
structure tree to the left in CeweConfig to display the various functions that can be configured. For more
information see the section Changing configuration (pg. 20).
Tip: You can save a configuration from a meter to a file. A summary of the configuration can also be printed out.
You can also create a configuration without being connected to a meter. For more information, see Working with
configurations (pg.21).
Meter clock: To configure the meter clock, choose the node Meter Configuration - Clock in the
structure tree. Find out how the meter clock works and how it can be configured in the section Meter
clock (pg. 25).
Page 18 of 80
Public
Transformer ratios: For the meter to measure accurately, the ratios must be correct. To configure the
transformer ratio in CeweConfig, choose the node Meter Configuration Measuring in the structure
tree. Click the General tab in the window that opens. Fill in the primary and secondary values for
current and voltage.
Note 1: The values you choose as primary and secondary values will be considered as the nominal
values. These nominal values are used by several functions in the meter: alarms, voltage monitoring
and transformer compensation.
Any change to measuring configuration is logged in the configuration log (see section Configuration
log).
Presentation format for energy registers: To configure the presentation format for energy registers,
choose the node Meter Configuration Measuring in the structure tree. Choose the prefix and
number of decimals for energy registers. Based on the nominal values, a capacity is calculated for how
long the meter can measure without registers resetting. Read about energy registers in the section
Energy registers (pg. 26).
Pulse constants for pulse outputs (Digital I/O): To configure pulse constants for pulse outputs in
CeweConfig, choose the node Meter Configuration Digital I/O in the structure tree. Find out how
Digital I/O works and how it can be configured in the section Digital inputs and outputs (pg. 29).
Display sequences: To configure display sequences in CeweConfig, choose the node Meter
Configuration Display sequences in the structure tree. Find out how display sequences work and
how they can be configured in the section Display sequences (pg. 32).
3.3
Overview of functions
The following is a brief overview of the functions available in CewePrometer. All functions in the meter can be
both configured and read in CeweConfig. In many cases, CeweConfig can also export data to a file or print out
data.
Function
Communication speed
Set the baud rate for the meter's
optical or serial port.
Passwords
Regulate access to data in 5
levels with passwords or
hardware strap.
Data logging
Log energy or instant values.
Public
Configuration location in
CeweConfig
Meter Configuration
Communication
Meter Configuration
Communication
Page 19 of 80
Alarms
Activate alarms for events such
as voltage unbalance. Determine
how alarms will be presented.
Maximum demand
Determine values that are to be
stored as maximum average
values.
Historical registers
Choose how a historical period
will be finished.
Time of use
Determine how rates shift over
the course of a day and which
registers will be divided by rates.
Transformer compensation
Compensate errors and losses for
instrument and power
transformers.
Power quality
Activate monitoring of voltage
sags, swells and interrupts.
Language on display
Choose between several
available languages for the
display.
Information texts
Enter information texts that can
be read on the display and via
communications.
Calibration LED
Set a pulse constant for the
calibration LED. This is used to
test meter accuracy.
Accumulate incoming pulses
Configure registers to accumulate
pulses representing a selectable
quantity.
Indicate alarms via pulse
output
Choose a pulse output to be
activated in case of alarms.
Synchronise clock via
incoming pulse
Set an interval that the clock shall
be synchronised to upon
incoming pulses.
Adjusting the clock for daylight
saving time
Set date and time for daylight
saving time.
3.4
Meter Configuration
Maximum Demand
Meter Configuration
Historical Registers
Meter Configuration
Measuring, Transformer
Compensation tab
Meter Configuration
Measuring, Power Quality tab
Meter Configuration
Measuring, General tab
Changing configuration
Page 20 of 80
Public
To open a configuration form, click the folder Configuration in the structure tree and then click one of the
nodes: Display Sequences, Measuring, Clock, etc. Configuration changes can be made in all configuration
form. In the lower right corner, there is an Apply button. If a meter is connected and you click Apply, changes
to the configuration will be immediately transferred to the meter. If the changes affect registers or measurement,
a warning dialog will be displayed. You can choose not to send a portion of the configuration by clearing
checkboxes in the dialog.
Warning dialog displayed sometimes when configurations are sent to the meter.
3.5
In CeweConfig, you can work with configurations as a collection of CewePrometer's settings and save them in a
file. On CeweConfig's File menu, are the commands Save configuration, Open configuration and New
configuration. A configuration can either be for a 2- or 3-element meter. You cannot transfer a 2-element
configuration to a 3-element meter or vice versa. Transformer corrections or passwords are not saved in
configuration files. On the File menu, there is a command for creating a configuration summary. Below is a list
of how you can use CeweConfig's functions to work with configurations.
Creating a configuration file without being connected to a meter
Choose New configuration when CeweConfig is not connected to create a configuration file offline.
The configuration file can be either of the 2- or 3-element type. Make all settings that are to be included
in the configuration file and save the file. The file's configuration can later be transferred to a meter.
Saving a meter's configuration to a file
Choose Save configuration when CeweConfig is connected to a meter to save the meter's
configuration to a file. The configuration file can later be used as a backup or be transferred to another
meter.
Transferring a configuration file to a meter
Choose Open configuration when CeweConfig is connected to a meter to transfer a configuration file
to the meter. The changes in configuration cause a dialog to open. The dialog shows all parameters
that can be updated in the meter. You can select some parameters which will not be updated, e.g.
transformer ratio, that might be specific for each meter. If you want an exact copy, all parameters must
be selected
Public
Page 21 of 80
3.6
Reading
If you are connected to a CewePrometer with an authorisation level between 1 and 5, several alternatives will
be available in the structure tree under the node Reading. For the alternatives Instant Values and Time,
displayed values are constantly updated. The others are only updated when the window is opened or when the
Update button is clicked. Read values can be printed out and often also saved to files, this can be done with the
help of Print and Save buttons.
Page 22 of 80
Public
3.7
Information about the connected meter can be obtained by choosing View Information about the meter.
Some of the information displayed is the same as what appears on the meter plate. Additionally, there is
information on when the meter was manufactured and when the most recent configuration change was made.
Under the Modules heading, the firmware currently used in the meter is listed. See the section Updating
firmware (pg. 23).
3.8
The latest version of CeweConfig can be used with all firmware versions of CewePrometer-R/W. The version
number for CeweConfig is displayed on the application's title bar or under About on the Help menu. The
version number for the meter's firmware can be viewed under View information about the meter on the View
menu.
CewePrometer and CeweConfig have three-digit version numbers according to the format main version.subversion.build number. As long as the main version and sub-version are the same, CeweConfig and the meter
are compatible. If the meter is of a newer version than CeweConfig and the main version and/or sub-version are
different, CeweConfig will display a message that connection is not possible. CeweConfig must be updated.
3.9
Updating firmware
CewePrometer is designed with a number of modules that each have their own processors and their own
firmware. The module firmware is distributed in a package file (.pkg) which is transferred to the meter using
CeweConfig. Newly developed and improved functions can thus be added in a meter that lacked these functions
when delivered.
Note: Be sure to update CeweConfig to the latest version before updating the meter. There is otherwise the risk
that CeweConfig will no longer be version-compliant after firmware updating.
Public
Page 23 of 80
On the Tools menu, there is an Update firmware command when the meter is connected with authorisation
level 4 or higher. Begin by choosing the file that contains the update. The file name and version number will
then be displayed, and sometimes a message. Click the Advanced button to view CeweConfig's version
number by module for both the file and the meter. Additionally, you can force modules to be updated even if the
file has the same version number. Click Update to begin updating.
During the time the update is being installed, the meter stops measuring and registering energy. Depending on
the size of the file to be transferred and the baud rate, the time for updating can vary from a few minutes to a
half hour at the highest baud rate. If possible, connect at the highest baud rate (19200 bps) to speed updating.
After updating, the meter is restarted to complete installation of the meter's new firmware.
Updating can be performed via a modem but this should be avoided since reliability for this method of
communication is too low. An interrupted update can leave a meter with incomplete firmware that cannot
measure at all. If an update via a modem has failed, the next update must be made via RS232/422 or the optical
head.
3.9.1
Restrictions
Firmware updates can only be made to a firmware version with the same major version number as the firmware
present in the meter. Example: It is not possible to update from 2.1.0 to 3.0.0. It is possible to update from 2.0.1
to 2.1.0.
3.10 Language
CeweConfig can be set to different languages. The available languages can be seen under Language on the
View menu.
Page 24 of 80
Public
4 Functions
4.1
Meter clock
The CewePrometer has an integrated real-time clock for time-dependent functions. Information about time
adjustment and daylight saving time status is recorded with tags on the logged values; see Loggers (pg.34).
Time adjustments are also noted as an event in the event log; see Appendix B - Events and Configuration Log
(pg.58).
4.1.1
Instantaneous adjustment
The meters date and time can be set to an absolute point in time. Instantaneous adjustment of the meters time
can influence logged values. To avoid this, the meter's log memory is reset when doing instantaneous
adjustment. For this reason, instantaneous adjustment of the meter clock is primarily intended for use at initial
configuration of the meter.
4.1.2
Sliding adjustment
The meters time can be adjusted successively. Instead of the meter adjusting the clock instantaneously, the
total adjustment is spread out over a longer period. A speed of adjustment can be chosen in the 140% range.
With 40%-adjustment, the clock is adjusted 24 seconds for each minute until the total adjustment has been
made.
4.1.3
CewePrometer offers the alternative of letting the meter clock follow daylight savings time. At a specified date,
the meter clock is adjusted forward, and at another, adjusted backward. CewePrometer can store ten (10) years
of DST configuration.
Example: On 28 March the clock is to be adjusted forward, from 02:00 to 03:00. The adjustment back to
standard time is to occur on 31 October at 3:00 (daylight savings time) when the clock is to be set back to
02:00. The following is set in the meters: Begin March, 28, 02:00. End October, 31, 03:00 and the standard time
is to be adjusted by 60 minutes.
4.1.4
External synchronisation
The meter time can be adjusted by a pulse on one of the meters digital inputs. When a pulse is registered, the
clock is adjusted to the closest multiple of a specified synchronisation interval. If the synchronisation interval is,
for example, one hour and the time is 13:29, a pulse will adjust the clock to 13:00. If the time had instead been
13:31, the clock would have been adjusted to 14:00. Synchronisation is made by sliding the time 30% (18s per
minute).
Available synchronisation intervals are:
10, 15, 20 and 30 minutes
1 hour
Times 12:00 and 00:00
Time 00:00
Besides specifying that the meter clock will synchronise via external pulses, a digital input must also be
configured for clock synchronisation; see the section Digital inputs and outputs (pg. 29).
4.1.4.1
Battery monitoring
The battery is used to backup the real time clock. The battery monitoring function estimates the time left of the
battery. At installation of a battery the monitoring function must be restarted via CeweConfig.
Public
Page 25 of 80
4.2
Energy registers
Energy registers in the CewePrometer are electronic counters that accumulate energy. Prefixes and number of
decimals are configured which apply to all energy registers. Energy registers have a width of nine digits,
regardless of the total number of decimals and the prefix configured. When an energy register has reached its
maximum figure (for example, 999999.999 kWh), it resets to zero. Fewer decimals and larger prefixes give the
energy registers space for more energy without resetting. Read more about how energy is calculated and
defined by quadrants in Appendix F Calculation Principles (pg.69).
4.2.1
Overview
Energy direction
Total values
Active energy
Import, export
Yes
Reactive energy
Import, export,
quadrants I-IV,
capacitive,
inductive
Import, export
Apparent energy
Reactive power
import (+)
II
Total number
Yes
Per phase
values
Yes (3-element
meter only)
No
Yes
No
8
8
I
S
Capacitive
Q
P
Inductive
Reactive power
export (-)
III
IV
Quadrants
I
II
Phase angle
0 to 90
90 to 180
III
IV
-180 to -90
-90 to 0
Lagging
Leading
4.2.2
All registers are saved in non-volatile memory once per second. Loss of auxiliary voltage therefore results in no
more than one second of lost historical energy measurement data. For optimal safekeeping, all registers are
saved in three alternating memory areas.
Page 26 of 80
Public
4.2.3
Delta values can be seen under logger channels display, only when selected in any of logger channel.
4.2.4
Integration period of delta values can be set by the time period of logger 2 using CeweConfig tool.
As per above picture, time interval of logger can be set to 1, 2, 3, 4, 5, 10, 15, 20, 30 or 60 minutes. Default time
period of logger is 1 minute which is also the default IP of all delta energy values.
Logger 2 time interval will only affect the IP of delta energy values; it will not log them unless the values are
selected as logger channel in any of the logger.
4.3
Instant values
Besides energy, the CewePrometer can also measure instant values. Instant values are constantly changing
values such as current, voltage, power and harmonics. The formulas and definitions used to calculate the
values are presented in Appendix F Calculation Principles (pg.69).
4.3.1
Overview
This table provides an overview of the instant values that can be read on the meter. Readings can be viewed
with CeweConfig, on the display and with other software that has implemented CewePrometers communication
protocol. Most instant values can be logged; for more information, see section Loggers (pg. 34).
Instant value
Frequency
Power factor total
Power factor per phase
Active power total
Active power per phase
Reactive power total
Reactive power per phase
Apparent power total
Apparent power per phase
Line to line voltage L12, L23, L31
Phase voltage
THD voltage
Amplitude voltage harmonics (231)4
Phase symmetry voltage
Public
Available on 3-element
meter
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
1
Yes (calculated)
Yes
Yes (phase volt.)
Yes (phase volt.)
Yes (phase volt.)
Available on 2-element
meter
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes (line to line volt.)2
Yes (line to line volt.)2
Yes (line to line volt.)
Page 27 of 80
Current
THD current
Amplitude current harmonics (231)4
Phase symmetry current
Phase angle total
Phase angle per phase
Voltage unbalance
4.3.2
Update frequency
The update frequency for instant values is proportional to the frequency of the measuring voltage. With a 50 Hz
measuring voltage, updating occurs 12.5 times per second, and at 60 Hz, 15 times per second. Instant values
can be read up to twice per second via the serial port when it is set to 19200 baud.
4.3.3
Accuracy
The table shows typical accuracy for a CewePrometer with accuracy class 0.2 for a selection of instant values.
Instant value
Voltage amplitude
Current amplitude
Current amplitude
Frequency
Power
Range
Umin - Umax
5 % of Imax - Imax
15% of Imax
4763 Hz
1 % of Imax - Imax
Power factor
Voltage amplitude,
harmonics
Voltage amplitude,
harmonics
Current amplitude,
harmonics
Current amplitude,
harmonics
Voltage unbalance
<1% of Un
0,05% of Un
>=3% of In
5% of reading
<3% of In
0,15% of In
Umin - Umax
0.5 %
The harmonics for voltage on the 2-element meter are to be seen from the standpoint of the voltages being Dconnected internally.
3
The value can be read in CeweConfig and via the communication protocol but cannot currently be presented
on the display (meter firmware 1.2.0).
Page 28 of 80
Public
4.3.4
The presentation for units and the number of decimals depends on the magnitude of the value.
4.3.5
Harmonics measurement
Harmonics numbers 2 to 31 are measured for all currents and voltages. At a fundamental frequency of 50 Hz,
the second harmonic is 100 Hz, the third harmonic is 150 Hz, etc. Both the harmonics amplitude and phase
angle are measured and included in the calculation of power and energy, and can be read via the meters
communication protocols. In CeweConfig, harmonic amplitudes are presented with a diagram.
4.3.6
THD
THD stands for Total Harmonics Distortion and is a measurement of the amount of harmonics present in a
signal. Voltages and currents THD can be read via CeweConfig and on the display.
4.3.7
The harmonics measurements of voltage on the 2-element meters should be seen from the standpoint of the
voltages being D-connected internally in the meter. The harmonics measured are the vector sums of the
phases harmonics.
4.4
The CewePrometer has several inputs and outputs that can be configured to perform various tasks. Both inputs
and outputs are protected against over voltages by varistors. They also have an isolated interface between the
electronics and the surroundings to ensure personal safety. For electrical data on the meters inputs and
outputs, see Appendix H Connection and General Details (pg.75).
4.4.1
Inputs
Registration of pulses
The meter registers pulses on positive or negative flanks, depending on if the input is set to inverted or not. A
pulse must be at least 16 ms long to be guaranteed of being detected by the meter. The maximum pulse width
that the meter can handle is 60 s. By setting limits for maximum and minimum pulse lengths, the meter can be
Public
Page 29 of 80
limited as to what it detects as a valid pulse. Pulses with lengths beyond the established limits are ignored. The
occurrence of too long or too short pulses can also be configured to be recorded in the event log.
VCC
GND
Pulse
length
Pulse length
(inverted input)
The figure shows pulse lengths when an input is inverted or non-inverted, respectively.
4.4.2
Outputs
Pulse
Gap
Maximum pulse frequency at outputs limited so that the gap is at least as long as the pulse length.
Remote control
With this function, the output can be made active or inactive by sending commands to the meter via the
IEC62056-21/IEC1107 protocol. This functions could be used control anything that can be controlled
with a digital relay output.
Alarm output
When an output is set to functions as an alarm output, one or more of the user-defined alarms can be
chosen to indicate at the output. When an alarm occurs, the output switches to active, and when the
alarm state ceases, the output returns to inactive. In the section Alarms (pg. 36), user-defined alarms
are described and how they can be configured.
In contrast to the other selectable functions for outputs, alarm outputs can be inverted. Note that outputs
are inverted via firmware. If the meter loses its auxiliary power, the relay will open, regardless of it is
inverted or not.
End of MD period (maximum demand period)
At the end of a set MD period, the output will go active for one second before returning to the inactive
state. See the section Maximum demand (pg. 38).
Page 30 of 80
Public
4.4.2.1
Output states
An active output means a closed relay when the output is not inverted. When the output is inverted, the active
relay is open. The output can only be inverted when used as an alarm or pulse output The CewePrometer
outputs are of the solid-state type and when the meter is turned off, they are open.
4.4.2.2
Meter variants
inputs/outputs
CewePrometer-W
CewePrometer-R
0/0
0/12
2/10
4/6
4/8
Public
Page 31 of 80
4.5
Display sequences
The following is a description of the function properties of CewePrometers display sequences. The section
Display sequences (pg.32) describes how to navigate in the display sequences via the meters buttons, and
Appendix A - Display Layouts (pg.50) lists all of the CewePrometers available display layouts.
Menu for choosing one of the four display sequences. The names of the sequences can be configured.
The CewePrometer is equipped with a graphic display that can show the information available in the meter. To
organise the information, there can be up to five display sequences with a maximum of 40 selectable display
layouts in each. Each display sequence can be given a name that will be presented on the display.
Display sequence five is only accessible via the sealed button under the front panel window. The front panel
window can be sealed to provide additional security. For this reason, it is appropriate that display layouts with
sensitive information and sensitive functions be placed in display sequence five.
4.5.1
Automatic display cycling means that the display layouts in one or more display sequences are automatically
cycled by the meter. If, for example, display sequences 1 and 3 are configured for automatic display layout
cycling, the meter will first cycle the display layouts in sequence 1 from the first to last layout, and then continue
with sequence 3. After the last layout in sequence 3, cycling restarts with the first layout in sequence 1. The
display layouts cycle with a configurable delay of 1 to 30 seconds. If a user manually navigates in the display
sequences via the meter's buttons, cycling automatically stops and continues again after one minute.
4.5.2
The display sequences can be configured to be password protected to limit access for various users. When a
user chooses a password-protected display sequence via the meters buttons, a password entry field is
displayed. Only a correctly entered password gives access to the display sequence and to the display layouts
that are included in it. A password can be up to six characters long and include the characters A-Z, 0-9 and
:;<>=?@. Passwords are not case-sensitive.
Note1: Password cannot be used on the first active display sequence.
Note2: If a password-protected display sequence is configured for automatic display layout cycling, password
protection is deactivated.
4.5.3
One minute after a user has stopped navigating in the display sequences, the CewePrometer returns to the first
display layout in display sequence 1 if automatic display layout cycling is not activated for any display sequence.
4.5.4
The meter can be configured to not allow any changes of display sequence 4. This setting (Block configuration
of display sequence 4) is available in the Communication and Security form. The setting can only be changed at
access level 5.
Since access level 5 typically requires the security hardware jumper, this feature can be used to enforce a
display sequence that cannot be changed or deactivated using CeweConfig.
4.6
All CewePrometers are equipped with an optical port for communication. The meter can be optionally equipped
with one or two (three on the rack meter) additional communication ports with RS232, RS422 (RS485) or
Ethernet interfaces. CewePrometer supports the IEC62056-21 (formerly IEC 1107) and on the additional ports
Page 32 of 80
Public
also the DLMS/COSEM protocol. For more information on protocol support, see the document CewePrometer
meter reading.
4.6.1
Communication speed
The meters optical port always starts with a baud rate of 300 bps, regardless of what is configured, before
shifting over to the specified communication speed. This means that software (for example, CeweConfig) that
communicates with the meter via the optical port does not need to know the speed that the meters optical port
is set to. The optional ports designated as communication ports #1 and #2 differ in this respect. They start at the
specified baud rate from the beginning, which means that connected software must be aware of the speed to be
able to communicate. Communication port #1 can be set at a speed of between 300 bps and 19200 bps, and
communication port #2 can be set at a speed of between 1200 and 19200 bps. The optical port can be set at a
speed of between 300 and 9600 bps.
4.6.2
Modem initiation
If a modem is connected to one of the optional ports, a modem initiation string can be configured that the meter
sends via the serial port. The initiation string can be used to set the correct communication settings for the
modem and can consist of AT-Commands. The meter sends the initiation string when the meter is turned on
and thereafter every tenth minute. During ongoing communications, the meter waits to send the initiation string
until communications has stopped.
4.6.3
Bus address
A bus address can be defined for any serial communication port in the meter and shall have a value of 16 or
higher. This setting is only used for the DLSM/COSEM protocol. See the document CewePrometer meter
reading for more details.
4.6.4
Security
The meter has five authorisation levels that can limit access to the meter during communication via any of the
meters communication ports. Authorisation levels 1 and 2 are password-protected. Authorisation levels 3 to 5
may be protected by passwords or by a circuit board jumper.
Authorisation levels
1
Provides access to everything in level 1 plus access to set the clock and
finish historical periods (also resets maximum demand values).
4.6.4.1
The meter limits the total number of access attempts to six when incorrect passwords are entered. At the
seventh attempt, the meter blocks access whether the password is correct or not. The block is in effect until the
next hour shift. After that, new password attempts may be made.
4.6.4.2
Passwords
A password consists of up to 12 case insensitive alpha-numerical characters. The authorisation check may be
deactivated for a level by deleting the password. When connecting to the meter, access is granted to the highest
level that is lacking password regardless of the password given by the user.
If the setting Require COP password compliance (min length 6) is activated, a new password is required to be
at least 6 characters. The setting can only be changed at access level 5.
Public
Page 33 of 80
4.6.4.3
Security settings
The following security settings modify what can be configured at what access level. The settings are of the type
active/not active, and can only be changed at access level 5.
4.6.4.4
Inside the CewePrometer, there is space for a circuit board jumper that provides access to authorisation level 5
when fitted. If the meter is connected with authorisation at level 5, the function of the jumper can be modified.
Security can be heightened by requiring the jumper even for lower authorisation levels down to level 3. Security
can also be relaxed by making authorisation level 5 accessible via a password. Cewe Instrument can provide a
technical fact sheet, tfcr0004, that describes the procedure for opening the meter and fitting the jumper.
4.6.4.5
Generally the meter allows to be reconfigured at access level 3. This function requires level 5 for measuring
configuration.
4.7
Loggers
The CewePrometer has two identical, parallel and individually configurable loggers. That which is described in
this section applies both to logger 1 and logger 2.
4.7.1
Overview
A logger in a CewePrometer can log values for instant quantities, energy registers and external registers. Some
quantities can be logged both by phase and as total values for all three phases, others only as total values. The
table provides an overview of quantities that can be logged. Certain instant values in the table are not available
in 2-element meters and thus cannot be logged; see the section Instant values (pg. 27).
Quantity
By phase
Total
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 34 of 80
Instant
values
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Public
Frequency
Phase angle
Power factor
THD voltage
THD current
External registers 18
Voltage harmonic 1-31
Current harmonic 1-31
Voltage unbalance
Active energy import Delta
Active energy export Delta
Reactive energy import Delta
Reactive energy export Delta
Reactive energy inductive Delta
Reactive energy capacitive Delta
Reactive energy QI Delta
Reactive energy QII Delta
Reactive energy QIII Delta
Reactive energy QIV Delta
Apparent energy import Delta
Apparent energy export Delta
Not applicable
Yes
Yes
Yes
Yes
Not applicable
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Energy is logged as register values, i.e. at each logging occasion the current registers values is logged. Based
on these register values, the reading software can present the energy as register values, periodic energy or as
average power. CeweConfig provides all three alternatives.
Instant values can be logged as average, maximum or minimum value during the logging interval or as the
instantaneous value at the end of the logging interval. Maximums and minimums are detected based on 1 sec.
interval snapshots, and average is calculated based on 1 sec. interval snapshots.
4.7.2
A logger can store data in 1 to 50 channels. Common for all channels in a logger is that the logging interval that
can be configured from one minute up to one hour. A loggers capacity is dependent on number of channels and
logging interval. When the logger is full, the oldest values will be written over. The table shows the capacity in
number of days before the oldest value is written over.
Capacity in days
Number of logging channels
Logging
interval (min)
4.7.3
10
30
50
21
14
10
8.6
7.2
6.2
5.4
4.8
4.3
3.9
1.4
0.8
43
28
21
17
14
12
10
9.6
8.6
7.9
2.8
1.7
108
72
54
43
36
31
27
24
21
19
7.0
4.2
10
217
144
108
86
72
62
54
48
43
39
14
8.5
15
326
217
163
130
108
93
81
72
65
59
21
12
20
435
290
217
174
145
124
109
97
87
79
28
17
30
652
434
326
260
217
186
163
144
130
118
42
25
60
1304
869
652
521
434
372
326
289
260
237
84
51
Logged values are saved with time stamps, tariff information and flags that indicate events that have occurred
during the logging interval.
Public
Page 35 of 80
The time stamp indicates the end-time. If the logging interval is configured to one hour, a value with the
time stamp 15:00 refers to the period 14:00 to 15:00.
Tariff information indicates active rates for energy and power during the past interval.
To indicate events or states during an interval, a logged value can be stored with one or more flags.
Event or state
Time adjusted
Disturbed
Alarm
Parameter
changed
Incorrect energy
direction
Daylight savings
time
Voltage
loss/missing
Invalid value
Battery
Power loss
During the past interval all measuring voltages have been lost or missing.
B
O
For several of the flags, additional information can be viewed in the event log. A more exact time for events
is specified in the log.
Note: When power is calculated from logged energy values, the resulting values will be somewhat more precise
than when power is logged directly. This is because power is logged as an average value of instant values. The
instant values are read twice per second, while energy is accumulated continuously.
4.7.4
When the meter starts again after loss of auxiliary power, any energy accumulated up to the power loss will be
stored with a time stamp immediately following the power loss.
The incomplete log record before the power loss will have the following limitations:
If any instant values were configured to be logged, they will be recorded as 0.
The only notification flags that are handled are D, S and O.
If tariff is controlled using rate input, tariff will be recorded as 1.
4.8
Alarms
The CewePrometer is equipped with alarms to be able to indicate when measured quantities are over or under
a configurable limit value. The meter enters the alarm state when the limit value is reached. An alarm is
generated only after the alarm state has continued for a configurable time (delay). Alarms are configurable by
the user and are therefore called user-defined alarms. For the CewePrometer 1.2.0 or earlier, the maximum
delay is 64 seconds.
Note: There are alarms and events that cannot be configured, but instead, are always active. Examples of such
alarms are indication that the clock has been changed or that an auxiliary power loss has occurred. For more
information, see the section Event log (pg. 38).
Page 36 of 80
Public
4.8.1
Overview
For most user-defined alarms, the limit value is specified as a percentage of the nominal value, which is the
configured, nominal primary value (current, voltage or power). For 3-element meters, the limit value corresponds
to phase voltage, and for 2-element meters, line to line voltage. The following table provides an overview of
available alarms.
Alarm
Low voltage
High voltage
Low power factor
Voltage unbalance
Current unbalance
Internal error
Current without voltage
4.8.2
Comments
Indication
Alarms are always stored in the event log. Alarms can also be configured to indicate in one or more of the
following ways:
Alarm LED on meter front
Changed digital output level
Indication of a logged value with a flag
Public
Page 37 of 80
The alarm LED stops flashing and the digital output returns to inactive low after the alarm state passes.
4.9
Event log
The CewePrometer has a number of defined events and alarms that are stored in the meters event log when
they occur. The event log can contain a maximum of 100 events. Thereafter, the oldest will be removed to make
room for the new. The meter has a counter for the total number of events that have occurred since the latest
reset.
An event is represented by a time stamp and a code that indicates what has occurred. See Appendix B - Events
and Configuration Log (pg.58) for a complete list of all events. For certain events, data is also stored for the
events, for example, which phase the event concerns.
Events are divided into three categories:
User-defined alarms
The meter has a number of alarms that when they occur, generate an event in the event log. The
alarms each have an individual configuration that determines the conditions for when an alarm is to be
activated. See the section Alarms (pg. 36).
Meter events
The meter is also equipped with a number of alarms that are not configurable by the user, so-called
meter events. These have set conditions and are stored only in the event log. Examples of meter events
are auxiliary power loss and clock resetting. A complete list of meter events is in Appendix B - Events
and Configuration Log (pg.58)
Internal errors
The contents of the internal data structures, such as configuration and energy registers, are checked by
the meter. If an error is detected in one of the data structures, it is designated as an internal error. If an
internal error is indicated, the event log should be checked for related information, and suitable actions
should be taken. Internal errors are listed in Appendix B - Events and Configuration Log (pg.58).
4.9.1
Display of events
The event log can be viewed on the meters display if the display layout Events is configured to be included in
one of the meters display sequences. Only the time stamp and event code are shown on the display. A more
detailed description of the meter's events can be viewed in CeweConfig, which converts the code into plain text
and displays any related data. Via CeweConfig, the event log can also be printed out or saved to a file.
Page 38 of 80
Public
4.11.1 Overview
Up to eight quantities can be saved in the maximum demand registers, which makes a total of 24 values with
time stamps for when they occurred. The table shows the types of energy that can produce maximum demand
values.
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Reactive energy inductive
Reactive energy capacitive
Reactive energy QI
Reactive energy QII
Reactive energy QIII
Reactive energy QIV
Apparent energy import
Apparent energy export
The calculation interval for average values determines the period during which average values are calculated.
At the end of the interval, the new average value is compared with the previous and possibly stored as a new
maximum demand value. The calculation interval can be chosen between 1 and 60 minutes in the following
predefined steps: 1, 2, 3, 4, 5, 10, 15, 20, 30 and 60 minutes.
Example: A historical period has just been finished and all maximum demand values have been reset. The
meter is configured with a calculation interval of 30 minutes and active power as the quantity for which to
calculate the average value. The table is read from top to bottom and illustrates what will be stored in the
maximum demand registers at the various times.
Point in time
Average
power
12:59, 4 July
Highest value
Second highest
Third highest
13:00, 4 July
90 kW
90 kW 07-04 13:00
13:30
89 kW
90 kW 07-04 13:00
14:00
91 kW
91 kW 07-04 14:00
00:00, 5 July
75 kW
91 kW 07-004 14:00
75 kW 07-05 00:00
00:30
95 kW
95 kW 07-05 00:30
91 kW 07-04 14:00
00:00, 6 July
93 kW
95 kW 07-05 00:30
93 kW 07-06 00:00
91 kW 07-04 14:00
16:00, 7 July
94 kW
95 kW 07-05 00:30
94 kW 07-07 16:00
93 kW 07-06 00:00
Note: There is never more than one maximum demand value for one day.
4.11.1.1 Cumulative Maximum Demand
For each MD value there is an associated accumulating register. When a historical period is finished, the MD
values are accumulated to these registers.
Public
Page 39 of 80
Maximum demand
values
External registers
Historical register includes a number of stored registers, and dates/times when they were stored.
4.12.1.1 Finish historical period
By finishing a historical period, the current registers values are stored in historical registers and the maximum
demand values are reset. When a period is finished, an event is stored in the meters event log. Periods can be
finished in various ways:
Via meter button
Via CeweConfig
Note: The display layout Finish period will only work if the meter is configured to permit ending a period via a
button.
4.12.1.2 Lock out time for finish historical period
The Lock out time prevents the user to create a new historical period within a configurated time.
Page 40 of 80
Public
4.13.3 Season
A season refers to a period. During this period, the season defines the day types that will apply during the days
of the week. In the CewePrometer, there are 16 seasons per tariff structure. The seasons are arranged in a
sequence where one season replaces the previous at a predetermined date.
Public
Page 41 of 80
Day types
Three day types must be configured. Day type A to apply to energy during the autumn, winter and spring. Day
type B to apply during the summer months, and day type C for maximum demand values throughout the year.
Day type A
00:00
Rate 1
07:00
Rate 2
17:00
Rate 1
Day type B
00:00 Rate 1
Day type C
00:00 Rate 3
Seasons
Two seasons must be configured. The first season will apply during the summer period and the second the rest
of the year. The season that applies from 1 September will also apply from 1 January to 31 May.
06-01
Energy
MD
A
C
A
C
A
C
A
C
A
C
A
C
B
C
09-01
Energy
MD
B
C
B
C
B
C
B
C
B
C
B
C
B
C
Special day
For rate 1 to apply all of Christmas Eve, a special day must be configured. Because no year is specified, the
special day will apply every year.
12-24
Energy
MD
C
C
TOU register
A TOU register is configured to accumulate active energy in several registers for the different rates.
4.14.1 Overview
The tables present an overview of the transformer compensations in CewePrometer.
Instrument transformer compensations
Name
Value to entered
Voltage error L1, L2, L3
Amplitude error as percent
Phase angle in minutes
Current error L1, L2, L3
Amplitude error as percent
Phase angle in minutes
Power transformer compensations
Name
Copper losses, Total values
Iron losses, Total values
Page 42 of 80
Value to entered
Active loss as percent of nominal power
Reactive loss as percent of nominal power
Active loss as percent of nominal power
Reactive loss as percent of nominal power
Public
Powernom
Public
Page 43 of 80
State
Sags and swells
Duration
160 ms5 1 s
Registered in
Accumulating counter
Duration presented as
Duration not specified
> 1s
5
160 ms 3 s
Event log
Event log
Duration of state
<3s
Interrupt
>3s
Event log
Duration of state
4.15.2 Hysteresis
Hysteresis means that the limit for a state and the limit for when it is restored are different. This to avoid several
states being registered when the voltage level varies around a limit. The hysteresis limit is always midway
between the low or high limit and nominal voltage.
Primary voltage (example)
Percent
11 kV
110%
10,5 kV
105%
10 kV
100%
9,5 kV
95%
9 kV
90%
Duration sag
1 kV
10%
Duration
interrupt
4.16 Miscellaneous
4.16.1 General information texts
General information texts are used in the CewePrometer for all types of information, such as the name of the
station where the meter is installed. The information texts can be shown on the meter's display and read with
CeweConfig. There are four information texts that consist of a label and an associated text. Both the label and
text can be up to 17 characters long. To present information texts on the display, display layouts for this can be
entered in a display sequence.
Example of general information texts where the label is "Owner" and the text "Cewe Instrument".
Page 44 of 80
Public
Public
Page 45 of 80
Quantity
Unit
Quadrant I
Phase
Quadrant II
Quadrant III
Quadrant IV
Display layout
Import/Export
For quantities that can be Import or Export, a setting in the Display Sequence form controls whether Import is
shown as Imp or +, and correspondingly, whether Export is shown as Exp or -.
5.1
When the CewePrometer starts, the display layout Voltage Order is always shown for about 15 seconds. The
display layout shows the order of the connected measurement voltages. If the voltage order is correct, the
current direction is indicated with a + or a -. If not all voltages are connected, Phase missing is shown on the
display. The current direction is indicated with a + if the currents phase angle is following its voltage with a
maximum deviation of 90; if it is not, a - is displayed.
Page 46 of 80
Public
5.2
Use the buttons on the front of the CewePrometer to step through the display sequences. For more information,
see the Product Description (pg. 6) section for button placement.
Step forward
Step to next layout in the display sequence or moves upward in a menu.
Menu/Apply
The Menu/Apply button is used to open the menu where one of four configurable display sequences can be
chosen. The button is used to confirm choices or initiate other activities depending on the current display layout.
Step backward
Step to previous layout in the display sequence or moves downward in a menu.
Sealed button
A Short press to the sealed button provides access to the fifth display sequence. Press the button for about two
seconds to open the system menu. From the system menu, you can view program versions for all modules and
activate the trace function for the communication ports. For more information, see Using the display for
communication diagnostics (pg. 49)
5.3
5.3.1
Time of Use
5.3.2
Layout for finishing historical periods. #5 indicates total number of previously finished periods.
Finish a historical period means that all registers are saved and maximum demand values are reset. The meter
may be configured so that periods may be finished by pressing a button on the meter. For more information, see
the section Historical registers (pg. 40). Additionally, the display layout shown above must be included in a
display sequence. To finish a period, press the Menu/Apply button for about two seconds.
5.3.3
Public
Historical registers
Page 47 of 80
5.3.4
Switching rates
Historical registers also contain TOU registers, and for these, rates also can be changed. Choose historical
period and then press Menu/Apply to be able to change rate with the step buttons. Press Menu/Apply to return
to stepping between display layouts.
5.3.5
Logger
Logger
There are display layouts for viewing logger 1 and logger 2. Press Menu/Apply for about two seconds to view a
list of all logger items. Each item starts with date and time, followed by a row showing the notification flags for
that item. Then follows a row for every active channel in the logger, with value and unit.
5.3.6
Events
No of events.
The meter registers different types of events; see the section Event log (pg. 38). This display layout shows how
many events are saved in the meter. Press Menu/Apply for about two seconds to view a list of events in
chronological order with ID numbers. Explanations of these IDs are in Appendix B - Events and Configuration
Log (pg. 58).
5.3.7
Configuration log
No of changes.
Page 48 of 80
Public
5.3.8
Confirming alarms
By pressing Apply for about two seconds, alarms of the type internal error in the meter can be
confirmed/acknowledged. For more information on internal errors, see section Event log (pg. 38).
5.4
To facilitate troubleshooting of communications with the meter, there is a trace function integrated into the
CewePrometer. The incoming characters that the meter registers are presented on the display. The function can
be chosen from the system menu, accessible by pressing the sealed button for about two seconds. Use the step
buttons to choose one of the three communication ports: trace opto, trace port 1 or trace port 2. Confirm with the
Menu/Apply button and an empty display with a cursor at the upper-left corner will be shown.
Note that the procedure described here assumes the IEC62056-21/IEC1107 protocol.
Page 49 of 80
Instant Values
Page 50 of 80
Public
Energy Registers
Graphs
Public
Page 51 of 80
Historical Registers
Time of Use
TOU register 2 of 8.
Page 52 of 80
Public
\Miscellaneous
Total events.
No of configuration changes.
Logger
Public
Page 53 of 80
Transformer Compensation
Page 54 of 80
Public
Historical Registers
In display pictures where a star is present (where the number to the right of the star signifies a certain historical
period, element F of the OBIS code), it is possible to switch between periods by holding down the Apply button
for two seconds, and then using up/down buttons. This mode is indicated by the top row in the display being
black. Push the Apply button again to return to normal mode.
In display pictures with both historical period and rate, the period can be changed as described above. By
pushing the Apply button again, the bottom row in the display turns black. This indicates a mode where the rate
can be switched by using the up/down buttons. Push the Apply button a third time to return to normal mode.
Public
Page 55 of 80
External registers
An external register must have been configured for pulse input in the Digital I/O form to be available.
Furthermore, a rate register must be allocated for the external register for it to be available in rated version (E
0).
In rate pictures, hold down Apply for two seconds to be able to switch between rate 1 8 using up/down
buttons. Push Apply again to leave the switching mode.
Maximum Demand
Cumulative Demand
Page 56 of 80
Public
Rising Demand
Miscellaneous
Present date.
Public
Present time.
Page 57 of 80
Meter event
User-defined alarm
Internal error
Event
Data
Category
ID
None
None
None
None
None
14
15
16
None
17
None
18
None
19
None
20
None
21
None
22
None
23
None
24
Page 58 of 80
Public
None
25
26
27
28
29
30
Configuration changed.
None
42
Calibration changed.
None
43
Initiation changed.
None
44
45
None
46
None
47
None
49
None
1001
None
1002
None
1003
1004
1005
None
1006
None
1007
None
1008
None
1009
Public
Page 59 of 80
Configuration Log
The following configuration changes are registered in the configuration log. The parameter ID is shown to the
right of date and time in the meter display picture.
ID
Parameter
CT ratio
VT ratio
Secondary Voltage
Secondary Current
Page 60 of 80
Public
Contact in meter
Communication protocol
Handshaking
Data format
Baud rate
RD
TD
Signal GND
6
7
8
9
RTS
CTS
-
Connector in meter
Communication protocol
Data format
Baud rate
Public
Signal GND
TX+
TXRXRX+
Page 61 of 80
Hardware
Communication protocol
Data format
Baud rate
3009600 bps
Hardware
Ethernet RJ-45
Communication protocol
Data format
Baud rate
Page 62 of 80
Public
When Device Installer has found the device on your LAN, highlight it and click on Web configuration.
Click external browser to open a www-window. The device does not have any password. Just click OK when the
question about password is given.
Configure the Serial Settings screen as below.
By default, the baud rate in the CewePrometer is set at 9600 baud. If you choose to set it to another you also
need to change it for the appropriate port via CeweConfig software.
Public
Page 63 of 80
To save the new configuration, click the Apply Settings tag on the left menu.
Public
Click Port Settings and set the boxes Timeout reconnect, Server Reconnect and Raw Mode. Also check that
reconnect limit is set to 0.
Click Save and close.
Launch CeweConfig and connect to the meter on the appropriate Com port.
Specifications
Cable: Unshielded Twisted Pair (UTP) in categories 1 to 5e.
Public
Page 65 of 80
Page 66 of 80
Public
Meter Clock
What happens if a new successive adjustment is made when one is already underway?
The current adjustment will be stopped and the new begun.
What happens if the meter time is set within an hour before the change from daylight savings time to
standard time?
If the meter time is set to daylight savings time before the change, it will be set back to standard time
automatically at the approaching time change. If the meter time is set to standard time before the change, it will
not be affected at the approaching time change.
If you set the meter to use DST during the summer period, will the meter clock then change time to
DST?
No, the meter will always have the same time regardless when you set DST.
When summer time starts, the clock jumps one hour. What happens if the user sets the meter to a time
within that hour?
The mter will ignore the new time because that hour does not exist.
When the DST ends the clock will move backwards one hour. What happens if one set the time in the
meter to that hour? Will there be four or two occasions of that hour?
The meter assumes that the time is in DST if it is during that period and assumes it is in normal time when it is
in that period. The meter will not shift twice.
What happens if more than one input is used for clock synchronisation?
Several inputs can be used simultaneously to receive synchronising pulses even if this is unlikely.
How are logged values affected by the daylight savings time change?
According to the example:
Change from standard to daylight savings time
2005-03-28 01:30
3467.4 kWh
2005-03-28 03:00
3523.2 kWh
2005-03-28 03:30
3602.5 kWh
3345.4 kWh
BGX501-856-R02, CewePrometer User Manual
Page 67 of 80
2005-10-31 02:00
3756.7 kWh
2005-10-31 02:30
4132.8 kWh
2005-10-31 03:00
4583.1 kWh
Logged values during daylight savings time are labelled with the flag S. S means that the timestamp is in DST.
What are the possible consequences of adjusting the meter clock immediately?
Because CeweConfig does not permit the clock to be adjusted immediately without simultaneously resetting the
logging memory, this is purely hypothetical. If it were to be allowed, then if the clock is adjusted forward over
one or more interval limits, there will be empty spaces in the logging memory and values will be lacking for one
or more intervals.
It the clock is adjusted backward over one or more interval limits, one or more values will exist with the same
time stamps. In the worst event, this can result in data read from the meter not matching the expected period.
Page 68 of 80
Public
I1
I2
The currents second harmonic component specified as peak value, has doubled frequency compared
to the first harmonic.
( I 12
I RMS
I 22
...I 312 )
(U112 U 212
U121
2 U11 U 21 cos(U11 p U 21 p)
Calculated I2
In the 2-element meter, I2 is not measured but is calculated for monitoring purposes. It is calculated from the
currents fundamental vectors.
I 21
I 21
( I11
I 31 cos(I11 p I 31 p))2
Voltage unbalance
Class A
The basic measurement of voltage harmonics, for class A, is defined in IEC 61000-4-7 class I. That standard
shall be used to determine a 10/12-cycle gapless harmonic subgroup measurement, denoted Uisg,h in IEC
61000-4-7.
Power
Harmonic component power
The calculations below are for active power, the calculations for reactive are identical except for that cosfunctions are replaced with sin-functions.
P1n
Pn
3-element meter:
P1n
Public
U 1n I1n cos(
Page 69 of 80
2-element meter:
For 2-element meters, only the total power is calculated in each harmonic component.
1n
2n
Pn
P1
Active power in L1
Q1
Reactive power in L1
P1 P2 P3
Q1 Q2 Q3
Apparent power
S1
Apparent power in L1
S
S1
P2
Q2
P12
Q12
Energy
Energy is calculated by integrating power (P, Q and S) over time.
Definition of quadrants
The term phase angle is described under its own heading below.
Quadrant I: phase angle 190
Quadrant II: phase angle 90180
Quadrant III: phase angle -180(-90)
Quadrant IV: phase angle (-90)0
Active energy
Active energy is calculated for import and export. The direction is controlled by the sign for active power
(+ import, export).
Active energy import: quadrant I and IV
Page 70 of 80
Public
Reactive energy
Reactive energy is calculated for four quadrants. The quadrant is controlled by the sign for active and reactive
power (e.g., active power >= 0 and reactive power >= 0 corresponding to quadrant I).
Reactive energy import: quadrant I and II
Active energy export: quadrant III and IV
Apparent energy
Apparent energy is calculated for import and export. The direction is controlled by the sign for active power;
apparent energy is registered for the direction that the active energy has during the same period.
Apparent energy import: quadrant I and IV
Apparent energy export: quadrant II and III
Power Factor
pf ( L1)
P1/ S1
pf (Tot)
P/ S
The power factor is calculated without signs and is thus always positive.
Phase angle
( L1) U1 p I1 p
Phase angle for an element is calculated from the fundamental phase angles.
(Tot )
THD
Total harmonic distortion
THDeur
I 22
I 32 ...I n2
I12
I 22 ...I n2 1
100%
Where I 1 I n are the currents harmonic components. The calculation is made in the same ways for current
and voltage.
Public
Page 71 of 80
Transformer Compensations
Instrument transformer compensations
Instrument transformer compensations are specified as error in percent for amplitude, and as error in minutes
(one-sixtieth of a degree) for phase angle. These errors can be specified separately for all voltages and
currents.
AmpErr
PhaseErr
u meas
Measured voltage
Compensated voltage
Amplitude compensation
up
upmeas
PhaseErr
In 3-element meters, phase voltages are compensated and in 2-element meters, line to line voltages. The same
calculation is used for all currents and voltages.
Iron loss
FeLoss
P1meas
Measured power.
P1
Compensated power.
Nom
P1
P1meas
FeLoss Nom
Copper loss
CuLoss
Phase current.
inom
Nominal current.
P1
P1meas
U1 p
U1p
Page 72 of 80
Public
U2p
120
U 3p 120
The same system is represented graphically below. The vectors rotate in an anti-clockwise direction.
Public
Page 73 of 80
Rear panel
Side plates
Handle
Plastic parts
Inner window
Polycarbonate V0
Outer window
Polycarbonate V0
Side pieces
Polycarbonate/ABS V0
Battery cover
Polycarbonate/ABS V0
CewePrometer-W
Enclosure
Bottom plate
Polycarbonate/ABS V0
Meter cover
Polycarbonate/ABS V0
Inner window
Polycarbonate V0
Outer window
Polycarbonate V0
Battery cover
Polycarbonate/ABS V0
Terminal cover
Polycarbonate/ABS V0
PPO + 10 % GF V0
Terminals
Brass
Screws
Steel
Page 74 of 80
Public
Current circuit
Measurement current (In)
1- 10 A configurable
Measuring range
1 1000% of In
Burden
0.7 mVA/phase at 1 A
0.03 VA/phase at 5 A
Starting current
<0.1% of In
Voltage circuit
Measuring voltage (Un)
3-wire system:
3x100240 V
4-wire system:
3x57/99240/415 V
Measuring range
80% - Un 115%
Frequency range
50 Hz or 60 Hz +/- 5 %
Burden
5 mVA/phase at 57.7 V
17 mVA/phase at 120 V
67 mVA/phase at 240 V
Auxiliary power
CewePrometer-W
Internal auxiliary voltage/ Self Powered
Separate auxiliary voltage Uaux
40 276 VAC/DC
Power Consumption
Typically 6-8 VA
Max 14 VA (With additional communication module)
CewePrometer-R
Power Consumption
40 276 VAC/DC
Single supply
2 x 40 276 VAC/DC
Dual supply
Typically 6-8 VA
Max 14 VA (With additional communication module)
Accuracy
CewePrometer-W
Public
Page 75 of 80
CewePrometer-R
Temperature range
Working temperature range
-20C - +55C
-40C - +70C
-40C - +80C
Temperature coefficient
<0.3%/10C
Protection Class
CewePrometer-W
CewePrometer-R
Humidity
Non Condensing
Mounting Arrangement
CewePrometer-W
CewePrometer-R
Rack Mounted
Mechanical Environment
As per IEC standard & Category M1 as per EN standard
Electromagnetic Environment
As per IEC standard & Category E1 & E2 as per EN standard
Digital outputs
Type
Relay performance
Digital inputs
Type
Optical switch
48220 V
Incoming resistance
20k ohm
Page 76 of 80
Public
Tests have also been done in part for the following standards:
EN61038:1996 Time switches for tariff and load control. Applicable parts according to
accuracy requirements for the real time clock.
Certificates:
SP - Sweden
Certificate no. 22 00 04. CewePrometer-R Electronic watt-hour and var-hour meter
Certificate no. 22 00 05. CewePrometer-W Electronic watt-hour and var-hour meter
Performed by Ofgem - UK
Certificate no. 983. CewePrometer-R Electronic watt-hour and var-hour meter. Class 0.2S, 0.5S, 1
Certificate no. 999. CewePrometer-W Electronic watt-hour and var-hour meter. Class 0.2S, 0.5S
Performed by SGS - UK
Compliance with Code of Practise 1, 2, 3 &5
CewePrometer-R and CewePrometer-W
Public
Page 77 of 80
Argument
-d
Devicetype [modem|serialPort|opticalPort]
-b
Baudrate
-p
Port
-n
Phonenumber
-w
Password
-s
Serialnumber
-t
Trace
Page 78 of 80
Public
Notes
Public
Page 79 of 80
Cewe Instrument AB
Box 1006,
SE 611 29 Nykping
Sweden