Generator set data sheet

Model:
Frequency:
Fuel type:
kW rating:

C1000 D6
60
Diesel
920 Data Center Continuous

Spec sheet:

SS14-CPGK-DC60

Noise data sheet (open/enclosed):

ND50-OSHHP/ND50-CS550

Cooling system data:

MCP-1081

Fuel consumption

kW (kVA)

Ratings
Load
US gph
L/hr

920 (1150)
1/4
1/2
17.4
31.5
66
119

3/4
46.7
177

Full
63.3
240

Engine
Engine manufacturer
Engine model
Configuration
Aspiration
Gross engine power output, kWm
BMEP at set rated load, kPa
Bore, mm
Stroke, mm
Rated speed, rpm
Piston speed, m/s
Compression ratio
Lube oil capacity, L
Overspeed limit, rpm
Regenerative power, kW
Governor type
Starting voltage

Cummins
QST30-G4
Cast iron, 50 V12 cylinder
Turbo charged and charge air cooled
1007
2199
140
165
1800
9.9
14:1
133
2075 50
82
Electronic
24 Volts DC

Fuel flow
Maximum fuel flow, L/hr
Maximum fuel inlet restriction, mm Hg
Maximum fuel inlet temperature, C

570
203
71

2015| Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS82c-CPGK-DC (6/15)

Air
Combustion air, m3/min
Maximum air cleaner restriction, kPa

75
6.2

Exhaust
Exhaust gas flow at set rated load, m3/min
Exhaust gas temperature, C
Maximum exhaust back pressure, kPa

197
495
6.7

Standard set-mounted radiator cooling


Ambient design, C
Fan load, kWm
Coolant capacity (with radiator), L
Cooling system air flow, m3/sec @ 12.7 mmH2O
Total heat rejection, Btu/min
Maximum cooling air flow static restriction, mm H2O

40
42
192
17.07
31470
12.7

Weights*

Open

Enclosed

Unit dry weight, kgs


7416
N/A
Unit wet weight, kgs
7621
N/A
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions

Length

Width

Height

Standard open set dimensions, mm


Enclosed set standard dimensions, mm

4417
N/A

2000
N/A

2387
N/A

Genset outline
Open set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

2013| Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS82c-CPGK-DC (6/15)

Alternator data
Connection
Wye, 3-phase

Temp rise C
150/125 C

Duty
DCC

Alternator
HC6K

Voltage
380-480V

Ratings definitions
Data Center Continuous (DCC): Applicable for supplying power continuously to a constant electrical load for unlimited hours in a data
center application where a reliable utility is present. The Data Center Continuous (DCC) power rating is in accordance with ISO8528.

Formulas for calculating full load currents:


Three phase output

kW x 1000
Voltage x 1.73 x 0.8

See your distributor for more information.


Cummins Power Generation
Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax +44 (0) 1843 255902
E-mail: cpg.uk@cummins.com
Web: www.cumminspower.com
2015| Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS82c-CPGK-DC (6/15)

You might also like