Power ®

XP-DSM Field Installation Instructions for XM2 Power Supply


Pre-installation Assumptions:
These instructions assume the following:
• Connection to an XM2 power supply running firmware version 3.0 or higher
• Network using DOCSIS version 1.0, 1.1, or 2.0. See XP-DSM Network Provisioning Instructions information on
configuring the network
• A single IP mode configuration
• Completed network configuration, including assigning an IP address
Detailed instructions for both network and field personnel are available in the XP-DSM Installation and Operation Manual
(Alpha P/N 704-818-B0) available at www.alpha.com. The XP-DSM can also be configured to register a second IP
address on your customer network, allowing technicians access to the power supply from anywhere.
Before Installation:
• Verify that the device address is either 1, 2, or 3. The power supply's device address
cannot be set to zero and every power supply monitored by a single XP-DSM must have
a unique address. See instructions for checking the device address in the installation
and operation manual.
Verify Device Address
• Record the RF MAC address, located on the XP-DSM. This address indicates the type
of cable modem used with the XP-DSM and is needed for network provisioning.

Basic Steps:
1. Installing the XP-DSM in the power supply
2. Installing the battery sense cable
3. Connecting the RF drop
4. Make remaining front panel connections (tamper, serial port connections)
5. Start up and test the system RF MAC
Address

WARNING!

To reduce the risk of electric shock, remove the inverter module from the power supply prior to
installation. For units in service, backup battery power will not be available during this procedure.

Page 1 of 4
Total Power Solutions
Installing the XP-DSM Disconnect
1. Turn off the XM2 battery breaker and disconnect all inverter
module connections.
2. Loosen the inverter module thumb screws and slide the
inverter module out of the power supply just far enough to
disconnect the ribbon cable. Disconnect the ribbon cable and
remove the inverter module (Fig. 1). If the inverter module
is equipped with a communication module, remove it by
loosening the two Phillips captive screws (Fig. 2).
3. Insert the long side of the 18-pin jumper into the side of the
inverter module (Fig. 3).
Fig. 1
4. On the XP-DSM, find and record the RF MAC address. This
address is needed for network configuration. If you want to
set the unit to dual IP mode, see the instructions in the XP-
DSM Installation and Operation Manual, available at www.
alpha.com.
5. Line up the 18-pin jumper with the XP-DSM connector and
connect the unit to the inverter module (Fig. 4). Captive
6. Tighten the two captive screws to secure the XP-DSM. screws
7. Re-install the inverter module, reconnect the ribbon cable,
and make other front panel connections.

Fig. 2

Inverter Module

Fig. 3 Insert Long Side Into Connect the inverter module to


Inverter Module the XP-DSM connector
Fig. 4

Page 2 of 4
Total Power Solutions
Battery Sense Wire Kit Connections

To Power Supply

36V System 36V System


Single String NEG NEG NEG Dual String
874-842-21 (6') 874-842-20 (6')
874-842-27 (9') 3A 2A 1A 874-842-28 (9') NEG NEG NEG

3A 2A 1A
POS POS POS
Vbatt 3A [C] 36V

Vbatt 1A [C] 12V


Vbatt 2A [C] 24V
POS POS POS
A/B [C/D] NEG

Vbatt 2A [C] 24V


Vbatt 3A [C] 36V

Vbatt 1A [C] 12V


A/B [C/D] NEG
Pin 1

Pin 4

Pin 2
Pin 3

Pin 1

Pin 3
Pin 4

Pin 2
5 1
5 1
6 2
6 2
7 3 3
7

Vbatt 2B [D] 24V

Vbatt 1B [D] 12V


Vbatt 3B [D] 36V
8 4 8 4

Pin 6

Pin 5
Pin 7
Back of Plug
Back of Plug

NEG NEG NEG

3B 2B 1B

POS POS POS

To Power Supply
48V System 48V System
Single String Dual String
874-841-20 (6')
875-841-21 (6')
875-841-25 (9') 874-841-24 (9') NEG NEG NEG NEG

To Power Supply 4A 3A 2A 1A

POS POS POS POS


A/B [C/D] NEG

Vbatt A/B [C/D] 48V


Pin 1

Vbatt 2A [C] 24V

Vbatt 1A [C] 12V


Vbatt 3A [C] 36V

Pin 3

Pin 2
Pin 4
Pin 8

NEG NEG NEG NEG

4A 3A 2A 1A
Vbatt 3B [D] 36V

Vbatt 2B [D] 24V

Vbatt 1B [D] 12V


Pin 7

POS POS POS


Pin 6

POS
Pin 5
Vbatt 3A [C] 36V

Vbatt 1A [C] 12V


Vbatt 2A [C] 24V
A/B [C/D] NEG

Vbatt 4A [C] 48V


Pin 1

Pin 4

Pin 2
Pin 3

NEG NEG NEG NEG


Pin 8

4B 3B 2B 1B

POS POS POS POS

Page 3 of 4
Total Power Solutions
Connecting the RF Drop
Connect the RF drop according to the diagram. The recommended downstream RF level is 0 dBmV.

CAUTION!

Install a grounded surge suppressor (Alpha P/N 162-028-10) or equivalent.

STAT

ALM
XP-DSM
RDY
COM
LNK

RF
DS
REG

DC
TMPR

Battery
Breaker

Battery

RF Cable
O
nput

Temp

to Headend
Probe

Grounded Surge Protector (required)

Front Panel Connection Overview

Make the front panel connections appropriate for your configuration.

Generator (ECM)

AlphaBus

"Master"
XM XM2
XM2
Dashed lines indicate
STAT
wiring for 48V strings
S S
Y Y
ALM
S S RDY
COM
C C LNK
O
M
O
M

RF
RF Cable 4A 3A 2A 1A
REG
DS Network
DC 36/48V
TMPR

24V 12V
Battery Pack
Battery 48V 36V

C
O
Sense
M

4B 3B 2B 1B

36/48V
LOCAL
Battery Wire Sense
Battery Pack
Harness Battery
48V 36V 24V 12V
Sense

Initial Start-up
1. Plug the power supply into the AC outlet and turn on the battery breaker.
2. The XP-DSM LEDs blink three times and the RDY light begins blinking on and off.
3. Verify no alarms are active.
4. Verify LNK LED is blinking (not on solid).
5. Verify the DS and REG LEDs are on solid (this verifies successful network registration). A solid Registration LED
indicates registration with the CMTS. Use this indicator to confirm the communication with the headend.

For more information visit www.alpha.com


United States Bellingham, Washington Tel: 360 647 2360 Fax: 360 671 4936
Canada Burnaby, British Columbia Tel: 604 430 1476 Fax: 604 430 8908
Page 4 of 4
Alpha Technologies reserves the right to make changes to the products and information contained in this document without notice.
Copyright © 2006 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. member of The Alpha Group™ is a trademark of Alpha Technologies. member of The GroupTM
704-818-B1-002, Rev. B (10/2006)