You are on page 1of 16

UniMix JTI

Secondary distribution switchgear


with rapid delivery times

UniMix JTI:
thought up and built for industry customers
The JTI Just To Install acronym indicates a type of medium voltage switchgear
for primary and secondary distribution featuring very rapid delivery and putting
into service.

Deliver
y of UniMix JTI switchgear usually takes place within two weeks.
Delivery
By means of a product configurator which allows precise and rapid estimates to
be prepared, the customer receives complete proposals and is relieved of the
task of preparing the technical specifications and design drawings.
JTI switchgear are based on the standard switchgear design and have a range of
types able to satisfy even special installation requirements, thanks both to their
electrical characteristics and to their standard fitting of accessories.

UniMix JTI are always fitted with mechanical and electro-mechanical interlocks
according to IEC 62271-200 Standards and are available with gas circuit-breakers. All the solutions have the incoming unit and use of the on-board circuitbreaker PR521 release or, alternatively, the REF542plus unit, as the protection unit.
The technical design documentation is immediately available and the customer
gives official approval of the project during the offer stage.

UniMix JTI:
thought up and built for industry customers
Main Components

REF542plus multi-function control


and protection unit.

SHS2 gas switch-disconnector.

HD4/Unimix-F gas circuit-breaker


(with PR521 release and current sensors).

Current transformer.
Current/voltage sensor.

Characteristics
Version

Electrical characteristics
Rated voltage
Test voltage (50 Hz/1 min)
Impulse withstand voltage
Rated frequency
Rated current
Short-time withstand current (1s)
Peak current

24
50
125
50
630
16
40

kV
kV
kV
Hz
A
kA
kA

General characteristics
Units and sides made of pre-galvanised sheet
Front panel doors painted grey RAL 7035
Fixed HD4/Unimix-F circuit-breaker
On-board circuit-breaker current sensors or
combined current/voltage sensors according to DIN
Standards
On-board circuit-breaker PR521 protection release or
REF542plus electronic protection and control unit

Standard (not arc proof)


Classification
Service continuity: LSC2A
Partitions: PM (Partition Metallic)
Degree of protection
IP2X inside the switchgear
IP3X on the external housing (except for the
operating seats)
IP2XC on the operating seats
Mechanical interlocks available
Circuit-breaker with line-side insulator
Line-side insulator with earthing switch
Door with earthing switch
Auxiliary circuit voltage

Conformity with Standards

220 V a.c.

IEC 62271-200
EN 62271-200

UniMix JTI:
thought up and built for industry customers
Configurations available
JTI A1-CLsx Switchgear

No. 1 Incoming/Outgoing Unit with CL Left Cable Riser Unit + No. 1 P1/F Unit
with fixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,
operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release with
electronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contact
signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth
fault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable key
in the open position
- 1 removable key with earthing switch in the closed position and 1 removable key in
the open position

Switchgear description

Or
dering code
Ordering

Equipment

JTI_A1_Z_CLSX_N_N

1VCF594000R0062

Without accessories

JTI_A1_Z_CLSX_N_R

1VCF594000R0063

Anticondensation heater

JTI_A1_Z_CLSX_I_N

1VCF594000R0064

Internal light

JTI_A1_Z_CLSX_I_R

1VCF594000R0065

Internal light and anticondensation heater

JTI A1-CLdx Switchgear

No. 1 Incoming/Outgoing Unit with CL Right Cable Riser Unit + No. 1 P1/F Unit
with fixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,
operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release with
electronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contact
signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth
fault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable key
in the open position
- 1 removable key with earthing switch in the closed position and 1 removable key in
the open position

Switchgear description

Or
dering code
Ordering

Equipment

JTI_A1_Z_CLDX_N_N

1VCF594000R0066

Without accessories

JTI_A1_Z_CLDX_N_R

1VCF594000R0067

Anticondensation heater

JTI_A1_Z_CLDX_I_N

1VCF594000R0068

Internal light

JTI_A1_Z_CLDX_I_R

1VCF594000R0069

Internal light and anticondensation heater

UniMix JTI:
thought up and built for industry customers
Configurations available
JTI A1-AC Switchgear

No. 1 Incoming/Outgoing with top cable entry AC + No. 1 P1/F Unit with
fixed circuit-breaker
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release,
operation counter, 2 NO + 2 NC auxiliary contacts, undervoltage release with
electronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contact
signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth
fault
SHS2/IB switch-disconnector with:
- 1 removable key with line-side insulator in the closed position and 1 removable key
in the open position
- 1 removable key with earthing switch in the closed position and 1 removable key in
the open position

Switchgear description

Or
dering code
Ordering

Equipment

JTI_A1_Z_AC_N_N

1VCF594000R0070

Without accessories

JTI_A1_Z_AC_N_R

1VCF594000R0071

Anticondensation heater

JTI_A1_Z_AC_I_N

1VCF594000R0072

Internal light

JTI_A1_Z_AC_I_R

1VCF594000R0073

Internal light and anticondensation heater

JTI A2-CLsx Switchgear

No. 1 Incoming/Outgoing with top cable entry A2 AC + No. 1 P1/F Unit with
fixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts, operation counter and springs
charged signalling, undervoltage release with electronic time-delay device (selectable
delay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltage
sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the open
position
- with 1 removable key with the earthing switch in the closed position and 1
removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for the
earthing switch

Switchgear description

Or
dering code
Ordering

Equipment

JTI_A2_Z_CLSX_N_N

1VCF594000R0074

Without accessories

JTI_A2_Z_CLSX_N_R

1VCF594000R0075

Anticondensation heater

JTI_A2_Z_CLSX_I_N

1VCF594000R0076

Internal light

JTI_A2_Z_CLSX_I_R

1VCF594000R0077

Internal light and anticondensation heater

UniMix JTI:
thought up and built for industry customers
Configurations available
JTI A2-CLdx Switchgear

No. 1 Incoming/Outgoing Unit with CL Right Cable Riser Unit + No. 1 P1/F Unit
with fixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts, operation counter and springs
charged signalling, undervoltage release with electronic time-delay device (selectable
delay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltage
sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the open
position
- with 1 removable key with the earthing switch in the closed position and 1
removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for the
earthing switch

Switchgear description

10

Or
dering code
Ordering

Equipment

JTI_A2_Z_CLDX_N_N

1VCF594000R0078

Without accessories

JTI_A2_Z_CLDX_N_R

1VCF594000R0079

Anticondensation heater

JTI_A2_Z_CLDX_I_N

1VCF594000R0080

Internal light

JTI_A2_Z_CLDX_I_R

1VCF594000R0081

Internal light and anticondensation heater

JTI A2-AC Switchgear

No. 1 Incoming/Outgoing with top cable entry AC + No. 1 P1/F Unit with
fixed circuit-breaker
Presence of voltage on busbar side and cable side
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, shunt
closing release, 3 NO + 4 NC auxiliary contacts, operation counter and springs
charged signalling, undervoltage release with electronic time-delay device (selectable
delay times: from 0.5 s to 3 s) and contact signalling release de-energised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltage
sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator closed and 1 removable key in the open
position
- with 1 removable key with the earthing switch in the closed position and 1
removable key in the open position
- auxiliary contacts: 1 NO or NC for the line-side insulator and 1 NO or NC for the
earthing switch

Switchgear description

Or
dering code
Ordering

Equipment

JTI_A2_Z_AC_N_N

1VCF594000R0082

Without accessories

JTI_A2_Z_AC_N_R

1VCF594000R0083

Anticondensation heater

JTI_A2_Z_AC_I_N

1VCF594000R0084

Internal light

JTI_A2_Z_AC_I_R

1VCF594000R0085

Internal light and anticondensation heater

11

UniMix JTI:
thought up and built for industry customers
Configurations available
JTI B1 Switchgear

No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer Protection Units
P1/A Incoming Unit
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p 230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NC
auxiliary contacts, operation counter, undervoltage release with electronic time-delay device
(selectable delay times: from 0.5 s to 3 s) and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open
position
- with 2 removable keys with the earthing switch in the open position
P1/F Transformer Protection Unit
Presence of voltage on cable side
HD4/Unimix-F p230 circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts and
operation counter
PR521 protection release (50-51) with 2 on-board circuit-breaker 80A sensors
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open
position
- 1 removable key with the earthing switch in the closed position and 1 removable key in the open
position

12

Switchgear description

Or
dering code
Ordering

Equipment

JTI B1

1VCF594000R0056

Without accessories

JTI B2 Switchgear

No. 1 Incoming Line with P1/A Unit + No. 2 P1/F Transformer Protection Units
P1/A Incoming Unit
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p 230 non-motorised circuit-breaker with shunt opening release, shunt closing release, 3
NO + 4 NC auxiliary contacts, operation counter, springs charged signalling, undervoltage release with
electronic time-delay device (selectable delay times: from 0.5 s to 3 s) and contact signalling release deenergised
REF542plus protection and control unit with 3 ABB type KEVCD current/voltage sensors and toroid for
earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open
position
- with 2 removable keys with the earthing switch in the open position
- auxiliary contacts: 1 NO or NC for line-side insulator and 1 NO or NC for earthing switch
P1/F Transformer Protection Unit
Presence of voltage on cable side
HD4/Unimix-F p 230 circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts and
operation counter
PR521 protection release (50-51) with 2 on-board circuit-breaker 80A sensors
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open
position
- 1 removable key with the earthing switch in the closed position and 1 removable key in the open position

Switchgear description

Or
dering code
Ordering

Equipment

JTI B2

1VCF594000R0057

Without accessories

13

UniMix JTI:
thought up and built for industry customers
Configurations available
JTI B3 Switchgear

No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer Protection Units with switchdisconnector
P1/A Incoming Unit
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary
contacts, operation counter, undervoltage release with electronic time-delay device (selectable delay times:
from 0.5 s to 3 s) and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- with 2 removable keys with the earthing switch in the open position
P2 Transformer Protection Unit (unit width: 500mm)
Presence of voltage on cable side
SHS2/T2F switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- 1 removable key with the earthing switch in the closed position and 1 removable key in the open position
- shunt opening release
- fuse-holder
- mechanical trip system for blown fuse
- contact for signalling fuse blown
- auxiliary contacts: 2 NO or NC for line-side insulator and 2 NO or NC for earthing switch
Fuses not included in the supply

14

Switchgear description

Or
dering code
Ordering

Equipment

JTI B3

1VCF594000R0058

Without accessories

JTI B4 Switchgear

No. 1 Incoming Line with P1/A Unit + No. 2 P2 Transformer Protection Units with switch-disconnector
P1/A Incoming Unit
235 mm LV compartment
Presence of voltage on busbar side and cable side
HD4/Unimix-F p230 non-motorised circuit-breaker with shunt opening release, 2 NO + 2 NC auxiliary contacts,
operation counter, undervoltage release with electronic time-delay device (selectable delay times: from 0.5 s to 3 s)
and contact signalling release de-energised
PR521 protection release with 2 on-board circuit-breaker sensors and toroid for earth fault
SHS2/IB switch-disconnector with:
- 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- 2 removable keys with the earthing switch in the open position
P2 Transformer Protection Unit (unit width: 375mm)
Presence of voltage on cable side
SHS2/T2F switch-disconnector
- with 1 removable key with the line-side insulator in the closed position and 1 removable key in the open position
- with 1 removable key with the earthing switch in the closed position and 1 removable key in the open position
- shunt opening release
- fuse-holder
- mechanical trip system for blown fuse
- contact for signalling fuse blown
- auxiliary contacts: for line-side insulator and 2 NO or NC for earthing switch
Fuses not included in the supply

Switchgear description

Or
dering code
Ordering

Equipment

JTI B4

1VCF594000R0059

Without accessories

15

16

ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
Petzower Strasse 8
D-40472 Ratingen
D-14542 Glindow
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: calor.info@de.abb.com
Internet:http://www.abb.de/calor

1VCP000249 Rev.B, en Technical catalogue 2006.10 (UniMix JTI)

The data and illustrations are not binding. We reserve the right to make changes
in the course of technical development of the product.

ABB Power Technologies S.p.A.


Unit Operativa Sace
Via Friuli, 4
I-24044 Dalmine
Tel: +39 035 395111
Fax: +39 035 395874
E-mail: sacetms.tipm@it.abb.com
Internet://www.abb.com

You might also like