SCOPE OF WORK
TYPE OF MACHINE : WATER-COOLED PACKAGED UNIT
INTERVALS: MONTLY, HALF-YEARLY,YEARLY.
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Belt tension.
Pulley Alignment at fan wheel.
Check refgrigeration pressure.
Check starter board / thermostat in plant room.
Motor ampere and voltage.
Clean filter, drain pan and flush drain pipe.
Clean cooling coil with water.
Check condenser water in and out
PROGRAM B ( HALF YEARLY)
Relubricate bearing motor and blower.
Check locking collar and allen key.
Temperature on coil off coil.
Check intergrity of cable.
Service starter panel.
Check corrosion.
PROGRAM C ( YEARLY )
Clean condenser strainer. ( if applicable)
Chemical cleaning, condenser, cooling coil if needed.
Megger the 3 phase motor.

ACS
SCOPE OF WORK
TYPE OF MACHINE : AIR-COOLED SPLIT UNIT 1HP-5HP
INTERVALS: MONTLY, HALF-YEARLY,YEARLY.
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Check proper function and damage to unit.
Check for condensation at drainpan.
Check for damage on refrigerant piping.
Check operation of temperature, fan and timer controls.
2. Maintenance
Clean air filter.
Clean air intake coil surfaces (outdoor and indoor)
Check and clean condensate drainage. (Flust Drainpan)
PROGRAM B ( HALF YEARLY)
Check Support and brackets.
Check for corrosion.
Check for refrigerant leaks.
3. Electrical check.
Check intergritiy of cables and connectors.
Check operation of starter lights and indicators.
PROGRAM C ( YEARLY )
Chemical cleaning outdoor ang indoor unit.

COOLING TOWER
SCOPE OF WORK
TYPE OF MACHINE : COOLING TOWER
INTERVALS: MONTLY AND YEARLY.
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Inspecting the general condition of unit.
Cleaning debris from unit.
Cleaning and flushing sump.
Cleaning sump strainer.
Checking and adjusting sump water level.
Inspecting heat transfer section and reporting condition.
Inspecting spray nozzles or water distribution pans.
Checking and adjusting fan belt tension. ( it applicable)
Checking unit for unusual noise or vibration.
Checking fan bearing locking collars.
Checking motor voltage and current
Checking fan rotation without obstruction
Checking fan and pump motor for proper rotation.
Checking water balancing.
PROGRAM B ( HALF YEARLY)
Lubricating fan shaft bearing ( if applicable)
Lubricating motor base adjusting screw
Inspecting gear box oil comtimination changing gear box oil when required.
Draining sump ang piping.
Megger motor.

PUMP
SCOPE OF WORK
TYPE OF MACHINE : PUMP
INTERVALS: MONTLY, HALF-YEARLY,YEARLY.
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Check for proper function and signs of damage.
Check corrosion
Check security of mounting
Check intergrity of cables and connectors.
Check for the abnormal noise and vibration ( at bearing side )
Check for execcive leaking ( replace new seal if applicable)
Check the operation of flow and pressure gauges.
Check for condensation.
Check operation electric lights and indicators
Check control panel for sign of overheating
Check fluid drainage
2. Room Condition
Check general condition of room.
Check ventilation , lighting and drainage.
Check security of doors and locks ( included fire extinguisher )
PROGRAM B ( HALF YEARLY)
Clean equipment
Lubricate bearing
PROGRAM C ( YEARLY )
Check for presence of circuit diagrams
Megger motor

FCU
SCOPE OF WORK
TYPE OF MACHINE : FAN COIL UNIT
INTERVALS: MONTLY, MONTH, HALF YEARLY, YEARLY..
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Check starter panel
Check condition of air filter ( clean or change )
Check for abnormal noise and vibration.
Check for condensation.
Check for leakage at valves and flanges.
Check for condensate drain blockage
Check for damage to insulation
Check operation of motorized valves and controls.
2. Maintenance
Check and clean condensate drainage.
3. Electrical check.
Check intergrity of cables and connectors.
Check operation of starter lights and indicators.
PROGRAM B ( HALF YEARLY)
Check supports and brackets
Service starter panel
Check for corrosion.

AHU
SCOPE OF WORK
TYPE OF MACHINE : AIR HANDLING UNIT
INTERVALS: MONTLY, MONTH, HALF YEARLY, YEARLY...
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Check for abnormal noise and vibration.
Check for normal readings on temp/pressure gauges.
Check condition of air filter ( clean or change)
Check for condensation.
Check for water leakage at valves and flanges.
Check operation of stanby or duty motor
Check plant room switch board.
Check operation of motorized valves and controllers.
2. Maintenance
Clean coils with low pressure water
Inspect & clean condensate pan and drainage
3.External check
Check all seals and gasket ( use sealand if needed )
Check AHU panels, plates, latches and etc.
4. Cleanliness and security
Check the cleanliness and drainage of plant room.
Check lighting and switches in plant room
Check locks and security in plant ( included fire extinguisher )
PROGRAM B ( HALF YEARLY)
Lubricate bearings
Clean fan
Check damper mechanism
Check bearing collar for tightness
Check and adjust/align belt tension
Service starter panel / switch board
PROGRAM C ( YEARLY )
Chemical cleaning
Cleaning chill water strainer
Megger motor insulation

WINDOW
SCOPE OF WORK
TYPE OF MACHINE : WINDOW UNIT
INTERVALS: MONTLY, MONTH, HALF YEARLY, YEARLY...
PROGRAM A ( MONTLY SERVICE)
1.General Inspection.
Check proper function and damage to unit.
2. Operation check.
Check for abnormal noise and vibration
Check for condensation
Check for missing knobs, switches, etc.
Check operation of thermostat, fan and timer.
3. Maintenance
Clean air filter and grills.
Check and clean condensate drainage ( flushing )
Clean air intake coil surfaces.
4. Electrical check
Check integrity of cables and connector
Check operation of starter, light and indicators.
PROGRAM B ( HALF YEARLY)
Check supports and brackets
Check for corrosion
Check for refrigeration leaks.

VENTILATION FAN
SCOPE OF WORK
TYPE OF MACHINE : VENTILATION FAN
INTERVALS : 1 MONTH, HALF YEARLY
PROGRAM B ( MONTLY SERVICE)
1.General Inspection.
Check proper function and damage to unit.
2. Operation check
Check for abnormal noise and vibration.
3. Electrical check
Check intergrity of cables and connectors.
PROGRAM B ( HALF-YEARLY)
Check supports and brackets.
Clean fan

Provided customer agree to pay.

SCOPE OF WORK
AIR COND SWITCH BOARD : STAR DELTA, AUTO TRANS, DOL STARTER
INTERVALS : 1 MONTH, HALF YEARLY
PROGRAM B ( MONTLY SERVICE)
1.General Inspection.
Check for signs of damage.
Check proper support and mounting
Check all panels are securely fastened-lock, latches, hinges.
2. Maintenance
Check for abnormal overheating, humming or noise.
Check proper operation of meters, light and indicators.
Vote voltage and current.
PROGRAM B ( HALF-YEARLY)
Check intergrity of cable, conduits, connectors and terminator.
Check for signs of corrosion
Check relay
PROGRAM C ( YEARLY )
Check Circuit Breaker.
Check for presence of safety chart, circuit diagram.
Check Earthing.

SCOPE OF WORK
TYPE OF MACHINE : RECIPROCATING CHILLER AIR COOLED / WATER COOLED
INTERVALS : 1 MONTH, QUARTELY, HALF YEARLY, YEARLY.
PROGRAM B ( MONTLY SERVICE)
1.General Inspection.
Check proper function and damage to unit.
Check for abnormal noise and vibration
Check temp/pressure gauges reading
Checck for condensation
Check for water leakage at valves and flanges
Check chiller switchboard
Clean condenser coil ( when applicable )
2. Maintenance
Check refrigerant charge, refill if needed.
Check compressor oil colour, change if needed.
Inspect compressor oil filter & dryer.
Analysis of chiller performance
Check all seals ang gaskets.
3. External check
Check all seals and gaskets
Check chiller covers, plates. Latches, etc.
4. Cleanliness and security
Check the cleanliness and drainage of chiller room.
Check lighting and switches in chiller room.
Check locks and security devices in chiller room. Included fire-extinguisher.
PROGRAM B (QUARTERLY-YEARLY)
Service chiller starter board ( only apply BAS Control System)
PROGRAM C ( HALF-YEARLY SERVICE )
Service chiller starter board ( apply to operator assist system
PROGRAM D ( YEARLY SHUTDOWN SERVICE)
The following tasks are performed once year during a shutdown period in order to evaluate your
Equipment status and prepare your unit for the next year :
Meging and recording motor winding resistance.
Change oil, clean oil sump, oil strainer and conducting an oil analysis.
Changing the filter drier
Checking the crankcase heater for proper operation
Tightening the power wiring on contactors in the motor terminal box.

PROGRAM D ( YEARLY SHUTDOWN SERVICE) continued


Cleaning all contactor and recommended replacement if required
Checking oil relay, operating control and safeties
Checking and calibrating all control, safeties
Checking for general condition and operation
Logging operating conditions and indentifying inconsistences
Adjusting operating control if required
Checking for proper oil level and refrigerant charge
Checking the oil temperature and crankcase heater
Inspecting starter, relay and controls
Inspecting the air-cooled condenser fan, and motor operation
Removing debris from inside and around the air-cooled condenser if applicable.
Reviewing operating procedures and the owners log the operator.

SCOPE OF WORK
TYPE OF MACHINE : YS 1 ( ROTARY SCREW CHILLER)
INTERVALS : 1 MONTH, QUARTELY, HALF YEARLY, YEARLY.
PROGRAM B ( MONTLY SERVICE)
1.General Inspection.
Check proper function and damage to unit.
Check for abnormal noise and vibration
Check temp/pressure gauges reading
Checck for condensation
Check for water leakage at valves and flanges
Check chiller switchboard
2. Maintenance
Check refrigerant charge, refill if needed.
Check compressor oil colour, change if needed.
Inspect compressor oil filter & dryer.
Analysis of chiller performance
Check all seals and gaskets.
Check chiller cover plates, latches, etc.
3. Cleanliness and security
Check the cleanliness and drainage of chiller room.
Check lighting and switches in chiller room.
Check locks and security devices in chiller room. Included fire extinguisher.
PROGRAM B (QUARTERLY-YEARLY)
Service chiller starter board ( only apply BAS Control System)
PROGRAM C ( HALF-YEARLY SERVICE )
Service chiller starter board ( apply to operator assist system
PROGRAM D ( YEARLY SHUTDOWN SERVICE)
1.Checking the Compressor- Motor Assembly
Recording voltages
Meging and recording motor winding resistance
Lubricating open motor
Checking the alignment on open motor drive units.
Checking the coupling
Checking seals
Checking operation and calibration of slide valve potential meter.

PROGRAM D ( YEARLY SHUTDOWN SERVICE) continued


2. Checking the Compressor Oil System.
Change oil, oil filter and dryer
Conducting analysis on oil and oil filter at an independent laboratory.