Outdoor Power System

TP48120A-HD09A1
Introduction
TP48120A-HD09A1 is a small outdoor cabinet to supply power for
wireless site. It configures 30A/50A rectifier modules to supply
rated of 120A output current, with heat exchange cooling for
equipment cabin and fan cooling for battery cabin. The cabinet is
compactly designed and support various installation scenarios
such as wall mounted, pole mounted or grounding. It has excellent
performance such as wide range of AC input voltage, high power
efficiency, surge protection, intelligent temperature and battery
management, and remote management.

Features
High protection level:IP55
High efficiency of rectifier module: >96%
Super temperature performance for rectifiers with range from
-40 to 75
The power module supports hot-swapping, easy to install and
maintain
Temperature control system built-in door, easy to maintain,
clean, replace

Strong anti-theft design: Door embedded, hinge hidden, 3point lock, door sensor, support padlock
Intelligent battery management, prolong battery lifespan

Pole Mounted
(Pole size:114220mm)

Support battery anti-reverse function, reducing operating risk


Support remote management, reducing customer operating

cost

Application Scenarios
Outdoor wireless site
Outdoor enterprise communication network

Wall Mounted

Specifications

System

AC
Distribution

Dimension

650mm(W)650mm(D)900mm(H) (excluding base)

Weight

75kg (without rectifier module and battery)

Cooling mode

Heat exchange(equipment cabin) +Fan cooling(battery cabin)

Cooling capacity

1500W

Heater

500W(optional)

Installation mode

On ground\Wall mounted\Pole mounted

Cabling mode

At the bottom, inlet/outlet downwards

Maintenance mode

In front

Noise

ETS300 753 4.1E standard

Protection level

IP55

Battery space

8U (100AH)

User space

8U

MTBF

200,000 hours

Input mode

Three phase, single phase

Input voltage

85VAC300VAC, rated: 220VAC;

Input frequency

45~65Hz, rated value: 50Hz/60Hz

Input capacity

163A/3P

SPD

20kA/40kA, 8/20s

Maintenance socketAC output Universal


Three phase/single phase:
116A/1P(maintenance socket)
AC output
116A/1P

DC
Distribution

Rectifier

Output voltage

42~58VDC, rated value: 53.5VDC

Maximum capacity

120A

Battery branch

1x125A MCB

LLVD branch

180A MCB, 330A FUSE

BLVD branch

330A FUSE

SPD

10kA/20kA, 8/20s

Input voltage

85VAC300VAC, rated 220VAC

Rated power

30A/50A

Working temperature

-40~+75

Weight

<2kg

Power factor

0.99

THD

5%

Signal input

Controller

Environment

3 AI(battery temp., ambient temp., ambient humidity)


9 DI(water, smoke, gate, 6 common DI)

Alarm output

8 dry contact

Communication port

RS232, RS485, SNMP

Storage capacity

Up to 1000 historical records

Display mode

LCD

Operating temperature

-40~+45 (+ solar radiation)

Storage temperature

-40~+70

Operating humidity

5%~95%(non-condensing)

Altitude

0~4000m

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Outdoor Power System


TP48200A-HD15A6
Introduction
TP48200A-HD15A6 is an AC/DC outdoor power system that configures 1U
48V/50A rectifier modules to supply rated of 200A output current, with heat
exchanger in power cabin and direct ventilation in battery cabin . The system
has excellent performance such as wide range of AC input voltage, high
power efficiency, surge protection, intelligent temperature and battery
management, and remote management. The TP48200A-HD15A6 is used in
class C environment for various outdoor scenarios.

Features
High protection level: IP55 for power cabin, IP45 for battery cabin
Super temperature performance for rectifiers with range from
-40 to 75
The power module supports hot-swapping, easy to install and maintain
Temperature control system built-in door, easy to maintain, clean and replace
Strong anti-theft design: door embedded, hinge hidden, 3-point lock, door sensor and
supporting padlock
Intelligent battery management prolongs battery lifespan

Support battery anti-reverse function, reducing operating risk


Support remote management, reducing customer operating cost

Application Scenarios
Outdoor wireless site
Outdoor enterprise communication network

Specifications
Dimension

650mm(W)650mm(D)1500mm(H) (excluding base)

Weight

100kg (without rectifier module)

Cooling mode

System

DC
Distribution

Rectifier

Grounding\rooftop\wall against

Cabling mode

At the bottom, inlet/outlet downwards

Maintenance mode

In front

Noise level

Satisfied GR487, noise65dBA@1.5m

Environment

Power cabin: IP55


Battery cabin: IP45

Battery space

16U (Maximum 2*190Ah)

User space

9U

MTBF

200,000 hours

Input mode

Three phase compatible with single phase

Input voltage

380V/220VAC

Input frequency

45~65Hz, rated value: 50Hz/60Hz

Input capacity

163A/3P

SPD

20kA/40kA, 8/20s

Maintenance socket

Universal 220Vac socket (with 16A MCB protection)

AC output

1*16A/1P MCB, 220Vac output

Output voltage

42~58VDC, rated value: 53.5VDC

Maximum capacity

12kW (4*3000W)

Battery branch

2*125A MCB

LLVD branch

2*63A MCB, 2*32A MCB

BLVD branch

2*16A MCB, 1*10A MCB

SPD

10kA/20kA, 8/20s

Input voltage

85VAC300VAC, rated 220VAC

Rated power

3000W(>96%)

Working temperature

-40~+75

Dimensions

105mm(W)281mm(D)40.8mm(H)

Weight

<2kg

Power factor

0.99

THD

5%

Signal input

Controller

Battery cabin: direct ventilation

Installation mode

Protection level

AC
Distribution

Power cabin: Heat exchange 850W

3 AI(battery temp., ambient temp., ambient humidity)


9 DI(water, smoke, gate, 6 common DI)

Alarm output

8 dry contact

Communication port

RS232, RS485, SNMP

Storage capacity

Up to 50000 historical records

Display mode

LCD

Operating temperature

-10~+45 (+ solar radiation)

Storage temperature

-40~+70

Operating humidity

5%~95%(non-condensing)

Altitude

0~4000m

Remark: normal efficiency(>94%, 3000W) rectifier is optional

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

Outdoor Power System


TP48200A-HD15A7
Introduction
TP48200A-HD15A7 is an AC/DC outdoor power system that configures 1U
48V/50A rectifier modules to supply rated of 200A output current, with heat
exchanger in power cabin and direct ventilation in battery cabin . The system
has excellent performance such as wide range of AC input voltage, high
power efficiency, surge protection, intelligent temperature and battery
management, and remote management. The TP48200A-HD15A7 is used in
class B environment for various outdoor scenarios.

Features
High protection level: IP55 for power cabin, IP45 for battery cabin
Super temperature performance for rectifiers with range from
-40 to 75
The power module supports hot-swapping, easy to install and maintain
Temperature control system built-in door, easy to maintain, clean and replace
Strong anti-theft design: door embedded, hinge hidden, 3-point lock, door sensor and
supporting padlock
Intelligent battery management prolongs battery lifespan

Support battery anti-reverse function, reducing operating risk


Support remote management, reducing customer operating cost

Application Scenarios
Outdoor wireless site
Outdoor enterprise communication network

Specifications
Dimension

650mm(W)650mm(D)1500mm(H) (excluding base)

Weight

100kg (without rectifier module)

Cooling mode

System

DC
Distribution

Rectifier

Grounding\rooftop\wall against

Cabling mode

At the bottom, inlet/outlet downwards

Maintenance mode

In front

Noise level

Satisfied GR487, noise65dBA@1.5m

Environment

Power cabin: IP55


Battery cabin: IP45

Battery space

16U (Maximum 2*190Ah)

User space

9U

MTBF

200,000 hours

Input mode

Dual live wire

Input voltage

110V/220VAC

Input frequency

45~65Hz, rated value: 50Hz/60Hz

Input capacity

1125A/2P

SPD

30kA/60kA, 8/20s

Maintenance socket

Universal 110Vac socket (with 10A RCD protection)

AC output

1*16A/2P MCB, 220Vac output

Output voltage

42~58VDC, rated value: 53.5VDC

Maximum capacity

12kW (4*3000W)

Battery branch

2*125A MCB

LLVD branch

1*80A MCB, 6*32A MCB

BLVD branch

1*80A MCB, 2*32A MCB, 1*10A MCB

SPD

10kA/20kA, 8/20s

Input voltage

85VAC300VAC, rated 220VAC

Rated power

3000W(>96%)

Working temperature

-40~+75

Dimensions

105mm(W)281mm(D)40.8mm(H)

Weight

<2kg

Power factor

0.99

THD

5%

Signal input

Controller

Battery cabin: direct ventilation

Installation mode

Protection level

AC
Distribution

Power cabin: Heat exchange 850W

3 AI(battery temp., ambient temp., ambient humidity)


9 DI(water, smoke, gate, 6 common DI)

Alarm output

8 dry contact

Communication port

RS232, RS485, SNMP

Storage capacity

Not less than 1000 historical records

Display mode

LCD

Operating temperature

-10~+45 (+ solar radiation)

Storage temperature

-40~+70

Operating humidity

5%~95%(non-condensing)

Altitude

0~4000m

Remark: normal efficiency(>94%, 3000W) rectifier is optional

Copyright Huawei Technologies Co., Ltd. 2014. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

HUAWEI TECHNOLOGIES CO., LTD.


Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com

You might also like