Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.

33kV MV SWITCHBOARD- HEAD HOUSE AREA (Ref. Drawing No.20110824191132421, Page A


1)
Sl No

33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42,


MV Switchboard.

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

INCOMER
1

1250A VCB

VCB

INCOMER-1

1250A VCB

VCB

INCOMER-2

OUTGOINGS - FEEDER
3

630A VCB

VCB

HEAD HOUSE -1

630A VCB

VCB

HEAD HOUSE -2

630A VCB

VCB

Future ( Spare)

1250A VCB

VCB

BUS TIE

33kV MV SWITCHBOARD- WARE HOUSE AREA (Ref. Drawing No.20110824191132421, Page 1)

Sl No

33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42,


MV Switchboard.

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

INCOMER
1

1250A VCB

VCB

INCOMER-1

1250A VCB

VCB

INCOMER-2

OUTGOINGS - FEEDER
3

630A VCB

VCB

WARE HOUSE -1

630A VCB

VCB

WARE HOUSE -2

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.

630A VCB

VCB

SPARE-1

1250A VCB

VCB

BUS TIE

33kV MV SWITCHBOARD- BERTH AREA (Ref. Drawing No.20110824191132421, Page - 1)

Sl No

33kV AC , 1250A, 3PH, 50Hz, 25KA, 3Sec, IP42,


MV Switchboard.

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

INCOMER
1

1250A VCB

VCB

INCOMER-1

1250A VCB

VCB

INCOMER-2

OUTGOINGS - FEEDER
3

630A VCB

VCB

BERTH AREA -1

630A VCB

VCB

BERTH AREA -1

630A VCB

VCB

BERTH AREA -1

630A VCB

VCB

BERTH AREA -2

630A VCB

VCB

SPARE-1

630A VCB

VCB

SPARE-2

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
9

1250A VCB

VCB

POWER TRANSFORMER (Ref. Drawing No.20110824191132421, Page - 1)

BUS TIE

Sl No Head House Area

QTY.

Type of Feeder TAG NO.

Feeder Details

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

Tx-1

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

Tx-2

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

FUTURE

Ware House Area


4

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

Tx-3

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

Tx-4

Berth Area
6

3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,

ONAN

Tx-5

3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,

ONAN

Tx-6

3200kVA - Indoor transformer dyn11, ONAN, 33kV/11kV,

ONAN

Tx-7

3200kVA - Indoor transformer dyn11, ONAN, 33kV/400V,

ONAN

Tx-8

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.

LV SWITCHBOARD- HEAD HOUSE AREA (Ref. Drawing No.20110824191132421, Page - 2)

Sl No

400V AC , 5000A, 3PH, 4W, 50Hz, 65KA, 1Sec,


Form-4B, Drawout type, IP43, LV Switchboard.

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

INCOMER- (BUS-A)
1

5000A, 4P, ACB, INCOMER from Tx-1

ACB

INCOMER-1

5000A, 4P, ACB, BUS COUPLER

ACB

BUS COUPLER

OUTGOINGS - FEEDER- BUS SECTION :A


3

800A 3P ACB

ACB

MCC-1

2500A 3P ACB

ACB

MCC-2

2500A 3P ACB

ACB

MCC-3

300A 3P MCCB for 200KVAR Capacitor Banks

MCCB

PFC-1

ACB

INCOMER-2

INCOMER- (BUS-B)
7

5000A, 4P, ACB, INCOMER from Tx-2


OUTGOINGS - FEEDER- BUS SECTION :B

300A 3P MCCB

MCCB

OFFICE

300A 3P MCCB

MCCB

AMEMNES

10

200A 3P MCCB

MCCB

HEAD HOUSE
LIGHTS/POWER

11

300A 3P MCCB for 200KVAR Capacitor Banks

MCCB

PFC-2

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
F

LV SWITCHBOARD- WARE HOUSE AREA (Ref. Drawing No. 20110824191132421, Page - 3)

Sl No

400V AC , 2000A, 3PH, 4W, 50Hz, 65KA, 1Sec,


Form-4B, Drawout type, IP43, LV Switchboard.

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

INCOMER- (BUS-A)

2000A, 4P, ACB, INCOMER from Tx-3

ACB

INCOMER-1

2000A, 4P, ACB, BUS COUPLER

ACB

BUS COUPLER

OUTGOINGS - FEEDER- BUS SECTION :A


3

1000A 3P ACB

ACB

MCC-4

400A 3P MCCB

MCCB

WARE HOUSE
LIGHTS/POWER

100A 3P MCCB

MCCB

GATE HOUSE

MCCB

PFC-3

ACB

INCOMER-2

MCCB

REGISTRATION
BLDG

3P MCCB for Capacitor Banks


INCOMER- (BUS-B)

2000A, 4P, ACB, INCOMER from Tx-4

OUTGOINGS - FEEDER- BUS SECTION :B


8

200A 3P MCCB

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
9

3P MCCB

MCCB

SPARE

10

3P MCCB

MCCB

SPACE

11

3P MCCB for Capacitor Banks

MCCB

PFC - 4

11 KV MV SWITCHBOARD- BERTH AREA-1


(Ref. Drawing No. 20110824191132421, Page-4)

Sl No

11kV AC , 630A, 3PH, 50Hz, 16KA, 1Sec, IP43,


Standalone Cabinet.

QTY.of Panel

Type of Feeder TAG NO.

Feeder Details

11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from


Tx- 5.

VCB

SHIP UNLOADER-1

11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from


Tx- 6.

VCB

SHIP UNLOADER-2

11kV Switchgear; 11kV; 630A; 16kA/1s; Standalone Panel from


Tx- 7.

VCB

SHIP UNLOADER-3

LV SWITCHBOARD- BERTH AREA- 2 (Ref. Drawing No. 20110824191132421, Page - 5)

Sl No

400V AC , 1000A, 3PH, 4W, 50Hz, 65KA, 1Sec,


Form-4B, Drawout type, IP43, LV Switchboard.
INCOMER

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.

1000A, 4P, ACB, INCOMER from Tx-8

ACB

INCOMER

MCCB

PFC - 5

OUTGOINGS - FEEDER
2

Feeder-1

Feeder-2

Feeder-3

3P MCCB for Capacitor Banks

MCC - 1 (Ref. Drawing No. 20110823094801671)

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
400V AC , 800A, 3PH, 4W, 50Hz, 50KA, 1Sec,
Sl No Form-4B, Drawout type, IP43, Intelligent MCC
with modbus TCP protocol .

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

ACB

INCOMER

INCOMER
1

800A, 3P, ACB, INCOMER


OUTGOINGS- Intelligent Starter feeder

7.5 KW

DOL Starter

110-07MS

MAGNET
SEPARATOR

7.5 KW

DOL Starter

120-07MS

MAGNET
SEPARATOR

25.0 KW

DOL Starter

110-19C

INTAKE CONVEYOR

25.0 KW

DOL Starter

120-19C

INTAKE CONVEYOR

40.0 KW

Soft starter

140-03C

TRUCK INTAKE
CONVEYOR

40.0 KW

Soft starter

210-01B

OUT TAKE BELT


CONVEYOR

40.0 KW

Soft starter

220-01B

OUT TAKE BELT


CONVEYOR

40.0 KW

Soft starter

230-01B

OUT TAKE BELT


CONVEYOR

10

40.0 KW

Soft starter

240-01B

OUT TAKE BELT


CONVEYOR

11

7.5 KW

DOL Starter

23A

TRUCK/BAGGING
DOZ CONVEYOR

12

2.0 KW

DOL Starter

23B

TRUCK LOADING
SPOUTS/BELLOW

13

3.0 KW

DOL Starter

DF36

LOADING DUST
FILTER

14

25.0 KW

DOL Starter

25A

AIR COMPRESSOR

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
15

15.0 KW

MCC - 2 (Ref. Drawing No. 20110823094801671)

400V AC , 2500A, 3PH, 4W, 50Hz, 50KA, 1Sec,


Sl No Form-4B, Drawout type, IP43, Intelligent MCC
with modbus TCP protocol .

DOL Starter

25

AIR COMPRESSOR

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

ACB

INCOMER

INCOMER
1

2500A, 3P, ACB, INCOMER


OUTGOINGS- Intelligent Starter feeder

125 KW

Soft starter

210-05C

SILO OUT TAKE


CONVEYOR

125 KW

Soft starter

220-05C

SILO OUT TAKE


CONVEYOR

300 KW

Soft starter

110-05B

LONG HAUL BELT

300 KW

Soft starter

120-05B

LONG HAUL BELT

300 KW

Soft starter

110-17E

RECEIVE BUCKET
ELEVATOR

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
7

300 KW

Soft starter

120-17E

RECEIVE BUCKET
ELEVATOR

125 KW

Soft starter

110-21C

DISTRIBUTION
CHAIN CONVEYOR

125 KW

Soft starter

120-21C

DISTRIBUTION
CHAIN CONVEYOR

MCC - 3 (Ref. Drawing No. 20110823094801671)

400V AC , 2500A, 3PH, 4W, 50Hz, 50KA, 1Sec,


Sl No Form-4B, Drawout type, IP43, Intelligent MCC
with modbus TCP protocol .

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

ACB

INCOMER

INCOMER
1

2500A, 3P, ACB, INCOMER


OUTGOINGS- Intelligent Starter feeder

100 KW

Soft starter

110-23C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

120-23C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

130-23C

SILO INTAKE
CONVEYOR

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
5

100 KW

Soft starter

140-23C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

110-25C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

120-25C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

130-25C

SILO INTAKE
CONVEYOR

100 KW

Soft starter

140-25C

SILO INTAKE
CONVEYOR

10

200 KW

Soft starter

210-17E

OUT TAKE BUCKET


ELEVATOR

11

200 KW

Soft starter

220-07E

OUT TAKE BUCKET


ELEVATOR

12

125 KW

Soft starter

210-09C

OUT TAKE CHAIN


CONVEYOR

13

125 KW

Soft starter

220-09C

OUT TAKE CHAIN


CONVEYOR

MCC - 4 (Ref. Drawing No. 20110823094801671)

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
400V AC , 1000A, 3PH, 4W, 50Hz, 50KA, 1Sec,
Sl No Form-4B, Drawout type, IP43, Intelligent MCC
with modbus TCP protocol .

QTY.of Feeder Type of Feeder TAG NO.

Feeder Details

ACB

INCOMER

INCOMER
1

1000A, 3P, ACB, INCOMER


OUTGOINGS- Intelligent Starter feeder

0.5 KW

DOL Starter

11

PELLET DISPENSER

3.0 KW

DOL Starter

DF1

DUST FILTER LONG


CONVEYOR

3.0 KW

DOL Starter

DF2

DUST FILTER LONG


CONVEYOR

3.0 KW

DOL Starter

DF3

DUST FILTER
RECEIVE B.E

3.0 KW

DOL Starter

DF4--DF7

DUST FILTER
INTAKE CONVEYOR

3.0 KW

DOL Starter

DF8--DF14

DUST FILTER
CONVEYOR 210-01B

3.0 KW

DOL Starter

DF15--DF21

DUST FILTER
CONVEYOR 220-01B

3.0 KW

DOL Starter

DF22--DF28

DUST FILTER
CONVEYOR 230-01B

10

3.0 KW

DOL Starter

DF29--DF35

DUST FILTER
CONVEYOR 240-01B

11

30.0 KW

Soft starter

15E

FAN

12

3.0 KW

DOL Starter

15D

AIRLOCK

13

20.0 KW

DOL Starter

15N

FAN

14

3.0 KW

DOL Starter

15E

AIRLOCK

15

3.0 KW

DOL Starter

DF4B, DF5B, DF6B, DF7B.

16

1.0 KW

DOL Starter

24A

BAG CLOSE
CONVEYOR

Q0111/695: Enquiry of Electrical items for Aqaba New South Port - Grain Terminal - Jordan.
17

1.0 KW

110VDC SYSTEM/MOTORS & DRIVES

Control voltage shall be 110 V DC;During a


power failure, the 110V DC power supply of the
MDS shall be operational for at least six hours

Motors & drives

DOL Starter

24B

SEWINE HEAD

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

We have considered the Bus tie as


mentioned in the attached
specifications, however same is
not shown in drawing (Ref.
Drawing No.20110824191132421,
Page - 1). Please confirm whether
the same is correct.

please to follow the rating indicated


on the dwg. No.2011082419113242

ABB reply/queries dtd 22-Sep-2011


We have considered the Bus tie &
spare feeder as mentioned in the
above attached specifications,
however same is not shown in
drawing(Ref. Drawing
No.20110824191132421, Page 1). Please confirm whether the
same is correct.

We have considered the Bus tie &


spare feeder as mentioned in the
above attached specifications,
however same is not shown in
drawing(Ref. Drawing
No.20110824191132421, Page 1). Please confirm whether the
same is correct.

Astraco Reply

same as above

same as above

spare feeder as mentioned in the


above attached specifications,
however same is not shown in
drawing(Ref. Drawing
No.20110824191132421,
Page ABB reply/queries dtd 22-Sep-2011
1). Please confirm whether the
same is correct.

Rating of future Transformer is not


shown in drawing, we have
considered the rating as 3200kVA .
Please confirm whether the same
is correct.

We have considered the ratng of


Transformers for Ware house &
Berth area as 3200kVA as shown in
the attached drawing(Ref. Drawing
no.20110824191132421, Page 1). Please confirm whether the
same is correct.

Astraco Reply

confirmed

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

PFC-1(200kvar) has been indicated


in drawing for the Bus-A(Ref.
Drawing No.20110824191132421,
Page - 2), but for the Bus B
capacitor bank is not shown in the
drawing. Please confirm whether
PFC-2 is required or not for Bus B.

PFC-2 is required

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

The rating of incomer feeder is


2000A as shown in drawing where
as the rating of incoming
Transformer is 3200kVA. Please
confirm whether the same is
correct.

confirmed

Please confirm rating of Capacitor


bank/feeder.
The rating of incomer feeder is
2000A as shown in drawing where
as the rating of incoming
Transformer is 3200kVA. Please
confirm whether the same is
correct.

ABB reply/queries dtd 22-Sep-2011


Please confirm rating of spare
feeder.
Please confirm rating of spare
space of future feeder.
Capacitor Bank(PFC-3) has been
indicated in drawing for the BusA(Ref. Drawing
No.20110824191132421, Page 3), but for the Bus B capacitor
bank is not shown in the drawing.
Please confirm with rating
whether PFC-4 is required or not
for Bus B.

Astraco Reply
200A
200A

consider cap. Bank for each


bus(headhouse , ware house, berth
area )

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

The rating of incomer feeder is


1000A as shown in drawing where
as the rating of incoming
Transformer is 3200kVA. Please
confirm whether the same is
correct.

CONFIRMED , VALUE IS CORRECT

100A for each feeder


The rating of the outgoing feeder
are not shown in the drawing,
Please provide the same

Please confirm rating of Capacitor


bank/feeder if required..

We have considered the rating( in


KW )and quantity of feeder as per
the attached drawing(Ref. Drawing
No. 20110823094801671),
however starter type has not been
indicated in the drawing. Please
confirm/approve the Rating,
Starter type & no. of feeder
indicated in this BOQ to enable us
prepare the offer.

DOL type and the rating not


confirmed from client yet ,

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

We have considered the rating( in


KW )and quantity of feeder as per
the attached drawing(Ref. Drawing
No. 20110823094801671),
however starter type has not been
indicated in the drawing. Please
confirm/approve the Rating,
Starter type & no. of feeder
indicated in this BOQ to enable us
prepare the offer.

same as above

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

We have considered the rating( in


KW )and quantity of feeder as per
the attached drawing(Ref. Drawing
No. 20110823094801671),
however starter type has not been
indicated in the drawing. Please
confirm/approve the Rating,
Starter type & no. of feeder
indicated in this BOQ to enable us
prepare the offer.

same as above

ABB reply/queries dtd 22-Sep-2011

Astraco Reply

We have considered the rating( in


KW )and quantity of feeder as per
the attached drawing(Ref. Drawing
No. 20110823094801671),
however starter type has not been
indicated in the drawing. Please
confirm/approve the Rating,
Starter type & no. of feeder
indicated in this BOQ to enable us
prepare the offer.

same as abopv

ABB reply/queries dtd 22-Sep-2011

We have considered the CDP as


part of MCC-4 in this BOQ. Please
confirm whether the same is
correct

Astraco Reply

ABB
reply/queries
dtdCDP
22-Sep-2011
We have
considered the
as
part of MCC-4 in this BOQ. Please
confirm whether the same is
correct

Astraco Reply

DC UPS: Please confirm whether


the supply of DC UPS is in the
scope of this package. If required,
please provide us the rating &
other details of the DC UPS &
Batteries

DC UPS is required with 110V DC ,


6 hr , 750A

Motors & Drive: Please confirm


whether the supply of Motors &
Drive are in the scope of this
package. If required, please
provide us the rating, Qty & other
details of the same.

included in the scope , but no data


from client

S.NO. RATING

QTY

NUMBERING AS
PER CUBICLES

1. Switchgear Tag No: A


1250A, ACB
380V,50HZ,50KA

SIEMENS MAKE 380V SWITCHGEAR


1
3
1
1

100A

100A
100A
6.4KW,100A
125A
100A

20KW,100A

1
1
1
1
1
1
1
1
1
1

1
1
1
1

01A
01B
01C
1A
1B
1C
1D
2A
2B
2C
2D
2E
3A
3B
4A
4B
4C
4D
4E

2. Switchgear Tag No: A


SIEMENS MAKE 380V SWITCHGEAR
404KW,1250A
1250A, ACB
380V,50HZ,50KA
100A

10KW,100A
100A
10KW,100A
100A
100A
50A

1
1
1

1
1
1
1
1
1
1
1
1
1
1

6
3
1A
1B
1C
2A
2B
2C
2D
2E
3A
4A
4B
4C

125A
125A

1
1
1
1
1
1

4D
4E
5A
5B
5C
5D
5E

3. Switchgear Tag N
3150A, ACB
380V,50HZ,50KA
3150A, ACB
100A
15KW,75A
15KW,75A
110A
229A
100A
15KW,75A
2KW,75A
0.25KW,75A
3KW,75A
110A
250A
100A
32KW,100A
400A
400A
4KW,75A
2000A,ACB

SIEMENS MAKE 380V SWITCHGEAR


2
1
1
2
2
1
1
3
2
1
2
1
1
3
2
1
1
1
1
2

4. Switchgear Tag No
2000A, ACB
2000A, ACB
2000A, ACB
380V,50HZ,50KA
40A
100A

5KW
8KW

SIEMENS MAKE 380V SWITCHGEAR


1
7
1
8
1
9
1
1
1
1
1
5
1

1A
1B
1C
1D
1E
2A-2E
3A

50A
40A
60KW
100KW
6KW
25KW
175A
175A
11KW,<75A
80-125A
1250A,ACB
110A-170A
6KW
5KW
175A
175A
8KW

81-125A
10KW

40-53A

1
1
1
1
1
1
1
1
1
1
2
1
1
2
3
1
1
1
1
2
1
1
1
1
1
1
1
1
1

3B
3C
3D
3E
4A
4B
4C
4D
4E
5A
5B &14D
5C
5D
6 & 10
11A-11C
11D
12A
12B
12C
12D-12E
13A
13B
13C
13D
13E
14A
14B
14C
14E

7. Switchgear Tag No
1250A, ACB
380V,50HZ,50KA
4KW,100A
4KW,100A
20KW,100A
33KW,100A
10KW,100A
2KW,100A
225A
400A
400A,5KVA
400A
75A

SIEMENS MAKE 380V SWITCHGEAR


1
2
2
1
1
2
2
3
1
1
1
2

8. Switchgear
SIEMENS MAKE 380V SWITCHGEAR
800A, ACB
2
800A, ACB
1
800A,380V,50HZ,50KA,3-PH,4N,
50A,3P,
1
30A,3P
1
80A,3P
1
100A,3P
1
40A,SP
1

9. Switchgear
SIEMENS MAKE 380V SWITCHGEAR
800A, ACB
1
800A,380V,50HZ,50KA,3-PH,4N,
160A,3P
1
630A,3P
1
60A,3P
1
40A,SP
1
80A,3P
2
30A,3P
1
50A,3P,
1
50A,SP
1
30A,SP
1

10. Switchgear Tag N


SIEMENS MAKE 380V SWITCHGEAR
2000A, ACB
2
2000A, ACB
1
380V,3-ph,50HZ,50KA for 1sec
225A,40KW
1
100A
3
50KW,100A
2
75A
10
110A
6
100A
6
100KW,225A
2
15KW,100A
2
0.5KW,100A
2
1250A,ACB
2
34KW,225A
1

11. Switchgear Tag


1250A, ACB

SIEMENS MAKE 380V SWITCHGEAR


2

1250A, ACB
380V,3-ph,50HZ,50KA for 1sec
75A
30KW,110A
150W,100A
10KW,100A
15KW,100A
225A
6KW,100A
4KW,100A
30KW,100A
5KW,100A
400A
100A
100A

1
3
2
3
2
4
3
2
2
1
1
1
1
1

14. Switchgear Tag N


SIEMENS MAKE 380V SWITCHGEAR
1250A, ACB
2
1250A, ACB
1
380V,3-ph,50HZ,50KA for 1sec
75A
7
100A
3
100A
3
7.5KW,75A
1

15. Switchgear Tag N


SIEMENS MAKE 380V SWITCHGEAR
REFER DRAWING FOR OPTION -1
FOR OPTION -2
2000A, ACB
2000A, ACB
380V,3-ph,50HZ,50KA for 1sec
225A,40KW
100A
50KW,100A
75A
110A

2
1
1
3
2
10
6

TYPE OF FEEDER

TYPE

FEEDER DETAILS

1. Switchgear Tag No: A1-SP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 1 Rev H )

V SWITCHGEAR
INCOMER
BUSBAR
METERING
STANDBY SUPPLY FOR HVAC
BLANK
SAFENIFE UPS2 INPUT
SPARE
GUTOR UPS-1
REHEATING INVERTER
WELDING RECEPTABLE
CHARGER NO.-1
SPARE
SPARE
METERING
BLANK
BLANK
48V DC BATTERY CHARGER-1
SPARE
NORMAL LIGHTING
SPARE

LOCATION : CONT
TYPE-3

DRAWOUT TYPE ACB

TYPE-3

DRAWOUT TYPE MCCB

TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

TYPE MCCB
TYPE MCCB
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

2. Switchgear Tag No: A1-SSP-D30( Ref Drg No: 6400-A1-400-70-15 Sh 2 Rev H )

V SWITCHGEAR
AIR CONDITIONING CONTROL ROOM TYPE-3
METERING & PROTECTION
INCOMER
TYPE-3
BUSBAR
SPARE
SAFENIFE UPS INPUT
TYPE-3
SAFENIFE UPS1 INPUT
TYPE-3
EMERGENCY LIGHTING
TYPE-3
SPARE
TYPE-3
BATTERY CHARGER
TYPE-3
SPARE
TYPE-3
SPARE
TYPE-3
METERING
TYPE-3
SPARE
TYPE-3
48V DC BATTERY CHARGER-2
TYPE-3
TRANSFORMER
TYPE-3

LOCATION : CONT
DRAWOUT TYPE MCCB
DRAWOUT TYPE ACB
EMPTY
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

DRAWOUT TYPE MCCB


DRAWOUT TYPE MCCB
DRAWOUT TYPE MCCB

SPARE
SPARE
REHEATING STATIC CHARGER OVER
REHEATING INVERTER NO.-2
SPARE
GUTOR BYPASS
GUTOR UPS-2

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB

TYPE MCCB
TYPE MCCB

3. Switchgear Tag No: A1-SG-D3( Ref Drg No: 6400-A1-400-70-37 Rev K )

V SWITCHGEAR
INCOMER
BUSBAR
BUSCOUPLER
SPARE
CRUDE OIL PUMP
AIR COOLED HEAT EXCHANGER
SPARE
SPARE
SPARE
RESIDUAL PUMP
OIL RECIRCULATING PUMP
INJECTION PUMP
DIESEL FEED PUMP
SPARE
SPARE
WELDING RECEPTABLE
NORMAL LIGHTING
SPARE
AIR CONDITIONING
CRUDE HEATER FAN

LOCATION : SUBS
TYPE-3

DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-4

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

ACB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
ACB

4. Switchgear Tag No: A1-SP-SSP-D3( Ref Drg No: 6400-A1-400-70-44-001 )

V SWITCHGEAR
INCOMER
BUS TIE
INCOMER
BUSBAR
SPARE
FIRE STATION BATTERY CHARGER
SPARE
CRUDE TRANSFER PUMP
SPARE
REHEAT MOTORS & CELLS
BATTERY CHARGER 48VDC

LOCATION : SUBS
TYPE-3
TYPE-3
TYPE-3

DRAWOUT TYPE ACB


DRAWOUT TYPE ACB
DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT

TYPE-3
TYPE-3

TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
CONTACTOR

TYPE MCCB
TYPE MCCB

SPARE
SPARE
FIRE STATION
LABORATORY
125V DC BATTERY CHARGER
SPARE
GATE HOUSE
SPARE
SPARE
SPARE
STRIPPER REBOILING PUMP
SPARE
SPARE
CONTROL ROOM
SPARE
SPARE
125V DC BATTERY CHARGER
SUBSTN. AUXILLARIES
MOV PANEL
SPARE
BATTERY CHARGER 48VDC
FIRE STATION BATTERY CHARGER
FIRE STATION TRANSFORMER
SPARE
SPARE
EMERGENCY LIGHTING
LAB. TRAFO
OIL DEHYDRATION PROJECT
SPARE

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
EMPTY
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB

TYPE MCCB
TYPE MCCB
TYPE MCCB
TYPE CONTACTOR
TYPE CONTACTOR
TYPE ACB
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

CONTACTOR
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
CONTACTOR

TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
CONTACTOR

7. Switchgear Tag No: C5-SG-D1( Ref Drg No: 6400-A1-SS11-70-4 Rev H )

V SWITCHGEAR
INCOMER
BUSBAR
125V DC BATTERY CHARGER
48V DC BATTERY CHARGER
SUBSTATION AUXILLARIES
AIR CONDITIONING SUBSTATION
REHEATING SWITCHGEAR
ONLOAD TAP CHANGER OUTGOING
SPARE
FIRE ALARM PANEL
SPARE
SPARE

LOCATION : SUBS
TYPE-3

DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

8. Switchgear Tag No: AP-LC-D ( Ref Drg No: 406-4001. )

V SWITCHGEAR
INCOMER
BUSCOUPLER
BUSBAR

LOCATION : SUBS
TYPE-3
TYPE-3

DRAWOUT TYPE ACB


DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB

9. Switchgear Tag No: AP-LCE-D ( Ref Drg No: 406-4001. )

V SWITCHGEAR
INCOMER
BUSBAR

LOCATION : SUBS
TYPE-3

DRAWOUT TYPE ACB

10. Switchgear Tag No: A1-SG-D1( Ref Drg No: 6400-A1-400-70-42 Rev J )

V SWITCHGEAR
INCOMER
BUSCOUPLER
BUSBAR
NORMAL LIGHTING
WELDING RECEPTABLE
PUMPING STN. EQPT.
SPARE
SPARE
SPARE
DESALINATION PLANT
SEA WATER CHLORINATION UNIT
REHEATING RIGHT ANGLE FAN
AIR CONDITIONING SUBSTATION

V SWITCHGEAR
INCOMER

LOCATION : SUBS
TYPE-3
TYPE-3

DRAWOUT TYPE ACB


DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
ACB
MCCB

11. Switchgear Tag No: A1-SP-SSP-D1( Ref Drg No: 6400-A1-400-70-48 )

LOCATION : SUBS
TYPE-3

DRAWOUT TYPE ACB

BUSCOUPLER
BUSBAR
SPARE
FIRE WATER JOKEY PUMP
REHEATING CELLS
SEA WATER PREFILTERATION
SUBSTATION AUXILLARIES
SPARE
48V DC BATTERY CHARGER
125V DC BATTERY CHARGER
EMERGENCY LIGHTING
SUBSTATION AUXILLARIES
SPARE
MOV PANEL
SPARE

TYPE-3

DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB

14. Switchgear Tag No: A4-SG-D1 ( Ref Drg No: 6400-A1-444-70-6 Rev F )

V SWITCHGEAR
INCOMER
BUSCOUPLER
BUSBAR
SPARE
SPARE
WELDING RECEPTABLE
LUBE OIL PUMP

LOCATION : SUBS
TYPE-3
TYPE-3

DRAWOUT TYPE ACB


DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB

15. Switchgear Tag No: A1-SG-D4 ( Ref Drg No: 6400-A1-400-70-38 Rev J )

V SWITCHGEAR

INCOMER
BUSCOUPLER
BUSBAR
NORMAL LIGHTING
WELDING RECEPTABLE
PUMPING STN. EQPT.
SPARE
SPARE

LOCATION : SUBS

TYPE-3
TYPE-3

DRAWOUT TYPE ACB


DRAWOUT TYPE ACB

TYPE-3
TYPE-3
TYPE-3
TYPE-3
TYPE-3

DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT
DRAWOUT

TYPE
TYPE
TYPE
TYPE
TYPE

MCCB
MCCB
MCCB
MCCB
MCCB

ADDITIONAL INFO.

h 1 Rev H )
LOCATION : CONTROL ROOM

Sh 2 Rev H )
LOCATION : CONTROL ROOM

7 Rev K )
LOCATION : SUBSTATION 02
AUTOMATIC TRANSFER SCHEME WITH BUS COUPLER

INCOMERS FOR NEXT LV BOARD

0-44-001 )
LOCATION : SUBSTATION 02
TWO FEEDERS MERGED
AUTOMATIC TRANSFER WITH INCOMER -9 & ANOTHER FEEDER

4 Rev H )
LOCATION : SUBSTATION 11

)
LOCATION : SUBSTATION 14
INCOMERS FROM 630KVA, 22KV/380V
INTERLOCKED WITH INCOMERS FROM TRAFO's

)
LOCATION : SUBSTATION 14
INCOMING FROM GENERATOR VIA AUTO TRANSFER SWITCH

2 Rev J )
LOCATION : SUBSTATION 15
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER

AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER

-70-48 )
LOCATION : SUBSTATION 15
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER

6 Rev F )
LOCATION : SUBSTATION 111
AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER

38 Rev J )
LOCATION : SUBSTATION 111

AUTOMATIC TRANSFER WITH INCOMER BUSCOUPLER

You might also like