Document Number: EDS 01-0045

Date: 13/05/2013

ENGINEERING DESIGN STANDARD

EDS 01-0045

OVERHEAD LINE RATINGS


Network(s):

EPN, LPN, SPN

Summary:

This standard details the Electricity Networks Association Engineering (ENA)


Recommendation P27 Current Rating Guide for UK Power Networks Overhead
Lines.

Originator:

Florence Nanyonjo

Date:

13/05/2013

Approved By:

Steve Mockford

Approved Date:

12/06/2013

Review Date:

30/04/2016

This document forms part of the Companys Integrated Business System and its requirements are mandatory throughout UK
Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset
Management. If you have any queries about this document please contact the originator of the current issue.

Document History
(The document history notes below are intended as a guide only and may not cover all of the changes. If you wish to make use
of this document it should be read in full.)

Version

Date

Details

Originator

1.0

29/12/2010

Original. NBC_11_0018.

Martin Payne

1.1

02/08/2011

Reclassified from EI to EDS

Chris Anderson

1.2

23/07/2012

Document reviewed for publishing on G81


website

Lee Strachan

2.0

13/05/2013

Appendix A amended to include ratings for


conductor sizes and types used on the LV
network and a section of all conductor post
fault ratings

Florence Nanyonjo

THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE

Version: 2.0

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Contents
1

Introduction ................................................................................................................3

Scope ..........................................................................................................................3

Methodology of Conductor Ratings .........................................................................3

Circuit Identification ..................................................................................................3

Ratings ........................................................................................................................4

Applying Appropriate Levels of Exceedance ..........................................................4

Calculating of Conductor Ratings ............................................................................4

Appendix A Pre-fault and Post-fault Conductor Current Ratings at 500c Operating


Temperature ...............................................................................................................5
Table A1- Aluminium Conductor Steel Reinforced (ACSR), All Aluminium Alloy
Conductor (AAAC) and Hard Drawn Aluminium (HDAL) ........................................5
Table A2- Hard drawn (HD) Copper and Cadmium (CAD) Copper ....................................7
Table A3- Covered Core Conductor (CCC) or BLX and Aerial Bundled Conductor
(ABC) .........................................................................................................................10

UK Power Networks 2013 All rights reserved

2 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Introduction

This standard details the Electricity Networks Association Engineering Recommendation


P27 Current Rating Guide for UK Power Networks Overhead Lines (P27).

Scope

This standard specifies the use of the cable rating tool ORAT 4 (developed by EA
Technology as part of the Overhead Line Strategic Technology Project), which specifies the
current ratings that UK Power Networks overhead line network should be designed and
operated to.

Methodology of Conductor Ratings

The ratings contained in P27 are based on statistical studies by CERL. These studies
provided data on the likelihood of a conductor exceeding its maximum operating temperature
for a given continuous current in specified weather conditions.
The aggregate period of time during which the conductor exceeds its maximum operating
temperature is called the 'exceedance'. It is usually expressed as the percentage of the total
time for which the current was maintained.
P27 makes no distinction between pre-fault and post-fault ratings and allows 0.001%
excursion time for single circuits and 3% for double circuits.
Under post-fault conditions the duration of the excursion is not set out as in P27. Under
these conditions and dependant on the network configurations, the percentage exceedance
can be altered. Table 1 gives guidance on this.
All ratings are appropriate to their maximum operating temperature and the season (winter,
spring/autumn, summer), for which an ambient temperature is specified.

Circuit Identification

Under P27 there is the need to identify the type of circuit you are operating. These types of
circuit are identified as:

Single Circuit. Single circuit radial systems. E.g. LV and 11kV spur.

Secondary Distribution. These refer to ring-type systems with a number of tapping off
points, such as 11kV main lines.

Multi-circuit Primary. These refer to circuits which would be called upon to supply
maximum load only in the event of the outage of another circuit, the category therefore
includes 132kV and 33kV duplicate transformer feeders, together with some untapped
11kV circuits providing a firm supply to end loads.

UK Power Networks 2013 All rights reserved

3 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Ratings

Two different ratings criteria will be applied to an overhead line:

Pre-fault Rating. This is the maximum continuous rating appropriate to the season
which may be applied without time limitation.

Post-fault Rating. This is the maximum continuous rating appropriate to the season
which may be applied in a fault situation until pre-fault requirements can be restored.
Normally this would be for a period well within 24 hours.

Applying Appropriate Levels of Exceedance

The table below gives guidance on the exceedance levels that should be applied to the
different types of circuit configurations. It is split into two categories:

Pre-fault. Normal operating conditions that apply to the methodology of P27.

Post-fault. Due to the nature of the circuit configuration and the duration of the running
arrangement the exceedance levels have been altered from those set out in P27.

Type of Circuit
Single Circuit
Secondary Distribution
Multi-circuit Primary

Load Shape

Pre-fault Exceedance
Value
Rating Not Dependant 0.001%
on Load Shape
0.001%
General Distribution
3%
Intensive Industrial or 3% for loads at
City Centre
0.96 x Rating
Table 1 Levels of Exceedance

Post-fault
Exceedance Value
0.001%
3%
10%
10%

Calculating of Conductor Ratings

The most commonly used conductor ratings have been included in Appendix A of this
document.
If additional ratings are required, these will be calculated by the UK Power Networks Circuit
Standards Team within Asset Management, using the EA Technology OHRAT Calculation of
Distribution Ratings for Overhead Conductors software.

UK Power Networks 2013 All rights reserved

4 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Appendix A Pre-fault and Post-fault Conductor Current Ratings at 500c Operating Temperature
Table A1- Aluminium Conductor Steel Reinforced (ACSR), All Aluminium Alloy Conductor (AAAC) and Hard Drawn Aluminium (HDAL)
PRE- FAULT RATING
Conductor

Size and Type

Gopher

Exceedance
Level

POST- FAULT RATING

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

25mm2 ACSR

100

116

Rabbit

50mm ACSR

158

Horse

70mm2 ACSR

Dog

100mm ASCR

Wolf

150mm ACSR

Exceedance
Level

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

125

100

116

125

184

198

158

184

198

206

238

258

206

238

258

252

289

310

252

289

310

0.001%

346

401

431

3%

392

454

488

3%

392

454

488

10%

415

481

517

0.001%

382

442

476

3%

432

501

539

3%

432

501

539

10%

458

531

571

0.001%

407

472

507

3%

416

534

575

3%

416

534

575

10%

489

566

609

0.001%

Lynx

Jaguar

0.001%

175mm ACSR

200mm ASCR

UK Power Networks 2013 All rights reserved

5 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

PRE- FAULT RATING


Conductor

Zebra

Hazel

Size and Type

POST- FAULT RATING

Exceedance
Level

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

Exceedance
Level

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

0.001%

658

760

817

3%

745

861

925

3%

745

861

925

10%

790

913

981

165

191

206

165

191

206

259

301

324

400mm ACSR

50mm AAAC
0.001%

Oak

100mm AAAC

Ash

150mm AAAC

Poplar

Upas

Ant

0.001%
259

301

324

0.001%

343

398

428

3%

389

450

485

3%

389

450

485

10%

412

477

514

0.001%

413

479

515

3%

468

542

584

3%

468

542

584

10%

497

575

619

0.001%

546

632

679

3%

618

715

769

3%

618

715

769

10%

655

759

816

163

189

204

163

189

204

258

299

322

200mm AAAC

300mm AAAC

50mm2 HDAL
0.001%

Wasp

100mm2 HDAL

UK Power Networks 2013 All rights reserved

0.001%
258

299

322

6 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Table A2- Hard drawn (HD) Copper and Cadmium (CAD) Copper
PRE- FAULT RATING
Conductor

Size and Type

0.025 Copper

0.025in HDC

0.05 Copper

0.05in HDC

0.1 Copper

0.1in HDC

0.15 Copper

0.15in HDC

0.2 Copper

Exceedance
Level

POST- FAULT RATING

Summer
Rating (A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

99

114

123

155

180

194

237

275

296

0.001%

309

358

385

3%

350

405

0.001%

375

3%

0.001%

Exceedance
Level

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

99

114

123

155

180

194

237

275

296

3%

350

405

437

437

10%

379

440

474

435

465

3%

425

490

530

425

490

530

10%

437

507

545

99

115

124

99

115

124

126

147

158

126

147

158

155

180

194

155

180

194

0.001%

0.2in HDC

16 Metric
Copper

2
16mm HDC

25 Metric
Copper

2
25mm HDC

32 Metric
Copper

2
32mm HDC

0.001%

UK Power Networks 2013 All rights reserved

0.001%

7 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

PRE- FAULT RATING


Conductor

Size and Type

16 Metric
Copper

Summer
Rating (A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

16mm2 HDC

99

115

124

99

115

124

25 Metric
Copper

25mm2 HDC

126

147

158

126

147

158

32 Metric
Copper

32mm2 HDC

155

180

194

155

180

194

35 Metric
Copper

35mm2 HDC

156

181

195

156

181

195

70 Metric
Copper

2
70mm HDC

245

285

307

245

285

307

100 Metric
Copper

0.001%

316

367

395

3%

358

415

447

100mm2 HDC
3%

358

415

447

10%

379

440

474

0.001%

364

422

454

3%

412

478

515

3%

412

478

515

10%

437

507

545

0.001%

78

90

97

0.001%

78

90

97

125 Metric
Copper

125mm HDC

0.17 CAD
Copper

0.17in CADC

Exceedance
Level

POST- FAULT RATING

0.001%

Exceedance
Level

0.001%

UK Power Networks 2013 All rights reserved

8 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

PRE- FAULT RATING


Conductor

Size and Type

0.025 CAD
Copper

Exceedance
Level

POST- FAULT RATING

Summer
Rating (A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

0.025in CADC

96

111

0.035 CAD
Copper

0.035in CADC

121

0.04 CAD
Copper

0.04in CADC

131

Exceedance
Level

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

120

96

111

120

141

152

121

141

152

152

164

131

152

164

0.001%

0.001%

0.05 CAD
Copper

0.05in CADC

150

174

188

150

174

188

0.075 CAD
Copper

0.075in CADC

197

229

247

197

229

247

0.1 CAD
Copper

0.1in CADC

237

275

296

237

275

296

0.15 CAD
Copper

0.001%

312

362

389

3%

353

410

441

0.15in CADC
3%

353

410

441

10%

375

434

468

0.175 CAD
Copper

0.001%

347

402

433

3%

393

456

490

0.175in CADC
3%

393

456

490

10%

417

483

520

UK Power Networks 2013 All rights reserved

9 of 10

OVERHEAD LINE RATINGS

Document Number: EDS 01-0045


Version: 2.0
Date: 13/05/2013

Table A3- Covered Core Conductor (CCC) or BLX and Aerial Bundled Conductor (ABC)
PRE- FAULT RATING
Conductor

Size and Type

50 BLX

50mm CCC

120 BLX

120mm CCC

185 BLX

185mm CCC

Exceedance
Level

POST- FAULT RATING

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter
Rating (A)

148

172

185

264

306

329

0.001%

346

401

431

3%

392

454

489

105

115

124

143

157

163

Exceedance
Level

0.001%

35 ABC

35mm2 ABC

50 ABC

50mm2 ABC

Summer Rating
(A)

Spring/Autumn
Rating (A)

Winter Rating
(A)

148

172

185

264

306

329

3%

392

454

489

10%

416

481

518

105

115

124

143

157

163

0.001%

0.001%

0.001%

95 ABC

95mm2 ABC

228

250

260

228

250

260

120 ABC

120mm2 ABC

277

304

327

277

304

327

UK Power Networks 2013 All rights reserved

10 of 10