You are on page 1of 2

How should I connect the T60 CT terminals to the secondary circuits of

the main CTs?


Normally, the T60 relay requires the main CT to be wye-connected. When the
relay is connected as recommended, the T60 Percent Differential algorithm, performs
magnitude and phase shift compensations, and under normal conditions displays zero
differential current.
In some cases where the T60 relay is to substitute an old analog transformer
protection relay, the customer should take an action to reconnect the CT secondary
circuits to match the requirement described above.
An alternative way is to connect the secondary circuits to perform external ratio
and vector group compensation, and setting the relay to External compensation.
For any given CT connection and transformer type, an advanced user can analyze
the currents and figure out a transformer type setting that would force the T60 relay to
perform correct operations that would take into account other then wye connections of
the main CTs. For correct metering purposes and to reduce chances for miswiring, wye
connections of the main CTs are, however, strongly recommended.
The figure below illustrates the T60 metering and connection conventions.

The T60 relay displays the transformer winding currents in primary Amps, in directions
as shown in the picture with reference to phase A.
--- end of public record ---Author: Lubo Sevov
Date: June 25, 2001
Products: T60
Keywords: T60, main CTs, CT connection, metering convention
Reviewed by: Bogdan Kasztenny
Reviewed on: June 26, 2001
Approved by: Bogdan Kasztenny
Approved on: June 26, 2001

You might also like