Medium voltage vacuum circuit-breakers
12...36 kV - 630...4000 A - 16...50 kA
Index
1. Description
1 2
66
70
4. Overall dimensions
9 6
1. Description
1
2
3
4
5
6
7
8
9
10
1 Upper terminal
2 Vacuum interrupter
3 Housing/pole
4 Stem of moving contact
5 Lower terminal
6 Flexible connection
1. Description
1
2
3
4
5
6
7
8
9
10
1 Stem/terminal
2 Twist protection
3 Bellows
4 Interrupter housing
5 Shield
Vacuum interrupter
6 Ceramic insulator
7 Shield
8 Contacts
9 Terminal
10 Interrupter housing
Diffuse arc.
Contraction
over anode.
Contraction over
anode and cathode.
Corrent, Voltage
Short-circuit
current
Arc voltage
System
voltage
Short-circuit current
interruption
Time
Contact
separation
Recovery voltage
(system frequency)
Transient recovery voltage (TRV)
(high frequency)
Development of current and voltage trends during a single phase vacuum interruption process.
1. Description
Versions available
The VD4 circuit-breakers are available in the fixed and
withdrawable version with front operating mechanism.
The withdrawable version is available for UniGear ZS1,
ZS2, ZS8.4 and UniSec switchgear and for PowerCube and
Powerbloc enclosures.
Fields of application
The VD4 circuit-breakers are used in power distribution for
control and protection of cables, overhead lines, transformer
and distribution substations, motors, transformers, generators
and capacitor banks.
Standards
The VD4 circuit-breakers comply with the IEC 62271-100
Standards and with those of the major industrialised
countries.
The VD4 circuit-breakers have undergone the tests indicated
below and guarantee the safety and reliability of the apparatus
in service in any installation.
Type tests: heating, withstand insulation at power frequency,
withstand insulation at lightning impulse, short-time and peak
withstand current, mechanical life, short-circuit current making
and breaking capacity.
Individual tests: insulation of the main circuits with
voltage at power frequency, auxiliary circuit and operating
mechanism insulation, measurement of the main circuit
resistance, mechanical and electrical operation.
Service safety
Thanks to the complete range of mechanical and electrical
locks (available on request), it is possible to construct safe
distribution switchgear with the VD4 circuit-breakers.
The locking devices have been studied to prevent incorrect
operations and to inspect the installations whilst guaranteeing
maximum operator safety.
Key locks or padlock devices enable opening and closing
operations and/or racking in and racking out.
The racking-out device with the door closed allows the circuitbreaker to be racked into or out of the switchgear only with
the door closed.
Anti-racking-in locks prevent circuit-breakers with different
rated currents from being racked in, and the racking-in and
racking out operation with the circuit-breaker closed.
Accessories
The VD4 circuit-breakers have a complete range of
accessories to satisfy all installation requirements.
The operating mechanism has a standardised range of
accessories and spare parts which are easy to identify and
order.
The accessories are installed conveniently from the front of
the circuit-breaker. Electrical connection is carried out with
plug-socket connectors.
Use, maintenance and service of the apparatus are simple
and require limited use of resources.
N
M
L
H
C
G
D
E
B
F
1. Description
Rated voltage
(1)
Rated frequency
Rated normal current
kV
12
Hz
50 - 60
kA
16 ... 31.5
40
50
Making capacity
kA
40 ... 80
100
125
63
(3)
158
d (mm)
150 - 275
210 - 275
210 - 275
275
H (mm)
205 - 310
310
310
310
a (mm)
450 - 700
570 - 700
600 - 750
750
b (mm)
424
424
459
459
c (mm)
461 - 599
kg
73 - 105
94 - 180
147 - 260
Embedded poles
Assembled poles
Maximum overall
dimensions
(fixed version)
H
c
d
a
Weight
Technical documentation
10
599
(5)
608
(7)
677
260
To go into technical and application aspects of the VD4 circuitbreakers in depth, please ask us for the following publications:
PowerCube modules
code 1VCP000091
Powerbloc modules
code BA441/03E
UniGear ZS1 switchgear
code 1VCP000138
ZS8.4 switchgear
code L2288
REF542plus unit
code 1VTA100001
UniSec cod. 1VFM200003
17.5
24
36
40,5
50 - 60
50 - 60
50-60
50-60
630 3150
630 3150
630 . . . 4000
630 . . . 3150
(2)
(2)
16 ... 31.5
40 ... 50
16 ... 31.5
16 ... 31.5
16 40
40 ... 80
40 ... 80
40 ... 80
40 100
150 - 275
210 - 275
210 - 275
275
205 - 310
310
310
328 / 280
(6)
450 - 700
570 - 700
570 - 700
786 / 853
(6)
424
424
424
492 / 789
(6)
631 - 661
876 / 973
(6)
461 - 599
(5)
599
(5) (7)
280 - 360
(4)
328
895
(6)
- 1000
555 - 686
(6)
1575
73 - 105
94 - 180
100 - 110
170 / 210
290 - 350
Test voltage according to IEC 622711 Standards table 1a, VDE 0670, - part
1000, list 2
(2)
With forced ventilation
(3)
Higher values on request
(4)
360 mm for fixed version, 280 mm for
withdrawable version
(5)
Circuit-breaker with eat sink 616 mm
(2500 A)
(6)
Withdrawable version
(7)
Circuit-breaker with eat sink 634 mm
(3150 A)
(1)
Quality System
Complies with ISO 9001 Standards, certified by an
independent organisation.
Test Laboratory
Complies with UNI CEI EN ISO/IEC 17025 Standards,
accredited by an independent organisation.
11
Circuit-breaker
VD4 12
Standards
IEC 62271-100
Rated voltage
Ur [kV] 12 (2)
Us [kV] 12
Withstand voltage at 50 Hz
Ud (1 min) [kV] 28
Up [kV] 75
Rated frequency
fr [Hz] 50-60
Ir [A] 630
Making capacity
630
630
1250
1250
1250
1250
1250
1250
1250
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
50
50
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
50
50
40
40
40
40
40
40
50
50
50
50
50
50
63
63
63
63
63
63
80
80
80
80
80
80
100
100
125
125
H [mm] 461
461
461
461
461
461
589
589
610
610
W [mm] 450
570
700
450
570
700
570
700
600
750
D [mm] 424
424
424
424
424
424
424
424
459
459
210
275
150
210
275
210
275
210
275
75
79
73
75
79
84
84
146
158
7406(1)
7405(1)
7406(1)
000051(1)
Isc [kA]
Ik [kA]
Ip [kA]
Operation sequence
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of
dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
(2)
(3)
(4)
12
[kg] 73
TN 7405(1)
1VCD
003441
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
Poles in polyamide
Available in 10 kV voltage version in accordance with GOST standards
Up to 4000 A with forced ventilation
On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism (instead of linear loading by a lever built into the front of
operating mechanism)
12 (2)
12
28
75
50-60
1600
1600
1600
1600
1600
1600
1600
2000
2000
2000
2000
2500
2500
2500
3150 ( 3) 3150 ( 3)
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
40
40
40
40
40
40
40
50
50
50
50
50
50
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
63
63
63
63
63
63
63
63
80
80
80
80
80
80
80
80
100
100
100
100
100
100
100
125
125
125
125
125
125
599
599
599
589
589
610
610
599
599
610
610
599
599
610
635
636
450
570
700
570
700
600
750
570
700
600
750
570
700
750
700
750
424
424
424
424
424
459
459
424
424
459
459
424
424
459
424
459
150
210
275
210
275
210
275
210
275
210
275
210
275
275
275
275
93
98
105
84
84
146
158
98
105
146
158
98
105
163
140
177
7407 (1)
7408 (1)
7407 (1)
7408 (1)
7407 (1)
7408 (1)
000050
003441
003440
003441
003441
33 ... 60
10 ... 15
43 ... 75
30 ... 60
- 5 ... + 40
13
Circuit-breaker
VD4 17
Standards
IEC 62271-100
Rated voltage
Ur [kV] 17.5
Us [kV] 17.5
Withstand voltage at 50 Hz
Ud (1 min) [kV] 38
Up [kV] 95
Rated frequency
fr [Hz] 50-60
Ir [A] 630
630
630
1250
1250
1250
1250
1250
1250
1250
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
50
50
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
50
50
40
40
40
40
40
40
50
50
50
50
50
50
63
63
63
63
63
63
80
80
80
80
80
80
100
100
125
125
H [mm] 461
461
461
461
461
461
589
589
610
610
W [mm] 450
570
700
450
570
700
570
700
600
750
D [mm] 424
424
424
424
424
424
424
424
459
459
210
275
150
210
275
210
275
210
275
75
79
73
75
79
84
84
146
158
7406( )
7405( )
7406( )
000051(1)
Isc [kA]
Making capacity
Ik [kA]
Ip [kA]
Operation sequence
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of
dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
(2)
(3)
14
[kg] 73
TN 7405( )
1
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
Poles in polyamide
Up to 4000 A with forced ventilation
On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism (instead of
linear loading by a lever built into the front of operating mechanism)
003441
17.5
17.5
38
95
50-60
1600
1600
1600
1600
1600
1600
2000
2000
2000
2000
2500
2500
3150 ( 2)
3150 ( 2)
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
40
40
40
40
50
50
50
50
50
50
20
20
20
20
20
20
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
50
50
50
63
63
63
63
63
63
80
80
80
80
80
80
100
100
100
100
100
100
125
125
125
125
125
125
599
599
589
589
610
610
599
599
610
610
599
610
635
636
570
700
570
700
600
750
570
700
600
750
700
750
700
750
424
424
424
424
459
459
424
424
459
459
424
459
424
459
210
275
210
275
210
275
210
275
210
275
275
275
275
275
98
105
84
84
146
158
98
105
146
158
105
163
140
177
7407 ( )
7408 ( )
7408 ( )
003441
003440
003441
003441
000149 (1)
003443
33 ... 60
10 ... 15
43 ... 75
30 ... 60
7407 ( )
7408 ( )
- 5 ... + 40
15
Circuit-breaker
VD4 24
Standards
IEC 62271-100
Rated voltage
Ur [kV] 24
Us [kV] 24
Withstand voltage at 50 Hz
Ud (1 min) [kV] 50
Up [kV] 125
Rated frequency
fr [Hz] 50-60
Ir [A] 630
630
1250
1250
1600
2000
2500
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
16
16
16
16
16
16
20
20
20
20
20
20
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
40
40
40
40
40
40
50
50
50
50
50
50
63
63
63
63
63
63
63
80
80
80
80
[O - 0.3 s - CO - 15 s - CO]
H [mm] 631
631
631
631
642
642
642
W [mm] 570
700
570
700
700
700
700
D [mm] 424
424
424
424
424
424
424
275
210
275
275
275
275
[kg] 100
104
100/106
104
110
110
110
7410
7409
7410
7411
7411
7411
000172
Making capacity
Isc [kA]
Ik [kA]
Ip [kA]
Operation sequence
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
TN 7409
1VCD
(1)
(1)
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
16
Circuit-breaker
VD4 36
Standards
IEC 62271-100
Rated voltage
Ur [kV] 36
Us [kV] 36
Withstand voltage at 50 Hz
Ud (1 min) [kV] 70
Up [kV] 170
Rated frequency
fr [Hz] 50
Ir [A] 1250
Making capacity
Operation sequence
1600
2000
2500
20
20
20
20
Isc [kA] 25
25
25
25
31.5
31.5
31.5
31.5
20
20
20
20
Ik [kA] 25
25
25
25
31.5
31.5
31.5
31. 5
50
50
50
50
Ip [kA] 63
63
63
63
80
80
80
80
H [mm] 564
564
564
564
W [mm] 778
778
778
778
D [mm] 468
468
468
468
275
275
275
[kg] 150
150
170
170
1VYN300901-LT
1VYN300901-LT
1VYN300901-LT
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 35 ... 60
Arcing time
[ms] 10 ... 15
[ms] 45 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
(1)
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
TN 1VYN300901-LT
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
17
VD4 fixed circuit-breaker without bottom and top terminals (12 kV)
Ur
kV
Isc
kA
H=589
H=599
H=610
H=636
D=424
D=424
D=424
D=459
D=459
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
l/g=217.5
l/g=238
l/g=237.5
l/g=237
l/g=237
P=150
P=210
P=275
P=210
P=275
P=150
P=210
P=275
P=210
P=275
P=275
W=450
W=570
W=700
W=570
W=700
W=450
W=570
W=700
W=600
W=750
W=750
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
20
1600
25
1600
1600
31.5
12
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
20
2500
25
2500
31.5
2500
40
2500
u/l
l/g
= Distance between the bottom terminal and the resting surface of the circuit-breaker.
18
Circuit-breaker type
VD4 fixed circuit-breaker without bottom and top terminals (12 kV)
Ur
kV
Isc
kA
H=589
H=599
H=610
H=636
D=424
D=424
D=424
D=459
D=459
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
l/g=217.5
l/g=238
l/g=237.5
l/g=237
l/g=237
P=150
P=210
P=275
P=210
P=275
P=150
P=210
P=275
P=210
P=275
P=275
W=450
W=570
W=700
W=570
W=700
W=450
W=570
W=700
W=600
W=750
W=750
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
50
1250
20
1600
25
1600
31.5
1600
40
12
Circuit-breaker type
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
20
2500
25
2500
31.5
2500
40
2500
50
20
3150 (1)
25
3150 (1)
31.5
3150 ( )
40
3150 (1)
50
3150 (1)
u/l
l/g
= Distance between the bottom terminal and the resting surface of the circuit-breaker
(1)
19
VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV)
Ur
Isc
kV
kA
17.5
H=589
H=599
H=610
H=635
D=424
D=424
D=424
D=459
D=459
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
l/g=217.5
l/g=238
l/g=237.5
l/g=237
l/g=237.5
P=150
P=210
P=275
P=210
P=275
P=150
P=210
P=275
P=210
P=275
P=275
W=450
W=570
W=700
W=570
W=700
W=450
W=570
W=700
W=600
W=750
W=750
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
H
u/l
l/g
= Distance between the bottom terminal and the resting surface of the circuit-breaker.
20
Circuit-breaker type
VD4 fixed circuit-breaker without bottom and top terminals (17.5 kV)
Ur
Isc
kV
kA
H=589
H=599
H=610
H=635
D=424
D=424
D=424
D=459
D=459
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
l/g=217.5
l/g=238
l/g=237.5
l/g=237
l/g=237.5
P=150
P=210
P=275
P=210
P=275
P=150
P=210
P=275
P=210
P=275
P=275
W=450
W=570
W=700
W=570
W=700
W=450
W=570
W=700
W=600
W=750
W=750
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
50
1250
20
1600
25
1600
31.5
1600
40
17.5
Circuit-breaker type
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
20
2500
25
2500
31.5
2500
40
2500
50
20
3150
25
3150
31.5
3150
40
3150
50
3150
u/l
l/g
= Distance between the bottom terminal and the resting surface of the circuit-breaker.
(1)
21
VD4 fixed circuit-breaker without bottom and top terminals (24 kV)
Ur
Isc
kV
kA
24
H
W
D
u/l
l/g
P
22
=
=
=
=
=
=
H=642
D=424
D=424
u/l=310
u/l=310
l/g=282.5
Circuit-breaker type
l/g=282.5
P=210
P=275
P=275
W=570
W=700
W=700
16
630
20
630
25
630
16
1250
20
1250
25
1250
31.5
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
16
1600
20
1600
25
1600
31.5
1600
16
2000
20
2000
25
2000
31.5
2000
25
2500
31.5
2500
VD4 fixed circuit-breaker without bottom and top terminals (36 kV)
Ur
Isc
kV
kA
P = 478.5
Circuit-breaker type
u/l = 328
l/g = 428.5
l = 275
36
H
W
D
u/l
l/g
P
(1)
=
=
=
=
=
=
=
20
1250 A
25
1250 A
31.5
1250 A
20
1600 A
25
1600 A
31.5
1600 A
20
2000 A
25
2000 A
31.5
2000 A
20
2500 A
(1)
25
2500 A
(1)
31.5
2500 A
(1)
VD4 - 36 kV
23
Circuit-breaker
VD4/P 12
Standards
IEC 62271-100
Rated voltage
Ur [kV] 12 (4)
Us [kV] 12
Withstand voltage at 50 Hz
Ud (1 min) [kV] 28
Up [kV] 75
Rated frequency
fr [Hz] 50-60
Ir [A] 630
(1)
Making capacity
Isc [kA]
Ik [kA]
Ip [kA]
Operation sequence
1250
1250
1250
1250
1600
1600
16
16
20
20
20
20
25
25
25
25
31.5
31.5
31.5
31.5
40
40
50
16
16
20
20
20
20
25
25
25
25
31.5
31.5
31.5
31.5
40
40
50
40
40
50
50
50
50
63
63
63
63
80
80
80
80
100
100
125
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
H [mm] 628
628
691
691
691
691
691
W [mm] 503
503
653
853
681
653
853
D [mm] 662
662
641
642
643
642
642
150
210
275
210
210
275
[kg] 116
116
174
176
180
160
166
7412( 3)
7415( 3)
7416(3)
003284( )
003444
TN 7412( 3)
1VCD
003286( )
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Poles in polyamide
(4) Available in 10 kV voltage version in accordance with GOST standards
(5) On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
24
12 ( 4)
12
28
75
50-60
1600
1600
1600
1600
2000
2000
2000
2000
2500
2500
3150
20
20
20
20
25
25
25
25
31.5
31.5
31.5
31.5
40
40
40
40
40
40
50
50
50
50
50
50
20
20
20
20
25
25
25
25
31.5
31.5
31.5
31.5
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
50
63
63
63
63
80
80
80
80
100
100
100
100
100
100
125
125
125
125
125
125
691
691
691
691
691
691
691
691
691
691
730
742
653
853
681
853
653
853
681
853
853
853
853
853
641
642
643
643
642
642
643
643
640
643
640
643
210
275
210
275
210
275
210
275
275
275
275
275
174
176
180
193
160
166
190
205
186
225
221
240
7415(3)
7416( 3)
7417( 3)
003284(3)
003286(3)
003444
003445
003444
003445
003446
000153(3)
003447
(2)
3150
(2)
33 ... 60
10 ... 15
43 ... 75
30 ... 60
- 5 ... + 40
25
Circuit-breaker
VD4/P 17
Standards
IEC 62271-100
Rated voltage
Ur [kV] 17,5
Us [kV] 17,5
Withstand voltage at 50 Hz
Ud (1 min) [kV] 38
Up [kV] 95
Rated frequency
fr [Hz] 50-60
Ir [A] 630
(1)
Making capacity
1250
1250
1250
1250
1600
1600
16
16
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
50
16
16
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
50
40
40
50
50
50
50
63
63
63
63
80
80
80
80
100
100
125
H [mm] 632
632
691
691
691
691
691
W [mm] 503
503
653
853
681
653
853
D [mm] 664
664
641
642
643
642
642
150
210
275
210
210
275
[kg] 116
116
174
176
180
160
166
7412(3)
7415(3)
7416( 3)
003284( 3)
003286( 3)
003444
Isc [kA]
Ik [kA]
Ip [kA]
Operation sequence
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
TN 7412( 3)
1VCD
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Poles in polyamide
(4) On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
26
17,5
17,5
38
95
50-60
1600
1600
1600
1600
2000
2000
2000
2000
2500
2500
3150
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
40
40
50
50
50
50
50
50
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
50
63
63
63
63
80
80
80
80
100
100
100
100
100
100
125
125
125
125
125
125
691
691
691
691
691
691
691
691
691
691
730
742
653
853
681
853
653
853
681
853
853
853
853
853
641
642
643
643
642
642
643
643
640
643
640
643
210
275
210
275
210
275
210
275
275
275
275
275
174
176
180
193
160
166
190
205
186
225
221
240
7415(3)
7416( 3)
7417( 3)
003284(3)
003286(3)
003444
003445
003444
003445
003446
000153(3)
003447
(2)
3150
(2)
33 ... 60
10 ... 15
43 ... 75
30 ... 60
- 5 ... + 40
27
Circuit-breaker
VD4/P 24
Standards
IEC 62271-100
Rated voltage
Ur [kV] 24
Us [kV] 24
Withstand voltage at 50 Hz
Ud (1 min) [kV] 50
Up [kV] 125
Rated frequency
fr [Hz] 50-60
Ir [A] 630
630
1250
1250
1600
2000
2500
16
16
16
16
16
16
16
20
20
20
20
20
20
20
25
25
25
25
25
25
25
31,5
31,5
31,5
31,5
31,5
31,5
16
16
16
16
16
16
16
20
20
20
20
20
20
20
25
25
25
25
25
25
25
31,5
31,5
31,5
31,5
31,5
31.5
40
40
40
40
40
40
40
50
50
50
50
50
50
50
63
63
63
63
63
63
63
80
80
80
80
80
80
[O - 0.3 s - CO - 15 s - CO]
H [mm] 794
794
794
794
838
838
838
838
W [mm] 653
853
653
853
853
853
853
853
D [mm] 802
802
802
802
790
790
790
790
275
210
275
275
275
275
275
[kg] 140
148
140/146
148
228
228
228
277
7414
7413
7418
7418
7418
000173
000177
(1)
Isc [kA]
Making capacity
Ik [kA]
Ip [kA]
Operation sequence
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 43 ... 75
Closing time
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
(2)
(3)
(4)
(5)
TN 7413
1VCD
(4)
7414
(4)
000174
(4)
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 C ambient temperature.
2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
2700 A rated current guaranteed with natural ventilation; 3150 A rated current guaranteed with forced ventilation.
31.5 kA version.
On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
28
3150
(3)
[ms] 30 ... 60
P P
Maximum
overall
dimensions
(2)
Circuit-breaker
VD4/W 36
Standards
IEC 62271-100
Rated voltage
Ur [kV] 36
Us [kV] 36
Withstand voltage at 50 Hz
Ud (1 min) [kV] 70
Up [kV] 170
Rated frequency
fr [Hz] 50
Ir [A] 1250
Making capacity
Operation sequence
1600
2000
2500 ( 1)
20
20
20
20
Isc [kA] 25
25
25
25
31.5
31.5
31.5
31.5
20
20
20
20
Ik [kA] 25
25
25
25
31.5
31.5
31.5
31.5
50
50
50
50
Ip [kA] 63
63
63
63
80
80
80
80
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
Arcing time
[ms] 10 ... 15
[ms] 45 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
H [mm] 973
973
973
973
W [mm] 842
842
842
842
D [mm] 788
788
788
788
275
275
275
[kg] 230
230
230
230
1VYN300901-KG
1VYN300901-KG
1VYN300901-KG
TN 1VYN300901-KG
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
29
kV
12
W =
P =
u/l =
=
30
Isc
kA
W=800
W=1000
W=1000
W=1000
P=150
P=210
P=275
P=275
P=275
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
=35
=79
=79
=109
=109
Circuit-breaker type
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
1250
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
40
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
Switchboard width.
Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.
kV
12
Isc
kA
W=800
W=1000
W=1000
W=1000
P=150
P=210
P=275
P=275
P=275
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
=35
=79
=79
=109
=109
Circuit-breaker type
20
2500
25
2500
31,5
2500
40
2500
50
2500
20
3150 (1)
25
3150
(1)
31,5
3150
(1)
40
3150
(1)
50
3150
(1)
W = Switchboard width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.
31
kV
17.5
W =
P =
u/l =
=
32
Isc
kA
W=800
W=1000
W=1000
W=1000
P=150
P=210
P=275
P=275
P=275
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
=35
=79
=79
=109
=109
Circuit-breaker type
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
1250
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
40
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
Switchboard width.
Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.
kV
17.5
Isc
kA
W=800
W=1000
W=1000
W=1000
P=150
P=210
P=275
P=275
P=275
u/l=205
u/l=310
u/l=310
u/l=310
u/l=310
=35
=79
=79
=109
=109
Circuit-breaker type
20
2500
25
2500
31.5
2500
40
2500
50
2500
20
3150
(1)
25
3150
(1)
31.5
3150
(1)
40
3150
(1)
50
3150
(1)
W = Switchboard width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.
33
kV
24
Isc
kA
W=1000
W=1000
W=1000
P=210
P=275
P=275
P=275
u/l=310
u/l=310
u/l=310
u/l=310
=35
=35
=79
=109
16
630
20
630
25
630
16
1250
20
1250
25
1250
31.5
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
31.5
1250
16
1600
20
1600
25
1600
31.5
1600
16
2000
20
2000
25
2000
31.5
2000
16
2300
(1)
20
2300
(1)
25
2300
(1)
31.5
2300
(1)
31.5
W = Switchboard width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) 2500 A rated current guaranteed with forced ventilation.
(2) 3150 A rated current guaranteed with forced ventilation.
34
Circuit-breaker type
(2)
Isc
kV
kA
W = 778
Circuit-breaker type
u/l = 380
= 399
P= 275
36
20
1250 A
25
1250 A
31.5
1250 A
20
1600 A
25
1600 A
31.5
1600 A
20
2000 A
25
2000 A
31.5
2000 A
20
2500 A (1)
25
2500 A (1)
31.5
2500 A (1)
VD4 up to 24 kV
H =
D =
W =
u/l =
=
P =
(1)
VD4 - 36 kV
35
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 C)
(1)
PowerCube module
IEC 62271-100
Ur [kV]
Us [kV]
Ud (1 min) [kV]
Up [kV]
fr [Hz]
Ir [A]
Isc [kA]
Rated short-time
withstand current (3s)
Ik [kA]
Making capacity
Ip [kA]
Operation sequence
Opening time
Arcing time
Total breaking time
Closing time
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
[O - 0.3 s - CO - 15 s - CO]
[ms]
[ms]
[ms]
[ms]
H [mm]
W [mm]
D [mm]
Pole distance P [mm]
[kg]
TN
1VCD
[C]
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
VD4/P 12
VD4/W 12 (6)
PB1
12 (4)
12
28
75
50-60
630
16
20
25
31.5
16
20
25
31.5
40
50
63
80
33 ... 60
10 ... 15
43 ... 75
30 ... 60
628
503
662
150
116
7412 (3)
- 5 ... + 40
PB2
12 ( 4)
12
28
75
50-60
630
16
20
25
31.5
16
20
25
31.5
40
50
63
80
33 ... 60
10 ... 15
43 ... 75
30 ... 60
691
653
642
210
135
7420 (3)
- 5 ... + 40
1250
16
20
25
31.5
16
20
25
31.5
40
50
63
80
628
503
662
150
116
7412 (3)
1250
16
20
25
31.5
16
20
25
31.5
40
50
63
80
691
853
642
210
135
7420 (3)
(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature
(2) Up to 4000 A with forced ventilation.
(3) Poles in polyamide
(4) Available in 10 kV voltage version in accordance with GOST standards
(5) On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
(6) VD4/W does not need insulation for the feed-through and tulip contacts in module PB2. On request, the same circuit-breaker with insulated feed-through and tulip
contacts is available for installation in enclosures not produced by ABB (version VD4/PW).
36
VD4/P 12
PB2
12 (4)
12
28
75
50-60
1250
40
40
100
33 ... 60
10 ... 15
43 ... 75
30 ... 60
691
653
641
210
174
003284 (3)
- 5 ... + 40
VD4/W 12
1250
50
50
125
1600
20
25
31.5
20
25
31.5
50
63
80
1600
40
40
100
1600
50
50
125
2000
20
25
31.5
40
20
25
31.5
40
50
63
80
100
2000
50
50
125
691
681
643
210
180
003444
691
653
642
210
160
7415 (3)
691
653
641
210
174
003284 (3)
691
681
643
210
180
003444
690
653
642
210
160
7415 ( 3)
691
681
643
210
190
003444
PB3
12 ( 4)
12
28
75
50-60
2500
20
25
31.5
40
20
25
31.5
40
50
63
80
100
33 ... 60
10 ... 15
43 ... 75
30 ... 60
691
853
640
275
186
7417 ( 3)
- 5 ... + 40
2500
50
50
125
691
853
643
275
225
003445
PB3
12 ( 4)
12
28
75
50-60
3150 (2)
20
25
31,5
40
20
25
31,5
40
50
63
80
100
33 ... 60
10 ... 15
43 ... 75
30 ... 60
730
853
640
275
221
000152 (3)
- 5 ... + 40
3150 (2)
50
50
125
691
853
643
275
240
003596
37
Circuit-breaker
VD4/P 17
VD4/W 17 (5)
PB2
IEC 62271-100
Rated voltage
Ur [kV] 17,5
17,5
Us [kV] 17,5
17,5
Withstand voltage at 50 Hz
mpulse withstand voltage
Rated frequency
Ud (1 min) [kV] 38
38
Up [kV] 95
95
fr [Hz] 50-60
Ir [A] 630
(1)
Isc [kA]
Rated short-time
withstand current (3s)
Ik [kA]
Making capacity
Ip [kA]
Operation sequence
50-60
1250
630
1250
16
16
16
16
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
16
16
16
16
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
50
50
50
50
63
63
63
63
80
80
80
80
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
33 ... 60
Arcing time
[ms] 10 ... 15
10 ... 15
[ms] 43 ... 75
43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
30 ... 60
H [mm] 628
628
691
691
w [mm] 503
503
653
653
D [mm] 662
662
642
642
150
210
210
[kg] 116
116
135
135
7412 (3)
7420 (3)
7420 ( 3)
TN 7412 ( 3)
1VCD
[C] - 5 ... + 40
- 5 ... + 40
IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature.
(2) Up to 4000 A with forced ventilation.
(3) Poles in polyamide.
(4) On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
(5) VD4/W does not need insulation for the feed-through and tulip contacts in module PB2. On request, the same circuit-breaker with insulated feed-through
and tulip contacts is available for installation in enclosures not produced by ABB (version VD4/PW).
38
VD4/P 17
VD4/W 17
PB2
PB3
PB3
17,5
17,5
17,5
17,5
17,5
17,5
38
38
38
95
95
95
50-60
50-60
50-60
1250
1250
1600
1600
1600
2000
2000
2500
2500
3150
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
40
50
50
50
50
50
20
20
20
20
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
40
50
50
50
50
50
50
50
50
50
63
63
63
63
80
80
80
80
100
100
100
100
100
125
125
125
125
125
(2)
33 ... 60
33 ... 60
33 ... 60
10 ... 15
10 ... 15
10 ... 15
43 ... 75
43 ... 75
43 ... 75
30 ... 60
30 ... 60
3150
(2)
30 ... 60
691
691
691
691
691
690
691
691
691
730
691
653
681
653
653
681
653
681
853
853
853
853
641
643
642
641
643
642
643
640
643
640
643
210
210
210
210
210
210
210
275
275
275
275
174
180
160
174
180
160
190
186
225
221
240
7415 (3)
7415 ( 3)
7417 ( 3)
003284 (3)
003444
003284 (3)
003444
003444
003445
000152 ( 3)
003596
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
39
Circuit-breaker
VD4/P 24
PowerCube module PB4
Standards
PB5
IEC 62271-100
Rated voltage
Ur [kV] 24
24
Us [kV] 24
24
Ud (1 min) [kV] 50
50
Withstand voltage at 50 Hz
Impulse withstand voltage
Up [kV] 125
Rated frequency
125
fr [Hz] 50-60
(1)
Ir [A] 630
Isc [kA]
Rated short-time
withstand current (3s)
Ik [kA]
Making capacity
Ip [kA]
Operation sequence
50-60
1250
1600
2000
2500
16
16
16
16
16
20
20
20
20
20
25
25
25
25
25
31,5
31,5
31,5
31,5
16
16
16
16
16
20
20
20
20
20
25
25
25
25
25
31,5
31,5
31,5
31,5
40
40
40
40
40
50
50
50
50
50
63
63
63
63
63
80
80
80
80
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
33 ... 60
Arcing time
[ms] 10 ... 15
10 ... 15
[ms] 43 ... 75
43 ... 75
Closing time
[ms] 30 ... 60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
30 ... 60
H [mm] 794
794
838
838
838
W [mm] 653
653
853
853
853
D [mm] 802
802
790
790
790
210
275
275
275
228
228
228
7418
7418
7418
[kg] 140
TN 7413
1VCD
140/146
(3)
7413
000173
(3)
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC: 62271-1
(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 C ambient temperature.
(2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
(3) 31.5 kA version.
(4) On request, the closing spring can be loaded by means of a removable crank handle outside operating mechanism
(instead of linear loading, only possible with the door open, by means of a lever built into the front of the operating mechanism).
40
(2)
kV
12
Isc
kA
W=750
W=750
W=1000
P=150
P=210
P=210
P=275
u/l=205
u/l=310
u/l=310
u/l=310
=35
=35
=79
=109
Circuit-breaker type
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
1250
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
20
2500
25
2500
31.5
2500
40
2500
50
2500
20
3150 (1)
25
3150
(1)
31.5
3150
(1)
40
3150
(1)
50
3150
(1)
W = Enclosure width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.
41
kV
17.5
Isc
kA
W=750
W=750
W=1000
P=150
P=210
P=210
P=275
u/l=205
u/l=310
u/l=310
u/l=310
=35
=35
=79
=109
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
16
630
20
630
25
630
31.5
630
16
1250
20
1250
25
1250
31.5
1250
40
1250
50
1250
20
1600
25
1600
31.5
1600
40
1600
50
1600
20
2000
25
2000
31.5
2000
40
2000
50
2000
20
2500
25
2500
31.5
2500
40
2500
50
2500
20
25
3150
(1)
3150
(1)
31.5
3150
(1)
40
3150
(1)
50
3150
(1)
W = Enclosure width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 4000 A with forced ventilation.
42
Circuit-breaker type
kV
24
Isc
kA
W=1000
P=210
P=275
u/l=310
u/l=310
=35
=79
Circuit-breaker type
16
630
20
630
25
630
16
1250
20
1250
25
1250
31.5
1250
16
1600
20
1600
25
1600
31.5
1600
16
2000
20
2000
25
2000
31.5
2000
16
2300
(1)
20
2300
(1)
25
2300
(1)
31.5
2300
(1)
W = Enclosure width.
P = Pole horizontal centre distance.
u/l = Distance between bottom and top terminal.
= Diameter of the isolating contact.
(1) Up to 2500 A rated current guaranteed with forced ventilation.
Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.
43
Circuit-breaker
VD4/Z8
Panel without partitions
Panel with partitions
Preussen Elektra - EON
Standards
(2)
650
650
650
800
800
1000
1000
1000
1200
1200
Ur [kV] 12
12
17.5
17.5
24
24
IEC 62271-100
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Us [kV] 12
12
17.5
17.5
24
24
Ud (1 min) [kV] 28
28
38
38
50
50
Up [kV] 75
75
95
95
125
125
fr [Hz] 50-60
(1)
Making capacity
Operation sequence
Ir [A] 630
1250
630
1250
630
1250
16
16
Isc [kA] 20
20
20
20
20
20
25
25
25
25
25
25
16
16
Ik [kA] 20
20
20
20
20
20
25
25
25
25
25
25
40
40
Ip [kA] 50
50
50
50
50
50
63
63
63
63
63
63
H [mm] 579
579
579
579
680
680
W [mm] 503
503
503
503
653
653
D [mm] 548
548
548
548
646
646
150
150
150
210
210
[kg] 116
116
116
116
140
140
000137
000137
000137
000089
000138
[O-0.3s-CO-15s-CO]
Opening time
[ms] 33...60
Arcing time
[ms] 10...15
[ms] 43...75
Closing time
[ms] 30...60
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalisation
Electromagnetic compatibility
1VCD 000092
[C] 5 ... + 40
IEC 60068-2-30
IEC 60721-2-1
IEC 62271-1
(1) Rated current guaranteed with circuit-breaker installed in switchgear with 40 C ambient temperature.
(2) Special type with device for charging the closing spring by means of a rotary handle outside the operating mechanism.
44
VD4/ZT8
VD4/ZS8
650
650
650
650
800
800
650
650
800
800
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
12
12
17.5
17.5
24
24
12
12
24
24
12
12
17.5
17.5
24
24
12
12
24
24
28
28
38
38
50
50
28
28
50
50
75
75
95
95
125
125
75
75
125
125
50-60
50-60
630
1250
630
1250
630
1250
630
1250
630
1250
16
16
16
16
20
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
25
16
16
16
16
20
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
25
40
40
40
40
50
50
50
50
50
50
50
50
50
50
63
63
63
63
63
63
63
63
63
63
33...60
33...60
10...15
10...15
43...75
43...75
30...60
30...60
579
579
579
579
680
680
579
579
680
680
503
503
503
503
653
653
503
503
653
653
638
638
638
638
646
646
638
638
646
646
150
150
150
150
210
210
150
150
210
210
116
116
116
116
140
140
116
116
140
140
000093
000134
000134
000134
000090
000136
000091
000133
000088
000135
5 ... + 40
5 ... + 40
45
kV
12
17.5
24
W =
P =
u/l =
=
46
Isc
kA
W = 650
W = 800
W = 650
W = 800
W = 650
W = 800
P = 150
P = 210
P = 150
P = 210
P = 150
P = 210
u/l = 205
u/l = 310
u/l = 205
u/l = 310
u/l = 205
u/l = 310
= 35
= 35
= 35
= 35
= 35
= 35
Circuit-breaker type
20
630
25
630
20
1250
25
1250
20
630
25
630
20
1250
25
1250
20
630
25
630
20
1250
25
1250
20
630
25
630
20
1250
25
1250
20
630
25
630
20
1250
25
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
Switchboard width.
Pole horizontal centre distance.
Distance between bottom and top terminal.
Diameter of the isolating contact.
Note: with the group of ten auxiliary contacts supplied as standard and the
maximum number of electrical applications, three break contacts (signalling
circuit-breaker open) and four make contacts (signalling circuit-breaker closed)
are available.
Caption
1) Device with crank handle for loading closing spring (only version VD4/ZS8)
2) Harting 64 plus socket with mechanical interlock which prevents traverse
when the socket is not inserted
3) Interlock that prevents door from closing if plug is not in socket (only version
VD4/ZS8)
VD4/Z8 - VD4/ZT8
Harting 64-pin socket with mechanical interlock which
prevents traverse of the circuit-breaker when the plug is not
inserted in the socket.
47
Circuit-breaker
VD4/US 24
Standards
VD4/US 24
(3)
(4)
IEC 62271-100
Rated voltage
Ur [kV] 24
24
24
24
Us [kV] 24
24
24
24
Ud (1 min) [kV] 50
50
50
50
125
125
125
fr [Hz] 50-60
50-60
50-60
50-60
Ir [A] 630
1250
630
1250
Withstand voltage at 50 Hz
Impulse withstand voltage
Up [kV] 125
Rated frequency
Rated normal current (40 C)
(1)
Rated short-time
withstand current (3 s)
(2)
16 (20)
(5)
16 (25)
(5)
16
16
(5)
20 (25)
(5)
20
20
25
25
16 (20)
(5)
16 (25)
(5)
16
16
Ik [kA] 20 (25)
(5)
20 (25)
(5)
20
20
25
25
40
40
50
50
63
63
Making capacity
40 (50)
(5)
40 (50)
(5)
Ip [kA] 50 (63)
(5)
50 (63)
(5)
Operation sequence
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
33 ... 60
33 ... 60
33 ... 60
Arcing time
[ms] 10 ... 15
10 ... 15
10 ... 15
10 ... 15
[ms] 43 ... 75
43 ... 75
43 ... 75
43 ... 75
Closing time
[ms] 30 ... 60
30 ... 60
30 ... 60
30 ... 60
H [mm] 680
680
680
680
W [mm] 653
653
653
653
D [mm] 742
742
742
742
210
210
210
[kg] 125
125
125
125
000047
000047
000047
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
IEC 62271
P P
Maximum
overall
dimensions
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
(2)
(3)
(4)
(5)
48
1VCD 000047
[C] - 5 ... + 40
Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature
The value and duration of the rated short-time withstand current depends on the switchgear. See the specific catalogues of the UniSwitch and UniMix switchgear
The top shutter activation wheels of the UniSwitch switchgear (CBW unit) are mounted and adjusted by the manufacturer of the UniSwitch switchgear
The top shutter activation wheels of the UniMix switchgear (P1/E unit) are available on request
The values in brackets refer to the 12 kV rated voltage.
Withdrawable c.-breaker for UniSwitch switchgear (CBW type unit) and UniMix switchgear (P1/E type unit)
Ur
kV
24
Isc
UniMix P1/E
P=210
P=210
u/l=310
u/l=310
=35
=79
16
630
(1)
630
20
630
(1)
630
25
630
16
1250
(1)
1250
20
1250
(1)
1250
25
1250
kA
Circuit-breaker type
49
VD4/SEC
Circuit-breaker
Standards
IEC 62271-100
VD4/P 12
VD4/P 17
Rated voltage
Ur [kV] 24
12
17.5
Us [kV] 24
12
17.5
Ud (1 min) [kV] 50
28
38
75
95
Withstand voltage at 50 Hz
Impulse withstand voltage
Up [kV] 125
Rated frequency
Rated normal current (40 C)
fr [Hz] 50-60
Ir [A] 630 - 1250
(1)
Rated short-time
withstand current (3 s)
Making capacity
Operation sequence
50-60
1250
630
1250
16
16
16
16
16
Isc [kA] 20
20
20
20
20
25
25
25
25
25
16
16
16
16
16
Ik [kA] 20
20
20
20
20
25
25
25
25
25
40
40
40
40
40
Ip [kA] 50
50
50
50
50
63
63
63
63
63
[O - 0.3 s - CO - 15 s - CO]
Opening time
[ms] 33 ... 60
33 60
Arcing time
[ms] 10 ... 15
10 15
[ms] 43 ... 75
43 75
Closing time
[ms] 30 ... 60
30 60
P P
H
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
Electromagnetic compatibility
H [mm] 743
628
628
632
632
W [mm] 653
503
503
503
503
D [mm] 742
662
662
664
664
150
150
150
150
[kg] 133
116
1VCD 000190
7412
[C] - 5 ... + 40
IEC: 60068-2-30, 60721-2-1
IEC 62271
(1) Rated current guaranteed with withdrawable circuit-breaker installed in switchgear with 40 C ambient temperature.
(2) Poles in polyamide.
50
50-60
630
116
(2)
7412
116
(2)
7412
116
(2)
7412
(2)
Isc
kV
kA
12
17
24
P=150
P=210
u/l=205
u/l=205
u/l=310
=35
=35
=79
Circuit-breaker type
16
630
20
630
25
630
16
1250
20
1250
25
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
16
630
20
630
25
630
16
1250
20
1250
25
1250
51
The accessories identified with the same number are alternative to each other.
Characteristics
Un
24-30-48-60-110...132-220...250 V DC
Un
48-60-110...127-220...250 V AC 50-60 Hz
Operating limits
65 120% Un
60...100 W / VA
1.5 mA
Opening time
33...60 ms
Insulation voltage
(*) The minimum current that the relay with TCS function (used for monitoring coil
continuity) detects as a condition denoting that the trip circuit is operating correctly
(specified for each relay in the relative manual), must be sensibly higher than the
current consumption of the actual coil (~1.5 mA).
If this fails to occur, always add, in parallel to the TCS, a circuit able to absorb sufficient current to compensate the gap while preventing the total current in the TCS
circuit from rising above the maximum threshold (Itcs < 10 mA for High Voltage coils
- from 110V to 250V, and Itcs < 50 mA for Low Voltage coils from 24 V to 60 V).
A simple resistor can be sized for the purpose, depending on the parameters of the
TCS and the auxiliary voltage range used.
52
Note: for combination with the protection relays, please ask for the
document: Data sheet 1VCD600854.
Characteristics
(*) The minimum current that the relay with TCS function (used for monitoring coil
continuity) detects as a condition denoting that the trip circuit is operating correctly
(specified for each relay in the relative manual), must be sensibly higher than the
current consumption of the actual coil (~1.5 mA).
If this fails to occur, always add, in parallel to the TCS, a circuit able to absorb sufficient current to compensate the gap while preventing the total current in the TCS
circuit from rising above the maximum threshold (Itcs < 10 mA for High Voltage coils
- from 110V to 250V, and Itcs < 50 mA for Low Voltage coils from 24 V to 60 V).
A simple resistor can be sized for the purpose, depending on the parameters of the
TCS and the auxiliary voltage range used.
Un
24-30-48-60-110...132-220...250 V DC
Un
48-60-110...127-220...250 V AC 50-60 Hz
Operating limits
65 120% Un
60...100 W / VA
Opening time
33...60 ms
Insulation voltage
1.5 W
1.5 mA
53
54
Un
24-30-48-60-110...132-220...250 V DC
Un
48-60-110...127-220...250 V AC 50-60 Hz
Operating limits
150 W / VA
Opening time
60...80 ms
Insulation voltage
1.55 W
1.5 mA
Note
As an alternative to the undervoltage release, an additional
shunt opening release (-MBO4) with the same electrical
and operating specifications as shunt opening release
(-MBO1) can be installed on request (only for circuit-breakers
12..17.5 kV up to 40 kA and 24 kV up to 31.5 kA).
Warning! Since installation of the additional shunt opening
release (-MBO4) requires a special mounting plate for
releases, ask for application (-MBO4) when ordering and not
after delivery.
Un
Un
55
56
Consult circuit diagrams 1VCD400151 for fixed circuitbreakers and 1VCD400155 for withdrawable circuit-breakers.
Note: The main shunt opening release and/or the additional
shunt opening release use 1 and/or 2 closing contacts "a",
thereby reducing the number of auxiliary contacts available.
Always check the maximum number of contacts available with
non-standard equipment.
The new diagrams are interchangeable with the existing ones,
with the following exceptions:
diagram 1VCD400151 (substitutes 1VCD400046 and
1VCD400099)
fig. 34 on the previous diagrams is represented by fig. 31 +
fig. 32 on the new diagram;
fig. 33 and fig. 35 on the previous diagrams are not
available with the new layout
diagram 1VCD400155 (substitutes 1VCD400047)
220 V AC
Cosj = 0.70
20 A
220 V DC
Cosj = 0.45
10 A
1 ms
12 A
15 ms
9A
50 ms
6A
1 ms
10 A
15 ms
6A
50 ms
4,6 A
1 ms
7A
15 ms
4.5 A
50 ms
3.5 A
1 ms
2A
15 ms
1.7 A
24 V DC
60 V DC
110 V DC
General characteristics
Insulation voltage to standard
VDE 0110, Group C
660 V AC
800 V DC
Rated voltage
24 V ... 660 V
50 ms
1.5 A
Test voltage
2 kV for 1 min
1 ms
2A
10 A - 50/60 Hz
15 ms
1,4 A
Breaking capacity
50 ms
1.2 A
Number of contacts
Groups of contacts
10 / 16 / 20
Contact travel
90
Rated current Un
Breaking capacity
Actuating force
0.66 Nm
24 Vcc 20 ms
18,8 mA
Resistance
<6.5 m
60 Vcc 20 ms
7,4 mA
Storage temperature
110 Vcc 20 ms
4,2 mA
250 Vcc 20 ms
1,8 mA
Contact overtemperature
30 C ... +120 C
20 C ... +70 C
(-30 ref. ANSI 37.09)
10 K
Mechanical life
Protection class
IP20
Cable section
1 mm2
Operating temperature
220 V DC
250 V DC
57
General characteristics
Insulation voltage to standard
VDE 0110, Group C
660 V a.c.
800 V d.c.
Rated voltage
Test voltage
2 kV 50 Hz (for 1 min)
Rated overcurrent
10 A
Number of contacts
Contact run
6 mm ... 7 mm
Activation force
26 N
Resistance
3 m
Storage temperature
20 C ... +120 C
Operating temperature
20 C ... +70 C
Contact overtemperature
20 K
Number of cycles
30.000
Note
With the group of ten auxiliary contacts supplied as standard
and the maximum number of electrical applications, three
break contacts (signalling circuit-breaker open) and five make
contacts (signalling circuit-breaker closed) are available.
With the group of 15 auxiliary contacts, according to the
electrical applications required, the following are available:
for fixed circuit-breakers: thirteen auxiliary contacts,
differently divided between break contacts and make
contacts according to the figure selected of the electrical
diagram;
for withdrawable circuit-breakers, since the plug of the
auxiliary circuits has a limited number of poles: five break
contacts (signalling circuit-breaker open) and five make
contacts (signalling circuit-breaker closed).
58
Un
Rated current
Breaking capacity
220 V a.c.
Cosj = 0.7
2.5 A
25 A
380 V a.c.
Cosj = 0.7
1.5 A
15 A
500 V a.c.
Cosj = 0.7
1.5 A
15 A
660 V a.c.
Cosj = 0.7
1.2 A
12 A
1 ms
10 A
12 A
15 ms
10 A
12 A
50 ms
8A
10 A
200 ms
6A
7.7 A
1 ms
8A
10 A
15 ms
6A
8A
50 ms
5A
6A
200 ms
4A
5.4 A
1 ms
6A
8A
15 ms
4A
5A
50 ms
2A
4.6 A
200 ms
1A
2.2 A
1 ms
1.5 A
2A
15 ms
1A
1.4 A
50 ms
0.75 A
1.2 A
200 ms
0.5 A
1A
24 V d.c.
60 V d.c.
110 V d.c.
220 V d.c.
This contact closes momentarily (duration > 30 ms) on circuitbreaker opening controlled remotely with a shunt opening
release.
The indication is not provided when opening is manual and
local. In fact, a contact (BGB11) is activated by the manual
pushbutton and cuts off the transient contact closure (
BGB4).
The transient contact is activated directly from the main
operating shaft when the indication is provided only on actual
opening of the main circuit-breaker contacts.
Characteristics
Un
Un
Operating limits
85 110% Un
40 kA
50 kA
DC = 600 W;
AC = 600 VA
DC = 200 W;
AC = 200 VA
DC = 900 W;
AC = 900 VA
DC = 350 W;
AC = 350 VA
Charging time
0,2 s
0,2 s
Charging time
6-7 s
6-7 s
Insulating voltage
2000 V 50 Hz
(for 1 min)
2000 V 50 Hz
(for 1 min)
60
61
62
Characteristics
Un
Un
Operating limits
85 110% Un
DC 250 W; AC = 250 VA
DC = 5 W; AC = 5 VA
Inrush duration
150 ms
Insulating voltage
63
64
Un
24 - 30 - 48 - 60 - 110 - 220 V
Operating limits
85 110% Un
40 W
6A
250 V AC
65
Resistance to vibrations
Altitude
The VD4 circuit-breakers are designed to satisfy high levels of
resistance to stresses caused by mechanical vibrations.
Many versions are able to satisfy both the approval criteria of the
major International Shipping Registers (DNV, Lloyds Register,
RINA) and the qualification criteria of the International Seismic
Standards (IEEE 344, IEEE 323 and IEC 60980).
For the versions approved by the shipping registers, please
contact us.
Tropicalization
66
kA
1,50
m=1
Ka = e m (H 1000)/8150
1,40
1,30
1,10
1,20
1,00
1000
1500
2000
2500
3000
3500
4000 H
H = altitude in metres;
m = value referred to power frequency and the lightning impulse withstand
voltages and those between phases.
Anti-pumping device
The EL operating mechanism of VD4 circuit-breakers
(in all versions) is fitted with a mechanical anti-pumping
device which prevents re-closing due to either electrical or
mechanical commands.
Should both the closing command and any one of the
opening commands (local or remote) be active at the same
time, there would be a continuous succession of opening and
closing commands.
The anti-pumping device avoids this situation, ensuring
that each closing operation is only followed by an opening
operation and that there is no other closing operation
after this. To obtain a further closing operation, the closing
command must be released and then re-launched.
Furthermore, the anti-pumping device only allows circuitbreaker closure if the following conditions are present at the
same time:
operating mechanism spring fully charged
opening pushbutton and/or shunt opening release
(-MBO1/-MBO2) not activated
circuit-breaker open.
67
68
Spare parts
Ordering
For availability and to order spare parts, please contact our
Service department, specifying the circuit-breaker serial
number.
69
4. Overall dimensions
Fixed circuit-breakers
450
kA
25
kA
31.5
kA
205
kA
20
52
16
115
451
1250
65
32
65
kV
630
205
17.5
PT1 POLES
95
56
Isc
kV
461
Ir
12
30
16
Ur
P1 POLES
95
248
7405
435
56
TN
52
VD4
236
28
49
25
28
45
400
45
114
424
12
424
45
150
22
22
150
250
409
161
22
22
12
22
kA
20
kA
25
kA
31.5
kA
296
28
49
25
520
45
22
45
12
22
22
210
160
345
28
250
424
44
114
22
12
409
424
22
16
52
1250
205
210
70
PT1 POLES
95
451
630
115
65
kV
205
kV
17.5
30
16
12
24
Isc
32
461
Ir
P1 POLES
7406
435
56
Ur
95
52
308
VD4
TN
65
Fixed circuit-breakers
45
Fixed circuit-breakers
700
1250
16
kA
20
kA
25
kA
31.5
kA
95
32
205
475
25
650
28
49
275
52
65
24
14
236
451
115
461
16
205
65
kV
630
97
Isc
17.5
30
Ir
kV
95
171
Ur
12
PT1 POLES
P1 POLES
373
1VCD000051
435
56
TN
52
VD4
424
28
345
45
44
250
409
424
12
114
275
213
22
22
22
22
45
22
12
45
Fixed circuit-breakers
210
210
475
589
310
28
28
49
520
45
160
44
345
250
409
424
45
114
12
12
20
20
1111
20
11
20
1111
11
11
44
12
26
114
PT2 Pole
P3 Pole
11
345
250
409
424
12
296
77.5
24
77.5
24
238
kA
475
40
310
1600
589
PT2 Pole
238
kV
1250
16
17.5
56
Isc
kV
171
Ir
12
P3 Pole
30
Ur
95
1VCD003282
435
TN
95
308
12
570
VD4
71
4. Overall dimensions
Fixed circuit-breakers
310
238
36
28
28
49
77.5
77.5
361
45
250
345
424
650
25
275
275
475
589
475
kA
24
40
310
1600
PT2 Pole
589
238
kV
1250
30
kV
17.5
171
Isc
12
16
Ir
1VCD003285
435
Ur
95
P3 Pole
56
TN
95
373
24
700
VD4
45
114
44
12
250
345
424
114
44
12
213
PT2 Pole
20 20
P3 Pole
11
11 11
12
12
11 11
22
12
11
20 20
11
11
Fixed circuit-breakers
600
VD4
12
20
77.5
2.5
40
135
116
165
28
28
520
31
172
142
404
428
210
12
22
210
72
20
kA
24
50
12
2000
20
475
2.5
1600
20
310
74
32
610
1250
4xM12 deep 25
2xM10 deep 20
237
kV
171
Isc
kV
17.5
16
Ir
12
459
130
300
30
Ur
323
1VCD003440
435
56
TN
156
Fixed circuit-breakers
750
20
kA
20
50
12
2500
475
2000
20
78
24
24
1600
20
310
74
610
1250
2xM10 deep 20
32
237
kV
375
16
17.5
4xM12 deep 25
130
171
Isc
kV
30
Ir
12
435
Ur
1VCD003441
56
TN
459
398
12
VD4
28
116
69.5
28
165
30.5
2.5
2.5
135
270
689
225
64.7
404
275
31
275
24
428
12
22
12
Fixed circuit-breakers
450
VD4
97
171
14
435
20
20
kA
12
kA
31.5
12
25
475
kA
236
345*
28
45
49 28
25
250
44*
114
12
409
400
150
DETAIL A
SCALE 1 : 2 . 5
56
20
4XM12 PROF.25
310
77,5
1600
20
2XM10 PROF.20
599
Ir
20
32
237,5
kV
16
12
30
1VCD000050
Ur
56
TN
Isc
95
248
424
150
12
22
161
73
4. Overall dimensions
Fixed circuit-breakers
VD4
570
kA
VD4
TN
7407
Ur
12
kV
Ir
2500
20
kA
25
kA
31.5
kA
40
kA
Isc
20
310
20
20
20
11 11
12
kA
40
12
12
31.5
160
20
kA
210
11 11
25
210
44
250
409
424
20
kA
345
20
20
45
20
Isc
2000
28
28
49
520
12
22
Ir
296
25
12
12-17.5 kV
12
7407
Ur
24
TN
77.5
77.5
VD4
77.5
kA
589
kA
31.5
237.5
25
Isc
310
kA
616
20
32
237.5
475
1600
310
Ir
95
599
12-17.5 kV
95
237.5
Ur
95
308
30
16
7407
435
56
TN
Fixed circuit-breakers
700
VD4
kV
17.5
kV
1600
20
kA
25
kA
31.5
kA
Isc
kA
25
kA
31.5
kA
40
kA
74
237
475
616
599
310
599
78
11 11
20
12
20
20
20
12
2500
24
20
20
11 11
2000
213
20
kV
44
12
114
20 20
kV
17.5
345
250
409
424
45
12
12
28
28
650
12
Ir
49
25
22
Ur
361
7408
12
VD4
TN
95
171
Isc
12
16
Ir
95
32
30
Ur
95
373
7408
435
56
TN
Fixed circuit-breakers
VD4
20
20
20
12
310
635
475
5
th 2
dep
12
4xM
2,5
77,5
A (1:4)
25
2
th
24
kA
237
40
16
kA
30
31.5
171
kA
ep
kA
25
2d
20
M1
kV
kV
A
20
4x
Isc
12
17.5
3150
20
307
435
Ir
1VCD000149
32
Ur
95
56
TN
424
373
28
49
142
28
361
650
45
700
345
44
250
114
409
412,5
424
137,5
12
22
213
Fixed circuit-breakers
50
kA
20
20
30
2,5
116
30,5
69,5
28
689
31
270
404
428
64,5
225
24
275
12
275
22
172
28
165
2,5
24
171
237
435
56
135
24
Isc
20
A (*)
20
3150
12
Ir
74
32
475
kV
310
kV
17.5
189
130
636
12
Ur
375
12
1VCD003443
4xM12 deep 25
2xM10 deep 20
240
16
TN
459
398
189
118
750
VD4
75
4. Overall dimensions
Fixed circuit-breakers
570
VD4
kA
20
kA
25
kA
115
22
22
DETAIL A
SCALE 1:2
296
28
49
25
24
77,5
171
Isc
22
16
M12 PROF.25
475
310
1250
2XM10 PROF.20
32
631
282,5
kV
630
16
24
30
Ur
45
A
435
56
7409
Ir
95
308
TN
M12
345*
28
45
250
409
424
520
210
39*
114
12
210
160
Fixed circuit-breakers
570
95
308
85
VD4
4XM12 DEEP25
31,5
kA
22
72
24
DETAIL A
SCALE 1:2
77,5
170
282,5
435
Isc
45
296
28
49
25
250
344,5*
409
28
424
520
210
210
160
76
72
12 12
1250
2XM10 DEEP 20
475
630
Ir
40
32
310
kV
647
24
16
Ur
31
1VCD000172
56
TN
114
39*
Fixed circuit-breakers
700
VD4
kA
22
kA
25
475
kA
20
115
28
361
49
25
424
24
16
Isc
310
M12 PROF.25
77.5
1250
32
631
282.5
630
30
kV
16
24
171
Ur
45
22
2XM10 PROF.18
435
7410
56
TN
Ir
95
373
345*
28
45
250
650
44*
114
DETAIL A
SCALE 1:2
12
409
275
275
22
12
213
Fixed circuit-breakers
20
12
361
28
49
25
28
650
20
kA
12
kA
31.5
661
kA
25
4XM12 DEEP 25
475
kA
20
DETAIL A
SCALE 1:2
24
16
20
310
77,5
2500
647
2000
282,5
1600
16
kV
20
2XM10 DEEP 20
171
24
95
44*
345*
45
250
114
409
424
275
275
213
22
Isc
95
373
30
Ir
7411
435
Ur
700
56
TN
2500A
1600-2000A
VD4
77
4. Overall dimensions
Fixed circuit-breakers
764
VD4
2000
2500
20
kA
25
kA
31.5
kA
Ir
305
Isc
612
1600
328
kV
1250
876
36
482.5
Ur
239
15.5
30
1VYN300901-LT
556
TN
28
49
28
331
447
470
786
275
478.5
275
22
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB1 modules
kA
74
503
14
29
438
661
55
608
490
39
320
370
36
501
47
25
383
417
531
78
35
P1 POLES 1250A
2
0
53
kA
31.5
91
25
78
kA
35
kA
20
98
16
627
23
1250
23
630
10
91
kV
79
17.5
306
35
kV
674
125
12
78
12
66
P1 POLES 630A
Isc
7412
19
Ir
43
619
Ur
233
626
TN
127
492
VD4/P
kA
31.5
kA
688
kA
25
35
20
303
71
38
650
25
18
19.5
14
653
21.5
76
kA
310
16
280
1250
36
165
28
691
630
36
31
kV
111
62.5
16
kV
17.5
119
28
213
Isc
12
688
Ir
230
49
56
Ur
7420
691
TN
44
VD4/W
320
359.5
640
370
626
383
550
416
53
642
210
38
48
111
119
589
55
210
12
kV
36
28
17.5
kV
1250
1600
40
kA
111
17
62.5
79
688
16
303
71
18
25
320
165
650
359.5
640
370
626
383
552
210
416
210
38
76
19.5
14
21.5
653
214
280
56
30
310
37
53
587
55
640
640
38
53
Isc
28
688
Ir
49
691
Ur
125
230
1VCD003284
TN
44
VD4/P
79
4. Overall dimensions
122
122
688
310
79
688
71
416
850
36
836
25
57
146
53
25
320
29
360 2
370
383
550
36
550
806
750
19.5
320
360 2
370
383
21.5
25
29
38
14
853
38
280
71
25
kA
19.5
40
75
1600
21.5
1250
416
53
640
640
275
38
53
586
55
275
688
478
14
19
12
4
605
653
650
640
626 2
550
14
26
25
kA
122
50
19,5
2000
303
360
590
12
23
320
29
360+2
34
383
370
554 1,5
643
210 1
29
210 1
25
416
36
80
433
20
79
16
76
1600
21,5
310 1
kV
1250
119
111
25
280 1
Isc
kV
17.5
220
165 1
Ir
12
636
44
691
Ur
135
1VCD 003444
688
TN
10
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB2 modules
VD4/P
17
303
303
310
kV
17
111
280
Isc
kV
17.5
230
79
Ir
12
119
111
119
144
164
Ur
842
1VCD003286
690
688
TN
VD4/P
49,5
53
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB2 modules
653
14
VD4/P
TN
7415
kV
17.5
kV
Ir
2000
Isc
40
kA
122
688
310
320
29
360 0
370
383
416
36
25
320
29
53
36
550
550
360 0
370
383
416
53
639
639
550
210
25
640
626
38
210
53
38
586
55
Ur
25
650
12
79
kA
71
38
280
31.5
71
164
75
kA
36
kA
25
18
688
20
25
310
2000
119
303
79
1600
111
62,5
PT2 POLES
303
36
280
kV
Isc
kV
17.5
17
165
76
Ir
12
119
111
62,5
P2 POLES
Ur
7415
233
691
688
TN
636
44
122
VD4/P
853
VD4/P
850
836
7416
kV
Ir
2000
Isc
40
kA
750
275
10
122
8
550
639
688
79
25
75
320
25
29
359
34
53
36
0
2
370
383
416
53
550
638,5
275
55
17.5
Ur
38
kV
320
360 2
370
383
416
34
36
806
587
12
25
29
38
53
TN
14
21,5
kA
310
kA
31.5
71
38
280
25
71
164
kA
688
20
25
2000
21,5
303
79
1600
119
110
110
303
310
kV
Isc
kV
17.5
280
Ir
12
230
165
76
Ur
7416
119
144
692
688
TN
842
122
VD4/P
81
4. Overall dimensions
850
836
36
806
25
320
29
360
370
383
416
550
638
2
0
109
688
71
25
38
75
164
53
25
320
29
360
370
383
417
550
638
36
750
2
0
53
275
53
38
585
55
275
17
303
24
14
119
111
158
152
853
38
310
kA
688,004
40
71
kA
25
kA
31.5
24
25
303
109
kA
17
76
20
310
280
kV
2500
165
kV
17.5
Isc
12
Ir
7417
230
688
Ur
144
692
TN
119
111
842
280
VD4/P
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB3 modules
742
kA
356
853
14
25
kA
40
166
kA
31.5
25
19,5
kA
25
52
109
20
850
836
806 2
750
29
34
2751
2751
42
587
55
29
16
8
22
38
189
12
94
302
82
17
76
A (*)
149
3150
125
111
92
86
165 1
kV
19
Isc
kV
17.5
17kV
310 1
Ir
12
280 1
Ur
1VCD000152
12kV
730
TN
230
10
842
144
VD4/W
303
320
0
360+ 2
370
382
416
5481,5
643
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB3 modules
842
VD4/P
50
kA
10
20
688
2000
433
122
79
kV
1600
16
25
76
25
19,5
165 1
21,5
14
26
805
853
850
836
806 2
750
14
12
19
280 1
478
Isc
kV
17.5
310 1
Ir
12
111
691
Ur
1VCD003445
25
688
TN
119
217,5
144
135
320
370
0
29
360 + 2
34
383
416
36
49,5
53
554 1,5
275 1
22
12
303
360
590
29
643
275 1
VD4/P
119
110
25
10
152
109
310 1
433
25
19,5
75
164 1
27
21,5
14
805
853
850
836
806 2
750
14
12
19
280 1
478
688
691
20
29
320
370
0
360+2
34
383
25
49,5
417
36
275 1
554 1,5
643
275 1
303
kA
11
50
22
Isc
A
688
2500
kV
Ir
29
kV
17.5
16
588
12
Ur
217,5
143
1VCD003446
360
TN
83
4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear
842
2
166
275 1
356
853
850
836
806 2
750
14
732
25
19,5
kA
52
21,5
40
86
109
Isc
17
76
A (*)
111
93
149
kV
3150
19
17.5
Ir
165 1
kV
310 1
12
17kV
12kV
280 1
Ur
373,5
1VCD000153
730
TN
10
VD4/P
53
0
360+2
29
370
382
416
548 1,5
34
275 1
303
320
25
42
643
12
189
22
39
96
587
55
16
8
VD4/P
kA
20
19,5
76
25
26
21,5
280 1
12
19
4
805
853
14
165 1
478
730
433
733
50
10
Isc
118
A (*)
152
3150
109
kV
Ir
16
130
310 1
kV
17.5
111
240
25
742
12
Ur
361
1VCD003447
678
TN
850
836
806 2
750
275 1
36
275 1
22
12
303
360
589
29
189
84
25
320
370
0
29
360+2
34
383
416
554 1,5
643
49,5
53
1VCD003596
50
kA
742
730
20
433
320
370
0
360+2
29
34
49,5
383
416
53
554 1,5
36
275 1
25
76
25
19,5
26
21,5
280 1
19
12
805
853
850
836
806 2
750
14
165 1
478
732
Isc
118
A (*)
152
3150
109
kV
Ir
310 1
kV
17.5
16
130
30
742
12
Ur
119
111
240
25
678
TN
361
10
842
VD4/W
643
275 1
22
12
303
360
588
29
189
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB4 modules
653
14
79
71
25
650
38
320
370
383
641
610 2
210 1
35
771
48
25
kA
1250A
72
kA
25
79
20
Isc
310 1
kA
35
16
325 1
197 1
1250
630
Ir
630A
36
458+ 2
303
710 1,5
53
799
210 1
55
kV
23
19
770
24
782
Ur
119
232
7413
746
TN
20
44
98
636
VD4/P
85
4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear
842
79
35
kA
20
kA
25
788
20
Isc
48
853
14
71
38
25
kA
1250A
72
16
197 1
310 1
1250
35
630
Ir
325 1
kV
23
19
630A
25
24
775
Ur
119
232
770
7414
79
144
TN
98
VD4/P
320
370
383
0
850
458 + 2
303
836
805 2
275 1
53
710 1,5
799
53
55
746
275 1
36
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB4 modules
636
VD4/P
44
Ur
24
kV
Ir
1250
Isc
31.5
kA
232
119
23
19
49
28
28
48
770
35
770
71
653
13.5
72
197
213
326
56
16
31
775
310
36
20
1VCD000173
79
TN
25
320
303
650
370
641
610
383
800
210
19
119
55
747
210
86
458
53
24
kV
Ir
1250
Isc
31.5
kA
23
232
49
28
28
48
1971
14
853
72
213
56,5
325 1
16
31
35
775
770
3101
36
20
Ur
144
790
1VCD000174
79
TN
98
VD4/P
850
836
805 2
36
25
320
370
383
4582
303
53
710 1,5
799
275 1
53
119
55
746
275 1
VD4/P
16
kA
20
kA
25
kA
31.5
kA
345 1
817
810
4
Isc
(1)
834
2500
853
14
45
72
2000
Ir
2500A
79
kV
1600
197 1
24
119
1600-2000A
310 1
Ur
233
25
7418
132
842
140,500
TN
20
Withdrawable circuit-breakers for UniGear ZS1 switchgear and PowerCube PB5 modules
320
370
383
850
36,011
805 2
275 1
46
303
836
458 +2
696 1,5
275 1
53
52
55
732
784
(1) The rated uninterrupted current of 2300 A is guaranteed with natural ventilation. The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.
87
4. Overall dimensions
Withdrawable circuit-breakers for UniGear ZS1 switchgear
842
1VCD000177
Ur
24
kV
3150
31.5
kA
49
28
36
28
834
233
345
56
16
31
810
817
310
Isc
233
141
166
TN
109
VD4/P
14
25
853
850
836
805
320
383
303
458
787
275
52
119
55
734
275
1600
2000
2500
A (*)
20
kA
25
kA
31.5
kA
Ir
Isc
956
973
kV
1250
198
125
36
380
1VYN300901-KG
Ur
480
TN
VD4/W
264
853
736
880
460
53
838
275
275
A
1250 A
79 mm
1600-2000-2500 A
736
35 mm
(*) The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.
88
46
370
53
12
kV
Ir
630
20
kA
25
kA
260
510
Isc
52
563
Ur
303
205
1VCD000092
35
TN
91
VD4/Z8
503
53
548
150
495
55
150
25
kA
TN
1VCD000137
Ur
17.5
kV
630
1250
20
kA
25
kA
Ir
Isc
563
kA
Isc
84
20
205
kV
1250
260
12
Ir
52
507
Ur
303
503
150
53
150
55
1VCD000137
495
TN
35
VD4/Z8
89
4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
681
24
kV
Ir
630
16
kA
20
kA
25
kA
325
563
Isc
52
680
Ur
303
35
1VCD000089
310
TN
91
VD4/Z8
210
653
53
210
583
55
640
12
kV
Ir
630
20
kA
25
kA
503
153
260
510
Isc
52
563
Ur
303
91
1VCD000093
205
TN
35
VD4/ZT8
195
486
90
380
150
640
55
584
150
53
TN
1VCD000138
Ur
24
kV
Ir
1250
16
kA
20
kA
25
kA
25,5
325 1
35
677
Isc
50
310 1
VD4/Z8
210 1
548 0,5
53
587
210 1
587
55
640
kV
Ir
1250
20
kA
25
kA
VD4/ZT8
1VCD000134
Ur
17.5
kV
630
1250
20
kA
503
25
kA
486
150
195
383
53
637
150
55
Isc
583
Ir
260
TN
52
153
Isc
303
563
12
98
Ur
35
1VCD000134
514
TN
205
VD4/ZT8
91
4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
681
636
VD4/ZT8
24
kV
Ir
630
16
kA
20
kA
25
kA
611
325
563
Isc
52
680
Ur
303
310
1VCD000090
35
TN
210
195
653
636
53
380
210
585
55
640
VD4/ZT8
24
kV
Ir
1250
16
kA
20
kA
25
kA
611
325
563
677
Isc
52
84
Ur
303
35
1VCD000136
310
TN
210
653
636
195
380
210
92
55
587
640
53
20
kA
25
kA
86
153
260
510
Isc
69
503
195
53
380
486
150
640
67
584
55
150
563
kV
630
12
Ir
52
524
Ur
303
205
1VCD000091
35
TN
91
VD4/ZS8
563
524
98
35
205
153
kA
514
kA
25
Isc
260
20
69
kV
1250
52
195
503
380
150
53
637
486
150
55
12
Ir
303
86
Ur
583
1VCD000133
67
TN
VD4/ZS8
93
4. Overall dimensions
Withdrawable circuit-breakers for ZS8.4 switchgear
681
636
24
kV
Ir
630
16
kA
20
kA
25
kA
611
86
325
524
563
Isc
52
680
Ur
303
310
1VCD000088
35
TN
91
VD4/ZS8
69
653
636
195
210
67
583
55
210
53
380
640
VD4/ZS8
kV
1250
16
kA
20
kA
25
kA
86
325
524
677
Isc
611
69
653
636
195
380
640
67
94
210
55
587
210
53
563
24
Ir
52
84
Ur
303
35
1VCD000135
310
TN
1250
16
kA
20
kA
25
kA
Ir
48
3251
Isc
35
kV
630
1250A
121
435,5
24
630A
570
79
Ur
626
3101
1VCD000047
35
TN
25
38
25
653
650
36
53
6501,5
742
2101
55
2101
320
370
383
303
14
35
42
38
9
653
25
320
370
383
303
415
14
650
648 1.5
742
210 1
23
36.3
kA
739
20
435 1
kA
Isc
18
16
79
1250
Ir
1250A
310 1
kV
630
35
24
121 1
41
325 1
Ur
1VCD000190
149
53
DETAIL A
210 1
55
TN
630A
45
626 1
604
VD4/Sec
95
96
Thermal effect
Mass, frame
Capacitor (general
symbol)
Electromagnetic effect
Conductors in shielded
cable (two conductors
shown)
Motor
(general symbol)
Timing
Connection of
conductors
Opening position
contact (limit switch)
Pushbutton control
Terminal or clamp
Make contact
Power circuit-breaker
with automatic opening
Key control
Break contact
Control coil
(general symbol)
Earth
(general symbol)
Resistor
(general symbol)
Change-over break
before make contact
Lamp
(general symbol)
97
98
99
Caption
*
-BER
100
Incompatibility
The circuits indicated in the following figures cannot be
supplied at the same time in the same circuit-breaker:
5-6-66
7-67
9-69
31-91
32-92
33-93
10-11
Notes
A) The circuit-breaker is equipped solely with the applications
specified in the order confirmation. Consult this catalogue
for information about how to make out an order.
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuitbreaker or from an independent source.
Circuit-breaker closing is only allowed when the release
is energized (closing lock is obtained mechanically). If
there is the same power supply for the shunt closing and
under-voltage releases and the circuit-breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage release's
enabling instant and energizing of the shunt closing
release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether several
motors for loading the closing springs can be operated
at the same time. To prevent excessive power draw, the
springs must be loaded by hand before the auxiliary circuit
is powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases.
-MBO4 incompatible with -MBU.
-MBO4 not available for VD4 50 kA.
101
102
103
104
Caption
*
-BER
105
Incompatibility
The circuits indicated in the following figures cannot be
supplied at the same time in the same circuit-breaker:
5-6
106
10-11
32-33-34-35
70-71 -72-73
Notes
A) Circuit-breaker is equipped solely with the applications
specified in the order confirmation. Consult this catalogue
for information about how to make out an order.
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuitbreaker or from an independent source.
Circuit-breaker closing is only allowed when the release
is energized (closing lock is obtained mechanically). If
there is the same power supply for the shunt closing and
under-voltage releases and the circuit-breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage release's
enabling instant and energizing of the shunt closing
release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether several
motors for loading the closing springs can be operated at
the same time. To prevent excessive power draw, springs
must be loaded by hand before auxiliary circuit is powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases.
E) When fig. 6 is required, contact -BGB3 (41-42) of fig. 32-33
is not available and fig. 34-35 cannot be supplied.
When fig. 9 is required, contact -BGB1 (43-44) of fig. 31 is
not available.
F) Only available for 31.5 kA.
107
108
109
110
Caption
*
-BER
-BGB1
-BGB4
-BGB6
-BGB11
-BGD1
-BGS1
-BGS2
-BGT1
-BGT2
-BGT3
-MAS
-MBC
-MBO1
-MBO2
-MBO3
-MBO4
-MBU
-QAB
-RLE1
-RLE2
-SFC
= Figure number of the diagram.
= See note indicated by the letter.
= SOR Test Unit device for monitoring continuity
of shunt opening and closing release winding
(see note D)
= Auxiliary contacts of circuit-breaker.
= Auxiliary let-through contact of circuit-breaker
with momentary closing during circuit-breaker
opening.
= Contact for electrical signalling of undervoltage
release de-energized.
= Contact for cutting off electrical signal -BGB4 if
opening operation is performed in the manual
mode.
= Enclosure door position contact.
= Limit contact of spring loading motor.
= Contact for signalling closing springs loadeddischarged.
= Electrical signalling contacts for circuit-breaker
in racked-in position (see note F)
= Electrical signalling contacts for circuit-breaker
in isolated position (see note F).
= Circuit-breaker position contact, open during
isolating travel.
= Motor for loading closing springs (see note C).
= Shunt closing release (see note D).
= First shunt opening release (see note D).
= Second shunt opening release (see note D).
= Opening solenoid for release outside circuitbreaker.
= Third shunt opening release (see note D).
= Under-voltage release (see note B).
= Circuit-breaker applications.
= Locking magnet. Mechanically inhibits circuitbreaker closing if de-energized. (Consumption
can be limited by connecting a delayed
pushbutton in series so as to enable the
operation).
= Locking magnet (on truck). Mechanically inhibits
circuit-breaker racking-in and isolating if deenergized. (Consumption can be limited by
connecting a delayed pushbutton in series so as
to enable the operation).
111
Incompatibility
The circuits indicated in the following figures cannot be
supplied at the same time in the same circuit-breaker:
3-4 3-33-34 4-31-32 5-6
31-32-33-34
31-32-52
33-34-51
51-52
112
10-11
Notes
A) Circuit-breaker is equipped solely with the applications
specified in the order confirmation. Consult this catalogue
for information about how to make out an order.
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuitbreaker or from an independent source.
Circuit-breaker closing is only allowed when the release
is energized (closing lock is obtained mechanically). If
there is the same power supply for the shunt closing and
under-voltage releases and the circuit-breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage release's
enabling instant and energizing of the shunt closing
release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether several
motors for loading the closing springs can be operated
at the same time. To prevent excessive power draw, the
springs must be loaded by hand before auxiliary circuit is
powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases:
-MBO4 incompatible with -MBU.
-MBO4 not available on Vmax and VD4 50kA.
E) When fig. 6 is required, contact -BGB1 (23-24) of fig. 3234 is not available.
When fig. 7 is required, contact -BGB1 (3-4) of fig. 31-3233-34 is not available.
When fig. 9 is required, contact -BGB1 (7-8) of fig. 31-3233-34 is not available.
When fig. 10 or 11 are required, contact -BGB1 (31-32) of
fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB1 (25-26) of fig. 32
and 34 is not available.
F) The contacts for electrical signalling of circuit-breaker in
isolated and racked-in position (-BGT1 and BGT2) shown
in fig. 51-52 are installed on circuit-breaker truck (movable
part).
G) Fig. 3 is supplied when fig. 31 or 32 are required.
Fig. 4 is supplied when fig. 33 or 34 are required (in this
case, it is obligatory to supply BGT3).
H) Fig. 10 is only available for VD4 up to 31.5 kA and Vmax.
Fig. 11 is only available for VD4 up to 31.5 kA.
I) The energizing voltage must be the same for both signals.
113
114
115
116
Caption
*
-BER
-RLE2
117
Fig. 8
Incompatibility
The circuits indicated in the following figures cannot be
supplied at the same time in the same circuit-breaker:
3-4 3-33-34 4-31-32 5-6
31-32-33-34
31-32-52
33-34-51
51-52
118
10-11
Notes
A) The circuit-breaker is equipped solely with the applications
specified in the order confirmation. Consult this catalogue
for information about how to make out an order.
B) The undervoltage release can be supplied for energizing
with voltage derived from the supply side of the circuitbreaker or from an independent source.
Circuit-breaker closing is only allowed when the release
is energized (closing lock is obtained mechanically). If
there is the same power supply for the shunt closing and
under-voltage releases and the circuit-breaker must close
automatically when auxiliary voltage returns, there must
be a 50 ms delay between the under-voltage release's
enabling instant and energizing of the shunt closing
release.
Incompatible with -MBO4.
C) Check power of auxiliary circuit to find out whether several
motors for loading the closing springs can be operated at
the same time. To prevent excessive power draw, springs
must be loaded by hand before auxiliary circuit is powered.
D) The circuit for monitoring the continuity of the release
windings must only be used for that purpose. The SOR
Test Unit can be used for checking the continuity of the
various different releases.
-MBO4 incompatible with -MBU.
E) When fig. 6 is required, contact -BGB3 (41-42) of fig. 3234 is not available.
When fig. 9 is required, contact -BGB1 (43-44) of fig. 3132-33-34 is not available.
When fig. 10 or 11 are required, contact -BGB3 (31-32) of
fig. 32 and 34 is not available.
When fig. 30 is required, contact -BGB3 (53-54) of fig. 32
and 34 is not available.
F) The contacts for electrical signalling of circuit-breaker in
racked-in and isolated positions (-BGT1 and -BGT2) shown
in fig. 51-52 are located on circuit-breaker truck (moving
part).
G) Fig. 3 is supplied when fig. 31 or 32 are required. Fig. 4 is
supplied when fig. 33 or 34 are required (in this case, it is
obligatory for -BGT3 to be supplied).
H) Fig. 10 is only available for VD4 up to 31.5 kA. Fig. 11 is
only available for VD4 up to 31.5 kA.
I) The energizing voltage must be the same for both signals.
119
ABB S.p.A.
Electrification Products Division
Medium Voltage Products
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874