Reliability Analysis* State Estimation * Dynamic Modelling (DSL) * System Dynamics (RMS / EMT)
Motor Starting * Real-Time Simulation* Small Signal Stability * Interfacing PowerFactory * Installation Options
Rev 1 14/4/2010
PowerFactory V14
Basic Software Features & Calculation Functions
Advanced Functions and Features
Protection Coordination * Distribution Network Optimization * Harmonic Analysis * Optimal Power Flow
Reliability Analysis * State Estimation * Dynamic Modelling (DSL) * System Dynamics (RMS / EMT)
Motor Starting * Real-Time Simulator * Small Signal Stability * Interfacing PowerFactory * Installation Options
Rev 2.30/01/2013_E
Table of Contents
Table of Contents
1 Introduction ...................................................................................................................................... 6
2 PowerFactory Overview .................................................................................................................... 8
2.1 Functional Integration and Applications ...................................................................................................... 8
2.2 PowerFactory Software Concept ................................................................................................................ 8
3 Network Models .............................................................................................................................. 11
3.1 Grid Representations and Power Equipment ............................................................................................. 11
3.2 Built-in Calculation and Integrated Modelling Functions ............................................................................. 15
3.3 Load and Generation Profiles ................................................................................................................... 15
4 Data Management ........................................................................................................................... 16
4.1 V14 Standard Data Model ........................................................................................................................ 16
4.1.1 Arrangement of Data in Project Folders ............................................................................................... 16
4.1.2 Study Time ........................................................................................................................................ 17
4.2 Data Organisation ................................................................................................................................... 17
5 Network Diagrams & Graphic Capabilities ...................................................................................... 19
6 Results and Reporting ..................................................................................................................... 22
6.1 Text Reports........................................................................................................................................... 22
6.2 Spreadsheet Reports (Tabular Views)....................................................................................................... 22
6.3 Reporting in Network Diagrams ............................................................................................................... 23
6.4 Result File Management .......................................................................................................................... 23
6.5 Plots and Diagrams ................................................................................................................................. 23
6.6 Additional Features ................................................................................................................................. 25
7 External Data Format Support ........................................................................................................ 26
7.1 Standard Data Formats ........................................................................................................................... 26
7.2 DIgSILENT Data Base Level Exchange (DGS)............................................................................................ 26
8 DPL- DIgSILENT Programming Language ....................................................................................... 27
9 PowerFactory Modes of Operation .................................................................................................. 29
9.1 Standard Windowing Mode ...................................................................................................................... 29
PowerFactory V14
Table of Contents
PowerFactory V14
Table of Contents
PowerFactory V14
Table of Contents
PowerFactory V14
1 Introduction
1 Introduction
DIgSILENT has set standards and trends in power system modelling, analysis and simulation for more than 25
years. The proven advantages of the PowerFactory software are its overall functional integration, its applicability
to the modelling of generation-, transmission-, distribution- and industrial grids, and the analysis of these grids
interactions.
Electrical grids, planning processes and operation processes are becoming increasingly complex due to market
unbundling, expansion of interconnections and distributed generation. This increases the demands on software
tools in terms of data quality, flexibility and manageability.
With PowerFactory Version 14, DIgSILENT presents a further step towards seamless integration of
functionality and data management within a multi-user environment. The building and organizing of schemes,
scenarios, versions and running arrangements has been added for improved handling.
Version 14 Key Features
DIgSILENT PowerFactory is the most economical solution, as data handling, modelling capabilities and overall
functionality replace a set of other software systems, thereby minimizing project execution costs and training
requirements. The all-in-one PowerFactory solution promotes highly-optimized workflow.
PowerFactory V14
1 Introduction
DIgSILENT PowerFactory is easy to use and caters for all standard power system analysis needs, including highend applications in new technologies such as wind power and distributed generation and the handling of very
large power systems. In addition to the stand-alone solution, the PowerFactory engine can be smoothly
integrated into GIS, DMS and EMS supporting open system standards.
PowerFactory V14
2 PowerFactory Overview
2 PowerFactory Overview
2.1 Functional Integration and Applications
Implemented as a single software solution allowing for fast 'walk around' through the database and
execution environment
No need to reload modules and update, transfer and convert data and results between different program
applications
Vertically integrated power equipment model concept allowing models to be shared by all analysis
functions
Smart Grid modelling including virtual power plants and distributed generation such as PVpanels, micro turbines, battery storage, CHP, etc.
Optimal data organization and project definitions for performing any type of calculation, storage of
settings, diagrams and visualization options or software operation sequences.
No need for tedious organization of several files for defining the various analysis aspects and project
execution workflows.
Database environment fully integrates all necessary data, such as that required for defining cases,
scenarios, variants, single-line graphics, outputs, run conditions, calculation options, graphics or userdefined models. Saving a project includes everything required to rerun all defined cases at a later stage.
Access to all data via a comfortable and powerful data manager, object browser, plus various types of
diagrams and wizards.
PowerFactory V14
2 PowerFactory Overview
User Roles
Folder sharing between users with read-only access. This is especially useful for libraries and network
base cases which should be administrated only by authorized personnel.
Support of user accounting, access rights and data sharing, featuring the powerful option of allowing
several users to work on the same project in a coordinated way. This demonstrates the concept of nonredundant data management in PowerFactory..
Management of multi-user data editing via the definition of a base project, project versions and derived
projects (virtual projects).
Activation of network stages according to study time. This automatically addresses the handling of
power system components according to their commissioning and de-commissioning dates
Multi-Level Models
Data describing network models such as cables, machines, loads, transformers, etc., are subdivided into
element data and type data which point to libraries.
All data to be entered are grouped into basic data (data required for all calculations) and function level
data (data required only for executing specific calculations).
Data are simply entered in physical quantities rather than in per unit values, minimizing the need for
manual recalculation and conversion of data.
PowerFactory V14
2 PowerFactory Overview
Integrated calculators for asynchronous machines, cable data and tower configurations
Various communication features to exchange data with other applications such as GIS, SCADA and realtime control systems via OPC, shared memory, DGS (CSV, ODBC), etc.
Hybrid operation switching between background and windowing mode according to users needs
Data exchange via CIM, PSS/E, UCTE and many other file formats
PowerFactory V14
10
3 Network Models
3 Network Models
3.1 Grid Representations and Power Equipment
Grid Models
Meshed and radial AC systems with 1-, 2-, 3-, and 4-phases
Phase Technologies
Substations
Simple terminal models to be used for node and branch representation, marshalling panels,
terminal blocks, terminal strips, clamping bars, joints and junctions.
Complex substation models with the provision of various standard busbar configurations such as
single- and double busbars with/without tie-breakers, bypass busbars, 1 busbar systems and
flexible busbar configurations according to user-specific needs.
Templates for holding any type of user-specific busbar configuration, including pre-configured
protection schemes
Static generator (for PV, fuel cell, wind generator, battery storage, etc.)
PowerFactory V14
11
3 Network Models
External grid
AC voltage source
AC current source
Loads
Complex load model (for feeders with a large number of induction motors)
Low voltage load (can be assigned across line and cable sections)
Branch models
Overhead line and cable models (-models and distributed parameter models)
DC Models
DC/DC converter
Inductive DC-coupling
PowerFactory V14
12
3 Network Models
Softstarter
Load-Break-Disconnector
Load-Switch
Grounding Switch
Fuse
Surge arrester
Composite Models
Parameter characteristics
PowerFactory V14
13
3 Network Models
Controllers
Operator, owner
Boundaries
Operational Library
CB ratings
Thermal ratings
Library of faults/contingencies
Others
Manufacturer-specific relay library with relay models from all major manufacturers
PowerFactory V14
14
3 Network Models
PowerFactory supports 500 different objects for defining, organizing and storing users grid definitions and project
settings. The above-listed objects are a summary of those most frequently used.
Support of two different parameter input modes: (a) electrical parameters and (b) slip-torque/current
characteristic
When entering electrical parameters, such as the rated mechanical power, stator resistance and
reactance, magnetisation reactance, etc., all electrical parameters which precisely define and describe
the asynchronous machine are then calculated. This includes the determination of the torque-/speed
characteristic.
The alternative definition via the slip-torque/current characteristic requires entering data such as
characteristics at nominal operation point, torque at stalling point, locked rotor torque and other
parameters typically available from manufacturer handbooks or test reports. This alternative data
entering method will then determine the electrical machine parameters.
Load and generator parameter characteristics can be defined on a per-element basis for parametric
studies. Parameter characteristics can be imposed on each input parameter. They may be timedependent, refer to predefined discrete cases, or result from external sources.
All operational data (generation and demand patterns, switch positions, etc) can be saved and
maintained in distinct Operation Scenarios.
PowerFactory V14
15
4 Data Management
4 Data Management
4.1 V14 Standard Data Model
4.1.1 Arrangement of Data in Project Folders
All data required for grid modelling, project organization and project execution are arranged in project folders.
Project data are structured into Libraries, Network Models, Operation Scenarios and Study Cases.
Libraries
Libraries contain equipment types, special operation information, DPL scripts, templates and userdefined models.
The Equipment Type Library can store manufacturer and standard data for cables, conductors, circuit
breakers, transformers, motors, generators, protection devices, PV panels, converters, wind turbines,
etc.
Operational Libraries help organize standard settings and operational structures of grids. Typical entries
include specific device Mvar limits and capability curves, outages, fault conditions and sequences,
specific thermal ratings, running arrangements, etc.
Network Models
All network data are organized and stored in various folders such as grid- and area folders, folders for
boundaries, circuits, feeders, routes, zones, etc.
Comprehensive network topology handling defining: Nodes, Substations, Sites, Boundaries, Circuits,
Routes, Operators and Owners.
Graphical information such as overview diagrams, simplified single line diagrams and detailed single line
diagrams are automatically organized in a separate diagram folder
Grid Variations are linked to the original grid data, allowing non-redundant grid variation
management.
Planned grid expansions are organized by time-stamped Expansion Stages which are considered
depending on the selected Study Time. Expansion Stages are stored in Variations and handled via the
Variation Scheduler. In other words, variations can be seen as expansion plans composed of
different stages which are activated chronologically.
PowerFactory V14
16
4 Data Management
Operation Scenarios
Definition of operation and dispatch conditions, grid loading, ambient temperature, daily load variation
pattern, etc
Organisation of characteristics to generate ranges of values such as daily load curves, temperature
dependencies, wind conditions, solar radiation pattern, etc
Study Cases
Grid configurations, operation conditions, trigger settings, calculation options, fault sequences, results
and DPL scripts to be executed are all stored in Study Cases
Study Cases can be activated to reproduce any grid condition and its associated calculation results
The Study Time automatically determines which expansion stages of a variation will be considered.
Selection of Study Time along with the operational conditions will automatically create grid expansion
scenarios
Rollback functions allow a controlled Undo of a projects execution steps, thereby rolling back to a
specific stage of the project
PowerFactory V14
17
4 Data Management
Derived Projects
Derived Projects are virtual copies of a Version of a Master Project that can be developed by any
number of users simultaneously. Only the differences to the original version are stored
The users will be automatically notified if a new version of their Master Project is available
Comprehensive tools for merging several derived projects and/or their versions into a new project via
the Merge Tool. This allows the consolidation of independent and parallel model modifications
introduced by different users.
PowerFactory V14
18
Simplified Single Line Diagrams with various options for a schematic view of substation topology
and switching status
Detailed Single Line Diagrams showing all switches (circuit breakers and disconnectors)
Intelligent Overview Diagrams providing a node and branch representation of the network. Can be
schematically, geographically or semi-geographically arranged
General Features
Handle mixed representations of Detailed Single Line Diagrams, Simplified Single Line Diagrams and
Overview Diagrams
Access equipment editing menus in the single line diagram via cursor selection of the appropriate
element, region or composite model
Initiate calculation events directly within the graphical environment, including circuit breaker switching,
fault implementation and other data changes
Display any calculation results immediately in result boxes in single line diagrams. All program variables
and signals can be displayed according to a highly flexible user definition for various object categories
and analysis functions
Display any calculation result to be defined on various functional levels and categories for any object
View and operate several graphic windows with different layers and grid sections simultaneously. Utilize
several graphical representations of the same system simultaneously.
PowerFactory V14
19
Placement of user-definable icons as buttons for executing DPL scripts. This way users can create
custom panels of frequently-executed DPL-initiated commands.
Provision of various colouring modes according to topology criteria such as areas, zones, owners,
operators, routes, station connectivity, energizing status, boundaries/interior regions, isolated grids, etc.
Colouring options to display voltage levels, equipment loading and operation ranges
Display of grid modifications and variants, recording of expansion stage modifications, missing grid
connections
User-definable Symbols
Support of user-definable symbols based on standard graphical formats (.wmf,.bmp). E.g. use your own
symbols for wind turbines, PV panels, hydro units, etc.
Define specific graphical representations for transformers, shunts, circuit breakers, isolators to fit
individual needs.
Composite Graphics
Elements can be grouped together and stored as Composite Graphics. Typical applications are
standard busbar arrangements, switchboard configurations, HVDC structures, PV panels, typical wind
turbine configurations or complete wind parks.
Composite Graphics can be easily handled via the Template Manager. Templates can be populated
with type and element data. For drawing Composite Graphics, the Template Manager is operated as
Drawing Tool Box.
Virtual Instruments
DIgSILENT PowerFactory applies the concept of Virtual Instruments (VI) as a tool for displaying any
calculated result or variable.
Results may be displayed in the form of bar graphs, plotted curves, or even tables of values, with all of
these representations being completely user-definable.
PowerFactory V14
20
VIs are used to display protection curves, harmonics analysis results or to view electrical variables from
any location in the network single line diagram, and any model variable during RMS and EMT
simulations.
Many VIs provide additional built-in functionality such as curve labelling and measuring, scaling, curve
fitting, filtering and digitizer functions.
Curve-digitizing diagram
Text label
PowerFactory V14
21
Automatic reports for documentation of network components, such as transformers, lines, generators, relay
settings, etc.
Flexible selection of calculation module, e.g. report only input data required for load flow and shortcircuit
Numerous predefined spreadsheet reports for all key calculation functions via Flexible Data Pages
User-definable setup of Flexible Data Pages. Tabular view of any combination of input parameters/
calculation results
Several Flexible Data Page definitions (variable selections) may exist concurrently
Output facilities to: Output window, clipboard and clipboard with column headers for use in spreadsheet
programs such as MS Excel
PowerFactory V14
22
Concept of result boxes in network diagrams to flexibly display any element/type parameter, as well as
any calculation result
Output window
Clipboard (compatible with spreadsheet programs such as MS EXCEL)
Text file (compatible with spreadsheet programs such as MS EXCEL)
COMTRADE (for transient data)
PowerFactory measurement file (ASCII)
DIgSILENT PowerFactory applies the concept of Virtual Instruments (VI) as a tool for visualizing
calculation results as plots and diagrams.
Many VIs provide additional built-in functionality such as curve labelling and measuring, scaling, curve
fitting, filtering and digitizer functions.
PowerFactory V14
23
Harmonics
-
Protection
-
Time-overcurrent diagrams
Time-distance diagrams
Relay characteristic diagram
Additional diagrams for results of load flow, short circuit, harmonics, etc.:
-
Bar diagrams
Vector diagrams
Path diagram
x-y diagrams
Eigenvalue calculation
-
Measurement VIs
-
Digital display
Metering device (vertical/horizontal scales)
Combination of both
Picture box for displaying graphic files. Supported file formats are:
-
Eigenvalue diagram
Phasor diagrams and bar diagrams (controllability, observability, participation)
Curve-digitizing diagram
PowerFactory V14
24
Printing or plotting to any device supported by the Windows Print Manager to produce high quality
graphical documents from within the program.
Conversion of graphic files between several file formats such as *.png, *.dxf, *.gif, *.tiff, *.eps, etc. This
is achieved via an external tool which is shipped with PowerFactory.
PowerFactory V14
25
NEPLAN (BCP)
NETCAL (STZ Konstanz), NEPS ( I+P Consult) and ReticMaster (Inspired Interfaces)
Import and export of complete network models as well as incremental data for updating existing models
File formats supported: ASCII Text (CSV), XML, MS-Excel and MS Access
Available for PowerFactory Interactive Window Mode and PowerFactory Engine Mode
PowerFactory V14
26
Parametric sweep calculations (e.g. sliding fault location, wind profile load flows)
Implementation of user-specific commands (e.g. transfer capability analysis, penalty factor calculation)
Report generation
The DPL object-oriented scripting language is intuitive and easy to learn. The basic set of commands includes:
New: Calling of external libraries (DLLs) for linking and executing other applications
PowerFactory V14
27
Easy Development
DPLs basic syntax allows for the quick creation of simple high-level commands to automate tasks. Such tasks
may include renaming objects, search and replace, post-processing calculation results and creating specific
reports.
Transparency
All parameters of all objects in the network models are accessible. DPL can be used to query the entire database
and to process all user-input and result parameters without restrictions.
Standardizing Commands
The DPL language can be used to create new 'standardized' DPL commands that can be used over and over
again. DPL commands allow input parameters to be defined, and can be executed for specific selections of
objects. Proven DPL commands can be safely stored in DPL command libraries and be used from there without
the risk of damaging the scripts.
Control
DPL commands can configure and execute all PowerFactory commands. This includes not only the load flow and
short-circuits calculation commands, but also the commands for transient simulation, harmonic analysis, reliability
assessment, etc. New objects can be created by DPL in the database, and existing objects can be copied,
deleted and edited. New reports can be defined and written to the output window; new graphs can be created
and existing graphs can be adjusted to reflect a user-defined selection or the current calculation results.
Modularity
A DPL command may contain other DPL commands as subroutines. This modular approach allows the execution
of subroutines as independent commands. Existing commands can be combined to quickly create more complex
commands.
PowerFactory V14
28
Bi-directional, high-speed exchange of data via DIgSILENT Shared Memory Interface or via OPC
(OLE for Process Control). When using OPC, PowerFactory is executed as an OPC-Client.
Temporary activation/popup of the Windowing Mode featuring interactive windowing operation until
the windowing mode is closed and the engine mode resumes (Hybrid Operation Mode).
In principle, a number of additional application features may be operated as background processes in situations
where it is integrated into GIS/NIS or SCADA systems or linked with other simulation tools such as
Matlab/SIMULINK, ASPENTECHs process simulation tool or other software systems requiring interaction with
network analysis procedures. The engine mode also features parallel processing with other PowerFactory
processes.
The Engine Mode permits the remote control of all PowerFactory functions with fast data and execution
command exchange.
Hybrid operation mode is supported by activating the Windowing Operation mode for combined operation.
PowerFactory V14
29
Any combination of meshed 1-, 2-, and 3-phase AC and/or DC systems can be represented and solved
simultaneously, from HV transmission systems, down to residential and industrial loads at LV voltage
levels. Neutral conductors can be modelled explicitly.
The Load Flow tool accurately represents unbalanced loads, generation, grids with variable neutral
potentials, HVDC systems, DC loads, adjustable speed drives, SVSs and FACTS devices, etc., for all AC
and DC voltage levels.
DIgSILENT PowerFactory offers a new, intuitive and easy-to-use modelling technique which avoids the
definition of bus types such as SL, PV, PQ, PI, AS, etc. PowerFactory simply provides the control
mechanisms and device characteristics which are found in reality.
Consideration of reactive power limits: detailed model for generator Mvar capability curves (including
voltage-dependency).
Practical station control features with various local and remote control modes for voltage regulation and
reactive power generation. Reactive power is automatically adjusted to ensure that generator output
remains within its capability limits.
Various active power control modes, e.g. as dispatched, according to secondary or primary control, or
inertial response.
Supports device characteristics, such as voltage-dependent loads and asynchronous machines with
saturation and slip dependency, etc.
Comprehensive area/network power exchange control features using Secondary Controllers (SCO) with
flexible participation factors.
PowerFactory V14
30
Transformer OLTC able to control local or remote bus voltages, reactive power flows and voltage-drop
compensation (LDC) within distribution systems. Special transformer controller model for parallel
transformers. Transformer tap adjustment supports discrete and continuous methods.
Device controllers for shunts, doubly-fed asynchronous machines and other power electronics elements
such as self-commutated converters (VSC), thyristor/diode converters or integrated FACTS devices.
Local and remote control mechanisms for SVCs. Automatic and continuous control of TCR and TSC
switching is performed within component ratings to hold the voltage at a given value.
Shunts can be modelled to consist of a combination of series and/or parallel connected capacitors,
reactors and resistors. Shunts can be connected to busbars and feeders or to the remote ends of cables
and lines. Filters may consist of any number of shunt combinations, and automatic shunt switching can
be included in the automatic voltage regulation.
Support of the Virtual Power Plant model for generator dispatch based on merit order algorithm.
Feeder load scaling to control power flows at feeder entry point including nested and parallel feeders.
Full support of any parameter characteristic and scale to allow parametric studies or easy definition of
loading scenarios or load profiles.
All operational data (generation and demand patterns, switch positions, etc) can be saved and
maintained in distinct Operational Scenarios.
Calculation of Load Flow Sensitivities. Evaluation of expected active/reactive power flow and voltage
changes in the network based on the effect of demand/generation or transformer tap change.
Support of DPL scripts; e.g. to perform load balancing, determination of penalty factors or any other
parameter required.
Implicit calculation of a large number of individual result variables and summary figures
Display of any variable within the single line graphic, station diagram, and a tabular Flexible Data Page
PowerFactory V14
31
Various colouring modes for the single line graphic to visualize quantities such as calculated loading
and/or voltage levels
Detailed analysis reporting, which can list overloaded system elements, unacceptable bus voltages,
system islands, out-of-service components, voltage levels, area summaries, and more
PowerFactory V14
32
11 Fault Analysis
11 Fault Analysis
DIgSILENT PowerFactory features fault calculation functionality based on international standards as well as the
most accurate DIgSILENT General Fault Analysis (GFA) method.
The following features and options are supported by all implemented fault analysis methods:
Provision of specially designed graphs and diagrams including all quantities typically required by the
protection engineer
Thermal overloads highlighted on the single line graphic for busbars and cables, with all equipment
overloads available in a summary text report
Calculation of apparent phase impedances (magnitude and angle) at any location along a transmission
line/cable or busbar, for all branches, selected subsets thereof, or 1, 2 or 3 nodes from the faulted node
Calculation of the initial symmetrical peak current Ik" and short-circuit power Sk", peak short-circuit
current ip, symmetrical short-circuit breaking current Ib, and thermal equivalent current Ith (IEC 60909-0
2001). Both minimum and maximum short-circuit currents can also be calculated based on network
voltage c-factors
Support of all fault types (three-phase, two-phase, two-phase to ground, single-phase to ground)
PowerFactory V14
33
11 Fault Analysis
Selectable method for calculating the peak short-circuit current in meshed networks
Fault calculation can optionally include or exclude motor contribution to the fault current
Provision of specially designed graphs and diagrams required by the protection engineer for protection
coordination and design
User-defined fault impedance and pre-fault voltage can be included in the fault current calculation
Other Standards
G 74 and IEC 61363
The Multiple Fault Analysis executes a complete network analysis based on subtransient and transient
representations of electrical machines taking into account all specified network devices with their full
representation and pre-faulted load conditions.
Combination with IEC60909 principles for the calculation of aperiodic components and peak short-circuit
currents
PowerFactory V14
34
11 Fault Analysis
Calculation of any asymmetrical, single or multiple fault condition with or without fault impedance,
including single- and double-phase line interruptions.
Display of any variable within the single line graphic, station diagram and Flexible Data Page
Detailed analysis reporting, which can list overloaded system elements, unacceptable bus voltages,
system islands, out-of-service components, voltage levels, area summaries and more
PowerFactory V14
35
12 Network Reduction
12 Network Reduction
The typical application of the network reduction tool is a project where a specific network has to be analyzed but
cannot be studied independently of a neighbouring network of the same or of a higher or lower voltage level. In
this case, one option is to model both networks in detail for the calculation. However, there may be situations in
which it is not desirable to perform studies with the complete model; for example when the calculation time
would increase significantly, or when the data of the neighbouring network is confidential. In such cases it is
good practise to provide a representation of the neighbouring network which contains the interface nodes
(connection points) which may be connected by equivalent impedances and voltage sources.
The objective of Network Reduction is to calculate the parameters of a reduced AC equivalent of part of a
network, as defined by a boundary. This boundary must completely split the network into two parts. The
equivalent network is valid for both load flow and short-circuit calculations. ,Following this, a model variation can
be optionally created in the PowerFactory database, whereby the full representation of the portion of network
that has been reduced is replaced by the equivalent.
Flexible definition and maintenance of network boundaries. Various features such as colouring of
boundaries and topological checks
Support of Standard Ward (PQ-equivalent), Extended Ward (PV-equivalent) and equivalent loads
Support of short-circuit equivalents for transient, subtransient, peak-make and peak-break currents
The reduced network can be created in a network variation. This allows for simple comparison and
swapping between reduced and non-reduced cases.
Robust reduction algorithms based on the sensitivity approach, i.e. reduced network matches for the
current operating point as well as for network sensitivities
PowerFactory V14
36
PV curves can be calculated for a selected set of contingencies. Diagrams are automatically created.
PowerFactory V14
37
Sensitivity to a single busbar (calculation of the voltage sensitivities of all busbars and branch flow
sensitivities according to variations in power (P and Q) at the selected busbar).
Sensitivity to a transformer tap position change (calculation of the voltage sensitivities of all busbars and
branch flow sensitivities according to changes of a transformer/quad booster tap).
Modal analysis
- Identification of weak and strong parts of the network based on modal transformation of the
v/Q sensitivity matrix.
- Eigenvalue calculation on the v/Q sensitivity matrix, with a user-defined number of eigenvalues
to be calculated.
- Results of eigenvalues are displayed (in descending order according to magnitude), and
branch/bus sensitivities can be displayed for each mode.
PowerFactory V14
38
15 Contingency Analysis
15 Contingency Analysis
The new Contingency Analysis tool in DIgSILENT PowerFactory has been designed to offer a high degree of
flexibility in configuration, calculation methods and reporting options. Single- and multiple- time-phase
contingency analyses are available, both of which offer automatic or user-defined contingency creation based on
events, and the consideration of controller time constants and thermal (short-term) ratings.
Calculation Options for Contingency Analysis:
Single- and Multiple- Time-Phase calculations. Multiple time-phase contingency analysis facilitates userdefined post-fault actions within discrete time periods.
Ultimate Performance via Grid Computing: Possibility to perform the contingency analysis calculation in
parallel (on multi-core machines and/or clustered PCs)
User-friendly definition of contingencies (n-1, n-2, n-k, busbar) as Fault Cases supporting user-defined
events to model post-fault actions (re-switching, re-dispatching, tap adjustment, load shedding)
Clustering of Fault Cases into Fault Groups for efficient data management
Special Operational Libraries to manage Fault Cases and Fault Groups for future re-use
Automatic creation of contingency cases based on Fault Cases, considering current network topology
PowerFactory V14
39
15 Contingency Analysis
Recording of results in (sparse) result file; accessible for any kind of export and/or customer-specific
post-processing
Predefined and user-definable monitoring lists for recording of results; selection of individual
components, component classes and their associated variables to be recorded. Any available calculation
result for a standard load flow calculation is accessible during contingency analysis.
User-defined limits for recording of results (thermal loadings, voltage limits, voltage step change)
Reports:
A wide range of standard reports is available, facilitating summary views or the presentation of results on a percontingency basis:
Tracing Facilities: Use of the new Trace function to step through events in a multiple time-phase
contingency, while viewing updated results in the single-line graphic
Support of component-wise Short-Term Ratings based on pre-fault loading and post-fault time
Special Contingency Analysis toolbar for user-friendly configuration, calculation and reporting
PowerFactory V14
40
Any combination of line circuits (1-, 2- and 3-ph), neutral conductors and earth wires, with/without
automatic reduction of earth wires
A flexible definition of tower types and tower geometries, including conductor sags, allowing a multiple
combination of tower geometries and conductor types that avoids entry of redundant data
Circuit-wise, symmetrical and perfect transposition and user-defined phasing for the definition of any
non-standard transposition scheme
Solid and tubular conductor types, including sub-conductors for phase circuits and earth wires
Skin effect
Equivalent impedance and admittance matrices in natural, reduced and symmetrical components
Flexible definition of cable layouts, including conducting, semi-conducting and insulating layers
Compact and hollow core shapes, filling factor for stranded conductors
Calculation of layer impedances and admittances in natural, reduced and symmetrical components, including
sheath and armour reduction, cross-bonding
PowerFactory V14
41
Feeder Plots: Graphical display feature (Virtual Instrument, VI) to increase transparency in grid loading
and voltage profile analysis along the feeder. Displayed result variables are freely configurable. Full
interactivity is given via the VI to access all relevant data of the components belonging to the feeder.
Schematic Visualization of Feeder: Automatic generation of single line diagram to visualize components
of the feeder with distance/index view.
Feeder Load Scaling: A load flow calculation feature that allows the automatic adjustment of individual
bus loads to match a specified total feeder load. The selection of loads which are to participate in the
feeder scaling procedure is user-defined. This method allows for complex scaling scenarios with nested
and parallel feeders.
Perform a load flow analysis that considers load diversity for calculating maximum voltage drops and
maximum branch current
Perform cable reinforcement optimization to either automatically reinforce selected cables, or to provide
a report of recommendations
Perform statistical calculations of neutral currents caused by unbalanced single-phase loading and load
diversity, to represent a realistic network
PowerFactory V14
42
Power factor
In addition, the user may select one of two methods for considering the stochastic nature of loads:
Maximum current estimation (application of stochastic rules for estimating maximum branch flow and
maximum voltage drops)
The Load Flow with stochastic load modelling then provides maximum currents for each branch component,
maximum voltage drops, and minimum voltages at every bus bar..
The usual variables for currents and voltages in this case represent average values of voltages and currents.
Losses are calculated based on average values; the maximum circuit loading is calculated using maximum
currents.
User-definable library of available cable/OHL types with costs that can be used for reinforcement
Consideration of:
- Admissible voltage band limits
- Maximum voltage drop limit at the end of the feeder
- Maximum admissible Cable/OHL overloading
Calculated results: report of the recommended new cable/overhead types for lines and cost evaluation
for the recommended upgrading
PowerFactory V14
43
Automatic change of the voltage level and/or phase technology inside a pre-defined feeder
Automatic replacement of type data (for transformers, lines, loads and motors) according to preconfigurable type mapping tables including automatic creation of new compatible types if
necessary
Auto-Balancing Tool
PowerFactory V14
44
18 Protection Functions
18 Protection Functions
The basic functional model library of DIgSILENT PowerFactorys protection analysis tool has been extended to
include additional devices such as CTs, VTs, relays, fuses and more complex protection schemes including userdefined modelling capabilities. Additionally, there are specially designed interactive VIs (Virtual Instruments) for
displaying system quantities and, more importantly, for modifying protection settings in the graphical
environment. This last feature is especially useful, as coordinated settings between different protection schemes
can be modified via the cursor in the graphical environment, following which the settings in both the database
and the simulation environment are also updated.
All protective devices are fully-functional under steady-state and transient conditions, allowing device response
assessment under all possible simulation modes, including load flow calculation, fault analysis, RMS and
Instantaneous Values (EMT) simulation.
PowerFactorys main protection features are:
Accurate steady-state relay checking via short-circuit and load flow (balanced & unbalanced)
Time-overcurrent diagrams
PowerFactory V14
45
18 Protection Functions
Fuses are represented by their melting curves. It is possible to take minimum and maximum melting curves into
account.
Time-Overcurrent Relays for 1-phase, 3-phase, ground and negative sequence time over-currents.
Additionally, the relay characteristics can incorporate the following standards and solution methods:
ABB/Westinghouse CO (Mdar)
Instantaneous Overcurrent Relays for 1- phase, 3-phase, ground and negative sequence time over-currents.
Directional Relays for overcurrent, power, ground current, and any combination of time and instantaneous
overcurrent relays. Additionally, voltage and current polarization is used for the detection of negative and zero
sequence components considering also dual polarization. Optional: with voltage memory.
Distance Relays for phase, ground and zone distance protection. Provision is available for incorporating
overcurrent and under-impedance starting units (U-I or Z) as well as angle under-impedance.
Different characteristics are available for distance relay zones including:
Self-polarized
PowerFactory V14
46
18 Protection Functions
Additional devices such as: Breaker Fail, Motor Protection, Generator Protection, Differential
Protection, Reclosing Relays, Low Voltage Circuit Breakers, and Out-of-Step Relays.
In addition to these protection functions and relays, DIgSILENT PowerFactory provides further devices and
characteristics for more detailed protection system modelling, such as:
Conductor, cable damage curves, cable overload curves and inrush peak current modelling
Transformer damage curves (ANSI/IEEE Standard C57.109-1985) and inrush peak current modelling
Motor starting curves, cold and hot stall, in-rush peak current modelling, and any user-defined curves
All protection device models are implemented within the composite model frame environment. This allows users
to easily design and implement their own models, by utilizing the graphical user interface for constructing block
diagrams.
User-defined labels
Tripping times are automatically displayed for calculated currents in time-overcurrent diagrams
PowerFactory V14
47
18 Protection Functions
PowerFactory V14
48
18 Protection Functions
Kilometric method: The reach of the zones is calculated from the intersection of the given positive
sequence impedance of the lines, and the impedance characteristic of the relays.
Short-circuit method: This is the main method for checking the selectivity. Short-circuits (user-defined
fault type) are calculated along the coordination path. The tripping times for the time-distance curve are
determined using the calculated impedances. The starting signal of a relay is also considered.
A special feature of the distance protection is the consideration of blocking signals or POTT (permissive overreach transfer tripping), PUTT (permissive under-reach transfer tripping), which are also taken into account. In
addition to tripping curves of distance relays, the curves of overcurrent relays can be displayed and coordinated
in the same diagram using the short-circuit method.
Both the kilometric and the short-circuit method consider breaker opening times in the calculation of tripping
times. The breaker opening time can be optionally ignored.
PowerFactory V14
49
User-definable library of proposed capacitor candidates together with annual installation costs
Consideration of:
- Benefits due to loss reduction
- Voltage limits
- Maximum total investment costs
Calculated results: set of locations where capacitors should be installed, which type of capacitor(s)
should be installed at each site, and whether or not a switched capacitor is proposed.
PowerFactory V14
50
Heuristic algorithm which explores all potential meshes in the grid to evaluate the optimal tie-points to
open
User-definable section of the network where optimal open tie-points should be determined
PowerFactory V14
51
IT product
Harmonic losses
PowerFactory V14
52
RMS values
Unbalance factors
Flicker Assessment:
- Pst, Plt (Short-, and long-term Flicker Disturbance Factors; continuous and switching operation)
- Relative voltage change value
The frequency dependent representation of network elements such as lines, cables, two- and three-winding
transformers, machines, loads, filter banks etc. for considering skin effects is fully-supported.
All impedances are calculated simultaneously in the same run. Since DIgSILENT PowerFactory uses a
variable step-size algorithm, the calculation time of frequency sweeps is very low while the resolution
around resonance points remains very high (typically 0.1 Hz).
Frequency sweeps can either be performed with the positive-sequence network model (very fast) or the
complete three-phase abc-network model.
PowerFactory V14
53
In addition to common applications relating to harmonic distortion, PowerFactorys Frequency Sweep function can
also be used for subsynchronous resonance studies. The calculation of damping and undamping torques is
supported by special scripts.
Network Modelling
The skin effect is considered by associating frequency characteristics with line or transformer resistances and
inductances. These characteristics can be specified by either setting the parameters of a polynomial expression or
by entering the characteristic point by point using tables. DIgSILENT PowerFactory uses cubic splines or hermite
polynoms for appropriate interpolation.
Filters can be specified by either layout parameters or design parameters. Layout parameters are
typically the rated reactive power, the resonance frequency and the quality factor. Design parameters
are the actual R, L, and C values.
In addition to the explicit specification of frequency dependent resistance or inductance via parameter
characteristics, overhead lines can be modelled by defining the tower geometry and cables can be modelled by
specifying the cable layout. In such cases, frequency dependent effects, such as the skin effect or frequency
dependent earth return, are automatically calculated and considered by the model.
The level of the ripple control signal in the entire network is calculated and reported in the single line
diagram, the output window or the browser.
PowerFactory V14
54
DC optimization based on linear programming using simplex methods, also supporting contingency
constrained optimization.
OPF in PowerFactory allows easy configuration of the optimization task via the simple selection of an objective
function, controls (i.e. system variables to be optimized), and constraints. The optimal solution for the selected
objective function is calculated under the consideration of a number of possible constraints with which the final
solution must comply. All controls and constraints can be flexibly-defined on a component level.
21.1 AC Optimization
Supported Objective Functions:
Minimization of costs (based on arbitrary (non-linear) cost curves for generators and load tariffs for
external grids)
Control Variables:
Switchable shunts
PowerFactory V14
55
Supported Constraints:
Boundary flow limits (min/max limits for active and reactive power flow along any user-definable
boundary)
Since the OPF can dispatch the active power of generators considering reserve limits and considering fuel cost
minimization (which is based on non-linear fuel cost functions), the PowerFactory OPF is also a highly advanced
economic dispatch function.
21.2 DC Optimization
The DC Optimization builds on a sensitivity-based linear programming approach. Most notably, it allows a
contingency constrained optimization to be carried out for any predefined list of contingency cases. The
optimization simultaneously considers all contingency cases, and the solution is globally optimal and guaranteed
to be feasible over all contingency cases (i.e. not violating any constraints in any of the contingencies).
Supported Objective Functions:
Feasibility check
Minimization of costs (based on arbitrary (non-linear) cost curves for generators and load tariffs for
external grids)
Minimization of generator dispatch change, i.e. finding a feasible solution with minimal re-dispatching
Minimization of pre- to post-fault generator dispatch change (available for contingency constrained
optimization only), i.e. finding optimal dispatch for the base case and each contingency case such that
the change between the base case and each contingency case is minimal
Minimization of pre- to post-fault transformer tap change (available for contingency constrained
optimization only), i.e. finding optimal transformer tap settings for the base case and each contingency
case such that the change between the base case and each contingency case is minimal
PowerFactory V14
56
Control Variables:
Generator active power dispatch - for base case and all contingency cases
Transformer tap positions - for base case and all contingency cases
Load consumption
Supported Constraints:
Branch flow limits (loading) for base case and all contingency cases
Active power limits of generators for base case and all contingency cases
Transformer tap changer limits for base case and all contingency cases
Boundary flow limits (min/max limits for active and reactive power flow along any user-definable
boundary) for base case and all contingency cases
PowerFactory V14
57
22 Reliability Analysis
22 Reliability Analysis
Reliability calculations are essential for the evaluation and comparison of electrical power systems in terms of
both design and operation. Although non-stochastic contingency analyses (i.e. n-1) are able to highlight obviously
unacceptable operational events, they cannot rank these events in terms of either frequency or duration. The
DIgSILENT PowerFactory Reliability Analysis tool incorporates standard reliability assessment features together
with sophisticated modelling techniques that enable all forms of reliability assessment to be carried out.
Failure models are defined using mean yearly failure frequency and repair duration data. For lines and cables, this
data is entered in per-length terms. Detailed models are available for generators that enable de-rated states to be
represented, with maintenance and common mode models also available.
Load forecast and growth curves can be imposed via time-varying load characteristics. Load models are
additionally available for hard-to-predict industrial situations, and each can be assigned its own interruption cost
using one of the following cost functions: cost/customer/interruption, cost/kW/interruption or cost/interruption.
All failure and load models can be represented either by the Markov method, where simple mean repair durations
are modelled, or by the sophisticated Weibull-Markov method, where repair duration variance is additionally
modelled. The Weibull-Markov model also has the unique property that annual interruption cost indices such as
load and process (industrial) interruption costs can be calculated both analytically and quickly. Consequently,
PowerFactorys Reliability Analysis tool enables the comparison and justification of alternative investment
proposals on a financial basis.
The basic calculation method used is analytical state enumeration. This method is very efficient, produces exact
results and is flexible for addressing a wide range of reliability calculation problems. The network reliability
analysis can be carried out on the basis of a simple connectivity check (primarily intended for distribution
networks) or on the basis of AC load flow calculations which consider load curtailments due to overloading or
voltage constraints (for bulk power system analysis).
The approach combines fast topological analysis for fault clearance, fault isolation and power restoration, with AC
load flow and optimization techniques for addressing energy at risk, load transfer and load shedding.
Finally, the results of all reliability assessments can be presented in text format, as user-defined graphs, or within
the single-line graphics environment.
PowerFactory V14
58
22 Reliability Analysis
In addition to the above-listed failure models, planned outages such as scheduled maintenance can also be
considered.
Special failure models can be used by various network components to share failure data. The failure models hold
stochastic failure information (mean yearly failure frequency for sustained, transient and earth faults on a per km
basis, as well as mean repair durations). PowerFactorys user-interface allows for both an easy setup, as well as
for simple modification of input data for various studies.
The Maintenance feature simulates the effects of network reliability under predefined planned outage scenarios.
Maintenance of individual network components can be modelled on an hourly basis.
Analysing load variation correlations, thereby reducing the overall number of load states
Using linear approximation techniques to improve performance in the case of large numbers of load
states
PowerFactory V14
59
22 Reliability Analysis
Overload alleviation by optimized generator re-dispatch, load transfer and load shedding, under
consideration of load priorities and the amount of load that is available for shedding.
Under-voltage load-shedding
For classical bulk power system analysis, it is assumed that post-fault overloads may occur. A full AC load flow,
incorporating basic generator re-dispatch and automatic tap changing, is used to analyse post-fault system
conditions. Additional load transfer and/or load shedding will then be simulated.
In cases where it can be assumed that system restoration will not lead to any overloading, the overload
alleviation can be omitted and a fast network connectivity analysis is sufficient.
System indices (also available for user-defined feeders, zones, and areas):
PowerFactory V14
60
22 Reliability Analysis
Load Indices:
PowerFactory V14
61
22 Reliability Analysis
Busbar Indices:
Formatted reports
PowerFactory V14
62
22 Reliability Analysis
PowerFactory V14
63
23 State Estimation
23 State Estimation
The PowerFactory State Estimator provides an accurate real-time analysis of the full operating system based on
the information provided by selectively monitored data, e.g. that of an installed SCADA system. The objective of
the state estimator is to assess the generator and load injections in a way such that the resulting load flow
solution matches as closely as possible the measured branch flows and busbar voltages. The features of
PowerFactorys State Estimation tool include:
Flexible definition of external measurement devices in the network model supporting the following
measurement types:
-
Loads: Active and reactive power demand, or alternatively the scaling factor
Generators and static generators: Active and reactive power generation
Asynchronous machines: Active power generation
Static Var Systems: Reactive power injection
Transformers: Tap positions
High-precision estimation of full system state that minimizes deviations from measurements
Innovative patch strategies for unobservable areas; usage of automatically created pseudomeasurements
PowerFactory V14
64
23 State Estimation
The PowerFactory State Estimator is supporting a variety of communication options such as OPC (OLE for Process
Control) or Shared Memory Interface for implementing data interchange with any kind of SCADA system.
PowerFactory V14
65
Any existing PowerFactory object can be plugged into a Composite Model Frame Slot.
Hundreds of objects such as power system components (e.g. busbars, generators, lines, transformers,
motors, voltage controllers, prime movers, power system stabilizers, motor driver machines, relays, relay
components, CTs, VTs, measurement files, FFT devices, real time clock, RMS signal transducer,
parameter identifiers, controllers, power plant control components, A/D converter, RPC links), result files
or display objects are at the users disposal.
In cases where additional functions are required which are not included in the built-in model- and
macros-library, these can be created using the DSL language.
Flexible definition of macros, functions and models, which is not limited to the use of predefined blocks
of a block-oriented simulation language (BOSL).
DSL is a Continuous System Simulation Language (CSSL) featuring a complete syntactical description of
continuous linear and nonlinear as well as digital systems. DSL is dedicated to common control and logic
diagrams; it is a non-procedural language as the sequence of elements can be chosen arbitrarily.
DSL syntax elements are algebraic and differential equations as well as intrinsic functions such as signal
limiting blocks, tables and curve approximation, delay, interrupt procedures, logical blocks, etc.
Basic control elements such as PID, PTn or even complete physical subsystems such as HVDC valve
groups or excitation systems can be defined as macros or high-level functions.
Automatic calculation of initial conditions utilizing various iterative procedures for initializing complex,
nonlinear equations of coupled systems.
Provision of various formal procedures for error detection and testing purposes, e.g. algebraic loop
detection, reporting of unused and undefined variables and missing initial conditions.
DSL models are considered by the PowerFactory EMT/RMS simulation. Multi-level modelling is provided
for the different steady-state descriptions and transient time domains (short/mid-term, long-term and
electromagnetic).
PowerFactory V14
66
DSL models can be created by drawing a block diagram. Any block may contain another DSL model,
a macro or any sequence of DSL syntax. The DSL-editor will then generate the DSL description
automatically and will also provide direct model testing functions such as eigenvalue analysis or stepresponse tests of the complete DSL model or of sub-models only.
DSL Implementation
The DIgSILENT Simulation Language (DSL) is fully-integrated into the PowerFactory program kernel via the
graphical interface.
Signals: Specific input- and output signals defined for all PowerFactory objects as well as any variable
defined in a DSL model can be accessed in their corresponding read- or write- mode.
Interrupts: Conditions derived by DSL models can cause interrupts to be sent to the simulation kernel
where they are scheduled within the event queue.
Output and Monitoring: Conditions may trigger an output to be displayed in the output window and
stored in the simulation log file.
Advanced Features
DSL models feature the direct interaction with external processes such as DAQ interfaces, SIMULINK
modules or other software systems via time-synchronized communication channels
Procedures written in C++ code can be directly linked via appropriate interface mechanisms
User-defined intrinsic functions can be linked via external DLL for extending the already broad range of
DSL standard intrinsic functions such as: abs, sin, cos, exp, etc. and DSL special functions such
as lapprox, lim, limstate, delay, picdro, time, file, flipflop, etc. User defined intrinsic
functions are to be linked to PowerFactory via the DLL digexfun.
2.
Complete user-defined models of any modelling level, linked via the DLL digexdyn is supported for any
discrete system. Typical applications are digital control systems which are executed via clocksynchronized calls, simulation models being implemented via difference equations, or models which incl.
their state variables and integration algorithms internally.
PowerFactory V14
67
Simulation of radial and meshed 1-, 2-, 3- and 4-phase AC and/or DC systems
High precision models for both solid and salient pole synchronous machines, asynchronous machine
model including a doubly-fed induction machine model with integrated or externally connected PWM
converter.
VSD (Variable Speed Drives) systems, PWM converter and other power electronic elements such as the
softstarter, inverter and rectifier. In general, all available power system elements are also supported for
stability simulations.
General load models where load inertia, bus voltage and frequency dependence is represented; a special
lumped load model to accurately represent feeders containing a high percentage of motor load (RMS
only). The capability of modelling motor stall effects is included, and was developed on the basis of
comprehensive system tests.
Generic wind turbine models with doubly-fed induction generator, direct driven synchronous generator
and asynchronous generator with static compensation (STATCOM).
PowerFactory V14
68
Large library of IEEE controller models covering prime movers, automatic voltage regulators (AVR) and
power system stabilizers (PSS).
Positive sequence only - the classical RMS representation for stability studies
a-b-c phase RMS representation supporting unbalanced grid loading initialized by a balanced or
unbalanced load flow, featuring precise definition of any unbalanced grid fault condition including
single- and double-phase line interruptions. This system representation mode avoids tedious handcalculations of equivalent fault impedance and allows access to any a-b-c phase quantity for plotting
or precise modelling purposes (e.g. protection devices).
Highly accurate, fixed or variable step-size integration technique for solving AC and DC network load
flow and dynamic model equations. This is combined with a non-linear electromechanical model
representation to enable a high degree of solution accuracy, algorithmic stability and time range validity.
A-stable simulation algorithm for the efficient handling of stiff systems. This is applicable to all or any
individually selected model featuring error-controlled automatic step-size adaptation, ranging from
milliseconds up to minutes or even hours, including precise handling of interrupts and discontinuities.
The calculation of initial conditions is carried out prior to the EMT simulation, and is based on a solved
load flow (symmetrical or asymmetrical). Consequently, there is no need for saving steady state
conditions being reached after transients are damped out aiming in simulation re-starting under steady
state conditions.
Special numerical integration methods have been implemented in DIgSILENT PowerFactory in order to
avoid numerical oscillations caused by switching devices and other non-linear characteristics.
Highly accurate, fixed or variable step-size integration technique for solving AC and DC network
transients and dynamic model equations. This is combined with a non-linear electromechanical model
representation to enable a high degree of solution accuracy, algorithmic stability and time range validity.
PowerFactory V14
69
The user can interrupt the simulation at any time, either manually, by a scheduled interrupt time or
automatically via interrupt conditions. When the simulation is interrupted, most PowerFactory commands
such as displaying or printing power flow results, checking the bus voltages, calculating eigenvalues or
analyzing the controller status, etc., can be executed.
By activating predefined fault types, or by accessing and modifying PowerFactory variables, any type of
fault can be implemented. Typical faults are:
- Tripping of any power system element such lines, transformers, feeder loads or generators;
- Application and clearing of faults at substations or along lines;
- Opening and closing of circuit breakers e.g. simulating load shedding, shunt switching,
starting/tripping of synchronous and asynchronous machines, or when simulating the
synchronization of isolated areas via synchro-check relays;
- Introduction of Parameter Change Events featuring the modification of any built-in and DSL
model parameter;
- Definition and introduction of inter-circuit events;
- Generation of message- and outage-events;
- Modification of integration step sizes;
- Event-driven modification of variables and signals either manually, via DSL models or by
reference to external measurement files.
Any PowerFactory variable, or any quantity identified in the transmission network, built-in dynamic
models or DSL models, may be selected for simulation observation or for later plotting within x/t or x/y
diagrams or any other VI (Virtual Instrument) provided. In addition to these variables, the DSL algebraic
expression interpreter and logical expression evaluator can be applied to generate further signals or any
user-defined quantity.
Plotting files may be retained for re-plotting in comparison with subsequent runs.
Output window log of all simulation events, providing a detailed analysis of manually entered or
automatically initiated events.
Simulation results are stored in a proprietary binary PowerFactory file format which can be directly
converted into COMTRADE files.
PowerFactory V14
70
Real-time simulation mode with user-defined real-time synchronisation periods (RMS only)
Parallel and sequential synchronization for integrated simulation, e.g. for simulation certain grid sections
in RMS mode whilst others are simulated in EMT mode.
Simulation of any number and combination of unbalanced faults including single- and double-phase line
interruptions
The a-b-c phase system representation mode avoids tedious hand-calculations of equivalent fault
impedance
It also allows for accessing any a-b-c phase quantity for plotting or precise modelling purposes (e.g.
protection devices)
Long-term stability simulations based on adaptive step-size algorithms with accuracy-controlled step-size
adaptation ranging from milliseconds to several minutes without any decrease in precision or even
manipulation of transient behaviour.
PowerFactory V14
71
A-stable simulation algorithm which fully covers fast transients as well as slow, semi steady-state
dynamics with high-precision event handling (stiff systems).
Typical Applications
Voltage stability analysis considering effects of load variations, tap-changer control and reactive power
limits
Long-term flicker analysis in cases such as fluctuating renewable generation or varying loads
What is the maximum voltage sag? (This is typically not the initial voltage sag at t=0)
How will the supply grid be loaded and which starting options should be considered?
The Transient Motor Starting function makes use of the PowerFactory stability module by providing a preconfigured shortcut for easy-to-use motor starting analysis. The motor starting is initiated by selecting the
respective motors within the single line diagram and initiating the motor starting calculation.
A complete symmetrical or asymmetrical AC/DC load flow will be computed prior to the motor starting
event; pre-selected and pre-configured VIs are automatically created and scaled with full flexibility for
user-configuration.
Typical motors supported are: single- and double cage asynchronous machines, squirrel and slip-ring
motors, double-fed induction machine, synchronous motors.
Access to the model library for built-in motor driven machine characteristics (torque-speed
characteristics) with flexible user-modelling support.
Support of various starting methods such as direct start, star-delta starting, variable rotor resistor,
thyristor softstarter, transformer softstarter, variable speed drives, etc.; start from any rotational speed.
PowerFactory V14
72
Full representation of generators with exciter/AVR model support on the basis of built-in models (e.g. IEEE
models) as well as user-defined models utilising the DSL approach; consideration of protection devices such as
under-voltage protection, over-current protection, automatic restarting relays (EMR) or transformer OLTC.
2- and 3-winding transformers and autotransformers for 1-, 2- or 3-phase systems, including stray
capacitances, tap dependent impedance and saturation effects. Flexible definition of non-linear
magnetizing reactance: two-slope, polynomial, flux-current values
HVDC valve groups (6- and 12-pulse Graetz bridge configurations) and other FACTS devices such as
SVCs, UPFCs, TCSCs and STATCOMs
PowerFactory V14
73
The package provides a powerful user-friendly graphical environment for the evaluation of simulation results
characterized by:
User-customizable plots for waveform visualisation, including filtering options, scaling, etc.
PowerFactory V14
74
facilitate the operator in understanding phenomena such as basic system dynamics, system control and
stability and protection, which are typically too fast for the operator to observe
Real-time simulation of typical grids, test systems or substations including generators, their control
systems and associated protection.
Communication with existing hardware such as controllers or relays via OPC, shared memory or A/D
systems.
Simulation of grid disturbance scenarios, sensitivity analysis on grid operating conditions, tuning optimization of
controllers, investigation of control structures, etc.
PowerFactory V14
75
Based on a converged and adjusted power flow, the modal analysis starts with the calculation of the
system initial conditions. Alternatively, any interrupted status of a time domain simulation could be used
as the initial condition.
The system A-matrix is constructed automatically for the complete system (including generators, general
loads, predefined system plant and controller models as well as DSL devices).
System and model linearization - including user-defined models - is performed by iterative procedures.
Limiting devices are disabled automatically. The representation of the network model is equivalent to the
simulation model, allowing a direct comparison/validation between time domain simulations and modal
analysis results.
computation of a certain part of the eigenvalue spectrum: calculation of a userdefinable number of (closest) eigenvalues around a complex reference point
recommended as a fast approach for higher order systems for which calculation of all
eigenvalues by QR algorithm is too time-consuming
Calculation results include eigenvalues (together with oscillation information such as damped frequency,
damping, damping ratio, damping time constant, etc) and left and right eigenvectors. From
PowerFactory V14
76
eigenvectors, the individual machines controllability, observability, and participation factors are derived
with respect to each mode.
Eigenvalue Plot
Plot has interactive features that facilitate detailed analysis of individual modes;
convenient creation of phasor plots/bar diagrams for each mode
PowerFactory V14
Automatic detection and highlighting of clusters for convenient identification of interarea modes
77
27 PowerFactory Interfaces
27 PowerFactory Interfaces
PowerFactory offers a number of mechanisms and options for interfacing with external applications such as GIS
and SCADA, or for a complete integration and background execution in Engine Mode. Depending on the
application, the user may choose from the options described below.
Available for PowerFactory Interactive Window Mode and PowerFactory Engine Mode
File formats supported: ASCII Text (CSV), XML, MS-Excel and MS Access
PowerFactory listening mode to receive any data or signal from a registered OPC Server
PowerFactory sending mode to write back any data or signal to a registered OPC Server
PowerFactory V14
78
27 PowerFactory Interfaces
PowerFactory Engine
(Client)
OPC Application
(Server)
OPC items (object parameters, object and model
Selected values *)
*) communication is asynchronous,
so neither the server nor the client
waits for a response
Via the shared memory, modification of any object parameter, initiation of command execution and
access to any calculation result is supported.
The communication is based on a request/response interaction. PowerFactory acts as a server that waits
for requests. Each request must contain a command and can optionally contain input data and result
definitions.
PowerFactory V14
79
27 PowerFactory Interfaces
Request
Object data
contained?
Copy data to
PowerFactory
objects
Execute
command
Result
definitions
contained?
Fetch results
from
PowerFactory
objects and
include them in
reponse
Response
PowerFactory
(Server)
Commands
event _REQUEST
Processes request:
Executes commands
Status
PowerFactory V14
event _RESPONSE
80
28 Interfacing PowerFactory
28 Interfacing PowerFactory
Interfacing and integrating power system software with other applications such as GIS (Graphical Information
Systems) and SCADA (Supervisory Control And Data Acquisition) systems is an important requirement. Utilizing
the implemented DGS, OLE and Shared Memory interfacing techniques, DIgSILENT PowerFactory features great
flexibility in supporting any level of interfacing and integration needs. The following sections summarize some
typical examples.
Unidirectional GIS to PowerFactory data transfer via DGS format definitions (CSV or ODBC)
Bidirectional data transfer (e.g. via the PowerFactory shared memory interface) when running
PowerFactory in Engine Mode or Hybrid Mode, which features full integration of PowerFactory
analysis functions and additional graphic display options in the GIS system
PowerFactory V14
81
28 Interfacing PowerFactory
Characteristics
Incremental data exchange utilizing PowerFactorys user accounting, project management and merge
tools featuring GIS -to -PowerFactory team working
Combines and merges several data sources via PowerFactorys data handling capabilities, thereby
avoiding any middleware requirement
Application Aspects
Sharing of data sources, thereby avoiding duplication of data entry and maintenance
As most applications require the merging of additional data such as customer load consumption, dispersed
generation infeeds and SCADA readings, PowerFactory GIS integration is often handled as a project
implemented via clearly defined specification of data sources and overall workflow.
PowerFactory V14
82
28 Interfacing PowerFactory
Direct 1-to-1 relation between SCADA network objects due to full substation topology support of
PowerFactory
Utilization of SCADA manufacturers state estimation functions, or, if not present, PowerFactorys
advanced state estimation features
Operators access to all PowerFactory functions such as load flow, contingency analysis, optimal power
flow, spinning reserve allocation
PowerFactory V14
83
28 Interfacing PowerFactory
PowerFactory V14
84
Although it is technically possible to store the PowerFactory database on any network drive, this is not
recommended as it requires high-speed LAN capabilities and might exhibit less reliability regarding database
integrity when the LAN connection is unexpectedly interrupted.
PowerFactory V14
85
If you have purchased several Workstation Licenses, the USB hardlock installation is required on all computers
where the Workstation License is to be used. Of course, if PowerFactory is installed on more computers than
there are USB hardlocks available, only those installations can be used simultaneously where the USB hardlock is
plugged-in at that point in time.
Provision of a License Server which can be installed centrally managing any independent number of
licensed functions. The License Server comes with only one single USB hardlock holding all licensed
functions. The License Server must be accessible for all PowerFactory installations via a network IPaddress.
2.
Support of multi-user database operation, featuring the simultaneous access of all connected users to a
single database. The Server License comes with database drivers for both databases; MS-SQL and
ORACLE (the database servers themselves are not included).
3.
The Server License can be executed in a Client-Server (Application Server) environment such as MS
Sever 2003/2005 or CITRIX, which has the advantage of centralized software installation and
maintenance a typical requirement of modern IT infrastructures.
PowerFactory V14
86
An optional feature of the Multi-User License Server is the Floating License which allows the temporary transfer
of a user license from the license server to a local PC. This option is typically required when a user is travelling
with his/her laptop, thereby preventing him/her from accessing the license server. When downloading the floating
license to a local machine, the license will disappear from the license server and will move to the local PC until
the user reconnects to the license server. The floating license is time-limited and, if not reconnected to the
license server, will automatically fly back to the license server after a defined time.
Typical M ulti-User installation w ith License Server and Floating License Option
PowerFactory V14
87
Note:
A clear advantage of the License Server is its ability to host a different number of licenses for certain
functions. This allows a more economical solution which considers the simultaneity of users. The
allocation of functions is made upon user login and not upon the execution of a certain PowerFactory
command. This philosophy is based on the notion that upon successful login and allocation of
functions, those functions should be available to the user throughout the entire PowerFactory session.
Multi-User Database
Centralized data handling is supported by a multi-user database featuring the simultaneous access of all
connected users to a single data source. Currently, database drivers for MS-SQL and ORACLE are available. This
execution option is designed for PowerFactory installations with a large number of users requiring access to the
same project data and, who would benefit from the PowerFactory team-working tools such as Master Project
management, Project Versioning, Project Deriving along with Project Compare- and Merge tools, which make
concurrent model building and data entry very easy.
In the configuration shown above, the execution of the PowerFactory software will still take place on the users
local PC while the multi-user database resides on a special high-speed database server.
PowerFactory V14
88
Application Server
A further step often required in large companies with tens or hundreds of users is the centralized installation and
execution of the PowerFactory software, the database and the License Server. This Application Server installation
is currently supported for MS Server 2003/8 and other server add-ons such as CITRIX. The figure below shows a
typical example of such a centralized installation environment.
PowerFactory V14
89
Local Installation
Workstation
Server
Educational &
Student / Private
License
License
Research License
Use License
[X]
[X]
[X]
[X]
[X]
Local Hardlock
[X]
[X]
License Server
[X]
[X]
[X]
[X]
[X]
[X]
(**)
(*)
Required hard disk space will heavily depend on the number of projects
handled, number of objects (e.g. size of the network modelled), number of
scenarios, etc. Total disk space requirements are therefore determined
individually.
(**)
The required main memory capacity will heavily depend on the network size
and the type of calculations being performed. A typical memory requirement
would be between 0.5-1.0 GB exclusively for executing PowerFactory unbalanced
load flow, fault analysis and stability for a 5000-bus system.
Supported operating systems are Windows 2000, Windows XP, Windows Vista
and Windows 7.
Application Server:
PowerFactory V14
90
Item
1
Sections 3-17
Section 27.1
Included:
Overcurrent-Time Protection
Included:
Section 18
Section 18.1-18.3 and 18.5
Not Included:
Section 18.4
Included:
Sections 19.1-19.2
Harmonic Analysis
Included:
Sections 20.1-20.4
Included:
Section 21.1
Active Power Controls disabled
Included:
Sections 21.1-21.2
Reliability Analysis
Included:
Sections 22.1-22.5
Included:
Section 23
10
Included:
11
Included:
12
Included:
13
Included:
14
Included:
15
Included:
16
Reference:
Section 7.1
17
Reference:
Section 7.1
18
Included:
Section 27.2
19
Included:
Section 27.3
PowerFactory V14
91
Base Package
100 nodes
250 nodes
500 nodes
unlimited
max.
max.
max.
no. of nodes
Workstation Edition
3.900,-
6.100,-
9.800,-
10.900,-
Server Edition
5.070,-
7.930,-
12.740,-
14.170,-
Edition
Prices of functional extensions can be requested from DIgSILENT and respective International Representatives.
PowerFactory V14
92
DIgSILENT GmbH
Heinrich-Hertz-Strae 9
72810 Gomaringen / Germany
Phone: +49-7072-9168-0
Fax: +49-7072-9168-88
E-mail: mail@digsilent.de