Less possibility of hot effluent air recirculating into the intake. The hot
air is discharged upward at approximately 2.5 times the intake velocity,
or about 1,500 ft per min.
Better process control and stability because the plenum covers 60%
of the bundle face area, reducing the effects of sun, rain, and hail.
Complete exposure of the finned tubes to sun, rain, and hail, which
results in poor process control and stability.
Bay is a part or entire of air cooler that may include one or several tube
bundles with at least one fan.
IPS-E-PR-785 item 8.1:At least two fans shall be provided for each bay.
According to EXXON Design Practice Section IX-I: Tubes for air-cooled heat
exchangers may be plain or may contain fins.
The fin density varies between 7 and 11 fins/in. (276 and 433 fins/m) and fin
height varies from 5/16 to 1 in. (8 to 25 mm).
Fin Types
The L-footed tension wound fin is normally used
in services where the tube wall temperature does
not exceed 350 degrees F and air side corrosion is
not extremely high.
Other Points
Under normal operating conditions, air outlet temperatures should not
Exceed:
60C with fans in operation.
80 C with free convection on the air side.
Fouling factor on air side of exchangers shall be 0.35m2. K/kW
(0.002h.ft2.F/Btu) , For fresh water cooling system the fouling factor shall
be 0.0004 hr. C m2/ kcal.
Design maximum ambient air temperature should be selected so that it will
not be exceeded more than 1-2 percent (sometimes 2-5%) of the total
annual hourly readings based on at least 5 consecutive years.
Units should not be located near heat sources. Experience cautions that
units near exhaust gases from engines can raise inlet air 8C or more
above the expected ambient
Design Procedure
Example
Figure 10-185