You are on page 1of 36

MV electrical network management

Easergy Range

Easergy T200 I & E


MV substation control unit

Catalogue

T200ie_PCRED398085EN.indd 1

28/05/2013 15:59:12

A new path for achieving your electrical installations


A comprehensive offer
The Easergy range is part of a comprehensive offer of products that are perfectly coordinated to meet all
medium and low voltage electrical distribution requirements.
All of these products have been designed to work together: electrical, mechanical
and communication compatibility.
The electrical installation is thus both optimised and has improved performance:
better service continuity,
increased personnel and equipment safety,
guaranteed upgradeability,
efficient monitoring and control.
You therefore have all the advantages at hand in terms of know-how and creativity
for achieving optimised, safe, upgradeable and compliant installations.

Tools for facilitating the design and installation


With Schneider Electric, you have a complete range of tools to help you get to know and install the products
whilst complying with current standards and good working practices. These tools, technical sheets and
guides, design software, training courses, etc are regularly updated.

Schneider Electric is associating itself with


your know-how and your creativity to produce
optimised, safe, upgradeable and compliant
installations
For a real partnership with you
A universal solution doesnt exist because each electrical installation is specific.
The variety of combinations on offer allows you to truly customise the technical solutions.You are able to
express your creativity and put your know-how to best advantage when designing, manufacturing and
exploiting an electrical installation.

T200ie_PCRED398085EN.indd 2

28/05/2013 15:59:12

Easergy T200 I & E

PCRED398085EN

T200ie_PCRED398085EN.indd 1

Contents

Application and benefits

Overview of the range

General description

Power supply

Switchgear control-command

Fault current detection and measurement

10

Preset automation systems

12

Programmable automation systems

16

Management and time-stamping of variables

17

Communication

19

Configuration and operation

21

General characteristics

23

Dimensions and mounting

24

Mounting of remote transmission equipment

25

Connection equipment

26

Accessories

27

Easergy L500: MV network remote control system


for the Easergy range

29

Order form

31

28/05/2013 15:59:12

Easergy T200 I & E

Easergy Range:
application and benefits

PE56261

Throughout the world, poor quality supply of electrical power is no longer acceptable
to consumers. In many countries, regulatory standards have been defined in order to
ensure a minimum standard of electrical service quality.
The most common indicators employed are:
SAIDI: Standard Average Interruption Duration Index - e.g.: 96 minutes/year
SAIFI: Standard Average Interruption Frequency Index - e.g.: 1.2 interruptions/year.
In order to respond as effectively as possible to the globally recognised indicators
for measuring their power quality, power distribution companies are looking for
new products and solutions, focused principally on reducing the following:
The number of interruptions to the supply
The duration of power outages
The areas affected by faults.
The above targets can be achieved by carrying out several actions, including:
Establishing preventive maintenance on the networks
Reducing the length of supply lines to limit the impact of a fault
Equipping the network with suitable equipment for better local and remote
operation.
For power distributors, an increase in service quality must be linked
with improved performance and competitiveness as well as management
of investments. This can be achieved by:
Reducing operating costs, particularly during incidents on the MV network
Reducing non-distributed power costs
Maximising cost and time efficiency on investments and benefiting from
immediate returns
Selecting easy-to-implement, high-performance equipment
to reduce equipment immobilisation and installation time
Reducing direct and indirect maintenance costs of MV lines and equipment.

DE40551FR

HV/MV

MV ring

T200

T200
4 channel

Flair 200C

Remote control center

T200
4 channel

T200
Source transfer switch
T200
16 channel

T200ie_PCRED398085EN.indd 2

PCRED398085EN

28/05/2013 15:59:12

Easergy T200 I & E

Easergy Range:
application and benefits
(cont.)

What are the benefits of managing


MVnetworks?
Network management results in a very
high level of service
It also has a positive impact on both
investments and operation
Network control fits into a comprehensive
policy over several years.

Reducing power outage durations

Optimised local and remote intervention based on reliable information


from the fault current detectors
Restoration of power to healthy parts of the network during an incident using
control units:
by the operator or automatically from the remote control centre: 50% to 70% of the
network resupplied in a few minutes (depending on the number of remotely
controlled stations).
by integrated automation systems: faulty sections isolated in the reclosing cycle.
by an automation system distributed across the various remote control units:
self-healing network, allowing 50 to 70% of the network to be resupplied within 20
seconds.

Improving distributed power quality

Precise information about transient and permanent faults enables corrective and
preventive maintenance measures to be taken to reduce the recurrence of faults.
Monitoring of distributed power quality using relevant, recorded and transmitted
measurements:
measurement of load currents and indication of variations in real time
measurement of voltages with indication and memorisation of voltage dips
and loss
power factor measurement.

Reducing operating costs

The accuracy of fault information significantly reduces the time required to locate
faults:
on-site intervention time is significantly reduced when using devices which
can communicate
precise information about faults simplifies fault detection tasks and operations.
Preventive maintenance on the MV network reduces the number of interventions
necessary outside normal working hours.

Rapid return on investments

Comprehensive solutions which are quick and easy to implement.


Product range compatibility and ease of upgrade in order to optimise investment
and profit from immediate returns.
Investment in the control station can be steep and time-consuming to implement.
Remote network control can be set up in phases by installing simple systems which
provide a rapid return on capital and can be implemented in a few months.
This can be used to evaluate the improvement in service quality:
basic SCADA system with network view, detailed view, alarms and archives
to enable control in real time and entry of data for maintenance purposes.
self-healing network from the same remote control units. This network operates
autonomously and requires no action from the control centre.
After the various network instrumentation phases, the basic SCADA system
can be replaced by a DMS type SCADA system.
adaptation of stations to remote control: motorisation of MV cells, communicating
control unit or detector, transmission equipment.

PCRED398085EN

T200ie_PCRED398085EN.indd 3

28/05/2013 15:59:12

Overview of the Easergy range

Easergy T200 I & E

Easergy: a range of solutions for MV network management


Easergy range
dedicated supervisor

Remote network control

L500

T200 P

Easergy range dedicated


remote control system
Capacity:
500 Easergy type devices

Main functions
Network view with
substation alarm
Detailed substation view
Alarm logs, archives
Direct access to substation
view via a list
Automatic sorting of alarms
and archives by substation
Online help

Communication
Integrated communication
front-end
Permanent and nonpermanent communications
management:
telephone/GSM
radio
direct public and dedicated
private line
Periodic call management
Communication protocol
Modbus

Data configuration
Professional
communications and
database editor
Data creation via dialogue
boxes
Accessories
Radio, PSTN, DL and fibre
optic modems

T200 I

Remote network monitoring

T200 E

Flite 116-SA/G200

Flair 200C

Overhead switch Control unit for MV and MV/LV


control unit
substations

Communicating fault current


detector for overhead lines

Communicating fault current


detector for an MV substation

Control of 1 or 2
switches

Control of 1 to 16
switches

Control of 4
switches

Single-phase ammetric detector

2-way three-phase fault current


detector, compatible with any
type of earthing system

Pole-mounted

Wall-mounted

Ringmastermounted

Flite 116:
Line installation
Phase-to-phase and
phase-to-earth fault current
detection
I and U presence measurements
Communication management
with G200
Powered by lithium battery

Switch monitoring and control


Fault current detector
Automation systems: sectionaliser, power supply
source changeover switch
Measurements: Measurements: I, U
I, U, P, Q, S, energy
and power factor
cos
Concentration of Modbus communication devices
Data and measurements archives
Back-up power supply for control unit, switch and
transmission equipment
Programmable logic controller IEC 61131-3 and
built-in calculation formulas to create or tailor specific
functions/applications

Wall-mounted
Phase-to-phase and
phase-to-earth fault current
detection
U, I, P, Q, S, energy and
power factor measurements cos
Management of 3 digital
outputs and 6 digital inputs
220 Vac supply backed-up
by Ni-CD battery
G200:
Concentration of Modbus
Pole-mounted
communicating devices
Flite 116 concentrator
Data and measurement
Processing and archiving
archives
Free I/O: 3 digital outputs and
Programmable logic controller
6digital inputs
220 Vac, solar or 12 Vdc supply IEC 61131-3 and built-in calculation
formulas to create or tailor specific
functions/applications

1 to 2 serial communication ports


1 Ethernet port
Communication port operation management
Transmission interface: PSTN, radio, GSM, GPRS,
3G, Ethernet, dedicated line, RS232, RS485
Communication between equipment in Modbus IP

915 MHz short range radio


communication
1 SCADA communication port
Transmission interface: radio,
GSM, GPRS, CDMA

1 communication port
1 Ethernet port (option)
Transmission interface:
PSTN, Radio, GSM, GPRS, 3G,
Ethernet, RS232, RS485

IEC 870-5-101 and IEC 870-5-104


Serial DNP3 and TCP/IP
Serial Modbus and TCP/IP
Other proprietary protocols

IEC 870-5-101
Serial DNP3 and TCP/IP
Modbus

IEC 870-5-101
DNP3
Modbus

Embedded web server


Local and remote configuration

Local and remote configuration


with Easergy W500

Local or remote configuration


Embedded web server

Simulation tools and tests

Installation tool

Open phase and zero


sequence sensors

Open phase and zero sequence


sensors

T200ie_PCRED398085EN.indd 4

PCRED398085EN

28/05/2013 15:59:14

Easergy T200 I & E

Overview of the Easergy range


(cont.)

Local fault indication

Flite 110-SA

Flite 210, 230

Flite 312, 315, 332,


335, 382

Fault current detectors for an overhead network

Flair 21D, 22D, 23D,


23DM

Flair 219, 279

Flair 510, 570, 590

Fault current detectors for MV substations

Single-phase ammetric
detector

Three-phase ammetric
detectors

Three-phase
directional
detectors

DIN format three-phase Three-phase ammetric


amperometric detectors detectors
compatible with all
neutral system types, and
which can communicate
(Flair 23DM)

Three-phase detectors
compatible with all
neutral system types

Main functions
Line installation

Pole-mounted

Pole-mounted

Wall-mounted

Wall-mounted

Phase-to-phase and
phase-to-earth fault
current detection
Indication of transient
and permanent faults

Phase-to-phase and
phase-to-earth fault
current detection
Indication of transient
and permanent faults

Phase-to-phase and
phase-to-earth fault
current detection

Phase-to-phase and
phase-to-earth fault
current detection
Indication of transient
and permanent faults

Powered by lithium
battery

Powered by lithium
battery

Phase-to-phase and
phase-to-earth fault
current detection
Transient and/or
permanent fault indicator
Fault counter
Powered by lithium
battery, solar panels or
12 Vdc depending on
model

Incorporated in the
switchgear
Phase-to-phase and
phase-to-earth fault
current detection
Measurements:
ammeter
maximeter
Self-powered by
current sensors

Power supply:
Flair 279: 220 Vac
(battery-backed)
Flair 219: battery

Power supply:
Flair 510: with Li battery
Flair 570: 110/220 VAC
with backup Li battery
Flair 590: 220 VAC with
backup supercapacitor

Signalling contact
for RTU
1 RS485
communication port
(Flair 23DM only)

Signalling contact
for RTU

Signalling contacts for


RTU (signalling possibility
separate from phase and
neutral faults)
Two external inputs
allowing:
resetting of faulty
signalling
detector tests

By micro-switches or
button and display unit

By micro-switches

Configurable via
display unit

Open phase and zero


sequence sensors
Unit for wall-mounting

Open phase and zero


sequence sensors

Open phase and zero


sequence sensors

Communication
Option: signalling
contact for RTU

Signalling contacts
for RTU

Modbus

Data configuration
By micro-switches

Accessories
Installation tool

PCRED398085EN

T200ie_PCRED398085EN.indd 5

By micro-switches

Configurable via
display unit

28/05/2013 15:59:14

Easergy T200 I & E

General description

Easergy T200 I & E: solutions


to optimise your MV substations.

Easergy T200 I & E are control units designed for installation in MV substations
to control any type of switch remotely.

A high level of integrated functions


PE57935

Easergy T200 I & E have been specially designed to meet the needs of customers
in managing MV substations, offering compact and open-ended solutions:
T200 I: management of 1 to 16 switches of any type
T200 E: 1 to 4 switches, Ringmaster or other type
Back-up power supply for motorisation, transmission equipment
and the control unit
High-performance fault current detector
Measurements for better control of the network load
Network reconfiguration automation systems
Communication with the control centre
Monitoring, for local or remote operation.
Two versions of T200:
The T200 E is a specific version of T200 I managing a maximum of 4 channels and
designed to be used with Ringmaster type cubicles.
The T200 I is used with standard SM6, RM6 type or other cubicles.

Compatible with any SCADA system


PE57936

A continuously updated range of protocols includes the main standards IEC8705101,


IEC 870-5-104, DNP3, Modbus and other proprietary protocols.
With our numerous installations around the world, we have considerable
experience in the interoperability of our protocols.

Open to all communication media

Optimum transmission network management via two serial communication ports


and an Ethernet port
Wide range of integrated modems, including radio, PSTN, GSM, GPRS,
3G and DL
Management of external modems via Ethernet or RS232 connections.

Reliable and rugged


PE57071

In view of difficult environmental conditions and the operational availability required,


Easergy T200 I & E have undergone strict reliability and qualification testing in
accordance with IEC international standards.
The reliability of the T200 range is proven by its use across five continents
in very varied environments under conditions more severe than those demanded by
the standards:
High temperature: Algeria, Saudi Arabia, Indonesia
Low temperature: Russia
Humidity: UK, China, Guyana, Bolivia, Indonesia, Gabon
Salt mist: Colombia, Portugal, Algeria.

Assured continuity of service

Overall improvements in power provision rely on ensuring the constant availability


of equipment responsible for reconfiguring networks during an incident.
Easergy T200 I & E perform numerous auto-tests, particularly on the power supplies
and battery.
The power supply module is sized to power a conventional radio in order
to transmit an alarm if the battery fails.
The alarms transmitted to the control centre during a fault enable immediate
corrective maintenance.
The auto-tests ensure the availability of equipment without the need
for preventive maintenance.

T200ie_PCRED398085EN.indd 6

PCRED398085EN

28/05/2013 15:59:15

Easergy T200 I & E

General description
(cont.)

PE56311

Compact enclosure

The equipment is housed in a basic enclosure containing all the functional elements
needed to control 1 to 4 switches (1 to 4 channels) and for the T200 I in an expansion
enclosure to expand the capacity to 16 switches (16 channels).
The T200 I enclosure is entirely of stainless steel. The T200 E enclosure is painted the
colour of the cubicle. Both ensure compliance with EMC standards. These enclosures
are provided with a padlocking system.
All information relating to the status of switches, fault currents and power supplies
is visible on the front panel of the rack (without opening the enclosure on T200 I).

T200 I 4-channel enclosure

Main components:
A rack containing all the electronic modules
An interface module with switchgear
A battery for back-up power supply
A slot for the transmission interface (not supplied)
On T200 I: tamper-proof connectors on the underside of the enclosure for
connection to electrical switch controls.

PE57937

Ease of installation and connection

Wall-mounted enclosure, supplied with drilling template (T200 I)


Enclosure mounted directly on the side of the Ringmaster cubicle (T200 E)
All the internal connections are made by connectors:
no screwdriver required
Connection to the switch via removable connectors
Connection of transmission equipment aerials (radio, GSM, GPRS, 3G) by
connector.

Fast and reliable installation

Equipment supplied preconfigured


Configuration in a few minutes by downloading from the database prepared
in the office
Numerous test and simulation tools available as accessories.
T200 I 8-channel enclosure

PE57938

Remote operation and maintenance by embedded


web server

Access to remote data parallel to the control system is possible


via the GSM, GPRS, 3G, Ethernet or PSTN transmission networks
Option to change the configuration, update software versions, load archive files,
display states and control the switch.

Optimum cost/performance ratio

Designed to simplify the work of power distributors and to optimise the quality
of the distributed power, Easergy T200 I & E also reduce your costs as follows:
Cost of ownership, thanks to the range of its catalogue, the modularity of the fault
detectors and the number of switches managed
Installation costs, thanks to the simplicity of connection and setup
Maintenance costs, thanks to numerous auto-tests with return to the control
centre, allowing preventive maintenance measures to be taken
Operating costs: Easergy T200 I & E require no routine maintenance.

PE57924G

T200 I 16-channel enclosure

T200 E 2 or 4-channel enclosure

PCRED398085EN

T200ie_PCRED398085EN.indd 7

28/05/2013 15:59:16

Easergy T200 I & E

Power Supply

PE57940

High-availability back-up power supply

The power supply module supplies the back-up operating voltages for the:
MV switch motorisation
transmission equipment, such as radio
control unit.
A battery ensures the operation of the whole substation in the event of loss of the
mains supply. The power supply module ensures its charge and monitoring
(regulated and temperature-compensated charger).

Power supply self-monitoring

Loss of AC supply: immediate and delayed alarm


48 Vdc motorisation fault: voltage fault, blown fuse
12 Vdc transmission fault: voltage fault, blown fuse
12 Vdc internal fault.

Battery self-monitoring
Battery availability check
The power supply module tests the battery status every 12 hours. When two tests
are negative, an alarm is generated and transmitted to the control centre.

DE56649FR

Prevention against serious discharge


Serious battery discharge is irreversible. T200 I protects the circuits and causes
the battery circuit to cut out when it detects:
A basic charger voltage fault
Consumption in excess of 1.3 A for over 3 minutes on the transmission output
Alarm transmission to the SCADA system
the power supply module is designed to power a conventional analogue radio with
a disconnected (faulty) battery
it is therefore possible to warn the control centre during a battery fault
(end of life, etc.) and to begin corrective maintenance.

Power supply characteristics


AC power supply
Supply voltage: 90 to 240 Vac, 50 Hz (43 and 57 Vac available as an option)
Input protected by 4 A HPC fuse (type G)
Connection to fuse terminal block inside the enclosure.
Motor mechanism power supply
Supply voltage: 48 or 24 Vdc 10%
Current: 16 A for 50 ms and 6 A for 15 s
Protection by time-delayed 5 A fuse (48 V) or time-delayed 10 A fuse (24 V).
Telecommunication equipment power supply
Supply voltage: between 10.8 V and 14.8 V
Available current: 1 A continuous; 7 A peak
Protection by delayed 4 A fuse.
Battery
Temperature-compensated charger
Charging time: 24 hours
Type: sealed lead 12 V, 24 Ah
Lifetime at 20C (as specified by the manufacturer): 10 years.
Battery autonomy
16 h without mains power supply for Easergy T200 I & E 4-channel with radio
remote transmission equipment
8 h without mains power supply for Easergy T200 I 16-channel with radio remote
transmission equipment
Ability to perform 10 open/close cycles at the end of autonomy (in normal
operating conditions: batteries fully charged before loss of AC supply).

T200ie_PCRED398085EN.indd 8

PCRED398085EN

28/05/2013 15:59:16

Easergy T200 I & E

Switchgear control-command

PE57941

Direct connection by connectors

Information can be acquired and orders passed on via a direct connection between
the control unit and the switch. The connections are made using removable
connectors (polarised on T200 I) which enable:
Fast and secure installation
Simple start-up, with the control system, by fitting a simulator in place
of the switchgear
Reliable operation and maintenance due to servicing operations which
do not require a screwdriver.

Switchgear control-command

PE57942

Management of different types of switches (SM6, RM6, FBX, Fluokit, Flusarc)


Single or dual control switches:
open position - closed position
earth isolation position
free input (voltage presence relay for automation system)
These inputs are connected to the switches via connection cords.
This data is received by 0V polarity.
Available voltages: 48 Vdc, 24 Vdc
Opening or closing orders by 0V or +V polarity or by current loop.

Local operator panel


Display of information by coloured LEDs
Equipment fault
Switch position: open, closed, inconsistent, locked
Fault current detection
Automation system on/off
Ua and Ub voltage presence
Automation system locked
Local or remote operating mode
Additional indication status.
Selection of remote or local operating mode
A rotary switch is used to select the operating mode:
Local: the command from the operator panel is confirmed. Any order from
the remote control centre is locked.
Remote: local commands are not permitted. Orders from the remote control
centre are validated.
Switch control
The switch must be in the local position. The control and validation buttons
must then be pressed at the same time.
Automation system activation
The automation system is activated and deactivated by pressing the control
and validation buttons at the same time.
Detector reset and indication test:
The reset button resets the fault detector
The test button checks all indications.
Connecting the PC to the front socket allows
internal data and parameter settings
to be consulted during commissioning

Additional information

6 general-purpose digital inputs per 4-channel control module (max. 24)


1 digital input for the fault detector RESET function
1 relay output to RESET an external fault detector
1 powered output for pulsed illumination of an external LED indicating
the detection of a fault current (visibility: 50 m; flashing period: 1 s).
These inputs are connected to a screw terminal block located on the interface
module front panel.
Note: when an automatic transfer system is used, certain inputs/outputs
are reassigned as follows:
If generator ATS automatic transfer system:
one dedicated relay output for control of a generating set
one digital input dedicated to retrieval of generator power-on information
one dedicated digital input to manually force switchover to the generator
channel
If network or generator ATS automatic transfer system:
One dedicated digital input to enable channel paralleling.

PCRED398085EN

T200ie_PCRED398085EN.indd 9

28/05/2013 15:59:16

Fault current detection


and measurement

Easergy T200 I & E

PE57943

One of the following modules can be linked to each channel (switch):


A current measuring and fault current detection module
A single-phase or three-phase voltage measuring module
A digital input acquisition module.
Combinations of these modules can be used. The module type is detected
automatically.

Current measurement and fault current detection

T200AT

T200AC
T200AD

MT10040

Acquisition modules for internal or external


current detection:
T200-AC, AS or AH: current measurement
T200-AD: acquisition of data from an external detector
T200-AT: acquisition of 3 phase-to-neutral voltages
from aVT.

1
2
3
4

1 Ja I1
2
I2
I3
3
I4
4

T200-AC
SW1

DE56657

1 current transformer on each phase

1
2
3
4

1 Ja I1
2
I2
I3
3
I4
4

T200-AS
SW1

DE56658

2 phase current transformers, 1 core balance CT

1
2
3
4

1 Ja I1
2
I2
I3
3
I4
4

PE57787

1 core balance CT

T200-AH
SW1

Current measurement and fault current detection on a single channel requires


the installation of a kit comprising:
A current acquisition card which is installed on the switchgear interface card. This
module provides direct acquisition and electrical isolation of the signal from the
current transformers.
A set of current sensors comprising (depending on the chosen assembly):
3 phase sensors
2 phase sensors and 1 zero sequence sensor
1 zero sequence sensor.
The current measurement kits are ordered separately from the T200 control unit.
They can be added later on site without modifying the Easergy T200 configuration.
Phase-to-phase and phase-to-earth fault current detection
Detection thresholds and sensing times are configurable.
Memorised faults can be cleared:
by remote control
by a time delay configurable for each channel
by return of AC supply configurable for each channel
by manual action on the operator panel.
Faults are indicated:
by the red LED opposite the rack
outside the station by flashing light
remotely via the communication protocol to the SCADA system.
Load current measurement on the line
The load current on the MV line measured by the detectors current sensors
can be recorded and sent to the control centre.
The measurements can be recorded in various ways (see Management
of variables).

Voltage measurement and monitoring

In addition to LV power supply presence monitoring by the supply module,


there are two options for measuring and monitoring the medium voltage:
From measurement voltage transformers
the voltage acquisition module T200-AT is responsible for the acquisition and
isolation of the three phase-to-neutral voltages produced by the measurement
voltage transformers
detection of voltage drops and presence of a residual voltage. The detection
and presence thresholds are configurable.
this option can be added at a later date on site.
From the LV power supply source for the Easergy T200 I unit
the measurement is scaled to provide a picture of the MV voltage
the detection and presence thresholds are configurable
this option has to be ordered with the control unit. It is installed on the last channel
of the control unit.
Voltage presence monitoring via capacitive dividers
Reconfiguration systems such as the power supply source changeover switch
require monitoring of three-phase voltages on the various channels.
In such a case we use the Easergy VD23 voltage presence relay,
which can be found in the accessories section.

External voltage presence relay VD23

10

T200ie_PCRED398085EN.indd 10

PCRED398085EN

28/05/2013 15:59:17

Easergy T200 I & E

Fault current detection


and measurement
(cont.)

PE40652EN

Characteristics

Application
Network
4 to 36 kV
Frequency
50 or 60 Hz
Current measurement and fault detection
Types of current sensors
Assembly A: 3 phase current sensors
Assembly B: 2 phase sensors and 1 zero sequence
sensor
Assembly C: 1 zero sequence sensor
Assemblies A and B phase fault
Configurable from 100 to 750 A in 50A steps
Zero sequence fault
Assembly A Configurable from 20 to 160 A in 1A steps
Assemblies B and C Configurable from 5 to 160 A in 1A steps
Sensing time: ST
50 to 800 ms in 25 ms steps
Reset
Automatic voltage return Configurable Yes/No
After delay Configurable from 15 min to 2 h in 15 min steps
Remote Yes
Local Yes
Indication
Remote Phase fault, zero sequence fault
Local Summary by LED on rack front panel, details via PC
Retrieved measurements
Average current per channel
Voltage measurement and monitoring
Type of measurement
Single-phase from the power supply source
Three-phase from the measurement VT
Input voltages
From VT 110 V/3
From LV 230 Vac
Scaling
50 V to 30,000V configurable
Detection threshold
Loss threshold 20 to 95%
Residual voltage (T200-AT) 5 to 50%
Retrieved measurements
1U per channel
Memorisation and processing of measurements
Periodic recording
On sample or averaged value (configurable)
Period: 10 s, 30 s, 1min, 15 min, 30 min or 1h
High and low thresholds
Configurable from 0 to 750 A
Dead band (variation of I)
Configurable from 1 to 100% of the value read
Min. and Max.
Configurable for 1, 7 or 14 days
Accuracy of measurements (excluding sensors)
Current and voltage measurements
3%
Fault current detector
3%

PCRED398085EN

T200ie_PCRED398085EN.indd 11

11

28/05/2013 15:59:17

DE40552FR

Easergy T200 I & E

Preset Automation systems

Current

The T200 can include two types of automation systems:


preset automation systems: some automation system functions are factory defined
and integrated (optional) in the basic functions of the T200. These functions require no
on-site programming. They correspond to known operations widely used for the MV
substation switch management application.
an IEC 61131-3 programmable logic controller: an RTU Control programming
workshop is used to create automation functions in addition to the preset ones of the
T200, in order to create and tailor specific applications.

Execution time

Voltage
drop

Note: the T200 can be controlled either with the preset automation systems or with the built-in
IEC61131-3 programmable logic controller, but exclusively. In either case, the calculation
formula function is included as a standard feature (see page 15).
Time
Configurable parameters:
Number of faults: from 1 to 4
Execution time: from 20 s to 4 mins configurable
in 5 s steps
Automation system valid/invalid.

The automation systems can be switched on and off from the local operator panel
and disabled using the configurator.
Switches can be controlled manually in the following circumstances:
automation system switched off
switch in local mode.

Sectionaliser (SEC)
DE56654

The sectionaliser automation system opens the switch after a predefined number of
faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker.

SW1

SW2

The automation system counts the number of times a fault current followed
by a voltage loss is detected. It sends an open order if:
the switch is closed
the fault has disappeared
the MV supply is absent.
The automation system is reset at the end of the execution time delay.

12

T200ie_PCRED398085EN.indd 12

PCRED398085EN

28/05/2013 15:59:17

Preset Automation systems

Easergy T200 I & E

DE59320FR

(cont.)

Vn

ATS automatic transfer system (source changeover)

SW2 voltage

O
Vn

The automatic transfer system performs automatic control and management of


sources in the MV secondary distribution network.
Two possible versions for ATS:

SW1 voltage

Network ATS version: control of two MV network channels.


The network ATS automatic transfer system requires use of
the VD23 relay for detection of voltage presence/absence.
NB: the VD23 relay cannot be used with a Ringmaster
type cubicle.

O
C

T1

O
C

TR

TR

SW1

TR

Generator ATS version: control of one network channel and


one generating set channel (not available on T200 E).

T1 TR

SW2

Network ATS - Semi-Auto Mode


(without paralleling upon automatic return)
TR: switch response time

Note: ATS automatic transfer system is available only on channels 1 and 2 of each
CONTROL module. Generator ATS automatic transfer system is available only on
the first CONTROL module (channels 1 to 4).

Vn

Operating modes

SW1 voltage

The operating mode is selected from the T200 Web server.

O
C

T1

SW1

TR

C
O

TR

T2

Mode SW1SW2 or SW2SW1 (or SWSWG if Generator ATS):


Automatic transfer system executes only one changeover from the priority channel
to the backup channel. Automatic transfer system then remains on that channel.

TR

Semi-Auto mode SW1SW2 (or SWSWG if Generator ATS):


In the event of a voltage loss on the active channel, automatic transfer system
switches to the other channel after a time delay T1. Automatic transfer system
executes no return, except in case of voltage loss on the new active channel.

TR

SW2

Network ATS - Auto Mode SW1


(with paralleling upon automatic return)
TR: switch response time
Vn

DE59321FR

0
1
0
Vg
0
C
O

Auto SW1 or Auto SW2 mode (or Auto SW if Generator ATS):


After a changeover, return to the priority channel occurs if the MV voltage on that
channel is restored. The channel that has priority can be defined according to
the state of a dedicated digital input.

SW1 voltage
T1

Tg1

Tg2

GE voltage
TR

TR

C
O
C
O

TR
TR

Changeover sequences:

6s

GE Command

SW

T2 TR

SWG

T2 TR

SWG

Generator ATS - Auto SW mode


(Without paralleling upon Auto return)
TR: Switch response time
Tg1: Generator starting time (maximum 60 s)
Tg2: Generator stopping time
Case : Generator channel closing after Generator power on
(configurable option)
Case : Generator channel closing after Generator start-up
command (configurable option)

PCRED398085EN

T200ie_PCRED398085EN.indd 13

Network ATS: in the event of voltage loss on the normal channel, changeover involves
opening the normal channel after time delay T1 and then closing the backup channel.
Note: in Auto mode, the sequence of return to the normal channel depends on
configuration of the Paralleling upon auto return option (see below).
Generator ATS: in the event of voltage loss on the network channel, changeover
involves sending the order for opening the network channel and at the same time
the Generator start-up order, after time delay T1.
The remainder of the changeover sequence depends on the management of
Generator channel closing (configurable option):
Case of Generator channel closing after start-up order:
After the Generator start-up order, the closing order is given to the Generator
channel, without waiting until the Generator is actually started.
Case of Generator closing after Generator power on:
The Generator channel closing order is sent only when Generator voltage is
detected.

13

28/05/2013 15:59:17

Preset Automation systems

Easergy T200 I & E

(cont.)

Configurable parameters:

1
2
3
4
5
6
7
8
9
10
11
12

DI 1

DI 2

Priority channel

DI 3

Genset voltage presence

DI 4

Parallel connection input

DI 5

Genset forcing

DI 6

The DIs can be assigned


for ATS automation
(configurable options)

Digital Input connection


(J2 or J10 terminal block)

DE56806

DE59175

Automatic transfer system ON/OFF


Operating mode: Semi-Auto, Auto SW1, Auto SW2,
SW1 > SW2, SW2 > SW1
T1: 0 ms to 2 min. in increments of 100 ms
T2: 0 s to 30 min. in increments of 5 s
Disabling/enabling transfer upon fault detection:
Choice of voltage presence detection: DI4 or VD23
Channel connected to generator: SW1 or SW2
Type of automatic transfer system: Network ATS
or Generator ATS
Manual control enabled/disabled if ATS in operation
Paralleling enabled/disabled in auto and/or manual
mode
Choice of type of changeover to Generator:
immediately or after detection of Generator power on

Paralleling upon Auto return

A software-configurable option allows the automatic transfer system to disable


or enable paralleling of the channels upon automatic return to the main channel
(in Auto mode).
Enabling of paralleling must be confirmed by the activation of a dedicated digital input.
Paralleling disabled: Auto return to the priority channel involves opening the backup
channel and, when it is open, closing the priority channel.
Paralleling enabled: Auto return to the priority channel involves first closing
the priority channel and, when it is closed, opening the backup channel.

Changeover conditions

Changeover takes place if the following conditions are met:


Automatic transfer system in operation
SW1 open and SW2 closed or SW1 closed and SW2 open
Absence of fault current on the two channels (only if locking by fault detection
option activated)
Transfer locking absent
Earthing switch absent on the two channels
MV voltage absent on the active channel
MV voltage present on the other channel.
Return to the main channel for the Auto modes occurs if:
The priority channel is open
The MV voltage on the priority channel is present during time delay T2.

Generating set connections

Relays are installed in factory in the T200 enclosure to provide interfacing with
the generating set (Generator ATS version only). Connection should be performed
as follows (see diagram opposite):
Voltage: contact closed if Generator started, to be wired on the two available
terminals (do not wire if detection of power on is performed by a relay VD23)
Start-up: Generator start-up order, to be wired on terminals C and B
Stop: Generator stoppage order, to be wired on terminals D and B.

Detection of voltage presence

Voltage presence on a channel managing the Generator can be executed by


two processes:
Either by a dedicated Voltage digital input
Or by voltage relay VD23 (via cubicle cable).
Terminal block T200
C

Override setting on generator (Generator ATS only)

For routine test or reduced pricing requirements, it is possible to perform override


setting of operation on the generator manually, remotely (from the supervisor) or
locally (activation by a dedicated digital input).
When the override setting is terminated, the automatic transfer system places itself
back in the initial mode, i.e. in the mode that was active before the override setting
(ON or OFF). During override setting, the automatic transfer system is set to ON
for channels 1 and 2.

Source transfer locking


Voltage

Stop

A dedicated digital input allows changeover to be locked if a problem occurs on one


of the devices related to the changeover. This input is generally connected to the
downstream circuit breaker. Local and remote controls are no longer possible
in this case.

Start-up
Genset

Specific Generator-related management


Generator Stop
Start
started
generator generator
contact
order
order

DE59173

G
Source transfer locking
DO 1
Stop/start generator order

1
2
3
4
+5
6

Upon transfer to the Generator, if the latter doesnt start, the automatic transfer
system waits for a period of 60 s at most before stopping changeover, then:
in SW SWG mode: the automatic transfer system is locked and must be reset
(on the Control panel) to restart the device.
in SW SWG mode or in Auto mode: the automatic transfer system remains
operational.
If voltage returns to the network channel, the automatic transfer system requests
return to the network channel.
When the automatic transfer system is configured with auto return on the
network channel, Generator stoppage is requested 6 s after the changeover
sequence is completed.

Lock connection (J1 terminal block on the 4-ways interface


or J9 on the 2-ways interface)

14

T200ie_PCRED398085EN.indd 14

PCRED398085EN

28/05/2013 15:59:17

Easergy T200 I & E

Preset Automation systems


(cont.)

DE56655

Bus tie coupling (BTA)


SW1

SW3

SW2

The BTA (Bus Tie Automatism) is an automation system for switching sources
between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3).
It must be used in conjunction with VD3H type voltage presence detectors and the
fault current detection function on the busbar incoming lines.
NB: the VD23 relay cannot be used with a Ringmaster type cubicle.

Operating mode
Normal position

SW1

SW3

SW2

Two operating modes can be configured:


Standard mode:
If the voltage is lost on one busbar, the automation system opens the incoming line
(SW1 or SW2) and closes the coupling switch SW3. Coupling is conditional upon
the absence of a fault current on the main source.
Interlock on loss of voltage after switching mode:
After execution of the automation system in standard mode, the voltage presence is
checked for a configurable period. If the voltage is lost during this period,
the coupling switch SW3 is opened and the automation system interlocked.

Coupling sequence

DE59322EN

Active coupling

SW1
V2
V1

SW3
SW2 voltage

SW2

SW1 voltage

O
C
O

T1

C
O

SW1
T3
SW3

T2

Configurable parameters:
Operating mode:
Standard/locking upon voltage loss
Automatic return: SW1/SW2
Automation system: on/off
Delay before switching
T1: 100 ms to 60 s in 100 ms steps
Delay before return
T2: 5 s to 300 s in 1s steps
Interlock delay on voltage loss
T3: 100 ms to 3 s in 100 ms steps
Motorisation type: command time
Manual control: enabled/disabled in local and remote modes
if automation system in operation
Paralleling: enabled/disabled in auto and (or) manual modes
Transfer locking upon fault detection.

Coupling takes place if the following conditions are met:


the automation system is switched on
the switches on incoming channels SW1 and SW2 are closed
the earthing switches SW1, SW2 and SW3 are open
there is no voltage on an incoming line SW1 or SW2
there is no fault current detection on SW1 and SW2
there is no transfer interlock
voltage is present on the other incoming line.
The coupling sequence in standard mode is as follows:
opening of the de-energised incoming line switch after a delay T1
closing of the coupling switch SW3.
The coupling sequence in Interlock on loss of voltage after coupling mode i
s completed as follows:
monitoring of the voltage stability for a delay T3
opening of the coupling switch SW3 if this condition is not met
locking of BTA automation system.
The system returns to standard mode after coupling if:
the return to SW1 or SW2 option is activated
voltage on the channel has been normal for a delay T2
the automation system is activated
the automation system is not locked
there is no coupling interlock.

Coupling interlock

A dedicated digital input allows changeover to be locked if a problem occurs


on one of the devices related to the changeover. This input is generally connected to
the downstream circuit breaker. Local and remote controls are no longer possible
in this case.
Locking the automation system
The BTA automation system is locked if one of the following conditions is met during
the coupling process:
Failure of a command to open or close a switch
Indication that an earthing switch has closed
Appearance of a fault current
Switch power supply fault
Appearance of the coupling interlock
Manual or remote ON/OFF command from the automation system.

Paralleling upon Auto return

A software-configurable option allows the automation system to disable or enable


paralleling of the channels upon automatic return to the main channel (in Auto mode).
Enabling of paralleling must be confirmed by the activation of a dedicated digital input.
If paralleling is disabled: Auto return to the normal channel involves opening
the coupling channel (SW3) and, when it is open, closing the normal channel.
If paralleling is enabled: Auto return to the normal channel involves first closing
the normal channel and, when it is closed, opening the coupling channel (SW3).

PCRED398085EN

T200ie_PCRED398085EN.indd 15

15

28/05/2013 15:59:17

Programmable Automation
systems

Easergy T200 I & E

EM100041EN

RTU Control programmable logic controller

Optionally, the T200 can incorporate the IEC 61131-3 programmable logic controller.
This allows the user to create specific tailored client applications.
The existing variables of the T200 that can be used in the programmes are:
TSD, TSS, TM, TSL, DI, DO
Virtual variables can also be created for the PLC programmes. T
hey can also be type: DI, DO, DDI, DDO, AI, AO.

DM101151EN

A specific development platform (RTU Control) is provided (on the Easergy CD


supplied with the equipment) to create or modify a PLC programme from the
following programming languages:
SFC Sequential Function Chart
FBD Function Block Diagram
LD
Ladder Diagram
ST
Structured Text
Il
Instruction List

Embedded
PLC
RTU Control :
development
platform

Programs
download

The platforms programme can be loaded onto the equipment and then checked via
the T200 Web server. A specific page is used to manage the programme (start, stop)
as well as the associated variables and another page is used to create and manage
the calculation formulas.

Variables exchanges

T200/F200C software

Inputs/outputs from internal I/O


or from an external PLC

Typical applications that can be created with the programmable logic controller are:
MV automatic loop reconfiguration (self-healing network).
Automation systems similar to those described previously (ATS, BTA): ATS
between two T200s or involving more than 2 channels, for example.
Load-shedding applications.
All other automation systems: voltage time, client-specific automation systems.

EM100042EN

Communication between equipment

The programmable automation system option also includes a complementary


function for communication between equipment including a Modbus exchange via a
TCP/IP link between T200s and/or Flair 200Cs connected on the same MV loop.
This communication allows the exchange of a data table between these T200s and/
or Flair 200Cs, for instance in order to contribute (with no other PLC than the T200s
and/or Flair 200Cs) to an automation system function serving to detect and remove a
current fault on an MV loop. This communication between equipment is typically
used self-healing network applications.
A specific page on the T200 server is used to define the exchange table and this
functions operating parameters.

Calculation formulas
EM100043EN

The calculation formulas are available as a standard feature in the T200.


They can be used in the T200 to create relatively simple logic equations not requiring
a programme to be written in PLC language.
These formulas can be used to create logic equations based on combinations of
variables more simply than a PLC programme. The variable types that can be used
are the same as for PLC programmes (existing variables or virtual variables created
specifically).

EM100044EN

Examples of typical applications that can be created with the calculation formulas:
Calculation of analogue values to determine averages, alarms or any other
calculation based on variables.
Combinations of variables, such as:
Combining phase and neutral faults rather than indicating them separately
Defining a synthesis of internal faults
Managing other equipment of the MV substation such as the light control, etc.
The following functions can be incorporated in the formulas:
Mathematical functions: absolute value, square root, natural logarithm, base10 logarithms, exponentials, powers, integer part, etc.
Statistical functions: smallest and largest values, sum and average of values,
etc.
Logic functions: set duration pulse, status copy after a set time, status hold for
a set time, etc.
Time/date functions: current date and time, character string converted into
date and time, time between two executions of formulas, test whether current day
is a working day, etc.
Other functions: values bounded by min and max, delta between previous and
current value.
16

T200ie_PCRED398085EN.indd 16

PCRED398085EN

28/05/2013 15:59:19

Management and
time-stamping of variables

Time-setting and time-stamping

Archiving events and measurements

A T200 can be time-stamped in one


of the following ways:
Locally using the laptop
By the remote control system
Via the Ethernet network
By an internal GPS (available as an option)
with time-stamping :
time zone management
summer/winter time management.
precision of time stamping:
resolution : 1 ms
discrimination between 2 events: 10 ms.

Events log: information transmitted to the SCADA system


Variables configured as events are recorded in this log.
They are transmitted to the control centre according to the protocol exchange
conditions.

PE56283

Easergy T200 I & E

All data (variables) from the T200 or from the local Modbus network can be recorded.
The recording and transmission mode for each variable can be configured.
This data is recorded in four logs for transmission to the SCADA system
or for viewing locally:

Alarm log: spontaneous transmission


Alarm configured variables spontaneously trigger a call from the control centre.
These variables are also recorded in the events log.
System log: this can be consulted locally and is intended for maintenance and
operation procedures, such as memorising transmission events, transmission
errors and system configuration modification.

GPS

Measurements log:
Measurements configured as records are stored in this log.
Measurements configured as events and alarms are also recorded
in the relevant logs.
The archive logs can be consulted locally and remotely via the Easergy T200
web server configurator and can be downloaded in Excel format.
Criteria for recording variables
Alarm log

Events log

TSD

TSS

Measurements Criteria
log

Indication

Control centre

On change of state
On loss of closing
On activity
On inactivity
Time-delayed
Alarm level: 1 to 3
e.g., SCADA, GSM, or GSM
and SCADA transmission

Measurements

Period: 10 s, 30 s, 1min,
15 min, 30 min or 1h
High and low
Value as %
1, 7 or 14 days

PE40648EN

PE40649EN

Periodic

or average
On thresholds

Dead band

Min. and Max.


Note: criteria can be combined.

PCRED398085EN

T200ie_PCRED398085EN.indd 17

17

28/05/2013 15:59:19

Easergy T200 I & E

Management and
time-stamping of variables
(cont.)
Counters
A counter can be declared for each remote indication (TS) and remote measurement
variable internal to the T200 or coming from a device connected to the local network.
Counters can therefore be declared in order to establish:
The number of operations of a switch
The number of fault current passes
etc.
There are 5 types of counter
Counters for digital data TSS
pulse counter: counts the number of high or low state transitions (configurable) by
a TSS. The theoretical scan interval for this counter is 10 ms
time counter: counts the time spent in the high or low state by a TSS
integrator counter: counts the number of high or low state transitions by a TSS
in each integration period.
Counters for analogue data
integrator: totals the associated TM every second
average: calculates the average for a TM over the last integration period.
The counter reading can be:
Sent to the control centre if the protocol permits it
Viewed on the display page of the operating software
Modified from the control centre or the control page of the operating software.

Event storage capacity


Events
Alarms
System
Measurements

10000
2000
6000
30000

For all logs, when the storage capacity is reached, the most recent event
clears the oldest from the list.

18

T200ie_PCRED398085EN.indd 18

PCRED398085EN

28/05/2013 15:59:19

Communication

Easergy T200 I & E

PE57933

Communication protocols

The communication module manages a serial type protocol and IP protocols


at the same time.
Example: IEC 870-5-101 and IEC 870-5-104.
It is therefore possible to mix standard and IP transmission media.
Communication protocols can be downloaded, which simplifies procedures
for updating versions. Two versions are embedded, which protects downloading and
switching.
The range of communication protocols is continually updated and includes:
IEC 870-5-101 and IEC 870-5-104
Level 3 Serial DNP3 and TCP/IP
Serial Modbus and TCP/IP with non-permanent communication management
Several proprietary protocols (please contact us).

SCADA

Communication
networks: radio, PSTN,
GSM/GPRS, 3G,
Ethernet, etc.

Protocols:
IEC, DNP3,
Modbus, etc.

: In GPRS/3G, the protocols manage the Permanent or Semi-permanent transmission


mode. The Modbus TCP/IP and DNP IP protocols can also manage the transmission mode Non
permanent serving to limit data flows.

Multi-channel SCADA communication


Three available communication ports

Easergy T200 I can manage up to three communication ports and ensure multi-site
redundant communications.
Ports 1 and 2: support all the transmission interfaces available in the product
range.
Ethernet port 3: this port is available for communication with the control centre
using an IP protocol and Ethernet transmission interfaces.
It can also be used for configuration and local operation.
Management of 3 virtual IP addresses on the Ethernet port for multi-SCADA access.

RS485 Modbus local network

Management of the various transmission modes

The ports can be configured to be used with single or redundant channels:


One SCADA communication channel

Normal/standby

Two SCADA communication channels


Used with different transmission media.
Two operating modes:
symmetrical: T200 I changes to the other
channel when there is a fault on the active channel
automatic return: dissymmetrical with or
without automatic return: one channel is declared
as the main channel and the other is the standby
channel. After changeover, the return to the main
channel is:
manual (local or remote reset) with the no return
option
automatic once the cause of the changeover
has disappeared with the with return option.

PE40651EN

Normal

PCRED398085EN

T200ie_PCRED398085EN.indd 19

19

28/05/2013 15:59:20

Easergy T200 I & E

Communication
(cont.)

Transmission interface range


Integrated modems
Modems and interface
RS232 serial interface

Technical characteristics
Non-isolated
Max. transmission speed : 38,400 bits/s

Telephone modem (PSTN)

V.32 bis standard


300 to 14,400 bits/s
Isolation: 8 kV
FSK V23 modulation
200 or 600-1200 bd
Receive level: - 30 to + 10 dBm on 600 Ohms
Transmission level: - 10 dBm or 0 dBm
Reception access impedance: 600 Ohms or high impedance
FFSK modulation
1200 - 2400 bd
Receive level: - 30 to + 10 dBm on 600 Ohms
Transmission level: - 10 dBm or 0 dBm
Reception access impedance: 600 Ohms or high impedance
FSK V.23 modulation: 600 - 1200 bd
V.24 interface
2-wire half-duplex or 4-wire full-duplex transmission
Line impedance: 600 ohms or high impedance (10 kohm)
Carrier loss detection: 10 ms
Carrier presence detection: 15 ms
Isolation: 8 kV
Dual-band modem GSM and GPRS (or four bands 900/1800/850/1900 MHz, availability to be confirmed)
Triple-band collinear aerial with 6-dB gain
and 5-m cable - Indoor/outdoor installation

FSK radio modem

FFSK radio modem

Multidrop private dedicated line modem


(DL)

GSM/GPRS modem

Main functions
Direct connection and management of
external transmission equipment
Direct: radio modem
Hayes: telephone, GSM
Signal management:
Rx, Tx, DP, CPD, PDP, DPE, PAE, IA
Message repetition (3)
Main call number
Backup call number
Signal management:
Rx, Tx, squelch, DP, DPE
Parity, frame errors
Test mode
Carrier generation
Signal management:
Rx, Tx, squelch, Em cmd
Parity, frame errors
Test mode
Carrier generation
Management:
Parity, frame errors

Transmission data:
Message repetition (3)
Main call number
Backup call number
SMS transmission (in GSM)
Management of IP protocols

GSM/3G modem

Four-band modem in GSM: 900/1800/850/1900 MHz


Five-band modem in 3G: UMTS and HSPA+ (3.75G), EDGE,
GPRS and GSM (800/850/AWS/1900/2100 MHz)
- Colinear antenna with 6-dB gain
and 5-m cable - Internal/external installation

Transmission data
Message repetition (3)
Main call number
Backup call number
SMS transmission (in GSM)
Management of IP protocols

Ethernet port

10 base T/100 base T - TX (RJ45)


10/100 Mbits

Management of IP protocols

External modems and transmission equipment


T200 manages any type of modem or transmission equipment via the RS232
or Ethernet connection.

Local communication network

An optional master port or the Ethernet port is used to communicate with the various
substation equipment (slaves).
Protocol: Modbus master
Port: RS232/485 or Ethernet
Equipment examples:
Sepam or other digital protection relay
PLCs
remote I/O for acquiring additional information
T200 slave in the same substation or nearby substation
metering unit
Easergy G200 and Flair 200C.
Local network
Protocol
Number of slaves
Maximum number of TAG

20

T200ie_PCRED398085EN.indd 20

Modbus master
31 in RS485 or Ethernet connection
Digital inputs: 300
Digital outputs: 100
Analogue inputs: 200
Analogue outputs: 100

PCRED398085EN

28/05/2013 15:59:20

Easergy T200 I & E

Configuration and operation

Local and remote configuration


Software download
Configuration download
Offline configuration

Embedded web data server

PE40650EN

Configuration, operation and diagnosis are carried out by connecting a laptop


equipped with a web browser. Internet Explorer version 6, 8 or 9 is required running
in Windows XP or Seven.
The menu on the home page enables the user to select the menu display
language.
Access is secured by entering a login name and password.
The web data servers HTML-format pages are used to:
display page: view states and measurements
control page: issue open/close orders and counter preset commands
diagnostic page: read and save archives
maintenance page: substation parameters, software version update, configuration
download, network analyser
parameters page:
Communication configuration, protocol, switch control, measurement and detection,
PLC, communication between equipment, calculation formulas, etc..

Remote and local connection

PE56298

Local access is achieved by connecting the PC to the USB or Ethernet port.


Access to remote data parallel to the control system is possible via the GSM,
GPRS, 3G, Ethernet or PSTN transmission networks regardless of the
communication protocol.
With local connection, pages are refreshed automatically either cyclically
or on a change of state. The embedded web server is used for local supervision
of the substation.

On-site
maintenance

GSM/GPRS
SMS Alert

Radio

SCADA
Control centre

PCRED398085EN

T200ie_PCRED398085EN.indd 21

3G/GSM/GPRS
PSTN
Ethernet/Intranet

Maintenance and
operation service

21

28/05/2013 15:59:20

Configuration and operation

Easergy T200 I & E

PE56301

(cont.)

DB generation of T200
Save DB

Data configuration

Easergy T200 is supplied with a factory-tested preconfigured database.

Configuration by web server

PE40653EN

On-site or
remote
configuration

Preparation of
configurations

Customisation of standard configurations and preparation of offline configurations


preparation of the standard database
preparation of site configurations.
Configuration by downloading files
loading the predefined configuration
saving the definitive configuration after commissioning.
The configurable parameters are:
switch management: command type, measurement sensors, fault current
detectors, voltage presence, automation systems
communication: protocol type, port operating mode, modem type, protocol
parameters, exchange table
variables: labels, address, associated information (remote controls), access type
(user session, administrator, etc.), definition of states and recording criteria
classes: customisation of display and command pages (variables are grouped
and presented in classes).
PLC: PLC programming, programme control, management of variables and
memory.
Calculation formulas: creation of formulas through combination of variables,
management of the refresh period.
Communication between equipment: definition of the data exchange table and the
communication parameters between T200.

Configuration by the SCADA system


PE40654EN

Some parameters are designed to be modified by the SCADA system via the
communication protocol. These are mainly parameters connected to network
operation:
Fault current detection thresholds and voltage monitoring
Measurement recording value for min., max. and dead band thresholds.

Operation and control

Alongside operation and control of the network from the SCADA system, it is also
possible to operate the equipment locally or remotely using three pages:
Display of states and measurements
Issuing commands: switches, counters (initialisation), automation system on/off,
fault detector reset and other digital outputs. The issuing of commands is made
secure by a selection and confirmation process.
Consultation of transmitted and archived data
on-screen consultation of archive logs
extraction of logs on a PC as an SCV file for analysis.
The views are refreshed periodically or automatically on a change of state.

Maintenance
Update of software versions or change of protocol
A new version of the communication card software or protocol can also
be downloaded from a PC. Two software versions are saved. It is possible
to switch between the two versions.
System events log file analysis
Memorisation of transmission events (to determine the origin of a recurrent
communication fault)
Indication of transmission errors (CRC error, collisions, PSTN line disturbance,
redundant changeover, etc.)
Indication of system events (T200 start-up, T200 reset, configuration modification,
etc.).
Communication analyser
This analyser observes the frames exchanged on ports 1 and 2 with the control
centre.

22

T200ie_PCRED398085EN.indd 22

PCRED398085EN

28/05/2013 15:59:21

Easergy T200 I & E

General characteristics

T200 I

T200 E

Controllable switch

1 to 16 channels

1 to 4 channels

Information via switch

Open/close orders
Open/closed positions
Earthing switch status

Additional information

6 digital inputs per control module

Capacity

Electrical and mechanical characteristics


AC voltage input
Dielectric

Electromagnetic

Climatic

IEC 60 255-4

Insulation (50 Hz/1 min): 10 kV


Surge (1.2/50 s): 5 kV

Toroid input

IEC 60 255-4

Insulation (50 Hz/1 min): 2 kV


Surge (1.2/50 s): 5 kV

Fast transient bursts

IEC 61 000-4-4

Level 4: 4 kV (mains, sensors),


2 kV (other circuits)

Electrostatic discharge

IEC 61 000-4-2

Level 3: 6 kV on contact

Electric fields

IEC 61 000-4-3

80 MHz to 1 GHz - 10 V/m

Radio frequency in MC

IEC 61 000-4-6

0.15 MHz to 80 MHz - 10 V rms

Damped oscillatory waves

IEC 61 000-4-12

2.5 kV common mode, 1 kV differential mode

Pulsed magnetic field

IEC 61 000-4-9

1000 A/m peak

Surge

IEC 61 000-4-5

Coupling between line wires 1 kV, between wire and frame 2 kV

50 Hz magnetic field

IEC 61 000-4-8

30 A/m

Operating temperature

93% at 40C, 96 h
IEC 60 068-2-11

Storage temperature

Mechanical

336 h at 35 C

Vibrations

IEC 60 068-2-6

10 to 500 Hz 1 g; 10 cycles 10 min

Dimensions

H x W x D (mm)

1 to 4 channels: 670 x 310 x 335 465 x 380 x 275


8 to 16 channels: 670 x 620 x 335

Protection

T200ie_PCRED398085EN.indd 23

192 h at 35C
25C to + 70C

Weight

PCRED398085EN

100 A/m

15C to + 55C

Relative humidity
Salt mist

80 MHz to 1 GHz - 30 V/m

IEC 60 529

2 and 4 channels: 40 kg
16 channels: 70 kg

4 channels: 40 kg

IP2x

IP54

23

28/05/2013 15:59:21

Dimensions and mounting

Easergy T200 I & E

1 to 4-channel T200 I enclosure


310
250

670 (1)

520

MT10030

335

(1) Height of 4-channel enclosure: unit supports tamper-proof connectors.

8 to 16-channel T200 I enclosure


560
250

335

760 (4)

670 (3)

520

MT10031

250

620
(3) Height of 8-channel enclosure: connectors mounted in one row.
(4) Height of 16-channel enclosure: connectors mounted in two rows.

DE59172

T200 E enclosure

1
2
3
4

24

T200ie_PCRED398085EN.indd 24

1 Ja I1
2
I2
I3
3
I4
4

T200-AH
SW1

PCRED398085EN

28/05/2013 15:59:21

Mounting of remote
transmission equipment

Easergy T200 I & E

Basic enclosure

240

On the upper right-hand side of the Easergy T200 (A) there is a slot for a transmission
device (modem, fibre optic, etc.).
A sliding plate allows for a variety of possible adaptations.

DE55034

85

Slot A
T200 I : Height = 300 mm; Width = 60 mm; Depth = 220 mm
T200 E : Height = 240 mm ; Width = 140 mm ; Depth = 240 mm

320

DE40553

Connection to Easergy T200


the 12 Vdc power supply for the interface is available at the connector located
on the right-hand side of the rack.
the serial connection is available at the SUB-D 9-pin connector located
on the right-hand side of the rack.
8 channel expansion

Basic enclosure

T200 I (basic enclosure)

240

DE59182

140

B
240

T200 E

A : standard slot for remote transmission equipment, basic enclosure.


B : free space for miscellaneous accessories, 8-channel expansion enclosure
PE57944

(T200 I only).

8-channel expansion T200 I enclosure

The 8-channel enclosure is supplied with a short expansion rack to release


the space to install various types of equipment (B).
Slot B
Height = 500 mm; Width = 180 mm; Depth = 220 mm

Connection
the 12 Vdc power supply is available on the left-hand side of the expansion rack.
a serial Modbus RS485 connection for communicating with local equipment
is also available.

Empty expansion T200 I enclosure

The empty expansion enclosure, supplied with two lateral sliding grids, can be used for
a variety of adaptations.

PCRED398085EN

T200ie_PCRED398085EN.indd 25

25

28/05/2013 15:59:21

Connection equipment

Easergy T200 I & E

PE56296

Current acquisition modules

On the T200 I, current acquisition modules are supplied as a kit comprising


measurement CTs, cable and acquisition card for installation on the interface
module.
Product references
T200-Txx: kit with 3 opening phase CTs
T200-TFxx: kit with 3 closed phase CTs (special RM6 feed-through)
T200-TSxx: kit with 2 opening phase CTs and one opening core balance CT
T200-THxx: kit with 1 opening core balance CT
xx = length of cables supplied with tamper-proof IP2X connectors at each end: 3m,
5 m, 10 m, 15 m, 25 m.
The phase CTs are opening CTs equipped as standard with an automatic holding
system for cable diameters from 30 to 55 mm.
The core balance CT is an opening CT of diameter 125 mm.

Opening CT

Closed CT

Cable
3m
5m
10 m
15 m
25 m

Acquisition
card

On the T200 E, only the acquisition module T200-AC is supplied on option and must
be ordered with the enclosure. The CTs and cables are supplied with the Ringmaster
cubicle.
Available product reference
T200-AC: 3-phase acquisition module.

Voltage acquisition module


Core balance CT

058685N

Kits dacquisition des courants (T200 I)

058686N

Module with 3 additional digital inputs

Single-phase measurement from the power supply (see enclosure reference)


Acquisition module 3V 110 V/3 (reference T200-AT).

Module with 3 additional digital inputs

This module can be installed in place of a current or voltage module.


Acquisition of 3 dry contacts
1 phase fault
2 earth faults.
Card supplied without cable
connection to screw terminal block
installation on interface module.
Reference: T200-AD.

T200 I cubicle connection kit

058687N

Cubicle connection cable (T200 I)

The connection kit for wiring to the cubicle comprises:


one 10-pin tamper-proof connector
one labelled connection cable: cable cross-section 1.5 mm2
This kit is intended for connection to terminal block extensions T-200-B1, T200-B2,
T200-B4.
Product references
T200-CP3: 3 metre cable
T200-CP5: 5 metre cable
T200-CP10: 10 metre cable
T200-CP15: 15 metre cable
T200-CP25: 25 metre cable.
Note: the cubicle connection kit is not supplied with the T200 E, it is an option
to be ordered with the Ringmaster cubicle.

External LED

Additional equipment

External LED
a sealed external LED can be connected to the Easergy T200 to indicate
memorisation of a fault current change:
- the Easergy T200 output is powered to allow rhythmic illumination of the LED
- period 1 s
characteristics:
- sealed 6 V lamp: IP54
- connection by 1.5 mm2 cable (not supplied)
- visibility range (50 m)
Reference: T200-LAMP.

26

T200ie_PCRED398085EN.indd 26

PCRED398085EN

28/05/2013 15:59:21

DE55673

DE55672

Easergy T200 I & E

058689N

USB or Ethernet cable

Accessories

PC connection cables

The cables to connect a PC to the Easergy T200 USB or Ethernet configuration ports
are standard. Three versions are available in the range.
Product references
T200-USB: 3 metre USB-A and USB-B type USB cable
T200-ETH3: 3 metre crossed Ethernet cable for direct PC-T200 connection
T200-ETH10: 10 metre crossed Ethernet cable for direct PC-T200 connection.

Implementation and operation tools


Test socket (Reference: T200-PT)
Test socket

The test socket is mounted in place of a cubicle connection socket on the Easergy
T200 I. It can be used to simulate the presence of a switch by looping control outputs
onto position inputs.
These sockets are used during commissioning for testing the entire communication
chain without actuating the switches.

058690N

Note: functions only on the T200 with 48 V motor pack power supply.

Current simulator (Reference: T200-SIM)

Current simulator

This is used for local testing of the operation of the Easergy T200:
Simulation of a variable phase current from 0 to 750 A
Simulation of a zero sequence current of 40 A, 80 A or 160 A
Simulation of an MV switch and display of its position.
The simulator is supplied with connection cables:
Current acquisition module connection cable
220 Vac mains power cable
Cubicle interface terminal block connection cable.

PE57945

Switch and auxiliary simulator (Reference: T200-ST)

The switch and auxiliary simulator is compatible with all types of power supply and
control logic and can perform all input and output tests for the T200. It is supplied with
connection cables fitted with connectors which come in place of the switch.
The simulator can be fitted without altering the wiring. It is used to:
Simulate control of two switches: open/close order and change of position
Display output states
Simulate digital inputs.

Test case for testing states, voltage and current injection

Switch and auxiliary simulator

(Reference: T200-TESTCASE)
The T200-TESTCASE test case is used to carry out all operational tests on site.
It operates independently using power supplied by the T200. It includes connection
cables and does not require any modifications to the T200 wiring. In addition to
the T200-ST functions, it is also used to:
Simulate a phase-to-phase or zero sequence fault current
Simulate a fault cycle (automation system test).

PE57946

The injection values can be configured in order to carry out all the operational tests
without modifying the T200 database:
Fault current detector: phase-to-phase and zero sequence
Voltage loss and presence detection
Automation systems.
This case includes:
The T200-ST simulator
A programmable voltage and current simulator
Connection cables.

Test case

PCRED398085EN

T200ie_PCRED398085EN.indd 27

27

28/05/2013 15:59:22

Accessories

Easergy T200 I & E

(cont.)

PE57787

Relay VD23

The VD23 is a voltage detection relay for medium-voltage electrical networks from
3 kV to 36 kV, 50 or 60 Hz.
The VD23 is in DIN 96 x 48 mm format and is designed to be installed in the front part
of the cubicle.
Relay VD23 can detect the presence or absence of phase voltage or a phase-tophase voltage imbalance, on line-to-neutral or line-to-line voltage, with choice of
phases to be monitored (one phase or 3 phases).
The VD23 self-adapts to the MV network voltage. No network voltage adjustment
is therefore needed.
It is generally used for automatic reconfiguration systems such as automatic transfer
systems or applications of earthing switch locking upon voltage presence.

DE58735

The VD23 requires the use of a capacitive divider and a VPIS-VO to acquire voltage
measurement. A specific connector is provided for connection of the VPIS-VO.

DIRECT
INVERSE
1

123456
Assignment of micro-switches
1
2
3
4
5
6

Action on output relays: Direct / Inverse


Simple voltage (V) / Composed voltage (U)
Phase 1: Used / Not used
Phase 2: Used / Not used
Phase 3: Used / Not used
Residual voltage: Used / Not used

R1

V
U

24V-48V

R2

+ -

V1 V2 V3 V0
U21U13U32

13 14 15 16 17 18 19 20

VD23

L1
L2
L3
Option
VPIS-VO

2 relay outputs are available on the VD23, allowing two operating modes:
R1 = detection of voltage presence (for source changeover application)
R2 = detection of voltage absence (for applications of earthing switch locking upon
voltage presence).
These two relay outputs can be used in normal or inverted position and their action
can also be time-delayed by configuration.
VD23 parameters setup allows definition of the detection thresholds with a percentage
of the line-to-neutral voltage (V) or the line-to-line voltage (U) or the residual voltage
(V0):
R1: 40% to 90% of the rated voltage (in 10% increments)
R2: 10% to 30% of the rated voltage (in 10% increments).
Several detection combinations are possible (selection by micro-switches):
3 phases + residual voltage: V1 + V2 + V3 + V0
3 phases: V1 + V2 + V3 or U12 + U13 + U23
Single phase: V0, V1, V2, V3, U12, U13, U23.
PE56302

Reference: EMS58421

Transmission equipment
Radio equipment
In order to simplify on-site implementation, the radio transmitter-receiver station
can be supplied as a factory-programmed and tested, pre-assembled option.
The equipment includes:
Aerial connector mounted on a partition in the connection section, complete with
mounting accessories (surge suppressor and connection cables)
Radio, type used: TAIT serial 81xx or Motorola
Rack connection cables and aerial connector
Reference included in the Easergy T200 I parts list.
Radio aerial and connection cable
Directional and omnidirectional aerials available on request
Aerial cable with type N connector at each end available on request.
GSM aerial

28

T200ie_PCRED398085EN.indd 28

PCRED398085EN

28/05/2013 15:59:22

Easergy T200 I & E

Easergy L500 : MV network


remote control system for the
Easergy range

Easergy L500 is a basic SCADA system


which operates under Windows and has
been designed to control Easergy products
in just a few clicks.

Easergy L500 includes all the functions needed to operate


the MV network in real time

Its range of functions and its value for money make


it an outstanding tool for the following
applications:
Remote control of small networks
System dedicated to network control in addition
to the DMS type system
Temporary system pending implementation
of a DMS
Installed base maintenance
Experimentation.
Easergy L500 offers:
An immediate return on investment: the network
is operational immediately after investment in the first
substations.
Confirmation of your blueprint by the installation
of a remote control system.
Balanced and gradual training of the personnel
in charge of operating the networks.

PE56310

With the compatibility of the Easergy T200 range with


any type of DMS SCADA proven by our installations,
we offer a global solution for the early phases of your
project which capitalises on the investment made
in substations.

A communication front-end managing up to 8 communication ports


a various transmission modes:
Continuous transmission (cyclical interrogation of equipment).
The interrogation cycle can be configured.
private dedicated line: permanent link
fibre optic
RS232, RS485 links
ETH/GPRS (T200, Flair 200C Series 3).
Non-continuous transmission (exchange on alarm initiated by remote or
equipment or supervisor)
digital or analogue UHF and VHF radios
telephone and GSM
ETH/GPRS (T200, Flair 200C).
One control station with 1 to 3 screens
Password-protected access. A number of profiles (display, control, configuration)
can be configured. The various views and data types can be displayed via icons and
lists in the toolbar.
General view with network representation (mimic-based or geographical)
The remotely controlled substations are animated on an alarm summary.
Substation view
Single-line representation of the substation with:
switch position, earthing switch, fault current detector, measurements,
trend curves
issuing of open and close orders secured by selection/confirmation
communication status: call, date of last connection
detailed views can be accessed from the network view (click on substation)
or the substation list.
Alarm log refreshed in real time, with the 6 most recent alarms displayed
in the toolbar which is present in all views. Alarms can be sorted by substation
and by filter. They are colour-coded according to their status
Archive log can be viewed by substation and by filter
System view with status of communication equipment.
A professional configurator for creating remotely controlled substations
and transmissions in just a few mouse clicks
Applications can be permanently enhanced using this editor
Representations of network and substation views can be enhanced using
the graphics editor on the supervisor.
Additional system functions
System synchronisation via GPS clock in the PC
Time setting of remote equipment via protocol
Call management: automatic general control, general control on operator request,
periodic call, single call on request
External visual and audible alarm
Event log printing.

The Easergy L500 offer includes a wide range of


communication accessories
FSK or FFSK radio modem
PSTN and GSM modems
FSK dedicated line modem
Fibre optic interface.

L500 capacity

500 T200 I 2-channel type devices


8 communication ports
Licence according to size of application:
256 variables, 500 variables, 1000 variables, unlimited.

PCRED398085EN

T200ie_PCRED398085EN.indd 29

29

28/05/2013 15:59:22

Easergy L500 : MV network


remote control system for the
Easergy range (cont.)

Easergy T200 I & E

General view:
network representation on a geographical map
General equipment call
PE56312

Access to system view


Connect/disconnect with password

Archives: global or by substation


Alarm list: global or by substation
Access to substation view by list
Network view
System disconnect
5 most recent alarms with states

PE56312

Help files and user manuals

T200 P
MV/LV substation with T200 I
Flair 200C

Substation view

PE56314

PE56313

Communication management bar

4-channel T200 I, radio communication

30

T200ie_PCRED398085EN.indd 30

Flair 200C, GSM communication

PCRED398085EN

28/05/2013 15:59:23

Easergy T200 I & E

Tick one box only between each of the horizontal lines.


Green box X corresponds to none priced functions.

Order form

T200 model

Quantity
T200 E (TE)

1 - T200

T200 I (TI)

PE57920p

Variants and options

2 - Number of channels
T200 I
2 ch. (02)

4 ch. (04)

T200 E

4 ch. (04)

2 ch. (02)

3 - Measurements

8 ch. (08)

5 - Battery

Motorisation voltage = 24 Vdc (B)


24 V PWR + 48 V aux. PWR (D)
24 V PWR + 24 V aux. PWR (F)

Without battery (Z)

With battery 12 V-24 Ah (B)

Standard (A)

ATS-SEC-BTA automation system (B)

ATS auto. transfer system


with GENSET relay-T200 I (D)

RTU Control PLC (P)

6 - Software options

PE57937

16 ch. (16)

Standard measurements (M-)


Voltage measurement from LV power supply (B-)

4 - Power supply Motorisation voltage = 48 Vdc (A)


48 V PWR + 48 V aux. PWR (C)
48 V PWR + 24 V aux. PWR (E)
Easergy T200 I 4 channels
Package reference: TI-2M... or TI-4M

12 ch. (12)

7 - Protocols

Modbus et Modbus TCP (M2)


CEI 870-5-101 et CEI 870-5-104 (I2)
DNP3 et DNP3 TCP (D2)
Others, contact us (xx)

8 - Modem port 1 (Ethernet and USB included as standard)


RS232/RS485 isol 2 kV (4)

Non-insulated RS232(2)

GSM/GPRS (G)

GSM and GPRS 850 - 1900 MHz (H)

Easergy T200 I 8 channels


Package reference: TI-8M

DUMMY control (J)

PSTN (F)

GSM/3G (3)

V23 FSK radio modem: 600-1200 baud (B)


FFSK radio modem: 1200-2400 baud (C)

PE57938

Multipoint LL: 600-1200 baud with 8 kV insulation (D)


Option (G): the GSM/GPRS dual band modem becomes four-band. Availability date to be confirmed.
Option (H): this choice will be unavailable when the GSM/GPRS (G) modem is four-band

9 - Modem port 2 (Ethernet and USB included as standard)


Without (Z)
RS232/RS485 insulated 2 kV (4)
Non-insulated RS232 (2)
GSM/GPRS (G)
GSM and GPRS 850 - 1900 MHz (H)
GSM/3G (3)
PSTN (F)
Full size forced (R)
V23 FSK radio modem: 600-1200 baud (B)
FFSK radio modem: 1200-2400 baud (C)
Multipoint LL: 600-1200 baud with 8 kV insulation (D)
Option (G): the GSM/GPRS dual band modem becomes four-band. Availability date to be confirmed.
Option (H): this choice will be unavailable when the GSM/GPRS (G) modem is four-band

PE57924p

Easergy T200 I 16 channels


Package reference: TI-16M

10 - Local network

Without (Z)

RS485 master Modbus 2 kV insulated (R)

11 - GPS synchro.

Without (Z)

Synchronisation GPS (G)

12 - Transmission equipment port 1

Without (Z)
Radio integration kit (connector, cable, ) (K)
TAIT 8110 VHF radio (B)
TAIT 8115 VHF radio (C)

TAIT 8110 UHF radio (A)


13 - Languages
French (F)
Spanish (S)
Easergy T200 E 2 or 4 channels
Package reference: TE-2M ; TE-4M

English (E)
Portuguese (P)

14 - Other options

German (G)
Chinese (C)
Turkish (T)

Without (Z)
According to customer requirements, contact us (x)

To create the reference for your T200, use the model below to fill in the codes located
to the left of the boxes you have just ticked.
Variants and options No.:
1

PCRED398085EN

T200ie_PCRED398085EN.indd 31

10

11

12

13

14

31

28/05/2013 15:59:23

Easergy T200 I & E

Order form
(cont.)

Tick X one box only between


each of the horizontal lines.

T200 I accessories

Cable connection kits


Connection to switchgear
T200-CP
Length

Connector only
5m
10 m
15 m
25 m
Current measurement (cables + measurement CTs + acquisition card)
3m
5m
10 m
T200-TO
Length
15 m
25 m
T200-TF
Length
3m
5m
10 m
15 m
25 m
T200-TS
Length
3m
5m
10 m
15 m
25 m
T200-TH
Length
3m
5m
10 m
15 m
25 m
3m

T200 E accessories

Acquisition modules
3 phases current inputs

T200-AC

T200 I & E accessories

Acquisition modules
3 voltage inputs
3 digital inputs
External LED
Configurator cables
USB length 3 m
Ethernet length 3 m
Ethernet length 10 m
Simulators
Harting test socket
Universal simulator with auxiliary
Current simulator
Test case
Voltage presence relay
VD23

T200-AT
T200-AD
T200-LAMP
T200-CFG-USB-3
T200-CFG-ETH-3
T200-CFG-ETH-10
T200-PT
T200-ST
T200-SIM
T200-TESTCASE
EMS58421

L500 accessories

Scada licence
256 variables - x communication ports
1000 variables - x communication ports
5000 variables - x communication ports
65000 variables - x communication ports
x = number of communication ports from 1 to 8
Application development (please contact us)
Accessories
Visual and audible alarms
FSK radio modem
FFSK radio modem
PSTN modem
FSK DL modem (private line)
GSM modem with aerial

L500-F-256-x
L500-F-1000-x
L500-F-5000-x
L500-F-65000-x

L500-ext-alarms
G500M-M-B
G500M-M-C
OLITEC-PSTN
MDU910LL
MODEM-GSM-KIT-GSM

Miscellaneous
Specify miscellaneous equipment to be supplied

32

T200ie_PCRED398085EN.indd 32

PCRED398085EN

28/05/2013 15:59:24

Easergy T200 I & E

PCRED398085EN

T200ie_PCRED398085EN.indd 33

Notes

33

28/05/2013 15:59:24

Schneider Electric Industries SAS


35, rue Joseph Monier
CS 30323
F - 92506 Rueil Malmaison Cedex (France)
Tel.: +33 (0) 1 41 29 70 00
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
PCRED398085EN

T200ie_PCRED398085EN.indd 34

As standards, specifications and designs change from time to


time, please ask for confirmation of the information given in
this publication.
Publishing: Schneider Electric Industries SAS - Sonovision