You are on page 1of 6

H07RN-F TITANEX (industrial flexible)

Industrial flexible cable, insulation and outer sheath in elastomer

Description
Application
TITANEX flexible cable is intended for installations with moving
equipment, electric appliances and for building sites. The cable may be
rated 0,6/1 kV where the installation has built-in protection and for motors
in lifting appliances - machine tools - etc.
This cable can be used in refrigerating installations.
Installation
This cable can be installed in open air or be buried but with extra
mechanical protection.
Conductors laid up
Assembled conductors.
Marking
USE <HAR> N (x ou G) S TITANEX
N = number of cores
G = with Green-Yellow
x = without Green-Yellow
S = section in mm
Nota
Max continuous operating conductor temperature in normal use :

Standards
International HD 22.4; HD
516; IEC 60245-4 type 66
National NF C 32-102-4

+60C ( in every case of mobile installation)


+85C ( fixed protected installation )
+200C ( in short circuit )
Permissible current rating is measured for an ambient temperature of 30C
and a maximum operating and conductor temperature of 85C . For other
temperature please refer to correction factors .

Lead free
Yes

Mechanical resistance to
impacts

Cable flexibility

Chemical resistance

Water proof

Flexible

Accidental

Good

Very good

Generated 9/15/06 - http://www.nexans.fr/e-service/

Operating temperature,
range
-25 .. 55 C

Page 1 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

H07RN-F TITANEX (industrial flexible)


Contact
Nexans - Building activity
4-10 rue Mozart
92587 Clichy Cedex
France
filscablesbt-pc.fr@nexans.com

Lead free
Yes

Mechanical resistance to
impacts

Cable flexibility

Chemical resistance

Water proof

Flexible

Accidental

Good

Very good

Generated 9/15/06 - http://www.nexans.fr/e-service/

Operating temperature,
range
-25 .. 55 C

Page 2 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

H07RN-F TITANEX (industrial flexible)


Characteristics
Construction characteristics
Outer sheath
Sheath colour
Insulation
Conductor material
Lead free
Mechanical characteristics
Mechanical resistance to impacts
Cable flexibility
Usage characteristics
Chemical resistance
Water proof
Short-circuit maximum core temperature
Operating temperature, range
Maximum core temperature still

Special cross-linked elastomer


Black
Special cross-linked elastomer
Bare copper
Yes
Very good
Flexible
Accidental
Good
200 C
-25 .. 55 C
60 C

New cores identification


Core identification in accordance with HD 308 S2 (October 2001)Identification of cores in cables and flexible
cords.
Number of cores

HD 308 S2 since january 2004


G (earth core)
X (without earth core)
1
Black (preferential)
Black (preferential)
2
Blue + Brown
Blue + Brown
3*
Green - Yellow + Blue + Brown
Brown + Black + Grey
3**
Blue + Brown + Black
4
Green - Yellow + Brown + Black + Grey
Blue + Brown + Black + Grey
5
Green - Yellow + Blue + Brown + Black + Grey Blue + Brown + Black + Grey + Black
> 5
White printed numbers + 1 Green - Yellow
White printed numbers
* For the cables without Green/Yellow with a cross-section >4mm
** For the cables without Green/Yellow with a cross-section of 1,5mm & 2,5mm

Single Core
Cross
section
mm
1.5
2.5
4
6
10

Perm. current rating


open air
A
23
32
43
56
77

Voltage drop,
single phase
V/A.km
23.3
14.0
8.7
5.9
3.4

Max. outer
diam.
mm
7.1
7.9
9.0
9.8
11.9

Generated 9/15/06 - http://www.nexans.fr/e-service/

Min. outer
diam.
mm
5.7
6.3
7.2
7.9
9.5

Approx. weight
(kg/km)
kg/km
50
66
94
109
182
Page 3 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

H07RN-F TITANEX (industrial flexible)


Cross
section
mm
16
25
35
50
70
95
120
150
185
240
240
500

Perm. current rating


open air
A
102
136
168
203
254

Voltage drop,
single phase
V/A.km
2.2
1.4
1.04
0.75
0.56

Max. outer
diam.
mm
13.4
15.8
17.9
20.6
23.3

Min. outer
diam.
mm
10.8
12.7
14.3
16.5
18.6

363
416
475
559
637
833

0.36
0.31
0.28
0.23
0.2
0.16

28.6
31.4
34.4
38.3
41.9
52.0

22.8
25.2
27.6
30.6
33.5
41.3

Approx. weight
(kg/km)
kg/km
256
369
482
662
895
1144
1430
1740
2160
2730
3480
5700

Two cores
Cross
section
mm
1
1.5
4
6
10
16
25

Perm. current rating


open air
A
18
23
43
56
77
102
136

Voltage drop,
single phase
V/A.km
39.4
27.0
10.1
6.7
3.8
2.5
1.68

Max. outer
diam.
mm
10.0
11.0
15.1
16.8
22.6
25.7
30.7

Min. outer
diam.
mm
7.7
8.5
11.8
13.1
17.7
20.2
24.3

Approx. weight
(kg/km)
kg/km
99
111
238
279
538
744
1074

Three cores
Cross
section
mm
1
1.5
1.5
2.5
2.5
6
10
16
25
35
50
70
95
120
150
185

Perm. current rating


open air
A
18
23
23
32
32
56
77
102
136
168
203
262
320
373
432
495

Voltage drop,
single phase
V/A.km
39.4
27.0
27.0
16.2
16.2
7.0
4.0
2.5
1.7
1.21
0.87
0.64
0.5
0.4
0.35
0.3

Max. outer
diam.
mm
10.7
11.9
11.9
14.0
14.0
18.0
24.2
27.6
33.0
37.1
42.9
48.3
54.0
60.0
66.0
72.0

Min. outer
diam.
mm
8.3
9.2
9.2
10.9
10.9
14.1
19.1
21.8
26.1
29.3
34.1
38.4
43.3
47.4
52.0
57.0

Approx. weight
(kg/km)
kg/km
117
134
134
195
195
346
663
924
1345
1760
2390
3110
4170
5080
6220
7730

Generated 9/15/06 - http://www.nexans.fr/e-service/

Page 4 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

H07RN-F TITANEX (industrial flexible)


Cross
section
mm
240
300

Perm. current rating


open air
A
587
680

Voltage drop,
single phase
V/A.km
0.26
0.22

Max. outer
diam.
mm
82.0
90.0

Min. outer
diam.
mm
65.0
72.0

Approx. weight
(kg/km)
kg/km
9780
12620

Four cores
Cross
section
mm
1
1.5
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240

Perm. current rating


open air
A
16
21
21
29
38
50
68
92
122
150
182
232
281
325
373
425
500

Voltage drop,
single phase
V/A.km
34.08
23.3
23.3
14.0
8.71
5.84
3.42
2.2
1.44
1.04
0.75
0.56
0.44
0.36
0.31
0.28
0.23

Max. outer
diam.
mm
12.0
13.1
13.1
15.5
18.0
20.0
26.5
30.1
36.6
41.1
47.5
54.0
61.0
66.0
73.0
80.0
91.0

Min. outer
diam.
mm
9.6
10.2
10.2
12.5
14.0
15.7
20.8
23.8
28.9
32.5
37.7
42.7
48.4
53.0
58.0
64.0
72.0

Approx. weight
(kg/km)
kg/km
144
165
165
245
357
443
818
1150
1700
2180
3030
3990
5360
6500
7990
9910
13120

Five cores
Cross
section
mm
1
1.5
2.5
4
6
10
16
25

Perm. current rating


open air
A
16
21
29
38
50
68
92
122

Voltage drop,
single phase
V/A.km
34.1
23.6
14.0
8.72
5.84
3.43
2.2
1.44

Max. outer
diam.
mm
14.0
14.4
17.0
19.9
22.2
29.1
33.3
40.4

Min. outer
diam.
mm
10.9
11.2
13.3
15.6
17.5
22.9
26.4
32.0

Approx. weight
(kg/km)
kg/km
180
238
297
453
557
1001
1430
2096

Seven cores
Cross section
mm
1.5
2.5

Approx. weight (kg/km)


kg/km
349
487

Generated 9/15/06 - http://www.nexans.fr/e-service/

Page 5 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

H07RN-F TITANEX (industrial flexible)


Twelve cores
Cross
Perm. current rating
section
open air
mm
A
1.5
11
2.5

Voltage drop,
single phase
V/A.km
23.3

Max. outer
diam.
mm
22.14

Min. outer
diam.
mm
17.6

Approx. weight
(kg/km)
kg/km
510
702

Eighteen cores
Cross
Perm. current rating
section
open air
mm
A
1.5
9
2.5

Voltage drop,
single phase
V/A.km
20.7

Max. outer
diam.
mm
26.3

Min. outer
diam.
mm
20.7

Approx. weight
(kg/km)
kg/km
730
1018

twenty four cores


Cross section
mm
1.5

Perm. current rating open


air
A
8

Min. outer diam.


mm
24.3

Max. outer
diam.
mm
30.7

Approx. weight (kg/


km)
kg/km
1000

Max. outer
diam.
mm
35.2

Approx. weight (kg/


km)
kg/km
1325
1879

thirty six cores


Cross section
mm
1.5
2.5

Perm. current rating open


air
A
6

Min. outer diam.


mm
27.8

Generated 9/15/06 - http://www.nexans.fr/e-service/

Page 6 / 6

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans
is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

You might also like