You are on page 1of 129

Instructions

95-8470-07
Eagle Quantum
Fire and Gas Detection/Releasing System

4/12

95-8470-07

Table of Contents
Section I - System Overview
SYSTEM DESCRIPTION .......................................................I-1
SYSTEM FEATURES ............................................................I-2
MAJOR COMPONENT DESCRIPTIONS ..............................I-2
Intelligent Field Devices on Local Operating
Network/Signaling Line Circuit (LON/SLC) .......I-2
Local Control Unit (LCU) ..............................................I-2
Local Output Unit (LIOU)..............................................I-3
THEORY OF OPERATION ....................................................I-3
NETWORK OPERATION DURING A FAULT CONDITION...I-3
Multiple Wiring Faults ...................................................I-4
LON/SLC Ground Fault Detection and LCU
Protection..............................................................I-4
Field Devices without Power ........................................I-4
Section II - Local Control Unit and Power Supplies
OVERVIEW ...........................................................................II-1
Logic Controller ...........................................................II-1
Communication Gateway ............................................II-1
Isolation Module ..........................................................II-1
Optional LCU Versions................................................II-1
EQ2100CG COMMUNICATION GATEWAY ........................II-1
Features ......................................................................II-1
Description ..................................................................II-1
EQ2100LC LOGIC CONTROLLER.......................................II-5
Features ......................................................................II-5
Description ..................................................................II-5
EQ2100IM ISOLATION MODULE ........................................II-7
Features ......................................................................II-7
Description ..................................................................II-7
EQ21XXPS SERIES POWER SUPPLIES AND
EQ2100PSM POWER SUPPLY MONITOR .........................II-8
Features ......................................................................II-8
Description ..................................................................II-8
EQ2100PSM ...............................................................II-8
EQ2200IDCGF ............................................................II-8
Section III - Local Output Unit
OVERVIEW ..........................................................................III-1
Enclosure ...................................................................III-1
Fault LED and Reset Switch ......................................III-1
RELAY MODULE .................................................................III-1
Features .....................................................................III-1
Description .................................................................III-1
RELEASE MODULE ............................................................III-2
Features .....................................................................III-2
Description .................................................................III-2
SIGNAL AUDIBLE MODULE ...............................................III-3
Features .....................................................................III-3
Description .................................................................III-3

Section IV - Addressable Field Devices


EQ2200IDC SERIES INITIATING DEVICE CIRCUIT .........IV-1
Description .................................................................IV-1
FLAME DETECTORS..........................................................IV-1
EQ2200UV UV FLAME DETECTOR ...................................IV-2
Description .................................................................IV-2
Software Selectable Options .....................................IV-2
EQ2200UVHT (Hi Temp) UV FLAME DETECTOR .............IV-4
Description .................................................................IV-4
EQ2200UVIR FLAME DETECTOR .....................................IV-4
Description .................................................................IV-4
Software Selectable Options .....................................IV-5
EQ2200DCU AND EQ2200DCUEX DIGITAL
COMMUNICATION UNIT ...........................................IV-8
Description..................................................................IV-8
EQ2500ARM AGENT RELEASE MODULE .........................IV-9
Description..................................................................IV-9
EQ2500SAM SIGNAL AUDIBLE MODULE........................IV-10
Description................................................................IV-10
EQ2400NE NETWORK EXTENDER .................................IV-11
Description................................................................IV-11
General Application Information ...............................IV-11
Section V - Detector Application Information
UV DETECTORS..................................................................V-1
Windows .....................................................................V-1
Obstructions................................................................V-1
Smoke.........................................................................V-1
Arc Welding ................................................................V-1
Common Environmental Conditions ...........................V-1
UV DETECTOR POSITIONING ...........................................V-2
UV/IR DETECTORS .............................................................V-2
False Alarm Sources ..................................................V-2
Factors Inhibiting Detector Response.........................V-3
UV/IR DETECTOR POSITIONING .......................................V-3
GAS DETECTOR POSITIONING .........................................V-3
CATALYTIC GAS SENSORS ...............................................V-4
Catalytic Sensor Operation .........................................V-4
Sensitivity Loss in Catalytic Combustible Gas
Sensors ...............................................................V-6
Calibration Gas ...........................................................V-7
Section VI - General Wiring Requirements
GENERAL INFORMATION .................................................VI-1
Power Wiring .............................................................VI-1
Network Wiring ..........................................................VI-2
Shield Grounding .......................................................VI-2
Junction Box Grounding ............................................VI-3
RS-485 Link Wiring ....................................................VI-3
Protection Against Moisture Damage ........................VI-3
Electrostatic Discharge ..............................................VI-3
DETERMINING POWER REQUIREMENTS .......................VI-3
EQ2110PS, EQ2130PS AND EQ2175PS .................VI-3
Backup Battery ..........................................................VI-3
Battery Charger .........................................................VI-3

Table of Contents Continued


Section VII System Wiring
EQ2100PSM POWER SUPPLY MONITOR USED WITH
EQ2110PS, EQ2130PS AND EQ2175PS
POWER SUPPLIES............................................................VII-1
Wiring........................................................................VII-1
Startup ......................................................................VII-3
Measuring Battery Voltage and Charging Current ....VII-3
EQ2100LCU SERIES LOCAL CONTROL UNIT ................VII-4
EQ2100LIOU LOCAL OUTPUT UNIT ................................VII-7
Backplane Wiring ......................................................VII-7
RS485 Link Wiring ....................................................VII-7
Power Wiring ............................................................VII-7
RELAY MODULE................................................................VII-8
Wiring........................................................................VII-8
Switch Setting ...........................................................VII-8
RELEASE MODULE ...........................................................VII-9
Wiring........................................................................VII-9
Jumpers ....................................................................VII-9
Switch Setting ...........................................................VII-9
SIGNAL AUDIBLE MODULE ............................................VII-11
Wiring......................................................................VII-11
Jumpers/Switches...................................................VII-11
Address Switch Setting ...........................................VII-11
FIELD DEVICES ...............................................................VII-13
EQ2200IDC Series Initiating Device Circuit ............VII-13
EQ2200IDCGF Series Initiating Device Circuit
Ground Fault ...................................................VII-14
EQ2200IDCSC Series Initiating Device
Circuit Short Circuit .........................................VII-14
EQ2200UV UV Flame Detector ..............................VII-15
EQ2200UVHT High Temperature UV Detector.......VII-17
EQ2200UVIR UV/IR Flame Detector ......................VII-19
EQ2200DCU Digital Communication Unit
used with Det-Tronics H2S/O2 Sensors
or other Two-Wire 4 to 20 ma Devices............VII-22
Sensor Separation for DCU with H2S and
O2 Sensors .....................................................VII-22
EQ2200DCU Digital Communication Unit
used with PointWatch......................................VII-23
EQ2200DCUEX Digital Communication Unit
used with Det-Tronics
Combustible Gas Sensors...............................VII-24
EQ2500ARM Series Agent Release Module ..........VII-27
EQ2500SAM Series Signal Audible Module ...........VII-29
EQ2400NE Series Network Extender .....................VII-30
TYPICAL APPLICATIONS................................................VII-31
INSTALLATION CHECKLIST ...........................................VII-32
Section VIII Switch Setting
GATEWAY .........................................................................VIII-1
LOGIC CONTROLLER ......................................................VIII-3
ISOLATION MODULE .......................................................VIII-3
LON/SLC DEVICE ADDRESS SWITCH SETTING ...........VIII-3

Section IX System Startup


PRE-COMMISSIONING CHECKLIST .................................IX-1
STARTUP PROCEDURE ....................................................IX-2
CALIBRATION .....................................................................IX-2
Calibration Algorithm A For Manual Calibration
of Universal DCU................................................IX-2
Calibration Algorithm C For Combustible Gas DCUs
and Automatic Calibration of Universal DCUs....IX-4
Calibration Algorithm D For Universal DCUs
with O2 Sensor...................................................IX-5
Calibration Algorithm G For DCUs with PointWatch ..IX-6
UV DETECTOR TEST .........................................................IX-7
Fire Alarm Test ..........................................................IX-7
False Alarm Test........................................................IX-7
UV/IR DETECTOR TEST ....................................................IX-7
Manual oi...................................................................IX-8
Automatic oi ..............................................................IX-8
Section X Specifications
CERTIFICATIONS ................................................................X-1
EQ2100LCU LOCAL CONTROL UNIT.................................X-1
EQ2200IDC/IDCGF/IDCSC INITIATING DEVICE CIRCUIT X-3
EQ2200UV and EQ2200UVHT UV FLAME DETECTORS ..X-3
EQ2200UVIR UV/IR DETECTOR.........................................X-6
EQ2200DCU AND EQ2200DCUEX
DIGITAL COMMUNICATION UNIT ......................................X-9
EQ2500ARM AGENT RELEASE MODULE .........................X-9
EQ2500SAM SIGNAL AUDIBLE MODULE ........................X-10
EQ2400NE NETWORK EXTENDER..................................X-10
EQ2100PSM POWER SUPPLY MONITOR .......................X-11
EQ2110PS, EQ2130PS AND EQ2175PS
POWER SUPPLIES............................................................X-11
LIOU Local Output Unit.......................................................X-12
LIOU RELAY MODULE ......................................................X-12
LIOU RELEASE MODULE .................................................X-12
LIOU SIGNAL AUDIBLE MODULE ....................................X-12
COMBUSTIBLE GAS SENSOR .........................................X-13
ELECTROCHEMICAL SENSORS......................................X-13
POINTWATCH....................................................................X-13
Section XI System Maintenance
ROUTINE MAINTENANCE .................................................XI-1
Manual Check of Output Devices ..............................XI-1
O-Ring Maintenance ..................................................XI-1
Flame Detector Maintenance.....................................XI-1
Gas Sensor Maintenance ..........................................XI-1
Batteries.....................................................................XI-2
TROUBLESHOOTING.........................................................XI-2
REPLACEMENT PARTS .....................................................XI-2
DEVICE REPAIR AND RETURN ........................................XI-3
ORDERING INFORMATION ...............................................XI-3
APPENDIX A
FM Approval Description ............................................A-1
APPENDIX B
CSA Approval Description ..........................................B-1
APPENDIX C
CE Mark / ATEX / CENELEC Details .........................C-1
APPENDIX D
Rocker Switch Table...................................................D-1

INSTRUCTIONS

Eagle Quantum
Fire and Gas Detection/
Releasing System
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the Eagle Quantum System. Only qualified
personnel should install, maintain or operate the
Eagle Quantum System.
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover or opening a
detector assembly with power applied.
CAUTION
1. T he wiring procedures in this manual are
intended to ensure proper functioning of the
devices under normal conditions. However,
because of the many variations in wiring codes
and regulations, total compliance to these
ordinances cannot be guaranteed. Be certain
that all wiring complies with the NEC as well as
all local ordinances. If in doubt, consult a
qualified official before wiring the system.
2. Some Eagle Quantum devices contain
semiconductor devices that are susceptible to
damage by electrostatic discharge. An
electrostatic charge can build up on the skin
and discharge when an object is touched.
Always observe the normal precautions for
handling electrostatic sensitive devices, i.e. use
of a wrist strap (if available) and proper
grounding.
3. To prevent unwanted actuation, alarms and
extinguishing devices must be secured prior to
performing system tests.

Detector Electronics Corporation 2012

Section I
System Overview
SYSTEM DESCRIPTION
The Eagle Quantum System serves multiple roles in the
monitoring and protection of hazardous areas. It is a
fire detection and extinguishing agent release system
combined with a hazardous gas monitoring system,
integrated on a fault tolerant digital communication
network. The Eagle Quantum system utilizes an
advanced distributed architecture that is equally adept
at monitoring analog process signals like combustible or
toxic gas concentrations, and discrete contact closure
type devices such as manual fire alarm call boxes and
heat detectors, as well as Det-Tronics optical flame
detection. This sensor information is then transmitted to
the control unit to execute the fire suppression logic, to
control agent release, signaling, and annunciation
outputs, and to communicate with external operator
interface systems for configuration and monitoring.

4/12 95-8470-07

SYSTEM FEATURES

FM Approved to ANSI/NFPA-72-1996 National Fire


Alarm Code. See Figure A1 in Appendix A for
installation requirements.

Deluge and pre-action release capability for fire


suppression.

FM, CSA, CENELEC and CE Mark Certifications. See


Appendix A, B and C respectively for details and
specific installation requirements.

Agent release capability for fire suppression.


Up to 244 addressable field devices and 32,500 feet
(10,000 meters) of wiring on the network.

MAJOR COMPONENT DESCRIPTIONS

Supports up to 6 network extenders.


Compatible with Det-Tronics flame and gas detectors.

The system consists of three basic components (see


Figure I-1):

Accommodates a variety of third-party devices with 4


to 20 ma or dry contact type inputs.

intelligent field devices on Local Operating


Network/Signaling Line Circuit (LON/SLC)

Fault tolerant communication loop.


Non-volatile memory for alarm and calibration logging.

The LON/SLC is a fault tolerant, two wire, digital


communication network, arranged in a loop starting and
ending at the Local Control Unit. The LON/SLC supports
up to 244 intelligent field devices spread over a distance
of up to 32,500 feet (10,000 meters). The LON/SLC
serves as the Signaling Line Circuit (SLC) for the fire
detection/suppression aspects of the system.

Built in diagnostics.
Programmable logic.
Modbus RTU Master/Slave and Allen Bradley DF1
communication capability through two electrically
isolated RS-232 serial ports.
Up to 4 gateways and 4 logic controllers.

Local Control Unit (LCU)

Up to 75 amperes of alarm current per power supply.

The LCU functions as the heart of the Eagle Quantum


system. The LCU contains three replaceable modules
FIRE DETECTION

POWER
MONITORS

NETWOR
E TENDERS

FLAME
DETECTORS

LON/SLC

GAS DETECTION

CONTACT
CLOSURE
DEVICE

GAS SENSOR
OR OTHER
4 TO 20 MA INPUT

IDCs

DCUs

LON/SLC

LOCAL CONTROL UNIT (LCU)


LOGIC
CONTROLLER

GATEWAY

ISOLATION
MODULE

OIS

PLC/DCS

AUDIBLE
INDICATORS

C1899

LOCAL
OUTPUT
UNIT
(LIOU)

VISUAL
INDICATORS

FIRE
SUPPRESSION

Figure I1Block Diagram of Eagle Quantum System


I2

FIRE/GAS RESPONSE

AGENT
RELEASE
MODULES

FIRE
SUPRESSION

SIGNAL
AUDIBLE
MODULES

VISUAL/
AUDIBLE
INDICATORS

that perform all the communication, command, and


control functions for the system. It includes all the
required operator interface controls for a fire alarm
system (silence, acknowledge, reset, isolate),
annunciation relays, a local information display, and
communication interfaces for computer based
configuration and monitoring of the system.

If a Fire Alarm is detected by a Flame Detector or


Initiating Device Circuit (IDC), the affected node will
send a special Acknowledged Exception Report (AER)
directly to the Logic Controller. The AER is transmitted
as soon as an alarm is detected to maximize system
performance. When the Logic Controller receives the
AER, it sends the originating node a message
acknowledging its receipt. If the node originating the
AER does not receive an acknowledgement, it will
re-transmit the AER until it receives an
acknowledgement. This exchange of messages is used
to ensure that critical messages are received at all
appropriate registers throughout the system.

Local output Unit (LIOU)


The LIOU consists of a rack controlled by the LCU that
can hold up to six FenwalNet 2000 modules. These
modules allow the control of Notification Appliance
Circuits (NACs), fire suppression agent release (CO2,
Halon, FM200) using supervised relays, as well as
unsupervised relays for other needs.

Once the Logic Controller receives a Fire Alarm


message from a field device, fixed logic will activate
built-in annunciation circuits, which consist of both a
visible and audible alarm. The programmable logic
will execute any specified voting, timing, and/or zone
logic and subsequently activate the appropriate output
circuits for Notification Appliance Circuits (NACs), agent
release circuits, and unsupervised relay outputs.

THEORY OF OPERATION
During normal operation, each node on the network
monitors its attached sensor or other input, determines if
it has an alarm condition, analyzes its own health,
checks network integrity, and then packages up this
information for transmission to the communication
gateway, located in the LCU. This Standard Periodic
Report (SPR) contains 16 pieces of discrete
information on the status of the node and, where
applicable, also contains the analog value of its sensor.
At the time of node configuration, the report rate of the
SPR can be set to anywhere between 1 and 10
seconds.

The faceplate of the Logic Controller has two


pushbuttons. ACKNOWLEDGE will silence the built in
audible alarm and illuminate the Acknowledge LED
located on the faceplate next to the Acknowledge
pushbutton. SILENCE will silence selected NACs in
the field and illuminate the Silence LED located on the
faceplate next to the Silence pushbutton. The Logic
Controller also features a keyswitch to reset the system
after the event is over.

In the LCU the Communication Gateway collects all of


the incoming SPRs from the field devices and puts the
information into datatables. Datatables are organized
areas of memory in the gateway that can be read by
external host devices using one of the gateways serial
ports. If any of the SPRs indicate an out of tolerance
condition, the gateway will display this information on its
integrated faceplate display. The gateway also has four
programmable relays whose action can be programmed
to events in the SPRs of the monitored nodes.

NETWORK OPERATION DURING A


FAULT CONDITION
The Eagle Quantum system utilizes a unique patented
technique for detecting problems in the communication
network wiring. This state-of-the-art feature minimizes
the possibility of a communication breakdown in the
event of a wiring fault in the communication loop and
can also serve as an aid in troubleshooting.

In addition to SPRs, nodes used as a part of the fire


detection and suppression system, such as fire
detectors or Initiating Device Circuits (IDCs) interfaced
with heat detectors, manual call points, etc. send a
separate Standard Supervisory Report (SSR) to the
Logic Controller, located in the Local Control Unit. The
Logic Controller, which manages the fire suppression
logic, uses these SSR messages to verify that the nodes
used in the fire alarm and suppression logic are active
and able to communicate. If the Logic Controller does
not receive SSRs from a required node, it will annunciate
a trouble condition.

The communication network is constructed as a loop


that starts and ends at a pair of communication ports
located at the LCU. The nodes communicate with the
LCU over the LON/SLC as shown in Figure I-2.
Each field device node contains both the hardware and
s o f t w a re n e c e s s a r y t o i s o l a t e a n d re - ro u t e
communication in the event of a network wiring fault.
When a problem occurs somewhere within the network
wiring, the communication gateway located in the LCU
annunciates the fault, while the fault isolation circuitry in
the affected nodes isolates the section of the network
where the fault has occurred. Communication is thereby

I3

95-8470

ensured and will continue over the network. See Figure


I-3.

NODE 4

A single open or short on the LON/SLC will not affect


system communication between the field devices and
the gateway. System communication will continue until
the wiring problem can be repaired.

NODE 5

NODE 3

NODE 6

NODE 2

NODE 7

LCU

NODE 1

NODE 8
A1851

Multiple Wiring Faults

Figure I2Normal Communication over the Digital Highway

In the event of multiple wiring faults on the LON/SLC, the


nodes between the faults will continue to function, but
the faults will prevent them from communicating with the
gateway. See Figure I-4. In this example, nodes 1 to 4
communicate using one gateway port (path A) and
nodes 7 and 8 use the other gateway port (path B).
Nodes 5 and 6 are unable to report to the gateway
because they are isolated by the two wiring faults.

NODE 4

NODE 5

WIRING FAULT

NODE 3

NODE 2

NODE 6

PATH A

PATH B

LCU

NODE 1

NODE 7

NODE 8
A1852

LON/SLC Ground Fault Detection and LCU


protection

Figure I3Communication with a Single Wiring Fault


on the Network

The LCU contains an isolation module that checks the


LON/SLC for ground faults. Should a ground fault be
detected, it is indicated by an LED on the isolation
modules faceplate. The isolation module also ensures
communication with the field devices even if there is a
LON/SLC short circuit directly adjacent to the LCU.

NODE 4

NODE 5

WIRING FAULTS

NODE 3

NODE 2

Field Devices without power

NODE 1

NODE 6

PATH A

PATH B

LCU

NODE 7

NODE 8
A1853

All Eagle Quantum field devices are designed so that a


pass-through circuit is created for the network wiring
on a loss of power to the node. This ensures network
integrity even when a node is down for service or has
been damaged. The Communication Gateway in the
LCU will report powered-down nodes as notcommunicating.

Figure I4Communication with Multiple Wiring Faults


on the Network

IMPORTANT
Since it is impossible to predict where a network
fault might occur or exactly what effect it will have
on actual system operation, it is important to
diagnose and repair any fault as soon as possible
after it is detected to ensure reliable system
operation.

I4

Section II
Local Control Unit (LCU) and
Power Supplies

OPTIONAL LCU VERSIONS


An optional EQ2101LCU is available with provisions for
two 24 vdc power inputs. Two reliable and independent
24 vdc supplies, in accordance with ANSI/NFPA 72
section 1-5.2, must be supplied. If either of the supplies
is missing or a wiring problem occurs, a trouble
condition will be annunciated.

OVERVIEW
The Local Control Unit (LCU) is the heart of the Eagle
Quantum system. External host devices such as PLCs
or DCSs interface through the LCU, the fire detection
and releasing logic resides in the LCU, control of the
releasing, signaling, and annunciation outputs are
handled by the LCU, and the Local Operating
Network/Signaling Line Circuit (LON/SLC), through
which all field devices communicate, starts and ends its
loop at the LCU. Physically, the LCU consists of a three
slot rack style enclosure that houses the Communication
Gateway, Logic Controller, and Isolation Module. These
three modules plug into the backplane and are secured
with thumb screws. All external wiring is routed through
conduit entries at the bottom and sides of the unit. The
wiring terminals are protected by a removable cover.
The LCU can be installed in Class I, Division 2
hazardous locations. Refer to Appendix A (FMRC) and
Appendix B (CSA) for details.

Logic controllers can be added to the communication


network to segment it into logical groups. Up to four
logic controllers can be used on each network.
Auxiliary gateways can be added to provide additional
relays or serial port connections to PLCs or DCSs. Up to
three auxiliary gateways can be added to the Quantum
network. Gateways located outside the LCU can be
turned off without disrupting LON/SLC communication
with the LCU.

EQ2100CG COMMUNICATION
GATEWAY
FEATURES

LOGIC CONTROLLER

The Eagle Quantum Logic Controller uses seven


microprocessors and parallel processing techniques to
execute the logic used for fire suppression. Its wealth
of logical operators allow for the easy development of
nearly any imaginable type of cross-zone monitoring,
voting, and timed operations that might be needed in a
fire suppression system. The Logic Controller supports
ANSI/NFPA 72 Class A, Style 7 communication with field
devices.

Utilizes Modbus or Allen Bradley protocols


Transformer isolation of network ports
Four programmable relay outputs
Three digit display and bar graph
LEDs indicate relay status
EMI/RFI hardened

DESCRIPTION
The Eagle Quantum Communication Gateway is used in
conjunction with Det-Tronics software to configure the
system as well as to provide information on an ongoing
basis to external systems such as PLCs and DCSs. It
also provides local display and four programmable
relay outputs. In addition, the gateway provides a
heartbeat signal used to test for LON/SLC integrity, to
provide time and date information to field devices, and
to monitor for the continued presence of all configured
field devices.

COMMUNICATION GATEWAY
The Eagle Quantum Communication Gateway
communicates through two serial links for configuration
and monitoring. This allows for device configuration
using a comprehensive set of Det-Tronics authored
software tools. The monitoring is provided to the
Operator Interface Station(s) (OIS) through Modbus or
Allen-Bradley compatible protocols. The gateway also
provides four programmable relays that can be used to
annunciate conditions being monitored by the devices
on the LON/SLC.

The gateway receives and stores the current status and


process variable information from all devices on the
Local Operating Network/Signaling Line Circuit
(LON/SLC) communication loop. It services all valid
requests by Modbus RTU masters and/or Allen-Bradley
DF1 masters that are received through its two host
interface serial ports. When acting as a Modbus RTU
master, the gateway will automatically transfer key
process variable and status information to a default or
user selected Modbus RTU slave address and register
offset.

ISOLATION MODULE
The Isolation Module protects the integrity of the
LON/SLC wiring by isolating shorts and monitoring for
ground faults. It also provides electrical isolation for the
two serial communication ports between the gateway
and host devices.
II1

95-8470

DET-TRONICS

DEVICE ADDRESS

DIGITAL DISPLAY

All three digits are on and the decimal point for each
digit is also on. Up to 250 addresses are available
(displayed 0.0.1. to 2.5.0.).

BAR GRAPH DISPLAY


100
90
80
70
60
50
40
30
20
10

RELAY 1
RELAY 1 LED
RELAY 2
RELAY 2 LED
RELAY 3
RELAY 3 LED

DEVICE IDENTIFICATION CODE


See Table II-1 for device identification codes.
DEVICE PERCENT FULL SCALE/FAULT
CODE/CALIBRATE

RELAY 4

RESET PUSHBUTTON
FAULT

RELAY 4 LED

RESET
EAGLE QUANTUM
GATEWAY

FAULT LED

The display follows the sensor input in percent of full


scale up to 100% full scale. A negative sign is used to
indicate a negative zero drift condition. See Table II-2
for the status codes used by the gateway display.
A fault condition is indicated as FXX, with F indicating
that a fault has occurred and XX identifying the type of
fault that is detected.

B1884

Figure II1Gateway Faceplate

If a detector is being calibrated, the display will show


CAL.

During normal operation the gateway produces a


periodic (250 millisecond) heartbeat signal on the
network, which is used by all field devices as a part of
their network fault isolation routine. Every fourth
heartbeat (1 second intervals) also includes a time
and date message that is used by the field devices for
logging calibration, alarm, and other events.

BAR GRAPH
The 20 segment bar graph tracks the input signal from
the sensor, providing a 0 to 100% full scale reading of
sensor input.
Table II1Device Identification Codes
used by Gateway Digital Display

The gateway has sufficient non-volatile memory to store


configuration data for all networked field devices, which
is downloaded to the gateway from the OIS.

DISPLAY READING

DEVICE
Gateway

Faceplate Description
The faceplate provides four relay LEDs and one fault
LED, a digital display, a bar graph, and a reset
pushbutton. See Figure II-1.

IDC

UV Detector

DIGITAL DISPLAY

UV/IR Detector

The digital display is a three digit seven segment


display. During normal operating conditions, the
display indicates 000. When a system event occurs
(alarm, fault or calibration) the display sequentially
shows the device address, followed by device
identification code, followed by device percent full
scale/fault code/calibrate signal.

Logic Controller

DCU

ARM

Each indication is shown for 3/4 second, followed by a


1/4 second delay before going to the next indication.

SAM

If more than one event should occur, the entire display


(digital display and bar graph) will track the status of
each address where activity is occurring by sequencing
through each event by order of address.

Power Supply Monitor

T0026B

II2

Table II2Status Codes used by Gateway Digital Display

F10
F20
F30
F32
F40
F50
F51
F60
ALA
Bytes

Gateway Fault
Not Communicating
LON Fault
Right Heartbeat Fault (Net Test Fault)
Stuck Reset Switch
Upper Transceiver Fault
Lower Transceiver Fault
Invalid Configuration or Unable to Configure
Output Relay Active
Bytes Remaining for Non-volatile Memory Write

IDC

F10
F11
F13
F14
F20
F60
A10
A01
A11

Fault
Low Voltage Fault
Input 1 Open
Input 2 Open
Not Communicating, Com 1 or Com 2 fault
Invalid Configuration or Unable to Configure
Input 1 is Active
Input 2 is Active
Both Inputs are Active

IDCSC

F10
F11
F13
F14
F20
F60
A10
A01
A11

Fault
Low Voltage Fault
Input 1 Open or Short
Input 2 Open or Short
Not Communicating, Com 1 or Com 2 fault
Invalid Configuration or Unable to Configure
Input 1 is Active
Input 2 is Active
Both Inputs are Active

IDCGF

F10
F11
F13
F14
F20
F60
A10
A01
A11

Fault
Low Voltage Fault
Ground Fault
Input Open
Not Communicating, Com 1 or Com 2 fault
Invalid Configuration or Unable to Configure
Ground Fault +
Input is Active
Input Active and Ground Fault +

UV Detector

F10
F11
F12
F13
F20
F60
cps

Fault
Low Voltage Fault
oi Fault
290 Volt Fault
Not Communicating, Com 1 or Com 2 fault
Invalid Configuration or Unable to Configure
Counts Per Second, Displayed During Alarm and Pre-Alarm

F10
F11
F20
F60
cps*
* Can be

Fault
Low Voltage Fault
Not Communicating, Com 1 or Com 2 fault
Invalid Configuration or Unable to Configure
Counts Per Second, Displayed During Alarm
either UV counts or IR counts, depending on the mode selected at the OIS.

Logic
Controller

F10
F17
F20
F60
ALA
Bytes

Trouble
Ground fault
Not Communicating, Upper Transceiver Fault or Lower Transceiver Fault
Invalid Configuration or Unable to Configure
Alarm
Bytes Remaining for Non-volatile Memory Write

DCU

F10
F11
F20
F60
CAL
nnn

Sensor Fault or Calibration Fault


Low Voltage Fault
Not Communicating, Com 1 or Com 2 fault
Unconfigured, Invalid Configuration or Unable to Configure
Calibration in Progress
Process variable displayed as a % of the Calibrated Full Scale Reading

ARM

Sol
F10
F11
F12
F20
F21
F60

Release display code


Open Output
Low Voltage Fault
Low Auxiliary Voltage Fault
Not Communicating, Com 1 or Com 2 fault
Network Variable Input Fault
Invalid Configuration or Unable to Configure

Gateway

UV/IR Detector

II3

95-8470

SAM

Power Supply
Monitor

Table II2Status Codes used by Gateway Digital Display (Continued)


Aud
Signal Audible display code
F11
Low Voltage Fault
F12
Low Auxiliary Voltage Fault
F13
Open/Short on Circuit 1
F14
Open/Short on Circuit 2
F20
Not Communicating, Com 1 or Com 2 fault
F21
Network Variable Input Fault
F60
Invalid Configuration or Unable to Configure

PS
F10
F11
F12
F13
F14
F20
F60

Power Monitor display code


AC Failed
Low Voltage Fault
Battery Fault
Ground Fault
Power Supply Fault
Not Communicating, Com 1 or Com 2 Fault
Invalid Configuration or Unable to Configure

The bar graph indicates 0 to 100% full scale, which


corresponds to the 4 to 20 ma signal for all gas sensors
except oxygen. The 4 to 20 ma signal from an oxygen
sensor corresponds to 0 to 25% oxygen. Sensor output
(measured in counts per second) is displayed for UV
and UV/IR detectors.

Automatic Diagnostics
The gateway features self-testing circuitry that
continuously checks for problems that could prevent
proper system response. The gateway performs three
forms of diagnostics: self-diagnostics, LON/SLC
diagnostics, and device diagnostics.

LEDS
Self-diagnostic tests monitor the condition of the
gateway. LON/SLC diagnostics check for shorts and
opens in the LON/SLC wiring. In the event of a
problem, the fault is annunciated in the gateway status
word and the gateway fault relay is activated.

Five faceplate LEDs are provided for indicating the


status of the gateway relays. When a relay is reset, the
corresponding LED is also reset.
RELAYS

For device diagnostics, the gateway provides a


watchdog timer for each configured device on the loop.
Each time the device reports to the gateway, the timer
accumulator is reset to zero and the timer starts over. If
a device does not respond before its watchdog timer
expires, the gateway sets the not communicating bit in
the status word for that device.

The communication gateway is provided with five


relays. Four of the relays are general purpose relays.
The fifth relay functions as a fault relay, responding only
to gateway or LON network faults. The relays have form
C contacts rated 5 amperes resistive at 30 vdc.
The specific function of the four general purpose relays
is programmable through Det-Tronics software. The
relays are selectable for latching or non-latching
operation and can be configured for normally energized
or de-energized operation.

Fault Tolerant Communication


Fault tolerance is provided by constructing the
LON/SLC as a loop that starts and ends at a pair of
network communication ports on the gateway. If a fault
occurs somewhere in the network wiring, fault isolation
circuitry in the communication modules isolates the
problem section of the network. When the gateway
detects the fault, it is immediately annunciated. The
gateway then reconfigures the network so data can be
transmitted to all devices.

CAUTION
When the relays are used as gas alarm outputs in
the non-latching mode, they must be connected to
another device that will perform the latching
function.
RESET PUSHBUTTON

This feature minimizes the possibility of a


communication breakdown in the event of an open or
short in the communication loop. A single open or short
on the LON/SLC will not affect system communication
performance. In the event of multiple opens or shorts,
only those detectors between the opens and shorts will
not be able to communicate with the LCU, even though
they will continue to function.

The programmable relays can be reset by pressing the


reset pushbutton or external reset (resetting all latching
relays) or by a command from the EagleVision NT
software (resetting individual relays). The reset function
resets the relay, regardless of the status of the initiating
device. This allows additional events to trigger the
same relay, even though the first device may still be in a
triggering mode.
II4

DET-TRONICS

The logic controller receives configuration information


through the gateway by means of its serial connection
to the operator interface system.

POWER
ALARM
TROUBLE

Faceplate Description

POWER FAULT
SUPERVISORY

ACKNOWLEGDE

The faceplate has a key switch, two pushbutton


switches, and nine LEDs. See Figure II-2.

SILENCE

KEY SWITCH

PUSHBUTTON
SWITCHES

PROGRAM

The key switch on the front panel of the logic controller


is used to select from four operating modes Normal,
Acknowledge & Silence Enable, Reset or Isolate. The
key may be removed in the Normal or Isolate position.

ISOLATE

EAGLE QUANTUM
LOGIC CONTROLLER

KEY SWITCH

NORMAL
ACKNOWLEDGE
& SILENCE
ENABLE

NOTE
Always rotate the key switch slowly when
selecting operating modes.

RESET
ISOLATE

Normal
C1854

In the normal mode, the controllers program is running


and the outputs are enabled.

Figure II2Logic Controller Faceplate

EQ2100LC LOGIC CONTROLLER

Acknowledge & Silence Enable

FEATURES

This mode enables the Acknowledge and Silence


pushbuttons.

Programmable logic

NOTE
The Acknowledge and Silence pushbuttons are
inhibited when the key switch is in the Normal
position.

LEDs indicate status conditions


Alarm, Trouble and Supervisory SPDT relays
EMI/RFI hardened

Reset
DESCRIPTION
In the reset mode, normal operation is inhibited and a
reset signal is sent to the LIOU and field output devices.

The logic controller provides the control function for the


fire detection portion of the Eagle Quantum fire and gas
safety system. It monitors messages from the devices
on the loop that are configured to report to that
controller (up to 120 in combination) and generates the
appropriate output(s) in response to the input
conditions. The logic controller supports ANSI/NFPA 72
Class A, Style 7 communication with the field devices.

This mode is also used for programming. In the


program mode, normal operation is inhibited. This is
the only mode that allows configuration information to
be downloaded to the logic controller from the gateway.
When the program mode is exited, configuration
information is sent to the LIOU.
NOTE
If the key switch is left in the RESET position for
more than a second or if the logic controller is in
the Program mode, a Trouble condition will be
indicated.

The logic controller uses fixed logic to control the


faceplate display and onboard alarm, trouble and
supervisory outputs per ANSI/NFPA 72.
The logic controller also has programmable logic, which
allows it to be customized to perform complex logic
operations including voting and timing. It also
communicates with the output modules located in the
LIOU, controlling system functions such as alarm
signaling, agent release and relay actuation.

II5

95-8470

Isolate

POWER FAULT (Yellow)

In the isolate mode, normal operation continues while


the logic controller sends an isolate command to all the
agent release outputs in the LIOU. The Isolate LED
turns on in a steady state if all release outputs are
isolated. The LED is off when none of the outputs are
isolated and blinks if only some of the outputs are
isolated.

Indicates that a power supply fault has been detected.


This could involve any of the following:

NOTE
User logic is required to isolate LON based agent
release modules.

ground fault
low or missing AC input voltage
24 vdc power supply
battery related fault
power supply monitor
IDCGF.

SUPERVISORY (Yellow)
Follows the status of the Supervisory relay.

PUSHBUTTON SWITCHES

ACKNOWLEDGE (Yellow)

Acknowledge

Illuminated when the acknowledge switch is pressed


and remains lit until the unit is reset.

Pressing the acknowledge pushbutton with


Acknowledge/Silence enabled acknowledges the
current status condition(s) and turns off the internal
buzzer.

SILENCE (Yellow)
Illuminated when the silence switch is pressed and
remains on until the unit is reset.

Silence
Pressing the silence pushbutton silences the selected
signaling outputs in the LIOU. (The specific LIOU
outputs that are affected by the silence button are
selected at the time of system configuration.)

PROGRAM (Yellow)
Indicates that the logic controller is in the
Reset/Program mode.

NOTE
Signaling devices connected to LON based Signal
Audible Modules must be silenced via user logic.

ISOLATE (Yellow)
Indicates that the logic controller is in the Isolate mode.

LEDS

Relays

Nine faceplate LEDs are provided for indicating system


status conditions.

The Logic Controller has three relay outputs,


responding to the following status conditions:
Fire alarm (Activated when any device that is
configured as a fire alarm input is active. This
includes all flame detectors and IDCs that are
configured as alarm type inputs.)

POWER (Green)
Indicates that power is applied to the device.
ALARM (Red)

Supervisory (Activated when a supervisory fault


occurs at any LON device that is configured to
report to the Logic Controller as a supervisory
input.)

Indicates that the Fire Alarm relay is actuated.


TROUBLE (Yellow)

Trouble (Normally energized). Activated when any


of the following occurs:
LIOU communication, wiring or other fault
AC input failure
Battery fault
Power supply fault
Invalid configuration
LON fault
LON device communication fault
Gateway LON fault
RAM fault.

Illuminated when a trouble condition occurs in the wiring


or devices associated with the fire system. (Trouble
relay is active). All logic controller faults are latching
and must be cleared by resetting with the key switch.
Det-Tronics configuration software should be used to
determine the specific problem.

II6

EQ2100IM ISOLATION MODULE


0.5 SEC

0.5 SEC

1.5 SEC

FEATURES
Ground fault detection

ALARM

RS-232 isolation for data rates up to 19.2 Kbaud

0.5 SEC

LEDs indicate status conditions

5.0 SEC

EMI/RFI hardened

TROUBLE
0.1 SEC

0.1 SEC

DESCRIPTION
2.0 SEC

The Eagle Quantum Isolation Module (LON Isolator)


protects the integrity of the communication network
wiring by isolating shorts and monitoring for ground
faults. The Isolation Module also provides electrical
isolation for the two serial communication ports between
the gateway and host devices.

SUPERVISORY
A1855

Figure II3Tone Pattern for Logic Controller Buzzer

The relays latch until the Logic Controller is reset.

Visual Indicators

The relays have SPDT (Form C) contacts, rated 5


amperes resistive at 30 vdc. Terminals are provided on
the LCU backplane for connecting EOL resistors.

LEDs on the front panel are provided for indicating


status conditions. See Figure II-4 for LED locations and
Table II-3A and II-3B for possible fault conditions.

Buzzer
The Logic Controller is furnished with an internal buzzer
for signaling a change in status. The buzzer has four
modes of operation:

Off
Alarm
Trouble
Supervisory.

DET-TRONICS

LON ISOLATOR

GROUND FAULT

In the normal mode with no events occurring, the buzzer


is off. If an alarm, trouble or supervisory event occurs,
the appropriate tone is generated. In the event of
multiple events, the order of priority is alarm,
supervisory, then trouble. Refer to Figure II-3 for the
tone patterns that identify each type of event.

POWER +
POWER

GROUND FAULT
COM 1
COM 2

The buzzer can be silenced by pressing the


ACKNOWLEDGE switch on the front panel (the key
switch must be in the Acknowledge & Silence Enable
position). If a second event occurs or if the original event
stops and then returns, the buzzer will again turn on.

EAGLE QUANTUM
LON ISOLATOR

NOTE
If a trouble condition has been acknowledged and
the condition exists for more than 24 hours, the
buzzer will again sound.

B1856

Figure II4Isolation Module Faceplate

II7

95-8470

Table II-3APower Supply Ground Fault

resides on the communication loop (LON), any trouble


condition related to system power will immediately be
reported through the Local Control Unit. Status
conditions being monitored include power supply
failure, loss of AC power, loss of battery power, power
ground fault, AC voltage, DC voltage and battery
charging current levels.

Power + ground fault occurs if:


- Resistance of Power + to earth is <136K ohms.
- DC voltage is below +19.0 vdc (with 26 vdc supply voltage).
- Current >0.14 ma between + wire and earth.
Power ground fault occurs if:
- Resistance of Power to earth is <15K ohms.
- DC voltage is below 4.9 vdc (with 26 vdc supply voltage).
- Current >0.1 ma between wire and earth.

The output of the power supply monitor is a status


message that is sent along the communication loop to
the gateway and logic controller in the Local Control
Unit (LCU). System response to the message is
determined at the time of configuration. The power
supply monitor supports ANSI/NFPA 72 Class A, Style 7
communication with the LCU.

Table II-3BLON Ground Fault

COM 1 / COM 2 ground fault occurs if:


- LON B wire resistance to earth is <4K ohms.
- LON B wire DC voltage is below 4.0 vdc.
- Current >1.0 ma between LON B wire and earth.
OR

Enclosure

- LON A wire resistance to earth is <2K ohms.


- LON A wire DC voltage is below +2.0 vdc.
- Current >1.0 ma between LON A wire and earth.
Note:

The power supply monitor must be located in a


controlled non-hazardous area and must be mounted in
a suitable metallic nationally recognized test laboratory
(NRTL) labeled NEMA rated enclosure.

Voltages are nominal and may vary slightly (voltages referenced to


earth).
Resistance/voltage levels between sides are different same
readings indicate they are shorted together.

Fault Tolerant Network

EQ21XXPS SERIES POWER


SUPPLIES AND EQ2100PSM POWER
SUPPLY MONITOR

Like other Eagle Quantum network devices, the power


supply monitor utilizes a unique patented technique for
detecting network wiring problems. This feature
minimizes the possibility of a communication breakdown
in the event of a wiring fault and can also serve as an
aid in troubleshooting.

FEATURES
Monitors primary AC supply and battery integrity.
Power supplies available with 10, 30 or 75 ampere
output.
Field addressable.
Unique patented fault isolation.
Utilizes state-of-the-art communication technology.
Pass through communication circuitry on power loss.
EMI hardened.
FMRC approved and CSA certified for use in Eagle
Quantum systems.

A single open or short on the network will not affect


system communication between the field devices and
the LCU. System communication will continue until the
wiring problem can be repaired.
Status LEDs
The power supply monitor has three LEDs to provide a
visual indication of status conditions:
Green
Red

DESCRIPTION
These power supplies are available with 10, 30 or 75
ampere outputs. Input voltage is selectable for 120, 208
or 240 vac. Refer to Section X or Table VI-5 (Section VI)
for power supply specifications.

Yellow

On when power is applied to the device.


On (flashing) indicates a trouble
condition.
Used for factory diagnostic purposes.

EQ2200IDCGF
The available EQ2200IDCGF Initiating Device Circuit
Ground Fault Monitor responds to the presence of a
ground fault within the power circuitry of the Eagle
Quantum system. It provides a supervised dry contact
input and ground fault monitoring circuitry for indicating
a power supply trouble condition. It is intended for use
with a third party power supply.

EQ2100PSM
The EQ2100PSM Power Supply Monitor is used in
conjunction with an EQ21xxPS power supply and
backup batteries to provide power for the Eagle
Quantum system. Since the power supply monitor

II8

The yellow LED also turns on if:

Section III
EQ2100LIOU
Local Output Unit

An output fault occurs (signal audible and agent


release modules only). The LED is reset automatically
when the fault clears.

OVERVIEW

A microprocessor fault occurs.

The Local Output Unit (LIOU) consists of a six position


card rack. Available modules include:

The card is not configured.


A loss of communication with the LCU occurs (RS485). If an output is on during a loss of
communication, the output will remain in the current
state and can only be reset using the reset switch on
the Logic Controller.

Relay Module four independently programmable


unsupervised relay contacts.
Release Module one release circuit and three
signaling circuits.
Signal Audible Module four independently
programmable signaling circuits.

RELAY MODULE

These modules can be installed in the rack in any


position. The Local Control Unit (LCU) automatically
reads the output modules type and address on powerup. It is recommended that modules performing like
functions be inserted adjacent to each other to facilitate
identification and field wiring runs.

FEATURES

The assembly is controlled and supervised by the local


control unit (using an RS-485 serial communication link)
and must be mounted nearby (less than 20 feet). Up to
four LIOUs can be controlled by the LCU, adding a
maximum of 24 output modules to the system. When
multiple LIOUs are used, the last one in the chain must
be no more than 20 cable feet from the LCU.

DESCRIPTION

Four independently programmable relays


SPDT dry contacts
Supervised module

The relay module is a convenient and economical


means of providing unsupervised output capability for
the Eagle Quantum System. The module is located in
the LIOU and provides four independently
programmable relays for control of auxiliary functions
such as fan shutdown and damper control. Each relay
has SPDT contacts, rated 2 amperes at 30 vdc.

NOTE
Input modules are not currently available for the
LIOU.

The connection of the relay module to the system is


supervised by the LCU. In the event of module removal,
the system will display a trouble condition at the LCU.

ENCLOSURE
The LIOU must be located in a controlled nonhazardous area and must be mounted in a suitable
metallic nationally recognized test laboratory (NRTL)
labeled NEMA rated enclosure.

The relay module is housed and secured in the LIOU. A


maximum of 8 relay modules can be installed in the
system.
NOTE
It is not recommended to configure relay outputs
as Normally Energized/Open on Alarm.

FAULT LED AND RESET SWITCH


Each card in the LIOU is furnished with a yellow fault
LED and a Reset switch. During Normal operation, the
LED is off. The yellow LED turns on when the Reset
button is pressed or a fault occurs. Pressing the Reset
button resets the microprocessor on the card, causing it
to re-initialize. At this time, the Trouble light on the LCU
is also turned on.
If the Reset button is pressed with an output energized,
the output is de-energized until the event that triggered
the output re-occurs. (Outputs are event driven.)

III-1

95-8470

Each signal circuit delivers up to 2 amperes at 24 vdc


enough to meet the power requirements of todays
ADA/UL 1971 Signaling Appliances. The three signal
outputs are individually programmable to allow
signaling of each phase of the release sequence.

RELEASE MODULE
FEATURES
One programmable releasing output
Three independently programmable signal circuit
outputs (style Y wiring)

The agent release output circuit is rated for 24 vdc


control devices. Each release output can supervise and
activate up to two solenoid control heads. Tables III-1
and III-2 identify the devices that can be controlled by
the releasing output. Refer to Section VII for specific
wiring information.

FM200, FE-13, CO2, Halon, water mist, dry and wet


chemical compatible, deluge and pre-action
Programmable for initiators or solenoid type releasing
devices for 90 sec., 10 min., 15 min., continuous.

Each circuit on the release module is furnished with a


self-restoring fuse to provide protection from short
circuit conditions. The three signaling circuits are
supervised for open and short circuit conditions. The
release circuit is supervised for open circuit conditions.
If a trouble condition occurs, it will be indicated at the
LCU.

DESCRIPTION
The release module is a convenient and economical
means of providing signaling and agent release
capability for the Eagle Quantum System. The release
module is located in the LIOU and provides one
programmable release circuit and three Style Y
signaling circuits. The release circuit is compatible with
all solenoid or initiator based Fenwal suppression
systems.

The connection of the release module to the system is


supervised by the LCU. In the event of module removal,
the system will display a trouble condition at the LCU.

Used in conjunction with the Eagle Quantums


programmable logic, each release circuit can be
programmed for Single, Cross or Counting Zone
Style initiation. Optional time delay, abort and manual
release sequences allow the output to be programmed
for use in unique applications.

The release module is housed and secured in the LIOU.


A maximum of 8 release modules can be installed in the
system.

Table III1Solenoid Compatibility with Release Module for


Releasing Applications

Table III-2Solenoid Compatibility with Release Module for Deluge


and Pre-Action Applications

Solenoids
Fenwal part no.
Fenwal part no.
Fenwal part no.
Fenwal part no.
Fenwal part no.
Fenwal part no.

Manufacturer

486500-001
890181
897494
899175
895630-000
31-199932-004

Model

Skinner

LV2LBX25

ASCO

8210A107

ASCO

8210G207

Skinner

73218BN4UNLVNOC111C2

Skinner

73212BN4TNLVNOC322C2

Skinner

71395SN2ENJ1NOH111C2
T0037B

III-2

SIGNAL AUDIBLE MODULE

The Signal Audible Module is located in the LIOU and is


supervised by the LCU. In the event of module removal,
the system displays a trouble condition at the LCU.

FEATURES
Four independently programmable indicating circuits

The Eagle Quantum system supports up to eight signal


audible modules, providing a maximum of 32 signal
outputs per system. Each module provides auxiliary
input terminals for additional 24 vdc signaling power
where required. All four module outputs are
synchronized for accurate activation of visual signaling
appliances.

NFPA Style Y or Z wiring


24 vdc power limited outputs
Self-restoring output design
Four optional coded outputs per circuit.

The signal outputs are programmable for activation by


the Eagle Quantums Logic Controller. Time delay and
stepped signaling functions can also be
accommodated. In release applications, signal outputs
can be programmed to provide pre-release, release
and post-release signaling.

DESCRIPTION
The signal audible module provides four indicating
circuits for controlling UL Listed 24 vdc polarized
audible/visual indicating appliances. Each output
circuit is independently programmable to allow
annunciation of separate events.

Each circuit is individually programmable for any one of


the following coded outputs:

The outputs are UL Listed for power limited


applications. The advanced circuitry design uses
resettable fuses, eliminating the need to replace
modules or components if the circuits are shorted or
overloaded. As a result, downtime and maintenance
costs are reduced.

1. Continuous sounding
2. 60 Beats per minute
3. 120 Beats per minute

The signal audible module can support four NFPA Style


Y or two Style Z field wiring circuits. Each output
circuit is supervised for open and short circuit
conditions. The outputs operate in the reverse polarity
fashion when activated. Each output delivers up to 2
amperes at 24 vdc enough to meet the power
requirements of todays ADA/UL 1971 signaling
appliances.

4. Temporal pattern.
The signal audible module is housed and secured in the
LIOU. A maximum of eight signal audible modules can
be installed in the system.

III-3

95-8470

Section IV
Addressable Field Devices

Addressability
Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
range is 5 to 250).

EQ2200IDC SERIES
INITIATING DEVICE CIRCUIT (IDC)

Status LEDs

DESCRIPTION

Three LEDs are located at the center of the


communication module circuit board and are visible
when the cover is removed.

Three IDC models are available:


The EQ2200IDC allows discrete inputs from smoke/heat
detectors, manual call stations or other contact devices.

The green LED serves as a power-on indicator and is


the only LED illuminated during normal operation (no
faults or alarms occurring).

The EQ2200IDCGF Initiating Device Circuit Ground


Fault Monitor responds to the presence of a ground fault
within the power circuitry of the Eagle Quantum system.
It provides a supervised dry contact input and ground
fault monitoring circuitry for indicating a power supply
trouble condition. It is intended for use with a third party
power supply.

The red LED is used to indicate an alarm or fault


condition. The flashing rate of the red LED indicates the
following conditions:
On steady =
Blinking =

The EQ2200IDCSC Initiating Device Circuit Short Circuit


(IDCSC) provides two supervised digital inputs for
monitoring the system for shorts circuits. The IDCSC
supports ANSI/NFPA 72 Class B Style C (3 state,
open/short circuit) supervised input circuits.

one of the inputs is active


fault condition such as an open input
circuit or not configured.

The amber LED is provided for factory diagnostic


purposes and is not used by the customer. Illumination
of the amber LED normally indicates a failure in the
communication chip. Replacement of the communication
module circuit board is required.

Inputs
Each IDC accepts two dry contact inputs for use with
devices such as relays, pushbuttons, key switches, etc.
The IDC supports ANSI/NFPA 72 Class B Style B
supervised input circuits (Class B Style C for IDCSC).

Alarm Log
The module tracks when either of its input circuits are
activated and will store these changes in non-volatile
memory. The time, date, and circuit number is stored
for the last eight events.

Each circuit requires its own end of line (EOL) resistor


for monitoring circuit continuity. Nominal resistance of
the resistor is 10 k ohms.

Enclosure

Inputs are software selectable in EagleVision NT to


actuate the alarm, trouble, or supervisory relays on the
LCU.

The explosion-proof, water-tight NEMA/Type 4X


enclosure is designed for use in a variety of hazardous
locations.

Outputs

FLAME DETECTORS

The output of the device is a status message that is sent


to the gateway and logic controller in the Local Control
Unit along the LON/SLC. System response to the
message is determined at the time of configuration. The
IDC supports ANSI/NFPA 72 Class A, Style 7
communication with the LCU.

The EQ22XXUV Series Ultraviolet Flame Detector has


been replaced by the X2200XXX24 Series Flame
Detectors. Refer to manual 95-8549 for details related
to the Model X2200 Series.
The EQ22XXUVIR Series Ultraviolet/Infrared Flame
Detector has been replaced by the X5200XXX24 Series
Flame Detector. Refer to manual 95-8546 for details
related to the Model X5200 Series.

A Standard Periodic Report (SPR) is sent to the gateway


at the rate determined at the time of configuration.
When programmed for response to a fire alarm
condition, a special Acknowledged Exception Report
(AER) is immediately sent to the Logic Controller.

The following EQ22XXUV and EQ22XXUVIR details are


provided for existing application purposes.

IV-1

95-8470

Table IV1EQ2200UV Detector Status/Indications

Status

LEDs

Normal with automatic oi selected

Blink every 5 seconds

Normal with manual oi selected


Fault (General)

Blink every 10 seconds

Power supply fault

Off

oi fault
UV being detected, but time delay not yet satisfied

LEDs continue blinking

Fire

On

Off
Off

T0005A

EQ2200UV UV FLAME DETECTOR

Terminal Wiring Board

DESCRIPTION

All external wiring is connected to screw terminal


connectors on the terminal wiring board located inside
the detector housing.

The EQ2200UV Series UV Flame Detector contains a UV


sensor module and control circuitry in an explosionproof, watertight enclosure. The detector is equipped
with both automatic and manual optical integrity (oi) test
capability.

Enclosure
The explosion-proof NEMA/Type 4X enclosure is
designed for use in a variety of hazardous locations.

Detector status is indicated by red LEDs visible through


the detectors viewing window. Table IV-1 indicates the
condition of the LEDs for each detector status.

SOFTWARE SELECTABLE OPTIONS

Output

The following software selectable options are available


through a PC running Det-Tronics configuration
software.

The output of the device is a status message that is sent


to the gateway and logic controller in the Local Control
Unit along the communication loop. System response
to the message is determined at the time of
configuration. The UV detector supports ANSI/NFPA 72
Class A, Style 7 communication with the LCU.

Operating Mode
The operating mode determines the type of logic that
the UV flame detector will use for processing fire signals
(either standard or arc rejection).

A Standard Periodic Report (SPR) is sent to the gateway


at the rate determined at the time of configuration.
When programmed for response to a fire alarm
condition, a special Acknowledged Exception Report
(AER) is immediately sent to the Logic Controller.

ARC REJECTION MODE


The arc rejection mode (recommended) enables the
detector to prevent nuisance fire alarms caused by UV
from short-duration electrical arcs or electrostatic
discharge, while maintaining the ability to reliably detect
the UV given off by a flame. The arc rejection mode is
not recommended unless these false alarm sources are
present within the application to be protected. Typical
applications that benefit from arc rejection logic include
electrostatic coating processes and uncontrolled
environments where transient UV sources can be
present, such as many typical outdoor applications.

Addressability
Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
range is 5 to 250).
Alarm Log
Each detector maintains an alarm log in non-volatile
memory. The time and date for the last eight alarms are
logged.

IV-2

The proper arc rejection setting for a given application


must be determined through testing. For indoor
applications with known electrostatic energy fields
within 15 feet of the detector, an arc rejection setting of
very high or high is typical. For outdoor
applications, medium or low arc rejection settings
are typical.

STANDARD MODE
In the standard processing mode, the detector output
(measured in counts per second) is compared to the
fire threshold (the sensitivity setting as described
below). If the radiant energy level from the fire exceeds
the selected alarm threshold level, the time delay
begins (if a time delay is selected). If the radiant energy
level from the fire remains above the selected sensitivity
level for the duration of the time delay, the fire alarm
output is activated. In every application, it is crucial to
ensure that the radiant ultraviolet energy level from the
expected fire at the required distance from the detector
will exceed the selected sensitivity level.

It is recommended that each detector be thoroughly


tested at the programmed arc rejection setting within
the ambient conditions that will be present during
normal operation. This will help to ensure that the
selected arc rejection setting is proper for the
application.
Sensitivity

Standard signal processing is recommended for


controlled indoor applications only.

Whether the Standard or Arc Rejection mode is


selected, the sensitivity setting must always be
programmed. The selected sensitivity level determines
the fire alarm threshold setpoint. The higher the
sensitivity level, the greater the detection range, but the
possibility of false alarms will be increased. Four
sensitivity levels are selectable. Refer to Table IV-3.

The arc rejection algorithm examines the radiant energy


level detected within a specified unit of time (timed
gate). Detector output is determined by three variables:
sensitivity level
gate length
number of consecutive gates required.

The sensitivity setting must be appropriate for the


anticipated fire size at the required distance from the
detector.

Different combinations of these variables allow for


various levels of transient arc rejection capability. There
are four arc rejection levels (very high, high, medium,
and low) that are selectable for each detector through
the PC. Refer to Table IV-2.

Table IV2Arc Rejection Levels for UV Detector

Arc Rejection Level

Consecutive Gates

Gate Length

Sensitivity*

Min. Processing Time

Very High

1/16 Second

Very High (8 CPS)

0.5 Second

High

1/16 Second

Very High (8 CPS)

0.25 Second

Medium

1/8 Second

Very High (8 CPS)

0.5 Second

Low

1/4 Second

Very High (8 CPS)

1.0 Second
T0006A

* CPS = counts per second


Table IV3Sensitivity Levels for UV Detector

Sensitivity Level Equivalents


Sensitivity Level Selected

Nominal Fire Alarm Threshold


In Counts per Second (CPS)

Very High

High

24

Medium

48

Low

96
T0007A

IV-3

95-8470

The EQ2200UVHT is an electronic module assembly


that is used in conjunction with a high temperature rated
C7050B UV detector (with DE1888K3 high temperature
rated UV sensor tube). The two devices are mounted in
separate explosion-proof, watertight enclosures.

Time Delay
Arc rejection mode If the fire signal meets the
programmed arc rejection requirements, the time delay
begins. A fire output is generated if the fire signal
continues for the duration of the time delay.

The UV detector is rated for continuous duty in


environments up to +125C (+257F). The electronic
module is rated up to +75C (+167F).

Standard mode A fire output is generated only if the


fire signal exceeds the sensitivity setting for the entire
duration of the programmed time delay.

NOTE
The electronic module cannot be located in the
high temperature area.

Automatic or Manual oi
The o i system uses an internally generated UV test
signal to determine the relative condition of the detector
and its optical surfaces.

The UV detector and electronic module assembly can


be separated up to 165 feet (50 meters) using high
temperature rated 4 core shielded cable.

If automatic o i testing is selected, the o i test is


automatically performed once every minute. The
automatic oi test does not generate an alarm output or
interfere with normal detector operation.

NOTE
In accordance with NFPA 72, the maximum
separation distance is 20 feet (6 meters) using
conduit or equivalent protection against
mechanical damage.

The manual oi test is initiated using a button on the


point display screen at the PC. The manual oi test can
be used in addition to automatic oi to verify correct
system operation.

LED
Detector status is indicated by a red LED that is visible
through the viewing window on the cover of the
electronic module junction box.

Fire Output Latching


When latching operation is selected, the fire alarm
signal is cleared by removing input power for a
minimum of 0.1 second.

Refer to the EQ2200UV UV Flame Detector section


above for a description of features, operating
characteristics and software selectable options of DetTronics Eagle Quantum UV detectors.

Fault Latching
If the fault output is set for latching, the fault will not
clear until it is corrected and the unit is reset. If a fire
occurs, the unit will indicate a fire, over-riding the fault
condition, i.e., the fault signal will clear if not latched. If
a fault is still present after the fire has been
extinguished, the unit will again indicate a fault until the
problem has been corrected and the unit is reset.

EQ2200UVIR FLAME DETECTOR


DESCRIPTION
The EQ2200UVIR Series Flame Detector is designed to
provide reliable fire protection in applications where the
use of either ultraviolet (UV) or infrared (IR) detectors
alone can result in false alarms. When used alone, a UV
detector can respond to sources of ultraviolet radiation
besides fire, such as lightning, x-rays or arc welding.
Likewise, an IR detector can respond to various hot
objects, such as flickering or chopped radiation from
electric heaters or exhaust manifolds.
The
microprocessor based EQ2200UVIR combines both a
UV and a single frequency IR sensor in a single
detector and requires simultaneous response of both
sensors to generate a fire alarm. These two detecting
elements monitor different portions of the radiation
spectrum and have virtually no common sources of
false alarms. This enables the detector to respond to a
real fire while ignoring potential false alarm sources
such as arc welding, x-rays, or hot vibrating objects.

EQ2200UVHT HIGH TEMPERATURE


UV FLAME DETECTOR
DESCRIPTION
The EQ2200UVHT UV Flame Detector provides UV
flame protection in continuous duty high temperature
applications, such as turbine compartments,
enclosures, generator rooms, etc. where ambient
temperatures can continuously exceed +75C (+167F).

IV-4

Microprocessor based circuitry located inside the


detector junction box continuously monitors the two
sensors, evaluating the signal(s) with fire and fault
algorithms to determine the current status of the
detector. When both sensors simultaneously detect the
presence of fire, the microprocessor generates a fire
signal, which is immediately sent over the LON/SLC to
the logic controller in the Local Control Unit (LCU). The
LEDs, visible through the UV sensor viewing window,
are also immediately illuminated. In addition, a
watchdog timer assures that the detectors operating
program is running properly.

Enclosure
The explosion-proof NEMA/Type 4X enclosure is
available in either aluminum or stainless steel and is
designed for use in a variety of hazardous locations.
LEDs
Detector status is indicated by a pair of red LEDs
(illuminated simultaneously) that are visible through the
viewing window of the UV sensor.
Table IV-4 indicates the condition of the LEDs for each
detector status.

Detector Output
The output of the device is a status message that is sent
to the gateway and logic controller in the LCU along the
communication loop. System response to the message
is determined at the time of configuration. The detector
supports ANSI/NFPA 72 Class A, Style 7 communication
with the LCU.

Automatic Diagnostics
The microprocessor based detector is equipped with
advanced fault detection and diagnostic capabilities.
The LED indicators on the UV sensor module provide
the user with visual annunciation of the problem area.
In addition, the point display screen at the OIS provides
a variety of information regarding detector status as well
as the actual UV and IR signal levels present at the
detector. Refer to Table IV-5 for a list of status
conditions.

Status Conditions
Detector status conditions include normal operation,
fire, fault, UV only, and IR only. A fire alarm signal is
generated when both UV and IR sensors are active.
The fire alarm status has the highest priority and will
override a fault condition.

SOFTWARE SELECTABLE OPTIONS


The following options are selectable through a PC
running Det-Tronics configuration software:

Addressability
Device identification is accomplished by setting rocker
switches on an eight position DIP switch (valid address
range is 5 to 250).

Processing Mode
The UV portion of the detector offers a choice of two
different types of logic that can be used for processing
fire signals either standard or arc rejection.

Alarm Log
Each detector maintains an alarm log in non-volatile
memory. The time and date for the last 8 alarms are
logged.

Table IV4EQ2200UVIR Detector Status/Indications

Detector Status

LED

Fault
Automatic oi
Manual oi
UV only
IR only
Alarm

Off
On for 0.25 second every 5 seconds
On for 0.25 second every 10 seconds
On for 50 milliseconds off for 500 milliseconds
On for 200 milliseconds off for 500 milliseconds
On steady
T0030

IV-5

95-8470

Table IV5Status Conditions of UV/IR Detector

Status Indication

Possible Cause

Low Voltage

Power supply.
Detector power wiring.

COM 1

LON wiring on COM 1 side of detector.


Detector communication circuitry problem.

COM 2

LON wiring on COM 2 side of detector.


Detector communication circuitry problem.

IR Alarm

IR radiation source within view of detector.

UV Alarm

UV radiation source within view of detector.

Not communicating

Power supply or power wiring problem.


LON wiring problem.
Detector communication circuitry problem.
Wrong DIP switch address setting.

Inhibit active

Inhibit activated at OIS.

Unable to configure

Configuration problem. Repeat configuration.

Invalid Configuration

Configuration problem. Repeat configuration.

UV fault

Defect in UV module. (See extended status.)

IR fault

Defect in IR module. (See extended status.)

Power-up

Detector in power-up time delay.


Solution: Wait for detector to exit delay. Replace detector.

Auto configuration fault

Configuration problem. Repeat configuration.

General fault

Power supply failure.


Power or LON wiring problem.
Electronic failure in detector.

Fire alarm

UV and IR radiation detected.

UV oi fault

UV viewing window or oi ring dirty.


UV oi ring missing.

UV tube missing

Module missing. Install module.


Dirty or broken contacts on module.

UV 290 volt fault

Internal power problem. Replace detector terminal board.

IR oi fault

IR viewing window or oi ring dirty.


IR oi ring missing.

IR missing module

Module missing. Install module.


Dirty or broken contacts on module.
T0031B

IV-6

ARC REJECTION MODE

Sensitivity

The arc rejection mode (recommended) enables the


detector to prevent nuisance fire alarms caused by
short-duration electrical arcs or electrostatic discharge,
while maintaining the ability to reliably detect a flame.
The arc rejection mode is not recommended unless
these false alarm sources are present within the
application to be protected. Typical applications that
benefit from arc rejection logic include any uncontrolled
environments where transient radiation sources can be
present, such as many typical outdoor applications.

Whether Arc Rejection or Standard mode is selected,


the sensitivity setting must always be programmed. The
selected sensitivity level determines the fire alarm
threshold setpoint. The higher the sensitivity level, the
greater the detection range, but the possibility of false
alarms will be increased. Four sensitivity levels are
selectable. (Sensitivity levels for UV and IR are selected
separately.)
The sensitivity setting must be appropriate for the
anticipated fire size at the required distance from the
detector. Refer to the Specifications section of this
manual for additional information.

The arc rejection algorithm examines the radiant energy


level detected within a specified unit of time (timed
gate). The output of the detector is determined by three
variables:
sensitivity level
gate length
number of consecutive gates required.

Time Delay
A time delay from 0 to 7 seconds is selectable.
STANDARD MODE

Different combinations of these variables allow for


various levels of transient arc rejection capability. There
are two arc rejection levels (medium and high) that are
selectable for the detector through the OIS. The proper
arc rejection setting for a given application must be
determined through testing.

A fire output is generated only if the fire signal exceeds


the sensitivity setting for the entire duration of the
programmed time delay.
ARC REJECTION MODE

It is recommended that each detector be thoroughly


tested at the programmed arc rejection setting within
the ambient conditions that will be present during
normal operation. This will help to ensure that the
selected arc rejection setting is proper for the
application.

If the fire signal meets the programmed arc rejection


requirements, the time delay begins. A fire output is
generated if the fire signal continues for the duration of
the time delay.

STANDARD MODE

The EQ2200UVIR is equipped with the Optical Integrity


(oi) feature. The oi test is performed on both the UV
and IR sensors to check the cleanliness of the detector
optics, as well as the proper functioning of the sensors
and electronic components of the detector. If a
problem should occur, it is quickly detected.

Automatic or Manual oi

In the standard processing mode, the UV sensor output


(measured in counts per second) is compared to the
fire threshold (the sensitivity setting as described
below). If the radiant energy level from the fire exceeds
the selected alarm threshold level, the time delay
begins (if a time delay is selected). If the radiant energy
level from the fire remains above the selected sensitivity
level for the duration of the time delay, a fire alarm
signal is generated. In every application, it is crucial to
ensure that the radiant energy level from the expected
fire at the required distance from the detector will
exceed the selected sensitivity level.

The detector is user programmable (from a PC running


Det-Tronics configuration software) for automatic o i
testing. If automatic testing is selected, the oi test is
automatically performed on each sensor. The rate for
the UV sensor test is once per minute. The rate for the
IR sensor is field selectable from once a minute to once
every four hours. If a fault is detected, a trouble signal
is sent to the LCU over the LON/SLC. A fault condition
is indicated at the logic controller and the gateway and
also by the LEDs on the detectors UV sensor. The
automatic oi test does not generate an alarm output or
interfere with normal detector operation.

Standard signal processing is recommended for


controlled indoor applications only.

IV-7

95-8470

The manual oi test is initiated using a button on the


point display screen at the OIS. A successful test is
signaled by the OIS. The manual oi test can be used in
addition to automatic o i to verify correct detector
operation.

Output
The Standard Periodic Report (SPR) is sent to the
gateway at the rate determined at the time of
configuration (from one to ten seconds).
Calibration

NOTE
The manual oi test does not generate an alarm
output or actuate any system outputs.

A magnetic reed switch, located on the terminal board,


enables calibration of the sensor without opening the
enclosure. The switch is activated by placing a
calibration magnet at a specified location on the side of
the enclosure. Once the calibration mode has been
entered, the DCU steps the user through the process.
For details, refer to the Calibration section of this
manual.

Fire Output Latching


When latching operation is selected, the fire alarm
signal is present until cleared by a reset command from
the PC.

Addressability

EQ2200DCU AND EQ2200DCUEX


DIGITAL COMMUNICATION UNIT

Device identification is accomplished by setting


switches on an eight position DIP switch (valid address
range is 5 to 250).

DESCRIPTION
The EQ2200 Series Digital Communication Unit (DCU)
digitizes a 4 to 20 ma analog signal and transmits the
value as the process variable portion of its Standard
Periodic Report (SPR) to the Communication Gateway
located in the LCU. All circuitry is housed in a single
explosion-proof/watertight enclosure for use in the area
of detection.

Status LEDs
Three LEDs are located at the center of the
communication module circuit board and are visible
through the window on the enclosure cover.
The green LED serves as a power-on indicator and is
illuminated whenever power is applied. During normal
operation, only the green LED is illuminated.

Designed for use with the Eagle Quantum system, the


DCU provides a unique technique for detecting and
isolating opens or shorts in the Local Operating
Network/Signaling Line Circuit (LON/SLC) wiring. This
fault isolation method allows for communication integrity
in the event of a single wiring fault in the LON/SLC
wiring.

The red LED is used to indicate a calibration, power-up,


fault or alarm condition. The flashing rate of the red
LED indicates the following conditions:
Power-up =
Calibration =
Fault =
Alarm =

The DCU is approved for use with a variety of Detector


Electronics sensors including catalytic combustible gas
sensors, the PointWatch IR gas detector, as well as
electrochemical sensors (hydrogen sulfide, carbon
monoxide, chlorine, sulfur dioxide, and nitrogen
dioxide). It will also accept any sensor with a linear 4 to
20 ma output signal and allows for one person nonintrusive calibration.

Pulsed at a 0.5 Hz rate


Pulsed at a 1 Hz rate or on steady
Pulsed at a 4 Hz rate
Illuminated continuously.

NOTE
If the communication module has not been
configured, the red LED blinks at the 4 Hz rate.
The amber LED is provided for factory diagnostic
purposes and is not used in the system. Illumination of
the amber LED normally indicates a failure in the
communication chip.
Replacement of the
communication module circuit board is required.

Inputs
The DCU features one 4 to 20 ma non-isolated input,
with an input impedance of 200 ohms in series with a
protection diode. (When used with a Det-Tronics
catalytic combustible gas sensor, a separate transmitter
board converts the millivolt output to a 4 to 20 ma
signal.) The DCU also monitors its 24 vdc supply
voltage and reports to the PC when requested.

IV-8

EQ2500ARM AGENT RELEASE


MODULE

Calibration Log
The DCU keeps a calibration log in non-volatile memory
that can be used by the operator to evaluate the
remaining life of some sensors. This log includes the
zero, span, date and time for each successful
calibration. An aborted calibration is indicated by zeros
in the zero and span values. The calibration log is
cleared when the sensor replacement switch is pressed
and the calibration is successfully completed.

DESCRIPTION
The EQ2500ARM Series Agent Release Module (ARM)
is located on the LON/SLC and provides agent release
capability for the Eagle Quantum system. The device is
controlled by programmable logic in the Logic
Controller and can be programmed for Single, Cross
or Counting Zone Style initiation. Optional time delay,
abort and manual release sequences allow the output to
be programmed for use in unique applications.

The initial calibration is logged in position one, where it


remains for the life of the sensor. If more than 8
calibrations are performed without the sensor
replacement switch being pressed, the newest
calibration data will replace the second oldest so that
the initial calibration data can be saved. The old
calibration data will be lost. This feature enables sensor
sensitivity trending to aid in maintenance or
troubleshooting.

The Agent Release Module can monitor and control two


output devices (rated for 24 vdc), which are
programmed and energized together. The release
circuits are compatible with a variety of solenoid or
initiator (squib) based suppression systems.
The release circuit is supervised for open circuit
conditions. If a trouble condition occurs (open circuit or
solenoid supply voltage less than 19 volts), it will be
indicated at the LCU.

The analog value for the sensor is represented in raw


analog to digital counts 0 to 4095, where 0 represents 0
ma and 4095 represents 24 ma.
Alarm Log

Each output is rated at 2 amperes. Auxiliary input


terminals are provided for additional 24 vdc output
power where needed.

A log of low and high alarms is stored in each DCU.


Time, date and alarm type are logged for each alarm
event. A maximum of eight events can be stored. If
more than eight events are logged, the oldest event will
be overwritten.

Solenoids/Initiators
The releasing output devices listed in Table IV-6 are
recommended for use with the Agent Release Module.

Enclosure

The solenoids listed in Table IV-7 are compatible with


the Agent Release Module for deluge and pre-action
applications.

The explosion-proof, watertight NEMA/Type 4X


enclosure is designed for use in a variety of hazardous
locations. The cover is furnished with a window to allow
the operator to view the three status indicator LEDs on
the communication module PC board.

Table IV-6Recommended Releasing Output Devices


for Agent Release Module

Terminal Wiring Board

Manufacturer
Fenwal

All external wiring is connected to screw terminal


connectors on the terminal wiring board located inside
the junction box.

Model
890181
(2.4 A. max., 10 , momentary)

Fenwal

899175
(2.4 A. max., 10.8 , momentary)

Fenwal

895630-000
(2 A. max., 12 , momentary)

Fenwal

897494
(1.5 A. max., 15.9 , continuous)

Fenwal

486500-001
(240 ma max., 103 , momentary)

Fenwal

31-199932-004
(2.4 A. max., 10 , momentary)

IV-9

95-8470

EQ2500SAM SIGNAL AUDIBLE


MODULE

Table IV-7Solenoid Compatibility with Agent Release Module for


Deluge and Pre-Action Applications

Manufacturer

Model

DESCRIPTION

Skinner

LV2LBX25

ASCO

8210A107

ASCO

8210G207

Skinner

73218BN4UNLVNOC111C2

Skinner

73212BN4TNLVNOC322C2

Skinner

71395SN2ENJ1NOH111C2

The EQ2500SAM Series Signal Audible Module (SAM)


provides two indicating circuits for controlling UL Listed
24 vdc polarized audible/visual indicating appliances.
The device is located on the LON/SLC and is controlled
by programmable logic in the Eagle Quantums Logic
Controller.

T0037B

Addressability
Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
range is 5 to 250).

Each output circuit is independently programmable to


allow annunciation of separate events. In release
applications, signal outputs can be programmed to
provide signaling for pre-release, release or postrelease. Each output can be individually activated for
any one of the following pre-defined coded outputs:
1. Continuous until reset

Status LEDs
2. 60 beats per minute
Three LEDs located at the center of the circuit board
provide a visual indication of device status conditions.
Green On steady when power is applied to the
device.
Red

Blinking at a 4 Hz rate with the LED on 50%,


off 50% of the time indicates a local trouble
condition such as an open output circuit or
low solenoid supply voltage.
Blinking at a 1 Hz rate with the LED on 5%,
off 95% of the time indicates an isolate
condition.
Blinking at a 1 Hz rate with the LED on 95%,
off 5% of the time indicates release and
isolate.

Yellow On indicates a malfunction in the electronic


circuitry. Replace the module.

3. 120 beats per minute


4. Temporal pattern.
The outputs operate in the reverse polarity fashion when
activated. Each output is rated at 2 amperes. Auxiliary
input terminals are provided for additional 24 vdc
signaling power where required.
The output circuits are supervised for open and short
circuit conditions. If a wiring fault occurs, a trouble
condition will be indicated at the LCU.
Addressability
Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
range is 5 to 250).
Status LEDs

Alarm Log
Time and date are logged each time that a release
occurs. Data for the last eight events is stored in nonvolatile memory.

Three LEDs located at the center of the circuit board


provide a visual indication of device status conditions.
Green On when power is applied to the device.
Red

Terminal Wiring Board

On steady indicates an active condition.


Blinking indicates a local trouble condition
such as an open or shorted output circuit or
low output supply voltage.

All external wiring is connected to screw terminal


connectors on the terminal wiring board located inside
the device enclosure.

Yellow On indicates a malfunction in the electronic


circuitry. Replace the module.

IV-10

Alarm Log

GENERAL APPLICATION INFORMATION

Time and date are logged each time that a fire alarm
occurs. Data for the last eight events is stored in nonvolatile memory.

System Capacity

Terminal Wiring Board


All external wiring is connected to screw terminal
connectors on the terminal wiring board located inside
the device enclosure.

EQ2400NE NETWORK EXTENDER


DESCRIPTION
The EQ2400NE Series Network Extender expands the
capabilities of the Eagle Quantum system by allowing
additional nodes as well as additional wiring to be
added to the LON/SLC (communication loop). Without a
network extender, the communication network is limited
to 60 nodes on a 2000 meter loop. Each network
extender, however, increases the capacity of the loop
by up to 40 nodes and 2000 meters of wiring, up to a
maximum of 244 field nodes and 10,000 meters of
wiring.
Network extender circuitry supports communication in
both directions. If a network wiring fault should occur,
uninterrupted communication can continue in the
opposite direction.
LEDs
The network extenders electronic module is furnished
with three LEDs (one green and two yellow) for
indicating device status.
The green LED indicates that power is applied and
flashes to indicate that messages are being transferred
over the network.

The basic Eagle Quantum system supports a


communication loop consisting of up to 60 detection
nodes and up to 2000 meters of connecting wiring.
Adding a network extender to the loop allows it to be
expanded by up to 40 nodes with an additional 2000
meters of wiring. Up to 6 network extenders can be
utilized in a single system, supporting up to 244 field
nodes and up to 10,000 meters of wiring.
To ensure optimum performance, it is important to
distribute the network extenders along the loop so that
there are no more than 40 detection nodes or 2000
meters of wiring on either side of a network extender.
See Figure IV-1.
Response Time vs. System Size
When designing a system, it is important to realize that
increasing the number of nodes on the communication
loop can result in an increase in the amount of time
required for a status change message from a detection
node to reach the host computer.
The gateway requires a finite length of time to process
each bit of information that is transferred along the
communication network. As the number of nodes
increases, so does the amount of data that is being
processed as well as the time required for processing
the data. As a result, the update time for each node
should be increased to accommodate the extra traffic
for a large system (one second minimum for each 50
nodes).
If the fastest possible communication response time is
an important criteria for a large system, it is
recommended that the number of nodes on an
individual loop be kept as small as practical. Consider
using multiple loops with fewer nodes per loop rather
than one large loop.

The two yellow LEDs correspond to the two


communication transceivers and are illuminated to
indicate that an internal fault has been detected.
Enclosure
The network extenders electronic circuitry is mounted
inside an explosion-proof, water-tight enclosure for
installation in hazardous locations. The enclosure is
available with up to six 3/4 inch NPT or 25 mm conduit
entries.

IV-11

95-8470

60 NODE LOOP

RIGHT

LCU

100 NODE LOOP

NE

50 NODES

50 NODES

WRONG

LCU

100 NODE LOOP

40 NODES

NE

NE

RIGHT
30 NODES

30 NODES

LCU

NOTES:

1.

2.

3.

BASIC LOOP WITHOUT A NETWORK EXTENDER


CANNOT EXCEED 60 NODES AND 2000 METERS
OF WIRE.
NO MORE THAN 40 NODES AND 2000 METERS OF
WIRE BETWEEN NETWORK EXTENDERS OR
BETWEEN A NETWORK EXTENDER AND THE LCU.
NO MORE THAN 244 FIELD NODES AND 10,000
METERS OF WIRE ON THE LOOP.
A1946

Figure IV-1Eagle Quantum Communication Loops

IV-12

Section V
Detector Application
Information

pressure. It is also insensitive to the ultraviolet


component of solar radiation.
UV radiation generated by periodic lightning or sparks
in the area can be effectively ignored by the detector
using the arc rejection feature or time delay.

UV DETECTORS
In applying any type
detector, it is important
can prevent the device
also to know what other
the device to respond.

of sensing device as a fire


to know of any conditions that
from responding to a fire, and
sources besides fire will cause

UV detectors should not be positioned so that their cone


of vision can scan the horizon. Rather, they should be
directed down over the designated hazardous area to
reduce the likelihood of picking up UV radiation from
distant sources.

WINDOWS
Table V-1UV and IR Absorbing Gases and Vapors

Glass and plexiglas windows significantly attenuate UV


radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Detector Electronics for recommendations regarding
window materials that will not attenuate UV radiation.

The following is a partial list of compounds that exhibit


significant UV absorption characteristics. These are also
usually hazardous vapors. While generally of little
consequence in small amounts, these gases can restrict
UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
not large amounts of these gases may be released as a
result of a fire-causing occurrence.

OBSTRUCTIONS
For an ultraviolet detector, dust, dirt and other films, UV
absorbing gases or vapors as well as physical
obstructions must not be allowed to come between the
detector and the protected hazard (see Table V-1).

Acetaldehyde
Acetone
Acrylonitrile
Ethyl Acrylate
Methyl Acrylate
Ethanol
Ammonia
Aniline
Benzene
1,3 Butadiene
2Butanone
Butylamine
Chlorobenzene
1-Chloro-1-Nitropropane
Chloroprene
Cumene
Cyclopentadiene
O-Dichlorobenzene
P-Dichlorobenzene

SMOKE
Smoke will absorb UV radiation, and if accumulations of
dense smoke can be expected to precede the
presence of flame, then ultraviolet detectors that are
used in enclosed areas should be mounted on the wall
approximately 3 feet (1 meter) from the ceiling where
the accumulation of smoke is reduced.
ARC WELDING
Electric arc welding is a source of intense ultraviolet
radiation, and care must be taken to ensure that arc
welding is not performed in the protected area without
securing the fire detection system. UV radiation from
arc welding readily scatters and can deflect across
significant distances, even when direct obstructions
exist. Any open door or window can allow nuisance UV
radiation from arc welding to enter an enclosed area.

Methyl Methacrylate
Alpha-Methylstyrene
Naphthalene
Nitroethane
Nitrobenzene
Nitromethane
1-Nitropropane
2-Nitropropane
2-Pentanone
Phenol
Phenyl Clycide Ether
Pyridine
Hydrogen Sulfide
Styrene
Tetrachloroethylene
Toluene
Trichloroethylene
Vinyl Toluene
Xylene

If UV-absorbing gases may be a factor in a given


application, precautionary measures should be taken.
Detectors can be placed closer to the potential hazard
area, and/or the sensitivity of the detection system can be
increased. Contact the factory for further details.
Substances such as methane, propane, butane, hexane,
camphor and octane are not UV absorbing.

When x-rays or radioactive substances are present in


the area being protected, the UV system must be
disabled until those sources are removed.

Absorption of infrared radiation in the range of 4.2 to 4.7


microns is not a significant problem with most organic
vapors, with the exception of those compounds that have
triple bonds such as acetylene, nitriles, silane, or
isocyanates. Carbon dioxide concentrations higher than
normally present in the atmosphere can also cause
substantial loss of fire detection sensitivity.

COMMON ENVIRONMENTAL CONDITIONS


The detector is not affected by environmental conditions
such as wind, rain or extremes of temperature and

V-1

95-8470

UV DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should be taken into consideration:

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

Identify all high risk fire ignition sources.


Be sure that enough detectors are used to adequately
cover the hazardous area.

INCORRECT

For fastest response time, locate the detector as close


as possible to the anticipated fire source. The central
axis of the detectors cone of vision provides the
highest sensitivity.
Be sure that the unit is easily accessible for cleaning
and other periodic servicing.

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

Particular attention should be paid to potential false


alarm sources within the cone of vision of the detector.

B1974

CORRECT

For outdoor applications, the detector should be


aimed downward at least 10 to 20 degrees to prevent
it from scanning the horizon. This minimizes response
to distant UV sources outside the protected area. See
Figure 1.

NOTE: DETECTOR MUST ALWAYS BE AIMED


DOWNWARD AT LEAST 10 TO 20 DEGREES.

Figure 1Detector Orientation Relative to Horizon

Any object having a temperature greater than 0


Kelvin (273C) emits infrared radiation. The hotter
the object, the greater the intensity of the emitted
radiation. The closer the infrared source is to the
detector, the greater the potential for a false alarm.
The IR sensor can respond to IR radiation sources
that can meet the amplitude and flicker
requirements of the detector such as vibrating hot
objects.

Dense fog, rain or ice will absorb UV radiation and


reduce the sensitivity of the detector.
If smoke is expected before flame, it is recommended
that smoke or other additional detectors be used in
conjunction with the UV detector.
If possible, fire tests should be conducted to verify
correct detector positioning and coverage.

Although the detector is designed to reduce false


actuations, certain combinations of ambient
radiation must be avoided. For example, if IR
radiation with an intensity that exceeds the fire
threshold of the IR sensor should reach the detector
as a flickering signal, and if at the same time an
electric arc welding signal also reaches the
detector, an alarm output will be generated.

UV/IR DETECTORS
FALSE ALARM SOURCES
UV: The UV sensor is insensitive to the ultraviolet
component of solar radiation. However, it will
respond to sources of UV besides fire, such as
electric arc welding, lightning, high voltage corona,
x-rays and gamma radiation.

NOTE
Radiation generated by false alarm sources such
as periodic lightning or sparks in the area can be
effectively ignored by the detector using the arc
rejection feature or time delay.

IR: The detector has been designed to ignore steady


state infrared sources that do not have a flicker
frequency characteristic of a fire, however, it should
be noted that if these steady state infrared sources
are hot enough to emit adequate amounts of
infrared radiation in the response range of the IR
sensor and if this radiation becomes interrupted
from the view of the detector in a pattern
characteristic of a flickering flame, the IR sensor
can respond.

Arc Welding
Electric arc welding is a source of intense ultraviolet
radiation. UV radiation from arc welding readily scatters
and can deflect across significant distances, even when
direct obstructions exist. Any open door or window can
allow nuisance UV radiation from arc welding to enter
an enclosed area.

V-2

UV/IR DETECTOR POSITIONING

The UV/IR detector does not respond to arc welding


beyond 10 feet from the detector. However, a UV only
signal will be generated in response to the intense UV
radiation generated by the arc welding, and at
distances closer than 10 feet the heated metal from the
welding can become a false alarm source for the IR
sensor.

IMPORTANT
Detectors should not be positioned so that their
cone of vision can scan the horizon. Rather, they
should be directed down over the designated
hazardous area to reduce the likelihood of picking
up radiation from distant sources. See Figure 1.

FACTORS INHIBITING DETECTOR RESPONSE


Detectors should be located in positions best suited for
covering the area to be protected. Whenever practical,
they should be placed where they will be easily
accessible for cleaning and other periodic servicing.
Particular attention should also be paid to potential false
alarm sources within the cone of vision of the detector,
such as distant arc welding, or the rotating blades of a
fan or surface vibration of an IR source, which could
allow a flickering IR signal to reach the detector. Rain
or ice can absorb radiation, which can reduce the
capability of the detector. For outdoor applications, aim
the detector downward to minimize the buildup of water
or ice on the detector viewing windows and to prevent
the cone of vision from scanning the horizon. This
minimizes response to distant radiation sources outside
the protected area.

Windows
Glass and Plexiglas windows significantly attenuate
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Detector Electronics for recommendations regarding
window materials that will not attenuate radiation.
Obstructions
Radiation must be able to reach the detector in order for
it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector. In
addition, UV or IR absorbing gases or vapors must not
be allowed to accumulate between the detector and the
protected hazard. See Table V-1 for a list of these
substances.

GAS DETECTOR POSITIONING


The sensor must be properly located to enable it to
provide maximum protection. The formula for
determining the most effective number and placement
of sensors varies depending on the conditions at the job
site. The individual performing the installation must rely
on experience and common sense to determine the
quantity of sensors and the best sensor locations to
adequately protect the area.

Smoke
Smoke will absorb radiation. If accumulations of dense
smoke can be expected to precede the presence of a
flame, then detectors that are used in enclosed areas
should be mounted on the wall approximately 3 feet (1
meter) from the ceiling where the accumulation of
smoke is reduced.

The following factors should be considered for every


installation:

Detector Viewing Windows


It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered
substances that can significantly attenuate UV and/or IR
radiation include, but are certainly not limited to, the
following:

1. What kind of gas is to be detected? If it is lighter


than air (acetylene, hydrogen, methane, etc.), place
the sensor above the potential source. Place the
sensor close to the floor for gases that are heavier
than air (benzene, butane, butylene, propane,
hexane, pentane, etc.) or for vapors resulting from
flammable liquid spills. However, note that air
currents can cause a gas that is heavier than air to
rise. In addition, if the gas is hotter than ambient
air, it could also rise.

Silicones
Oils and greases
Ice buildup
Dust and dirt buildup
Paint overspray.

2. How rapidly will the gas diffuse into the air? Select
a location for the sensor as close as practical to the
anticipated source of a gas leak.

V-3

95-8470

3. Ventilation characteristics of the immediate area


must also be considered. Movement of air will
cause gas to accumulate more heavily in one area
than another. The sensor should be placed in the
area where the most concentrated accumulation of
gas is anticipated. Also consider the fact that many
ventilation systems do not operate continuously.

When a sensor is exposed to a different or new


environment, calibration should be checked frequently
to determine the proper interval between periodic
calibrations.
Before performing calibration, the operator should
examine the sensor filter (flame arrester) to be sure that
it is not missing or damaged. If the filter is defective or
missing, it must be replaced. In some cases, an
exposed sensing element can act as an ignition source.
It should also be noted that a dirty cover can
significantly reduce the sensitivity of the sensor.

4. The sensor should be pointed down to prevent the


buildup of moisture or contaminants on the filter and
to ensure proper operation. For PointWatch, refer to
instruction manual 95-8440.
5. The sensor must be accessible for testing and
calibration. The use of the Sensor Separation Kit
will be required in some installations.

CATALYTIC SENSOR OPERATION


The sensing element used in the combustible gas
sensor consists of a pair of elements. One is an active
catalytic sensing element, and the other is inactive and
acts as a temperature compensating reference element.
Both elements are composed of a wire coil encased in
ceramic. The active element has a catalytic coating
applied to its surface, however, the reference element is
glazed so that it does not react to the presence of a
combustible gas/air mixture. The pair is computer
matched to have the same electrical resistance.

6. Catalytic sensors should be located where they are


safe from potential sources of contamination that
can poison the sensing element.
7. Exposure to excessive heat or vibration can result in
premature failure of any electronic device and
should be avoided if possible. Shielding the device
from intense sunlight will reduce solar heating and
can increase the life of the unit.

In the presence of a combustible gas/air mixture, the


resistance of the active sensing element increases in
proportion to the concentration of gas at the sensor.
The change in resistance of the active sensing element,
relative to that of the reference element, is used to
determine the actual level of combustible gas present at
the sensor.

For additional information on determining quantity and


placement for sensors in a specific application, refer to
Instrument Society of America (ISA) Transaction Volume
20, Number 2, titled The Use of Combustible Detectors
in Protecting Facilities from Flammable Hazards.

CATALYTIC GAS SENSORS

Both elements operate at a high temperature and are


enclosed by a porous stainless steel cup (flame
arrester). See Figure V-2. This cup allows the diffusion
of gas to and from the sensing element, but prevents
the ignition of the atmosphere outside the sensor should
the combustible gas concentration exceed its LFL.

CAUTION
Exposure to a high level of gas can have an
adverse effect on the sensitivity of catalytic sensing
elements. If the level of gas at the sensor should
reach 100% LFL, it is important that it be tested
and recalibrated if required. In some cases, it may
be necessary to replace the sensor.

A barrier is placed between the element pair to prevent


thermal interaction and to prevent the transfer of
catalytic material from the active element to the surface
of the reference element.

If an over-range condition should occur, the user


must exercise caution, since a highly explosive
condition could exist. The hazardous area should
be checked with a portable detection instrument to
determine the actual level of combustible gas
present.

All catalytic type sensors require oxygen to detect


combustible gases. The sensor response will decrease
if enough combustible gas displaces the normal oxygen
present in air. The sensor should not be used where the
oxygen level is less than 10%. See Figure V-3.

For best calibration results, allow a new sensor to


operate for several hours to ensure a stable output
before performing calibration. For the highest degree of
accuracy, perform a second calibration after 24 hours.

Figure V-4 shows the response of a typical sensor to


various levels of combustible gas. Note that a reading of
40% LFL will be given at 2.0% methane (40% LFL) and

V-4

BLK

RED

WHT

also at 80.0% methane, well above the upper flammable


limit of methane. Although gas levels above the upper
flammable limit will not propagate a flame, it stands to
reason that somewhere between the leak and clear air
there will be a flammable mixture.
CAUTION
It is possible for the display to drop to a low % LFL
reading after going into high alarm and still have an
unsafe level of combustible gas present.
Therefore, precautions should be taken to ensure
that the combustible gas has been cleared before
classifying the area as safe.

ACTIVE ELEMENT

REFERENCE ELEMENT
THERMAL BARRIER

FLAME ARRESTER

B1124

Figure V2Catalytic Combustible Gas Sensor

90% LFL METHANE IN STANDARD AIR


100

4.5% METHANE

90

80

70
50% LFL METHANE IN STANDARD AIR
60

CONTROLLER
DISPLAY
READING
(%LFL)

2.5% METHANE

50

40

30

20

10

0
0
B1126

10

15

20

30

40

50

60

70

80

90

100

PERCENT OF OXYGEN IN MIXTURE (BY VOLUME)

Figure V3Effect of Oxygen Enriched and Deficient Atmosphere on the Response of a Typical Catalytic Sensor

V-5

95-8470

180

160

140

120

DISPLAY
READING
(%LFL)

100

80
LOWER FLAMMABLE LIMIT
(100% LFL)
60

UPPER FLAMMABLE LIMIT

40

20

0
0

10

15

20

30

40

50

60

70

80

90

PERCENT OF METHANE (BY VOLUME)

100
B1125

Figure V4Typical Response of Catalytic Sensor to All Possible Mixtures of Methane and Air

include covering the sensor with a plastic bag


when painting or cleaning. The bag should be
removed as soon as possible when the
procedure is complete.

SENSITIVITY LOSS IN CATALYTIC COMBUSTIBLE


GAS SENSORS
There are a variety of factors that can cause a decrease
in the sensitivity of catalytic type combustible gas
sensors. Interfering or contaminating substances that
can adversely affect the response of the sensor to
combustible gases are as follows:

4. Polymer formation in the flame arrester.


This can occur where monomer vapors such as
1-3 butadiene, styrene, isoprene, etc. are
present.

A. Materials that can clog the pores of the sintered


metal flame arrestor and reduce the gas diffusion
rate to the sensor are:

B. Substances that cover or tie up the active sites on


the catalytic surface of the active sensing element.

1. Dirt and oil.


This occurs in the presence of volatile metal
organics, gases, or vapors of hydrides, and volatile
compounds containing phosphorous, boron,
silicone, etc.

A dust cover should be installed to protect the


flame arrester whenever these conditions exist.
The dust cover can be cleaned as part of routine
maintenance. This can be accomplished using
an organic solvent and an ultrasonic bath.

Examples:
RTV silicone sealants
Silicone oils and greases
Tetraethyl lead
Phosphine
Diborane
Silane
Trimethyl chlorsilane
Hydrogen fluoride
Boron trifluoride
Phosphate esters

2. Corrosive products.
This occurs when substances such as Cl 2
(Chlorine) or HCl are present. A dust cover
provides some protection. The dust cover
should be replaced as part of routine
maintenance.
3. Flame arrester clogged as a result of painting
or house cleaning.
The routine maintenance procedure should
V-6

C. Materials that remove the catalytic metals from the


active element of the sensor.

CALIBRATION GAS
Before calibrating a sensor, check the label on the
calibration gas cylinder to ensure that the correct gas
type and concentration are being used. If a different
gas type is being used for calibration, refer to DetTronics Technical Note No. GTN01 for K-Factor
information (Det-Tronics form number 99-1068-02).

Some substances react with the catalytic metal


forming a volatile compound. This erodes the metal
from the surface. With sufficient exposure, most or
all of the metal catalyst can be removed from the
surface of the active element of the sensor.
Halogens and compounds containing halogen are
materials of this nature.
Examples:
Chlorine
Bromine
Iodine
Hydrogen Chloride, Bromide or Iodide
Organic halides:
Trichloroethylene
Dichlorobenzene
Vinyl chloride
Freons
Halon 1301
(Bromotrifluoromethane).
A brief exposure to one of these materials can
temporarily increase the sensitivity of the sensor.
This results because the surface of the active
element is increased due to etching. Prolonged
exposure continues the etching process until the
sensitivity of the sensor is degraded, resulting in
shortened sensor life.
D. Exposure to high concentrations of combustible
gases.
Exposure of the sensor to high concentrations of
combustible gases for extended periods of time
can introduce stress to the sensing element and
seriously affect its performance. After exposure to
a high concentration of combustible gas,
recalibration should be performed and, if
necessary, the sensor should be replaced.
The degree of damage to the sensor is determined
by a combination of the type of contaminant, its
concentration in the atmosphere, and the length of
time the sensor is exposed. When a sensor has
been exposed to a contaminant or a high level of
combustible gas, it should be calibrated at the time,
followed by an additional calibration a few days
later to determine whether a significant shift in
sensitivity has occurred.
E. A combination of accessories such as rain shields
and dust covers is not recommended and can
result in slow response to a gas leak.

V-7

95-8470

Section VI
General Wiring Requirements

flameproof enclosure d, suitable for the


conditions of use and correctly installed. Unused
apertures shall be closed with suitable certified
blanking elements.

GENERAL INFORMATION

POWER WIRING

WARNING
Do not open any junction box or device enclosure
when power is applied without first de-classifying
the hazardous area.

The input voltage at the field devices must be 18 vdc


minimum to ensure proper operation of the devices.
Therefore, it is important to consider both the size
(gauge) of the power wiring and the wiring distance
from the power supply. As the wiring distance
increases, larger diameter wire is required to maintain a
minimum of 18 vdc at the device.

CAUTION
Any deviation from the recommended wiring
practices can compromise system operation.
Consult the factory if different wire types or
methods are being considered.

Refer to Table VI-1 to determine the minimum wire size


needed to prevent excessive voltage drop from power
supply to device for a given current load.

NOTE
All wiring must be marked per NFPA 70 Article
760.

To use Table VI-1, first determine the total current load


for the circuit and the maximum allowable voltage drop.
Then look under the appropriate Amp Load column to
determine the minimum wire size that will not allow the
voltage drop to exceed the maximum allowable.

NOTE
Specific installation requirements may differ
depending on local installation practices and
compliance with third party certifications. For local
installation practices, consult the local authority
having jurisdiction. For compliance with third party
certifications, consult the appropriate appendix in
this manual for additional specific installation
requirements.

For example:
What wire size is required to power ten DCUs at a
distance of 100 feet from the power supply, assuming a
24 VDC power supply and a minimum of 18 VDC
needed to power the DCUs?

NOTE
All cable entry devices and blanking elements shall
be certified in type of explosion protection

Table VI-1Voltage Drop Per Pair in Volts DC per 100 Feet from Power Supply to Device

AWG

1 AMP LOAD

2 AMP LOAD

3 AMP LOAD

4 AMP LOAD

5 AMP LOAD

22

3.3

6.6

9.9

13.2

16.5

20

2.1

4.1

6.2

8.3

10.4

18

1.5

3.1

4.6

6.2

7.7

16

1.0

2.0

2.9

3.9

4.9

14

0.6

1.2

1.9

2.5

3.1

12

0.4

0.8

1.2

1.5

1.9

10

0.2

0.5

0.7

1.0

1.2

0.2

0.3

0.5

0.6

0.8

0.1

0.2

0.3

0.4

0.5

0.1

0.1

0.2

0.2

0.3

0.0

0.1

0.1

0.1

0.2

1/0

0.0

0.0

0.1

0.1

0.1

NOTES: This table is for reference only and does not replace good engineering practice.
Use Ohms Law when designing the power distribution system.
Voltage drop and wiring distance are proportional.
Consult factory for assistance with system wiring requirements.
VI-1

95-8470

Maximum allowable voltage drop is 6 VDC.


(24 18 = 6)

Table VI3Communication Loop Wiring Cable

Cable Type

A combustible gas DCU draws approximately 500 mA


at startup, therefore, the total current load is 5 amps.
(10 units x 500 mA = 5 amps)

Maximum Length

Belden 8719
Belden 85231
Level IV, 22 AWG
JY (St) 2x2x0.8

Refer to the 5 Amp Load column in the table. Since the


maximum allowable voltage drop is 6 volts, 16 AWG (or
larger) wire is required.

Feet

Meters

6500
6500
4500
3000

2000
2000
1370
900

Be sure that selected cable meets all job specifications.


If necessary, consult factory for further suggested cable types.

IMPORTANT
To ensure proper operation of field devices, the
voltage input to the device (measured at the
device) must be within the range indicated for that
device in the Specifications section of this
manual.

used, the distances listed are for the entire loop. If


network extenders are used, the distances listed are for
the wiring length between network extenders or
between a network extender and the LCU. The use of
other cable types can degrade system operation. For
optimum fault isolation performance, the maximum
LON/SLC wiring length should not exceed 1600 feet
(500 meters).

NETWORK WIRING
All devices on the LON/SLC are wired in a loop that
starts and ends at the LCU. To ensure proper
operation, the LON/SLC should be wired using high
speed communication grade cable. Cable meeting the
specifications listed in Table VI-2 is suitable for
distances up to 2000 meters. Any of the cable types
listed in Table VI-3 can be used for wiring the LON/SLC
for the distances indicated. If no network extenders are

SHIELD GROUNDING
Two shield ground terminals are provided inside the
junction box of each field device and also at the LCU.
Connect the shield ends to the terminals provided (not
to each other) inside the junction box.

Table VI-2Specifications for LON Wiring Cable

DC Resistance, each conductor

Minimum

Typical

Maximum

Units

14

14.7

15.5

ohm/km

Condition
20 C per ASTM D 4566

DC Resistance Unbalanced

5%

Mutual Capacitance

55.9

nF/km

108

ohm

20 kHz

1.3

dB/km

20 C per ASTM D 4566

64 kHz

1.9

78 kHz

2.2

156 kHz

256 kHz

4.8

512 kHz

8.1

772 kHz

11.3

1000 kHz

13.7
nsec/m

78 kHz

Characteristic Impedance
Attenuation

Propagation Delay

92

100

5.6

20 C per ASTM D 4566


per ASTM D 4566
64 kHz to 1 MHz, per ASTM D 4566

Length:
6,500 feet/2000 meters maximum (basic loop or between Network Extenders).
Type:
Single twisted pair.
Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.
Cables meeting these specifications are good for up to 2000 meters.

VI-2

T0049B

DETERMINING POWER
REQUIREMENTS

CAUTION
Insulate the shields to prevent shorting to the
device housing or to any other conductor.

Tables VI-4 and VI-5 are provided for calculating the


total current requirements for those parts of the system
requiring battery backup.

JUNCTION BOX GROUNDING


Junction boxes should be electrically connected to
earth ground.

EQ2110PS, EQ2130PS AND EQ2175PS


Refer to Table VI-6 for Power Supply ratings.

RS-485 LINK WIRING


BACKUP BATTERY
The RS-485 link connecting the LCU and LIOU requires
termination at both ends. The LCU provides termination
for the beginning of the RS-485 link. All other devices,
except for the device at the end of the line, shall have
their termination resistor removed. The LIOU uses a
termination resistor that must be removed if it is not at
the end of the line.

Refer to Table VI-7 or VI-8 to calculate the minimum size


of the backup battery (in amp hours). Select a sealed
lead-acid battery with an adequate amp hour rating.

NOTE
Connect two batteries in series for 24 volts. Be
sure that the battery enclosure is adequately
ventilated.

All devices sharing a common RS-485 link must have a


common power return.
PROTECTION AGAINST MOISTURE DAMAGE

BATTERY CHARGER

Moisture can have a detrimental effect on the


performance of electronic devices. Therefore, it is
important to take proper precautions during installation
to ensure that moisture will not come in contact with the
electrical connections or components of the system.

Use the following formula to calculate the minimum


battery charger size:
Minimum = Alarm Current + Total Amp Hours
Charge Rate
48

In applications where the wiring cable is installed in


conduit, the use of watertight conduit seals, drains,
breathers, or equivalent is recommended to prevent
damage to electrical connections caused by
condensation within the conduit.

CAUTION
Care should be taken when considering the final
voltage at the device during AC power loss. With
loss of AC power, the device voltage will drop over
time as the batteries lose their charge. If extended
periods of AC power loss are to be expected,
either consider a heavier wire gauge than indicated
in Table VI-1, or specify batteries with higher amphour ratings.

ELECTROSTATIC DISCHARGE
Many system electronic modules contain semiconductor
devices that are susceptible to damage by electrostatic
discharge. An electrostatic charge can build up on the
skin and discharge when an object is touched.
Therefore, use caution when handling, taking care not to
touch the terminals or electronic components. For more
information on proper handling, refer to Service Memo
form 75-1005.

VI-3

95-8470

Table VI4Standby Current Requirements at 24 vdc

Device Type

Number of Devices

LCU

Standby Current

Total Current for Device Type

0.300

Release Module

0.070

Signal Audible

0.033

Relay Module

0.020

P. S. Monitor

0.060

IDC/IDCGF/IDCSC

0.055

EQ22xxUV Detector

0.100

EQ22xxUVIR Detector

0.100

X2200xxx24

0.135

X5200xxx24 with heater

0.490

X5200xxx24 w/o heater

0.155

DCUEX

0.145

DCU with H2S

0.060

DCU with PointWatch

0.300

ARM

0.075

SAM

0.060

Network Extender

0.090

Power Supply

0.300

Other

0.300

TOTAL STANDBY CURRENT FOR SYSTEM (IN AMPERES)

=
T0012B

VI-4

Table VI5Alarm Current Requirements at 24 vdc

Device Type

Number of Devices

LCU

Alarm Current

Total Current for Device Type

0.340

Release Module

0.165

Signal Audible

0.120

Relay Module

0.090

P. S. Monitor

0.060

IDC/IDCGF/IDCSC

0.090

EQ22xxUV Detector

0.120

EQ22xxUVIR Detector

0.120

X2200xxx24

0.135

X5200xxx24 with heater

0.490

X5200xxx24 w/o heater

0.155

DCUEX

0.160

DCU with H2S

0.075

DCU with PointWatch

0.320

ARM

0.120

SAM

0.120

Network Extender

0.090

Power Supply

0.300

Other

0.340

Total Solenoid Load

Total Signaling Load

TOTAL ALARM CURRENT FOR SYSTEM (IN AMPERES)

=
T0013B

Table VI-6EQ21xxPS Power Supply Specifications

Power Supply

Characteristic
EQ2110PS

EQ2130PS

EQ2175PS

Input Voltage

120 vac

120/208/240 vac

120/208/240 vac

Input Current

4 Amps

11/6/6 Amps

24/15/12 Amps

60 Hz

60 or 50 Hz

60 or 50 Hz

Supply Rating

10 Amps

30 Amps

75 Amps

Maximum Alarm Current

10 Amps

30 Amps

75 Amps

Maximum Standby Current

3.33 Amps

10 Amps

25 Amps

Recharge Current

6.67 Amps

20 Amps

50 Amps

100 AmpHours

300 AmpHours

750 AmpHours

1 Amp

3 Amps

7.5 Amps

Input Frequency

Maximum Battery Capacity


Maximum Deluge Standby Current

VI-5

95-8470

Table VI7Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge

Standby Current

Standby Time*
X

Standby Amp Hours


=

24 Hours
Alarm Current

5 Minute Alarm Time*


X

Alarm Amp Hours


=

0.083 Hours
Sum of Standby and Alarm Amp Hours

Multiply by 1.1 (10% Safety Factor)

X
T0014A

Total Battery Amp Hour Requirement


* FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS
IS 24 HOURS STANDBY TIME AND 5 MINUTES ALARM TIME.

Table VI-8Backup Battery Requirements for Deluge and Pre-Action Applications

Standby Current

Standby Time*
X

Standby Amp Hours


=

90 Hours
Alarm Current

10 Minute Alarm Time*


X

Alarm Amp Hours


=

0.166 Hours
Sum of Standby and Alarm Amp Hours

Multiply by 1.1 (10% Safety Factor)

X
T0040A

Total Battery Amp Hour Requirement


* FM MINIMUM REQUIREMENT FOR DELUGE SYSTEMS IS
90 HOURS STANDBY TIME AND 10 MINUTES ALARM TIME.

VI-6

Section VII
System Wiring

EQ2100PSM POWER SUPPLY


MONITOR USED WITH EQ2110PS,
EQ2130PS AND EQ2175PS POWER
SUPPLIES

NOTE
Specific installation requirements may differ
depending on local installation practices and
compliance with third party certifications. For local
installation practices, consult the local authority
having jurisdiction. For compliance with third party
certifications, consult the appropriate appendix in
this manual for additional specific installation
requirements.

WIRING
1. Mount the power supply monitor in a Nationally
Recognized Test Laboratory (NRTL) labeled
enclosure. Refer to the Specifications section for
mounting dimensions.
NOTE
Power supplies require unrestricted air flow for
proper cooling.
2. Securely mount the cabinet. The cabinet should be
electrically connected to earth ground.
3. Connect the external wiring to the appropriate
points as described below. Refer to Figure VII-1 for
terminal block locations and Figures VII-2 and VII-3
for terminal identification.

J1: POWER AND LON WIRING

LON ADDRESS SWITCHES

J3: AC INPUT

TERMINAL NO. 1

SWITCH NO. 1
+
+

+
+

1
+

YELLOW LED

RED LED

TERMINAL NO. 1

GREEN LED

A1949

TERMINAL NO. 1
J2: CURRENT TEST POINTS
TERMINAL "C"
TERMINAL "B"

Figure VII-1Location of Terminals, LEDs and Switches on the Power Supply Monitor

VII-1

95-8470

Connect the shield to the designated


"shield" terminal. (The two shield terminals
are connected internally.) Do not ground
any shield at the monitor / power
distribution cabinet. Insulate the shields
to prevent shorting to the device housing
or any other conductor.

WARNING
Do not connect or disconnect wires with power
applied.
4. Connect the 24 vdc power wires and the LON
network cable to the appropriate points on J1, the
Power & LON Wiring terminal block. See Figure VII2.
COM 1 -

Communication network connections:


Connect to COM 2 terminals of the next
device on the loop, A to A and B to B.

COM 2 -

Communication network connections:


Connect to COM 1 terminals of the
previous device on the loop, A to A and B
to B.

24 VDC -

Connect the "+" terminal to the positive


side of the 24 vdc power source. (Both "+"
terminals are connected internally.)
Connect the "-" terminal to the negative
side of the 24 vdc power source. (Both "-"
terminals are connected internally.)

5. Connect a two wire cable between the AC input of


the power supply and terminals 1 and 4 on J3, the
AC input terminal block on the power supply
monitor. See Figure VII-3.
6. Connect the B terminal on the power supply
monitor to the negative () side of the backup
battery. Connect a correctly sized circuit breaker or
disconnect switch in the battery circuit as shown in
Figure VII-4. If a circuit breaker is used, it must be
rated between 150% and 250% of the total load.
7. Connect the C terminal on the power supply
monitor to the negative () side of the power supply.
8. Wire the power distribution circuit breakers to the
output of the power supply. Circuit breaker ratings
must be between 150% and 250% of the full load
rating.
9. Check all field wiring to ensure that the proper
connections have been made.

SHIELD

SHIELD

SHIELD

COM 1

10. Set the LON address for the power supply monitor.
Refer to Figure VII-1 for rocker switch location.
Refer to LON/SLC Device Address Switch Setting
in the Switch Setting section (Section VIII) of the
Eagle Quantum system manual (form number 958470) for complete information regarding the switch
setting procedure.
11. Connect the mounting frame to chassis (earth)
ground.

24 VDC

10

11

12

AC INPUT 120 / 240 VAC

NOT USED

NOT USED

AC INPUT 120 / 240 VAC

COM 2

SHIELD

A1947

A1950

Figure VII-2J1: Power and LON Wiring Terminal

Figure VII-3J3: AC Input Terminal

VII-2

POWER SUPPLY MONITOR

1
AC MONITOR
4

C
B

12
11
10
9
8
7
6
5
4
3
2
1

24 VDC
OUTPUT

N
G

+ POWER DIST CKT #1


+ POWER DIST CKT #2
+ POWER DIST CKT #3

AC BREAKER

+ POWER DIST CKT #4

DC BREAKER

BATTERY
CIRCUIT
BREAKER

POWER SUPPLY
NRTL CABINET

12 VDC

12 VDC

BACKUP BATTERIES

C1951

NOTES
1. AC INPUT SELECTABLE (THROUGH THE OIS)
FOR 120 / 208 / 240 VAC.
2. BATTERY SIZE CALCULATED BASED ON
SYSTEM LOAD.
3. CIRCUIT BREAKER RATINGS MUST BE BETWEEN
150% AND 250% OF FULL LOAD RATING.
4. REMOVAL OF TERMINAL PLUG WITH POWER
APPLIED TO TERMINALS B AND C WILL DAMAGE
THE POWER SUPPLY MONITOR.

Figure VII-4A Typical Application Wiring Connections for a Power Supply Monitor, Power Supply and Backup Batteries

STARTUP
Turn on the power supply and allow the voltage to
stabilize at 27 volts before closing the circuit to the
battery.

To measure the battery charging current, connect a


digital voltmeter to terminals 1 and 2 of terminal block
J2. See Figure VII-5. The voltmeter will read 1 millivolt
(0.001 volt) for each 2 amperes of current.
Current in Amperes = Meter reading in millivolts x 2

MEASURING BATTERY VOLTAGE AND


CHARGING CURRENT

Example: A reading of 50 millivolts indicates a charging


current of 100 amperes.

Measure the battery voltage at terminals 3 and 4 of


terminal block J2.

CURRENT SENSE

CURRENT SENSE

BATTERY

BATTERY +

A1952

Figure VII-5J2: Current Test Points


VII-3

95-8470

EQ2100LCU SERIES
LOCAL CONTROL UNIT

NOTE
EOL terminals are provided to allow convenient
installation of EOL resistors. Installing an EOL
resistor at terminals 1D and 1E or 2D and 2E
places it across the normally open and common
contacts of the alarm and supervisory relays. Note
that the Trouble relay is energized during normal
operation, therefore the EOL resistor goes across
the normally closed contacts at 3D and 3E. To
insert the resistor lead into the terminal, depress
the orange lever.

All external wiring to the LCU is connected to the


terminal blocks that are an integral part of the LCU
backplane, extending below the card rack. To access
the terminals, the cover must be removed.
The terminals are arranged in three rows and numbered
from left to right. Row A is closest to the bottom of the
board, row B in the center, and row C on top.
See Figure VII-6 for wiring terminal identification.
Terminals 1 to 3

Terminals 4 to 6

DC Power.
(EQ2101LCU only)

Logic controller relay


contacts:

Two separate 24 vdc power


supplies with common ground
are required. Connect terminals
A4 and B4 to one supply and
A5 and B5 to the other. A
trouble condition is indicated if
either supply is missing.

Terminals A1 (NO), =
B1 (COM), =
C1 (NC), = Alarm relay
1D and 1E = EOL
Terminals A2 (NO), =
B2 (COM), =
C2 (NC), = Supervisory relay
2D and 2E = EOL

Connect terminals A6 and B6


(AUX OUT) to the auxiliary
terminals on the LIOU. This is
typically used for powering
solenoids, horns, strobes, etc.

Terminals A3 (NO), =
B3 (COM), =
C3 (NC), = Trouble relay
3D and 3E = EOL.

P7

GATEWAY RELAYS

LON/SLC
P1

R+
RXD
COM
TXD
T+
RXD
COM
TXD

{
25

RESET GATEWAY RELAYS


UNSUPERVISED INPUTS TO LOGIC CONTROLLER
RS-485 TO LIOU
CHASSIS (EARTH) GND
24 VDC TO STANDARD LCU RACK
USED WITH EQ2101 RACK ONLY, SEE TEXT
LOGIC CONTROLLER RELAY CONTACTS

Figure VII6Wiring Terminals on the LCU

VII-4

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

GATEWAY RELAY CONTACTS

COM1

NO

NO

TO OIS

D1859

COM2

24

23

22

21

20

19

18

17

16

15

15

SHIELD

17

P2

16

18

K4

FAULT

K3

K2

K1
14

13

14

RESET

12

NC

INPUT 1

11

COM

INPUT 2

10

COM

INPUT 3

A
RS-485
B
CHASSIS
EARTH

GND FLT

MAIN 24V

AUX 24V

DC1

NC

ROW A

DC2

3E
3D
2E
2D
1E
1D

EOL

ROW C

ROW B

TROUBLE

SUPER

ALARM

ROW D

Row A terminals = ()
Row B terminals = (+)

TO
COMMUNICATION
NETWORK

Terminal 7

contacts etc.
Wire the
contacts between the A and
B terminals. These inputs
can be used in the
programmable logic.

System power.
When used with the standard
LCU rack (EQ2100LCU),
terminals A7 and B7 are power
input terminals for supplying
the 24 vdc power from the
power supply to the LCU.

Terminal 13

Connect a normally open,


momentary closure switch
between terminals A13 and
B13 to reset the gateway
relays from a remote location
when
the
relays
are
programmed for latching
operation.

When used with the optional


LCU rack (EQ2101LCU),
terminals A7 and B7 are power
output terminals for supplying
isolated power with ground
fault monitoring from the LCU
to the main power terminals on
the LIOU and field devices.
Output current must not
exceed 2.8 amperes.

Terminals 14 to 18

A7 terminal = ()
B7 terminal = (+)
Terminal 8

Ground fault monitor.

Terminals A15 (NO), =


B15 (COM), =
C15 (NC), = Relay K2
Terminals A16 (NO), =
B16 (COM), =
C16 (NC), = Relay K3
Terminals A17 (NO), =
B17 (COM), =
C17 (NC), = Relay K4

IMPORTANT
The chassis ground stud must be connected to
earth ground.

Terminals A18 (NO), =


B18 (COM), =
C18 (NC), = Fault relay

RS-485 link.
Connect to the power supply
or LIOU rack RS485 terminals.
Be sure to observe polarity:

Terminals 10 to 12

Gateway relay contacts.

Terminals A14 (NO), =


B14 (COM), =
C14 (NC), = Relay K1

Terminal B8 (ground fault


monitor) must be connected to
A8 (chassis ground) to ensure
proper functioning of the
ground fault monitoring
circuitry.

Terminal 9

Remote reset.

Terminals 19 to 22

RS-232 serial
communication ports.
These two serial ports are
electrically isolated from each
other and from the system.

Connect A9 terminal to the RS485 A terminal of the next


device on the link. Connect
B9 terminal to the RS-485 B
terminal of the next device on
the link.

A19 = Port 2 common (COM).


Connects to common of the
other device.

All devices sharing a common


RS-485 link must have a
common system power return.

B19 = Port 2 transmit (TXD).


Connects to receive of the
other device.

Three unsupervised inputs


to the Logic Controller.

B20 = Port 2 receive (RXD).


Connects to transmit of the
other device.

These inputs are typically used


for contact inputs such as
switches, pushbuttons, relay

VII-5

95-8470

NOTE
B23 is connected directly to chassis ground. A23
is connected to chassis ground through a filter
network.

NOTE
Connection to Port 2 can also be made using the
9-pin (DB9) connector P7.
Pin 2 =
TXD =
B19
Pin 3 =
RXD =
B20
Pin 5 =
COM = A19

IMPORTANT
When installing the three modules in the LCU rack,
the Logic Controller must be in the left hand
position, the Gateway in the center position, and
the LON Isolator in the right hand position.

WARNING
Do not plug or unplug the connector unless the
area is known to be non-hazardous.
A20 = (T+) Not used.
A21 = Port 1 common (COM).
Connects to common of the
other device.
B21 = Port 1 transmit (TXD).
Connects to receive of the
other device.
B22 = Port 1 receive (RXD).
Connects to transmit of the
other device.
A22 = (R+) Not used.
Terminals 23 to 25 LON/SLC signaling circuit
terminals, with separate
shield connections.
The LON/SLC is polarity
sensitive due to ground fault
monitoring.
A23 = shield connection for COM 1
A24 = B side of signaling circuit for
COM 1
A25 = A side of signaling circuit for
COM 1
B23 = shield connection for COM 2
B24 = B side of signaling circuit for
COM 2
B25 = A side of signaling circuit for
COM 2

VII-6

EQ2100LIOU LOCAL OUTPUT UNIT


CAUTION
All personnel installing or servicing the LIOU must
wear a grounding strap to avoid generating static
electricity that can destroy or damage integrated
circuits. The circuit boards are shipped in antistatic plastic bags and should be kept in these
bags until the time of installation. If the circuit
boards are removed from the rack, they should be
replaced in the appropriate bags. Never pack the
boards in styrofoam or plastic pellets.

POWER WIRING
Connect to the () terminal of
the system power terminals on
the EQ2101LCU (terminal A7).

Main Power ()

CAUTION
Do not connect a breaker or other disconnect
device to power minus () with RS-485
connected. Doing so will damage the RS-485
circuitry.
Connect to the (+) terminal of
the system power terminals on
the EQ2101LCU (terminal B7).

Main Power (+):


CAUTION
LIOU modules must not be installed or removed in
a powered-up system. Always disconnect both AC
and battery power before installing the modules.
BACKPLANE WIRING

Auxiliary Power Input (): Connect to the () auxiliary


terminal of the EQ2101LCU
(terminal A6).

Power and communication wiring to the LIOU is


connected to the terminal block on the LIOU backplane.
See Figure VII-7.

Auxiliary Power Input (+): Connect to the (+) auxiliary


terminal of the EQ2101LCU
(terminal B6).

RS-485 LINK WIRING

Auxiliary Power Output:


J3, J4, J5

These terminals are provided


to distribute 24 vdc auxiliary
power to the auxiliary power
terminals on the release and
signal audible modules.
Maximum total current must
not exceed 8 amperes.

Chassis Ground:

Connect to earth ground.

The assembly is controlled and supervised by the Local


Control Unit (LCU) using an RS-485 serial
communication link. Up to four LIOUs can be
controlled by the LCU adding a maximum of 24 output
modules to the system.
The RS-485 link connecting the LCU and LIOU requires
termination at both ends. The LCU provides termination
for the beginning of the RS-485 link. If the LIOU is not
the last unit in the line, termination resistor R1 must be
removed. See Figure VII-7 for location.
Two sets of RS-485 terminals are provided to allow
daisy-chained wiring. A terminals are connected to
A terminals and B terminals to B terminals of the
next device on the link.
RS-485 A

Module Wiring
Wiring to the external devices that are controlled by the
LIOU modules is connected to the terminal strip on the
corresponding module.

Connect one terminal to A of


the previous device on the link
and the other terminal to A of
the next device on the link.

RS-485 TERMINATION RESISTOR


P1

RS-485 B

Connect one terminal to B of


the previous device on the link
and the other terminal to B of
the next device on the link.

P2

P3

P4

P5

AUX POWER

P6

J3 J4 J5

+
+

B
A

RS-485 MAIN AUX

All devices sharing a common RS-485 link must have a


common power return.
B1860

Figure VII-7Wiring Terminals on LIOU Backplane

VII-7

95-8470

RELAY MODULE
WIRING
Refer to Figure VII-8 for identification of relay wiring
terminals.
SWITCH SETTING
Each relay module must be assigned a unique address
(1 to 8) using switch assemblies S1 and S2 on the relay
module circuit board. See Figure VII-9 for the location
of switches on the circuit board. Refer to Table VII-1 to
determine the correct switch positions for the desired
address. Note that switch S1-1 is not used.

S3
RESET SWITCH
ON
S2
S1

1 2 1 2

DS1

TROUBLE LED

MODULE ADDRESS SWITCHES

1
2

K1
TB1
RELAY MODULE

3
4
5

K2
12

6
7

A1862

K3

9
10
11

Figure VII9Location of Switches on Relay Module

K4

12
NOTES:
1. ALL RELAY OUTPUTS ARE SHOWN IN NORMAL STANDBY CONDITION.
2. ALL CONTACTS ARE THE DRY CONTACT TYPE.
3. OUTPUTS OF ALL RELAYS ARE NOT SUPERVISED.
4. RATINGS ARE 2A MAXIMUM AT 24 VDC; 1A AT 120 VAC.
5. THE MAXIMUM NUMBER OF BOARDS PER SYSTEM IS EIGHT.
6. THE MAXIMUM WIRE SIZE IS 12 AWG, ONE WIRE PER TERMINAL.

Table VII1Switch Positions for Relay Module Addresses


B1861

Module
Address

Figure VII8Wiring Terminals for Relay Module

Switch Position
S12
S21
S22

ON

ON

ON

ON

ON

OFF

ON

OFF

ON

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

OFF

ON

OFF

OFF

OFF
T0016A

VII-8

RELEASE MODULE

SWITCH SETTING

WIRING

Each release module in the LIOU must be assigned a


unique address (1 to 8). This is accomplished using
switches S3-2, S4-1 and S4-2 on the release module
circuit board. Refer to Table VII-4 to determine the
correct switch positions for the desired address.

Refer to Figure VII-10 for identification of wiring


terminals.
To ensure adequate operating voltage for the output
device, the maximum wiring length from the power
source to the output device must not exceed the values
shown in Table VII-2 for automatic release applications
or Table VII-3 for deluge and pre-action applications.
(For solenoids, this wire length includes both the wiring
from the power supply to the agent release module and
the wiring from the module to the solenoid. For squibs,
use only the wire length from the power supply to the
module, since the resistance of the wire from the
module to the squib is included when determining the
value of the compensating resistor.)

Switches S1 and S3-1 must be set for solenoid or


explosive initiator (squib). Refer to Table VII-5 for switch
positions.

JUMPERS
When the auxiliary power input is used, jumpers W1 and
W2 must be cut. See Figure VII-11 for the locations of
jumpers and switches on the circuit board.

RELEASE SOLENOIDS
TB1
1
2
3
4
5
6
7
8
9
10
11
12

AUXILIARY POWER

3
4

+
RELEASE CIRCUITS

TB1
3

SIGNAL CIRCUITS

10

11
12

SOLENOID TWO

INITIATOR RELEASE
3

CKT #1

10K EOL
4
5

CKT #2

10K EOL
6

SEE NOTE 3.

TB1

SOLENOID ONE

SIGNAL CIRCUITS

SEE NOTE 3.

TB1
7
8

ONE SOLENOID

CKT #3

SEE NOTE 1.

SEE NOTE 2.

NOTES:
1. USED TO COMPENSATE FOR 10 OHMS MAXIMUM
CIRCUIT RESISTANCE.
1. RESISTOR MUST BE RATED AT 1 WATT MINIMUM.
2. MAXIMUM NUMBER OF INITIATORS PER CIRCUIT IS 12.
2. EACH CIRCUIT MUST NOT EXCEED 10 OHMS
INCLUDING CABLE RESISTANCE.
3. USE A 1200 OHM RESISTOR AS A LOAD FOR TEST PURPOSES.
4. POLARITY SHOWN IS FOR ACTIVATED CONDITION.
POLARITY IS REVERSED DURING MONITORING CONDITION.

10K EOL

B1863

Figure VII-10Wiring Terminals for Release Module

VII-9

95-8470

S4

S2

RESET SWITCH

S3

TROUBLE LED

1 2 1 2

ON

MODULE ADDRESS ASSIGNMENT

DS1

Table VII-2Maximum Wiring Length for Release Applications


J1

Device

Maximum Wire Length in Feet


12 AWG 14 AWG 16 AWG 18 AWG

S1
SQB

890181*

150

100

60

899175*

150

100

60

895630-000*

150

100

60

W1

SOL

1
W2

TB1

897494*

190

120

75

486500-001*

1500

1000

600

31-199932-004*
12

150

100

60

Squib

190

120

75

2 Amp Load

190

120

75

400

RELEASE MODULE

T0028B

*Fenwal Solenoid

A1864

Figure VII11Location of Switches and Jumpers on Release Module

Table VII-3Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids
Manufacturer

Maximum Wire Length in Feet (Meters)


Model

12 AWG

14 AWG

16 AWG

18 AWG

LV2LBX25

800 (244)

500 (152)

310 (94)

200 (61)

ASCO

8210A107

520 (158)

325 (99)

200 (61)

130 (40)

ASCO

8210G207

825 (251)

520 (158)

325 (99)

205 (62)

Skinner

73218BN4UNLVNOC111C2

860 (262)

540 (165)

340 (104)

215 (66)

Skinner

73212BN4TNLVNOC322C2

400 (122)

250 (76)

160 (49)

100 (30)

Skinner

71395SN2ENJ1NOH111C2

860 (262)

540 (165)

340 (104)

215 (66)

Skinner

T0041B

Table VII-4Switch Positions for Release Module Addresses

Module
Address

Table VII-5Switch Positions for Solenoid/Explosive Initiator

Switch Position
S32
S41
S42

ON

ON

ON

Switch S1 Position Assignments


S1

Single
Solenoid

Dual
Solenoid

Explosive
Initiators

SOL

SQB

ON

ON

OFF

ON

OFF

ON

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

OFF

ON

OFF

Solenoids

OFF

OFF

OFF

ON

Explosive Initiator

Switch S31 Position Assignments

T0018A

T0017A

VII-10

SIGNAL AUDIBLE MODULE

TB1

+24VDC
AUXILIARY POWER

WIRING
The signal audible module can support NFPA style Y or
style Z field wiring. Refer to Figures VII-12 through VII15 and determine which of the wiring styles will be
used. EOL resistor value is 10K ohms.

RET

10K EOL

CIRCUIT 1
6

10K EOL

CIRCUIT 2

+
+

NOTE
Polarity shown is for activated condition. Polarity
is reversed for monitoring condition.

7
8
9

10

10K EOL

CIRCUIT 3

11
+

To ensure adequate operating voltage for the signaling


device, the maximum wiring length from the power
source to the output device must not exceed the values
shown in Table VII-6. (This wire length includes both the
wiring from the power supply to the signal audible module
and the wiring from the module to the signaling device.)

12
+

W1

W2

W3

JUMPERS
W4
W5

W6

W7

W8

OFF
ON

ON

ON

OFF

OFF

OFF

ON

OFF

SWITCHES
SW21 SW32
ON

OFF

C1866

Figure VII13Two Style Y and One Style Z Circuits


for Signal Audible Module

JUMPERS/SWITCHES

TB1

Note that each wiring diagram is accompanied by its


corresponding jumper/switch setting table. This table
shows the correct positions for jumper plugs W1
through W8 and switches SW2-1 and SW3-2. For
jumper plugs W1 through W8, ON = jumper installed,
OFF = jumper removed.

+24VDC
AUXILIARY POWER

RET

10K EOL

When the auxiliary power input is used, jumpers W9 and


W10 must be cut. See Figure VII-16 for the locations of
jumpers and switches on the circuit board.

5
6
CIRCUIT 1
7
8
9

10

10K EOL

CIRCUIT 3

11
+

ADDRESS SWITCH SETTING

+12

Each signal audible module must be assigned a unique


address (1 to 8). This is accomplished using switches
SW2-2, SW1-1 and SW1-2 on the signal audible module
circuit board. Refer to Table VII-7 to determine the
correct switch positions for the desired address.

W1

W2

W3

JUMPERS
W4
W5

W6

W7

W8

OFF

OFF

OFF

ON

OFF

OFF

ON

OFF

SWITCHES
SW21 SW32
OFF

OFF

C1867

Figure VII14Two Style Z Circuits for Signal Audible Module

TB1

+24VDC
AUXILIARY POWER

TB1

RET

+24VDC

2
AUXILIARY POWER

10K EOL

+
+

10K EOL

5
6

CIRCUIT 1
7
10K EOL

10K EOL

10

10K EOL

RET

CIRCUIT 3

5
CIRCUIT 1
6
CIRCUIT 2
7
8
9
CIRCUIT 3

CIRCUIT 4

11
+

10K EOL

10

10K EOL

CIRCUIT 4

11
+

+12

12
+
W1

W2

W3

JUMPERS
W4
W5

OFF

OFF

OFF

ON

ON

W6

W7

W8

ON

ON

OFF

SWITCHES
SW21 SW32
OFF

ON

C1865

Figure VII12One Style Z and Two Style Y Circuits


for Signal Audible Module

W1

W2

W3

JUMPERS
W4
W5

W6

W7

W8

OFF
ON

ON

ON

OFF

ON

ON

OFF

ON

SWITCHES
SW21 SW32
ON

ON

C1868

Figure VII15Four Style Y Circuits for Signal Audible Module


VII-11

95-8470

Table VII6Maximum Wiring Length


from Nominal 24 VDC Power Source to Signaling Device

Maximum Wire Length in Feet (Meters)


12 AWG
14 AWG
16 AWG
(4 mm2)* (2.5 mm2)* (1.5 mm2)*
One 2 Ampere Load

190 (58)

120 (37)

75 (23)

Two 2 Ampere Loads

95 (29)

60 (18)

35 (11)

* Approximate Metric Equivalent.

T0029A

SIGNAL AUDIBLE MODULE

W11

SW4

TROUBLE LED

DS1

ON
SW1
SW2
SW3

1 2 1 2 1 2

RESET SWITCH

MICROCONTROLLER
WITH EPROM

U1

MODULE ADDRESS ASSIGNMENT

J1

W3

W1

W4
W9

W10

W2

TB1

W5

W6
12
W7

W8

A1869

Figure VII16Location of Switches and Jumpers


on Signal Audible Module

Table VII7Switch Positions for Signal Audible Module


Addresses

Module
Address

Switch Position
SW22
SW11 SW12

ON

ON

ON

ON

ON

OFF

ON

OFF

ON

ON

OFF

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

OFF

ON

OFF

OFF

OFF
T0019A

VII-12

FIELD DEVICES
EQ2200IDC SERIES INITIATING DEVICE CIRCUIT
GND

11

WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

12
7

14

10

13
1

NOTE
All cable entry devices and blanking elements shall
be certified in type of explosion protection flameproof
enclosure d, suitable for the conditions of use and
correctly installed. Unused apertures shall be closed
with suitable certified blanking elements.
1. Remove the cover from the junction box.

A1870

2. Connect external system wiring to the appropriate


terminals on the terminal block inside the junction
box. See Figure VII-17 for terminal block location
and Figure VII-18 for terminal identification. The
input to the IDC consists of one or more normally
open switches (momentary pushbuttons are not
recommended), with a 10K ohm, 1/4 watt EOL
resistor in parallel across the last switch. An EOL
resistor must be installed on both IDC inputs
(including unused inputs). Wiring impedance must
not exceed 500 ohms.

Figure VII17IDC Terminal Wiring Board Mounted


in Six-Port Junction Box

IDC

MANUAL PULL STATION


OR OTHER CONTACT DEVICE

CIRCUIT 1

EOL (10K)

CIRCUIT 2

3. Check the wiring to ensure proper connections.


4. Set the node address for the device. Refer to
Device Address Switch Setting in the Switch
Setting section (Section VIII) of this manual for
complete information regarding the switch setting
procedure.

EOL (10K)

COM 2

14

13

12

10

11

COM SHIELD

5. Install the communication module inside the


junction box. Be sure that the keyed ribbon cable is
properly connected.

24 VDC

COM 1

6. Inspect the junction box O-ring to be sure that it is


in good condition and properly installed. Lubricate
the O-ring and the threads of the junction box cover
with a thin coat of an appropriate grease to ease
installation and ensure a watertight enclosure. The
recommended lubricant is a silicone free grease,
available from Det-Tronics. Place the cover on the
junction box. Tighten only until snug. Do not over
tighten.

VII-13

A1871

Figure VII18Terminal Configuration for Initiating Device Circuit

95-8470

EQ2200IDCGF SERIES INITIATING DEVICE


CIRCUIT GROUND FAULT
+

RELAY CONTACT
FOR MONITORING BATTERY.
CONTACT OPENS
WITH BATTERY TROUBLE CONDITION.
3
68K OHM
RESISTOR

INPUT

1. Securely mount the aluminum enclosure. The


enclosure should be electrically connected to earth
ground.

RELAY CONTACT
FOR MONITORING AC POWER.
CONTACT CLOSES
ON LOSS OF AC POWER.

COM 2

2. Connect the external wiring to the appropriate


points on the terminal block. See Figure VII-17 for
terminal block location and Figure VII-19A for
terminal identification.

14

13

12

10

11

COM SHIELD

24 VDC

3. Check all field wiring to ensure that the proper


connections have been made.

COM 1

4. Install the communication module inside the


junction box. Be sure that the keyed ribbon cable is
properly connected.

B1922

NOTE: ENCLOSURE AND/OR MOUNTING BRACKET


MUST BE CONNECTED TO EARTH GROUND.

5. Set the node address for the device. Refer to


LON/SLC Device Address Switch Setting in the
Switch Setting section (Section VIII).
6. Inspect the enclosure O-ring to be sure that it is in
good condition and properly installed. Lubricate
the O-ring and the threads of the enclosure cover to
ease both installation and future removal of the
cover. The recommended lubricant is a silicone
free grease available from Detector Electronics. If
the installation uses catalytic type combustible gas
sensors, it is imperative that lubricants containing
silicone not be used, since they will cause
irreversible damage to the sensor. Place the cover
on the enclosure. Tighten only until snug. Do not
over tighten.

Figure VII-19AEQ2200IDCGF Wiring Terminal

EQ2200IDCSC SERIES INITIATING DEVICE


CIRCUIT SHORT CIRCUIT
The EQ2200IDCSC Initiating Device Circuit Short Circuit
(IDCSC) provides two supervised digital inputs for use
with dry contact inputs from devices such as relays,
pushbuttons, key switches, etc. The IDCSC supports
ANSI/NFPA 72 Class B Style C (3 state, open/short
circuit) supervised input circuits. Each circuit uses its
own end of line (EOL) resistor for monitoring circuit
continuity and a series resistor for each contact.
1. Remove the cover from the junction box.

Device Configuration
When configuring the EQ2200IDCGF, its device type
should be configured as an initiating device circuit
(IDC).
Both inputs must be configured for a trouble condition.
Circuit 1

Open indicates a 24 VDC ground fault


condition. Active indicates a +24 VDC
ground fault condition.

Circuit 2

Active indicates a loss of AC input


power.
Open indicates a loss of battery power.

2. Remove the communication module from the


junction box. Connect external system wiring to the
appropriate terminals on the terminal block inside
the junction box. See Figure VII-17 for terminal
block location and Figure VII-19B for terminal
identification. The input to the IDCSC consists of
one or more normally open switches, with a 10K
ohm, 1/4 watt EOL resistor in parallel across the last
switch. An EOL resistor must be installed on both
IDCSC inputs (including unused inputs). Wiring
impedance must not exceed 500 ohms. A 3.3K
ohm resistor must be installed in series with each
switch.
3. Check the wiring to ensure proper connections.

VII-14

4. Set the node address for the device. Refer to


Device Address Switch Setting in the Switch
Setting section (Section VIII) of this manual for
complete information regarding the switch setting
procedure.

EQ2200UV UV FLAME DETECTOR


1. Remove the sensor housing from the bulkhead (turn
counterclockwise). Install the sensor module and
replace the sensor housing. See Figure VII-20.

5. Install the communication module inside the


junction box. Be sure that the keyed ribbon cable is
properly connected.
6. Inspect the junction box O-ring to be sure that it is
in good condition and properly installed. Lubricate
the O-ring and the threads of the junction box cover
with a thin coat of an appropriate grease to ease
installation and ensure a watertight enclosure. The
recommended lubricant is a silicone free grease,
available from Det-Tronics. Place the cover on the
junction box. Tighten only until snug. Do not over
tighten.

NOTE
If the detector is equipped with a cover locking
device, it must be loosened using a 5/32
hexagonal (Allen) wrench (see Figure VII-21).
2. Mount the swivel mounting bracket using 1/4 inch
(M6) screws with a length of at least 1 inch (25
mm). The mounting surface should be free of
vibration. Allow adequate space around the swivel
to facilitate aiming and wiring of the detector.
Armored flexible conduit should be used for the
final 3 feet (one meter) of the cable run to allow for
aiming and alignment of the detector.
3. Attach the detector to the swivel mounting bracket.
4. Remove the rear housing from the bulkhead.

MANUAL PULL STATION


OR OTHER CONTACT DEVICE
IDCSC

5. Connect the wires to the appropriate screw


terminals on the terminal block. See Figure VII-22.
Connect the cable shields to the terminals
provided.

EOL (10K)
CIRCUIT 1

3.3 K

3.3 K

CIRCUIT 2

EOL (10K)
3.3 K

6. Set the rocker switches on the DIP switch assembly


on the electronic module for the desired address.
Refer to Device Address Switch Setting in the
Switch Setting section of this manual for complete
information regarding the switch setting procedure.
7. Install the electronic module, ensuring that the
connector is aligned correctly. Tighten the three
captive screws that hold the electronic module in
place. See Figures VII-20 and VII-23.

COM 2

14

13

12

10

11

8.

COM SHIELDS

24 VDC

Replace the rear housing and hand tighten to ensure


proper sealing. See Figures VII-20 and VII-21.

9. Aim the detector at the potential hazard and tighten


the nut.

COM 1

A2076

Figure VII-19BTerminal Identification for EQ2200IDCSC

10. Check the viewing window surface (Figure VII-24)


and ensure that:
A) the oi source (UV test lamp opening) is located
on top
B) the split in the oi reflective ring is not aligned
with the UV test lamp opening on the detector
module
C) the split in the oi ring is directed downward to
prevent a buildup of contaminants between the
oi ring and the viewing window.

VII-15

95-8470

CONDUIT ENTRY
BULKHEAD
SENSOR MODULE

SENSOR HOUSING

REAR HOUSING

ELECTRONIC MODULE
O-RING
CONDUIT ENTRY
O-RING

oi RING

A1840

DETECTOR WINDOW

Figure VII20EQ2200UV Detector Assembly

REAR HOUSING

BLIND HOLE

SCREW

COVER LOCKING CLAMP

CATCH

CATCH SCREW

COVER
LOCKING
ASSEMBLY

STRAP

BARREL

A1841

Figure VII21Optional Cover Locking Devices on UV Detector

VII-16

LENS CAP

11. Clean the viewing window and oi ring using the


procedure described in the Maintenance section.
+

COM 1

24 VDC

12. Install any optional accessories (such as air


shields).

COM 2
1

EQ2200UVHT HIGH TEMPERATURE UV FLAME


DETECTOR

9 10

TERMINALS 1 AND 2 24 VDC POWER SUPPLY (+)


TERMINALS 3 AND 4 POWER SUPPLY ()

WARNING
Do not open any junction box or device enclosure
when power is applied without first de-classifying
the hazardous area.

TERMINAL 5 COM 1 A
TERMINAL 6 COM 1 B
TERMINAL 7 SHIELD
TERMINAL 8 COM 2 A
TERMINAL 9 COM 2 B
TERMINAL 10 SHIELD

A1873

Electronic Module Assembly


Figure VII22EQ2200UV Detector Wiring Terminals

MOUNTING SCREWS

1. Mount the device on a solid surface that is free of


vibration.
2. Remove the cover from the junction box.

ADDRESS
SWITCHES

BULKHEAD

A1895

Figure VII23Electronic Module Mounted Inside Bulkhead

3. Loosen the three captive screws that hold the


electronic module to the terminal wiring board and
remove the module. See Figure VII-25.
4. Loosen (do not remove) the two captive screws that
secure the terminal wiring board inside the junction
box, and remove the terminal wiring board. See
Figure VII-26. (The terminal blocks are located on
the bottom side of the terminal wiring board.)
5. Connect the UV detector wires to the appropriate
points on the P3 terminal. Connect the 24 vdc
power wires and the communication network cable
to the appropriate points on the P2 terminal. See
Figure VII-27 for terminal identification. Note that the
plug-in terminals can be removed to facilitate wiring.

LOOSEN THREE SCREWS


TO REMOVE ELECTRONIC MODULE

oi RING

ELECTRONIC MODULE

UV TEST LAMP* OPENING

TERMINAL WIRING BOARD

SPLIT IN oi RING
(MUST BE POSITIONED
ON THE DOWNWARD SIDE
OF UNIT WHEN MOUNTED)
A1992

LEDs

* UV TEST LAMP OPENING MUST NOT BE ALIGNED WITH SPLIT IN oi RING

B1891

Figure VII-25Electronic Module Installed on Terminal Wiring Board


Figure VII24Viewing Window of UV Detector

VII-17

95-8470

P2

LOOSEN TWO SCREWS TO


REMOVE TERMINAL WIRING BOARD

SHIELD

SHIELD

COM 1

24 VDC
A1993

UV FLAME DETECTOR
TERMINAL BLOCK

P3

SHIELD

10

11

12

SHIELD

Figure VII-26 Terminal Wiring Board with Electronic Module


Removed

NOTE
Terminals 4 and 9 (shield) are connected
internally, as are terminals 5 and 8 (24 vdc +) and
terminals 6 and 7 (24 vdc ).

COM 2

A1989

Figure VII-27 EQ2200UVHT Wiring Terminal

6. Re-install the terminal wiring board inside the


junction box.
7. Set the rocker switches on the DIP switch assembly
on the electronic module for the desired address.
Refer to LON/SLC Device Address Switch Setting
in the Switch Setting section of this manual for
complete information regarding the switch setting
procedure.
8. Re-install the electronic module, ensuring that the
connector is aligned correctly. Tighten the three
captive screws that hold the electronic module in
place.

aiming and wiring of the detector. Armored flexible


conduit should be used for the final 3 feet (one
meter) of the cable run to allow for aiming and
alignment of the detector.
2. Attach the detector to the Swivel Mounting Bracket.
3. Disassemble the detector enclosure by turning the
housing cover counterclockwise. See Figure VII-28.
NOTE
If the detector is equipped with a cover locking
device, it must be loosened using a hexagonal
(Allen) wrench.

9. Replace the junction box cover and hand tighten to


ensure proper sealing.
UV Flame Detector
WIRING REQUIREMENTS
Wiring to the UV detector must be between 12 and 18
AWG with a minimum voltage rating of 600 volts rms
and a minimum temperature rating of 125C. The use of
shielded cable is highly recommended to provide
maximum protection from RFI/EMI interference.
1. Mount the Swivel Mounting Bracket using 1/4 inch
(M6) screws with a length of at least 1 inch (25 mm).
The mounting surface should be free of vibration.
Allow adequate space around the swivel to facilitate

4. Connect the wires to the appropriate screw terminals


on the detector terminal block. See Figure VII-27 for
terminal identification. Do not ground the shield to
the detector housing. (Tape off the shield and leave
it disconnected.)
5. Remove the UV sensor tube module from its
shipping package. When handling the sensor tube
module, be careful not to touch the sensor tube,
since oil from the skin can attenuate UV radiation,
reducing the sensitivity of the tube.
6. Using the index pin as a guide, install the sensor
module on the detector terminal block.

VII-18

7. Re-assemble the detector housing. If the detectors


are equipped with cover locking devices, loosen the
clamp sufficiently so that the catch can be seated
in the blind hole provided on the terminal cap. The
clamp must then be fastened securely around the
detector barrel by tightening with the proper tool.

EQ2200UVIR UV/IR FLAME DETECTOR


1. Mount and wire the detector.

8. Clean the viewing window and o i ring using the


procedure described in the Maintenance section.
9. Check the viewing window surface (Figure VII-24)
and ensure that:
A) The oi source (UV test lamp opening) is located
on top.
B) The split in the oi reflective ring is not aligned
with the UV test lamp opening on the detector
module.
C) The split in the oi ring is directed downward to
prevent a buildup of contaminants between the
oi ring and the viewing window.
10. Aim the detector at the potential hazard and tighten
the nut on the swivel mounting bracket.
11. Install any optional accessories (such as air shields).

A. Mount the detector and mounting bracket


assembly on the wall or ceiling. Observe the
following guidelines:
The mounting surface should be free of
excessive heat and vibration.
Allow adequate space around the swivel to
facilitate aiming and wiring of the detector.
Armored flexible conduit should be used
for the final 3 feet (one meter) of the cable
run to allow for aiming and alignment of the
detector.
Position the conduit below the detector and
orient the detector with the conduit entry at
the bottom or either side of the detector
(never at the top). This will prevent
condensation in the conduit from entering
the detector junction box.
B. Remove the junction box cover.
C. Connect the leadwires to the appropriate screw
terminals on the terminal block inside the
junction box. See Figures VII-29 and VII-30 for
location of the terminal block and Figure VII-31
for terminal identification. Connect the shield of
the power cable to earth ground at the power
source. Connect the shields for the LON/SLC
cable as indicated. Do not ground the shields
at the detector housing.

TERMINAL BLOCK

INDEX PIN

UV SENSOR TUBE MODULE

A1994

HOUSING COVER

Figure VII-28High Temperature UV Detector

VII-19

95-8470

JUNCTION BOX

JUNCTION BOX COVER


IR CONNECTOR PLUG
IR SENSOR MODULE

oi TEST LAMP (2)

O-RING
IR SENSOR HOUSING
UV TERMINAL BLOCK
BANANA PLUG

IR oi RING

UV SENSOR MODULE
oi TEST LAMP
LED (2)

O-RING

UV SENSOR HOUSING

UV oi RING

A1913

Figure VII29UV/IR Detector Parts Identification

GROUND SCREW

"D" CONNECTOR

A1912

TERMINAL BLOCK

LON/SLC ADDRESS SWITCHES


SERVICE SWITCH *
LED **

NOTES: ** SERVICE SWITCH NOT FOR USE IN THE FIELD.


NOTES: ** ILLUMINATION OF LED INDICATES AN ELECTRONIC MALFUNCTION.

Figure VII30UV/IR Detector Junction Box with Cover Removed

VII-20

2. Set the rocker switches.


1

SHIELD

A. Set the rocker switches on the DIP switch


assembly for the desired LON/SLC address.
Refer to LON/SLC Device Address Switch
Setting in Section VIII Switch Setting.

POWER

COM 1

B. Re-install the junction box cover. The six


screws must be tight to ensure the explosionproof and watertight integrity of the junction
box.
3. Complete the installation.
A. Aim the detector at the potential hazard.

COM 2

SHIELD

10

B. Inspect and clean (if necessary) the detector


viewing windows and oi rings by following the
instructions in the Maintenance section of this
manual.
C. Check the detector viewing windows (Figure
VII-32) and ensure that:
the oi test lamps are located at the top or
side of the sensor module (when viewed
from the front)
the opening in the oi ring is at the bottom.
This will ensure proper operation of the oi
system and also minimize the accumulation
of moisture and contaminants between the
oi ring and the viewing window.
D. Install any optional accessories (such as air
shields).

A1914

Figure VII31EQ2200UVIR Detector Wiring Terminals

*oi TEST LAMPS AT TOP OR SIDE

oi TEST LAMP
LED (2)

UV SENSOR
HOUSING

oi RING
OPENING
DOWN

*oi TEST LAMP


(2)
LED (2)
IR SENSOR
HOUSING

DETECTOR MUST
BE ORIENTED WITH
CABLE/CONDUIT ENTRY
AT BOTTOM (PREFERRED)
OR SIDE TO ELIMINATE
DRAINAGE INTO
JUNCTION BOX.
H1327

Figure VII32Front View of the UV/IR Detector

VII-21

95-8470

EQ2200DCU DIGITAL COMMUNICATION UNIT USED


WITH DET-TRONICS H2S/O2 SENSORS OR OTHER
TWO-WIRE 4 TO 20 MA DEVICES

COMMUNICATION MODULE

Determine the best mounting locations for the detectors.


Whenever practical, detectors should be placed where
they are easily accessible for calibration.
WARNING
Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases or vapors.

STANDOFFS (4)

The DCU utilizes the following:

TERMINAL WIRING BOARD

1. A terminal wiring board mounted at the bottom of


the junction box.
A1571

2. A communication module mounted above the


terminal wiring board using the standoffs provided.
See Figure VII-33.

Figure VII33Printed Circuit Boards in Universal DCU

Assembly and Wiring Procedure


NOTE
Before placing the cover back on the enclosure
following completion of assembly and wiring,
inspect the enclosure O-ring to be sure that it is in
good condition and properly installed. Lubricate
the O-ring and the threads of the cover with a thin
coat of an appropriate grease to ease installation.
Refer to the Ordering Information section for the
part number of the recommended grease
(available from Detector Electronics). If the
installation uses catalytic type combustible gas
sensors, it is imperative that lubricants containing
silicone NOT be used, since they will cause
irreversible damage to the sensor. Place the cover
on the enclosure. Tighten only until snug. Do not
over tighten.

Attach the sensor to the DCU enclosure. Do not overtighten. If a sensor separation kit is being used, attach
the sensor to the separation kit junction box and wire
the device as described in the Sensor Separation
section.
CAUTION
The sensor threads can be coated with an
appropriate grease to ease installation. Also
lubricate the cover threads. (See Ordering
Information for part number).
Connect the external wiring to the appropriate terminals
on the DCU terminal wiring board. Refer to Figure VII34 for terminal identification. See Figure VII-35 for an
example of a Det-Tronics electrochemical sensor
connected to a DCU.
Attach the communication module to the standoffs as
shown in Figure VII-33. Connect the ribbon cable from
the terminal wiring board to the communication module.
Set the address for the device. Refer to Device
Address Switch Setting in the Switch Setting section
of this manual for complete information regarding the
switch setting procedure.
Check the wiring to ensure proper connections, then
pour the conduit seals and allow them to dry (if conduit
is being used).

SENSOR SEPARATION FOR DCU WITH H2S AND O2


SENSORS
Since the transmitter for the electrochemical sensor is
already mounted within the sensor housing, simply
mount the entire sensor assembly to the sensor
separation kit junction box and wire it to terminals 2 and
4 inside the DCU, the same as a regular (without sensor
separation) installation. Connect the shield to the
ground terminal in the DCU junction box.
Refer to Table VII-8 for separation distance limitations
for H2S and O2 sensors.

VII-22

EQ2200DCU DIGITAL COMMUNICATION UNIT USED


WITH POINTWATCH
POINTWATCH CALIBRATE

4 TO 20 MA IN

Determine the best mounting locations for the detectors.


Whenever practical, detectors should be placed where
they are easily accessible for calibration.
WARNING
Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases and vapors.

SENSOR POWER

COM 2

The DCU utilizes the following:

14

13

12

10

11

1. A terminal wiring board mounted at the bottom of


the junction box.

COM SHIELD

24 VDC

COM 1

2. A communication module mounted above the


terminal wiring board using the standoffs provided.
See Figure VII-33.
Assembly and Wiring Procedure

A1726

Figure VII34Wiring Configuration for DCU


DCU

POINTWATCH CALIBRATE

4 TO 20 MA IN

H2S/TOXIC/O2

Attach the PointWatch to the DCU enclosure. Do not


over-tighten. If a sensor separation kit is being used,
attach the sensor to the separation kit junction box and
wire the device as described in the Sensor Separation
section.

BLACK

RED

GREEN

SENSOR POWER

Refer to the PointWatch instruction manual (form


number 95-8440) for complete installation and
application information.
Refer to Figure VII-36 when wiring a PointWatch IR gas
detector and a DCU. The wiring code for PointWatch is:

COM 2

14

13

12

10

11

Red =
Black =
White =
Yellow =
Green =

COM SHIELD

+ (24 vdc)
(common)
4 to 20 ma signal
Calibration input
Chassis ground

24 VDC

Set the address for the device. Refer to Device


Address Switch Setting in the Switch Setting section
of this manual for complete information regarding the
switch setting procedure.

COM 1

A1875

Figure VII35Electrochemical Sensor Connected to DCU

Table VII8
Maximum Separation Distances Electrochemical Sensor to DCU

Wire Size

Maximum Wiring Distance

(AWG)

Feet

Meters

18
16

5700
9000

1750
2800
T0020A

VII-23

95-8470

DCU

POINTWATCH

POINTWATCH CALIBRATE

YELLOW

4 TO 20 MA IN

WHITE

BLACK

RED

GREEN

EQ2200DCUEX DIGITAL COMMUNICATION UNIT


USED WITH DET-TRONICS COMBUSTIBLE GAS
SENSORS
Determine the best mounting locations for the detectors.
Whenever practical, detectors should be placed where
they are easily accessible for calibration. Always orient
the junction box with the sensor pointing down.

SENSOR POWER

WARNING
Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases or vapors.

COM 2

14

13

12

10

11

The DCUEX uses the following:


1. The terminal wiring board is mounted at the bottom
of the junction box.

COM SHIELD

24 VDC

2. The transmitter board is mounted above the


terminal wiring board.

COM 1

3. The communication module is mounted above the


transmitter board.

A1876

Figure VII36PointWatch Connected to DCU

The boards are connected to each other using the


standoffs provided. See Figure VII-37.

Sensor Separation for DCU with PointWatch

NOTE
Be sure to note correct orientation of the
transmitter board. If the transmitter board is
rotated 180 from proper orientation, the device
will not operate correctly a LON
communication fault will result. See Figure VII37.

Shielded four wire cable is recommended for


connecting the detector junction box to the DCU. Cable
with a foil shield is recommended. The shield of the
cable should be open at the detector junction box and
connected to earth ground at the DCU junction box.
Refer to Table VI-1 to determine the maximum allowable
wiring from the PointWatch to the power supply (through
the DCU).
NOTE
To ensure proper operation, it is essential to
maintain a minimum of 18 vdc (including ripple) at
the PointWatch detector.

Assembly and Wiring Procedure


Connect the external wiring to the appropriate terminals
on the DCU terminal wiring board. See Figure VII-38.
Attach the sensor to the DCU enclosure. Do not overtighten. If a sensor separation kit is being used, attach
the sensor to the separation kit junction box and wire
the device as described below.

VII-24

CAUTION
The sensor threads can be coated with an
appropriate grease to ease both the initial
installation and future replacement of the sensor.
Detector Electronics offers a silicone free grease
that is especially suited for use with catalytic type
combustible gas sensors (see Ordering
Information for part number). The use of other
lubricants is not recommended, since some
materials can cause irreversible damage to the
sensing element. SILICONE based lubricants or
compounds must NEVER be used.

COMMUNICATION MODULE

SWITCHES ON SAME SIDE


(RIGHT)

TRANSMITTER BOARD

TERMINAL WIRING BOARD

CORRECT ORIENTATION OF TRANSMITTER BOARD

COMMUNICATION MODULE

G
N
O
R
W

SWITCHES ON OPPOSITE SIDES


(WRONG)

TRANSMITTER BOARD

Screw the transmitter board to the standoffs as shown in


Figure VII-37. Connect the sensor plug to the
transmitter board.
Attach the communication module to the standoffs
mounted on the transmitter board. Connect the ribbon
cable from the terminal wiring board to the
communication module.
Set the address for the device. Refer to Device
Address Switch Setting in the Switch Setting section
of this manual for complete information regarding the
switch setting procedure.

TERMINAL WIRING BOARD

DCU TRANSMITTER BOARD1


(MIDDLE BOARD)

DCU TERMINAL BOARD

POINTWATCH CALIBRATE

4 TO 20 MA IN

INCORRECT ORIENTATION OF TRANSMITTER BOARD

SIG

SENSOR POWER
2

COMMUNICATION MODULE
COM 2

14

13

12

10

11

COM SHIELD

TRANSMITTER BOARD

24 VDC
STANDOFFS (4)
COM 1
TERMINAL WIRING BOARD
B1877

NOTES: 1 Catalytic Combustible Gas Sensor


Plugs into Connector Pins on the
Middle Board inside the Junction Box.

B1570

2 Connections Wired at the Factory.

Figure VII37Printed Circuit Boards in Combustible Gas DCU

Figure VII38DCU Transmitter Board Connected


to Terminal Wiring Board

VII-25

95-8470

Sensor Separation with DCUEX


If the installation requires mounting the sensor in a
different location than the DCUEX, observe the following
guidelines.

GR

When separating a combustible gas sensor from the


DCUEX, two options exist:

GR

1. Preferred Method
Mount the transmitter PC board inside the sensor
separation junction box. This assembly can be
separated from the DCUEX by up to 1000 feet using
three conductor 18 AWG shielded cable.
(Regardless of separation distance, operating
voltage at the transmitter MUST be at least 18 vdc
to ensure proper operation.) See Figure VII-39.

ELECTROCHEMICAL SENSOR

SPARE

CHASSIS
CAL

4-20

4-20

RET

RET

+24

+24

Assemble the DCUEX without the transmitter board


similar to the DCU as shown in Figure VII-33. Plug
the sensor into P2 on the transmitter board. Use a
three conductor 18 AWG shielded cable to connect
P1 on the transmitter board to terminals 2, 3 and 4
on the DCU terminal board (see Figure VII-39).
Connect the shield to the ground terminal in the
DCUEX junction box.

GND

CAL

POINTWATCH

2. Alternate Method.
P1

If the transmitter board must be mounted separate


from the sensor (high temperature applications,
etc.), separate the sensor only, leaving the
transmitter PC board inside the DCUEX enclosure.
When using this installation option, see Table VII-9
for maximum wiring distances.

Mount the sensor directly to the separation kit


junction box. Use three conductor shielded cable
for the connection between the terminal block in the
separation kit junction box and P1 on the transmitter
board. A plug with screw terminals is provided for
connecting the cable to P1 on the transmitter board.
Observe the wiring color code. Connect the shield
to the ground terminal in the DCUEX junction box.

TRANSMITTER BOARD

4 TO 20

P2

NOTE: ALWAYS ORIENT


JUNCTION BOX WITH
CATALYTIC SENSOR
POINTING DOWN.
SENSOR

CATALYTIC SENSOR

B1878

Table VII9Maximum Separation Distances


Combustible Gas Sensor to DCU (Alternate Method)

Figure VII39Sensor Separation Kits

Wire Size

Maximum Separation Distance


Feet
Meters

18 AWG (1.0 mm2)*


16 AWG (1.5 mm2)*
14 AWG (2.5 mm2)*
12 AWG (4.0 mm2)*
*Approximate Metric Equivalent.

VII-26

40
60
100
150

12
18
30
45

EQ2500ARM SERIES AGENT RELEASE MODULE

Table VII10Maximum Wiring Length for Release Applications

Device

Wiring

Maximum Wire Length in Feet


12 AWG 14 AWG 16 AWG 18 AWG

To ensure adequate operating voltage for the output


device, the maximum wiring length from the power
source to the output device must not exceed the values
shown in Table VII-10 for automatic release applications
or Table VII-11 for deluge and pre-action applications.
(For solenoids, this wire length includes both the wiring
from the power supply to the agent release module and
the wiring from the module to the solenoid. For squibs,
use only the wire length from the power supply to the
module, since the resistance of the wire from the
module to the squib is included when determining the
value of the compensating resistor.)
Refer to Figure VII-40 for identification of wiring
terminals.
Terminals 1 to 4

890181*

150

100

60

899175*

150

100

60

895630-000*

150

100

60

897494*

190

120

75

486500-001*

1500

1000

600

31-199932-004*

150

100

60

Squib

190

120

75

2 Amp Load

190

120

75

400

T0028B

*Fenwal Solenoid

Terminals 5 to 10

LON/SLC signaling circuit


terminals

Output terminals
Be sure to observe polarity
when wiring the LON/SLC.

Connect a single solenoid


between terminals 1 and 4.
Connect dual solenoids
between terminals 1 and 2, and
between terminals 3 and 4.

5 A side of signaling circuit for


COM 2
6 B side of signaling circuit for
COM 2

NOTE
For testing purposes, a load resistor of 1200 to
1500 ohms @ 1 watt can be placed across
terminals 1 and 4.

7 and 8 shield connection


9 A side of signaling circuit for
COM 1

When using an explosive


initiator, connect the resistor
between terminals 1 and 2 and
the initiator between terminals
3 and 4, as shown in Figure
VII-40.

10 B side of signaling circuit for


COM 1

CAUTION
Do not intermix different types of initiators in the
release circuit.
Table VII-11Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

Solenoids
Manufacturer

Maximum Wire Length in Feet (Meters)


Model

12 AWG

14 AWG

16 AWG

18 AWG

Skinner

LV2LBX25

800 (244)

500 (152)

310 (94)

200 (61)

ASCO

8210A107

520 (158)

325 (99)

200 (61)

130 (40)

ASCO

8210G207

825 (251)

520 (158)

325 (99)

205 (62)

Skinner

73218BN4UNLVNOC111C2

860 (262)

540 (165)

340 (104)

215 (66)

Skinner

73212BN4TNLVNOC322C2

400 (122)

250 (76)

160 (49)

100 (30)

Skinner

71395SN2ENJ1NOH111C2

860 (262)

540 (165)

340 (104)

215 (66)
T0041B

VII-27

95-8470

Terminals 11 to 14

24 vdc power input

Jumpers

Connect the module power


supply to terminals 12 and 13.
If an auxiliary output supply is
used for powering solenoids, it
should be connected to
terminals 11 and 14.

Terminals 13 and 14 are connected by jumper JP2 and


terminals 11 and 12 are connected by jumper JP3.
These two jumpers (JP2 and JP3) must be cut if an
auxiliary output power supply is being used. See Figure
VII-41 for the locations of jumpers on the circuit board.
When an explosive initiator is being used, jumper JP1
must be cut. If a solenoid is used, the jumper must
remain in.

SINGLE
SOLENOID

DUAL
SOLENOIDS

Address Switch Setting

Each device on the LON/SLC must be assigned a


unique address. This is accomplished by setting DIP
switches on the release module circuit board. The valid
address range is from 5 to 250. For complete
information on address switch setting, refer to
LON/SLC Device Address Switch Setting in Section
VIII. For convenience in determining the correct
positions for address switches, refer to the table
Address Switch Settings at the back of this manual.

COM 2

14

13

12

10

11

COM SHIELD

24 VDC

COM 1

JP1

NOTE:
TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.
TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.
JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

JP2
JP3

11 12 13 14
1 2 3 4 5 6 7 8 9 10

EXPLOSIVE INITIATOR OPTION

1
SEE NOTE 2.
2

A1902

Figure VII41Agent Release Module Wiring Terminals and Jumpers

4
NOTES:
1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED.
2. RESISTOR IS USED TO COMPENSATE FOR 10 OHMS CIRCUIT RESISTANCE.
RESISTOR MUST BE RATED 1 WATT MINIMUM (WIRE-WOUND RESISTOR PREFERRED).
WHEN MEASURING THE TOTAL RELEASE CIRCUIT RESISTANCE,
USE AN OHM METER WITH A CURRENT OUTPUT OF 10 MA MAXIMUM.
3. MAXIMUM NUMBER OF EXPLOSIVE INITIATORS PER CIRCUIT IS 12.
EACH CIRCUIT MUST NOT EXCEED 10 OHMS INCLUDING CABLE RESISTANCE.

B1900

Figure VII40Wiring Configuration for Agent Release Module

VII-28

EQ2500SAM SERIES SIGNAL AUDIBLE MODULE

Table VII12Maximum Wiring Length


from Nominal 24 VDC Power Source to Signaling Device

Wiring

Maximum Wire Length in Feet (Meters)


12 AWG
14 AWG
16 AWG
(4 mm2)* (2.5 mm2)* (1.5 mm2)*

To ensure adequate operating voltage for the signaling


device, the maximum wiring length from the power
source to the output device must not exceed the values
shown in Table VII-12. (This wire length includes both the
wiring from the power supply to the signal audible module
and the wiring from the module to the signaling device.)

One 2 Ampere Load

190 (58)

120 (37)

75 (23)

Two 2 Ampere Loads

95 (29)

60 (18)

35 (11)

* Approximate Metric Equivalent.

T0029A

Refer to Figure VII-42 for identification of wiring


terminals.
Terminals 1 to 4

Output terminals
Connect the first output device
between terminals 1 and 2,
and the second between
terminals 3 and 4.

10K EOL

OUTPUT 2*

Polarity shown in Figure VII-42


is for monitoring condition,
polarity is reversed when
activated.

10K EOL

COM 2

Each circuit must have a 10


kohm EOL resistor.
Terminals 5 to 10

+
OUTPUT 1*

14

13

12

10

11

COM SHIELD

24 VDC

LON/SLC signaling circuit


terminals
COM 1

Be sure to observe polarity


when wiring the LON/SLC.

B1901

5 A side of signaling circuit for


COM 2

POLARITY SHOWN IS FOR MONITORING CONDITION,


POLARITY IS REVERSED WHEN ACTIVATED.

NOTE:
TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.
TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.
JUMPERS JP1 AND JP2 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.

6 B side of signaling circuit for


COM 2

Figure VII42Wiring Configuration for Signal Audible Module

7 and 8 shield connection


9 A side of signaling circuit for
COM 1
10 B side of signaling circuit for
COM 1
Terminals 11 to 14

24 vdc power input

Jumpers
Terminals 13 and 14 are connected by jumper JP2 and
terminals 11 and 12 are connected by jumper JP1.
These two jumpers (JP1 and JP2) must be cut if an
auxiliary output power supply is being used. See Figure
VII-43 for the locations of jumpers on the circuit board.

Connect the module power


supply to terminals 12 and 13.
If an auxiliary output supply is
used for powering signaling
devices, it should be connected
to terminals 11 and 14.

VII-29

95-8470

EQ2400NE SERIES NETWORK EXTENDER


1. Securely mount the aluminum enclosure.
2. Remove the cover from the network extender
enclosure.

JP1
JP2

11 12 13 14
1 2 3 4 5 6 7 8 9 10

B1903

Figure VII43Signal Audible Module Wiring Terminals and Jumpers

3. Connect the 24 vdc power lead wires and the


communication network cable to the appropriate
points on the terminal block. See Figure VII-44A for
terminal location within the junction box and Figure
VII-44B for terminal identification. Refer to Table VII13 to determine maximum wiring length.
TERMINAL NO. 1

Address Switch Setting


Each device on the LON/SLC must be assigned a
unique address. This is accomplished by setting DIP
switches on the modules circuit board. The valid
address range is from 5 to 250. For complete
information on address switch setting, refer to
LON/SLC Device Address Switch Setting in Section
VIII. For convenience in determining the correct
positions for address switches, refer to the table
Address Switch Settings at the back of this manual.

12

A2021

Figure VII-44ANetwork Extender Wiring Terminal Location

SHIELD

SHIELD

SHIELD

10

11

12

SHIELD

COM 1

24 VDC

COM 2

A1947

Figure VII-44BNetwork Extender Wiring Terminal Identification

VII-30

COM 1 -

COM 2 -

24 VDC -

Communication network connections:


Connect to COM 2 terminals of the next
device on the loop, A to A and B to B.

TYPICAL APPLICATIONS
Figure VII-45 shows a power supply monitor wired on a
LON between a UV detector and a DCU.

Communication network connections:


Connect to COM 1 terminals of the
previous device on the loop, A to A and B
to B.

Figure VII-46 illustrates the power and communication


wiring for a UV detector, an IDC and a DCU, connected
to a standard LCU (EQ2100LCU) and an LIOU.

Connect the "+" terminal to the positive


side of the 24 vdc power source. (Both "+"
terminals are connected internally.)

Figure VII-47 illustrates the power and communication


wiring for a UV detector, an IDC and a DCU, connected
to the optional LCU (EQ2101LCU) and an LIOU.

Connect the "-" terminal to the negative


side of the 24 vdc power source. (Both "-"
terminals are connected internally.)

Figure VII-48 shows the power and communication


wiring for a UV/IR detector, an EQ2500SAM and an
EQ2500ARM, connected to a standard LCU
(EQ2100LCU) and an LIOU.

4. Connect the shields to the two designated "shield"


terminals. The two shield terminals are connected
internally to ensure shield continuity. Do not ground
either shield at the network extender enclosure.
Insulate the shields to prevent shorting to the
device housing or any other conductor.

Figure VII-49 shows a network extender wired between


a UV detector and a DCU.
Figure VII-50 shows a high temperature UV detector
wired between a standard UV detector and a DCU.

5. Check all field wiring to ensure that the proper


connections have been made.
6. Inspect the enclosure O-ring to be sure that it is in
good condition and properly installed. Lubricate the
O-ring and the threads of the enclosure cover to
ease both installation and future removal of the
cover. The recommended lubricant is a silicone free
grease available from Detector Electronics. If the
installation uses catalytic type combustible gas
sensors, it is imperative that lubricants containing
silicone not be used, since they will cause
irreversible damage to the sensor. Place the cover
on the enclosure. Tighten only until snug. Do not
over tighten.

Table VII-13Maximum Wiring Length from Nominal 24 vdc


Power Source to Network Extender

Wire Size

Maximum Wiring Distance


Feet
Meters

18 AWG (1.0 mm2)*


16 AWG (1.5 mm2)*
14 AWG (2.5 mm2)*

2200
3500
5600

650
750
1700

* Approximate Metric Equivalent.

VII-31

95-8470

INSTALLATION CHECKLIST

5. Sensor and LON/SLC wiring is correct.

The following checklist is provided as a means of


double checking the system to be sure that all phases
of system installation are complete and have been
performed correctly.

6. Power wiring is installed and power source is


operational.
7. External loads are properly connected and EOL
resistors are installed.

1. Junction boxes are mounted securely and detectors


are pointing in the proper direction.

8. DIP switches are set correctly. Record this


information for future reference.

2. All cable shields are properly insulated and


grounded.

9. Devices are properly installed in the mounting


racks.

3. All junction box covers are tightly installed.


10. Proper ventilation is provided (if needed) to prevent
equipment over-heating.

4. Explosion-proof and watertight electrical fittings


have been installed at all junction box entries as
required for the hazardous location.

EQ2200UV

9 10

COM 2

14 13 12 11
8

9 10

SHIELD

COM 1

COM 2

SHIELD

COM 1

SHIELD

B1953

+ SENSOR

SHIELD

24 VDC

COM 2
G

1 2

POWER

4 TO 20 MA IN

3 2

POINTWATCH CALIBRATE

5
+

SHIELD

12 11 10 9
SHIELD

TO PREVIOUS LON DEVICE

TO POWER DISTRIBUTION
TERMINALS

EQ2200DCU

24 VOLTS DC

A B SHIELD
5 6 7
COM 1

3 4

EQ2100PSM

+ +

24 VDC
1 2

Proceed to System Startup.

TO NEXT LON DEVICE

Figure VII-45A Typical Application LON Connections for a Power Supply Monitor Wired Between a UV Detector and a DCU

VII-32

VII-33

NC

ROW C

ROW B

COM

1
NO
ROW A

SHIELD

SHIELD

COM 2

COM 1

95-8470

Figure VII46A Typical System Field Devices Connected to EQ2100LCU (Standard)

POWER SUPPLY MONITOR

24 VDC

J1

C1879

J5

A C LINE

10

AUX POWER

5
+

J3

4
SHIELD

+
B

12 11 10 9

CIRCUIT 1

BUS
BAR

CIRCUIT 2
A

SYSTEM
POWER
SUPPLY

COM 2
SHIELD

24 VOLT
BATTERY
BACKUP

BATTERY
CKT BREAKER

RS-485

ALARM

J1
A

3E
3D
2E
2D
1E
1D

J4

SUPER

TROUBLE

EQ2100LIOU

11

J3

DC2

DC1

12
8

13
7

14

24 VOLTS DC

COM 1

AUX 24V

COM 2

MAIN 24V

A
B
CHASSIS
GND FLT
EARTH

INPUT 3 10

INPUT 2 11

RESET 13

SHIELD

INPUT 1 12

10

SHIELD

RS-485

NO

11
9

12

13

14

POINTWATCH CALIBRATE

COM

4 TO 20 MA IN

14

NC

15

K1

COM 2

16

10

K2

+
POWER

17

COM 1

A
SENSOR

K3

COM 1

24 VOLTS DC

18

B SHIELD
6
7

SHIELD

K4

19

20

21

22

A
5

TO GAS DETECTOR
POWER SUPPLY

EQ2200DCU

SHIELD

FAULT

P2

P1

RXD +
RXD
COM
TXD
TXD +
RXD
COM
TXD

SHIELD 23

24 VDC
1
2

B 24

A 25

COM1

EQ2200IDC

EQ2200UV

COM2

+
A

GATEWAY RELAYS

EQ2100LCU

J2

MAIN AUX

VII-34

ROW B

COM

TWO 24VOLT DC
POWER SUPPLIES
PER NFPA 72

ROW C

NC

NO
ROW A

Figure VII47A Typical System Field Devices Connected to EQ2101LCU (Optional)

EQ2100LIOU
B

ALARM

RS-485

J1
A

3E
3D
2E
2D
1E
1D

12
8

13
7

14
6

11

J4

SUPER

TROUBLE

DC2

DC1

AUX 24V

COM 2

MAIN 24V

A
B
CHASSIS
GND FLT
EARTH

INPUT 3 10

INPUT 2 11

RESET 13

INPUT 1 12

NO

COM

10

SHIELD

14

11
9

SHIELD

12

13

14

POINTWATCH CALIBRATE

CIRCUIT 1

4 TO 20 MA IN

RS-485

NC

15

16

COM 2

CIRCUIT 2

K1

K2

10

COM 2

+
POWER

17

COM 1

A
SENSOR

K3

18

24 VOLTS DC

K4

19

20

COM 1

24 VOLTS DC

SHIELD

FAULT

P2

21

B SHIELD
6
7

SHIELD

J3

10

J5
B1880

AUX POWER

P1

22

A
5

TO GAS DETECTOR
POWER SUPPLY

COM 1

RXD +
RXD
COM
TXD
TXD +
RXD
COM
TXD

SHIELD 23

24 VDC
1
2

B 24

A 25

COM2

COM1

EQ2200DCU

EQ2200IDC

EQ2200UV

+
A

GATEWAY RELAYS

EQ2101LCU

J2

MAIN AUX

VII-35

ROW C

NC

ROW B

COM

ROW A

NO

SHIELD

SHIELD

COM 2

MAIN AUX

COM 1

95-8470

Figure VII48A Typical System UV/IR Detector, EQ2500SAM and EQ2500ARM Connected to a Standard EQ2100LCU

POWER SUPPLY MONITOR

24 VDC

C1910

J5

A C LINE

5
+

12 11 10 9

10

AUX POWER

4
SHIELD

3
B

J3

BUS
BAR

OUTPUT 2
A

SYSTEM
POWER
SUPPLY

COM 2
SHIELD

24 VOLT
BATTERY
BACKUP

BATTERY
CKT BREAKER

RS-485

ALARM

J1
A

3E
3D
2E
2D
1E
1D

J4

SUPER

TROUBLE

EQ2100LIOU

11

J3

DC2

DC1

12
7

13
6

14

COM 1

AUX 24V

COM 2

MAIN 24V

A
B
CHASSIS
GND FLT
EARTH

RS-485

INPUT 3 10

INPUT 2 11

RESET 13

INPUT 1 12

NO

COM

SHIELD

14

SHIELD

NC

10

15

OUTPUT 1

K1

10

16

COM 2
9

K2

17

11

COM 1

K3

12

24 VOLTS DC

18

13

DUAL SOLENOIDS

SINGLE SOLENOID

SHIELD

K4

14

24 VOLTS DC

EQ2500ARM

SHIELD

FAULT

19

20

+
3

P2

+
2

21

COM 1
B

P1

22

SHIELD

RXD +
RXD
COM
TXD
TXD +
RXD
COM
TXD

SHIELD 23

B 24

A 25

EQ2500SAM

EQ2200UVIR

COM2

COM1

EQ2100LCU

GATEWAY RELAYS

SHIELD

J2

VII-36

ROW C

NC

ROW B

COM

ROW A

NO

SHIELD

SHIELD

COM 2

COM 1

24 VDC
COM 1

Figure VII-49A Typical System - Network Extender Wired Between UV Detector and DCU

POWER SUPPLY MONITOR

24 VDC

C1940

J5

A C LINE

5
+

12 11 10 9

10

AUX POWER

4
SHIELD

3
B

J3

BUS
BAR

SYSTEM
POWER
SUPPLY

COM 2
SHIELD

24 VOLT
BATTERY
BACKUP

BATTERY
CKT BREAKER

RS-485

ALARM

J1
A

3E
3D
2E
2D
1E
1D

J4

SUPER

TROUBLE

EQ2100LIOU

11

J3

DC2

DC1

12
8

13
7

14

24 VOLTS DC

COM 1

AUX 24V

COM 2

MAIN 24V

A
B
CHASSIS
GND FLT
EARTH

RS-485

SHIELD

INPUT 3 10

INPUT 2 11

SHIELD

RESET 13

INPUT 1 12

NO

POINTWATCH CALIBRATE

COM

10

4 TO 20 MA IN

14

4
SHIELD

NC

3
B

15

11
B

12

K1

COM 2

16

10

SHIELD

K2

+
POWER

17

COM 1

A
SENSOR

K3

B SHIELD
6
7

18

A
5

SHIELD

K4

19

20

21

22

24 VDC
1
2

TO GAS DETECTOR
POWER SUPPLY

EQ2200DCU

SHIELD

FAULT

P2

P1

RXD +
RXD
COM
TXD
TXD +
RXD
COM
TXD

SHIELD 23

B 24

A 25

COM1

EQ2401NE

EQ2200UV

COM2

+
A

GATEWAY RELAYS

EQ2100LCU

J2

MAIN AUX

VII-37

ROW B

COM

1
NO
ROW A

SHIELD

SHIELD

COM 2

COM 1
COM 1

Figure 50A Typical System EQ2200UVHT Wired Between a Standard UV Detector and a DCU

POWER SUPPLY MONITOR

24 VDC

B1990

J5

A C LINE

5
+

12 11 10 9

10

AUX POWER

4
SHIELD

3
B

J3

2
A

SYSTEM
POWER
SUPPLY

COM 2
BUS
BAR

SHIELD

24 VOLT
BATTERY
BACKUP

24 VDC

ROW C

NC

RS-485

ALARM

BATTERY
CKT BREAKER

J1
A

3E
3D
2E
2D
1E
1D

J4

SUPER

TROUBLE

EQ2100LIOU

11

J3

DC2

DC1

12
8

13
7

14

24 VOLTS DC

TO GAS DETECTOR
POWER SUPPLY

COM 1

AUX 24V

COM 2

MAIN 24V

12
SHIELD

A
B
CHASSIS
GND FLT
EARTH

10

11
B

RS-485

INPUT 3 10

SHIELD

INPUT 2 11

RESET 13

INPUT 1 12

NO

COM

4
SHIELD

POINTWATCH CALIBRATE

14

3
B

NC

2
A

5
1

SHIELD

15

COM 2

4 TO 20 MA IN

K1

10

POWER

16

SENSOR

K2

COM 1

17

B SHIELD
6
7

K3

A
5

18

19

20

21

22

24 VDC
1
2

SHIELD

K4

RXD +
RXD
COM
TXD
TXD +
RXD
COM
TXD

SHIELD 23

B 24

EQ2200DCU

SHIELD

FAULT

P2

P1

COM1

A 25

COM2

EQ2200UVHT

EQ2200UV

+
A

GATEWAY RELAYS

EQ2100LCU

J2

MAIN AUX

95-8470

Section VIII
Switch Setting

S5 Hardware Serial Port Configuration


Verify that S5 switches are set as follows:

GATEWAY

1 Open

The gateway contains four 8-position DIP switch


assemblies that are used for:

2 Closed

Selecting serial port 1 software parameters


Setting the gateway Modbus/Allen Bradley address
Selecting gateway relay operation (latching/nonlatching)
Setting the gateway type and address.

4 Open

3 Closed
5 and 6 Closed
7 and 8 Open.
S6 Software Serial Port Configuration for Port 1

Refer to Figure VIII-1 to identify the function of the DIP


switches. Refer to Figure VIII-2 to locate the DIP switch
assemblies on the side of the gateway.

1, 2, and 3 Determine the desired baud


rate, then refer to Table VIII-1
for the proper switch settings.
(19,200 is recommended and
cannot be exceeded in the
LCU.)

S8 LON CONFIGURATION
1

4 Parity enable.

CLOSED
OPEN
NON-LATCHING GATEWAY RELAYS
SELECT CONFIGURATION PORT
PORT 2 OPERATION
PORT 1 OPERATION
GATEWAY ADDRESS BIT 1 (MSB)
GATEWAY ADDRESS BIT 0 (LSB)

Open = no parity.
Closed = parity enabled.
5 Parity type.

S7 MODBUS ADDRESS
1

Open = odd.
Closed = even.

8
MODBUS ADDRESS BIT 7 (MSB)
MODBUS ADDRESS BIT 6
MODBUS ADDRESS BIT 5
MODBUS ADDRESS BIT 4
MODBUS ADDRESS BIT 3
MODBUS ADDRESS BIT 2
MODBUS ADDRESS BIT 1
MODBUS ADDRESS BIT 0 (LSB)

6 Stop bits.
Open = 1 stop bit.
Closed = 2 stop bits.

S6 SOFTWARE SERIAL PORT CONFIGURATION (CHANNEL 1 ONLY)


1

8
OPEN
NUMBER OF DATA BITS (OFF = 7, ON = 8)
NUMBER OF STOP BITS (OFF = 1, ON = 2)
PARITY TYPE (OFF = ODD, ON = EVEN)
PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED)
BAUD RATE BIT 2 (MSB)
0 = 1200
BAUD RATE BIT 1
1 = 2400
BAUD RATE BIT 0 (LSB)
2 = 9600
3 = 19200

S5 HARDWARE SERIAL PORT CONFIGURATION


1

8
OPEN
OPEN
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
OPEN

OPEN = OFF
CLOSED = ON

C1888

Figure VIII1Gateway DIP Switch Assignments

A1546

S5 S6

S7

S8

Figure VIII2Gateway DIP Switch Location

VIII-1

95-8470

7 Data bits.

Table VIII1Baud Rate Selection - Switches S6-1, S6-2, S6-3

Closed = 8 data bits


(required for
Modbus or Allen
Bradley
communication).
Open = 7 data bits (not
recommended).

BAUD RATE
1,200
2,400
9,600
19,200

SWITCH POSITIONS
1
2
3
Op
Cl
Op
Cl

Op
Op
Cl
Cl

Op
Op
Op
Op
T0022B

Op = Open
Cl = Closed

8 Open.
NOTE
Serial port 2 is fixed at 9600 baud, one stop bit and
even parity.

Table VIII2Gateway Address Switch Settings

S7 Port 1: Modbus/Allen Bradley Address


Set switches to match the
required slave address. 0 is
not a valid address. Refer to
Address Switch Settings in
the Appendix.

Gateway Address

S8-1

S8-2

Op

Op

Cl

Op

Op

Cl

Cl

S8 Network Configuration
Op = Open

1 and 2 Gateway LON/SLC address.


See Table VIII-2. Gateway
address 1 is recommended.
3 Port 1 operation:
Open = Modbus RTU Slave
Closed = Allen Bradley DF1
Slave
4 Port 2 operation:
Open = Modbus RTU Slave
Closed = Modbus RTU
Master (to PLC)
5 Select configuration port:
Open = Port 1
Closed = Port 2
6 Relay Operation.
Open = Latching
Closed = Non-latching.
7 Reserved. Leave switch Open
8 Gateway type.
Open = Reserved
Closed = Main gateway.

VIII-2

Cl = Closed

Cl
T0023A

LOGIC CONTROLLER

LON/SLC DEVICE ADDRESS SWITCH


SETTING

The logic controller contains three 8-position DIP switch


assemblies that are used for:
Serial port configuration
Communication parameters
Setting the LON/SLC address.
S5 Hardware Serial Port Configuration
Verify that S5 switches are set as follows:
1 Closed

Each individual device on the LON/SLC must be


assigned a unique address. Addresses 1 to 4 are
reserved for gateway use. Address 1 is for the main
gateway. Valid addresses for field devices are from 5 to
250. If the address is set to zero or an address above
250, the communication module will ignore the switch
setting. Duplicated addresses are not automatically
detected. All modules with the same address will report
on that address. The status word will show the latest
update, which could be from any of the reporting
modules at that address.

2 Open

NOTE
Logic controllers utilize two consecutive LON/SLC
addresses, the first of which must be an odd
number, i. e. a Logic Controller with an address of
7 will occupy both 7 and 8 on the LON/SLC.

3 Open
4 Closed
5 Open
6 Open
7 Closed
8 Open.
S6 Diagnostic Serial Port Configuration
Diagnostic serial port is
intended for factory use only.
Switch settings will not affect
normal operation.
S7 LON/SLC Address
Set switches for the LON/SLC
address. Valid addresses are
from 5 to 247, and must be an
odd number. If an address
outside this range is selected,
the address will default to 5.
S7-1 = LSB, S7-8 = MSB.

ISOLATION MODULE
A slide switch (SW1), located on the top edge of the
module, controls the 24 volt ground fault monitor
function.
On = Enabled
Off = Disabled

Power must be cycled before the new address will take


effect.
For your convenience in setting the address switches,
refer to the table Address Switch Settings at the back
of this manual.
After setting the address switches, record the address
number and device type on the Address Identification
Chart provided with this manual. Post the chart in a
convenient location near the LCU.

OPEN
BINARY
VALUE

16 32 64 128

NODE ADDRESS EQUALS THE ADDED VALUE


OF ALL CLOSED ROCKER SWITCHES

OPEN

Determine the type of LCU being used (Refer to the


label on the LCU mounting cage.) Set SW1 as follows:
Off EQ2100LCU
On EQ2101LCU

Selection of the node address for field devices is


accomplished by setting rocker switches on a DIP
switch assembly. (Note that only the first eight of the 12
switches are used for selecting the address.) The
address number is binary encoded with rocker switch
No. 1 on the 8 position switch assembly being the LSB
(least significant bit). Each rocker switch has a specific
binary value, as shown in Figure VIII-3. The node
address is equal to the added value of all closed rocker
switches. All open switches are ignored. For example:
for node No. 5, close rocker switches 1 and 3 (binary
values 1 + 4); for node No. 25, close rocker switches 1,
4 and 5 (binary values 1 + 8 + 16).

LEAVE IN
OPEN POSITION
OPEN = OFF
CLOSED = ON
A1557

Figure VIII3Field Device Address Switches

VIII-3

95-8470

The last device requires an EOL resistor.

Section IX
System Startup

All devices sharing a common RS-485 link must have a


common system power return.

PRE-COMMISSIONING CHECKLIST
GENERAL

LIOU

Insulate all shields to prevent shorting to the device


housing or to any other conductor.

Verify correct jumper positions and switch settings.


Never disconnect the circuit ground between the LIOU
and the LCU.

Place alarm/release output in Bypass/Isolate when


servicing devices.

Check signal circuits for correct polarity.

Maintain a log book containing the type and serial


numbers of devices as well as the location and date of
installation.

Check for correct installation of EOL resistors.

POWER SUPPLIES AND POWER MONITORS

Maintain a log of maintenance activities.


Observe normal precautions for handling electrostatic
sensitive devices.

Verify all earth ground connections as specified in the


wiring instructions.
Verify correct ac power to supply.

LON

Check power distribution to ensure that all devices are


receiving power.

Rocker switches for each LON device must be set to the


desired address prior to power-up.

Check power trouble indicator by introducing a short


and an open.

Test the loop with no power applied and all


communication modules removed. DC resistance
should be equal on A and B.

FLAME DETECTORS

Check polarity on A and B (no rolls). COM 1 connects


to COM 2 ; COM 2 connects to COM 1. A connects to
A and B to B.

Check for potential false alarm sources.


Check detector aiming and ensure that mounting
brackets are tight.

Measure voltage. A to chassis ground measures


approximately +7.5 vdc. B to ground measures
approximately 7.5 vdc.

Check for objects that can block the detectors view.


Detectors can be checked for proper response using
the test described in this manual.

Measure signal (400 mv P-P min.).


Check fault tolerance by introducing a short and an
open.

DCUs
LCU

Check modules for correct orientation.


Check for the presence of contaminants or poisoning
agents.

Verify correct switch positions.


All configuration data must be downloaded to the
device and written to the EPROM after any change is
made. Changes to the logic controller also require
downloading via the key switch.

Device should be oriented with the sensor pointing


down.

Chassis ground stud must be connected to earth


ground.

IDCs

Check RS-485 connections and polarity.

Check for correct installation of EOL resistors.

IX-1

95-8470

ARMs

CALIBRATION

Check jumpers.

To ensure optimum performance, calibration must be


performed on a regularly scheduled basis. Since each
application is different, the length of time between
regularly scheduled recalibrations can vary from one
installation to the next. In general, the more frequently a
system is checked, the greater the reliability.

SAMs
Check signal circuits for correct polarity.
Check for correct installation of EOL resistors.

IMPORTANT
4 to 20 ma devices not manufactured by DetTronics must be pre-calibrated. To ensure
adequate protection, calibration must be performed
on a regularly scheduled basis.

Check jumpers.

STARTUP PROCEDURE

NOTE
The calibration will be aborted and the detector will
revert back to the previous calibration values if the
calibration is not completed within 12 minutes. The
red LED will blink. The calibration will be logged
as aborted.

1. Output loads that are controlled by the system


should be secured (remove power from all output
devices) to prevent actuation.
2. Check all system wiring for proper connection.

NOTE
The Sensor Replacement calibration procedure
must be used for the initial calibration of a new
sensor. The Routine Calibration procedure can
then be used for all subsequent calibrations.

3. Before installing devices in the mounting racks,


inspect them to verify that they have not been
physically damaged in shipment. Check the rocker
switches for proper programming, then slide the
device fully into the mounting rack.

NOTE
Some calibration procedures require the operator
to activate the reed switch located on a circuit
board inside the junction box. See Figure IX-1 for
the location of the reed switch. To activate the
reed switch, hold the calibration magnet against
the side of the junction box near the switch location
approximately one inch above the mounting
surface. (Do not open the junction box.) Hold the
calibration magnet in place for about 4 seconds to
initiate steps of the calibration procedure.

4. Apply power to the system.


NOTE
To prevent the network modules from going into a
fault isolation condition, apply power to the LCU
prior to applying power to the network devices.
5. Program the system for the desired operation using
Det-Tronics configuration software. Refer to
software manual, form number 95-8479-02.
Download configuration data to all devices.

CALIBRATION ALGORITHM A

NOTE
After system configuration has been completed,
the entire system should be tested for proper
operation to ensure that configuration was
performed properly.

FOR MANUAL CALIBRATION OF UNIVERSAL DCU

Normal Calibration

6. Calibrate the sensors.

1. Activate the reed switch. The red LED blinks at a 2


Hz rate while the reed switch is closed.

7. Ensure that all trouble and alarm conditions have


been cleared and the LCU reset, then remove
mechanical blocking devices (if used) and restore
power to the output loads.

2. After the reed switch has been closed for 3


seconds, the calibrate LED on the communication
module flashes at a 1 Hz rate, indicating that it is
ready for the zero input.
3. Apply the zero input (4 ma).

IX-2

13. The calibration is complete. The calibrate LED


turns off.
If the calibration is not completed within 12 minutes, the
previous calibration values are restored and the
calibration is logged as aborted. The calibrate LED
flashes at a 4 Hz rate.

GND

11
12
5

SW1

14

10

13

Sensor Replacement

WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

MAGNETIC REED SWITCH *

1. Open the junction box cover and press the sensor


replacement switch.
2. The calibrate LED on the communication module
flashes at a 1 Hz rate, indicating it is ready for the
zero input.

A1881

TO ACTIVATE THE MAGNETIC REED SWITCH,


HOLD THE CALIBRATION MAGNET AGAINST THE SIDE OF THE ENCLOSURE
AT THE LOCATION OF THE REED SWITCH,
APPROXIMATELY ONE INCH ABOVE THE MOUNTING SURFACE.

3. Replace the sensor and apply the zero input (4 ma).

Figure IX1DCU Terminal Wiring Board Mounted


in Six-Port Junction Box

4. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

4. Activate the reed switch. The red LED will blink at a


2 Hz rate for 3 seconds while the reed switch is
closed.

5. The communication module records the


uncalibrated value in position one of the calibration
log and calibrates the zero value. The calibrate
LED goes on steady.

5. After the reed switch has been closed for 3


seconds, the communication module records the
uncalibrated value in the calibration log and
calibrates the zero value. The calibrate LED goes
on steady.

6. Apply the calibration gas.


7. The calibrate LED blinks at a 1 Hz rate when the
input increases.

6. Apply the calibration gas.


7. The calibrate LED blinks at a 1 Hz rate when the
input increases.

8. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

8. Activate the reed switch. The red LED blinks at a 2


Hz rate while the reed switch is closed.

9. The communication module records the


uncalibrated value in the first register of the
calibration log and calibrates the span value.

9. The communication module records the


uncalibrated value in the calibration log and
calibrates the span value after the reed switch is on
for 3 seconds.

10. The calibrate LED goes on steady.


11. Remove the span gas and return the analog input to
normal.

10. The calibrate LED goes on steady.


11. Remove the span gas and return the analog input to
normal.

12. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

12. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

13. The calibration is complete. The calibrate LED


turns off.

IX-3

95-8470

Pressing the sensor replacement switch aborts the


calibration and starts over.
Resetting the
communication module will abort sensor replacement.

Sensor Replacement Combustible Gas


NOTE
When replacing a sensor, compare part numbers
to be sure that the correct replacement sensor is
being used.

CALIBRATION ALGORITHM C
FOR COMBUSTIBLE GAS DCUs AND
AUTOMATIC CALIBRATION OF UNIVERSAL DCUs

WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

NOTE
After exposure of the H 2 S sensor to high
concentrations of gas, it is recommended that it be
exposed to fresh air for at least 30 minutes and
then re-calibrated.

1. Remove the cover from the DCU enclosure.


2. Press the sensor replacement switch on the
communication module for about 1 second. The
calibrate LED on the communication module blinks
at a 1 Hz rate, indicating that it is ready for the zero
input.

Routine Calibration
1. Apply the zero gas.

NOTE
Pressing the sensor replacement switch prevents
the communication module from generating a fault
signal when the input drops to zero due to
removing the sensor. In addition, the calibration
will not be aborted if the calibration procedure is
not completed within 12 minutes.

2. Activate the reed switch for at least 4 seconds. The


red LED blinks at a 2 Hz rate for 3 seconds while
the reed switch is activated.
3. The calibrate LED on the communication module
blinks at a 1 Hz rate, indicating it is ready for the
zero input.

3. Place the calibration switch on the transmitter board


in the calibrate position.

4. Wait until the calibrate LED goes on steady


(approximately 4 seconds). The communication
module records the uncalibrated value in the
calibration log and calibrates the zero value during
this time.

4. Replace the sensor.


5. Connect a volt meter to the test points on the
transmitter board. Connect the + lead to TP1
(red). Connect the lead to TP2 (black).

5. Apply the calibration gas. The calibrate LED blinks


at a 1 Hz rate when the sensor detects gas.

6. Wait at least 5 minutes for the sensor output to


stabilize, then adjust R2 for a reading of 0.40 vdc (4
ma) on the meter.

6. When the sensor input has been stable for 30


seconds, the communication module records the
uncalibrated value in the calibration log and
calibrates the span value.

NOTE
Do not make adjustments to R1 when calibrating
the sensor.

7. The calibrate LED goes on steady.


8. Remove the calibration gas.

7. Place the calibrate switch on the transmitter board


in the normal position.

9. The communication module waits until the sensor


input drops below 4% full scale.

8. Activate the reed switch for 4 seconds. The red


LED blinks at a 2 Hz rate for 3 seconds while the
reed switch is activated. The communication
module records the uncalibrated value in position
one of the calibration log and calibrates the zero
value. The calibrate LED goes on steady.

10. The calibration is complete. The calibrate LED


turns off.
NOTE
If the calibration is not completed within 12
minutes, the calibration will be aborted and the
detector will revert back to the previous calibration
values. The red LED will blink at a 4 Hz rate. The
calibration will be logged as aborted.

9. Place the calibration switch on the transmitter board


in the calibrate position.

IX-4

10. Apply the calibration gas and wait for the output to
stabilize.

3. Replace the sensor.


4. Wait at least 5 minutes for the sensor output to
stabilize.

11. With 50% LFL calibration gas applied to the sensor,


adjust R3 for a reading of 1.2 vdc (12 ma) on the
meter.

5. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
activated. The communication module records the
uncalibrated value in position one of the calibration
log and calibrates the zero value. The calibrate
LED goes on steady.

12. Place the calibrate switch on the transmitter board


in the normal position. The red LED blinks at a 1
Hz rate.
13. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is
activated.

6. Apply the calibration gas. The calibrate LED blinks


at a 1 Hz rate when the input increases.

14. The communication module records the


uncalibrated value in the first register of the
calibration log and calibrates the span value. The
calibrate LED goes on steady.

7. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
activated.
8. The communication module records the
uncalibrated value in the first register of the
calibration log and calibrates the span value. The
calibrate LED goes on steady.

15. Remove the calibration gas and place the cover


back on the DCU enclosure.
16. The communication module waits until the analog
value drops below 4% full scale. The calibration is
complete. The calibrate LED turns off.

9. Remove the calibration gas and place the cover


back on the DCU enclosure.

Pressing the sensor replacement switch aborts the


calibration and starts over.

10. The communication module waits until the analog


value drops below 4% full scale. The calibration is
complete. The calibrate LED turns off.

Sensor Replacement Toxic Gas


Pressing the sensor replacement switch aborts the
calibration and starts over.

NOTE
When replacing a sensor, compare part numbers
to be sure that the correct replacement sensor is
being used.

CALIBRATION ALGORITHM D
FOR UNIVERSAL DCUs WITH O2 SENSOR

WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

Normal Calibration
1. Apply clean air (20.9% oxygen).

1. Remove the cover from the DCU enclosure.

2. Activate the reed switch for at least 4 seconds. The


red LED blinks at a 2 Hz rate for 3 seconds while
the reed switch is closed.

2. Press the sensor replacement switch on the


communication module for about 1 second. The
calibrate LED on the communication module blinks
at a 1 Hz rate, indicating that it is ready for the zero
input.

3. The calibrate LED blinks at a 1 Hz rate, indicating


that calibration has begun.

NOTE
Pressing the sensor replacement switch prevents
the communication module from generating a fault
signal when the input drops to zero due to
removing the sensor. In addition, the calibration
will not be aborted if the calibration procedure is
not completed within 12 minutes.

4. The communication module waits 3 seconds.


5. The communication module records the
uncalibrated value in the calibration log and
calibrates the span value.
6. The calibrate LED goes on steady.

IX-5

95-8470

7. The communication module waits 3 seconds.

CALIBRATION ALGORITHM G
FOR DCUs WITH POINTWATCH

8. The calibration is complete. The calibrate LED


turns off.

Routine Calibration

Sensor Replacement

1. Apply the zero gas.

WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

2. Activate the reed switch for at least 4 seconds. The


red LED blinks at a 2 Hz rate for 3 seconds while
the reed switch is activated.

1. Open the junction box cover and press the sensor


replacement switch.

3. The calibrate LED on the communication module


blinks at a 1 Hz rate, indicating it is ready for the
zero input.

2. The calibrate LED on the communication module


blinks at a 1 Hz rate, indicating that it is ready for
the zero input.

4. When a steady zero reading is obtained, the


communication module records the uncalibrated
value in the calibration log and calibrates the zero
value during this time. The LED turns on steady.

3. Replace the sensor and set the sensor switch


(located on the sensor cell) to zero.

5. Apply the calibration gas. The calibrate LED blinks


at a 1 Hz rate when the sensor detects gas.

4. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

6. When the sensor input has been stable for 30


seconds, the communication module records the
uncalibrated value in the calibration log and
calibrates the span value.

5. The communication module records the


uncalibrated value in position one of the calibration
log and calibrates the zero value. The calibrate
LED is on steady.

7. The calibrate LED goes on steady.

6. Set the zero switch on the sensor to normal. Apply


clean air (20.9% oxygen) to set the sensor analog
span value.

8. Remove the calibration gas.


9. The communication module waits until the sensor
input drops below 4% full scale.

7. The calibrate LED blinks at a 1 Hz rate when the


input goes high.

10. The calibration is complete. The calibrate LED


turns off.

8. Activate the reed switch. The red LED blinks at a 2


Hz rate for 3 seconds while the reed switch is
closed.

NOTE
If the calibration is not completed within 12
minutes, the calibration will be aborted and the
detector will revert back to the previous calibration
values. The red LED will blink at a 4 Hz rate. The
calibration will be logged as aborted.

9. The communication module records the


uncalibrated value in the first register of the
calibration log and calibrates the span value.
10. The calibration is complete. The calibrate LED
turns off.

Sensor Replacement
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

Pressing the sensor replacement switch aborts the


calibration and starts over.

1. Remove power from the DCU and the PointWatch


unit. Replace the PointWatch. Apply power, then
press the sensor replacement switch on the
communication module for about 1 second. Allow
at least 10 minutes for the sensor to warm up.

IX-6

FALSE ALARM TEST

NOTE
Pressing the sensor replacement switch prevents
the communication module from generating a fault
signal when the input drops to zero. In addition,
the calibration will not be aborted if the calibration
procedure is not completed within 12 minutes.

1. Disable all alarm response equipment.


2. Allow the system to monitor the protected area for a
period of time with all the normal operations in the
area taking place. If the detector responds
(indicating a fire when no fire has occurred), check
the area to see if UV sources are present. If
possible, remove the sources, or reposition the
detectors so that the sources fall outside of the
detectors cone of vision. If problems still occur,
adjust the time delay, sensitivity or arc rejection
settings.

2. Apply zero gas.


3. The calibrate LED on the communication module
blinks at a 1 Hz rate, indicating that it is ready for
the zero input.
4. Continue from step 4 of the PointWatch routine
calibration procedure described above.

The model U7656 Hand-Held UV Monitor is


available from Detector Electronics for conveniently
scanning the protected area and pin-pointing the
exact source of UV radiation.

UV DETECTOR TEST
CAUTION
To prevent unwanted actuation, alarm and
extinguishing devices must be disconnected prior
to performing detection system tests.

3. Recycle power and test again as described above.


4. Once the correct settings are obtained, turn on all
alarm and extinguishing equipment that is
connected to the system. Record all switch settings
for future reference.

FIRE ALARM TEST


1. Disable any extinguishing equipment that is
connected to the system.

UV/IR DETECTOR TEST


IMPORTANT
Disable any extinguishing equipment that is
connected to the system to prevent unwanted
actuation.

2. Apply input power to the system. Allow a one


second power-up delay.
3. Hold a UV source (W8066) within the cone of vision
of the detector at a distance relative to the selected
detection range. Verify that an alarm condition is
indicated at the LCU. Reset the alarm indication
using the key switch on the LCU.

The detector can be tested by shining a UV/IR test lamp


(W867 or W8067) into the detector viewing windows or
by a live fire. (Refer to the test lamp manual for specific
instructions regarding proper use of the device.) This
will cause the detector to go into an alarm condition
the LEDs on the UV sensor will be on steady and the
LCU will indicate an alarm condition. If latching
operation is selected, the detector will remain in this
condition until it is reset at the OIS. If non-latching
operation is selected, the detector will return to normal
operation as soon as the test is terminated (the test
lamp or fire source is removed).

Lack of response may indicate reduced sensitivity


due to contamination on the viewing window, a
damaged sensor, or electronic circuitry or wiring
problems. Refer to Troubleshooting for additional
information.
4. Repeat this test for each fire detector in the system.
5. Verify that all detectors are properly aimed at the
area to be protected.

If a fire signal was not generated and the LEDs indicate


response by only one sensor, the other sensor has
failed to respond.
Check the cleanliness of the viewing window and
repeat the test.
If the sensor fails to respond again, replace the
sensor module.
If the sensor still does not respond, replace the
detector.

6. Enable extinguishing equipment when the test is


complete.

IX-7

95-8470

If a fire signal was not generated and the LEDs indicate


response by neither sensor, both sensors have failed to
respond.
Check input power and external wiring.
Check the cleanliness of both viewing windows.
If the detector still does not respond:
If using a test lamp, check the battery, window, etc.
to be sure that the test lamp is working properly.
If the detector still does not respond, replace the
detector.

IR Fault
To correct an IR oi fault, clean the viewing window and
oi ring of the IR sensor, and also check the module and
oi ring opening for proper orientation. If the fault does
not clear (fault reoccurs), a faulty sensor or electrical
problem is indicated. Check the connection of the
connector plug on the IR module. Also check the
condition of the wires. Repair or replace if needed. If
the problem persists, replace the IR sensor module. If
the problem still persists, replace the detector.

MANUAL oi
General Fault
When manual oi is selected, the automatically initiated
oi test is disabled.

If a general fault is indicated, check input power to the


detector as well as continuity of system wiring. Also
check the detector viewing windows for contamination
such as paint overspray, snow, etc. that could
simultaneously affect both sensors. Since simultaneous
failure of both sensor modules is unlikely, the problem is
most likely caused by loss of input power or failure of
the detectors electronic circuitry.

Regardless of the o i selection, internal diagnostic


circuitry will respond to failures such as a loss of input
power or to certain electronic failures. These failures
will be indicated at the LCU and also by the detectors
LEDs. If such a failure occurs, check the operation of
the power source and the continuity of the detector
wiring. If the detector appears to be dead with power
applied, it must be returned to the factory for repair.

Background Radiation

AUTOMATIC oi

Background radiation as such does not cause a


problem with the detector in most applications, unless
both UV and flickering IR non-fire radiation sources
occur simultaneously. If a UV or IR background
radiation indication occurs:
Determine its cause. The presence of background
radiation could indicate a problem in the protected
area. For example, background IR could be
caused by overheating equipment.
Determine whether or not repositioning the detector
could eliminate response to the background
radiation without reducing coverage of the
hazardous area.

The Automatic oi feature (if selected) tests the detector


at the selected interval (once per minute for UV and
from once a minute to once every four hours for IR),
checking the cleanliness of the optical surfaces, sensor
sensitivity, and proper functioning of the electronic
circuitry. If a problem is detected for three consecutive
automatic oi tests, a fault signal is generated at the
LCU (also indicated by the UV sensor LEDs). If the
detector passes three subsequent automatic oi tests,
the fault signal will be cleared
UV Fault
To correct a UV oi fault, clean the viewing window and
oi ring of the UV sensor, and also check the oi ring
opening for proper orientation. If the fault does not
clear (or fault reoccurs), a faulty sensor or electrical
problem is indicated. First replace the UV sensor
module. If the problem persists, replace the detector.

IX-8

Section X
Specifications

I/O PORTS
The LCU provides two electrically isolated RS-232 serial
ports, port 1 and port 2, both of which can be active
simultaneously. Port 1 can be configured as either a
Modbus RTU slave, or an Allen Bradley DF1 slave. Port
2 can be either a Modbus RTU slave or master.

CERTIFICATIONS
FMRC Approval See Appendix A.
CSA Certification See Appendix B.
CENELEC/ATEX and CE Mark See Appendix C.

Two 78.5 kb LON/SLC ports provide the start and end of


the communication loop for the detection devices. The
wiring is transformer coupled to protect the
transceivers. The LON/SLC is monitored for ground
faults.

EQ2100LCU LOCAL CONTROL UNIT


INPUT VOLTAGE
18 to 30 vdc. 10% overvoltage will not cause damage
to the equipment.
INPUT CURRENT
EQ2100LCU:
0.4 ampere maximum.
EQ2101LCU:
12 amperes maximum.

TEMPERATURE RANGE
Operating:
+32F to +140F (0C to +60C).
Storage:
67F to +185F (55C to +85C).

OUTPUT CURRENT (EQ2101LCU ONLY)


System:
2.8 amperes maximum
(ground fault monitored)
1.8 amperes standby current
2.8 amperes alarm current
Auxiliary:
8.0 amperes maximum
(input power to LIOU auxiliary).

HUMIDITY RANGE
0 to 95% RH, non-condensing.
VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS
See Figure X-1A for dimensions of the standard LCU
mounting configuration. The LCU can also be housed
in a 19 inch mounting rack (000840-xxx), with any
combination of up to 4 logic controllers, 4 gateways and
one isolation module. See Figure X-1B for dimensions.

RELAY OUTPUT RATING


5 amperes resistive at 30 vdc.

9.24 (23.5)

1.48 (3.8)

10.86 (27.6)
10.26 (26.1)

4.00
(10.2)

6.97
(17.7)

12.25
(31.1)

6.50
(16.5)

8.68 (22.0)
A1882

Figure X1ADimensions of LCU in Inches (Centimeters)

X-1

95-8470

TERMINAL
STRIP
REAR

13.2
(33.5)

FRONT

7.0
(17.7)

4.0
(10.2)

FRONT

19.0
(48.3)

DET-TRONICS

DET-TRONICS

POWER

DET-TRONICS

LON INSOLATOR

ALARM
TROUBLE
POWER FAULT

GROUND FAULT
100
90
80
70
60
50
40
30
20
10

SUPERVISORY
RELAY 1
ACKNOWLEGDE
RELAY 2

SILENCE

RELAY 3

PROGRAM

POWER +
POWER

GROUND FAULT
COM 1
COM 2

RELAY 4

ISOLATE

FAULT
RESET
EAGLE QUANTUM
LOGIC CONTROLLER

EAGLE QUANTUM
GATEWAY

EAGLE QUANTUM
LON ISOLATOR

SLOT 2

SLOT 3

NORMAL
ACKNOWLEDGE
& SILENCE
ENABLE

RESET
ISOLATE

B2044

SLOT 1

SLOT 4

SLOT 5

SLOT 6

SLOT 7

Figure X1BDimensions of Model 000840-XXX LCU in Inches (Centimeters)

X-2

SLOT 8

EQ2200IDC/IDCGF/IDCSC
INITIATING DEVICE CIRCUIT

EQ2200UV and EQ2200UVHT UV


FLAME DETECTORS

INPUT VOLTAGE
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.

INPUT VOLTAGE
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.

INPUT POWER
4.0 watts maximum.

INPUT POWER
2.0 watts typical, 4.0 watts maximum during oi test.

INPUTS
Two supervised non-incendive digital inputs (sealed or
unsealed switch or relay contacts). 10 kohm EOL
resistors are required.

TEMPERATURE RANGE

OUTPUTS
Digital communication, transformer isolated (78.5 kbps).

EQ2200UVHT
Electronic Module: 40F to +167F (40C to +75C).
UV Detector:
40F to +257F (40C to +125C).
Storage:
67F to +185F (55C to +85C).

EQ2200UV
Operating:
Storage:

TEMPERATURE RANGE
Operating:
40F to +167F (40C to +75C).
Storage:
-67F to +185F (55C to +85C).

HUMIDITY RANGE
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.

HUMIDITY RANGE
0 to 95% RH, non-condensing.

SPECTRAL SENSITIVITY RANGE


UV radiation over the wavelength of 1850 to 2450
angstroms (solar blind).

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS
See Figure X-2.
0.28
(0.71)

CONE OF VISION
The detector has a 90 degree cone of vision with the
highest sensitivity lying along its central axis. See
Figure X-3.

4.7
(11.8)
3.4
(8.6)

5.2
(13.2)

40F to +167F (40C to +75C).


67F to +185F (55C to +85C).

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.


THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.

2.7
(6.8)

0
15
30

100

15

90

30

80
45

45
70
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)

60
DETECTION
DISTANCE
(PERCENT)

50
40
30

6.6
(16.8)

20
10
D573

Figure X3Cone of Vision of UV Detector


1.28
(3.25)
B2045

Figure X2Dimensions of Tall Cover Junction Box


in Inches (Centimeters)
X-3

95-8470

FLAME SENSITIVITY
The detector has four adjustable sensitivity settings plus
transient arc rejection capabilities.

5/16-18 UNC

DETECTOR LOCK NUT

RESPONSE TIME
The detector is selectable for a 0 to 7 second time
delay.

1 3/8 INCH GLAND NUT


USED TO ROTATE
SWIVEL/DETECTOR ASSEMBLY
TO DESIRED POSITION
2.5
(6.4)

OUTPUTS
Digital communication, transformer isolated (78.5 kbps).
MOUNTING BASE

SEPARATION DISTANCE (EQ2200UVHT only)


Maximum separation distance between the UV detector
and the electronic module is 165 feet (50 meters).

2.5
(6.4)

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.

2.0 (5.08) DIA.


120 2 (2)

DIMENSIONS
See Figures X-4A and X4B for the standard UV
detector. For the high temperature UV detector, see
Figures X-5A and X-5B (UV detector) and Figure X-6
(electronic module).
2.5 (6.4) DIA.

DETECTOR SCREWS ONTO


SWIVEL MOUNT HERE

A1986

0.25 (0.64) DIA. (3)

Figure X5AQ9001B Swivel Mounting Bracket Dimensions


in Inches (Centimeters)

3/4 INCH NUT USED TO SECURE


DETECTOR TO SWIVEL MOUNT
1/2 INCH NUT USED TO ADJUST
ELBOW TO DESIRED ANGLE

5.25 (13.3)

1/2 INCH NPT


OR 20 MM

4.75 (12.06)

1-3/8 INCH NUT USED TO ROTATE


SWIVEL/DETECTOR ASSEMBLY
TO DESIRED POSITION

2.5
(6.35)

MOUNTING BASE
2.5 (6.4)
A1987

Figure X5BUV Detector Dimensions


in Inches (Centimeters)
120 2 (2)

0.25 (.64) (3)

2.0 (5.0) DIA.


A1886

2.5 (6.4) DIA.

Figure X4ADimensions of Optional Swivel Assembly


in Inches (Centimeters)

X-4

COVER LOCKING CLAMPS (BASEEFA)


9 (228.6)

5
(127)

2.5
(63.5)

4
(101.6)

4.375
(111.1)

CONDUIT/CABLE ENTRY (2)


A1844

4.5 (114.3)

Figure X4BDimensions of EQ2200UV Detector in Inches (Millimeters)

0.28
(0.71)

4.66
(11.8)
3.39
(8.6)

5.20
(13.21)

2.69
(6.83)

0.32 (0.81) OVAL SLOT MOUNTING


(TYPICAL FOUR PLACES)

6.62
(16.8)

1.28
(3.25)
A1887

Figure X6 EQ2200UVHT Junction Box Dimensions


in Inches (Centimeters)

X-5

95-8470

EQ2200UVIR UV/IR DETECTOR

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.


THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.
0

INPUT VOLTAGE
24 vdc nominal, 18 to 30 Vdc. 10% overvoltage will not
cause damage to the equipment.

15

15

100

30

30

90
80

45

45

INPUT POWER
2.0 watts nominal, 5.0 watts maximum during oi test.

70
60
DETECTION
DISTANCE
(PERCENT)

TEMPERATURE RANGE
Operating:
40F to +167F (40C to +75C).
Storage:
40F to +185F (40C to +85C).

50
40
30
20

HUMIDITY RANGE
0 to 95% RH. Can withstand 100% condensing
humidity for short periods of time.

10
D573

Figure X8Cone of Vision of UV/IR Detector

SPECTRAL SENSITIVITY RANGE


UV:
0.185 to 0.245 microns (solar blind).
IR:
4.45 microns (solar blind).
Figure X-7 illustrates the spectral response range of the
UV and IR sensors.

RESPONSE TIME
Selectable for a 0 to 7 second time delay. Fastest
response time is 0.5 second.

CONE OF VISION
90 degree cone of vision using gasoline fuel (1 sq. ft).
80 degree cone of vision using methane fuel (30 inch).
See Figure X-8.

OUTPUTS
Digital communication, transformer isolated (78.5 k
bps).

FLAME SENSITIVITY
Refer to Tables X-1 and X-2 for typical detector
response characteristics.

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.
ENCLOSURE MATERIAL
Copper-free aluminum (red) or 316 stainless steel, with
stainless steel mounting bracket.

CAUTION
The detector is extremely sensitive when the very
high setting is utilized. While this setting is
required to reliably detect certain types of fires,
care must be taken to minimize the possibility of
false alarms.

DIMENSIONS
See Figures X-9 and X-10.

VISIBLE

ULTRAVIOLET

INFRARED

100
75
ATMOSPHERIC
TRANSMISSION

50
25
0
0.1

0.2

0.3

0.4

0.5

0.6 0.7 0.8 0.9 1.0

1.5

2.0

3.0

4.0

5.0

WAVELENGTH (MICRONS)
ULTRAVIOLET
SENSOR
RESPONSE

INFRARED
SENSOR
RESPONSE

SOLAR
RADIATION
REACHING
THE EARTH

A1070

Figure X7Sensitivity Range of UV/IR Detector

X-6

Table X1UV/IR Detector Maximum Response Distances in Feet

Sensitivity
UV Standard

Low
Medium
High
Very High

UV Arc
Rejection

Low
Low
Medium
Medium
High
High
Very High
Very High

IR

Low
Medium
High
Very High

Arc Rejection

30 inch Methane

1 Ft x 1 Ft Gasoline

1 Ft x 1 Ft Methanol

40
60
80
100

30
45
65
100

15
20
35
55

35
35
55
55
60
65
85
85

30
30
40
40
50
50
65
65

10
10
15
15
25
25
50
50

40
55
65
90

65
75
90
100

40
45
55
60

Medium
High
Medium
High
Medium
High
Medium
High

Typical response time less than 5 seconds.


NOTE: Sensitivity level determines maximum response distance and is selected for UV and IR sensors individually (selected
through the configuration software). The maximum response distance for the UV/IR detector is the lesser of the two.

Table X2Recommended Settings for JP-4, 5, 8 Fires

Fuel

Size

Distance

UV

IR

JP4
JP5
JP8

3 Ft x 3 Ft
3 Ft x 3 Ft
3 Ft x 3 Ft

150 Ft.
150 Ft.
150 Ft.

Very High
High
Very High

High
High
Medium

JP4
JP5
JP8

2 Ft x 2 Ft
2 Ft x 2 Ft
2 Ft x 2 Ft

100 Ft.
100 Ft.
100 Ft.

High
High
High

Medium
Medium
Medium

Typical response time less than 5 seconds.

X-7

95-8470

JUNCTION BOX MOUNTING


BRACKET (ATTACHES
WITH TWO ENCLOSED
FLATHEAD SCREWS)
3/4 INCH NUT USED TO
SECURE DETECTOR
BRACKET TO SWIVEL MOUNT
1/2 INCH NUT USED TO ADJUST
ELBOW TO DESIRED ANGLE

5-1/4 INCHES
(133 MM)

1-3/8 INCH NUT USED TO ROTATE


SWIVEL/DETECTOR ASSEMBLY
TO DESIRED POSITION

MOUNTING BASE
2-1/2 INCHES
(64 MM)

B1303

120 2 (2)

0.25 (6.4 MM)


DIA. (3)

2.00 (50.8 MM) DIA.


21/2 (64 MM) DIA.

B1303

Figure X9Q9001G Swivel Mounting Bracket Dimensions

3.38 (85.8 MM)

7.11 (181 MM)

2.5 DIA.
(64 MM)

7.81
(198 MM)
5.25
(133 MM)

C1047

CONDUIT ENTRY 3/4 NPT OR 25 MM

Figure X10UV/IR Detector Dimensions in Inches (Millimeters)

X-8

EQ2200DCU AND EQ2200DCUEX


DIGITAL COMMUNICATION UNIT

EQ2500ARM AGENT RELEASE


MODULE

INPUT VOLTAGE
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.

RELEASE OUTPUT RATING


2 amperes at 30 vdc maximum.
SUPERVISORY CURRENT
2.0 ma, 1.0 ma each circuit.

POWER CONSUMPTION
DCU with toxic gas sensor/transmitter:
95 ma maximum.

INPUT VOLTAGE
24 vdc nominal.

DCU with transmitter and combustible gas sensor:


180 ma maximum during normal operation, 500 ma
during startup.

INPUT CURRENT
Standby:
75 ma maximum at 24 vdc.
Alarm:
120 ma maximum at 24 vdc.

INPUTS
4 to 20 ma analog signal.
Non-intrusive calibration.

STATUS OUTPUTS
Digital communication, transformer isolated (78.5 kbps).

OUTPUTS
Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE
Operating:
40F to +167F (40C to +75C).
Storage:
67F to +185F (55C to +85C).

TEMPERATURE RANGE
Operating:
40F to +167F (40C to +75C).
Storage:
67F to +185F (55C to +85C).

HUMIDITY RANGE
5 to 95% RH, non-condensing.

HUMIDITY RANGE
0 to 95% RH, non-condensing.

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.

DIMENSIONS
See Figure X-2.

DIMENSIONS
See Figure X-2.

X-9

95-8470

EQ2500SAM SIGNAL AUDIBLE


MODULE

EQ2400NE NETWORK EXTENDER


INPUT VOLTAGE
18 to 30 Vdc.

OUTPUT RATING
2 amperes at 30 vdc maximum.

POWER CONSUMPTION
2.2 watts nominal at 24 vdc, 2.7 watts maximum.

RESPONSE TIME
Output relay actuates in <0.1 second after
acknowledging an alarm command message.

INPUTS/OUTPUTS
Digital, transformer isolated (78.5k Baud).

SUPERVISORY CURRENT
3.0 ma 2.0ma, each circuit.

TEMPERATURE RANGE
Operating:
-40F to +167F (-40C to +75C)
Storage:
-67F to +185F (-55C to +85C).

EOL RESISTORS
10 kohm 2 kohm. Each circuit must have an EOL
resistor.

HUMIDITY
5 to 95% RH at 70C.

INPUT VOLTAGE
24 vdc nominal.

DIMENSIONS
See Figure X-11.

INPUT CURRENT (Excluding Output Current)


Standby:
60 ma maximum at 24 vdc.
Alarm:
120 ma maximum at 24 vdc.

0.28
(0.71)

4.66
(11.8)
3.39
(8.6)

STATUS OUTPUT
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE
Operating:
40F to +167F (40C to +75C).
Storage:
67F to +185F (55C to +85C).
HUMIDITY RANGE
5 to 95% RH, non-condensing.
5.20
(13.21)

2.69
(6.83)

VIBRATION
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS
See Figure X-2.

0.32 (0.81) OVAL SLOT MOUNTING


(TYPICAL FOUR PLACES)

3.7
(9.4)

1.28
(3.25)
A1883

Figure X11Dimensions of Short Cover Junction Box


in Inches (Centimeters)

X-10

EQ2100PSM POWER SUPPLY


MONITOR

EQ2110PS, EQ2130PS AND


EQ2175PS POWER SUPPLIES

INPUT VOLTAGE
24 vdc nominal, 18 to 30 Vdc.

INPUT VOLTAGE
Selectable for 120, 208 or 240 vac input power, 10%.

POWER CONSUMPTION
2.0 watts maximum.

INPUT FREQUENCY
60 Hz 5% standard, 50 Hz 5% optional.

MEASUREMENT RANGE
AC Voltage:
DC Battery Charging Current:

INPUT CURRENT
EQ2110PS: 4 amps at 120 VAC (60 Hz)
EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 VAC*
EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 VAC*.
*Specify 50 Hz or 60 Hz.

240 vac maximum.


75 amperes maximum.

OUTPUT
Digital communication, transformer isolated (78.5 k
bps).

OUTPUT CURRENT
EQ2110PS:
10 amperes at 24 VDC
EQ2130PS:
30 amperes at 24 VDC
EQ2175PS:
75 amperes at 24 VDC.

TEMPERATURE RANGE
Operating: +32F to +122F (0C to +50C)
Storage:
-67F to +185F (-55C to +85C).

POWER CONSUMPTION
EQ2110PS:
46 Watts
EQ2130PS:
140 Watts
EQ2175PS:
349 Watts.

HUMIDITY RANGE
5 to 95% RH, non-condensing.
DIMENSIONS
See Figure X-12.

TEMPERATURE RANGE
Operating: +32F to +122F (0C to +50C)
Storage:
-40F to +185F (-40C to +85C).
HUMIDITY RANGE
5 to 95% RH, non-condensing.

9
(22.9)
8.5
(21.6)

J3

J1

DIMENSIONS
in Inches (Centimeters)
Width
EQ2110PS:
19 (48.3)
EQ2130PS:
19 (48.3)
EQ2175PS:
19 (48.3)

2.25
(5.7)
4
(10.2)

Height
7 (17.8)
14 (35.6)
14 (35.6)

Depth
15 (38.1)
15 (38.1)
15 (38.1)

NOTE
Power supplies are designed for mounting in a
standard 19 inch rack. Optional mounting hardware
is available for floor or wall mount applications.

2.5
(6.4)

A2038

Figure X12Dimensions of Power Supply Monitor


in Inches (Centimeters)

X-11

95-8470

LIOU (Local Output Unit)

LIOU RELEASE MODULE

INPUT VOLTAGE
24 vdc nominal.

RELEASE OUTPUT RATING


2 amperes at 24 vdc.

INPUT POWER
30 watts maximum.

SUPERVISORY CURRENT
2.5 ma, each circuit.

MODULES PER SYSTEM


24 maximum.

SIGNAL OUTPUT RATING


2 amperes at 24 vdc.

TEMPERATURE RATING
Operating:
+32F to +120F (0C to +50C).
Storage:
67F to +185F (55C to +85C).

MODULES PER SYSTEM


8 maximum.
OUTPUTS PER SYSTEM
32 maximum.

HUMIDITY RANGE
0 to 95% RH, non-condensing.
VIBRATION
Meets FMRC Class number 3260 requirements.

LIOU SIGNAL AUDIBLE MODULE


OUTPUT RATING
2 amperes at 24 vdc

DIMENSIONS
See Figures X-13 and X-14.

WIRING STYLES
NFPA Four Style Y or Two Style Z circuits.

LIOU RELAY MODULE


MODULES PER SYSTEM
8 maximum.

CONTACT RATING
2 amperes at 24 vdc.

OUTPUTS PER SYSTEM


32 maximum.

MODULES PER SYSTEM


8 maximum.

10.25
(26)

OUTPUTS PER SYSTEM


32 maximum.

12.0
(30.5)

9.6
(24.4)

6.0
(15.2)

14.25
(36.2)

13.6
(34.6)

16.0
(40.6)

A1695

Figure X13Dimensions of LIOU Enclosure in Inches


A2037

Figure X14Dimensions of LIOU Mounting Plate


in Inches (Centimeters)

X-12

COMBUSTIBLE GAS SENSOR


Refer to the Combustible Gas Sensor Specification Data
sheet, form 90-1041, for specifications.

ELECTROCHEMICAL SENSORS
Refer to the Electrochemical Gas Sensor Specification
Data sheet, form 90-1079, for specifications.
Electrochemical sensors available from Det-Tronics
include Hydrogen Sulfide, Oxygen, Carbon Monoxide,
Chlorine, Sulfur Dioxide, and Nitrogen Dioxide.

POINTWATCH
Refer to the PointWatch manual, form 95-8440, for
PointWatch specifications.

X-13

95-8470

Section XI
System Maintenance

FLAME DETECTOR MAINTENANCE


The flame detector requires no periodic calibration.
However, to maintain maximum sensitivity, the viewing
window must be kept clean at all times.

ROUTINE MAINTENANCE
To ensure reliable protection, it is important to check
and calibrate the system on a regularly scheduled
basis. The frequency of these checks is determined by
the requirements of the particular installation.

To clean the optical surfaces, remove the oi ring from


the detector by gently squeezing the tabs together and
then pulling out. Clean the viewing window and the
back side of the oi ring using a clean cloth or tissue
and Det-Tronics window cleaning solution. Avoid the
use of commercial glass cleaners, since many of them
can leave a UV absorbing residue on the surface.
Avoid leaving fingerprints on the reflective surface of the
o i ring. Re-install the ring so that the opening is
positioned downward.

MANUAL CHECK OF OUTPUT DEVICES


It is important that response devices be checked initially
when the system is installed, as well as periodically
during the on-going maintenance program.
CAUTION
Be sure to secure all output devices that are
actuated by the system to prevent unwanted
activation of this equipment, and remember to
place these same output devices back into service
when the checkout is complete.

NOTE
If corrosive contaminants in the atmosphere cause
the reflective rings to deteriorate to the extent that
it is no longer possible to restore them to their
original condition, they must be replaced.
To ensure the watertight integrity of the detector, the Orings must be maintained following the guidelines
described above.

O-RING MAINTENANCE
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.

GAS SENSOR MAINTENANCE


All gas sensors must be calibrated on a regularly
scheduled basis, typically every 90 days for catalytic
and electrochemical sensors and annually for
PointWatch.

A rubber O-ring is used to ensure that the junction box


cover will seal tightly and provide protection against
water ingress. Periodically the enclosure should be
opened and the O-ring should be inspected for breaks,
cracks and dryness. To test the ring, remove it from the
enclosure and stretch it slightly. If cracks are visible, it
should be replaced. If it feels dry, a thin coating of
lubricant should be applied. When re-installing the ring,
be sure that it is properly seated in the groove on the
housing. It is imperative that this O-ring be properly
installed and in good condition. Failure to properly
maintain it can allow water to enter the enclosure and
cause premature failure. A coating of lubricant should
also be applied to the threads on the cover before reassembling the enclosure. This will both lubricate the
threads and help to prevent moisture from entering the
enclosure.

Catalytic sensors have a finite lifespan. If a successful


calibration cannot be performed, replace the sensor
and recalibrate following the procedure described in the
Calibration section. Exposure of the sensor to high
concentrations of combustible gases for extended
periods of time can introduce stress to the sensing
element and seriously affect its performance. After
exposure to a high concentration of combustible gas,
recalibration should be performed and, if necessary, the
sensor should be replaced.
Electrochemical sensors have a finite lifespan. If a
successful calibration cannot be performed, inspect the
hydrophobic filter. If the filter is plugged, replace it and
recalibrate the sensor. If the filter is in good condition,
replace the sensor. Recalibrate following the procedure
described in the Calibration section.

CAUTION
The O-rings should be lubricated with a silicone
free grease. The use of other lubricants is not
recommended, since they can adversely affect the
performance of some sensors. Under no
circumstances should a lubricant or compound
containing silicone be used on systems using
catalytic type combustible gas sensors.

If the PointWatch fails calibration, refer to the


PointWatch manual.
NOTE
Compare part numbers to be sure that the correct
replacement sensor is being used.
XI-1

95-8470

for proper wiring, programming and calibration. If it is


determined that the problem is caused by an electronic
defect, the device must be returned to the factory for
repair.

BATTERIES
Batteries must be replaced every 48 months, or sooner
if required by local codes. Only sealed batteries are to
be used.

NOTE
When replacing a device, be sure that the rocker
switches on the replacement are set the same as
the original. Remove power before removing or
plugging in the replacement unit. When a DCU,
IDC or flame detector is replaced, the point must
be re-configured. If the auto-configure feature is
enabled, configuration is done automatically.

TROUBLESHOOTING
Table XI-1 is intended to serve as an aid in locating the
cause of a system malfunction. If the problem cannot
be corrected, contact the factory for assistance.

REPLACEMENT PARTS
Eagle devices are not designed to be repaired in the
field. If a problem should develop, first carefully check

Table XI-1Troubleshooting Guide

Symptom

Possible Cause

Gateway Green Power LED is off.

Power wiring is wrong.

Gateway Fault LED is on and F30 is displayed.

An open in the LON wiring. This can also be caused by


a device that has isolated a short on the LON. Press
the Gateway reset switch after the LON is repaired to
clear the fault.

Gateway Fault LED is on and F40 is displayed.

The external or faceplate reset switch is held closed.

Gateway Fault LED is on and F50 or F51 is displayed.

A fault was detected on one of the LON communication


boards. Replace the gateway.

Gateway Fault LED is on and F60 is displayed.

The gateway was not configured using the OIS


software.

No communication with the host computer.

Wrong communication parameters (check the gateway


DIP switches), or communication wiring.

Logic Controller Fault LED is on.

See Logic Controller table (Table II-3).

Logic Controller Power Fault LED is on.

Power related fault.

Logic Controller Supervisory LED is on.

A field device programmed as a supervisory input is


active.

The Gateway displays F10 for a field device.

This is caused by a problem with the field device input.


Check for wiring or sensor faults.

The Gateway displays F20 for a field device.

The field device is not reporting or communication fault.


Check power and LON wiring. Check that the device
address is set properly.

The Gateway displays F60 for a field device.

The device configuration needs to be downloaded


using the OIS software.

EQ22xxUV Detector LEDs not blinking.

Dirty viewing window.


oi ring dirty, misaligned or missing.
Input voltage too low.
Internal high voltage out of tolerance.
Open, shorted or incorrect wiring.
Device not configured.

EQ22xxUV Detector does not respond to fire stimuli or to


manual oi test.

Dirty viewing window.


Insufficient supply voltage.
Open, shorted or incorrect wiring.
Defect in UV module.
Defect in electronic module.
T0025B

XI-2

DEVICE REPAIR AND RETURN

Table XI-2Combustible Gas Sensors

Prior to returning devices or components, contact the


nearest local Detector Electronics office so that a
Service Order number can be assigned. A written
statement describing the malfunction must accompany
the returned device or component to expedite finding
the cause of the failure.
Pack the unit or component properly. Use sufficient
packing material in addition to an antistatic bag or
aluminum-backed cardboard as protection from
electrostatic discharge.

OS Number

Part Number

Replaces

CGSS1A6C2R1X

006824-001

225006-004
225957-002
226530-003
226531-003
226931-005
226931-006
226999-011
226999-012

3/4 inch

6 inch

CGSS1A3C2R1X

006824-005

225006-003
226530-005
226531-004
226931-007
226931-008

3/4 inch

30 inch

CGSS1C6C2R1X

006824-003

226999-008
226999-020
226999-014
226999-021

20 mm

6 inch

CGSS1C3C2R1X

006824-007

226999-015

20 mm

30 inch

Return all equipment transportation prepaid to the


factory in Minneapolis.

Threads Wire Length

T0043A

ORDERING INFORMATION
POWER SUPPLIES
When ordering, please specify:
Part Number
006979-001
000604-013
000604-014
000604-015

LCU
Part Number
006814-001

Description
EQ2100LCU Local Control Unit for
use with EQ21XXPS Series Power
Supplies.
LCU Replacement Parts:
006570-001
EQ2100CG Communication Gateway
006566-001
EQ2100LC Logic Controller
006558-001
EQ2100IM Isolation Module
006668-001
EQ2100MR Mounting Rack

COMBUSTIBLE GAS SENSORS


See Table XI-2.
H2S SENSOR
Part Number
004539-009
005434-001

LIOU
Part Number
006641-xxx
102844-001
102843-001
102842-001

Description
EQ2100LIOU Local Input/Output Unit
Relay Module
Release Module
Signal Audible Module

006600-xxx
007082-xxx
006861-xxx
006607-xxx
006733-xxx
006738-xxx
006941-xxx
0083xx-xxx
0085xx-xxx

Description
Explosion-Proof H2S Sensor Housing
Electrochemical H2S Sensing
Element Assembly

Other toxic gas sensors available. Consult the factory.


ACCESSORIES
Part Number
102868-001
102740-001
226365-113

LON DEVICES
Part Number
006608-xxx
006943-xxx
007257-xxx

Description
EQ2100PSM Power Supply Monitor
EQ2110PS Power Supply (10 amps)
EQ2130PS Power Supply (30 amps)
EQ2175PS Power Supply (75 amps)

Description
EQ22XXIDC Initiating Device Circuit
EQ22XXIDCGF Ground Fault Monitor
EQ22XXIDCSC Initiating Device
Circuit Short Circuit
EQ22XXUV UV Flame Detector
EQ22XXUVHT High Temp. UV Detector
EQ22XXUVIR UV/IR Flame Detector
EQ22XXDCU DCU (specify gas)
EQ25XXARM Agent Release Module
EQ25XXSAM Signal Audible Module
EQ24XXNE Network Extender
X2200xxx24 UV Flame Detector
X5200xxx24 UV/IR Flame Detector

226365-104
006414-001
226349-001
225312-001
226190-001
226354-001

Description
Silicone Free Grease
Calibration Magnet
Sensor Separation Kit for Catalytic
Sensors
Sensor Separation Kit for
Electrochemical Sensors
Sensor Separation Kit for PointWatch
Sensor Rain Shield
Sensor Dust Cover (Stainless Steel)
Sensor Dust Cover (Porex)
Splash Guard

Other accessories are available. Consult the factory.

XI-3

95-8470

CALIBRATION KITS COMBUSTIBLE GAS

Accessories and Replacement Parts

Part Number
225130-001
225130-002
225130-003
225130-004
225130-005
225130-006
225130-007
225130-008

Part Number
004273-002
004483-001
004404-005
003240-202
006598-001
002507-001
002519-001
107427-040
107427-004

Gas
Methane (50% LFL)
Ethane (50% LFL)
Ethylene (50% LFL)
Propane (50% LFL)
Hydrogen (50% LFL)
Methane (20% LFL)
Methane (25% LFL)
Methane (35% LFL)

Description
Q1113 Air Shield Assembly
W8066 UV Test Lamp
Swivel Mount
Sensor Module
Electronic Module
Window cleaner kit
oi Ring
O-Ring (large)
O-Ring (small)

REPLACEMENT CYLINDERS
UV DETECTOR High Temperature
Part Number
226166-001
226166-002
226166-003
226166-004
226166-005
226166-006
226166-007
226166-008
226166-009

Gas
Methane (50% LFL)
Ethane (50% LFL)
Ethylene (50% LFL)
Propane (50% LFL)
Hydrogen (50% LFL)
Air (0% LFL)
Methane (20% LFL)
Methane (25% LFL)
Methane (35% LFL)

007082-xxx
006899-xxx

EQ22XXUVHT Hi Temp UV Flame


Detector Electronic Module Assembly
C7050B Hi Temp UV Detector

One electronic module assembly and one high


temperature UV detector are required for each
detection point. Both units must be ordered separately.
Specify material (aluminum or stainless steel) and
conduit entry size (3/4 inch NPT or 25/20 MM) for each.

REPLACEMENT PARTS FOR CALIBRATION KIT

Accessories and Replacement Parts

Part Number
162552-001
101678-007
004976-001
225777-001

Part Number
006598-002
003240-221
107427-004
002099-003
004404-002

Description
Regulator
3 foot hose
Standard calibration cup
Modified calibration cup (for sensor
separation)

Description
Electronic Module
DE1888K3 UV Sensor Module
O-Ring for UV Detector
Mounting Bracket (Aluminum)
Mounting Bracket (Stainless Steel)

H2S CALIBRATION KIT

UV/IR DETECTOR

227115-001

006861-xxx

H 2 S Calibration Kit (for electrochemical sensors only) includes


regulator, hose, calibration cup, and
two cylinders of calibration gas.

Accessories and Replacement Parts


Part Number
004404-001
004273-002

REPLACEMENT PARTS H2S


Part Number
005434-001
004532-002
107427-034
107427-004
227117-001

Description
Electrochemical Sensing Element
Assembly for H2S Sensor
Hydrophobic Filter for H2S Sensor
O-ring (for Hydrophobic Filter)
O-ring (for Sensor Housing)
Gas Bottle for 227115-001 Calibration
Kit - 50 ppm

004000-003
002519-001
003525-001
107427-004
DE1888B2
DE5600-002

UV DETECTOR
006600-xxx

EQ22XXUVIR UV/IR Flame Detector

001680-001
003996-001

EQ22XXUV UV Flame Detector

102868-001
XI-4

Description
Q9001G Swivel Mount Assembly
Q1113 Air Shield Assembly (two per
detector)
W867 Explosion-proof UV/IR Test
Lamp
oi ring for UV detector
oi ring for IR detector
O-rings for UV and IR detectors (two
O-rings per detector)
UV sensor module with LEDs
IR module with LEDs (standard
sensitivity)
Window Cleaner (six bottles)
UV/IR Window Maintenance Kit,
consisting of 2 bottles of
cleaner, 4 UV rings, 4 IR rings
Silicone Free Grease

APPENDIX A

FM Approvals
The Eagle Quantum Fire and Gas Detection/Releasing System (reference Figure A1) has the following FM approved
configurations:

Model EQ2100LCU Series Local Control Unit


(Up to four EQ2100LC, four EQ2100CG and one EQ2100IM for maximum system.)
Nonincendive for Class I, Division 2, Groups A, B, C, and D; temperature code T4A Hazardous (Classified)
Locations per FM 3611.
Operating Temperature Limits 0C to +60C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6320.
H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FM requirements.
NOTE
FM Approval allows the presence and operation of serial communications software in the LCU Gateway
(MODBUS or Allen Bradley protocols, etc.), however, the communications functions are not included in the
Approval.

MODEL EQ2175PS, EQ2130PS, and EQ2110PS POWER SUPPLies with MODEL EQ2100PSM SERIES
POWER SUPPLY MONITOR
Ordinary Locations verified per FM 3820.
Operating Temperature Limits 0C to +50C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

A-1

95-8470

Model EQ2100LIOU Local Input/Output Unit


Ordinary Locations verified per FM 3820.
Operating Temperature Limits 0C to +50C.
Storage Temperature Limits 55C to +85C.
Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
Approved for use with the following automatic deluge and pre-action solenoids:
Manufacturer Model
Skinner
LV2LBX25
ASCO
8210A107
ASCO
8210G207
Skinner
73218BN4UNLVNOC111C2
Skinner
73212BN4TNLVNOC322C2
Skinner
71395SN2ENJ1NOH111C2

Model EQ2200IDC Series Initiating Device Circuit and


Model EQ2200IDCGF Series Initiating Device Circuit Ground Fault
Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
EQ22EMIDC and EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A
Hazardous (Classified) Locations per FM 3611.
Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
The Model EQ2200IDC Series must be used in conjunction with any FM Approved device providing relay contact
closure.

Models X2200xxx24 and X5200xxx24 Flame Detectors


Refer to manual 95-8549 for the Model X2200xxx24 Series and manual 95-8546 for the Model X5200xxx24 Series
flame detector detail.
15 seconds maximum response time.

A-2

Model EQ2200DCU Series Digital Communication Units


Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615 (For use with Sensor Termination Box).
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations
per FM 3611.
Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)
Locations per FM 3611. (For use with sensor termination box.)
EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Termination Box).
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Combustible gas performance verified with any FM Approved stand alone linear 4 to 20 mA device per FM
6310/6320. Accuracy: 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL.
Toxic gas performance verified 0 to 100 ppm per FM requirements. Accuracy: 2 ppm from 0 to 20 ppm, 10% of
concentration from 21 to 100 ppm. Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S) Sensors
Explosion-proof for Class I, Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model
C7064E5014 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous
(Classified) Locations per FM 3615. Operating temperature limits are 40C to +40C.
NOTE
Sensor cross sensitivity has not been verified by FM.
NOTE
FM Approval of the 4 to 20 ma input does not include or imply approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain FM Approval of the system, all 4
to 20 ma gas detection instruments connected to the input must also be FM Approved.

A-3

95-8470

Model EQ2200DCUEX Series Digital Communication Unit


with Model CGS series Combustible Gas Sensor
Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615. (For use with Sensor Termination Box)
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations
per FM 3611.
Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)
Locations per FM 3611. (For use with sensor termination box.)
EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Termination Box).
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320. Accuracy: 3% LFL from
0 to 50% LFL, 5% LFL from 51% to 100% LFL.
NOTE
The high temperature characteristic has NOT been FM verified above 75C.
NOTE
Detector Electronics combustible gas detection K factors are not FM verified.
Sensor Termination box
226365-106
226365-113
226365-104

Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector


Combustible, Aluminum, 3/4 inch NPT, Wiring Harness
Toxic, Aluminum, 3/4 inch NPT

Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
NOTE
Ensure sensor hazardous (classified) location rating is applicable for the intended use.

A-4

Model EQ2500ARM Series Agent Release Module


Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
Approved for use with the following automatic deluge and pre-action solenoids:
Manufacturer Model
Skinner
LV2LBX25
ASCO
8210A107
ASCO
8210G207
Skinner
73218BN4UNLVNOC111C2
Skinner
73212BN4TNLVNOC322C2
Skinner
71395SN2ENJ1NOH111C2

Model EQ2500SAM Series Signal Audible Module


Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.

A-5

95-8470

MODEL EQ2400NE SERIES NETWORK EXTENDER


Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615.
Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM 3615.
Non-incendive for Class I, Div. 2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous (Classified)
Locations per FM 3611.
Enclosure Rating NEMA / Type 4X per ANSI/NEMA 250.
Operating Temperature Limits -40C to +75C.
Storage Temperature Limits -55C to +85C.
Relative Humidity Range: 5 to 95% RH.
National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996 and gas performance verified per FM
6310/6320.

OPTIONS
An optional EQ2101LCU with EQ2101MR Mounting Rack is available with provisions for two 24 vdc power inputs.
The customer must supply two reliable and independent 24 vdc supplies in accordance with ANSI/NFPA 72-1996
section 1-5.2. If either of the supplies is missing due to a broken wire, a trouble condition will be annunciated.
Operator Interface Station (OIS)
NOTE
Metric straight thread types are for use in non-North American applications.

CALIBRATION
Calibration of the above listed sensors has been FM verified using the respective EQ2200DCU and EQ2200DCUEX
Series with the Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.
The EQ2200DCU Series can be used with any FM Approved 4 to 20 ma device.

A-6

SUITABLE NRTL LABELED


NEMA RATED ENCLOSURE

EQ2100LIOU SERIES
LOCAL INPUT/OUTPUT UNIT
(006692-001)
NOTE:
24 OUTPUT MODULES MAXIMUM.

6 WARNING: ENSURE SENSOR HAZARDOUS (CLASSIFIED) LOCATION


RATING IS APPLICABLE FOR THE INTENDED USE.

8. PART NUMBERS IN PARENTHESIS DEFINE DESIGN REFERENCE DRAWING


ASSOCIATED WITH A DEVICE UNLESS OTHERWISE SPECIFIED.

1. FM APPROVED DRAWING - NO MODIFICATIONS PERMITTED


WITHOUT REFERENCE TO FM.

2 WHERE THE PRIMARY POWER IS SUPPLIED BY A DEDICATED BRANCH


CIRCUIT OF AN EMERGENCY SYSTEM IN ACCORDANCE WITH NFPA 70,
NATIONAL ELECTRICAL CODE, ARTICLE 700, OR A LEGALLY REQUIRED
STANDBY SYSTEM IN ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL
CODE, ARTICAL 701, A SECONDARY SUPPLY SHALL NOT BE REQUIRED.

3 WHERE THE PRIMARY POWER IS SUPPLIED BY A DEDICATED BRANCH


CIRCUIT OF AN OPTIONAL STANDBY SYSTEM IN ACCORDANCE WITH
NFPA 70, NATIONAL ELECTRICAL CODE, ARTICAL 702, WHICH ALSO MEETS
THE PERFORMANCE REQUIREMENTS OF ARTICAL 700 OR ARTICAL 701,
A SECONDARY SUPPLY SHALL NOT BE REQUIRED.

4 OVERCURRENT PROTECTION MUST BE IN ACCORDANCE


WITH NFPA 72-1996, CLAUSE 1-5.2.9.3.

5 NO MODIFICATIONS ARE PERMITTED ON


NRTL LABELED NEMA RATED ENCLOSURE(S).

<20 FT

OPTIONAL OPERATOR INTERFACE STATION

BATTERY
BACK-UP

SUITABLE METALLIC NRTL LABELED


NEMA RATED ENCLOSURE

FM APPROVED NOTIFICATION APPLIANCE OR


SUPPRESSION ACTUATOR
INSTALL PER
NFPA 70 & 72

EQ2100LCUPS SERIES

LOCAL CONTROL UNIT


POWER SUPPLY
(006691-001)

9 FM APPROVED FLAME DETECTOR WITH RELAY OUTPUT MAY BE USED.

BATTERY
BACK-UP

SUITABLE METALLIC NRTL LABELED


NEMA RATED ENCLOSURE

EQ2100PSM SERIES
POWER SUPPLY MONITOR
(006982-001)

006974-001

F1=50mA

(006691-001)

OR

ORDINARY LOCATIONS
(Tamb = 0C to +50C)

EQ2110PS, EQ2130PS OR
EQ2175PS POWER SUPPLY

F2=50mA

A-7

95-8470

DET
TRONICS

RESET

PROGRAM

TM

DET
TRONICS

18 - TOXIC
19 - O2

01 - Ex
02 - H2S
03 - CL2
04 - CO
05 - NH3
06 - S02
07 - HCL
08 - HCN

GAS

RELAY 4

10

20

30

40

50

60

70

80

90

100

TM

FAULT

FLAME

60 - OTHER

40 - OIL ON WATER
41 - PW HEAVY
42 - PW TOTAL
43 - PW BENZENE
44 - PW LOW SENS

ENVIRONMENTAL

20 - UV
21 - IR
22 - UV/IR

TYPE CODE

EAGLE QUANTUM
GATEWAY

RESET

RELAY 3

RELAY 2

RELAY 1

ADDRESS
TYPE
PERCENT

COMMUNICATIONS GATEWAY

DET
TRONICS
LON ISOLATOR

EAGLE QUANTUM
LON ISOLATOR

LON 1

LON 0

GROUND FAULT

POWER -

POWER +

GROUND FAULT

TM

NETWORK EXTENDER
(006980-001, ITEMS 11 & 22)

EQ24EMNE

INITIATING DEVICE CIRCUIT


(006685-001, ITEMS 10, 11,12 & 13)

EQ22EMIDC & EQ22EMIDCGF

AGENT RELEASE MODULE


(006752-001, ITEMS 10, 11,12 & 13)

EQ25EMARM

SIGNAL AUDIBLE MODULE


(006753-001, ITEMS 10, 11,12 & 13)

EQ25EMSAM

DIGITAL COMMUNICATION UNIT


(006684-001, ITEMS 16, 17,18 & 19)

EQ22EMDCU

LOCAL CONTROL UNIT


(006683-001)
FMRC LABELED ENCLOSURE
PROVIDED
(Tamb = 0C TO +60C)
NOTE:
4 EQ2100LC, 4 EQ2100CG,
1 EQ2100IM MAXIMUM.

EQ2100LCU OR EQ2101LCU

ISOLATE

NORMAL

EAGLE QUANTUM
LOGIC CONTROLLER

ISOLATE

PROGRAM

SILENCE

ACKNOWLEDGE

SUPERVISORY

GROUND FAULT

TROUBLE

ALARM

POWER

SUITABLE NRTL LABELED NEMA RATED ENCLOSURE


OR
KILLARK EXB-122412
FOR CLASS I, DIV 1 GROUPS C & D,
CLASS II, DIV 1, GROUPS E, F, G & CLASS III
HAZARDOUS LOCATIONS

<20 FT

CL I, DIV 2 GRPS A, B, C & D


HAZARDOUS LOCATIONS
(Tamb = -40C TO +75C)
EXCEPT WHERE SHOWN

NETWORK EXTENDER
(006980-001)

EQ24XXNE SERIES

INITIATING DEVICE CIRCUIT GROUND FAULT


(006685-001)

EQ22XXIDCGF SERIES

EQ22XXIDC SERIES
INITIATING DEVICE CIRCUIT
(006685-001)

EQ25XXARM SERIES
AGENT RELEASE MODULE
(006752-001)

EQ25XXSAM SERIES
SIGNAL AUDIBLE MODULE
(006753-001)

Figure A1

CONNECTED IN
CONJUNCTION WITH
EAGLE QUANTUM
FIELD DEVICES

FM APPROVED
INITIATING DEVICE
(SEALED OR UNSEALED)
INSTALL PER
NFPA 70 & 72

FM APPROVED
INITIATING DEVICE
(SEALED OR UNSEALED)
INSTALL PER
NFPA 70 & 72

FM APPROVED
SUPPRESSION ACTUATOR
INSTALL PER
NFPA 70 & 72

FM APPROVED
NOTIFICATION APPLIANCE
INSTALL PER
NFPA 70 & 72

DIGITAL
COMMUNICATION UNIT
(006684-001)

EQ22XXDCU SERIES

DIGITAL COMMUNICATION/
REFLECTION SUPPRESSION UNIT
CL I, DIV 2, GRPS A,B,C & D (T4)
CL II, DIV 2, GRPS F & G (T4)
Tamb = -10C TO +75C
(007715-001)

EQ22XXDCURSU SERIES

DIGITAL
COMMUNICATION UNIT
(006684-001)

EQ22XXDCU SERIES

COMBUSTIBLE DIGITAL
COMMUNICATION UNIT
(006684-001)

EQ22XXDCUEX SERIES

EQ22XXDCUEX SERIES
COMBUSTIBLE DIGITAL
COMMUNICATION UNIT
(006684-001)

C)

EQ2400RSU SERIES
REFLECTION SUPPRESSION UNIT
CL I, DIV 2, GRPS A,B,C & D (T4)
CL II, DIV 2, GRPS F & G (T4)
Tamb = -10C TO +75C
(007717-001)

CGS SERIES
COMBUSTIBLE GAS SENSOR
(006888-001)

(CLASS I
LOCATIONS ONLY, T3C)

X2200xxx24 SERIES
UV FLAME DETECTOR

CONNECTED IN
CONJUNCTION WITH
EAGLE QUANTUM
FIELD DEVICES

C TO +75
C, NEMA/TYPE 4X
(007399-001)

CL I, DIV I, GRP B,C & D(T5);


CL II, DIV I, GRP E,F &G(T5), CL III;
CL I, DIV 2, GRP A,B,C & D (T3);
CL II/III, DIV 2, GRP F&G (T3);
Tamb -40

OR OTHER
FM APPROVED
4-20mA DEVICE

C7064E5014 SERIES
HYDROGEN SULFIDE
SENSOR
(Tamb -40C TO +40C)
(006705-001)

PIR9400 SERIES
INFRARED GAS SENSOR
(006535-001)
OR OTHER
FM APPROVED
4-20mA DEVICE

C7064E5014 SERIES
HYDROGEN SULFIDE
SENSOR
(006705-001)

PIR9400 SERIES
INFRARED GAS SENSOR
(006535-001)

(CLASS I LOCATIONS ONLY)

(CLASS I
LOCATIONS ONLY, T3C)

(CLASS I LOCATIONS ONLY)

(CLASS I LOCATIONS ONLY)

CGS SERIES
COMBUSTIBLE GAS SENSOR
(006888-001)

(CLASS I LOCATIONS ONLY)

X5200xxx24 SERIES
UV/IR FLAME DETECTOR

PIR TERMINATION BOX


(006542-001)

SENSOR TERMINATION BOX


(006723-001)

SENSOR TERMINATION BOX


(006723-001)

CL I, DIV 1 GRPS B, C & D


CL II, DIV 1 GRPS E, F & G, CL III
CL I, DIV 2 GRPS A, B, C & D (T4A)
CL II, DIV 2 GRPS F & G (T4A)
HAZARDOUS LOCATIONS NEMA/TYPE 4X
(Tamb = -40
C TO +75
EXCEPT WHERE SHOWN

NEW RELEASE
DESCRIPTION

DATE
DATE

TITLE

SHEET

NO

(0)
.02
(0.0)
.01
(0.00)
.005
ANGLE 1'

(0.5)
(0.25)
(0.13)

DETECTOR ELECTRONICS CORP.


MINNEAPOLIS, MINNESOTA 55438

DATE

2/25/00

10/02

01/03

2/03

DO NOT SCALE DRAWING

SCALE

N/A

SIZE

DRAWING NO.

006695-001

APPROVED

CDS

KAT

KAT
KAT

C7064E SERIES
HYDROGEN SULFIDE
SENSOR
(006705-001)

C7064E SERIES
HYDROGEN SULFIDE
SENSOR
(006705-001)

THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY


INFORMATION AND ANY REPRODUCTION DISCLOSURE OR USE
THEREOF IS EXPRESSLY PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF DETECTOR ELECTRONICS CORPORATION.

REMOVE ALL BURRS BREAK ALL


EDGES AND SHARP CORNERS

0.0
0.00
0.000

UNLESS OTHERWISE SPECIFIED


TOLERANCES ARE :
DIMENSION
TOLERANCE
INCH (MM) INCH (MM)

DWG, DESIGN REFERENCE


EAGLE QUANTUM SYSTEM "FM"

1 OF 1

BILL OF MAT'L REQ.

FIRST USED ON

APP'D

DATE

9/6/02
APP'D

CHECKED

CDS

DATE

ADD EQ2500SAM & EQ2500ARM


ECO NO.

A
REV

ADD EQ2200UVHT/C7050B
ADD EQ2110PS, EQ2130PS &
C7064E GRP B
NETWORK EXTENSION
CHANGE CGS P/N
ADD UV/IR & NON-INCEN REQ.

ADD NOTE 9.

REMOVE EQ2200UV, UVHT, UVIR, C7050B.

SHOW DEVICES' DRD P/N'S.


ADD PIRTB BOX. REMOVE NOTE 7.

ADD EQ2200DCURSU & EQ2400RSU.

ADD X2200 & X5200.

DRAWN

F
E
D
B/C

6713
6280
6185

6880
6824
6777

H
G

M
L
K

SENSOR TERMINATION BOX


(006723-001)

6122-2
6047
5961
5829
5770

DIGITAL
COMMUNICATION UNIT
(006684-001)

EQ2200DCU SERIES

CL I, DIV 1, GRPS C & D


CL I, DIV 2, GRPS A,B,C & D (T4A)
HAZARDOUS LOCATIONS
(Tamb = -40C TO +40C)

REV

APPENDIX B

CANADIAN STANDARDS ASSOCIATION (CSA)


APPROVAL DESCRIPTION]
The Eagle Quantum Fire and Gas Detection/Suppression System (reference Figure B1) has the following CSA
approved configurations:

MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT


(Up to four EQ2100LCU, four EQ2100CG and one EQ2100IM for maximum system.)
Class I, Division 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
Operating Temperature Limits 0C to +60C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.

MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY AND


MODEL EQ2175PS, EQ2130PS AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIES
POWER SUPPLY MONITOR
Ordinary Locations verified per CSA C22.2 #142.
Operating Temperature Limits 0C to +50C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.

MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT


Ordinary Locations verified per CSA C22.2 #142.
Operating Temperature Limits 0C to +50C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.

B-1

95-8470

MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND


MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT
Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
EQ22EMIDC AND EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code
T4A Hazardous Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
The Model EQ2200IDC Series must be used in conjunction with any CSA certified device providing relay contact
closure.

MODELS X2200XXX24 AND X5200XXX24 FLAME DETECTORS


Refer to manual 95-8549 for the Model X2200xxx24 Series and manual 95-8546 for the Model X5200xxx24 Series
flame detector detail.

MODEL EQ2200UV SERIES UV FLAME DETECTOR:


Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Optional Q9001L Swivel Mount.

B-2

MODEL EQ2200UVHT SERIES HIGH TEMPERATURE UV FLAME DETECTOR


Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C for electronic module, 40C to +125C for UV detector.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Optional Q9001B Swivel Mount for UV detector.

MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR


Explosionproof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;
Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Optional Q9001G Swivel Mount.

MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS


Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Combustible gas performance verified with any CSA Certified stand alone linear 4 to 20 mA device per CSA C22.2
#152. Accuracy 3% LFL from 0 to 50% LFL, 5% LFL from 51% to 100% LFL.

B-3

95-8470

MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT


WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR
Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: 3% LFL from 0 to 50%
LFL, 5% LFL from 51% to 100% LFL.

NOTE
The high temperature characteristic has NOT been CSA verified above 75C.

SENSOR SEPARATION KITS


226365-106
226365-113
226365-104

Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector


Combustible, Aluminum, 3/4 inch NPT, Wiring Harness
Toxic, Aluminum, 3/4 inch NPT

Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
NOTE
Ensure sensor hazardous (classified) location rating is applicable for the intended use.

MODEL EQ2500ARM SERIES AGENT RELEASE MODULE


Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
Enclosure Rating NEMA Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.

B-4

MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE


Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
Enclosure Rating NEMA Type 4X per CSA C22.2 #94.
Operating Temperature Limits 40C to +75C.
Storage Temperature Limits 55C to +85C.
Relative Humidity Range: 5 to 95% RH.

MODEL EQ2400NE SERIES NETWORK EXTENDER


Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30.
Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25.
Non-incendive for Class I, Div.2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations
per CSA C22.2 #213.
Enclosure Rating NEMA / Type 4X per CSA C22.2 #94.
Operating Temperature Limits -40C to +75C.
Storage Temperature Limits -55C to +85C.
Relative Humidity Range: 5 to 95% RH.
Gas performance verified per CSA C22.2 #152.

OPTIONS
Operator Interface Station (OIS)
NOTE
Metric straight thread types are for use in non-North American applications.

CALIBRATION
Calibration of the above listed sensors has been CSA verified using the respective EQ2200DCU and
EQ2200DCUEX Series with Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.
The Model EQ2200DCU Series can be used with any CSA certified stand alone 4 to 20 ma linear device.

B-5

95-8470

BATTERY
BACK-UP

SUITABLE METALLIC NRTL LABELED


NEMA RATED ENCLOSURE

CSA CERTIFIED
SUPPRESSION ACTUATOR
INSTALL PER
CEC PART 1

SUITABLE NRTL LABELED


NEMA RATED ENCLOSURE

1. CSA CERTIFIED PRODUCT - NO MODIFICATIONS


PERMITTED WITHOUT REFERENCE TO CSA.

2 WARNING: ENSURE SENSOR HAZARDOUS (CLASSIFIED) LOCATION


RATING IS APPLICABLE FOR THE INTENDED USE.

3 NO MODIFICATIONS ARE PERMITTED FOR USE WITH TYPE


RATED ENCLOSURE(S).

4. PART NUMBERS IN PARENTHESIS DEFINE DESIGN REFERENCE DRAWING


ASSOCIATED WITH A DEVICE UNLESS OTHERWISE SPECIFIED.

LOCAL CONTROL UNIT


POWER SUPPLY
(006693-001)

EQ2100LCUPS SERIES

EQ2100LIOU SERIES
LOCAL INPUT/OUTPUT UNIT
(006694-001)
NOTE:
24 OUTPUT MODULES MAXIMUM.

OPTIONAL OPERATOR INTERFACE STATION

BATTERY
BACK-UP

SUITABLE METALLIC NRTL LABELED


NEMA RATED ENCLOSURE

EQ2100PSM SERIES
POWER SUPPLY MODULE
(006983-001)

006974-001

F1=50mA

(006693-001)

OR

ORDINARY LOCATIONS
(Tamb = 0C to +50C

EQ2110PS, EQ2130PS, &


EQ2175PS POWER SUPPLY

F2=50mA

B-6

TM

18 - TOXIC
19 - O2

01 - Ex
02 - H2S
03 - CL2
04 - CO
05 - NH3
06 - S02
07 - HCL
08 - HCN

GAS

10

20

30

40

50

60

70

80

90

100

TM

FAULT

FLAME

60 - OTHER

40 - OIL ON WATER
41 - PW HEAVY
42 - PW TOTAL
43 - PW BENZENE
44 - PW LOW SENS

ENVIRONMENTAL

20 - UV
21 - IR
22 - UV/IR

TYPE CODE

EAGLE QUANTUM
GATEWAY

RESET

RELAY 3

RELAY 2

RELAY 4

ADDRESS
TYPE
PERCENT

RELAY 1

DET
TRONICS
LON ISOLATOR

EAGLE QUANTUM
LON ISOLATOR

LON 1

LON 0

GROUND FAULT

POWER -

POWER +

GROUND FAULT

TM

HIGH TEMPERATURE
(007088-001, ITEM 17)

EQ22EMUVHT

(006981-001)

NETWORK EXTENDER

EQ24EMNE

INITIATING DEVICE CIRCUIT


(006689-001, ITEMS 10, 11,12 & 13)

EQ22EMIDC/EQ22EMIDCGF

AGENT RELEASE MODULE


(006771-001, ITEMS 10, 11,12 & 13)

EQ25EMARM

SIGNAL AUDIBLE MODULE


(006772-001, ITEMS 10, 11,12 & 13)

EQ25EMSAM

DIGITAL COMMUNICATION UNIT


(006688-001, ITEMS 16, 17,18 & 19)

EQ22EMDCU

NOTE:
4 EQ2100LC, 4 EQ2100CG,
1 EQ2100IM MAXIMUM.

(Tamb = 0C TO +60C)

LOCAL CONTROL UNIT


(006687-001)

SUITABLE NRTL LABELED NEMA RATED ENCLOSURE


OR
KILLARK EXB-122412
FOR CLASS I, DIV 1 GROUPS C & D,
CLASS II, DIV 1, GROUPS E, F, G & CLASS III
HAZARDOUS LOCATIONS

RESET

PROGRAM

DET
TRONICS
COMMUNICATIONS GATEWAY

EQ2100LCU OR EQ2101LCU

ISOLATE

NORMAL

EAGLE QUANTUM
LOGIC CONTROLLER

ISOLATE

PROGRAM

SILENCE

ACKNOWLEDGE

SUPERVISORY

GROUND FAULT

TROUBLE

ALARM

POWER

DET
TRONICS

CL I, DIV 2 GRPS A, B, C & D


HAZARDOUS LOCATIONS
(Tamb = -40C TO +75C)
EXCEPT WHERE SHOWN

X5200 SERIES
UVIR FLAME DETECTOR

CSA CERTIFIED
SEALED OR UNSEALED
INSTALL PER
CEC PART 1

CSA CERTIFIED
SUPPRESSION ACTUATOR
INSTALL PER
CEC PART 1

Figure B1

C TO +75
C, NEMA/TYPE 4X
(007399-001)

CL I, DIV I, GRP B,C & D(T5);


CL II, DIV I, GRP E,F &G(T5), CL III;
CL I, DIV 2, GRP A,B,C & D (T3);
CL II/III, DIV 2, GRP F&G (T3);
Tamb -40

C7050B SERIES

NETWORK EXTENDER
(006981-001)

EQ2400NE SERIES

CGS SERIES
COMBUSTIBLE GAS SENSOR
(006887-001)

CSA CERTIFIED
4-20mA DEVICE

OR OTHER

PIR9400 SERIES
INFRARED GAS SENSOR
(006367-001)

(005557-001)

(CLASS I
LOCATIONS ONLY, T3C)

CONNECTED IN
CONJUNCTION WITH
EAGLE QUANTUM
FIELD DEVICES

CSA CERTIFIED
4-20mA DEVICE

OR OTHER

PIR9400 SERIES
INFRARED GAS SENSOR
(006367-001)

UPDATE C7050 & PIR9400

ADD X2200 & X5200 FLAME DETECTORS.

DESCRIPTION

TITLE

SHEET

DATE

DATE

DATE

NO

9/23/02

(0)
.02
(0.0)
.01
(0.00)
.005
ANGLE 1'

(0.5)
(0.25)
(0.13)

DATE

DETECTOR ELECTRONICS CORP.


MINNEAPOLIS, MINNESOTA 55438

SCALE

N/A

SIZE

006793-001

DRAWING NO.

THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY


INFORMATION AND ANY REPRODUCTION DISCLOSURE OR USE
THEREOF IS EXPRESSLY PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF DETECTOR ELECTRONICS CORPORATION.

REMOVE ALL BURRS BREAK ALL


EDGES AND SHARP CORNERS

0.0
0.00
0.000

UNLESS OTHERWISE SPECIFIED


TOLERANCES ARE :
DIMENSION
TOLERANCE
INCH (MM) INCH (MM)

DO NOT SCALE DRAWING


1 OF 1
DWG, DESIGN REFERENCE
EAGLE QUANTUM
SYSTEM "CSA"
CADDS NAME: 6793-01h

BILL OF MAT'L REQ.

FIRST USED ON

APP'D

APP'D

CHECKED

NEW RELEASE
CDS

ADD UVIR & NON-INCEN REQ.

DATE

CHANGE CGS P/N

ADD EQ2100PSM & EQ2400NE


NETWORK EXTENSION

ADD EQ2200UVHT/C7050B.
ADD CL I, DIV. 2, GRPS A,B,C,D

CORRECT DWG NO'S ON EQ21100PS,


PSM, LCUPS, LCU & EQ2200DCU.

ECO NO.

6123

6913
6713
6495
6185

C7065E OXYGEN SENSOR OR


C7066E CARBON DIOXIDE SENSOR
(Tamb = -40C TO +40C)
(005897-001)

REV

SENSOR
SEPARATION KIT
(006724-001)

(Tamb = -40C TO +40C)


(005557-001)

C7064E HYDROGEN SULFIDE SENSOR OR


C7068E SULFUR DIOXIDE SENSOR OR
C7069E NITROGEN DIOXIDE SENSOR

C7065E OXYGEN SENSOR OR


C7066E CARBON DIOXIDE SENSOR
(Tamb = -40C TO +40C)
(005897-001)

DRAWN

C
B
A

H
G
F
E

DIGITAL
COMMUNICATION
UNIT
(006688-001)

EQ2200DCU SERIES

C7064E HYDROGEN SULFIDE SENSOR OR


C7068E SULFUR DIOXIDE SENSOR OR
C7069E NITROGEN DIOXIDE SENSOR
(Tamb = -40C TO +40C)
(005557-001)

CL I, DIV 1, GRPS C & D


CL I, DIV. 2, GRPS A,B,C & D
HAZARDOUS LOCATIONS
(Tamb = -40C TO +40C)

6047
5961
5839

C7064E5014 SERIES
HYDROGEN SULFIDE
SENSOR
(Tamb -40C TO +40C)
(005557-001)
(CLASS 1 LOCATIONS ONLY)

(CLASS I
LOCATIONS ONLY, T3C)

(CLASS 1 LOCATIONS ONLY)

C7064E5014 SERIES
HYDROGEN SULFIDE
SENSOR
(Tamb -40C TO +40C)

(CLASS 1 LOCATIONS ONLY)

CGS SERIES
COMBUSTIBLE GAS SENSOR
(006887-001)

(CLASS 1 LOCATIONS ONLY)

CSA CERTIFIED
SEALED OR UNSEALED
INSTALL PER
CEC PART 1

SENSOR SEPARATION KIT


(006724-001)

(006724-001)

SENSOR SEPARATION KIT

EQ2200IDC SERIES
INITIATING DEVICE CIRCUIT
(006689-001)

UV FLAME DETECTOR
(Tamb -40C TO +125C)
(006839-001)

CSA CERTIFIED
NOTIFICATION APPLIANCE
INSTALL PER
CEC PART 1

UV FLAME DETECTOR
ELECTRONIC MODULE
(007088-001)

EQ2200UVHT SERIES

X2200 SERIES
UV FLAME DETECTOR

EQ2200IDCGF SERIES
INITIATING DEVICE CIRCUIT
(006689-001)

AGENT RELEASE MODULE


(006771-001)

EQ2500ARM SERIES

SIGNAL AUDIBLE MODULE


(006772-001)

EQ2500SAM SERIES

EQ2200UVIR SERIES
UV/IR FLAME DETECTOR
(006909-001)

UV FLAME DETECTOR
(006690-001)

EQ2200UV SERIES

DIGITAL
COMMUNICATION UNIT
(006688-001)

EQ2200DCU SERIES

(006688-001)

DIGITAL
COMMUNICATION UNIT

EQ2200DCU SERIES

COMBUSTIBLE DIGITAL
COMMUNICATION UNIT
(006688-001)

EQ2200DCUEX SERIES

COMBUSTIBLE DIGITAL
COMMUNICATION UNIT
(006688-001)

EQ2200DCUEX SERIES

CL I, DIV 1 GRPS B, C & D


CL II, DIV 1 GRPS E, F & G, CL III
CL I, DIV 2 GRPS A, B, C & D (T4A)
CL II, DIV 2 GRPS F & G (T4A)
HAZARDOUS LOCATIONS NEMA/TYPE 4X
(Tamb = -40C TO +75C)
EXCEPT WHERE SHOWN

APPROVED

REV

APPENDIX C
CE MARK
The Eagle Quantum Fire and Gas Detection/Suppression System was tested and found to be compliant with
EN50130-4 and EN50270 when wired in conduit or with armoured instrument cable with individual screened twisted
pairs and galvanized steel wire armour. All screen drains shall be terminated to the chassis except for the LON/SLC
screen drains, which are terminated at LCU terminals 23 A and B and the LON/SLC screen termination in each field
device.
Communication wiring between the Local Control Unit (LCU), Local Input/Output Unit (LIOU) and Local Control Unit
Power Supply (LCUPS) shall be limited to a maximum of 3 meters for each section.
For use of the CE Mark, the system is not intended for use in buildings.

ATEX CERTIFICATION
INITIATING DEVICE CIRCUIT (IDC, IDCGF and IDCSC),
DIGITAL COMMUNICATION UNIT (DCU and DCUEX),
AGENT RELEASE MODULE (ARM),
SIGNAL AUDIBLE MODULE (SAM),
NETWORK EXTENDER (NE),
UV HIGH TEMPERATURE (UVHT, Electronic Module):
CE 0539 II 2 G
Ex d IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = 55C to +50C)
T5 (Tamb = 55C to +65C)
T4 (Tamb = 55C to +75C)
IP66.
Combustible gas performance certified per EN 60079-29-1: 2007 for DCU and DCUEX, and per EN 61779-4: 2000
for LCU.
Read and understand instruction manual before operating.
To obviate the risk of hotspots and capacitor energy storage, the enclosure must not be opened, even when isolated,
when an explosive gas atmosphere is present.
All cable entry devices and blanking elements shall be certified in type of explosion protection flameproof enclosure
d, suitable for the conditions of use and correctly installed. Unused apertures shall be closed with suitable certified
blanking elements.
For ambient temperatures above 60C, use field wiring suitable for maximum ambient temperature.
Special Conditions for Safe Use of Eagle Quantum Field Devices
The Eagle Quantum System has an ambient temperature rating for performance of 40C to +75C.

C-1

95-8470

CATALYTIC COMBUSTIBLE GAS SENSOR (CGS)


CE 0539 II 2 G
Ex d IIC T3, T5
DEMKO 02 ATEX 131323 X
T5 (Tamb = 40C to +75C)
T3 (Tamb = 55C to +125C)
Special Conditions for Safe Use of CGS
The performance ambient temperature rating is limited to 40C to +75C.
The CGS Combustible Gas Sensor can withstand repeated exposures to 125C for periods up to 12 hours. Sensor
replacement is recommended after a maximum of 500 hours of exposure to the 125C temperature condition.
The CGS Combustible Gas Sensor must be used in conjunction with a CENELEC certified Detector Electronics Corp.
combustible gas detector control unit for compliance with EN 61779 series standards.

CENELEC CERTIFICATION
X2200XXX24 UV FLAME DETECTOR
Refer to manual 95-8549.
EQ22XXUV FLAME DETECTOR:
Standard Temperature Version
EEx d IIB +H2 T6 (Tamb = 40C to +75C).
IP66.
Extended Temperature Version
EEx d IIB +H2 T6 (Tamb = 55C to +75C)
EEx d IIB +H2 T4 (Tamb = 55C to +125C)
IP66.
Special Conditions for Safe Use of UV Detector
The detector contains capacitors that could be an ignition source if the enclosure is opened within a hazardous area.
The enclosure must not be opened, even when isolated, when a flammable atmosphere is present. The cable must
only be connected to the enclosure by a flameproof cable entry device certified to EN 50 018. If only one cable entry
is used, any other entries must be closed by a certified flameproof stopping plug. The flame detector can be
delivered in two versions, one for ambient temperatures up to +75C, and one for temperatures up to +125C. The
label will indicate the actual maximum allowable ambient temperature.
EQ2200UVHT SERIES UV FLAME DETECTOR
UV Detector
Ex d IIB +H2 T4 (Tamb = 55C to +125C)
Ex d IIB +H2 T5 (Tamb = 55C to +90C)
Ex d IIB +H2 T6 (Tamb = 55C to +75C)
IP66.
Special Conditions for Safe Use of UV Detector
The cable entry temperature may rise 10C above the ambient temperature and cable shall be suitable for that
temperature. The flame detector shall be electrically connected by means of a flame-proof cable gland or stopping
box certified to EN 50018. The fused silica lens in this unit is liable to be damabed by impact. The unit should be
installed in such a manner as to protect the lens from mechanical damage.
C-2

X5200XXX24 UV/IR FLAME DETECTOR


Refer to manual 95-8546.
EQ22XXUVIR FLAME DETECTOR:
Standard Temperature Version
EEx d IIB +H2 T6 (Tamb = 40C to +75C).
EEx d IIB +H2 T5 (Tamb = 40C to +90C).
IP66.
Extended Temperature Version
EEx d IIB +H2 T6 (Tamb = 55C to +75C)
EEx d IIB +H2 T5 (Tamb = 55C to +90C)
EEx d IIB +H2 T4 (Tamb = 55C to +125C)
IP66.
Special Conditions for Safe Use of UV/IR Detector
The UV detector module contains a fused silica window, which can be damaged by impact. The detector should be
installed in such a manner as to prevent the window from receiving mechanical damage.

C-3

95-8470

APPENDIX D

D-1

95-8470

Node
Address

Rocker Switch Table


Node
Address
7
8

Rocker Switch
3
4
5
6

1
2
3
4
5
6
7
8
9
10

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

11
12
13
14
15
16
17
18
19
20

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

X
X
X
X
X
O
O
O
O
O

O
O
O
O
O
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

21
22
23
24
25
26
27
28
29
30

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

X
X
X
O
O
O
O
X
X
X

O
O
O
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

31
32
33
34
35
36
37
38
39
40

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

X
O
O
O
O
O
O
O
O
X

X
O
O
O
O
O
O
O
O
O

41
42
43
44
45
46
47
48
49
50

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

X
X
X
X
X
X
X
O
O
O

51
52
53
54
55
56
57
58
59
60

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

61
62
63
64
65
66
67
68
69
70

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

X
X
X
O
O
O
O
X
X
X

Rocker Switch
4
5
6

71
72
73
74
75
76
77
78
79
80

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

O
X
X
X
X
X
X
X
X
O

O
O
O
O
O
O
O
O
O
X

O
O
O
O
O
O
O
O
O
O

81
82
83
84
85
86
87
88
89
90

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

91
92
93
94
95
96
97
98
99
100

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

O
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

101
102
103
104
105
106
107
108
109
110

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
O
O
O
O
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

111
112
113
114
115
116
117
118
119
120

X
O
X
O
X
O
X
O
X
O

O
O
O
O
O
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

121
122
123
124
125
126
127
128
129
130

X
X
X
O
O
O
O
O
O
O

X
X
X
O
O
O
O
O
O
O

X
X
X
O
O
O
O
O
O
O

O
O
O
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

131
132
133
134
135
136
137
138
139
140

D-2

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
O
O
O
O
O

X
X
X
X
X
O
O
O
O
O

O
O
O
O
O
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
O
O
O
O
X
X
X

O
O
O
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

X
O
O
O
O
O
O
O
O
X

O
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

X
X
X
X
X
X
X
O
O
O

X
X
X
X
X
X
X
O
O
O

X
X
X
X
X
X
X
O
O
O

X
X
X
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

O
O
O
O
O
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

Rocker Switch
3
4
5
6

Rocker Switch Table


Node
Address
7
8

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

X
X
X
O
O
O
O
X
X
X

X
X
X
O
O
O
O
O
O
O

O
O
O
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

151
152
153
154
155
156
157
158
159
160

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

O
X
X
X
X
X
X
X
X
O

X
X
X
X
X
X
X
X
X
O

O
O
O
O
O
O
O
O
O
X

O
O
O
O
O
O
O
O
O
O

161
162
163
164
165
166
167
168
169
170

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

171
172
173
174
175
176
177
178
179
180

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

X
X
X
X
X
O
O
O
O
O

O
O
O
O
O
X
X
X
X
X

181
182
183
184
185
186
187
188
189
190

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

X
X
X
O
O
O
O
X
X
X

O
O
O
X
X
X
X
X
X
X

191
192
193
194
195
196
197
198
199
200

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

201
202
203
204
205
206
207
208
209
210

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

Node
Address

141
142
143
144
145
146
147
148
149
150

Rocker Switch
4
5
6

211
212
213
214
215
216
217
218
219
220

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

O
X
X
X
X
O
O
O
O
X

O
O
O
O
O
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

221
222
223
224
225
226
227
228
229
230

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

X
X
X
O
O
O
O
X
X
X

X
X
X
O
O
O
O
O
O
O

X
X
X
O
O
O
O
O
O
O

O
O
O
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

231
232
233
234
235
236
237
238
239
240

X
O
X
O
X
O
X
O
X
O

X
O
O
X
X
O
O
X
X
O

X
O
O
O
O
X
X
X
X
O

O
X
X
X
X
X
X
X
X
O

O
O
O
O
O
O
O
O
O
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

241
242
243
244
245
246
247
248
249
250

X
O
X
O
X
O
X
O
X
O

O
X
X
O
O
X
X
O
O
X

O
O
O
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

X
O
O
O
O
O
O
O
O
X

X
O
O
O
O
O
O
O
O
O

X
O
O
O
O
O
O
O
O
O

O
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
O
O
O

O
O
O
O
O
O
O
X
X
X

O
O
O
O
O
O
O
O
O
O

X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X
X

O = OPEN
X = CLOSED

D-3

95-8470

LON is a registered trademark of Echelon Corporation.


Modbus is a registered trademark of Modicon Inc.

Detector Electronics Corporation


6901 West 110th Street
Minneapolis, MN 55438 USA

X3301 Multispectrum
IR Flame Detector

PointWatch Eclipse
IR Combustible Gas Detector

FlexVu Universal Display


w/ GT3000 Toxic Gas Detector

Eagle Quantum Premier


Safety System

T: 952.941.5665 or 800.765.3473
F: 952.829.8750
W: http://www.det-tronics.com
E: det-tronics@det-tronics.com

Det-Tronics, the DET-TRONICS logo, Eagle Quantum Premier, Eclipse, and FlexVu are registered trademarks or trademarks of Detector Electronics
Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.
Copyright Detector Electronics Corporation 2012. All rights reserved.

You might also like