INTRODUCTION
THE first generation of gas-insulated switchgear (GIS)
that Hitachi developed was 550 kV. Developed in 1978,
this GIS used 4-break circuit breakers and all of its
phases were of the separated-phase type. Later, circuit
breakers were changed to the 2-break type.
In 1989, the LIWV (lightning impulse withstand
voltage) was lowered by using a high-performance
metal oxide surge arrester, which lowers residual
voltage. As a result, a large-radius, 3-phase common
Disconnecting switch
at feeder side
Main bus
Specifications
Rated voltage
Rated current
Rated short-time
withstand current
LIWV
AC withstand voltage
63 kA (2 s)
1,425/1,550 kV
475 kV-635 kV-475 kV
0.6 MPa (GCB)
0.4 MPa (except GCB)
Hydraulic
CB
Motor wounded spring
DS
Motor wounded spring (for line)
ES
Motor (for main bus)
Manual (for maintenance)
Operating method
CT
Bellows
550 kV
2,000/4,000/6,000/8,000 A
Rated pressure
GCB
286
100
90
80
70
60
50
40
30
20
10
0
Line DS
ES for maintenance
Bellows
100
100
100
85
83
72
Conventional
type
New type
GIB
Gas
bushing
Main bus DS
Lightning
arrester
CT
Main bus
Removal
joint
ES for maintenance
ES for line
287
Earthing circuit
Earthing circuit
current for GIB
0.9
(0.6)
Temperature (C)
140
120
100
80
60
640
Bellows
length
Maximum
solar radiation
11:30
Start
current-carrying
8:50
40
Ambient temperature
Tank temperature (top)
Tank temperature (right)
Tank temperature (bottom)
Tank temperature (left)
Average temperature
Bellows length (top)
Bellows length (lower right)
Bellows length (lower left)
Average bellows length
Analysis bellows length
660
620
600
Finished
current-carrying
17:50
580
560
Temperature
540
20
520
500
160
Measuring point
for temperature
Top GIS side
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20]00
21:00
22:00
23:00
24:00
1:00
3:00
Left
Bellows
288
Right
Measuring point
for length bellows
Top GIS side
Lower left
Lower right
Bottom
Fig. 4The Displacement of the Bellows Type Expansion and the Analysis Result for
Long GIB During a Current-carrying Test at the Site.
We confirmed that bellows displacement depended on tank temperature. The displacement that we
obtained by analyzing measurements of temperature agreed well with the displacement measurements.
289
REFERENCES
14 m
88 m
Carrying in
34 m
Carrying in
Manabu Takamoto
Joined Hitachi, Ltd. in 1980, and now works at the
Third Electric Power Department of the Electric
Utility Sales Operations Group. He is currently
engaged in the sale of transformation devices. Mr.
Takamoto is a member of the Institute of Electrical
Engineers of Japan.
Masaharu Matsuyama
Joined Hitachi, Ltd. in 1975, and now works at the
Gas Insulated Switchgear Department of Kokubu
Administrative Division. He is currently engaged in
the manufacture of gas insulated switchgear. Mr.
Matsuyama is a member of the Japan Society of
Mechanical Engineers, and can be reached by e-mail
at m-matsuyama@cm.kokubu.hitachi.co.jp.