Professional Documents
Culture Documents
WorkingGroupC13"UndervoltageLoadShedding
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Assignment.....................................................................................................................................................5
Scope...............................................................................................................................................................5
1.
Introduction.............................................................................................................................................5
Investigationsofrecentblackoutsindicatethattherootcauseofalmostallofthesemajorpowersystem
disturbancesisvoltagecollapseratherthantheunderfrequencyconditionsprevalentintheblackoutsof
the1960and70s.Thispaperexploresthenatureofrecentpowersystemblackouts(2003eastcoast,
1996 California and others) and explains why voltage collapse is the leading edge indicator of
impendingpowersystem problems.It alsodiscusses thedesign andsecurity issues that need tobe
addressed in the design of an undervoltage load shedding (UVLS) scheme and why relying on
underfrequencyloadshedding(UFLS)maybetoolittle,toolate.Thepaperaddressesthecurrentlevel
ofUVLSonutilitysystemsaswellascurrentNERC(NorthAmericanElectricReliabilityCouncil)
pronouncementsonthesubject....................................................................................................................5
2.
Background.............................................................................................................................................9
2.1.
VoltageStability(Begoric)......................................................................................................9
2.2. Voltage & reactive power management andemergency actions to avoid load
shedding(Begoric).................................................................................................................................9
2.2.1.
ContinuouslyControlledReactivePowerSource.....................................................9
2.2.2.
DiscontinuouslyControlledReactivePowerSource...............................................9
2.2.3.
AutomaticVoltageControl..............................................................................................9
2.2.4.
VoltagereductionandLTCblocking...........................................................................9
2.3.
3.
4.
CoordinationbetweenUVLSandUFLS.............................................................................9
3.1.
SystemStudies.............................................................................................................................9
3.2.
Selectionofmethod....................................................................................................................9
4.1.
Manual/SCADAloadshedding..............................................................................................9
4.2.
Automaticloadshedding(Buanno,Imai)............................................................................9
4.3.
Local(Buanno,Imai).................................................................................................................9
4.3.1.
Centralized(Substation/Bus)...........................................................................................9
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
Distributed(Feeder)...........................................................................................................9
4.3.3.
Adaptive(Begoric)..............................................................................................................9
4.4.
5.
WorkingGroupC13"UndervoltageLoadShedding
4.3.2.
Wideareaundervoltageloadshedding(Buanno,Imai)..................................................9
5.1.
U/V(Harley)..................................................................................................................................9
5.1.1. Voltage Slide Scheme [I.L. van der Merwe, J.Cloete and N.Fischer,
ImplementationofanUnconventionalVoltageSlideScheme].......................................9
6.
7.
5.2.
Rateofchangeofvoltage(Imai)............................................................................................9
5.3.
Impedancelocusdetection(Begoric,Novoseltobeasked)..........................................9
5.4.
Others............................................................................................................................................10
6.1.
Dependabilityandsecurity.....................................................................................................10
6.2.
Redundancy................................................................................................................................10
6.3.
Voltagemeasurementaccuracyandsecurity....................................................................10
6.4.
Otherconsiderations................................................................................................................10
6.4.1.
Timedelay...........................................................................................................................10
6.4.2.
Frequencyvariationeffects............................................................................................10
ExistingUVLSpractices(Young,Burger,Madanitobeasked,Henvilletobeasked)........................10
7.1. Classificationanddefinition[IEEEWGC4Draft4,IndustryExperiencesWith
SystemIntegrityProtectionSchemes(SIPS)]...............................................................................10
7.2.
Distributed(Buanno)...............................................................................................................12
7.2.1.
FlatArchitecture................................................................................................................12
PudgetSoundUVLS..........................................................................................................................12
FirstEnergyUVLS...........................................................................................................................12
7.2.2.
HierarchicalArchitecture...............................................................................................13
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
7.3.
Centralized(Imai).....................................................................................................................14
7.3.1.
FlatArchitecture................................................................................................................14
BC Hydro UVLS...............................................................................................................................14
Florida Power & Light FALS...........................................................................................................14
Entergy VSHED [S. Kolluri, Tao He, Design and Operating Experience with Fast
7.3.2.
HierarchicalArchitecture...............................................................................................15
TDST in HydroQuebec Defense Plan against extreme contingencies [D. Lefebvre, et al,
Undervoltage load shedding scheme for the Hydro-Quebec system, IEEE Power
Engineering Society General Meeting, June 2004]...................................................................15
Korea UVLS (To be asked).............................................................................................................16
8.
8.1.
Performancecriteria.................................................................................................................16
8.2.
Settingguidelinesforundervoltageloadshedding.........................................................16
9.
10.
10.1.
1987France............................................................................................................................16
10.2.
1987Tokyo(Imai)................................................................................................................16
10.3.
1989Quebec...........................................................................................................................18
10.4.
2001Peru.................................................................................................................................18
10.5.
2003NortheasternNorthAmerica...................................................................................18
10.6.
2003Sweden..........................................................................................................................18
10.7.
2003Italy.................................................................................................................................18
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
10.8. 2003 Mississippi, USA [Meyer Kao and Gary Kobet, Analysis of
UndervoltageLoadSheddingEventatPhiladelphia,Mississippi,GeorgiaTechFault
andDisturbanceAnalysisConferenceApril2627,2004]......................................................18
11.
Conclusion.........................................................................................................................................18
12.
Bibliography......................................................................................................................................18
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Assignment
This working group produces a report on the implementation of undervoltage load shedding
(UVLS) in electric power systems. It presents background information, guidance in implementing
UVLS schemes and a bibliography. Voltage instability, voltage and reactive power management,
emergency actions to avoid load shedding, UVLS philosophy and methods, voltage collapse
detection, existing practices, settings and coordination between UVLS and UFLS are discussed.
Scope
This report presents information on implementing undervoltage load shedding schemes in electric
power systems. It will provide much of the reference material necessary for a future guide on
UVLS. The report will not cover other uses of undervoltage protection or the implementation of
underfrequency load shedding except as it pertains to coordination issues.
1. Introduction
Investigations of recent blackouts indicate that the root cause of almost all of these major power
system disturbances is voltage collapse rather than the underfrequency conditions prevalent in
the blackouts of the 1960 and 70s. This paper explores the nature of recent power system
blackouts (2003 east coast, 1996 California and others) and explains why voltage collapse is the
leading edge indicator of impending power system problems. It also discusses the design and
security issues that need to be addressed in the design of an undervoltage load shedding (UVLS)
scheme and why relying on underfrequency load shedding (UFLS) maybe too little, too late.
The paper addresses the current level of UVLS on utility systems as well as current NERC (North
American Electric Reliability Council) pronouncements on the subject.
Power systems today are much more susceptible to voltage collapses than they were 35 years
ago as we increasingly depend on generation sources that are located remotely from load
centers. Generators in eastern Canada and the midwestern U.S. provide large amounts of power
to east coast load centers such as New York City. Generators in Washington, Oregon and
western Canada provide substantial power to southern California. Two factors promote
generation that is remote from load centers:
The economics of purchasing power from lower-cost remote sources rather than
more expensive local generation.
These two fundamental changes in operation of the U.S. power grid result in the transmission of
power over long distances. This makes the power grid very dependent on the transmission
system to deliver power to the load centers. It also results in increased reactive power losses
when transmission lines trip.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Another key factor that results in rapid system voltage collapse is the nature of the loads that are
being served by utilities. Many of todays loads are single-phase small air conditioning motors.
This was not the case 35 years ago when air conditioning was not as prevalent. These small
motors are prone to stall when subjected to voltage dips caused by transmission system short
circuits. During hot weather, these motors comprise a high percentage of the utility load. The
slow tripping of stalled motors and the relatively slow re-acceleration of more robust motors
result in low system voltage after a transmission system fault is cleared [2]. The voltage dip and
its effect on these motors are exacerbated if the transmission system fault is cleared via a time
delay backup relay or is a mullti-phase fault. Such a slow-clearing fault resulted in the voltage
collapse that caused a blackout of the city of Memphis in 1987 [3].
Fig. 1 shows an example of voltage recovery for a Phoenix area transmission system fault
incident that occurred in July 1995 during hot weather.
Residential Voltage Recovery for Phoenix Area Incident on July 29, 1995
Fig. 2 illustrates a basic power system with the remote generators supplying a significant
amount of power (Ps) over a considerable distance to the remote load center. The load is
comprised of resistive load and motor load. During a voltage dip resistive load current will
decrease and help limit the need for local reactive support. Motor loads are essentially constant
kVA devices. The lower the voltage, the more current they drawincreasing the need for local
reactive (VAr) support. Power systems loads consist of both resistive loads as well as reactive
motor loads. During hot weather, however, air conditioning motor loads comprise a large portion
of total load, thereby making the system more susceptible to voltage collapse.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Transmission System X
Load Center
Ps
Remote
Generation
PL
QL
VL
Resistive
Load
Motor
Load
Local
Generation
VAR
Support
Reactive power (VArs) cannot be transmitted very far, especially under heavy load
conditions, and so it must be generated close to the point of consumption. This is because the
difference in voltage causes VArs to flow and voltages on a power system are only typically +/- 5% of
nominal. This small voltage difference will not cause substantial VArs to flow over long distances.
Real power (MW) can be transmitted over long distances through the coordinated operation of
the interconnected grid whereas reactive power must be generated at, or near, the load center.
Since VArs cannot be transmitted over long distances, the sudden loss of transmission lines
results in the immediate need for local reactive power to compensate for the increased losses of
transporting the same power over fewer transmission lines. If that reactive support is not
available at the load center, the voltage will go down. For these reasons, voltagerather than
frequencyhas become the key indicator that the power system is under stress. Utilities
recognize that frequency can remain normal as voltage sags to a low level prior to a complete
system collapse and are implementing UVLS schemes to complement their existing
underfrequency load shedding programs.
[1] C. J. Mozina, Power Plant Protection and Control Strategies for Blackout Avoidance, Georgia
Tech Protective Relay Conference, April 2005.
[2] B.R. Williams, W.R. Schmus, D.C. Dawson, Transmission Voltage Recovery Delayed by
Stalled Air Conditioner Compressors, IEEE PES Transactions on Power Systems, Vol. 7,
No.3 August 1992.
[3] North American Electric Reliability Council (NERC), 1987 System Disturbance Report, p19,
July 1998.
[4] U.S. Canada Power System Outage Task Force, Final Report on the August 14, 2003
Blackout in the United States and Canada: Causes and Recommendations April 5, 2004.
[5] G.C. Bullock, Cascading Voltage Collapse in West Tennessee, August 22,1987, Georgia
Tech Relay Conference, May 1990.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
[6] S. Imai, Undervoltage Load Shedding Improving Security as Reasonable Measure for
Extreme Contingencies. IEEE PES Transactions on Power Delivery.
[7] IEEE Power System Relaying Committeee Report, Summary of System Protection and
Voltage Stability, Transactions on Power Delivery, Vol. 10. No. 2, April 1995.
[8] Undervoltage Load Shedding Task Force (UVLSTF), Technical Studies Subcommittee of the
WECC, Undervoltage Load Shedding Guidelines, July 1999.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
2. Background
2.1.
2.2.
2.2.1.
2.2.2.
2.2.3.
2.2.4.
2.3.
System Studies
3.2.
Selection of method
4.2.
4.3.
4.3.1.
Centralized (Substation/Bus)
4.3.2.
Distributed (Feeder)
4.3.3.
Adaptive(Begoric)
4.4.
U/V(Harley)
5.1.1.
5.2.
5.3.
5.4.
Others
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
6.2.
Redundancy
6.3.
Theschemewillneedtoconsidertheaccuraciesofthevoltagetransformersandtherelays.Itwillneedto
alsoconsiderthesecondaryvoltagedropwhichmightbeseveralvoltsifotherdevicesareconnectedto
voltagetransformerwindingandtheleadlengthfromtheinstrumenttransformerislong.Theoverallerror
mightneedtobelessthan2or3%ifforexamplethepickupinaflat distributedschemeis88%of
nominalsystemvoltage.
6.4.
Other considerations
6.4.1.
Time delay
Iftheschemeisdesignedtomitigateavoltagecollapseevent,thedelaywillneedtobeveryshortsothat
operationswillbegintotakeplacewithin30cycles.Iftheschemeisdesignedtomitigateaslowvoltage
declineevent,itmaysuccessfullyoperateinamatterofseconds.Itwillneedtobegreaterthanbackup
faultclearingtimes.ThesetypesofUVLSschemesalsoneedtooperatebeforegeneratoroverexcitation
limitersandtransformerloadtapchangersact.Theseactionswilloccurin15secondsormore.
6.4.2.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
SIPS(Subsystem/SystemWide)
SIPS
Measurements
Actions
Control
Coordination
EventReports
SIPS(Local)
PowerSystem
Seconds/
Minutes
Measurements
Milliseconds
/Seconds
Actions
FlatArchitecture
PowerSystem
HierarchicalArchitecture
The primary difference between the two architectures in Figure 1 is in the necessity of providing
information between the stations or between the measurement and switching devices in order to
add control coordination from the higher and wider system view. A hierarchical scheme may
involve multi-layers and will involve communication outside of the substation whereas a flat
scheme involves a single layer of decisions and actions. Note the typical operating times for
hierarchical schemes in Figure 1.
In some schemes, action is immediate and must satisfy the purpose instantly, hence scheme
logic may entail higher margins for actions taken. Other schemes may have a more adaptive
nature, which employ monitoring the system response to the control action. This implementation
requires communication. If the immediate action is not adequate to halt the progression of the
outage, then additional analysis and action is required.
For instance, SIPS that monitors transmission line congestion may immediately trip selected
transmission elements (lines or generators) and continue monitoring the system condition to
determine if further action is required. If the line loading is not relieved, tripping additional
generation or load, either local or distributed, may be required.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
7.2.
WorkingGroupC13"UndervoltageLoadShedding
Distributed (Buanno)
7.2.1.
Flat Architecture
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
1.0
0.88
Normal Voltage
Undervoltage Trip Level (27P1)
0.35
59A1
59B1
59C1
27S
3P27
UV Time Delay
3P59
SV1
SV1T
600
0
0
50P1 *
599
11
0
OUT101
Trip, Block Auto Reclose,
Alarm
67P1T
* Optional
FigureR1:UVLSLevelsandLogic
FEsUVLSschemehasanoptiontouseasecondvoltagesource(VS)asanextraverificationoflow
voltage(27S).ThisoptionwasoftenemployedwhenCCVTswereusedforthreephasevoltagesensing.
Anotheroptionthatisavailableiscurrentsupervision(50P1).Thisoptionwasusedatlargesubstations
witheightormoreloadcircuitstoaccountforextendedclearingtimesofevolvingfaultsorfaultsthat
mightinvolvemultiplecircuits.Thecurrentsupervisiondetectorissetatfaultcurrentlevelsandmustbe
pickedupalmostaslongastheUVLStripdelayinorderforthecurrentsupervisiontoblockanoperation.
Theinstallationstypesbrakedownasfollows:58%werethetypeAinstallation(singlerelay),27%were
typeB(tworelaysinseries)and15%weretheothertypes(theseincludedcurrentsupervisionlogic).
SinglerelaytypeinstallationssuchastypeAwereusedatthoselocationswithlessthan30MWofloadto
beshed.Forlocationsthatshedmorethan30MWofload,FErequiresmorethanonerelaytooperatefor
additionalsecurity. TheUVLSschemesweredesignedwithnewlocalandSCADAalarmstoprovide
goodindicationofaUVLSoperation,alossofpotentialsupplyorarelayfailure.
FE also installed UVLS protection for Central New Jersey in 1990 to prevent a wide area potential
collapsethatmightresultfrommultiplegeneratorandsystemcomponentoutages.Theschememonitors
thevoltageonthe34.5kVsystemat13locations.Insomelocations,thelowsidetransformerbreakeris
trippedandinothercasesspecificdistributionlinesaretripped(whereotherlinesaretoocriticaltobe
tripped). Studiesdeterminedtheuseofan85%voltagesetpointfortheUVLSrelaystotripwitha30
secondtimedelayandtolocatetheprotectionatornearthelocationswherethevoltagewouldbebelow
85%theearliest.Thestudiesalsodeterminedthenumberoflocationsrequiredsuchthatthesystemwould
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
beabletofullyrecover.TheUVLSschemesinNewJerseyareenabledmanuallythroughtheSCADA
systemgenerallywhenthearealoadsurpassesapredeterminedlevel.
TVA UVLS [Meyer Kao and Gary Kobet, Analysis of Undervoltage Load Shedding Event at
Philadelphia, Mississippi, Georgia Tech Fault and Disturbance Analysis Conference April 2627, 2004]
7.2.2.
Hierarchical Architecture
ComEd UVLS
TheComEdUVLSschemeswereinstalledtoserveasasafetynettominimizetheriskofsystemvoltage
collapseduringseveredisturbancestothebulkpowersystem. Theschemedetectslowvoltageat12
distributionsubstationsinachosensectionofComEd'sterritoryandtripsdistributionfeedersatthese
substations. Theschemeisautomaticallyarmedanddisarmedbasedonasystemloadof20000MW
(dispatcherscanalsoarmanddisarmtheschemeviaSCADA).Thevoltagesetpointis0.87puat138kV.
Thevoltagemustalsobeabove~0.43pu.If0.43pu<VB<0.87pufor3seconds,thefeedersaretripped.
Inmostcases,foravoltagetriptooccur,voltagemustbedetectedtobewithinrangeontwoseparate
CCVTs.Theamountofloadshedis~800MW(estimated)athighsystemloads.
7.3.
Centralized (Imai)
7.3.1.
Flat Architecture
BC Hydro UVLS
Purpose: To prevent voltage collapse following loss of major transmission or reactive power support
facilities.
System Description: The scheme of two independent subsystems, one at Vancouver Island and another at
Lower Mainland, which can shed load in their respective areas, or jointly for more severe system
problems. The System Control Centre directs local control centers supervising each area to arm or disarm
this scheme as required in accordance with system conditions. Each subsystem monitors three key station
bus voltages and a designated group of units for its VAR reserve, which is the remaining VAR boost
capacity of the group. If the bus voltage drops below a set level or if the VAR reserve drops below a set
level, its sensor will key a continuous signal to either subsystem to initiate load shedding after time delay
until the initiating conditions have reset.
Florida Power & Light FALS
Entergy VSHED [S. Kolluri, Tao He, Design and Operating Experience with Fast
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
onthevergeofvoltagecollapse,VSHEDactivatedandoperatedsuccessfully,protectingtheregionfrom
widespreadvoltagecollapse.
Public Service New Mexico ICLSS
[Jeff Mechenbier, et al, Design Of An
Under
Voltage
Load
Shedding
Scheme, IEEE Power Engineering
Society General Meeting, June 2004]
Purpose: To prevent voltage collapse
following loss of both 345kV lines serving
the Albuquerque area during peak load
periods.
SystemDescription:Thisschemeisdesigned
so as to deal with both of shortterm and
longterm voltage instability, mitigate
equipment overloads, and allow for
acceptablereclosingangles.Loadistripped
ateitherthesubtransmissionorfeederlevel
through PLC and distribution SCADA.
Fig.@describestheblockdiagramforthisscheme.
TEPCO UVLS
Purpose: To prevent voltage collapse following extreme
contingencies like loss of multiple 500kV transmission lines during
abnormal high load periods.
System Description: This scheme is composed of MJ (Monitoring
and Judging) units installed at four 500kV substations and LS
(Load Shedding) units installed at several 275 or 154/66 kV
substations. Each MJ unit is connected via microwave
communication channel and LS units are connected to a MJ unit as
star topology via microwave. Long-term voltage collapse can be
detected on 500kV network, because 275kV or lower voltages are
automatically regulated by tap changing on 500/275 or 154
transformers. Therefore, the SPS requires MS units measuring
500kV busbar voltages. For the purpose of security, the SPS uses 3
out of 4 decision-making logic. MJ units detect slow types of
voltage collapse, ten seconds to minutes order by using unusual
continuous V/t value. Fast voltage collapse can be also detected
by V/t calculation with one second of data window.
MJ
MJ
27kV,154kV
radial network
MJ
MJ
Communication; Voltage
collapse detection result
Sub-Station
LS 275,154/66
LS
Sub-Station
275,154/66
Fig@@TEPCOsUVLS
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
7.3.2.
Hierarchical Architecture
TDST in HydroQuebec Defense Plan against extreme contingencies [D. Lefebvre, et al,
Undervoltage load shedding scheme for the Hydro-Quebec system, IEEE Power
Engineering Society General Meeting, June 2004]
Purpose: To prevent voltage collapse following loss of two or more 735kV lines or any other extreme
disturbances.
SystemDescription:TDSTisredundantscheme,whichislocatedattwodifferentoperatingcentersand
alwaysbearmed.Thecommunicationlinksbetweentheoperatingcentersandthesubstationsarealso
redundant.Todetectvoltageinstability,3out
of5decisionmakinglogicareappliedbased
on the average value of five positive
sequence bus voltages in Montreal area.
Cumulated possible shedding of 1500MW
forfirststagedependsonthevoltagedecline
and duration like less than 0.94pu for
11seconds,0.92pufor9secondsand0.90pu
for 6seconds. Additional load shedding of
1000MWcanbeinitiatedbasedon3second
voltageintegralcalculation.Fig.@showsthe
TDST operation to justify load shedding
based on voltage integral calculation
comparing to the case with only shunt
Fig@TDSToperationafterlossoftwo735kVlines
tripping.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Performance criteria
8.2.
R eac t a n ce [o h m ]
150
Center
Angle
100
13:19
13:15
50
0
-100
-50
50
100
150
200
13:00
250
300
0
0.017453
0.034907
0.05236
0.069813
0.087266
0.10472
Resistance [ohm]
Fig. 1. Apparent impedance of power flow in the Shin-Tama 500 kV line (2L).
The phase comparison relay at the Shin-Fuji substation operated by the following sequence.
A few minutes before the tripping, the contact of the under-voltage relay (1) in Figure 2 was
closed due to the voltage drop. Receiving an alarm triggered by this, substation operators of the
Shin-Tama substation manually blocked the phase comparison relay (2). This toggled the phase
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
comparison relay at the Shin-Fuji substation from the phase comparison mode to the overcurrent
mode, in which the contact of the phase comparison relay (3) was closed as the Shin-Tama 500
kV line (1L) was carrying current flow over the setting value (400 A). In order to prevent the
unwanted tripping, the phase comparison relay at the Shin-Fuji substation had to be blocked (4).
However, the contact of the under-voltage relay (5) was closed before the relay was blocked (4),
and the Shin-Tama 500kV line (1L) was tripped at the Shin-Fuji substation.
Fig. 2. Trip sequence of the phase comparison relay of the Shin-Tama 500 kV line (1L).
In addition to 500 kV transmission lines, four 275 kV transmission lines and four 275/66 kV
transformers tripped due to zone 4 impedance relays. Note that no fault occurred to cause these
relays to operate.
Inordertolimitfaultcurrentsandpreventunexpectedcascadingevents,theTEPCOnetworkoperatingat
275kVandbelowhasaradialstructure.Thus,thesetrippingeventscutdowntheloadattheendofthe
radial network,causingthelossof8,168MW,or21percent ofthetotal load. Thevoltagecollapse
stopped,avoidingfurthercascadingevents.
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
10.8.
11. Conclusion
12. Bibliography
Voltage Instability
- Definition and Classification of Power System Stability, IEEE/CIGRE Joint Task
Force on Stability Terms and Definitions, IEEE Trans. on Power Systems, Vol. 19,
No. 2, May. 2004
- Transmission Voltage Recovery Delayed by Stalled Air Conditioner Compressors,
Bradley R. Williams, Wayne R. Schmus and Douglas C. Dawson, IEEE Transactions
on Power Systems, Vol. 7, No.3, August 1992
- C.W.Taylor,PowerSystemVoltageStability.NewYork:McGrawHill,1994
- J.A.DiazdeLeonIIandC.W.Taylor,UnderstandingandSolvingShortTerm
VoltageStabilityProblems,ProceedingofIEEE/PES2002SummerMeeting
- Khoi Vu, Miroslav Begovic, Damir Novosel and Murari Saha, Use of Local
Measurements to Estimate Voltage Stability Margin, IEEE Transactions on Power
Systems, Vol.14, No3, August 1999
- Verbic G and Gubina, Fast algorithm for voltage collapse protection based on local
phasors, PES Summer Meeting, 2002 IEEE, Vol.3, 1650-1655
- T.Van Cutsem, A Method to compute Reactive Power Margins with respect to
Voltage Collapse, IEEE Transactions on Power Systems, Vol.6, No.1, February
1991
- Miroslav M. Begovic and Arun G. Phadke, Control of Voltage Stability Using
Sensitivity Analysis, Transactions on Power Systems, Vol.7, No.1, February 1992
- T. Van Cutsem, Y. Jacquemart, J.-N. Marquet and P. Pruvot, A comprehensive
analysis of mid-term voltage stability, IEEE Transactions on Power Systems,
Vol.10, No.3, August 1995
- T. Van Cutsem and C.D.Vournas, Voltage stability analysis in transient and midterm time scales, IEEE Transactions on Power Systems, Vol.11, No.1, February
1996
- T. Van Cutsem and R. Mailhot, Validation of a fast voltage stability analysis method
on the Hydro-Quebec system, IEEE Transactions on Power Systems, Vol. 12, No.1,
February 1997
- D.E.Julian, R.P.Schulz, K.T.Vu, W.H.Quaintance, N.B.Bhatt and D.Novosel,
Quantifying Proximity To Voltage Collapse Using The Voltage Instability
Predictor(VIP)
Wide Area Control, Secondary Voltage Control
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
IEEEPowerEngineeringSocietyPowerSystemRelayingCommitteeSystemProtectionSubcommittee
WorkingGroupC13"UndervoltageLoadShedding
Stephen Lee, Recent EPRI R&D Threads related to Grid Operation and Planning,
available on http://phasors.pnl.gov/Meetings/2005%20April/presentations/Lee
%20EIPP_EPRI_4192005.pdf
Richard J.Kafka, Manually Initiated Fast Load Control
Daniel Lefebvre, Cedric Moors and Thierry Van Cutsem, Design of an undervoltage
load shedding scheme for Hydro-Quebec system
B.Isaias Lima Lopes and A.C.Zambroni de Souza, An Approach for Under Voltage
Load Shedding, 2003 IEEE Bologna PowerTech Conference, June 23-26, Bologna,
Italy
C.Moors, D.Lefebvre and T.Van Cutsem, Design of Load Shedding Schemes
against Voltage Instability
Charles J.Mozina, Protection Of Power Plant Transformers Using Digital
Technology
I.L. van der Merwe, J.Cloete and N.Fischer, Implementation of an Unconventional
Voltage Slide Scheme
Meyer Kao and Gary Kobet, Analysis of Undervoltage Load Shedding Event at
Philadelphia, Mississippi, Georgia Tech Fault and Disturbance Analysis Conference
April 26-27, 2004
System Disturbances
-
Technical Summary on The Athens and Southern Greece Blackout of July 12, 2004,
Costas Vournas
Report on The Events of September 28th ,2003 Culminating in The Separation of The
Italian Power System From The Other UCTE Networks
Power Failure in Eastern Denmark and Southern Sweden on 23.09.03- Final Report
on the Course of Events, 04.11.03
U.S.CanadaPowerSystemOutageTaskForce,FinalReportontheAugust14,
2003BlackoutintheUnitedStatesandCanada:CausesandRecommendations,
April2004
UnderFrequencyLoadShedding
- B.Delfino,S.Massucco,A.Morini,P.ScaleraandF.Silvestro,Implementationand
ComparisonofDifferentUnderFrequencyLoadSheddingSchemes
- S.Jovanovic,B.FoxandJ.G.Thompson,OnLineLoadReliefControl
- CharlesConcordia,LesterH.FinkandGeorgePoullikkas,LoadSheddingonan
Isolated System, IEEE Transactions on Power Systems, Vol.10, No.3, August
1995
- D.Prasetijo, W.R.Lachs and D.Sutanto, A New Load Shedding Scheme For
Limiting Underfrequency, IEEE Transactions on Power Systems, Vol.9, No.3,
August1994
- P.M.Anderson and M.Mirheydar, An Adaptive Method for Setting
Underfrequency LoadShedding Relays, IEEETransactions onPower Systems,
Vol.7,No.2,May1992