ABSTRACT
Based on field observations refrigeration air conditioning (AC) machine
with refrigran R22 is still very widely used, where the refrigerant has properties
that are not friendly to the environment. Refrigerant R407C as an alternative to
replacement (retrofit) R22 that has been done in the WCP (Water Cooled
Packaged) in Setiabudi Atrium Building. This is one reason to do some research
for obtaining performance generated from each refrigran that affect the energy
consumption of the refrigeration machine but it is also an attempt to preserve the
environment. This machine performance testing, done by collecting data every
hour operation of the machine within 10 hours, when using the R22 and shortly
after changed to R407C. And the results obtained from this study is that even
more environmentally friendly electricity comparison between energy
consumption by refrigeration effect produced by WCP (Water Cooled Packaged)
is still better to use the R22 is based on the data the average COP is R22 = 7.34
whereas R407C = 7,14.
Keywords: Retrofit, WCP (Water Cooled Packaged), R22, R407C, COP