You are on page 1of 5

ABB

Technical specification
Customer

EPHZHB

Project Name :

Project1

Date

16.12.2014.

Your Ref.
Our Ref.
Revision
Revision Date

:
:
:
:

Issuer
Office

:
:

Fahrudin Mehmedovi
Office Tuzla

Telephone
Fax
E-mail

:
:
:

+387 35 246 020 /


+387 35 255 098
+387 61 148 440

PP 14 8998
16.12.2014.

Page 1 of 5

ABB
Our. Ref.: PP 14 8998 Rev.

9
Date: 16.12.2014.

Item no. 1 Switchgear 1


SafePlus compact switchgear
Total number of modules 3 pcs
Switchgears consisting of two or more sections to be connected via external busbars, are
delivered as separate sections from factory for assembly on site.
STANDARDS AND MECHANICAL DATA
Metal Enclosed switchgear:
General Purpose switches:
Disconnectors and Earthing switches:
Switch Fuse Combination:
Circuit Breakers:
Common clauses:
Pressure of SF6 gas:
Cable bushings:
Temperature class:
Degree of protection:
- SF6 tank:
- Fusecanisters:
- Front cover:
- Cable cover:
Busbars:
Earth bar (external):
Thickness of Stainless Steel Tank:
Colours:
- Front cover:
- Side and cable cover:

IEC 62271-200
IEC 60265-1
IEC 62271-102
IEC 62271-105
IEC 62271-100
IEC 60694
1.4 bar at 20 C
DIN 47636
-25 C - +40 C indoor
IP 67
IP 67
IP 2X
IP 3X
240 mm2 Cu
100 mm2 Cu - Bolt dimension: M10
3.0 mm
RAL 7035
RAL 7035

ELECTRICAL DATA 24 kV
Nominal voltage: 20 kV
Rated frequency: 50 Hz
Rated current for busbars: 630 A
Rated current for cable switch disconnector : 630 A
Short time withstand current:
- cable switch disconnector with interface B (400-plug) bushing: 16 kArms 1 sec.
- cable switch disconnector with interface C (400-bolt) bushing: 21 kArms 3 sec.
- cable switch disconnector with interface D (600-bolt) bushing: 21 kArms 3 sec.
- vacuum circuit breaker with interface A (200-plug) bushing: 16 kArms 0,5 sec.
- vacuum circuit breaker with interface B (400-plug) bushing: 16 KArms 1 sec.
- vacuum circuit breaker with interface C (400-bolt) bushing: 16 kArms 3 sec.
- vacuum circuit breaker with interface D (600-bolt) bushing: 16 kArms 3 sec.
Rated current for transformer T-off : 200 / 630 A
Short time withstand current (3 sec) CB-module vacuum circuit breaker: 20kArms
Impulse withstand voltage :
To earth and between phases: 125 kV
Insulation level:

Page 2 of 5

ABB
Our. Ref.: PP 14 8998 Rev.

9
Date: 16.12.2014.

- Power frequency 1 min: 50 kV

Page 3 of 5

ABB
Our. Ref.: PP 14 8998 Rev.

9
Date: 16.12.2014.

A01 C
SafePlus C is a cable switch module with a three position load break switch and earthing switch,
busbars, interlocking and earthbar.
1
1
1
1
1
1
1
1

SafePlus type C: Cable switch 24kV, 630A


Manometer
Snap action mech. for manual operation
Cable cover standard
Cable bushings interface C (400 bolted), 630 A, standard
Aux. switch for load break switch position 2NO + 2NC
Capacitive voltage indication fixed type VPIS 10-24 kV
Cable support bars, standard for 1-way unit

A02 V
SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position
isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (Amech.).
1
1
1
1
1
1
1
1
1
1
1
1
1
3

SafePlus type V: Vacuum circuit breaker 24kV, 200A


Bushings outside cone interface C for connection of external busbar
Stored energy mech. for man.operation,with trip coil open
Control voltage, trip coil 230 V AC
Without padlocking device push buttons
Cable cover standard
Protection relay type ABB REJ 603
Cable bushings interface C (400 bolted), 200A
Aux. switch for vacuum circuit breaker position 2NO + 2NC
Aux. switch for disconnected position 2NO + 2NC
Aux. switch for earth switch position 2NO + 2NC
Capacitive voltage indication fixed type VPIS 10-24 kV
Cable support bars, standard for 1-way unit
Ring core current transformer type CT2 16-56A (50mm) 1YMA583791R0001

A03 CB
SafePlus CB is a vacuum circuit breaker module with vacuum circuit breaker, stored energy spring
mechanism for O - 0,3 s - CO - 15 s - CO operating sequence, three-position motor operated
isolator/earthing switch, busbars, earthbar and switchbay protection and control unit.
1

SafePlus type CB: Vacuum circuit breaker 24kV, 630A

Page 4 of 5

ABB
Our. Ref.: PP 14 8998 Rev.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

9
Date: 16.12.2014.

Bushings outside cone interface C for connection of external busbar


Manometer
Stored energy mech. for motor operation
Cable bushings interface C (400 bolted) with sensors
Manual operation disconnector and earthing
Control voltage, motor operation 230 V AC
Remote Control On/Off selection switch
Control voltage, relay trip coil 230 V AC (relay control voltage converted to 48VDC)
Cable cover standard
Protection relay type ABB REF 615
Aux. switch for vacuum circuit breaker position 2NO + 2NC
Aux. switch for disconnected position 2NO + 2NC
Aux. switch for earth switch position 2NO + 2NC
Capacitive voltage indication test sockets HR module 12-24 kV
Cable support bars, standard for 1-way unit

Additional equipment delivered separately or mounted in respective panel.


2
3
2
1
1
2

End adapter (3 pcs) NHSN620024P0001


Busbar L = 226mm Standard module / CB-module (NHSN620024P0226)
Distance plate std / metering or CB - Metering (NHP 304633P0001)
Fixing material (1VDC000031R0004)
Low voltage compartment 2-way unit
Operating handle

Page 5 of 5