SITE INSPECTION AND TEST RECORD

Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)
ALGIHAZ CO. LTD
Site:

24/02/2013

SEC-WOA
Panel Ref:

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

1 of 4

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

50/51N-LV

30/31

FINAL SETTING TEST:


1. RELAY DETAILS:
Type No :

P122

Designation

50/51N

Model No :

MiCOM P122B00Z112CD0

Nominal Current : In

1/5 A, 50/60Hz

Serial Number

36041859

Aux. Volts

24-250 V DC, 48-240 V AC

Make

ALSTOM

: Vx

2. VISUAL INSPECTION:
Sl. No

Description

Inspect For Physical Damage / Defects

Verify Connections As Per Approved Drawing

Check Tightness Of All Connections

Check relay version and switching elements on printed circuit board

Checked

3. GENERAL CHECK:
Description

Sl. No
1

Auxiliary voltage value on terminals 33 ( + ) and 34 ( - )

Watchdog contact when relay OFF

Watchdog contact when relay ON

Check if the frequency is set on required value

Checked

Terminals 35- 36

Close

Terminals 37- 36

Open

Terminals 35- 36

Open

Terminals 37- 36

Close

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Over Current & Earth Fault Relay


(MICOM P122)

Date:

24/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

2 of 4
project no.:

13.8/11kV Tabuk Air Base S/S

50/51N-LV

30/31

4. BINARY INPUT OPERATION CHECK:


Terminal No.

Input No.

Active

Function Assigned

24

High

Future use

26

28

High

Future use

17

19

High

Not Used

(+)

(-)

OPTO 1

22

OPTO 2
OPTO 3

Result

5. BINARY OUTPUT CONTACT CHECK:


Commission Test Test Mode Contacts Blocked. Check Test Pattern Each BO.
Output No.

Terminal No.

Type

Function Assigned

42

NC

Spare

62

NO

O/C & E/F Trip

10 8

NC

Spare

12 8

NO

Spare

RL 3

14 16

NO

Spare

RL 4

18 20

NO

Spare

RL 5

13

NO

Spare

RL 6

57

NO

Spare

RL 1
RL 2

6.1.

6.2.

Result

FIXED LED INDICATIONS TEST:


LED No.

LED Label

Color

LED HI

Trip

Red

LED H2

Alarm

Yellow

LED H3

Warning

Yellow

LED H4

Healthy

Green

LED INDICATIONS TEST: (RIGHT SIDE LED)

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

Result

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)

24/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

3 of 4

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

50/51N-LV

30/31

LED No.

LED Label

Color

LED H5

O/C-Start

Red

LED H6

O/C-Trip

Red

LED H7

E/F-Start

Red

LED H8

E/F-Trip

Red

7.

Result

MEASUREMENT VALUE TEST:


CT Ratio: 1250/1

Inj. Current
(A)

Calculated
Current
( A)

0.25

312.5

0.50

625

1.00

1250

R
Prim.

Deviation: Typical 0.5% at In ,

8.

Relay Reading ( A )
Y
Prim.
%Error

%Error

B
Prim.

%Error

Manual : Schneider Technical Guide P12x/EN AD/Eb6

STAGE 1 (I>) OVER CURRENT :


8.1 PICK UP TEST:
Set Current
( A)

Measured Current ( A )
R
Pick up

Y
Drop off

Pick up

B
Drop off

Pick up

0.95
Deviation: Pickup: DT =Is 2%, IDMT =1.1Is2%
Drop off: DT =0.95Is 2%, IDMT =1.05Is2%
8.2 TIMING TEST:
Curve : VI

K : 0.3

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

Drop off

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)

24/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

50/51N-LV

Set Current
( A)

Injected Current
(A)

Calculated Time
(S)

0.95

2 Times

4.05

0.95

4 Times

1.35

0.95

8 Times

0.579

30/31
Measured Time ( S )
Y

Deviation : DT = 2%<50ms, IDMT =5%<50ms


9.
9.1

STAGE 1 (Ie>) EARTH FAULT :


PICK UP TEST:
Measured Current ( A )

Set Current
( A)

IN
Pick up

Drop off

0.12
Deviation: Pickup: DT =Ies 2%, IDMT =1.1Ies2%
Drop off: DT =0.95Ies 2%, IDMT =1.05Ies2%
9.2

4 of 4

TIMING TEST:

Set Current
( A)

Set Time
(S)

Injected Current
(A)

0.12

1.4

0.24

Measured Time ( S )
IN

Deviation : DT = 2%<50ms, IDMT =5%<50ms

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :