You are on page 1of 1

NOTES:

GROUT

PIPE
GASKET

PIPE
SLEEVE
150

50mm x 50mm x 6mm


THK.
ANGLE BAR GALV.

2GA-BP-6101

BITUMINOUS
COAT

5mm THK.
RUBBER
GASKET

1100x900 RC
HEAVY DUTY TYPE
MANHOLE COVER
(SEE NOTE 2)

800

1.

REFER TO DWG. NO. PHPY-26811-26812 FOR GENERAL NOTES


AND LEGENDS.

2.

ALL MANHOLES OUTSIDE THE BUILDING SHALL BE HEAVY DUTY,


AIR & WATER TIGHT RC. MANHOLE COVERS AND FRAMES TO BE
BS EN124 CLASS C250 OR APPROVED EQUAL.

3.

ALL TRENCH DRAIN GRATINGS & ANGLE BAR SEATING SHALL BE


MADE OF HOT DIPPED GALVANIZED STEEL 300mm WIDTH
WHEREAS ITS LENGTH MAY VARY ACCORDINGLY UNLESS
OTHERWISE SPECIFIED.

4.

THE CONTRACTOR TO FIT ALL TRENCH GRATING AS PER SITE


CONDITION ARCHITECTURAL/CIVIL REQUIREMENTS. CHECK
ACTUAL AND FINAL GRADING PRIOR TO SHOP DRAWING
PREPARATION FOR CLIENT ENGINEER APPROVAL PRIOR T TO
SITE EXECUTION.

DIRECTION OF FLOW
1100x900 RC
HEAVY DUTY TYPE
MANHOLE COVER
(SEE NOTE 2)

ROD WELDED
TO ANGLE (2
EACH SIDE)

150

STANDARD PIPE GASKET


(TYPICAL TO ALL WALL
PENETRATIONS)

FOR INCLINATION
REQUIREMENT
SEE NOTE 4
50

SEE NOTE 3

300

ENSURE TOP OF TRENCH GRATING


FLUSHED TO TOP OF GRADING

50

F.F.L.
@ LAST MAN HOLE

1000

150

HOT DIPPED GALVANIZED


STEEL GRATING 30mm

3
2GA-BP-6101

250
(MINIMUM)

DIRECTION OF FLOW

CONCRETE INVERT SHAPE.


ALL PVC PIPE TO BE
REMOVED FROM INVERT.

150

TRENCH DRAIN
LENGTH X 300W X DEPTH
BITUMINOUS COAT
(COAL TAR)

150mm RC WALL. REFER TO


STRUCTURAL DWGS. FOR DETAIL
"U-SHAPED" INVERT MIN. 34 OF
LARGEST PIPE I.D.

BITUMINOUS COAT

150mm RC WALL. REFER TO


STRUCTURAL DWGS. FOR DETAIL
(SEE NOTE2)

SLLOPE 1:12
150

FLOOR GULLY

SLOPE 1:12 SLOPE 1:12


DIRECTION OF
FLOW
BITUMINOUS COAT 500 MIN. FROM
BOTTOM OF MANHOLE

STANDARD PIPE GASKET


ON ALL WALL PENETRATIONS

WASTE/PROCESS
DRAINAGE PIPE

NOTE:
FOR MANHOLE UP TO
1500mm DEEP

DIRECTION OF FLOW

TYPICAL TRENCH DRAIN DETAIL

2GA-BP-6101 SCALE :

PLAN VIEW - MANHOLE

2GA-BP-6101

NTS

SCALE :

SECTION VIEW - MANHOLE 1

2GA-BP-6101

NTS

150

SCALE :

NTS

1400

150

1000

1100x900mm RC HEAVY DUTY


MANHOLE COVER (SEE NOTE 2)

SEE SPOT DETAIL AT


SECTION VIEW MAN HOLE

150

100

SS 304L
STEEL
SLOPE

SLOPE

SEE SPOT DETAIL AT


PLAN VIEW MANHOLE
CL

DIRECTION
OF FLOW

SEE SPOT DETAIL AT


PLAN VIEW MANHOLE
CL

DIRECTION
OF FLOW

WYE FITTING

EMBEDDED
IN WALL

100

WYE FITTING
MANHOLE WALL

150

400

MANHOLE WALL
SEE STRUCTURAL DRAWINGS
FOR DETAILS

500MIN

STEEL LADDER
RUNG
NOTE:
FOR MANHOLE DEEPER
THAN 1500mm
BITUMINOUS COAT

TYP. LADDER RUNG DETAIL

2GA-BP-6101 SCALE :

NTS

BITUMINOUS COAT
BITUMINOUS COAT

CL

RC THRUST BLOCK

DIRECTION
OF FLOW

SCREED GROUT TO
MATCH INVERT LEVEL

CL

RC THRUST BLOCK

DIRECTION
OF FLOW

SCREED GROUT TO
MATCH INVERT LEVEL

SEE SPOT DETAIL AT


PLAN VIEW MAN HOLE

150

SLOPE

VENT
PIPE
WITH
ALUMINUM
CLADDING
VENT
TERMINATION
WITH HOOD
AND INSECT
SCREEN
WIRE MESH

70

DIRECTION
OF FLOW

150

STANDARD BEDDING
MATERIAL

CHB WALL

SLOPE

DIRECTION
OF FLOW

STANDARD BEDDING
MATERIAL

VENT
PIPE

200

1000

W/ DROP MANHOLE
REQUIREMENT

550

7
4a

SECTION VIEW-DROP MANHOLE (FOR HDPE / PVC PIPE)

2GA-BP-6101 SCALE :

4b

SECTION VIEW-DROP MANHOLE (FOR STAINLESS PIPE)

2GA-BP-6101 SCALE :

NTS

SECTION VIEW - MANHOLE 2

2GA-BP-6101 SCALE :

NTS

VENT
TERMINATION
WITHINSECT
SCREEN
WIRE MESH

EXPOSED

VENT PIPE TERMINATION DETAIL

2GA-BP-6101 SCALE :

NTS

NTS

FOR TENDER
NOT FOR CONSTRUCTION
NO.
0

DESCRIPTION
ISSUE FOR TENDER

BY
DA

CHK
GF

APPD DATE
SF 09.09.16

PROJECT MANAGERS, ARCHITECTURE AND ENGINEERING CONSULTANTS:

CLIENT:

Philippines Inc.
Tanauan Factory

2ND ST. FPIP


BARANGAY ULANGO
TANAUAN CITY, BATANGAS
PHILIPPINES

Beca Philippines Ltd


27TH FLOOR, BPI BUENDIA CENTRE
372 SEN. GIL PUYAT AVENUE
MAKATI CITY
PHILIPPINES

ARCHITECTS AND ENGINEERS:

PROJECT:

PacificTech Solutions Inc.


10/F BTTC CENTRE
288 ORTIGAS AVENUE, GREENHILLS
SAN JUAN CITY 1502, METRO MANILA
PHILIPPINES

DRAWING NAME:

TANAUAN TOWER 2
FIRST PHILIPPINES INDUSTRIAL PARK
PHILIPPINES

2GA - EGRON 2 BUILDING


SEWER, WASTE AND PROCESS DRAINAGE
TYPICAL DETAIL 1

NTS

SCALE
DRAWN BY

DA

DESIGN BY

GF

DATE

09.09.16

CHECKED BY

SF

REVISION
DRAWING NO.

Rev.

4812140-DR-2GA-BP-6101

IF IN DOUBT ASK.

You might also like