You are on page 1of 1

s

_____________________________________________________________________________________________________________
Siemens Transzformtor Kft.

Item ID: 2000kVA 20/0.4kV Dyn5

Technical description
Type designation
Design:
Transformer acc. to
Environmental class
Climatic class
Fire behaviour class
Installation
Altitude installation
Ambient temperature
Temp. rise windings HV / LV
Thermal class HV / LV
Frequency
Type of duty
Type of cooling
Protection

4GB6364-3DA
GEAFOL Three-phase cast-resin transformer
IEC 60076-11:2004 / VDE 0532
E2
C2
F1
Indoor
1000 m
40 C
100 K / 100 K
F /F
50 Hz
continuous
AN
IP 00

Rated power
Vector group
High voltage
tappings
tappings at
insulation level
Low voltage (U2)
insulation level
No load losses
Load losses (PK 75)
Load losses (PK 120)
Total losses tolerance
Impedance voltage
Sound power level LW(A)
Sound pressure level (LP(A),1m)
tolerance
Winding material LV / HV
Terminals:
High voltage
Low voltage
Dimensions, approximately
Length x width x height
Distance between rollers
Total mass
Painting scheme
Color RAL , thickness
Accessories:
Transport rollers
Thermal protection

2000 kVA
Dyn5
20000 V
2,5; 5%
Back
LI 95 AC 50
400 V
LI - AC 3
3500 W +15 %
13800 W +15 %
15700 W +15 %
+10 %
6 % 10 %
83 dB(A)
67 dB(A)
+3 dB(A)
Alu / Alu
Top
Top
2000 mm x 1280 mm x 2150 mm
1070 mm
4550 kg
RAL 5009 , 80
4 pcs
PTC thermistors in coils for warning and tripping

Fisa tehnica GEAFOL 2000kVA-20-0,4, p. normale 1 / 1

26.11.2015